sc_calc format.pdf

PDF 141 KB Posted

Attached to
H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) Federal contract opportunity
Solicitation number
36C26224Q1724
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 22

About this file

This document is a combined synopsis/solicitation for a federal commercial services contract for an Arc Flash Analysis at the VA Loma Linda Healthcare System (VALLHCS). The Department of Veterans Affairs (VA) is seeking to purchase Arc Flash Analysis services to comply with NFPA 70E and other electrical safety standards. The contractor will be required to collect electrical system data, perform an arc flash analysis, develop one-line diagrams, and provide a comprehensive report with recommendations. The contract is set-aside for 100% Service-Disabled Veteran-Owned Small Businesses (SDVOSB). The period of performance is September 1, 2024 to August 31, 2025. Quotes are due by August 23, 2024, and the award will be based on a comparative evaluation of price and past performance, with price being the more important factor. The contractor will be required to follow all applicable federal, state, and local safety regulations and provide all necessary safety equipment and personnel.

View the file

Other files for this federal contract opportunity

Other files attached to H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025), newest first.
File Type Posted
Tbl 3_3 Equip Eval.pdf PDF
lf_calc format.pdf PDF
input_data format.pdf PDF
EYE Clinic One Line Drawings.docx DOCX document
E-112.pdf PDF
E-110.pdf PDF
E-108.pdf PDF
E-104.pdf PDF
CANCER CENTER SIGNAL LINE DRAWINGS 2017.png PNG image
Arc Flash Study 2016 Schneider Full Facility.pdf PDF
20110460 - Sheet - E-611 - SINGLE LINE DIAGRAM OP Pharmacy.pdf PDF
116801E5.1.5.pdf PDF
022712 SCC and OCPD Coordination Study - VA Loma Linda.pdf PDF
Tbl 4_1 MV Prot Dev Settingsa.pdf PDF
Tbl 3-1_2 Prot Dev Eval.pdf PDF
MV Coordination Descrip Tbl.pdf PDF
Loma Linda MV TCCs.pdf PDF
E-109.pdf PDF
E-103.pdf PDF
CLC ReHab SIGNAL LINE DRAWINGS.png PNG image
CLC PC SIGNAL LINE DRAWINGS.png PNG image
VALL Electrical Single Line Diagrams.pdf PDF
Short Circuit Study - Op Pharmacy.pdf PDF
Loma Linda-60pc.pdf PDF
E601 BEHAVIORAL HEALTH BUILDING.pdf PDF
E-115.pdf PDF
E-114.pdf PDF
E-113.pdf PDF
E-101.pdf PDF
Cover.pdf PDF
116801E5.1.12.pdf PDF
116801E5.1.11.pdf PDF
116801E5.1.10.pdf PDF
116801E5.1.8.pdf PDF
116801E5.1.2.pdf PDF
116801E5.1.1.pdf PDF
Tbl 6-1_2_Arc_Flash.pdf PDF
E-111.pdf PDF
E-107.pdf PDF
E-106.pdf PDF
E-105.pdf PDF
E-102.pdf PDF
E1.1 AUDIOLOGY.pdf PDF
E-001.pdf PDF
Arc Flash Study CLC Reb.pdf PDF
Arc Flash Study CLC Ph 2.pdf PDF
116801E5.1.9.pdf PDF
116801E5.1.7.pdf PDF
116801E5.1.6.pdf PDF
36C26224Q1724.docx DOCX document
Show all 50

H959--ARC FLASH ANALYSIS - POP (09/01/2024 - 08/31/2025) has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VA Loma Linda - Jerry L. Pettis VAHCS – Loma Linda, California Electrical Condition Assessment – Short Circuit Current Calculations

Model: mv_system

Prepared for: Dept. of Veterans Affairs Prepared by: Wiley|Wilson

Mar 27, 2018 06:01:111

ALL INFORMATION PRESENTED IS FOR REVIEW, APPROVAL

INTERPRETATION AND APPLICATION BY A REGISTERED ENGINEER ONLY

SKM DISCLAIMS ANY RESPONSIBILITY AND LIABILITY RESULTING

FROM THE USE AND INTERPRETATION OF THIS SOFTWARE.

SKM POWER*TOOLS FOR WINDOWS

A_FAULT SHORT CIRCUIT ANALYSIS REPORT

COPYRIGHT SKM SYSTEMS ANALYSIS, INC. 1996-2017

Mar 27, 2018 06:01:11 THREE PHASE LOW VOLTAGE DUTY PAGE 1

T H R E E P H A S E F A U L T R E P O R T

(FOR APPLICATION OF LOW VOLTAGE BREAKERS)

