A-501
F1
TYP.
A-600
C6
10' - 14"Ø STEEL PIPE
10' X 2'2"
ACCESS
DOOR
10' X 2'2"
ACCESS
DOOR
CPI CANOPY (OR
APPROVED EQUAL)
1-5/8" unistrut, typical6"x4"x3/8" HSS
10"x10"x3/8" HSS
OPEN ACCESS DOOR
10' X 2'2"
ACCESS
DOOR
10' X 2'2"
ACCESS
DOOR
1-5/8"
UNISTRUT,
TYPICAL
6"x4"x3/8" HSS
10"x10"x3/8" HSS
LIGHT FIXTURE AT 20'-0"
6"x4"x3/8"
HSS, BEYOND
FORKLIFT AND CANOPY
DOORS
FORKLIFT FITS BETWEEN
CANOPY AND UP TO FIRST
DUCTBANK
FORKLIFT MOVES TOWARDS
CANOPY AND PLACES PIPE IN
DUCTBANK
FORKLIFT FITS BETWEEN
CANOPY AND UP TO THE
SECOND DUCTBANK
FORKLIFT MOVES TOWARDS
CANOPY AND PLACES PIPE IN
DUCTBANK
SECTION VIEW(S)SPAN
12'-0"
1'-0"
SIDEWALK
10'-0" 1'-0"
ELEVATION VIEW(S)
T Y
P
2' -2
10'-0"
10' X 1'6"
ACCESS
DOOR
A-501
F1
CPI CANOPY (OR
APPROVED EQUAL)
10' X 1'6"
ACCESS
DOOR
'-2
T
O P
O F
C A
N O
P Y
SPAN
12'-0"
R 10'-0"
1'-0" 1'-0" 1'-0"
1'-0"
1'-0"
1'-0"
SIDEWALK
10'-0" 1'-0"
14" CHR
14" CHS
4"6"
8"
3"
2' -2
'-1
0" B
O T
T O
M O
F P
IP
E
D U
C T
'-2
B
O T
T O
M O
F P
IP
E
D U
C T
'-6
T
O P
O F
S T
E E
L
1'-5 1/2"
1/
2"
A-503
E5
A-503
E5
OPPOSITE
HAND
A-503
F6
A-503
F6
A-503
E6
A-502
D4
2" 9 1/2" 3'-2 1/2" 5'-7" 4'-0"
2' -2
1"
KEYED NOTES - (N) DUCTBANK - UNSUPPORTED ROOF STRUCTURE (ADD ALT. NO. 3)
CANOPY: 10'-0" RADIUS, 90°, CENTERED AT 45°, TRANSLUCENT ROOF PANEL SYSTEM1
ACCESS DOOR (TYPE 2), SEE F5/A-501
HSS STRUCTURAL FRAMING, SEE STRUCTURAL DRAWINGS
4 1-5/8" X 1-5/8" UNISTRUT P1000, OR APPROVED EQUAL, TYP.
5 PIPE GUIDE
6 PIPE INSULATION VARIES, SEE SPECIFICATIONS
METAL PANEL WALL SYSTEM WITH ACCESS DOORS W/ AUTO PRESSURE SWITCH
TO ACTUATE DUCTBANK INTERIOR LIGHTNG
CEILING SYSTEM: 24" X 24" STD TORSION SPRING PANEL (7210) ON
1-5/8" X 1-5/8" UNISTRUT P1000, OR APPROVED EQUAL, TYP.
LIGHT FIXTURE CENTERED IN TILE, WHERE OCCURS
FUTURE 6" FIRE WATER AND 4" FIRE SPRINKLER12
FUTURE 8" HPS SLOPED AT 1/4"/5', 3" AND 1-1/4" PUMPED CONDENSATE, SLOPE 1/8"/5'13
14 2" OXYGEN
ELECTRICAL AND COMMUNICATIONS INCLUDING FIRE ALARM AND SECURITY: (2) 4" OD
INNERDUCTS, (3) 2" OD INNERDUCTS
1'-0"TYP.
7 METAL PANEL WALL SYSTEM, DRY SEAL WALL SYSTEM
4 7
15 COLUMN PROFILE
3 3
A-503
C6 A-503
C6
3 3
'-0
C
E
IL
IN
G
H E
IG
H
T
3"
1' -1
1" 2'
-8
2' -8
1' -6
SIM
SIM
A-503
F5
OPPOSITE
HAND
SIM
A-503
F5
OPPOSITE
HAND
BBQ AREA
2' -6
'-0
CEILING
FLOORø 2'-0"
STEEL COLUMN PER STRUCTURAL
ARCHITECTURAL CONCRETE COLUMN
TOP OF FOOTING
SEE SHEET A-503
D U
C
TB
A N
K
4' -0
EQ 2'-0" 2'-0" 2'-0"
2'-0"
2'-0" 2'-0" EQ
COMMON PIPE LENGTH
10'-0"
ACCESS DOOR PANEL
10'-0"
ACCESS DOOR PANEL
10'-0"
R 55"
R 4'-7"
2' -2
FORKLIFT MINIMUM
OUTSIDE TURN
RADIUS
O P
E N
T O
R O
O F
5' -7
INTERMEDIATE PIPE SUPPORT
SOILDER SHAPED
STONE VENEER
COLUMN
SEE SHEET A-502
DRIP
9' -8
4"
'-0
1' -3
1'-5" 1'-5 1/2" 1 1/2"
3'-0"
2'-0
4" CURB
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
Drawing number
Drawn
Building Number
Location
Project Title
Date
Project Number
Checked by
Drawing Title
Approved : Project Director
1 2 3 4 5 6
F
E
D
C
B
A
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
PROJECT TEAM ARCHITECTS/ENGINEERS Office of Construction and Facilities Management
Department of Veterans Affairs
7 8 9
TRIPLE C - THE A-E GROUP
4401 ATLANTIC AVE. SUITE 200
LONG BEACH, CA 90807
CONTACT: DAVID POTTER
PHONE: 307 460-2054
ISSUED FOR CONSTRUCTION
BRIDGERS & PAXTON CONSULTING ENGINEERS, INC.
1839 S. ALMA SCHOOL ROAD, SUITE 300
MESA, AZ 85210
CONTACT: JOHN MONTANO
PHONE: 602 336-5415
UNITED STRUCTURAL DESIGN, LLC
720 W. COMMERCE AVE OR P.O. BOX 33245
GILBERT, AZ 85233 PHOENIX, AZ 85067
CONTACT: DAVID GRAPSAS
PHONE: 480 382-9768
B
IM
0-
-3
V A
F re sn o
C hi lle r
P la nt P
/5
-1
6-
V
A F re sn o C hi lle r P la nt
-O P
T 4A
.rv t
4/
/2
2:
:1
P
M
A-501
ARCHITECTURAL DETAILS
M. PERKINS D. YOUNG02/07/2018
570-16-302DESIGN EXPANDED CHILLED
WATER CAPACITY, PHASE 2
100% CONSTRUCTION DOCUMENTS
SUBMISSION
2615 E Clinton Ave, Fresno, CA 93703
A. CONTRACTOR TO COORDINATE WITH ROOF INSTALLATION WARRANTY
REQUIREMENTS FOR ANY MODIFICATIONS TO ROOFING TO ENSURE NO
VIOLATIONS OCCUR OF THE WARRANTY. CONTRACTOR TO EMPLOY A
CERTIFIED ROOFING INSPECTOR MEETING THE REQUIREMENTS OF THE
INSTALLED ROOF. ALL WARRANTY VIOLATIONS WILL BE REQUIRED TO
BE CORRECTED PRIOR TO CLOSE OUT. ROOFS AND/OR ROOFING
IMPACTED BY WORK INCLUDE, AND MAY NOT BE LIMITED TO: B1, B3,
B22, B24 & B31.
B. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR
SMOKE RATED WALLS AND ASSEMBLIES INDICATED ON PLANS IN
WORK AREA. PROVIDE ALL PIPING PENETRATIONS OF FIRE, SMOKE
AND FULL HEIGHT WALLS SHALL BE CAULKED AIRTIGHT TO THE
ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF
CAULKING MATERIAL. SEE MECHANICAL AND PLUMBING DRAWINGS
FOR ADDITIONAL INFORMATION.
C. CONTRACTOR SHALL COORDINATE ALL PIPING, PLUMBING, AND
CONDUIT PIPING WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL
SYSTEMS AND SHALL PROVIDE NECESSARY OFFSETS TO AVOID
CONFLICTS AND TO MAINTAIN REQUIRED EQUIPMENT ACCESS AND
SERVICEABILITY.
D. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD
VERIFICATION WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER
FROM THOSE INDICATED. CONTRACTOR TO FIELD VERIFY IN ADVANCE
THE LOCATION AND CONDITION OF THOSE EXISTING SYSTEMS SHOWN
TO BE MODIFIED OR REMOVED. CONTRACTOR TO NOTIFY ARCHITECT
SHOULD CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY FROM
CONSTRUCTION DOCUMENTS.
E. CONTRACTOR TO COORDINATE ALL NEW EQUIPMENT LOCATIONS WITH
ALL TRADES PRIOR TO INSTALLATION.
F. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT
CONNECTIONS BETWEEN ALL DISSIMILAR METALS.
G. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED
TO COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND
PAINT AND RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.
H. CONTRACTOR TO PROVIDE ESCUTCHEONS ON ALL NEW EXPOSED
EXTERIOR PIPE PENETRATIONS AND SEAL COMPLETELY.
I. CONTRACTOR TO PROVIDE TEMPORARY COVERED ACCESSIBLE
PATHWAY PRIOR TO PHASE 1 INTEGRATED SYSTEMS CANOPY
CONSTRUCTION AND/OR DEMOLITION. AN ACCESSIBLE BED ROUTE IS
REQUIRED TO BE MAINTAINED AT ALL TIMES BETWEEN BUILDINGS.
J. ANY LANDSCAPE, HARDSCAPE, FIXTURE, SIGNAGE AND SYSTEMS OR
PEDESTRIAN CONTROL DEVICES WITHIN THE TEMPORARY ACCESSIBLE
PATHWAY SHALL BE PROTECTED IN PLACE OR TEMPORARILY
RELOCATED AS NECESSARY FOR CONTINUED UNINTERRUPTED
OPERATION, ACCESS, MAINTENANCE AND / OR VISIBILITY.
