About this file

This document is a combined synopsis/solicitation for a commercial service contract for an Arc Flash Analysis at the VA Loma Linda Healthcare System (VALLHCS) located in Loma Linda, CA. The VA is seeking to purchase an Arc Flash Analysis to be in compliance with required electrical inspections. The contract is set-aside for 100% Service-Disabled Veteran-Owned Small Businesses (SDVOSB), with a North American Industrial Classification System (NAICS) code of 238210. The key requirements include conducting an Arc Flash Analysis, updating one-line diagrams, and placing Arc Flash warning labels on all evaluated equipment. Interested offerors must provide quotations by August 23, 2024 at 10:00 AM PDT. The contract period of performance is September 1, 2024 through August 31, 2025. Pricing is requested for the Arc Flash Study and Over and Above services as needed. Award will be based on a comparative evaluation of price and past performance, with price being the more important factor.

View the file

Other files for this federal contract opportunity

Other files attached to H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025), newest first.
File Type Posted
Tbl 3_3 Equip Eval.pdf PDF
lf_calc format.pdf PDF
input_data format.pdf PDF
EYE Clinic One Line Drawings.docx DOCX document
E-112.pdf PDF
E-110.pdf PDF
E-108.pdf PDF
CANCER CENTER SIGNAL LINE DRAWINGS 2017.png PNG image
Arc Flash Study 2016 Schneider Full Facility.pdf PDF
20110460 - Sheet - E-611 - SINGLE LINE DIAGRAM OP Pharmacy.pdf PDF
116801E5.1.5.pdf PDF
022712 SCC and OCPD Coordination Study - VA Loma Linda.pdf PDF
Tbl 4_1 MV Prot Dev Settingsa.pdf PDF
Tbl 3-1_2 Prot Dev Eval.pdf PDF
sc_calc format.pdf PDF
MV Coordination Descrip Tbl.pdf PDF
Loma Linda MV TCCs.pdf PDF
E-109.pdf PDF
E-103.pdf PDF
CLC ReHab SIGNAL LINE DRAWINGS.png PNG image
CLC PC SIGNAL LINE DRAWINGS.png PNG image
VALL Electrical Single Line Diagrams.pdf PDF
Short Circuit Study - Op Pharmacy.pdf PDF
Loma Linda-60pc.pdf PDF
E601 BEHAVIORAL HEALTH BUILDING.pdf PDF
E-115.pdf PDF
E-114.pdf PDF
E-113.pdf PDF
E-101.pdf PDF
Cover.pdf PDF
116801E5.1.12.pdf PDF
116801E5.1.11.pdf PDF
116801E5.1.10.pdf PDF
116801E5.1.8.pdf PDF
116801E5.1.2.pdf PDF
116801E5.1.1.pdf PDF
Tbl 6-1_2_Arc_Flash.pdf PDF
E-111.pdf PDF
E-107.pdf PDF
E-106.pdf PDF
E-105.pdf PDF
E-102.pdf PDF
E1.1 AUDIOLOGY.pdf PDF
E-001.pdf PDF
Arc Flash Study CLC Reb.pdf PDF
Arc Flash Study CLC Ph 2.pdf PDF
116801E5.1.9.pdf PDF
116801E5.1.7.pdf PDF
116801E5.1.6.pdf PDF
36C26224Q1724.docx DOCX document
Show all 50

H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E-104

ONE-LINE DIAGRAM

SERVICE BAY 1-3 MCC-MAB

t h r e e q u a r t e r s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t

F o n e h a l f i n c h o n e f o o t

E

D

2 3 4 5 o n e i n c h o n e f o o t

C o n e h a l f i n c h o n e f o o t

B t h r e e i n c h e s o n e f o o t

A

1 2 3 4 5

Project Location

Building Number

6 7 8

Drawing Title

Scale

Revision

No. Date

VA MEDICAL CENTER

LOMA LINDA, CA

U.S. GOVERNMENT PRINTING OFFICE: 1983-400-285

DWG. Of

Checked

SAB

Drawn

DRAWING NO.

F E

D

6 7 8

C B

A

NO SCALE

Fax: 757-471-4205

Ph: 757-471-0537

Norfolk, VA 23510

101 West Main Street, Suite 7000

World Trade Center

ELT

LLCMiller-Remick

FAX: (856)429-5002

PHONE: (856)429-4000

CHERRY HILL, NEW JERSEY 08034

1010 KINGS HIGHWAY SOUTH

M.E.P. & Structural Engineering

Small Business

A Service Disabled Veteran Owned

A S e r v ic e D i s a b le d V eteran Ow ne d S m a l l B u s in e ss

SDVOSB

EVC

434.947.1901 | wileywilson.com | 100% Employee-Owned

127 Nationwide Drive | Lynchburg, VA 24502

NO SCALE

SERVICE BAY 1-3 - MCC-MAB ONE-LINE DIAGRAM

Check for FU or CB

SEE "SWBD MDBA -- SERVICE BAY 1-3 US-1B ONE-LINE DIAGRAM" FOR CONTINUATION

MCC: 1_MCC-MAB

480V, 300A

CB: 1_E3 Ex Fan Canopy Fl 1

CUTLER-HAMMER (MCP)

7 A, 7 A Plug

CB: 1_E2 Emer Dpt Fl 1 Ex Fan

CUTLER-HAMMER (MCP)

7 A, 7 A Plug

CB: 1_E1 CageWasher Ex Fan

CUTLER-HAMMER (MCP)

3 A, 3 A Plug

CB: 1_E8 Gen Ex Fl 1 Ex Fan

CUTLER-HAMMER (MCP)

30 A, 30 A Plug

CB: 1_E5 Gen Ex Fl 1-3 Ex Fan

CUTLER-HAMMER (MCP)