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

BUS: 1_SW US-1A West 3P Duty: 7.161 KA AT -83.18 DEG ( 148.84 MVA) X/R: 8.52

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.1149 + J 0.9606 OHMS

F: 1_A-3-2 BUS: 1_FDR A-3-1 7.161 KA ANG: -83.18

BUS: 1_SW US-1B West 3P Duty: 7.150 KA AT -83.11 DEG ( 148.60 MVA) X/R: 8.43

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.1163 + J 0.9620 OHMS

F: 1_B-3-3 BUS: 1_FDR B-3-1 7.150 KA ANG: -83.11

BUS: 1_SW US-2A East 3P Duty: 7.406 KA AT -85.01 DEG ( 153.94 MVA) X/R: 11.76

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0814 + J 0.9319 OHMS

F; 1_B-2-5 BUS: 1_B-2-2 7.406 KA ANG: 94.99

BUS: 1_SW US-2B East 3P Duty: 7.397 KA AT -84.94 DEG ( 153.75 MVA) X/R: 11.60

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0826 + J 0.9329 OHMS

F; 1_A-2-6 BUS: 1_FDR A-2-2 7.397 KA ANG: 95.06

BUS: 1_SW US-3A West 3P Duty: 7.076 KA AT -82.79 DEG ( 147.07 MVA) X/R: 8.04

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.1229 + J 0.9714 OHMS

F: 1_A-3-5 BUS: 1_FDR A-3-2 7.076 KA ANG: 97.21

BUS: 1_SW US-3B West 3P Duty: 7.067 KA AT -82.73 DEG ( 146.88 MVA) X/R: 7.97

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.1241 + J 0.9725 OHMS

F; 1_A-3-6 BUS: 1_FDR A-3-2 7.067 KA ANG: 97.27

BUS: 1_SW US-4A East 3P Duty: 7.484 KA AT -85.38 DEG ( 155.55 MVA) X/R: 12.74

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0745 + J 0.9227 OHMS

F; 1_B-2-2 BUS: 1_FDR B-2-1 7.484 KA ANG: -85.38

BUS: 1_SW US-4B East 3P Duty: 7.475 KA AT -85.31 DEG ( 155.36 MVA) X/R: 12.55

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0757 + J 0.9238 OHMS

F: 1_A-2-3 BUS: 1_FDR A-2-1 7.475 KA ANG: -85.31

BUS: 1_SW US-5A East 3P Duty: 7.469 KA AT -85.27 DEG ( 155.24 MVA) X/R: 12.43

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0765 + J 0.9245 OHMS

F: 1_A-1-2 BUS: 1_FDR A-1-1 7.469 KA ANG: 94.73

BUS: 1_SW US-5B East 3P Duty: 7.456 KA AT -85.19 DEG ( 154.98 MVA) X/R: 12.22

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0779 + J 0.9259 OHMS

F; 1_B-1-3 BUS: 1_FDR B-1-1 7.456 KA ANG: 94.81

BUS: 1_SW US-6 East 3P Duty: 7.455 KA AT -85.18 DEG ( 154.96 MVA) X/R: 12.19

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0781 + J 0.9260 OHMS

F: 1_A-1-4 BUS: 1_FDR A-1-1 7.455 KA ANG: -85.18

Mar 27, 2018 06:01:11 THREE PHASE LOW VOLTAGE DUTY PAGE 2

T H R E E P H A S E F A U L T R E P O R T

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

SWGR: 1_NORTH 3P Duty: 7.500 KA AT -85.48 DEG ( 155.88 MVA) X/R: 13.04

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0727 + J 0.9209 OHMS

F: 1_SCE BUS: 1_SCE 6.499 KA ANG: -265.23

CBL-0009 SWGR: 1_SOUTH 1.001 KA ANG: 92.88

SWGR: 1_SOUTH 3P Duty: 7.499 KA AT -85.48 DEG ( 155.86 MVA) X/R: 13.04

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0727 + J 0.9210 OHMS

F: 1_12KV Gen BUS-0082 1.001 KA ANG: 92.88

CBL-0009 SWGR: 1_NORTH 6.499 KA ANG: -85.23

SWGR: 1_US-7 3P Duty: 6.980 KA AT -81.99 DEG ( 145.08 MVA) X/R: 7.21

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.1384 + J 0.9829 OHMS

BUS: 1_US-7-2 BUS: 1_US-7-1 6.980 KA ANG: -81.99

Mar 27, 2018 06:01:11 UNBALANCED LOW VOLTAGE DUTY PAGE 1

U N B A L A N C E D F A U L T R E P O R T

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES

VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *

BUS: 1_SW US-1A West 3P Duty: 7.161 8.52 Z1= 0.6718 10.017 8.654

SLG DUTY: 2.313 11.56 Z2= 0.6718 3.401

12000. VOLTS LN/LN: 6.202 Z0= 4.8965

LN/LN/GND: 6.214 ( 1.379 GND RETURN KA)

BUS: 1_SW US-1B West 3P Duty: 7.150 8.43 Z1= 0.6729 9.981 8.628

SLG DUTY: 2.312 11.43 Z2= 0.6729 3.393

12000. VOLTS LN/LN: 6.192 Z0= 4.8990

LN/LN/GND: 6.203 ( 1.379 GND RETURN KA)

BUS: 1_SW US-2A East 3P Duty: 7.406 11.76 Z1= 0.6496 10.916 9.253

SLG DUTY: 2.354 15.92 Z2= 0.6496 3.607

12000. VOLTS LN/LN: 6.414 Z0= 4.8329

LN/LN/GND: 6.432 ( 1.399 GND RETURN KA)

BUS: 1_SW US-2B East 3P Duty: 7.397 11.60 Z1= 0.6504 10.881 9.230

SLG DUTY: 2.352 15.70 Z2= 0.6504 3.599

12000. VOLTS LN/LN: 6.406 Z0= 4.8358

LN/LN/GND: 6.424 ( 1.398 GND RETURN KA)

BUS: 1_SW US-3A West 3P Duty: 7.076 8.04 Z1= 0.6800 9.794 8.494

SLG DUTY: 2.299 10.88 Z2= 0.6800 3.349

12000. VOLTS LN/LN: 6.128 Z0= 4.9195

LN/LN/GND: 6.139 ( 1.372 GND RETURN KA)

BUS: 1_SW US-3B West 3P Duty: 7.067 7.97 Z1= 0.6808 9.765 8.474

SLG DUTY: 2.297 10.79 Z2= 0.6808 3.343

12000. VOLTS LN/LN: 6.120 Z0= 4.9220

LN/LN/GND: 6.130 ( 1.371 GND RETURN KA)

BUS: 1_SW US-4A East 3P Duty: 7.484 12.74 Z1= 0.6429 11.154 9.418

SLG DUTY: 2.366 17.24 Z2= 0.6429 3.658

12000. VOLTS LN/LN: 6.481 Z0= 4.8139

LN/LN/GND: 6.501 ( 1.405 GND RETURN KA)

BUS: 1_SW US-4B East 3P Duty: 7.475 12.55 Z1= 0.6437 11.118 9.394

SLG DUTY: 2.365 16.98 Z2= 0.6437 3.649

12000. VOLTS LN/LN: 6.473 Z0= 4.8167

LN/LN/GND: 6.493 ( 1.404 GND RETURN KA)

Mar 27, 2018 06:01:11 UNBALANCED LOW VOLTAGE DUTY PAGE 2

U N B A L A N C E D F A U L T R E P O R T

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

LOCATION FAULT KA X/R EQUIVALENT (PU) ASYM. KA AT 0.5 CYCLES

VOLTAGE DUTIES (RMS) FAULT IMPEDANCE * MAX. RMS AVG. RMS *

BUS: 1_SW US-5A East 3P Duty: 7.469 12.43 Z1= 0.6442 11.095 9.379

SLG DUTY: 2.364 16.83 Z2= 0.6442 3.644

12000. VOLTS LN/LN: 6.468 Z0= 4.8182

LN/LN/GND: 6.487 ( 1.404 GND RETURN KA)

BUS: 1_SW US-5B East 3P Duty: 7.456 12.22 Z1= 0.6452 11.049 9.349

SLG DUTY: 2.362 16.55 Z2= 0.6452 3.635

12000. VOLTS LN/LN: 6.458 Z0= 4.8206

LN/LN/GND: 6.476 ( 1.403 GND RETURN KA)

BUS: 1_SW US-6 East 3P Duty: 7.455 12.19 Z1= 0.6453 11.044 9.345

SLG DUTY: 2.362 16.51 Z2= 0.6453 3.633

12000. VOLTS LN/LN: 6.457 Z0= 4.8215

LN/LN/GND: 6.475 ( 1.403 GND RETURN KA)

SWGR: 1_NORTH 3P Duty: 7.500 13.04 Z1= 0.6415 11.213 9.458

SLG DUTY: 2.369 17.63 Z2= 0.6415 3.670

12000. VOLTS LN/LN: 6.495 Z0= 4.8107

LN/LN/GND: 6.515 ( 1.406 GND RETURN KA)