GENERAL SHEET NOTES
1/4" = 1'-0" C5
FORKLIFT ILLUSTRATION SECTIONS AND ELEVATIONS
3/4" = 1'-0" F1
DETAIL - (N) DUCTBANK - SELF SUPPORTED ROOF STRUCTURE
NTS
D7
DETAIL - COLUMN TYPE 2
1/4" = 1'-0" F5
FORKLIFT ILLUSTRATION PLAN
NTS
D6
DETAIL - COLUMN TYPE 1
N O R T H
F R E S N O
S T R E E T
EAST HARVARD AVENUE
N O R T H
A N G U S
S T R E E T
EAST CLINTON AVENUE
TANK
O2
TANK
O2
KEY PLAN
P3 B31
B3
B32
B24
B25
B2
B22A
B1
OPC
B27
B34
B
B19& B19A
NO REVISIONS DATE
Expires 6.30.16Expires: 6/30/18
2/7/2018
'-2
T
O P
O F
C A
N O
P Y
SPAN
12'-0"
R 10'-0"
1'-0"
SIDEWALK
10'-0" 1'-0"
14" CHR
14" CHS
4"6"
8"
3"
2' -2
'-1
0" B
O T
T O
M O
F P
IP
E
D U
C T
'-2
B
O T
T O
M O
F P
IP
E
D U
C T
'-6
T
O P
O F
S T
E E
L
1'-5 1/2"
1/
2"
SIM
A-503.1
F5
A-503.1
D1
A-503.1
D1
OPPOSITE
HAND
A-503
F6
A-503
F6
A-503
E6
A-502
D4
9 1/2" 3'-2 1/2" 5'-7" 4'-0"
2' -2
1"
KEYED NOTES - (N) DUCTBANK - SUPPORTED ROOF STRUCTURE (BASE BID)
CANOPY: 10'-0" RADIUS, 90°, CENTERED AT 45°, TRANSLUCENT ROOF PANEL SYSTEM1
ACCESS DOOR, SEE F5/A-501 AND A-600
HSS STRUCTURAL FRAMING, SEE STRUCTURAL DRAWINGS
4 1-5/8" X 1-5/8" UNISTRUT P1000, OR APPROVED EQUAL, TYP.
5 PIPE GUIDE
6 PIPE INSULATION VARIES, SEE SPECIFICATIONS
CEILING SYSTEM: 24" X 24" STD TORSION SPRING PANEL (7210)
ON 1-5/8" X 1-5/8" UNISTRUT P1000, OR APPROVED EQUAL, TYP.
LIGHT FIXTURE CENTERED IN TILE, WHERE OCCURS
FUTURE 6" FIRE WATER AND 4" FIRE SPRINKLER12
FUTURE 8" HPS SLOPED AT 1/4"/5', 3" AND 1-1/4" PUMPED CONDENSATE, SLOPE 1/8"/5'13
14 2" OXYGEN
ELECTRICAL AND COMMUNICATIONS INCLUDING FIRE ALARM AND SECURITY: (2) 4" OD
INNERDUCTS, (3) 2" OD INNERDUCTS
7 METAL PANEL WALL SYSTEM, DRY SEAL WALL SYSTEM
15 COLUMN PROFILE
3 3
A-503.1
D6 A-503.1
D6
3 3
'-0
C
E
IL
IN
G
H E
IG
H
T
3"
1' -1
1" 2'
-8
2' -8
1' -6
SIM
A-503
F5
OPPOSITE
HAND
OPPOSITE
HAND
SIM
A-503
F5
OPPOSITE
HAND
SIM
F1
A-503.1
SIM
F1
A-503.1
OPPOSITE
HAND
METAL PANEL WALL SYSTEM WITH ACCESS DOORS AND PUSH BUTTON SWITCH TO
ACTUATE DUCTBANK INTERIOR LIGHTNG
1/
2"
16 CONTINUOUS ANGLE BETWEEN RAFTERS CONNECTED TO UNISTRUT FRAMING, FLASHED
TO METAL PANEL, BY CANOPY MANUFACTURER
17 CONTINUOUS FASCIA FLASHING ATTACHED TO CANOPY, BY CANOPY MANUFACTURER
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
Drawing number
Drawn
Building Number
Location
Project Title
Date
Project Number
Checked by
Drawing Title
Approved : Project Director
1 2 3 4 5 6
F
E
D
C
B
A
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
PROJECT TEAM ARCHITECTS/ENGINEERS Office of Construction and Facilities Management
Department of Veterans Affairs
7 8 9
TRIPLE C - THE A-E GROUP
4401 ATLANTIC AVE. SUITE 200
LONG BEACH, CA 90807
CONTACT: DAVID POTTER
PHONE: 307 460-2054
ISSUED FOR CONSTRUCTION
BRIDGERS & PAXTON CONSULTING ENGINEERS, INC.
1839 S. ALMA SCHOOL ROAD, SUITE 300
MESA, AZ 85210
CONTACT: JOHN MONTANO
PHONE: 602 336-5415
UNITED STRUCTURAL DESIGN, LLC
720 W. COMMERCE AVE OR P.O. BOX 33245
GILBERT, AZ 85233 PHOENIX, AZ 85067
CONTACT: DAVID GRAPSAS
PHONE: 480 382-9768
B
IM
0-
-3
V A
F re sn o
C hi lle r
P la nt P
/5
-1
6-
V
A F re sn o C hi lle r P la nt
-O P
T 4A
.rv t
4/
/2
2:
:2
P
M
A-501.1
ARCHITECTURAL DETAILS
Checker Author02/07/2018
570-16-302DESIGN EXPANDED CHILLED
WATER CAPACITY, PHASE 2
100% CONSTRUCTION DOCUMENTS
SUBMISSION
2615 E Clinton Ave, Fresno, CA 93703
A. CONTRACTOR TO COORDINATE WITH ROOF INSTALLATION WARRANTY
REQUIREMENTS FOR ANY MODIFICATIONS TO ROOFING TO ENSURE NO
VIOLATIONS OCCUR OF THE WARRANTY. CONTRACTOR TO EMPLOY A
CERTIFIED ROOFING INSPECTOR MEETING THE REQUIREMENTS OF THE
INSTALLED ROOF. ALL WARRANTY VIOLATIONS WILL BE REQUIRED TO
BE CORRECTED PRIOR TO CLOSE OUT. ROOFS AND/OR ROOFING
IMPACTED BY WORK INCLUDE, AND MAY NOT BE LIMITED TO: B1, B3,
B22, B24 & B31.
B. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR
SMOKE RATED WALLS AND ASSEMBLIES INDICATED ON PLANS IN
WORK AREA. PROVIDE ALL PIPING PENETRATIONS OF FIRE, SMOKE
AND FULL HEIGHT WALLS SHALL BE CAULKED AIRTIGHT TO THE
ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF
CAULKING MATERIAL. SEE MECHANICAL AND PLUMBING DRAWINGS
FOR ADDITIONAL INFORMATION.
C. CONTRACTOR SHALL COORDINATE ALL PIPING, PLUMBING, AND
CONDUIT PIPING WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL
SYSTEMS AND SHALL PROVIDE NECESSARY OFFSETS TO AVOID
CONFLICTS AND TO MAINTAIN REQUIRED EQUIPMENT ACCESS AND
SERVICEABILITY.
D. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD
VERIFICATION WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER
FROM THOSE INDICATED. CONTRACTOR TO FIELD VERIFY IN ADVANCE
THE LOCATION AND CONDITION OF THOSE EXISTING SYSTEMS SHOWN
TO BE MODIFIED OR REMOVED. CONTRACTOR TO NOTIFY ARCHITECT
SHOULD CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY FROM
CONSTRUCTION DOCUMENTS.
E. CONTRACTOR TO COORDINATE ALL NEW EQUIPMENT LOCATIONS WITH
ALL TRADES PRIOR TO INSTALLATION.
F. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT
CONNECTIONS BETWEEN ALL DISSIMILAR METALS.
G. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED
TO COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND
PAINT AND RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.
H. CONTRACTOR TO PROVIDE ESCUTCHEONS ON ALL NEW EXPOSED
EXTERIOR PIPE PENETRATIONS AND SEAL COMPLETELY.
I. CONTRACTOR TO PROVIDE TEMPORARY COVERED ACCESSIBLE
PATHWAY PRIOR TO PHASE 1 INTEGRATED SYSTEMS CANOPY
CONSTRUCTION AND/OR DEMOLITION. AN ACCESSIBLE BED ROUTE IS
REQUIRED TO BE MAINTAINED AT ALL TIMES BETWEEN BUILDINGS.
J. ANY LANDSCAPE, HARDSCAPE, FIXTURE, SIGNAGE AND SYSTEMS OR
PEDESTRIAN CONTROL DEVICES WITHIN THE TEMPORARY ACCESSIBLE
PATHWAY SHALL BE PROTECTED IN PLACE OR TEMPORARILY
RELOCATED AS NECESSARY FOR CONTINUED UNINTERRUPTED
OPERATION, ACCESS, MAINTENANCE AND / OR VISIBILITY.
GENERAL SHEET NOTES
N O R T H
F R E S N O
S T R E E T
EAST HARVARD AVENUE
N O R T H
A N G U S
S T R E E T
EAST CLINTON AVENUE
TANK
O2
TANK
O2
KEY PLAN
P2P3 B31
B3
B32 P1
ADD- ALT.
B24
B25
B2
B22A
B1
OPC
B27
B34
B
B19& B19A
3/4" = 1'-0" F4
DETAIL - (N) DUCTBANK - SUPPORTED ROOF STRUCTURE
NO REVISIONS DATE
STONE VENEER FINISH SYSTEM
ON EXTERIOR SHEATHING ON 6"
METAL STUD FRAMING, TYPICAL
BASIS OF DESIGN IS CORONADO
STONE BLACK RIVER TO MATCH
EXISTING STONE VENEER ON
CAMPUS
4" HIGH CONCRETE CURB
TUBE STEEL COLUMN, SEE
STRUCTURAL DRAWINGS
DRIP
2'-10 1/2"
1'-5" 1'-5 1/2" 1 1/2"
2'-0"
C E
IL
IN
G H
E
IG
H T
'-0
11"
SLOPE
10'-0" / 1'-0"
SLOPE 9"/
1'-0"
A-502
D1
DRIP
2'-10 1/2"
1'-5" 1'-5 1/2" 1 1/2"
11"
SLOPE
10'-0" / 1'-0"
BASE BID DEDUCT ALTERNATE
TUBE STEEL COLUMN, SEE
STRUCTURAL DRAWINGS
CAST-IN-PLACE
CONCRETE COLUMN
DIRECT APPLIED STONE
VENEER FINISH SYSTEM
8 1/2" 10 1/2"
A-502
D3
4"
LE
D
S T
R
IP
L
IG
H T
L
I G H
T T
O
IN
S T
A
LL
V E
R T
IC
A
L
6' -0
LED STRIP LIGHT IN
ALUMINUM CHANNEL WITH
OPAQUE CHANNEL COVER,
CENTERED HORIZONTALLY,
MOUNTED AT EVERY
COLUMN
GROUT BED TO
HOLD CHANNEL
TOE KICK WITH ACCENT
LIGHTING 4" HIGH TOE KICK WITH ACCENT
LIGHTING
SECTION VIEW
BASE BID DEDUCT ALTERNATE
PLAN VIEW
2'-10 1/2"
2'-0"
2' -0
2'-10 1/2"
1'-9"
2' -0
TOP
BASE
2'-10 1/2"
2'-0"
2' -0
2'-10 1/2"
1'-9"
2' -0
BASE
CAST-IN-PLACE
CONCRETE COLUMN,
2" MIN COVERAGE
DIRECT APPLIED STONE
VENEER FINISH SYSTEM
STONE VENEER FINISH SYSTEM
ON EXTERIOR SHEATHING ON 6"
METAL STUD FRAMING, TYPICAL
1'-0" 1'-0"
TUBE STEEL COLUMN, SEE
STRUCTURAL
M
IN
5"
2" MIN.
