E-104.pdf
PDF 315 KB Posted
- Attached to
- H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) Federal contract opportunity
- Solicitation number
- 36C26224Q1724
About this file
This document is a combined synopsis/solicitation for a commercial service contract for an Arc Flash Analysis at the VA Loma Linda Healthcare System (VALLHCS) located in Loma Linda, CA. The VA is seeking to purchase an Arc Flash Analysis to be in compliance with required electrical inspections. The contract is set-aside for 100% Service-Disabled Veteran-Owned Small Businesses (SDVOSB), with a North American Industrial Classification System (NAICS) code of 238210. The key requirements include conducting an Arc Flash Analysis, updating one-line diagrams, and placing Arc Flash warning labels on all evaluated equipment. Interested offerors must provide quotations by August 23, 2024 at 10:00 AM PDT. The contract period of performance is September 1, 2024 through August 31, 2025. Pricing is requested for the Arc Flash Study and Over and Above services as needed. Award will be based on a comparative evaluation of price and past performance, with price being the more important factor.
View the file
Other files for this federal contract opportunity
Show all 50
H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E-104
ONE-LINE DIAGRAM
SERVICE BAY 1-3 MCC-MAB
t h r e e q u a r t e r s i n c h o n e f o o t o n e q u a r t e r i n c h o n e f o o t o n e e i g h t h i n c h o n e f o o t t h r e e e i g h t h s i n c h o n e f o o t
F o n e h a l f i n c h o n e f o o t
E
D
2 3 4 5 o n e i n c h o n e f o o t
C o n e h a l f i n c h o n e f o o t
B t h r e e i n c h e s o n e f o o t
A
1 2 3 4 5
Project Location
Building Number
6 7 8
Drawing Title
Scale
Revision
No. Date
VA MEDICAL CENTER
LOMA LINDA, CA
U.S. GOVERNMENT PRINTING OFFICE: 1983-400-285
DWG. Of
Checked
SAB
Drawn
DRAWING NO.
F E
D
6 7 8
C B
A
NO SCALE
Fax: 757-471-4205
Ph: 757-471-0537
Norfolk, VA 23510
101 West Main Street, Suite 7000
World Trade Center
ELT
LLCMiller-Remick
FAX: (856)429-5002
PHONE: (856)429-4000
CHERRY HILL, NEW JERSEY 08034
1010 KINGS HIGHWAY SOUTH
M.E.P. & Structural Engineering
Small Business
A Service Disabled Veteran Owned
A S e r v ic e D i s a b le d V eteran Ow ne d S m a l l B u s in e ss
SDVOSB
EVC
434.947.1901 | wileywilson.com | 100% Employee-Owned
127 Nationwide Drive | Lynchburg, VA 24502
NO SCALE
SERVICE BAY 1-3 - MCC-MAB ONE-LINE DIAGRAM
Check for FU or CB
SEE "SWBD MDBA -- SERVICE BAY 1-3 US-1B ONE-LINE DIAGRAM" FOR CONTINUATION
MCC: 1_MCC-MAB
480V, 300A
CB: 1_E3 Ex Fan Canopy Fl 1
CUTLER-HAMMER (MCP)
7 A, 7 A Plug
CB: 1_E2 Emer Dpt Fl 1 Ex Fan
CUTLER-HAMMER (MCP)
7 A, 7 A Plug
CB: 1_E1 CageWasher Ex Fan
CUTLER-HAMMER (MCP)
3 A, 3 A Plug