SWGR: 1_SOUTH 3P Duty: 7.499 13.04 Z1= 0.6416 11.211 9.456

SLG DUTY: 2.369 17.64 Z2= 0.6416 3.670

12000. VOLTS LN/LN: 6.494 Z0= 4.8103

LN/LN/GND: 6.514 ( 1.407 GND RETURN KA)

SWGR: 1_US-7 3P Duty: 6.980 7.21 Z1= 0.6893 9.460 8.270

SLG DUTY: 2.282 9.74 Z2= 0.6893 3.268

12000. VOLTS LN/LN: 6.045 Z0= 4.9463

LN/LN/GND: 6.053 ( 1.364 GND RETURN KA)

Mar 27, 2018 06:01:11 UNBALANCED LOW VOLTAGE DUTY PAGE 3

F A U L T S T U D Y S U M M A R Y

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

BUS RECORD VOLTAGE A V A I L A B L E F A U L T D U T I E S (KA)

NO NAME L-L 3 PHASE X/R LINE/GRND X/R

BUS: 1_SW US-1A West 12000. 7.161 8.52 2.313 11.56 BUS: 1_SW US-1B West 12000. 7.150 8.43 2.312 11.43 BUS: 1_SW US-2A East 12000. 7.406 11.76 2.354 15.92 BUS: 1_SW US-2B East 12000. 7.397 11.60 2.352 15.70 BUS: 1_SW US-3A West 12000. 7.076 8.04 2.299 10.88

BUS: 1_SW US-3B West 12000. 7.067 7.97 2.297 10.79 BUS: 1_SW US-4A East 12000. 7.484 12.74 2.366 17.24 BUS: 1_SW US-4B East 12000. 7.475 12.55 2.365 16.98 BUS: 1_SW US-5A East 12000. 7.469 12.43 2.364 16.83 BUS: 1_SW US-5B East 12000. 7.456 12.22 2.362 16.55

BUS: 1_SW US-6 East 12000. 7.455 12.19 2.362 16.51

SWGR: 1_NORTH 12000. 7.500 13.04 2.369 17.63

SWGR: 1_SOUTH 12000. 7.499 13.04 2.369 17.64

SWGR: 1_US-7 12000. 6.980 7.21 2.282 9.74

57 FAULTED BUSES, 58 BRANCHES, 2 CONTRIBUTIONS

UNBALANCED FAULTS REQUESTED

*** SHORT CIRCUIT STUDY COMPLETE ***

Mar 27, 2018 06:01:11 THREE PHASE MOMENTARY DUTY PAGE 1

T H R E E P H A S E M O M E N T A R Y D U T Y R E P O R T

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

BUS: 1_SW US-1A West E/Z: 7.161 KA AT -83.18 DEG ( 148.84 MVA) X/R: 8.52

SYM*1.6: 11.458 KA MOMENTARY BASED ON X/R: 10.017 KA

SYM*2.7: 19.335 KA CREST BASED ON X/R: 17.132 KA

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.1149 + J 0.9606 OHMS

Mar 27, 2018 06:01:11 THREE PHASE MOMENTARY DUTY PAGE 2

MODEL TRANSFORMER TAPS: NO

BUS: 1_SW US-1B West E/Z: 7.150 KA AT -83.11 DEG ( 148.60 MVA) X/R: 8.43

SYM*1.6: 11.439 KA MOMENTARY BASED ON X/R: 9.981 KA

SYM*2.7: 19.304 KA CREST BASED ON X/R: 17.075 KA

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.1163 + J 0.9620 OHMS

BUS: 1_SW US-2A East E/Z: 7.406 KA AT -85.01 DEG ( 153.94 MVA) X/R: 11.76

SYM*1.6: 11.850 KA MOMENTARY BASED ON X/R: 10.916 KA

SYM*2.7: 19.997 KA CREST BASED ON X/R: 18.493 KA

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0814 + J 0.9319 OHMS

BUS: 1_SW US-2B East E/Z: 7.397 KA AT -84.94 DEG ( 153.75 MVA) X/R: 11.60

SYM*1.6: 11.836 KA MOMENTARY BASED ON X/R: 10.881 KA

SYM*2.7: 19.973 KA CREST BASED ON X/R: 18.441 KA

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0826 + J 0.9329 OHMS

BUS: 1_SW US-3A West E/Z: 7.076 KA AT -82.79 DEG ( 147.07 MVA) X/R: 8.04

SYM*1.6: 11.321 KA MOMENTARY BASED ON X/R: 9.794 KA

SYM*2.7: 19.105 KA CREST BASED ON X/R: 16.778 KA

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.1229 + J 0.9714 OHMS

BUS: 1_SW US-3B West E/Z: 7.067 KA AT -82.73 DEG ( 146.88 MVA) X/R: 7.97

SYM*1.6: 11.307 KA MOMENTARY BASED ON X/R: 9.765 KA

SYM*2.7: 19.080 KA CREST BASED ON X/R: 16.733 KA

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.1241 + J 0.9725 OHMS

BUS: 1_SW US-4A East E/Z: 7.484 KA AT -85.38 DEG ( 155.55 MVA) X/R: 12.74

SYM*1.6: 11.974 KA MOMENTARY BASED ON X/R: 11.154 KA

SYM*2.7: 20.207 KA CREST BASED ON X/R: 18.855 KA

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0745 + J 0.9227 OHMS

BUS: 1_SW US-4B East E/Z: 7.475 KA AT -85.31 DEG ( 155.36 MVA) X/R: 12.55

SYM*1.6: 11.960 KA MOMENTARY BASED ON X/R: 11.118 KA

SYM*2.7: 20.182 KA CREST BASED ON X/R: 18.801 KA

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0757 + J 0.9238 OHMS

Mar 27, 2018 06:01:11 THREE PHASE MOMENTARY DUTY PAGE 3

MODEL TRANSFORMER TAPS: NO

CONTRIBUTIONS TO BUS: 1_SW US-4B East (CONTINUED)