TOP
1' -3
SLOPE 9"/
1'-0"
PATHWAY LIGHTING
STAGGERED EACH SIDE
AT BASE OF COLUMNS
RETAINING WALL AND
FOUNDATION, WHERE
OCCURS, SEE
STRUCTURAL SHEET
S-501 DRAWING F4
STONE VENEER
WALL SYSTEM
DIRECT APPLIED TO
CONCRETE
RETAINING WALL
4' -0
A
T S
E A
T W
A
LL
2' -0
A
T R
E T
A
IN
IN
G
W A
LL
ALIGN FACE OF STONE
VENEER WITH COLUMN,
BEYOND
PATHWAY LIGHTING AT SEAT
WALL BASE, REFER TO
ELECTRICAL FOR LOCATIONS
TOE KICK WITH ACCENT
LIGHTING
SIDEWALK SECTION VIEWA-502
D1
A-502
F3
4" M
IN
V A
R
IE
S
ROUND EDGES
1/2" RADIUS
6 1/2"
CONCRETE CURB
DIRECT APPLIED MASONRY
VENEER
METAL MESH ON VAPOR BARRIER
WEEP
EXTERIOR SHEATHING
ON METAL STUD
FRAMING
SCREED
BASE FLASHING
ROPE LIGHTING UNDER
BASE FLASHING
3"
SECTION VIEW
1" FLASHING TRANSITION
EXTEND MIN. 1" BELOW
TOP OF FOUNDATION
LAP MESH AND BARRIER OVER SILL
SCREED FLANGE
LAP DRIP FLASHING OVER
VERTICAL SURFACE
LAP METAL MESH AND VAPOR
BARRIER OVER FLASHING
SECTION VIEW
FIBERGLAS EXTERIOR
SHEATHING OR EQUAL
BASE BID - DIRECT APPLIED
MASONRY VENEER ON
CAST-IN-PLACE CONCRETE
COLUMN
DEDUCTIVE ALT. - METAL
LATH ON VAPOR
BARRIER ON EXTERIOR
SHEATHING ON METAL
STUD FRAMING
BASE BID - METAL PANEL
ACCESS DOORS ON METAL
FRAMING
EXTERIOR STONE VENEER METAL ACCESS PANEL
(INTERIOR)
CONTINUOUS CONCEALED
PIANO HINGE
PANEL LATCH, 3 PER PANEL
WALL
1" X 2" BOX MOLDING
2' X 2' STANDARD
TORSION SPRING
PANEL
1.50" SPEADER
HOLD DOWN
7301TS (MAIN BEAM
SLOTTED 6" O.C.)
3"
METAL PANEL CEILINGBUILT-UP ROOF SYSTEM
4" CANT STRIP,
4" MN LAP
3 LAYERS SINGLE PLY
MEMBRANE ON COLD
APPLIED MASTIC UNDER
VERTICAL MEMBRANES
COVER BOARD AND
CONTINUOUS FELT
UNDERLAYMENT
APPLY MASTIC
OVER INSULATION
FASTENERS
NEW METAL DECK
NEW RIGID INSULATION,
3" MINIMUM
NOTE:
SOLAR REFLECTIVITY
INDEX TO MEET ASHRAE
90.1 AND ENERGY STAR
REQUIREMENTS,
MINIMUM SRI 82.
EXTEND ROOFING TO TOP
OF WALL, BENEATH CAP
EXTERIOR METAL PANEL
SEE SHEET A-600
FOR ADDITIONAL INFORMATION
SEE EXTERIOR ELEVATIONS
FOR ADDITIONAL INFORMATION
SEE THIS SHEET
FOR ADDITIONAL INFORMATION
SEE SHEET A-511
FOR ADDITIONAL INFORMATION
SEE SHEET SERIES 500
FOR ADDITIONAL INFORMATION
SEE STRUCTURAL
DRAWINGS FOR
STEEL FRAMING
1-5/8" X 1-5/8" UNISTRUT
P1000, OR APPROVED
EQUAL, TYP.
EXTERIOR METAL PANEL
(BBQ CANOPY)
SEE EXTERIOR ELEVATIONS
FOR ADDITIONAL INFORMATION
FIRE TREATED PLYWOOD
SHEATHING ON 6" METAL
STUD FRAMING, SEE
STRUCTURAL
METAL PANEL WALL
SYSTEM, DRY SEAL WALL
SYSTEM
METAL PANEL WALL
SYSTEM, DRY SEAL
WALL SYSTEM
2'-6 1/2"
2'-4 1/2"
1/
2"
2"
1" 1/ 2" 3"
8'-0" M
AXVARIES
STONE VENEER TO
OVERLAP PRECAST
ROUNDED EDGE
1/2" RADIUS
MIN
2"
REMOVE FASCIA AND
CUT OVERHANG
REMOVE AND REPLACE
GUTTER AND
DOWNSPOUTS ONTO
NEW CANOPY
EXISTING ENGINEERING
BUILDING TO REMAIN
PATCH AND REPAIR
(E) ROOFING
(E) CANOPY TO BE
REMOVED IN PHASE 2
SEE DETAIL FOR PHASE 2
AND FUTURE CONSTRUCTION
WORK
D6
A-504
LEDGER AND FACE OF
WALL, NEW OR EXISTING
NEW TERMINATION BAR ON 3 LAYERS SINGLE PLY
MEMBRANE ON COLD APPLIED MASTIC OVERLAPPING
HORIZONTAL MEMBRANES
4" CANT STRIP
3 LAYERS SINGLE PLY
MEMBRANE ON COLD
APPLIED MASTIC UNDER
VERTICAL MEMBRANES
CONTINUOUS FELT
UNDERLAYMENT
COVER BOARD
APPLY MASTIC
OVER INSULATION
FASTENERS
NEW METAL DECK
NOTE:
SOLAR REFLECTIVITY INDEX TO
MEET ASHRAE 90.1 AND ENERGY
STAR REQUIREMENTS, MINIMUM
SRI 82.
PARAPET WALL; SIMILAR AT NEW
MASONRY WALL
T Y
P
IC
A L
M
IN
IM
U
M
SEALANT
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
Drawing number
Drawn
Building Number
Location
Project Title
Date
Project Number
Checked by
Drawing Title
Approved : Project Director
1 2 3 4 5 6
F
E
D
C
B
A
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
PROJECT TEAM ARCHITECTS/ENGINEERS Office of Construction and Facilities Management
Department of Veterans Affairs
7 8 9
TRIPLE C - THE A-E GROUP
4401 ATLANTIC AVE. SUITE 200
LONG BEACH, CA 90807
CONTACT: DAVID POTTER
PHONE: 307 460-2054
ISSUED FOR CONSTRUCTION
BRIDGERS & PAXTON CONSULTING ENGINEERS, INC.
1839 S. ALMA SCHOOL ROAD, SUITE 300
MESA, AZ 85210
CONTACT: JOHN MONTANO
PHONE: 602 336-5415
UNITED STRUCTURAL DESIGN, LLC
720 W. COMMERCE AVE OR P.O. BOX 33245
GILBERT, AZ 85233 PHOENIX, AZ 85067
CONTACT: DAVID GRAPSAS
PHONE: 480 382-9768
B
IM
0-
-3
V A
F re sn o
C hi lle r
P la nt P
/5
-1
6-
V
A F re sn o C hi lle r P la nt
-O P
T 4A
.rv t
4/
/2
2:
:3
P
M
A-502
ARCHITECTURAL DETAILS
M. PERKINS L. FALK02/07/2018
570-16-302DESIGN EXPANDED CHILLED
WATER CAPACITY, PHASE 2
100% CONSTRUCTION DOCUMENTS
SUBMISSION
2615 E Clinton Ave, Fresno, CA 93703
1" = 1'-0" D4
DETAIL - TYPICAL TYPE 1 COLUMN
1" = 1'-0"
F1
DETAIL - STONE VENEER SEAT WALL
1 1/2" = 1'-0" D1
DETAIL - TYPICAL COLUMN BASE
1 1/2" = 1'-0"
D3
DETAIL - TYPICAL COLUMN DRIP
1 1/2" = 1'-0" A2
DETAIL - TYPICAL WALL AND SOFFIT ASSEMBLIES
N O R T H
F R E S N O
S T R E E T
EAST HARVARD AVENUE
N O R T H
A N G U S
S T R E E T
EAST CLINTON AVENUE
TANK
O2
TANK
O2
KEY PLAN
P2P3 B31
B3
B32 P1
ADD- ALT.
B24
B25
B2
B22A
B1
OPC
B27
B34
B
B19& B19A
A. CONTRACTOR TO COORDINATE WITH ROOF INSTALLATION WARRANTY
REQUIREMENTS FOR ANY MODIFICATIONS TO ROOFING TO ENSURE NO
VIOLATIONS OCCUR OF THE WARRANTY. CONTRACTOR TO EMPLOY A
CERTIFIED ROOFING INSPECTOR MEETING THE REQUIREMENTS OF THE
INSTALLED ROOF. ALL WARRANTY VIOLATIONS WILL BE REQUIRED TO
BE CORRECTED PRIOR TO CLOSE OUT. ROOFS AND/OR ROOFING
IMPACTED BY WORK INCLUDE, AND MAY NOT BE LIMITED TO: B1, B3,
B22, B24 & B31.
B. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR
SMOKE RATED WALLS AND ASSEMBLIES INDICATED ON PLANS IN
WORK AREA. PROVIDE ALL PIPING PENETRATIONS OF FIRE, SMOKE
AND FULL HEIGHT WALLS SHALL BE CAULKED AIRTIGHT TO THE
ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF
CAULKING MATERIAL. SEE MECHANICAL AND PLUMBING DRAWINGS
FOR ADDITIONAL INFORMATION.
C. CONTRACTOR SHALL COORDINATE ALL PIPING, PLUMBING, AND
CONDUIT PIPING WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL
SYSTEMS AND SHALL PROVIDE NECESSARY OFFSETS TO AVOID
CONFLICTS AND TO MAINTAIN REQUIRED EQUIPMENT ACCESS AND
SERVICEABILITY.
D. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD
VERIFICATION WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER
FROM THOSE INDICATED. CONTRACTOR TO FIELD VERIFY IN ADVANCE
THE LOCATION AND CONDITION OF THOSE EXISTING SYSTEMS SHOWN
TO BE MODIFIED OR REMOVED. CONTRACTOR TO NOTIFY ARCHITECT
SHOULD CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY FROM
CONSTRUCTION DOCUMENTS.
E. CONTRACTOR TO COORDINATE ALL NEW EQUIPMENT LOCATIONS WITH
ALL TRADES PRIOR TO INSTALLATION.
F. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT
CONNECTIONS BETWEEN ALL DISSIMILAR METALS.
G. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED
TO COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND
PAINT AND RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.
H. CONTRACTOR TO PROVIDE ESCUTCHEONS ON ALL NEW EXPOSED
EXTERIOR PIPE PENETRATIONS AND SEAL COMPLETELY.
I. CONTRACTOR TO PROVIDE TEMPORARY COVERED ACCESSIBLE
PATHWAY PRIOR TO PHASE 1 INTEGRATED SYSTEMS CANOPY
CONSTRUCTION AND/OR DEMOLITION. AN ACCESSIBLE BED ROUTE IS
REQUIRED TO BE MAINTAINED AT ALL TIMES BETWEEN BUILDINGS.
J. ANY LANDSCAPE, HARDSCAPE, FIXTURE, SIGNAGE AND SYSTEMS OR
PEDESTRIAN CONTROL DEVICES WITHIN THE TEMPORARY ACCESSIBLE
PATHWAY SHALL BE PROTECTED IN PLACE OR TEMPORARILY
RELOCATED AS NECESSARY FOR CONTINUED UNINTERRUPTED
OPERATION, ACCESS, MAINTENANCE AND / OR VISIBILITY.
GENERAL SHEET NOTES
1" = 1'-0" F3
DETAIL - PRECAST CAP AT SEAT WALL
THE DETAILS ON THIS SHEET
OCCUR IN THESE LOCATIONS
1" = 1'-0" C2
DEMOLITION DETAIL - AT
ENGINEERING BLDG B3
3" = 1'-0" C1
ROOFING SYSTEM DETAIL
NO REVISIONS DATE
03_ROOF
120' - 0"
ACCESS DOOR,
BEYOND
TRANSLUCENT
PANEL ROOF
SYSTEM
METAL PANEL
WALL SYSTEM
TUBE STEEL
FRAMING
CYLINDRICAL CAST-IN-
PLACE CONCRETE
ACCENT LIGHTING,
LED ROPE LIGHT
4" TOE
KICK
SECTION VIEW
4"
J-BOX COVER,
COLOR TO
MATCH
FINISHED
CONCRETE
COLOR
R
'-6
STRUCTURAL
STEEL, REFER TO
STRUCTURAL
SHEETS FOR
ADDITIONAL
INFORMATION
PLAN VIEW
CAST-IN-
PLACE
CONCRETE
6"
CEILING AS
SCHEDULED
STRUCTURAL
STEEL, REFER TO
STRUCTURAL
SHEETS FOR
ADDITIONAL
INFORMATION
9" 6"
DOWN SPOUT
DOWN SPOUT
(N) METAL STUD
PARAPET
BACKUP WALL
METAL PANEL
CEILING SYSTEM
METAL PANEL
WALL SYSTEM
BUILT-UP ROOF
TO MATCH
CAMPUS
STANDARDS
A-504
C7
SIM
A-503
F5
SIMILAR
2/ 3H
1/ 3H
VA LOGO
METAL PANEL
WALL SYSTEM
CEILING SYSTEM, 24"X24"
STD TORSION SPRING
PANEL
SECTION VIEW
TRANSLUCENT
ROOF PANEL
SYSTEMROOF PANEL SYSTEM
SEAT ON STEEL
FRAMING
STRUCTURAL STEEL
FRAMING
METAL PANEL WALL
SYSTEM ON METAL
FRAMING
CAPTURE TOP OF
WALL IN TRACK AND
SEAL TO ROOF
PANEL
TRANSLUCENT
SKYLIGHT SYSTEM
METAL PANEL
WALL SYSTEM
METAL PANEL
WALL HEAD CLIP
SECTION VIEW
Y
1'-0"
MECHANICAL PIPING,
WHERE OCCURS
METAL PANEL WALL SYSTEM
TRIM TO MATCH SEAMS OF
ACCESS DOORS
120"x26"x3-1/2" METAL PANEL
ACCESS DOOR NESTED IN
1-5/8" STEEL FRAMING
STEEL FRAMING, SEE
STRUCTURAL DRAWINGS
120"x26"x3-1/2" METAL PANEL
ACCESS DOOR NESTED IN
1-5/8" STEEL FRAMING
14" CHS
14" CHS
CEILING SYSTEM: 24" X 24"
STD TORSION SPRING PANEL
(7210)
METAL PANEL WALL
SYSTEM TRIM TO MATCH
SEAMS OF ACCESS DOORS
SECTION VIEW
120"x26"x1-1/2" METAL
PANEL ACCESS DOOR ON
1-5/8" STEEL FRAMING
PANEL TRANSITION POINT
STEEL FRAMING,
SEE STRUCTURAL
DRAWINGS
3"
1-5/8" STEEL FRAMING TO
SUPPORT CEILING
SYSTEM
TRANSLUCENT ROOF
PANEL SYSTEM
ACCESS DOOR,
SEE F5/A-501
1-5/8" X 1-5/8" UNISTRUT
P1000, OR APPROVED
EQUAL, TYP.
WALL TO ROOF
ANCHORAGE BY CANOPY
MANUFACTURER
MANUFACTURED
CLIP IN CANOPY TO
ATTACH UNISTRUT
3"
SECTION VIEW
6"
02_CANOPY LEVEL
110' - 0"
AA
(N) TRANSLUCENT ROOF
PANEL SYSTEM, BASE BID
OR ADD ALT. NO 1
(N) STEEL STRUCTURE,
SEE STRUCTURAL
DRAWINGS
(E) MODULAR BUILDING TO
REMAIN OPERATIONAL
UNTIL (F)PHASE
NOTE:
PAINT ALL (N)
STEEL TO REMAIN
EXPOSED, COLOR:
WHITE
T5
3"
V E
R
IF
Y
2' -0
M
IN
3' -0
3'
-0
7"
(N) CEILING SYSTEM: 24" X 24" STD
TORSION SPRING PANEL (7210)
1-5/8" STEEL
FRAMING TO
SUPPORT
CEILING SYSTEM
CONNECTION BY CANOPY
MANUFACTURER
METAL PANEL WALL
SYSTEM, EACH SIDE
SIM
A-503
F5
SIM
A-503
F5
1' -1
0"
TRANSLUCENT PANEL SKYLIGHT
SYSTEM (BY SKYLIGHT
MANUFACTURER)
STEEL
STRUCTURE
BREAK METAL FLASHING
ADHERED TO EXISTING
WALL
TWO-PIECE GUTTER AND
BRACKET SYSTEM (BY
SKYLIGHT MANUFACTURER)DUCTBANK
INTERIOR
WALL FRAMING CLIP
EXISTING WALL TO REMAIN
SAWCUT AND FILL WILL
SEALANT4"
8" o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
Drawing number
Drawn
Building Number
Location
Project Title
Date
Project Number
Checked by
Drawing Title
Approved : Project Director
1 2 3 4 5 6
F
E
D
C
B
A
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
PROJECT TEAM ARCHITECTS/ENGINEERS Office of Construction and Facilities Management
Department of Veterans Affairs
7 8 9
TRIPLE C - THE A-E GROUP
4401 ATLANTIC AVE. SUITE 200
LONG BEACH, CA 90807
CONTACT: DAVID POTTER
PHONE: 307 460-2054
ISSUED FOR CONSTRUCTION
BRIDGERS & PAXTON CONSULTING ENGINEERS, INC.
1839 S. ALMA SCHOOL ROAD, SUITE 300
MESA, AZ 85210
CONTACT: JOHN MONTANO
PHONE: 602 336-5415
UNITED STRUCTURAL DESIGN, LLC
720 W. COMMERCE AVE OR P.O. BOX 33245
GILBERT, AZ 85233 PHOENIX, AZ 85067
CONTACT: DAVID GRAPSAS
PHONE: 480 382-9768
B
IM
0-
-3
V A
F re sn o
C hi lle r
P la nt P
/5
-1
6-
V
A F re sn o C hi lle r P la nt
-O P
T 4A
.rv t
4/
/2
2:
:4
P
M
A-503
ARCHITECTURAL DETAILS
M. PERKINS D. YOUNG02/07/2018
570-16-302DESIGN EXPANDED CHILLED
WATER CAPACITY, PHASE 2
100% CONSTRUCTION DOCUMENTS
SUBMISSION
2615 E Clinton Ave, Fresno, CA 93703
1" = 1'-0" B6
DETAIL - TRANSLUCENT ROOF PANEL
SYSTEM SUPPORT
N O R T H
F R E S N O
S T R E E T
EAST HARVARD AVENUE
N O R T H
A N G U S
S T R E E T
EAST CLINTON AVENUE
TANK
O2
TANK
O2
KEY PLAN
P2P3 B31
B3
B32 P1
ADD- ALT.