CB: 1_E8 Gen Ex Fl 1 Ex Fan
CUTLER-HAMMER (MCP)
30 A, 30 A Plug
CB: 1_E5 Gen Ex Fl 1-3 Ex Fan
CUTLER-HAMMER (MCP)
15 A, 15 A Plug
CB: 1_E6 MICU Fl 4 Ex Fan
CUTLER-HAMMER (MCP)
15 A, 15 A Plug
CB: 1_E7 CCU Fl 4 Ex Fan
CUTLER-HAMMER (MCP)
15 A, 15 A Plug
CB: 1_E10A Inf Ani Fl 1 Ex Fan
CUTLER-HAMMER (MCP)
7 A, 7 A Plug
MCP: 1_CB: 1_E9 Fl 1 Fume Hood
CUTLER-HAMMER (MCP)
7 A, 7 A Plug
CB: 1_E10 Fl 1 Radio Iso
CUTLER-HAMMER (MCP)
7 A, 7 A Plug
CB: 1_AH-38 Elev Mach Rm
CUTLER-HAMMER (MCP)
7 A, 7 A Plug
CB: 1_AF T-A5 Pnl RLA
WESTINGHOUSE (HFB)
30 A
MCP: 1_CB: 1_EF-68
CUTLER-HAMMER (HMCP)
15 A, 15 A Plug
MCP: 1_CB: 1_EF-7A
CUTLER-HAMMER (MCP)
30 A, 30 A Plug
MCP: 1_CB: 1_E-4
CUTLER-HAMMER (HMCP)
50 A, 50 A Plug
MCP: 1_CB: 1_E-10B
CUTLER-HAMMER (HMCP)
7 A, 7 A Plug
F: 1_MCC MAB
(1) #500 THWN; 265 ft
F: 1_E3 Ex Fan Canopy Fl 1
(1) #12 THWN; 60 ft
F: 1_E2 Emer Dpt Fl 1 Ex Fan
(1) #12 THWN; 80 ft
F: 1_E1 CageWasher Ex Fan
(1) #12 THWN; 65 ft
F: 1_E5 Gen Ex Fl 1-3 Ex Fan
(1) #12 THWN; 65 ft
F: 1_E7 CCU Fl 4 Ex Fan
(1) #12 THWN; 50 ft
F: 1_E10A Inf Ani Fl 1 Ex Fan
(1) #12 THWN; 35 ft
F: 1_E10 Fl 1 Radio Iso
(1) #10 THWN; 50 ft
DISC: 1_E-10
480V, F: 1_AH-38 Elev Mach Rm
(1) #12 THWN; 1 ft
F: 1_AF T-A5 Pnl RLA
(1) #10 THWN; 5 ft
F: 1_CB: 1_EF-68 Disc
(1) #12 THWN; 60 ft
F: 1_CB: 1_EF-7A
(1) #12 THWN; 65 ft
F: 1_CB: 1_E-4
(1) #8 THWN; 60 ft
FU: 1_EX-10
FERRAZ SHAWMUT (TRS)
20 A
PNL: 1_RLA
208V, 100A
10k SCAR
F: 1_Pnl RLA
(1) #4 THWN; 5 ft
DISC: 1_E-8
480V, DISC: 1_E-9
480V, FU: 1_E-8
FERRAZ SHAWMUT (TRS)
30 A
F: 1_E8 Gen Ex Fl 1 Ex Fan
(1) #10 THWN; 60 ft
FU: 1_E-9
FERRAZ SHAWMUT (TRS)
20 A
F: 1_E9 Fl 1 Fume Hood
(1) #10 THWN; 50 ft
MTR: 1_EF-9
1 @ 2 hp
MTR: 1_EF-10A
1 @ 3 hp
MTR: 1_EF-8
1 @ 7.5 hp
MTR: 1_EXH-10
1 @ 2 hp
VFD: 1_EF-7A
F: 1_E-6
(1) #12 THWN; 85 ft
MTR: 1_E-6
1 @ 7.5 hp
MTR: 1_EF-10B
1 @ 3 hp
MTR: 1_EF-7B
1 @ 0.8 hp
MTR: 1_E-5
1 @ 7.5 hp
DISC: 1_EF-68
480V, F: 1_EF-68
(1) #12 THWN; 5 ft
MTR: EF-68
1 @ 7.5 hp
MTR: 1_E-4
1 @ 20 hp
MTR: 1_EF-7A
1 @ 1.5 hp
DISC: 1_E-1
480V, F: 1_E-1
(1) #12 THWN; 5 ft
MTR: 1_E-1
1 @ 1 hp
F: 1_E-3
(1) #12 THWN; 5 ft
MTR: 1_E-3
1 @ 1.5 hp
DISC: 1_E-3
480V, F: 1_E-8
(1) #10 THWN; 5 ft
F: 1_E-9
(1) #10 THWN; 5 ft
F: 1_E-10
(1) #10 THWN; 5 ft
MTR: 1_E-7
1 @ 7.5 hp S
P
XF: 1_T-A5
15kVA; 2.80%Z
Pri: 480V
Sec: 208V
DISC: 1_E-4
480V, F: 1_CB: 1_E-10B
(1) #10 THWN; 25 ft
FU: 1_E-3
FERRAZ SHAWMUT (TRS)
20 A
FU: 1_E-1
FERRAZ SHAWMUT (TRS)
20 A
FU: 1_E-4
FERRAZ SHAWMUT (TRS)
50 A
F: 1_E-4
(1) #8 THWN; 5 ft
F: 1_EF-7B
(1) #12 THWN; 5 ft
FU: 1_EF-7B
LITTELFUSE (FLSRID)
3 A
DISC: 1_EF-7B
480V, F: 1_Disc EF-7B
(1) #12 THWN; 95 ft
MCP: 1_CB: 1_Unk
CUTLER-HAMMER (MCP)
15 A, 15 A Plug
E-104 - SB 1-3.dgn 3/30/2018 8:36:58 AM
File details come from the government source that posted it. Updated .