BUS: 1_SW US-5A East E/Z: 7.469 KA AT -85.27 DEG ( 155.24 MVA) X/R: 12.43

SYM*1.6: 11.950 KA MOMENTARY BASED ON X/R: 11.095 KA

SYM*2.7: 20.166 KA CREST BASED ON X/R: 18.767 KA

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0765 + J 0.9245 OHMS

BUS: 1_SW US-5B East E/Z: 7.456 KA AT -85.19 DEG ( 154.98 MVA) X/R: 12.22

SYM*1.6: 11.930 KA MOMENTARY BASED ON X/R: 11.049 KA

SYM*2.7: 20.133 KA CREST BASED ON X/R: 18.699 KA

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0779 + J 0.9259 OHMS

BUS: 1_SW US-6 East E/Z: 7.455 KA AT -85.18 DEG ( 154.96 MVA) X/R: 12.19

SYM*1.6: 11.929 KA MOMENTARY BASED ON X/R: 11.044 KA

SYM*2.7: 20.130 KA CREST BASED ON X/R: 18.691 KA

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0781 + J 0.9260 OHMS

Mar 27, 2018 06:01:11 THREE PHASE MOMENTARY DUTY PAGE 4

MODEL TRANSFORMER TAPS: NO

SWGR: 1_NORTH E/Z: 7.500 KA AT -85.48 DEG ( 155.88 MVA) X/R: 13.04

SYM*1.6: 11.999 KA MOMENTARY BASED ON X/R: 11.213 KA

SYM*2.7: 20.249 KA CREST BASED ON X/R: 18.942 KA

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0727 + J 0.9209 OHMS

SWGR: 1_SOUTH E/Z: 7.499 KA AT -85.48 DEG ( 155.86 MVA) X/R: 13.04

SYM*1.6: 11.998 KA MOMENTARY BASED ON X/R: 11.211 KA

SYM*2.7: 20.247 KA CREST BASED ON X/R: 18.940 KA

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0727 + J 0.9210 OHMS

SWGR: 1_US-7 E/Z: 6.980 KA AT -81.99 DEG ( 145.08 MVA) X/R: 7.21

SYM*1.6: 11.168 KA MOMENTARY BASED ON X/R: 9.460 KA

SYM*2.7: 18.846 KA CREST BASED ON X/R: 16.257 KA

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.1384 + J 0.9829 OHMS

Mar 27, 2018 06:01:11 UNBALANCED MOMENTARY DUTY PAGE 1

U N B A L A N C E D M O M E N T A R Y D U T Y R E P O R T

MODEL TRANSFORMER TAPS: NO

LOCATION FAULT E/Z X/R EQUIVALENT MOMENTARY FAULT DUTIES

VOLTAGE TYPE KA IMPEDANCE (PU) E/Z * 1.6 @ 0.5 CYCLE

3P Duty: 7.16 8.5 Z1= 0.6718 11.46 10.02 BUS: 1_SW US-1A West SLG DUTY: 2.31 11.6 Z2= 0.6718 3.70 3.40

12000. VOLTS LN/LN: 6.20 Z0= 4.8965

LN/LN/GND: 6.21 ( 1.38 GND RETURN KA)

3P Duty: 7.15 8.4 Z1= 0.6729 11.44 9.98 BUS: 1_SW US-1B West SLG DUTY: 2.31 11.4 Z2= 0.6729 3.70 3.39

12000. VOLTS LN/LN: 6.19 Z0= 4.8990

LN/LN/GND: 6.20 ( 1.38 GND RETURN KA)

3P Duty: 7.41 11.8 Z1= 0.6496 11.85 10.92 BUS: 1_SW US-2A East SLG DUTY: 2.35 15.9 Z2= 0.6496 3.77 3.61

12000. VOLTS LN/LN: 6.41 Z0= 4.8329

LN/LN/GND: 6.43 ( 1.40 GND RETURN KA)

3P Duty: 7.40 11.6 Z1= 0.6504 11.84 10.88 BUS: 1_SW US-2B East SLG DUTY: 2.35 15.7 Z2= 0.6504 3.76 3.60

12000. VOLTS LN/LN: 6.41 Z0= 4.8358

LN/LN/GND: 6.42 ( 1.40 GND RETURN KA)

3P Duty: 7.08 8.0 Z1= 0.6800 11.32 9.79 BUS: 1_SW US-3A West SLG DUTY: 2.30 10.9 Z2= 0.6800 3.68 3.35

12000. VOLTS LN/LN: 6.13 Z0= 4.9195

LN/LN/GND: 6.14 ( 1.37 GND RETURN KA)

3P Duty: 7.07 8.0 Z1= 0.6808 11.31 9.76 BUS: 1_SW US-3B West SLG DUTY: 2.30 10.8 Z2= 0.6808 3.68 3.34

12000. VOLTS LN/LN: 6.12 Z0= 4.9220

LN/LN/GND: 6.13 ( 1.37 GND RETURN KA)

3P Duty: 7.48 12.7 Z1= 0.6429 11.97 11.15 BUS: 1_SW US-4A East SLG DUTY: 2.37 17.2 Z2= 0.6429 3.79 3.66

12000. VOLTS LN/LN: 6.48 Z0= 4.8139

LN/LN/GND: 6.50 ( 1.41 GND RETURN KA)

3P Duty: 7.47 12.5 Z1= 0.6437 11.96 11.12 BUS: 1_SW US-4B East SLG DUTY: 2.36 17.0 Z2= 0.6437 3.78 3.65

12000. VOLTS LN/LN: 6.47 Z0= 4.8167

LN/LN/GND: 6.49 ( 1.40 GND RETURN KA)

Mar 27, 2018 06:01:11 UNBALANCED MOMENTARY DUTY PAGE 2

U N B A L A N C E D M O M E N T A R Y D U T Y R E P O R T

MODEL TRANSFORMER TAPS: NO

LOCATION FAULT E/Z X/R EQUIVALENT MOMENTARY FAULT DUTIES

VOLTAGE TYPE KA IMPEDANCE (PU) E/Z * 1.6 @ 0.5 CYCLE

3P Duty: 7.47 12.4 Z1= 0.6442 11.95 11.09 BUS: 1_SW US-5A East SLG DUTY: 2.36 16.8 Z2= 0.6442 3.78 3.64

12000. VOLTS LN/LN: 6.47 Z0= 4.8182

LN/LN/GND: 6.49 ( 1.40 GND RETURN KA)

3P Duty: 7.46 12.2 Z1= 0.6452 11.93 11.05 BUS: 1_SW US-5B East SLG DUTY: 2.36 16.6 Z2= 0.6452 3.78 3.64

12000. VOLTS LN/LN: 6.46 Z0= 4.8206

LN/LN/GND: 6.48 ( 1.40 GND RETURN KA)

3P Duty: 7.46 12.2 Z1= 0.6453 11.93 11.04 BUS: 1_SW US-6 East SLG DUTY: 2.36 16.5 Z2= 0.6453 3.78 3.63

12000. VOLTS LN/LN: 6.46 Z0= 4.8215

LN/LN/GND: 6.48 ( 1.40 GND RETURN KA)

3P Duty: 7.50 13.0 Z1= 0.6415 12.00 11.21

SWGR: 1_NORTH SLG DUTY: 2.37 17.6 Z2= 0.6415 3.79 3.67

12000. VOLTS LN/LN: 6.49 Z0= 4.8107

LN/LN/GND: 6.51 ( 1.41 GND RETURN KA)

3P Duty: 7.50 13.0 Z1= 0.6416 12.00 11.21

SWGR: 1_SOUTH SLG DUTY: 2.37 17.6 Z2= 0.6416 3.79 3.67

12000. VOLTS LN/LN: 6.49 Z0= 4.8103

LN/LN/GND: 6.51 ( 1.41 GND RETURN KA)