B24
B25
B2
B22A
B1
OPC
B27
B34
B
B19& B19A
A. CONTRACTOR TO COORDINATE WITH ROOF INSTALLATION WARRANTY
REQUIREMENTS FOR ANY MODIFICATIONS TO ROOFING TO ENSURE NO
VIOLATIONS OCCUR OF THE WARRANTY. CONTRACTOR TO EMPLOY A
CERTIFIED ROOFING INSPECTOR MEETING THE REQUIREMENTS OF THE
INSTALLED ROOF. ALL WARRANTY VIOLATIONS WILL BE REQUIRED TO
BE CORRECTED PRIOR TO CLOSE OUT. ROOFS AND/OR ROOFING
IMPACTED BY WORK INCLUDE, AND MAY NOT BE LIMITED TO: B1, B3,
B22, B24 & B31.
B. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR
SMOKE RATED WALLS AND ASSEMBLIES INDICATED ON PLANS IN
WORK AREA. PROVIDE ALL PIPING PENETRATIONS OF FIRE, SMOKE
AND FULL HEIGHT WALLS SHALL BE CAULKED AIRTIGHT TO THE
ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF
CAULKING MATERIAL. SEE MECHANICAL AND PLUMBING DRAWINGS
FOR ADDITIONAL INFORMATION.
C. CONTRACTOR SHALL COORDINATE ALL PIPING, PLUMBING, AND
CONDUIT PIPING WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL
SYSTEMS AND SHALL PROVIDE NECESSARY OFFSETS TO AVOID
CONFLICTS AND TO MAINTAIN REQUIRED EQUIPMENT ACCESS AND
SERVICEABILITY.
D. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD
VERIFICATION WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER
FROM THOSE INDICATED. CONTRACTOR TO FIELD VERIFY IN ADVANCE
THE LOCATION AND CONDITION OF THOSE EXISTING SYSTEMS SHOWN
TO BE MODIFIED OR REMOVED. CONTRACTOR TO NOTIFY ARCHITECT
SHOULD CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY FROM
CONSTRUCTION DOCUMENTS.
E. CONTRACTOR TO COORDINATE ALL NEW EQUIPMENT LOCATIONS WITH
ALL TRADES PRIOR TO INSTALLATION.
F. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT
CONNECTIONS BETWEEN ALL DISSIMILAR METALS.
G. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED
TO COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND
PAINT AND RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.
H. CONTRACTOR TO PROVIDE ESCUTCHEONS ON ALL NEW EXPOSED
EXTERIOR PIPE PENETRATIONS AND SEAL COMPLETELY.
I. CONTRACTOR TO PROVIDE TEMPORARY COVERED ACCESSIBLE
PATHWAY PRIOR TO PHASE 1 INTEGRATED SYSTEMS CANOPY
CONSTRUCTION AND/OR DEMOLITION. AN ACCESSIBLE BED ROUTE IS
REQUIRED TO BE MAINTAINED AT ALL TIMES BETWEEN BUILDINGS.
J. ANY LANDSCAPE, HARDSCAPE, FIXTURE, SIGNAGE AND SYSTEMS OR
PEDESTRIAN CONTROL DEVICES WITHIN THE TEMPORARY ACCESSIBLE
PATHWAY SHALL BE PROTECTED IN PLACE OR TEMPORARILY
RELOCATED AS NECESSARY FOR CONTINUED UNINTERRUPTED
OPERATION, ACCESS, MAINTENANCE AND / OR VISIBILITY.
GENERAL SHEET NOTES
1" = 1'-0" F1
DETAIL - TYPICAL BBQ AREA COLUMN BASE
3/4" = 1'-0" B1
DETAIL- CANOPY AT BBQ AREA
3/4" = 1'-0" B8
DETAIL - CANOPY END PANEL
1" = 1'-0" E5
DETAIL - SKYLIGHT AT METAL PANEL
WALL
1" = 1'-0" B5
DETAIL - METAL PANEL AT END WALL
1" = 1'-0" E6
DETAIL - (N) METAL ACCESS PANEL
1" = 1'-0" F6
DETAIL - (N) SOFFIT - INTERIOR
CORNER
1" = 1'-0" C6
DETAIL - (N) METAL ACCESS PANEL AT
ROOF - SELF SUPPORTED
1" = 1'-0" F5
DETAIL - (N) SOFFIT - EXTERIOR
CORNER
3/4" = 1'-0" D1
DETAIL - SHORT SOFFIT AT MODULAR
1" = 1'-0" C5
CANOPY SECTION NORTH - GUTTER
DETAIL SELF SUPPORTED
NO REVISIONS DATE
SECTION VIEW
ROLLED
TRANSLUCENT
ROOF PANEL
SYSTEM,
CAPTURED BY
BATTENS
ALUMINUM RAFTER
AND PURLIN SYSTEM
SEAT ON STEEL
FRAMING
STRUCTURAL STEEL
FRAMING
METAL PANEL WALL
SYSTEM ON METAL
FRAMING
CAPTURE TOP OF
WALL IN TRACK AND
SEAL TO ROOF
PANEL
SIM
A-503.1
F5 CONNECTION TO STEEL
BY CANOPY
MANUFACTURER
CONTINUOUS FASCIA
FLASHING TRACK
ATTACHED TO CANOPY, BY
CANOPY MANUFACTURER
TRANSLUCENT ROOF
PANEL SYSTEM
ACCESS DOOR,
SEE A-600
1-5/8" X 1-5/8" UNISTRUT
SOFFIT FRAMING, P1000, OR
APPROVED EQUAL, TYP.
WALL TO ROOF
ANCHORAGE, CONTINUOUS
ANGLE BETWEEN RAFTERS
PROVIDED BY CANOPY
MANUFACTURER
RAFTER AND PURLIN
SYSTEM
SIM
A-503.1
F5
METAL PANEL
TRIM TO MATCH
ACCESS DOORS
A-503.1
D8
METAL PANEL WALL SYSTEM,
EACH SIDE, UNISTRUT
FRAMING
MPC12, METAL PANEL CLIP
W/ (2) PLTD #10 X 5/8" WHTEK
U2 PANEL BATTEN
@ 23 11/16" (+/-) O.C.
TUBE PURLIN
(SIZE TO BE DETERMINED)
U2 PANEL BATTEN
@ 23 11/16" O.C.
MPC 12, METAL PANEL CLIP
W/ (2) PLTD #10 X 5/8" WHTEK
E2CL BATTEN CLOSURE
HEAT OR TAPE SEAL
ENDS OF PANELS
3/8" Ø WEEP HOLES
@12" O.C.
CPI-1220, "J" RECEIVER
U2 PANEL BATTEN
@ 23 11/16" (+/-) O.C.
MPC12, METAL PANEL CLIP
W/ (2) PLTD #10 X 5/8" WHTEK
#14 X 1" SS
FHTS UNDERCUTS
TUBE PURLIN
(SIZE TO BE DETERMINED)
ROLLED ALUM TUBE RAFTER
(SIZE TO BE DETERMINED)
2 3/8"
1/4"
SIM
F1
A-503.1
CPI-4029, 1 1/2" x 1 1/2" x 1/4"
ANGLE CLIP ATTACHED TO
RAFTER W/ (2) #14 X 3/4" HHTS
W/ (2) #14 X 3/4" SS FHTS (UC)
CONT. SEALANT BEAD
1 1/2" X 5/8" X 1/8"
ROLLED ALUM ANGLE BY CPI
1/4" X 1/2" X 2"
ALUM SPACER BY CPI
BACKER ROD & SEALANT
BY INSTALLER
1 7/8" X 1 1/4" X 1/8"
ROLLED ANGLE BY CPI
SPACER BAR 2" LONG
@ 12" O.C. TAC WELD
TO GLAZED BAR
CPI-1082, CLAMPING BAR
W/SS #14 X 1 1/4" HHTS
W/WSW @ 12" O.C. MAX
G1 EPDM GASKET
CPI-1156, GLAZED BAR
#14 X 3/4" SS HHTS
W/ WSW @ 12" O.C. MAX
ALUM TUBE PURLIN
(SIZE TO BE DETERMINED)
#10 X 5/8" PLTD
WHTEK @ 12" O.C.
ROLLED ALUM TUBE RAFTER
(SIZE TO BE DETERMINED)
2 1/8"
1 1/8"
1/4"
VA LOGO
RAFTER AND
PURLIN
SYSTEM
TRANSLUCENT ROOF
PANEL SYSTEM
METAL PANEL
WALL SYSTEM,
EACH SIDE,
UNISTRUT
FRAMING
A-503.1
D3
TRANSLUCENT
SKYLIGHT SYSTEM
METAL PANEL
WALL SYSTEM
METAL PANEL
WALL HEAD CLIP
SECTION VIEW
RAFTER AND PURLIN
ROOF SYSTEM
A-503.1
D3
STRUCTURAL
STEEL
TOP OF DUCTBANK,
BEYOND
TRANSLUCENT
PANEL ROOF
SYSTEM
METAL PANEL
TUBE STEEL
FRAMING
RAFTER AND
PURLIN ROOF
SYSTEM
SIM
A-503.1
F3
TRANSLUCENT PANEL
SKYLIGHT SYSTEM (BY
SKYLIGHT MANUFACTURER)
STEEL STRUCTURE
BREAK METAL FLASHING
ADHERED TO EXISTING
WALL
TWO-PIECE GUTTER AND
BRACKET SYSTEM (BY
SKYLIGHT MANUFACTURER)
DUCTBANK
WALL FRAMING CLIP
RAFTER AND PURLIN
EXISTING WALL TO REMAIN
SAWCUT AND FILL WITH
SEALANT
4"
10"
TRANSLUCENT PANEL SKYLIGHT SYSTEM
(BY SKYLIGHT MANUFACTURER)
STEEL
STRUCTURE
PARAPET CAP AND
COUNTER-FLASHING
(BY ROOFING
CONTRACTOR)
1/2" FIRE TREATED
PLYWOOD ON BACK OF
FRAMING
TWO-PIECE GUTTER AND
BRACKET SYSTEM (BY
SKYLIGHT
MANUFACTURER)
WALL FRAMING CLIP
RAFTER AND
PURLIN
CPI-4029, 1 1/2" x 1 1/2" x 1/4"
ANGLE CLIP ATTACHED TO
RAFTER W/ (2) #14 X 3/4" HHTS
W/ (2) #14 X 3/4" SS FHTS (UC)
1 7/8" X 1 1/4" X 1/8"
ROLLED ANGLE BY MFR
CPI-1156, GLAZED BAR
#14 X 3/4" SS HHTS
W/ WSW @ 12" O.C. MAX
ALUM TUBE PURLIN
(SIZE TO BE DETERMINED)
ROLLED ALUM TUBE RAFTER
(SIZE TO BE DETERMINED)
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
Drawing number
Drawn
Building Number
Location
Project Title
Date
Project Number
Checked by
Drawing Title
Approved : Project Director
1 2 3 4 5 6
F
E
D
C
B
A
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
PROJECT TEAM ARCHITECTS/ENGINEERS Office of Construction and Facilities Management
Department of Veterans Affairs
7 8 9
TRIPLE C - THE A-E GROUP
4401 ATLANTIC AVE. SUITE 200
LONG BEACH, CA 90807
CONTACT: DAVID POTTER
PHONE: 307 460-2054
ISSUED FOR CONSTRUCTION
BRIDGERS & PAXTON CONSULTING ENGINEERS, INC.