15 A, 15 A Plug

CB: 1_E6 MICU Fl 4 Ex Fan

CUTLER-HAMMER (MCP)

15 A, 15 A Plug

CB: 1_E7 CCU Fl 4 Ex Fan

CUTLER-HAMMER (MCP)

15 A, 15 A Plug

CB: 1_E10A Inf Ani Fl 1 Ex Fan

CUTLER-HAMMER (MCP)

7 A, 7 A Plug

MCP: 1_CB: 1_E9 Fl 1 Fume Hood

CUTLER-HAMMER (MCP)

7 A, 7 A Plug

CB: 1_E10 Fl 1 Radio Iso

CUTLER-HAMMER (MCP)

7 A, 7 A Plug

CB: 1_AH-38 Elev Mach Rm

CUTLER-HAMMER (MCP)

7 A, 7 A Plug

CB: 1_AF T-A5 Pnl RLA

WESTINGHOUSE (HFB)

30 A

MCP: 1_CB: 1_EF-68

CUTLER-HAMMER (HMCP)

15 A, 15 A Plug

MCP: 1_CB: 1_EF-7A

CUTLER-HAMMER (MCP)

30 A, 30 A Plug

MCP: 1_CB: 1_E-4

CUTLER-HAMMER (HMCP)

50 A, 50 A Plug

MCP: 1_CB: 1_E-10B

CUTLER-HAMMER (HMCP)

7 A, 7 A Plug

F: 1_MCC MAB

(1) #500 THWN; 265 ft

F: 1_E3 Ex Fan Canopy Fl 1

(1) #12 THWN; 60 ft

F: 1_E2 Emer Dpt Fl 1 Ex Fan

(1) #12 THWN; 80 ft

F: 1_E1 CageWasher Ex Fan

(1) #12 THWN; 65 ft

F: 1_E5 Gen Ex Fl 1-3 Ex Fan

(1) #12 THWN; 65 ft

F: 1_E7 CCU Fl 4 Ex Fan

(1) #12 THWN; 50 ft

F: 1_E10A Inf Ani Fl 1 Ex Fan

(1) #12 THWN; 35 ft

F: 1_E10 Fl 1 Radio Iso

(1) #10 THWN; 50 ft

DISC: 1_E-10

480V, F: 1_AH-38 Elev Mach Rm

(1) #12 THWN; 1 ft

F: 1_AF T-A5 Pnl RLA

(1) #10 THWN; 5 ft

F: 1_CB: 1_EF-68 Disc

(1) #12 THWN; 60 ft

F: 1_CB: 1_EF-7A

(1) #12 THWN; 65 ft

F: 1_CB: 1_E-4

(1) #8 THWN; 60 ft

FU: 1_EX-10

FERRAZ SHAWMUT (TRS)

20 A

PNL: 1_RLA

208V, 100A

10k SCAR

F: 1_Pnl RLA

(1) #4 THWN; 5 ft

DISC: 1_E-8

480V, DISC: 1_E-9

480V, FU: 1_E-8

FERRAZ SHAWMUT (TRS)

30 A

F: 1_E8 Gen Ex Fl 1 Ex Fan

(1) #10 THWN; 60 ft

FU: 1_E-9

FERRAZ SHAWMUT (TRS)

20 A

F: 1_E9 Fl 1 Fume Hood

(1) #10 THWN; 50 ft

MTR: 1_EF-9

1 @ 2 hp

MTR: 1_EF-10A

1 @ 3 hp

MTR: 1_EF-8

1 @ 7.5 hp

MTR: 1_EXH-10

1 @ 2 hp

VFD: 1_EF-7A

F: 1_E-6

(1) #12 THWN; 85 ft

MTR: 1_E-6

1 @ 7.5 hp

MTR: 1_EF-10B

1 @ 3 hp

MTR: 1_EF-7B

1 @ 0.8 hp

MTR: 1_E-5

1 @ 7.5 hp

DISC: 1_EF-68

480V, F: 1_EF-68

(1) #12 THWN; 5 ft

MTR: EF-68

1 @ 7.5 hp

MTR: 1_E-4

1 @ 20 hp

MTR: 1_EF-7A

1 @ 1.5 hp

DISC: 1_E-1

480V, F: 1_E-1

(1) #12 THWN; 5 ft

MTR: 1_E-1

1 @ 1 hp

F: 1_E-3

(1) #12 THWN; 5 ft

MTR: 1_E-3

1 @ 1.5 hp

DISC: 1_E-3

480V, F: 1_E-8

(1) #10 THWN; 5 ft

F: 1_E-9

(1) #10 THWN; 5 ft

F: 1_E-10

(1) #10 THWN; 5 ft

MTR: 1_E-7

1 @ 7.5 hp S

P

XF: 1_T-A5

15kVA; 2.80%Z

Pri: 480V

Sec: 208V

DISC: 1_E-4

480V, F: 1_CB: 1_E-10B

(1) #10 THWN; 25 ft

FU: 1_E-3

FERRAZ SHAWMUT (TRS)

20 A

FU: 1_E-1

FERRAZ SHAWMUT (TRS)

20 A

FU: 1_E-4

FERRAZ SHAWMUT (TRS)

50 A

F: 1_E-4

(1) #8 THWN; 5 ft

F: 1_EF-7B

(1) #12 THWN; 5 ft

FU: 1_EF-7B

LITTELFUSE (FLSRID)

3 A

DISC: 1_EF-7B

480V, F: 1_Disc EF-7B

(1) #12 THWN; 95 ft

MCP: 1_CB: 1_Unk

CUTLER-HAMMER (MCP)

15 A, 15 A Plug

E-104 - SB 1-3.dgn 3/30/2018 8:36:58 AM

File details come from the government source that posted it. Updated .