3P Duty: 6.98 7.2 Z1= 0.6893 11.17 9.46

SWGR: 1_US-7 SLG DUTY: 2.28 9.7 Z2= 0.6893 3.65 3.27

12000. VOLTS LN/LN: 6.04 Z0= 4.9463

LN/LN/GND: 6.05 ( 1.36 GND RETURN KA)

Mar 27, 2018 06:01:11 UNBALANCED MOMENTARY DUTY PAGE 3

M O M E N T A R Y D U T Y S U M M A R Y R E P O R T

MODEL TRANSFORMER TAPS: NO

SOLUTION METHOD : E/Z

BUS RECORD VOLTAGE * 3 P H A S E * * * * SLG * * *

NO NAME L-L KA X/R KA X/R

BUS: 1_SW US-1A West 12000. 10.017 8.52 3.401 11.56 BUS: 1_SW US-1B West 12000. 9.981 8.43 3.393 11.43 BUS: 1_SW US-2A East 12000. 10.916 11.76 3.607 15.92 BUS: 1_SW US-2B East 12000. 10.881 11.60 3.599 15.70 BUS: 1_SW US-3A West 12000. 9.794 8.04 3.349 10.88

BUS: 1_SW US-3B West 12000. 9.765 7.97 3.343 10.79 BUS: 1_SW US-4A East 12000. 11.154 12.74 3.658 17.24 BUS: 1_SW US-4B East 12000. 11.118 12.55 3.649 16.98 BUS: 1_SW US-5A East 12000. 11.095 12.43 3.644 16.83 BUS: 1_SW US-5B East 12000. 11.049 12.22 3.635 16.55