1839 S. ALMA SCHOOL ROAD, SUITE 300
MESA, AZ 85210
CONTACT: JOHN MONTANO
PHONE: 602 336-5415
UNITED STRUCTURAL DESIGN, LLC
720 W. COMMERCE AVE OR P.O. BOX 33245
GILBERT, AZ 85233 PHOENIX, AZ 85067
CONTACT: DAVID GRAPSAS
PHONE: 480 382-9768
B
IM
0-
-3
V A
F re sn o
C hi lle r
P la nt P
/5
-1
6-
V
A F re sn o C hi lle r P la nt
-O P
T 4A
.rv t
4/
/2
2:
:4
P
M
A-503.1
ARCHITECTURAL DETAILS
Checker Author02/07/2018
570-16-302DESIGN EXPANDED CHILLED
WATER CAPACITY, PHASE 2
100% CONSTRUCTION DOCUMENTS
SUBMISSION
2615 E Clinton Ave, Fresno, CA 93703
1" = 1'-0" D1
DETAIL - SUPPORTED ROOF AT METAL
PANEL WALL
N O R T H
F R E S N O
S T R E E T
EAST HARVARD AVENUE
N O R T H
A N G U S
S T R E E T
EAST CLINTON AVENUE
TANK
O2
TANK
O2
KEY PLAN
P2P3 B31
B3
B32 P1
ADD- ALT.
B24
B25
B2
B22A
B1
OPC
B27
B34
B
B19& B19A
A. CONTRACTOR TO COORDINATE WITH ROOF INSTALLATION WARRANTY
REQUIREMENTS FOR ANY MODIFICATIONS TO ROOFING TO ENSURE NO
VIOLATIONS OCCUR OF THE WARRANTY. CONTRACTOR TO EMPLOY A
CERTIFIED ROOFING INSPECTOR MEETING THE REQUIREMENTS OF THE
INSTALLED ROOF. ALL WARRANTY VIOLATIONS WILL BE REQUIRED TO
BE CORRECTED PRIOR TO CLOSE OUT. ROOFS AND/OR ROOFING
IMPACTED BY WORK INCLUDE, AND MAY NOT BE LIMITED TO: B1, B3,
B22, B24 & B31.
B. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR
SMOKE RATED WALLS AND ASSEMBLIES INDICATED ON PLANS IN
WORK AREA. PROVIDE ALL PIPING PENETRATIONS OF FIRE, SMOKE
AND FULL HEIGHT WALLS SHALL BE CAULKED AIRTIGHT TO THE
ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF
CAULKING MATERIAL. SEE MECHANICAL AND PLUMBING DRAWINGS
FOR ADDITIONAL INFORMATION.
C. CONTRACTOR SHALL COORDINATE ALL PIPING, PLUMBING, AND
CONDUIT PIPING WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL
SYSTEMS AND SHALL PROVIDE NECESSARY OFFSETS TO AVOID
CONFLICTS AND TO MAINTAIN REQUIRED EQUIPMENT ACCESS AND
SERVICEABILITY.
D. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD
VERIFICATION WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER
FROM THOSE INDICATED. CONTRACTOR TO FIELD VERIFY IN ADVANCE
THE LOCATION AND CONDITION OF THOSE EXISTING SYSTEMS SHOWN
TO BE MODIFIED OR REMOVED. CONTRACTOR TO NOTIFY ARCHITECT
SHOULD CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY FROM
CONSTRUCTION DOCUMENTS.
E. CONTRACTOR TO COORDINATE ALL NEW EQUIPMENT LOCATIONS WITH
ALL TRADES PRIOR TO INSTALLATION.
F. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT
CONNECTIONS BETWEEN ALL DISSIMILAR METALS.
G. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED
TO COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND
PAINT AND RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.
H. CONTRACTOR TO PROVIDE ESCUTCHEONS ON ALL NEW EXPOSED
EXTERIOR PIPE PENETRATIONS AND SEAL COMPLETELY.
I. CONTRACTOR TO PROVIDE TEMPORARY COVERED ACCESSIBLE
PATHWAY PRIOR TO PHASE 1 INTEGRATED SYSTEMS CANOPY
CONSTRUCTION AND/OR DEMOLITION. AN ACCESSIBLE BED ROUTE IS
REQUIRED TO BE MAINTAINED AT ALL TIMES BETWEEN BUILDINGS.
J. ANY LANDSCAPE, HARDSCAPE, FIXTURE, SIGNAGE AND SYSTEMS OR
PEDESTRIAN CONTROL DEVICES WITHIN THE TEMPORARY ACCESSIBLE
PATHWAY SHALL BE PROTECTED IN PLACE OR TEMPORARILY
RELOCATED AS NECESSARY FOR CONTINUED UNINTERRUPTED
OPERATION, ACCESS, MAINTENANCE AND / OR VISIBILITY.
GENERAL SHEET NOTES
1" = 1'-0" D6
DETAIL - (N) METAL ACCESS PANEL AT
ROOF - SUPPORTED
3/4" = 1'-0" B8
DETAIL - CANOPY END PANEL
6" = 1'-0" F1
SECTION AT BATTEN - SUPPORTED ROOF
6" = 1'-0"
F5
SECTION AT SILL / PURLIN - SUPPORTED ROOF
6" = 1'-0" F3
SECTION AT WALL - SUPPORTED ROOF
1" = 1'-0" D8
DETAIL - CANOPY END PANEL AT
SUPPORTED ROOF
1" = 1'-0" D5
DETAIL - METAL PANEL END WALL AT
DUCTBANK
1" = 1'-0" B6
DETAIL - TRANSLUCENT ROOF PANEL
SYSTEM SUPPORT
1" = 1'-0" B3
CANOPY SECTION NORTH - GUTTER
DETAIL SUPPORTED
1 1/2" = 1'-0" B1
GUTTER DETAIL AT HEX - SUPPORTED
6" = 1'-0" D3
SECTION AT OPEN END - SUPPORTED ROOF
NO REVISIONS DATE
(N) METAL PANEL
CEILING PANEL
(E) WALL TO
REMAIN
(N) METAL STUD
FRAMING, SEE
STRUCTURAL DRAWINGS
(N) BLDG JOINT
4"
N O
T T
O S
C A
LE
'-0
NOT TO SCALE
5'-0" +/-
NOT TO SCALE
SEE STRUCTURAL
3'-9" +/-
(N) STEEL COLUMN
(E) FACE OF WALL AT B1
(N) PIPING DOWN TO
UTILITY TUNNEL BELOW,
SEE MECHANICAL /
PLUMBING DRAWNIGS
(N) STONE VENEER ON
METAL STUD FRAMING
PLAN VIEW
SIM
A-504
C4
4"
8" M
IN
IM
U M
SKYLIGHT
LAP VERTICAL
MEMBRANE
LAYERS OVER
CURB
OVERLAP
HORIZONTAL
MEMBRANE LAYERS
AT CANT OR CRICKET
SECURE LEVELED
ROOF CURB TO
FIRE TREATED
NAILER SECURED
TO ROOF DECK
OPENING FRAMING,
SEE STRUCTURAL
DRAWINGS
LIGHT TUBE
SEAL ALL
FASTENERS
THROUGH CAP,
SEAL CAP TO
CURB
EACH SIDE
1'-0" MIN.
NOTE:
INSTALL ALL OVERFLOW DRAINS
WITH A 2" COLLAR AND
CONTINUOUS DRAIN PAN
ROOF DRAIN SYSTEM
ADHERED BTU MEMBRANE FLASHING,
WHERE APPLICABLE
BUILT-UP BITUMINOUS
ROOFING SYSTEM
RIGID
INSULATION
STEEL ROOF
DECK
CLAMPING RINGINSULATE ROOF
DRAIN SUMP (SAME
R-VALUE AS ROOF)
DRAIN PIPE AND
INSULATION
10"
2"
TYP 1'-5"
TRANSLUCENT PANEL SKYLIGHT SYSTEM
(BY SKYLIGHT MANUFACTURER)
STEEL
STRUCTURE
PARAPET CAP AND COUNTER-
FLASHING (BY ROOFING
CONTRACTOR)
1/2" FIRE TREATED
PLYWOOD ON BACK OF
FRAMING
TWO-PIECE GUTTER AND
BRACKET SYSTEM (BY
ROOFING CONTRACTOR)
DUCTBANKWALL FRAMING CLIP
P R
E F
E R
R E
D M
IN
4"
REVEAL LAP ROOF MEMBRANE
OVER TOP OF WALL
SYSTEM
EXTRUSIONS
AND CLIPS
METAL PANEL
WALL SYSTEM
METAL PANEL
PARAPET CAP
SLOPE
EXTERIOR WALL
SHEATHING
SECTION VIEW
future demo
3"
6"
11 7/8"
1'-3 1/4"
3' -0
EXISTING WALL
SECTION VIEW
phase 2
3"
6"
LAP
6"4" 4"
6"
11 7/8"
1'-3 1/4"
3' -0
EXISTING WALL
3" LAP GUTTER BRACKETS
DEMO B3(E) B3 ROOF
DUCTBANK
INTERIOR
DUCTBANK
INTERIOR
REMOVE PANEL AND
GUTTER BRACKET
3 LAYERS SINGLE PLY
MEMBRANE ON COLD
APPLIED MASTIC
OVERLAPPING
HORIZONTAL
MEMBRANES
PREFABRICATED
PARAPET CAP
M
IN
4"
M
IN
6"
(N) STONE VENEER
WALL SYSTEM
FIRE TREATED
2xCONTIUOUS
BLOCKING
LAP MEMBRANE
LAYERS OVER
BLOCKING
M
IN
4"
(N) METAL PANEL
WALL SYSTEM, OR
FRAMED STONE
VENEER WALL
(N) EXPANSION
JOINT
FACE OF (E) WALL
(N) DUCTBANK
(N) DUCTBANK,
BEYOND
(E) ROOF
(N) BLDG JOINT
SIM
C4
A-504
(N) TRANSLUCENT ROOF
PANEL SYSTEM, BEYOND,
WHERE OCCURS
BEYOND
(N) METAL PANEL
CEILING SYSTEM
REMOVE AND REPLACE (E)
PARAPET CAP WITH 3-PIECE
BD JOINT AND COUNTER
FLASHING, COLOR TO
MATCH
(N) METAL PANEL
WALL SYSTEM
A-504
D4
(N) UNISTRUT
SOFFIT FRAMING,
SEE STRUCTURAL
(N) STRUCTURAL
FRAMING
1' -0
(N) ROOF MEMBRANE
LAYERS TO LAP OVER
(N) CURB AND CANT
AND 6" OVER (E)
ROOFING, MIN
6" MIN
SIM
4" MIN
(E) CANOPY FACIA AND SOFFIT
TO REMAIN
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
Drawing number
Drawn
Building Number
Location
Project Title
Date
Project Number
Checked by
Drawing Title
Approved : Project Director
1 2 3 4 5 6
F
E
D
C
B
A
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
PROJECT TEAM ARCHITECTS/ENGINEERS Office of Construction and Facilities Management
Department of Veterans Affairs
7 8 9
TRIPLE C - THE A-E GROUP
4401 ATLANTIC AVE. SUITE 200
LONG BEACH, CA 90807
CONTACT: DAVID POTTER
PHONE: 307 460-2054
ISSUED FOR CONSTRUCTION
BRIDGERS & PAXTON CONSULTING ENGINEERS, INC.