BUS: 1_SW US-6 East 12000. 11.044 12.19 3.633 16.51

SWGR: 1_NORTH 12000. 11.213 13.04 3.670 17.63

SWGR: 1_SOUTH 12000. 11.211 13.04 3.670 17.64

SWGR: 1_US-7 12000. 9.460 7.21 3.268 9.74

43 FAULTED BUSES, 58 BRANCHES, 2 CONTRIBUTIONS

UNBALANCED FAULTS REQUESTED

Mar 27, 2018 06:01:11 THREE PHASE INTERRUPTING DUTY PAGE 1

T H R E E P H A S E I N T E R R U P T I N G D U T Y R E P O R T

MODEL TRANSFORMER TAPS: NO

NACD OPTION: INTERPOLATED

BUS: 1_SW US-1A West E/Z: 7.161 KA AT -83.18 DEG ( 148.84 MVA) X/R: 8.52

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.1149 + J 0.9606 OHMS

CONTRIBUTIONS: BUS: 1_FDR A-3 7.161 KA ANG: -83.18

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL: 1_SCE-2 6.206 0.06 R

GEN: 1_12KV 0.956 0.06 L

TOTAL REMOTE: 6.206 KA NACD RATIO: 0.8666

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.001

DUTY (KA) : 7.161 7.161 7.161 7.171

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.164 1.032 1.000 1.000

DUTY (KA) : 8.333 7.388 7.161 7.161

BUS: 1_SW US-1B West E/Z: 7.150 KA AT -83.11 DEG ( 148.60 MVA) X/R: 8.43

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.1163 + J 0.9620 OHMS

CONTRIBUTIONS: BUS: 1_FDR B-3 7.150 KA ANG: -83.11

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL: 1_SCE-2 6.196 0.06 R

GEN: 1_12KV 0.954 0.06 L

TOTAL REMOTE: 6.196 KA NACD RATIO: 0.8666

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.001

DUTY (KA) : 7.150 7.150 7.150 7.159

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.161 1.030 1.000 1.000

DUTY (KA) : 8.297 7.366 7.150 7.150

BUS: 1_SW US-2A East E/Z: 7.406 KA AT -85.01 DEG ( 153.94 MVA) X/R: 11.76

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0814 + J 0.9319 OHMS

CONTRIBUTIONS: BUS: 1_B-2-2 7.406 KA ANG: 94.99

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL: 1_SCE-2 6.418 0.02 R

GEN: 1_12KV 0.988 0.02 L

TOTAL REMOTE: 6.418 KA NACD RATIO: 0.8666

Mar 27, 2018 06:01:11 THREE PHASE INTERRUPTING DUTY PAGE 2

MODEL TRANSFORMER TAPS: NO

NACD OPTION: INTERPOLATED

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.015

DUTY (KA) : 7.406 7.406 7.406 7.520

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.256 1.089 1.024 1.000

DUTY (KA) : 9.300 8.065 7.587 7.406

BUS: 1_SW US-2B East E/Z: 7.397 KA AT -84.94 DEG ( 153.75 MVA) X/R: 11.60

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0826 + J 0.9329 OHMS

CONTRIBUTIONS: BUS: 1_FDR A-2 7.397 KA ANG: 95.06

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL: 1_SCE-2 6.411 0.02 R

GEN: 1_12KV 0.987 0.02 L

TOTAL REMOTE: 6.411 KA NACD RATIO: 0.8666

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.014

DUTY (KA) : 7.397 7.397 7.397 7.503

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.252 1.086 1.023 1.000

DUTY (KA) : 9.260 8.032 7.565 7.397

BUS: 1_SW US-3A West E/Z: 7.076 KA AT -82.79 DEG ( 147.07 MVA) X/R: 8.04

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.1229 + J 0.9714 OHMS

CONTRIBUTIONS: BUS: 1_FDR A-3 7.076 KA ANG: 97.21

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL: 1_SCE-2 6.132 0.07 R

GEN: 1_12KV 0.944 0.07 L

TOTAL REMOTE: 6.132 KA NACD RATIO: 0.8666

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.001

DUTY (KA) : 7.076 7.076 7.076 7.081

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.148 1.024 1.000 1.000

DUTY (KA) : 8.121 7.249 7.076 7.076

Mar 27, 2018 06:01:11 THREE PHASE INTERRUPTING DUTY PAGE 3

MODEL TRANSFORMER TAPS: NO

NACD OPTION: INTERPOLATED

BUS: 1_SW US-3B West E/Z: 7.067 KA AT -82.73 DEG ( 146.88 MVA) X/R: 7.97

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.1241 + J 0.9725 OHMS

CONTRIBUTIONS: BUS: 1_FDR A-3 7.067 KA ANG: 97.27

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL: 1_SCE-2 6.124 0.07 R

GEN: 1_12KV 0.943 0.07 L

TOTAL REMOTE: 6.124 KA NACD RATIO: 0.8666

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.001

DUTY (KA) : 7.067 7.067 7.067 7.071

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.145 1.023 1.000 1.000

DUTY (KA) : 8.094 7.232 7.067 7.067

BUS: 1_SW US-4A East E/Z: 7.484 KA AT -85.38 DEG ( 155.55 MVA) X/R: 12.74

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0745 + J 0.9227 OHMS

CONTRIBUTIONS: BUS: 1_FDR B-2 7.484 KA ANG: -85.38

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL: 1_SCE-2 6.486 0.00 R

GEN: 1_12KV 0.999 0.00 L

TOTAL REMOTE: 6.486 KA NACD RATIO: 0.8666

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.022

DUTY (KA) : 7.484 7.484 7.484 7.649

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.279 1.108 1.035 1.000

DUTY (KA) : 9.575 8.294 7.743 7.488

BUS: 1_SW US-4B East E/Z: 7.475 KA AT -85.31 DEG ( 155.36 MVA) X/R: 12.55

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0757 + J 0.9238 OHMS

CONTRIBUTIONS: BUS: 1_FDR A-2 7.475 KA ANG: -85.31

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL: 1_SCE-2 6.478 0.00 R

GEN: 1_12KV 0.997 0.00 L

TOTAL REMOTE: 6.478 KA NACD RATIO: 0.8666

Mar 27, 2018 06:01:11 THREE PHASE INTERRUPTING DUTY PAGE 4

MODEL TRANSFORMER TAPS: NO

NACD OPTION: INTERPOLATED

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.021

DUTY (KA) : 7.475 7.475 7.475 7.629

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.275 1.104 1.033 1.000

DUTY (KA) : 9.528 8.256 7.718 7.475

BUS: 1_SW US-5A East E/Z: 7.469 KA AT -85.27 DEG ( 155.24 MVA) X/R: 12.43

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0765 + J 0.9245 OHMS

CONTRIBUTIONS: BUS: 1_FDR A-1 7.469 KA ANG: 94.73

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL: 1_SCE-2 6.473 0.01 R

GEN: 1_12KV 0.997 0.01 L

TOTAL REMOTE: 6.473 KA NACD RATIO: 0.8666

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.020

DUTY (KA) : 7.469 7.469 7.469 7.618

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.272 1.102 1.031 1.000

DUTY (KA) : 9.500 8.232 7.703 7.469

BUS: 1_SW US-5B East E/Z: 7.456 KA AT -85.19 DEG ( 154.98 MVA) X/R: 12.22

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0779 + J 0.9259 OHMS

CONTRIBUTIONS: BUS: 1_FDR B-1 7.456 KA ANG: 94.81

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL: 1_SCE-2 6.462 0.01 R

GEN: 1_12KV 0.995 0.01 L

TOTAL REMOTE: 6.462 KA NACD RATIO: 0.8666

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.018

DUTY (KA) : 7.456 7.456 7.456 7.594

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.267 1.098 1.029 1.000

DUTY (KA) : 9.446 8.187 7.674 7.456

Mar 27, 2018 06:01:11 THREE PHASE INTERRUPTING DUTY PAGE 5

PRE FAULT VOLTAGE: 1.0000

MODEL TRANSFORMER TAPS: NO

NACD OPTION: INTERPOLATED

BUS: 1_SW US-6 East E/Z: 7.455 KA AT -85.18 DEG ( 154.96 MVA) X/R: 12.19

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0781 + J 0.9260 OHMS

CONTRIBUTIONS: BUS: 1_FDR A-1 7.455 KA ANG: -85.18

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL: 1_SCE-2 6.461 0.01 R

GEN: 1_12KV 0.995 0.01 L

TOTAL REMOTE: 6.461 KA NACD RATIO: 0.8666

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.018

DUTY (KA) : 7.455 7.455 7.455 7.592

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.266 1.097 1.029 1.000

DUTY (KA) : 9.439 8.181 7.670 7.455

SWGR: 1_NORTH E/Z: 7.500 KA AT -85.48 DEG ( 155.88 MVA) X/R: 13.04

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0727 + J 0.9209 OHMS

CONTRIBUTIONS: BUS: 1_SCE 6.499 KA ANG: -265.23

CBL-0009 SWGR: 1_SOUTH 1.001 KA ANG: 92.88

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL: 1_SCE-2 6.499 0.00 R

GEN: 1_12KV 1.001 0.00 L

TOTAL REMOTE: 6.499 KA NACD RATIO: 0.8666

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.024

DUTY (KA) : 7.500 7.500 7.500 7.680

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.287 1.114 1.038 1.003

DUTY (KA) : 9.649 8.356 7.782 7.520

SWGR: 1_SOUTH E/Z: 7.499 KA AT -85.48 DEG ( 155.86 MVA) X/R: 13.04

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.0727 + J 0.9210 OHMS

F: 1_12KV Gen BUS-0082 1.001 KA ANG: 92.88

Mar 27, 2018 06:01:11 THREE PHASE INTERRUPTING DUTY PAGE 6

MODEL TRANSFORMER TAPS: NO

NACD OPTION: INTERPOLATED

CONTRIBUTIONS TO SWGR: 1_SOUTH (CONTINUED)

CBL-0009 SWGR: 1_NORTH 6.499 KA ANG: -85.23

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL: 1_SCE-2 6.499 0.00 R

GEN: 1_12KV 1.001 0.00 L

TOTAL REMOTE: 6.499 KA NACD RATIO: 0.8666

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.024

DUTY (KA) : 7.499 7.499 7.499 7.679

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.287 1.114 1.038 1.003

DUTY (KA) : 9.648 8.355 7.781 7.519

SWGR: 1_US-7 E/Z: 6.980 KA AT -81.99 DEG ( 145.08 MVA) X/R: 7.21

VOLTAGE: 12000. EQUIV. IMPEDANCE= 0.1384 + J 0.9829 OHMS

CONTRIBUTIONS: BUS: 1_US-7-1 6.980 KA ANG: -81.99

GENERATOR NAME -- AT BUS -- KA VOLTS PU LOCAL/REMOTE

UTIL: 1_SCE-2 6.049 0.09 R

GEN: 1_12KV 0.931 0.09 L

TOTAL REMOTE: 6.049 KA NACD RATIO: 0.8666

SYM2 SYM3 SYM5 SYM8

MULT. FACT: 1.000 1.000 1.000 1.000

DUTY (KA) : 6.980 6.980 6.980 6.980

TOT2 TOT3 TOT5 TOT8

MULT. FACT: 1.120 1.012 1.000 1.000

DUTY (KA) : 7.817 7.062 6.980 6.980

Mar 27, 2018 06:01:11 UNBALANCED INTERRUPTING DUTY PAGE 1

U N B A L A N C E D I N T E R R U P T I N G D U T Y R E P O R T

MODEL TRANSFORMER TAPS: NO

NACD OPTION: INTERPOLATED

LOCATION FAULT E/Z X/R ANSI AC/DC INTERRUPTING

TYPE KA DECREMENT FACT. DUTIES (KA)

3 PHASE SLG 3 PHASE SLG

BUS: 1_SW US-1A West 3P Duty: 7.16 8.5 SYM2: 1.00 1.00 7.16 2.31

VOLTS: 12000.0 SLG: 2.31 11.6 SYM3: 1.00 1.00 7.16 2.31

NACD: 0.867 LN/LN: 6.20 SYM5: 1.00 1.00 7.16 2.31

LN/LN/GND: 6.21 SYM8: 1.00 1.01 7.17 2.35

GND RETURN: 1.38 TOT2: 1.16 1.25 8.33 2.90

Z1(PU): 0.67184 TOT3: 1.03 1.09 7.39 2.51

Z2(PU): 0.67184 TOT5: 1.00 1.03 7.16 2.37

Z0(PU): 4.89652 TOT8: 1.00 1.00 7.16 2.31

BUS: 1_SW US-1B West 3P Duty: 7.15 8.4 SYM2: 1.00 1.00 7.15 2.31

VOLTS: 12000.0 SLG: 2.31 11.4 SYM3: 1.00 1.00 7.15 2.31

NACD: 0.867 LN/LN: 6.19 SYM5: 1.00 1.00 7.15 2.31

LN/LN/GND: 6.20 SYM8: 1.00 1.01 7.16 2.34

GND RETURN: 1.38 TOT2: 1.16 1.25 8.30 2.89

Z1(PU): 0.67294 TOT3: 1.03 1.08 7.37 2.51

Z2(PU): 0.67294 TOT5: 1.00 1.02 7.15 2.37

Z0(PU): 4.89899 TOT8: 1.00 1.00 7.15 2.31

BUS: 1_SW US-2A East 3P Duty: 7.41 11.8 SYM2: 1.00 1.00 7.41 2.35

VOLTS: 12000.0 SLG: 2.35 15.9 SYM3: 1.00 1.00 7.41 2.36

NACD: 0.867 LN/LN: 6.41 SYM5: 1.00 1.01 7.41 2.37

LN/LN/GND: 6.43 SYM8: 1.02 1.05 7.52 2.47

GND RETURN: 1.40 TOT2: 1.26 1.35 9.30 3.19

Z1(PU): 0.64961 TOT3: 1.09 1.17 8.06 2.76

Z2(PU): 0.64961 TOT5: 1.02 1.08 7.59 2.54

Z0(PU): 4.83288 TOT8: 1.00 1.03 7.41 2.42

BUS: 1_SW US-2B East 3P Duty: 7.40 11.6 SYM2: 1.00 1.00 7.40 2.35

VOLTS: 12000.0 SLG: 2.35 15.7 SYM3: 1.00 1.00 7.40 2.35

NACD: 0.867 LN/LN: 6.41 SYM5: 1.00 1.01 7.40 2.37

LN/LN/GND: 6.42 SYM8: 1.01 1.05 7.50 2.46

GND RETURN: 1.40 TOT2: 1.25 1.35 9.26 3.18

Z1(PU): 0.65040 TOT3: 1.09 1.17 8.03 2.75

Z2(PU): 0.65040 TOT5: 1.02 1.08 7.57 2.53

Z0(PU): 4.83576 TOT8: 1.00 1.02 7.40 2.41

Mar 27, 2018 06:01:11 UNBALANCED INTERRUPTING DUTY PAGE 2

MODEL TRANSFORMER TAPS: NO

NACD OPTION: INTERPOLATED

LOCATION FAULT E/Z X/R ANSI AC/DC INTERRUPTING

TYPE KA DECREMENT FACT. DUTIES (KA)

3 PHASE SLG 3 PHASE SLG

BUS: 1_SW US-3A West 3P Duty: 7.08 8.0 SYM2: 1.00 1.00 7.08 2.30

VOLTS: 12000.0 SLG: 2.30 10.9 SYM3: 1.00 1.00 7.08 2.30

NACD: 0.867 LN/LN: 6.13 SYM5: 1.00 1.00 7.08 2.30

LN/LN/GND: 6.14 SYM8: 1.00 1.01 7.08 2.32

GND RETURN: 1.37 TOT2: 1.15 1.24 8.12 2.84

Z1(PU): 0.67995 TOT3: 1.02 1.07 7.25 2.47

Z2(PU): 0.67995 TOT5: 1.00 1.02 7.08 2.34

Z0(PU): 4.91950 TOT8: 1.00 1.00 7.08 2.30

BUS: 1_SW US-3B West 3P Duty: 7.07 8.0 SYM2: 1.00 1.00 7.07 2.30

VOLTS: 12000.0 SLG: 2.30 10.8 SYM3: 1.00 1.00 7.07 2.30

NACD: 0.867 LN/LN: 6.12 SYM5: 1.00 1.00 7.07 2.30

LN/LN/GND: 6.13 SYM8: 1.00 1.01 7.07 2.32

GND RETURN: 1.37 TOT2: 1.15 1.23 8.09 2.84

Z1(PU): 0.68084 TOT3: 1.02 1.07 7.23 2.46

Z2(PU): 0.68084 TOT5: 1.00 1.02 7.07 2.33

Z0(PU): 4.92202 TOT8: 1.00 1.00 7.07 2.30

BUS: 1_SW US-4A East 3P Duty: 7.48 12.7 SYM2: 1.00 1.00 7.48 2.37

VOLTS: 12000.0 SLG: 2.37 17.2 SYM3: 1.00 1.02 7.48 2.41

NACD: 0.867 LN/LN: 6.48 SYM5: 1.00 1.02 7.48 2.41

LN/LN/GND: 6.50 SYM8: 1.02 1.06 7.65 2.51

GND RETURN: 1.41 TOT2: 1.28 1.38 9.57 3.25

Z1(PU): 0.64287 TOT3: 1.11 1.19 8.29 2.82

Z2(PU): 0.64287 TOT5: 1.03 1.09 7.74 2.59

Z0(PU): 4.81387 TOT8: 1.00 1.04 7.49 2.46

BUS: 1_SW US-4B East 3P Duty: 7.47 12.5 SYM2: 1.00 1.00 7.47 2.36

VOLTS: 12000.0 SLG: 2.36 17.0 SYM3: 1.00 1.01 7.47 2.40

NACD: 0.867 LN/LN: 6.47 SYM5: 1.00 1.02 7.47 2.40

LN/LN/GND: 6.49 SYM8: 1.02 1.06 7.63 2.50

GND RETURN: 1.40 TOT2: 1.27 1.37 9.53 3.24

Z1(PU): 0.64366 TOT3: 1.10 1.19 8.26 2.81

Z2(PU): 0.64366 TOT5: 1.03 1.09 7.72 2.58

Z0(PU): 4.81674 TOT8: 1.00 1.04 7.47 2.45

Mar 27, 2018 06:01:11 UNBALANCED INTERRUPTING DUTY PAGE 3

MODEL TRANSFORMER TAPS: NO

NACD OPTION: INTERPOLATED

LOCATION FAULT E/Z X/R ANSI AC/DC INTERRUPTING

TYPE KA DECREMENT FACT. DUTIES (KA)