1839 S. ALMA SCHOOL ROAD, SUITE 300
MESA, AZ 85210
CONTACT: JOHN MONTANO
PHONE: 602 336-5415
UNITED STRUCTURAL DESIGN, LLC
720 W. COMMERCE AVE OR P.O. BOX 33245
GILBERT, AZ 85233 PHOENIX, AZ 85067
CONTACT: DAVID GRAPSAS
PHONE: 480 382-9768
B
IM
0-
-3
V A
F re sn o
C hi lle r
P la nt P
/5
-1
6-
V
A F re sn o C hi lle r P la nt
-O P
T 4A
.rv t
4/
/2
2:
:5
P
M
A-504
ARCHITECTURAL DETAILS
M. PERKINS D. YOUNG02/07/2018
570-16-302DESIGN EXPANDED CHILLED
WATER CAPACITY, PHASE 2
100% CONSTRUCTION DOCUMENTS
SUBMISSION
2615 E Clinton Ave, Fresno, CA 93703
1" = 1'-0" D4
DETAIL - (N) SOFFIT AT (E) WALL
3/4" = 1'-0" F4
DETAIL - PIPE CHASE AT B1
N O R T H
F R E S N O
S T R E E T
EAST HARVARD AVENUE
N O R T H
A N G U S
S T R E E T
EAST CLINTON AVENUE
TANK
O2
TANK
O2
KEY PLAN
B31
B3
B32
B24
B25
B2
B22A
B1
OPC
B27
B34
B
B19& B19A
A. CONTRACTOR TO COORDINATE WITH ROOF INSTALLATION WARRANTY
REQUIREMENTS FOR ANY MODIFICATIONS TO ROOFING TO ENSURE NO
VIOLATIONS OCCUR OF THE WARRANTY. CONTRACTOR TO EMPLOY A
CERTIFIED ROOFING INSPECTOR MEETING THE REQUIREMENTS OF THE
INSTALLED ROOF. ALL WARRANTY VIOLATIONS WILL BE REQUIRED TO
BE CORRECTED PRIOR TO CLOSE OUT. ROOFS AND/OR ROOFING
IMPACTED BY WORK INCLUDE, AND MAY NOT BE LIMITED TO: B1, B3,
B22, B24 & B31.
B. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR
SMOKE RATED WALLS AND ASSEMBLIES INDICATED ON PLANS IN
WORK AREA. PROVIDE ALL PIPING PENETRATIONS OF FIRE, SMOKE
AND FULL HEIGHT WALLS SHALL BE CAULKED AIRTIGHT TO THE
ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF
CAULKING MATERIAL. SEE MECHANICAL AND PLUMBING DRAWINGS
FOR ADDITIONAL INFORMATION.
C. CONTRACTOR SHALL COORDINATE ALL PIPING, PLUMBING, AND
CONDUIT PIPING WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL
SYSTEMS AND SHALL PROVIDE NECESSARY OFFSETS TO AVOID
CONFLICTS AND TO MAINTAIN REQUIRED EQUIPMENT ACCESS AND
SERVICEABILITY.
D. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD
VERIFICATION WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER
FROM THOSE INDICATED. CONTRACTOR TO FIELD VERIFY IN ADVANCE
THE LOCATION AND CONDITION OF THOSE EXISTING SYSTEMS SHOWN
TO BE MODIFIED OR REMOVED. CONTRACTOR TO NOTIFY ARCHITECT
SHOULD CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY FROM
CONSTRUCTION DOCUMENTS.
E. CONTRACTOR TO COORDINATE ALL NEW EQUIPMENT LOCATIONS WITH
ALL TRADES PRIOR TO INSTALLATION.
F. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT
CONNECTIONS BETWEEN ALL DISSIMILAR METALS.
G. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED
TO COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND
PAINT AND RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.
H. CONTRACTOR TO PROVIDE ESCUTCHEONS ON ALL NEW EXPOSED
EXTERIOR PIPE PENETRATIONS AND SEAL COMPLETELY.
I. CONTRACTOR TO PROVIDE TEMPORARY COVERED ACCESSIBLE
PATHWAY PRIOR TO PHASE 1 INTEGRATED SYSTEMS CANOPY
CONSTRUCTION AND/OR DEMOLITION. AN ACCESSIBLE BED ROUTE IS
REQUIRED TO BE MAINTAINED AT ALL TIMES BETWEEN BUILDINGS.
J. ANY LANDSCAPE, HARDSCAPE, FIXTURE, SIGNAGE AND SYSTEMS OR
PEDESTRIAN CONTROL DEVICES WITHIN THE TEMPORARY ACCESSIBLE
PATHWAY SHALL BE PROTECTED IN PLACE OR TEMPORARILY
RELOCATED AS NECESSARY FOR CONTINUED UNINTERRUPTED
OPERATION, ACCESS, MAINTENANCE AND / OR VISIBILITY.
GENERAL SHEET NOTES
THE DETAILS ON THIS
SHEET OCCUR IN
THESE LOCATIONS
1 1/2" = 1'-0" D3
ROOF CURB DETAIL
1 1/2" = 1'-0" F2
ROOF DRAIN
1 1/2" = 1'-0" B7
GUTTER DETAIL AT HEX - SELF SUPPORTED
3" = 1'-0" C7
PARAPET DETAIL
1" = 1'-0" D6
DETAIL - (N) GUTTER AT B3
3" = 1'-0" C2
DETAIL - (N) ROOF TO (E) WALL JOINT
3" = 1'-0" C6
NEW METAL COPING DETAIL
1 1/2" = 1'-0"
C4
DETAIL - EXPANSION JOINT PLAN DETAIL AT (E) BREEZEWAY
1" = 1'-0" A4
DETAIL - CANOPY AT EXISTING B1 & B24 BREEZEWAY
NO REVISIONS DATE
02_CANOPY LEVEL
110' - 0"
1 2 3 B22.CB31.1
6'-9"
(N) CUSTOM SOLDIER PROFILE
COLUMNS WITH EMBEDDED
STRUCTURAL STEEL COLUMN,
SEE STRUCTURAL SHEETS.
TYP. ON CANOPY GRIDS
METAL PANEL
WALL SYSTEM
ON METAL
FRAMING
(N) TRANSLUCENT SKYLIGHT
SYSTEM CANOPY WITH
INTEGRATED UTILITY HOUSING -
PHASE 1
B31
F1
S-502
(N) ACCESS DOORS, SEE
A-600 FOR SCHEDULE AND
DETAILS
(N) PATHWAY ACCENT
LIGHTING, SEE ELECTRICAL
(N) FLY-
OVER CHASE
TO B22A
(N) UTILITY
DUCT-BANK
(N) STRUCTURAL STEEL (E) B22A SCREEN
WALL TO REMAIN
B
B
B
B
B
B
(N) CANOPY SOFFIT LIGHTING,
SEE ELECTRICAL
(N) FIXED STAINLESS STEEL METAL
WALL PANELS TO MATCH ACCESS
DOORS BELOW B22A
SIM
A-505
D3
SIM
A-505
D3
(N) REMOVAL TILE CEILING
SYSTEM
A-505
C2
(N) UTILITY
DUCT-BANK
EXISTING FASCIA
AND PARAPET TO
REMAIN
EXISTING LIGHT
FIXTURE TO
REMAIN
02_CANOPY LEVEL
110' - 0"
B31.1
(N) WALL-TO-WALL
BLDG JOINT, ALL
AROUND
A-504
D4
(N) METAL PANEL
CEILING SYSTEM
B31
(N) PIPE CHASE
ON (E) B31
PARAPET, SEE
STRUCTURAL
(E) B31 ENTRY FASCIA
TO REMAIN
(N) METAL PANEL
ROOF TO MATCH
WALL SYSTEM
(N) METAL PANEL
WALL SYSTEM
TOP OF (E) PARAPET,
BEYOND
TOP OF (E) ROOF
M
IN
12" HIGH ALUMINUM
BRAKE METAL
FLASHING
UNISTRUT FRAMING,
OR APPROVED
EQUAL
TOP OF (E) PARAPET
TUBE STEEL
FRAMING, SEE
STRUCTURAL
DRAWINGS
EMBED UNISTRUT
FRAMING BETWEEN
STRUCTURAL
FRAMING
6"
SEE PLAN
3' -6
2'-0" TYP
ROUTE & BEND AT RIDGE
PIPE AT B24 OR B31 SEE MECHANICAL
SEISMIC BRACING
ROUTE &
RETURN DRY
SEAL SYSTEM
STRUCURAL FRAMING
SEE F1/S-502
WEATHER ASSEMBLY:
1/2" EXTERIOR
SHEATHING WITH
WRAP, BREAK AT
ACCESS PANEL
SIM
A-505
D5
SIM
D3
A-505
WEATHER
ASSEMBLY
ALUMINUM
COMPOUND
MATERIAL
EXTRUSION
AND CLIPS
RISER / SEPARATOR,
AS NECESSARY
STEEL FRAMING, SEE
STRUCTURAL
DRAWINGS
METAL FRAMING
NESTED IN STEEL
FRAMING
4" MIN
4" M
IN
WEATHER ASSEMBLY
ALUMINUM COMPOUND
MATERIAL
EXTRUSION AND CLIPS
RISERS / SEPARATORS,
AS NECESSARY
A S
S E
M B
LY
T Y
P
IC
A L
W A
LL
2"
STEEL FRAMING, SEE
STRUCTURAL
DRAWINGS
METAL FRAMING
NESTED IN STEEL
FRAMING
(E) WALL
TO REMAIN
9/
6" 9/
"1
/8
3/ 8"
B31.1
B31 PENTHOUSE
D7
A-551
(E) STAIRS
(BEYOND)
(N) TRANSLUCENT
CANOPY
(N) METAL
PANEL WALL
SYSTEM
(N) METAL PANEL WALL
SYSTEM DOGHOUSE PIPE
CHASE, SEE STRUCTURAL
FOR FRAMING
(N) TO (E) POC FOR B31
UTILITIES IN
PENTHOUSE, SEE
MECHANICAL
(E) DOUBLE DOOR
(BEYOND)
(E) PIPING, SEE
MECHANICAL
(E) B31 ENTRY
EYEBROW
(N) 4" BLDG
JOINT
FACE OF EXISTING BUILDING
ANCHOR AND SEAL PER
MANUFACTURER'S
RECOMMENDATIONS
NEW ROOF-TO-WALL
BUILDING JOINT COVER
ROUTE & RETURN
DRY SEAL SYSTEM ON
WEATHER ASSEMBLY
M
IN4"
LAP WEATHER BARRIER
OVER BRAKE METAL
FLASHING, 6" MIN
6" MIN
LIGHT GAUGE METAL
FRAMING ROOF SUPPORT
STRUCTURAL STEEL,
SEE STRUCTURAL
DRAWINGS
o n e -e ig h th i n c h o n e f o o t o n e -q u a rt e r in c h o n e f o o t th re e -e ig h th i n c h o n e f o o t o n e -h a lf i n c h o n e f o o t th re e -q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e -h a lf i n c h o n e f o o t th re e i n c h e s o n e f o o t
Drawing number
Drawn
Building Number
Location
Project Title
Date
Project Number
Checked by
Drawing Title
Approved : Project Director
1 2 3 4 5 6
F
E
D
C
B
A
F
E
D
C
B
A
1 2 3 4 5 6 7 8 9
PROJECT TEAM ARCHITECTS/ENGINEERS Office of Construction and Facilities Management
Department of Veterans Affairs
7 8 9
TRIPLE C - THE A-E GROUP
4401 ATLANTIC AVE. SUITE 200
LONG BEACH, CA 90807
CONTACT: DAVID POTTER
PHONE: 307 460-2054
ISSUED FOR CONSTRUCTION
BRIDGERS & PAXTON CONSULTING ENGINEERS, INC.