3 PHASE SLG 3 PHASE SLG

BUS: 1_SW US-5A East 3P Duty: 7.47 12.4 SYM2: 1.00 1.00 7.47 2.36

VOLTS: 12000.0 SLG: 2.36 16.8 SYM3: 1.00 1.01 7.47 2.39

NACD: 0.867 LN/LN: 6.47 SYM5: 1.00 1.02 7.47 2.40

LN/LN/GND: 6.49 SYM8: 1.02 1.06 7.62 2.50

GND RETURN: 1.40 TOT2: 1.27 1.37 9.50 3.23

Z1(PU): 0.64417 TOT3: 1.10 1.19 8.23 2.80

Z2(PU): 0.64417 TOT5: 1.03 1.09 7.70 2.57

Z0(PU): 4.81820 TOT8: 1.00 1.04 7.47 2.45

BUS: 1_SW US-5B East 3P Duty: 7.46 12.2 SYM2: 1.00 1.00 7.46 2.36

VOLTS: 12000.0 SLG: 2.36 16.6 SYM3: 1.00 1.01 7.46 2.38

NACD: 0.867 LN/LN: 6.46 SYM5: 1.00 1.01 7.46 2.39

LN/LN/GND: 6.48 SYM8: 1.02 1.05 7.59 2.49

GND RETURN: 1.40 TOT2: 1.27 1.36 9.45 3.22

Z1(PU): 0.64524 TOT3: 1.10 1.18 8.19 2.79

Z2(PU): 0.64524 TOT5: 1.03 1.09 7.67 2.56

Z0(PU): 4.82057 TOT8: 1.00 1.03 7.46 2.44

BUS: 1_SW US-6 East 3P Duty: 7.46 12.2 SYM2: 1.00 1.00 7.46 2.36

VOLTS: 12000.0 SLG: 2.36 16.5 SYM3: 1.00 1.01 7.46 2.38

NACD: 0.867 LN/LN: 6.46 SYM5: 1.00 1.01 7.46 2.39

LN/LN/GND: 6.48 SYM8: 1.02 1.05 7.59 2.49

GND RETURN: 1.40 TOT2: 1.27 1.36 9.44 3.22

Z1(PU): 0.64533 TOT3: 1.10 1.18 8.18 2.79

Z2(PU): 0.64533 TOT5: 1.03 1.08 7.67 2.56

Z0(PU): 4.82146 TOT8: 1.00 1.03 7.46 2.44

SWGR: 1_NORTH 3P Duty: 7.50 13.0 SYM2: 1.00 1.00 7.50 2.37

VOLTS: 12000.0 SLG: 2.37 17.6 SYM3: 1.00 1.02 7.50 2.42

NACD: 0.867 LN/LN: 6.49 SYM5: 1.00 1.02 7.50 2.42

LN/LN/GND: 6.51 SYM8: 1.02 1.06 7.68 2.52

GND RETURN: 1.41 TOT2: 1.29 1.38 9.65 3.27

Z1(PU): 0.64153 TOT3: 1.11 1.20 8.36 2.84

Z2(PU): 0.64153 TOT5: 1.04 1.10 7.78 2.60

Z0(PU): 4.81074 TOT8: 1.00 1.04 7.52 2.47

Mar 27, 2018 06:01:11 UNBALANCED INTERRUPTING DUTY PAGE 4

MODEL TRANSFORMER TAPS: NO

NACD OPTION: INTERPOLATED

LOCATION FAULT E/Z X/R ANSI AC/DC INTERRUPTING

TYPE KA DECREMENT FACT. DUTIES (KA)

3 PHASE SLG 3 PHASE SLG

SWGR: 1_SOUTH 3P Duty: 7.50 13.0 SYM2: 1.00 1.00 7.50 2.37

VOLTS: 12000.0 SLG: 2.37 17.6 SYM3: 1.00 1.02 7.50 2.42

NACD: 0.867 LN/LN: 6.49 SYM5: 1.00 1.02 7.50 2.42

LN/LN/GND: 6.51 SYM8: 1.02 1.06 7.68 2.52

GND RETURN: 1.41 TOT2: 1.29 1.38 9.65 3.27

Z1(PU): 0.64160 TOT3: 1.11 1.20 8.35 2.84

Z2(PU): 0.64160 TOT5: 1.04 1.10 7.78 2.60

Z0(PU): 4.81027 TOT8: 1.00 1.04 7.52 2.47

SWGR: 1_US-7 3P Duty: 6.98 7.2 SYM2: 1.00 1.00 6.98 2.28

VOLTS: 12000.0 SLG: 2.28 9.7 SYM3: 1.00 1.00 6.98 2.28

NACD: 0.867 LN/LN: 6.04 SYM5: 1.00 1.00 6.98 2.28

LN/LN/GND: 6.05 SYM8: 1.00 1.00 6.98 2.29

GND RETURN: 1.36 TOT2: 1.12 1.21 7.82 2.75

Z1(PU): 0.68929 TOT3: 1.01 1.05 7.06 2.40

Z2(PU): 0.68929 TOT5: 1.00 1.01 6.98 2.30

Z0(PU): 4.94632 TOT8: 1.00 1.00 6.98 2.28

Mar 27, 2018 06:01:11 UNBALANCED INTERRUPTING DUTY PAGE 5

I N T E R R U P T I N G D U T Y S U M M A R Y R E P O R T

MODEL TRANSFORMER TAPS: NO

NACD OPTION: INTERPOLATED

BUS RECORD VOLTAGE NACD * 3 P H A S E * * * * S L G * * *

NO NAME L-L RATIO E/Z KA X/R E/Z KA X/R

BUS: 1_SW US-1A West 12000. 0.867 7.161 8.52 2.313 11.56 BUS: 1_SW US-1B West 12000. 0.867 7.150 8.43 2.312 11.43 BUS: 1_SW US-2A East 12000. 0.867 7.406 11.76 2.354 15.92 BUS: 1_SW US-2B East 12000. 0.867 7.397 11.60 2.352 15.70 BUS: 1_SW US-3A West 12000. 0.867 7.076 8.04 2.299 10.88

BUS: 1_SW US-3B West 12000. 0.867 7.067 7.97 2.297 10.79 BUS: 1_SW US-4A East 12000. 0.867 7.484 12.74 2.366 17.24 BUS: 1_SW US-4B East 12000. 0.867 7.475 12.55 2.365 16.98 BUS: 1_SW US-5A East 12000. 0.867 7.469 12.43 2.364 16.83 BUS: 1_SW US-5B East 12000. 0.867 7.456 12.22 2.362 16.55

BUS: 1_SW US-6 East 12000. 0.867 7.455 12.19 2.362 16.51

SWGR: 1_NORTH 12000. 0.867 7.500 13.04 2.369 17.63

SWGR: 1_SOUTH 12000. 0.867 7.499 13.04 2.369 17.64

SWGR: 1_US-7 12000. 0.867 6.980 7.21 2.282 9.74

43 FAULTED BUSES, 58 BRANCHES, 2 CONTRIBUTIONS

UNBALANCED FAULTS REQUESTED