1839 S. ALMA SCHOOL ROAD, SUITE 300
MESA, AZ 85210
CONTACT: JOHN MONTANO
PHONE: 602 336-5415
UNITED STRUCTURAL DESIGN, LLC
720 W. COMMERCE AVE OR P.O. BOX 33245
GILBERT, AZ 85233 PHOENIX, AZ 85067
CONTACT: DAVID GRAPSAS
PHONE: 480 382-9768
B
IM
0-
-3
V A
F re sn o
C hi lle r
P la nt P
/5
-1
6-
V
A F re sn o C hi lle r P la nt
-O P
T 4A
.rv t
4/
/2
2:
:0
P
M
A-505
ARCHITECTURAL DETAILS
Checker Author02/07/2018
570-16-302DESIGN EXPANDED CHILLED
WATER CAPACITY, PHASE 2
100% CONSTRUCTION DOCUMENTS
SUBMISSION
2615 E Clinton Ave, Fresno, CA 93703
A. CONTRACTOR TO COORDINATE WITH ROOF INSTALLATION WARRANTY
REQUIREMENTS FOR ANY MODIFICATIONS TO ROOFING TO ENSURE NO
VIOLATIONS OCCUR OF THE WARRANTY. CONTRACTOR TO EMPLOY A
CERTIFIED ROOFING INSPECTOR MEETING THE REQUIREMENTS OF THE
INSTALLED ROOF. ALL WARRANTY VIOLATIONS WILL BE REQUIRED TO
BE CORRECTED PRIOR TO CLOSE OUT. ROOFS AND/OR ROOFING
IMPACTED BY WORK INCLUDE, AND MAY NOT BE LIMITED TO: B1, B3,
B22, B24 & B31.
B. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR
SMOKE RATED WALLS AND ASSEMBLIES INDICATED ON PLANS IN
WORK AREA. PROVIDE ALL PIPING PENETRATIONS OF FIRE, SMOKE
AND FULL HEIGHT WALLS SHALL BE CAULKED AIRTIGHT TO THE
ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED FIRE PROOF
CAULKING MATERIAL. SEE MECHANICAL AND PLUMBING DRAWINGS
FOR ADDITIONAL INFORMATION.
C. CONTRACTOR SHALL COORDINATE ALL PIPING, PLUMBING, AND
CONDUIT PIPING WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL
SYSTEMS AND SHALL PROVIDE NECESSARY OFFSETS TO AVOID
CONFLICTS AND TO MAINTAIN REQUIRED EQUIPMENT ACCESS AND
SERVICEABILITY.
D. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD
VERIFICATION WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER
FROM THOSE INDICATED. CONTRACTOR TO FIELD VERIFY IN ADVANCE
THE LOCATION AND CONDITION OF THOSE EXISTING SYSTEMS SHOWN
TO BE MODIFIED OR REMOVED. CONTRACTOR TO NOTIFY ARCHITECT
SHOULD CONDITIONS BE FOUND TO DIFFER SIGNIFICANTLY FROM
CONSTRUCTION DOCUMENTS.
E. CONTRACTOR TO COORDINATE ALL NEW EQUIPMENT LOCATIONS WITH
ALL TRADES PRIOR TO INSTALLATION.
F. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT
CONNECTIONS BETWEEN ALL DISSIMILAR METALS.
G. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED
TO COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND
PAINT AND RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.
H. CONTRACTOR TO PROVIDE ESCUTCHEONS ON ALL NEW EXPOSED
EXTERIOR PIPE PENETRATIONS AND SEAL COMPLETELY.
I. CONTRACTOR TO PROVIDE TEMPORARY COVERED ACCESSIBLE
PATHWAY PRIOR TO PHASE 1 INTEGRATED SYSTEMS CANOPY
CONSTRUCTION AND/OR DEMOLITION. AN ACCESSIBLE BED ROUTE IS
REQUIRED TO BE MAINTAINED AT ALL TIMES BETWEEN BUILDINGS.
J. ANY LANDSCAPE, HARDSCAPE, FIXTURE, SIGNAGE AND SYSTEMS OR
PEDESTRIAN CONTROL DEVICES WITHIN THE TEMPORARY ACCESSIBLE
PATHWAY SHALL BE PROTECTED IN PLACE OR TEMPORARILY
RELOCATED AS NECESSARY FOR CONTINUED UNINTERRUPTED
OPERATION, ACCESS, MAINTENANCE AND / OR VISIBILITY.
GENERAL SHEET NOTES
1/2" = 1'-0" C7
PHASE 1 CANOPY CONNECTION AT B31
1" = 1'-0"
C2
CEILING DETAIL AT CANOPY
CONNECTION TO B31
1" = 1'-0" D8
DETAIL - (N) FLY-OVER CHASE FROM
(N) DUCTBANK TO (E) BUILDING
3" = 1'-0" D5
DETAIL - (N) FLY-OVER CHASE
OUTSIDE CORNER CONNECTION
3" = 1'-0" D3
DETAIL - (N) FLY-OVER CHASE
ENDWALL CONDITION
NO REVISIONS DATE
1/2" = 1'-0" E1
B31 PENTHOUSE DOGHOUSE CHASE
AND WALL PENETRATION
1 1/2" = 1'-0" F8
ROOF-TO-WALL BUILDING JOINT AT
METAL PANEL ROOF SYSTEM
SLIP
END
SLIP
END
4 DIAGONAL
BRACE WIRES
AT 8'X12' GRID
MAX.
FIXED
END
FIXED
END
ADDITIONAL
CROSS RUNNERS
WHERE 2'X2'
GRID OCCURS
MAIN RUNNERS
AT 4'-0" O.C.
12 GA. VERTICAL
HANGER HANGER
WIRES AT 4'-0" O.C.
MAX. - TYP.
12 GA. HANGER
WIRE AT
PERIMETER
CROSS
RUNNERS AT
2'-0" O.C.
8" MAX. OR 1/4 OF
LENGTH OF THE END
RUNNER, WHICHEVER
IS LESS
4'-0" MAX. 8'-0" MAX. 8'-0" MAX. 4'-0" MAX.
4' -0
M
A X
'-0
M A
X
4' -0
M
A X
1"
PARTITION AS SCHEDULED;
SEE PLAN FOR TYPE
ACOUSTICAL PANEL
ANGLE MOLDING
GRID
LOOSE SCREW
PARTITION AS
SCHEDULED;
SEE PLAN FOR
TYPE
ACOUSTICAL PANEL
ANGLE MOLDING
GRID
TIGHT SCREW
1"
350IU20
250IU20
158IU200.24IN
STRUTREQr
0.382 0.399 0.410
RSUPP.LENGTH
4'
400IU20 0.380
COMPRESSION STRUT:
1" Ø COMPRESSION
STRUT. COMPRESSION
STRUT SHALL NOT
REPLACE HANGER WIRE
TYPICAL:
12 GAUGE BRACING
WIRE W/ MIN. 4 TIGHT
TURNS IN 1-1/2"
BOTH ENDS OF WIRE
MAIN RUNNER
CROSS RUNNER
2" MAX. FROM
BRACING WIRES
TO CROSS
RUNNERS
4'-0"
MAX.
4'-0" MAX.
45° MAX. TYP.45° MAX. TYP.
TYPICAL:
12 GAUGE VERTICAL
HANGER WIRE @ 4'-0"
EACH WAY W/ MIN. 3
TIGHT TURNS IN 1-1/2"
BOTH ENDS OF WIRE
SECTION 'A' EXTERIOR ELEVATION
A
A
FOR PIPE MATERIAL, SEE SPECIFICATIONS.
PIPE SLEEVE, SEE SPECIFICATIONS FOR
MATERIALS, LENGTH OF SLEEVE AS
REQUIRED.
SEE STRUCTURAL DRAWINGS FOR
CONSTRUCTION OF WALL.
PROVIDE ESCUTCHEON PLATE AT ALL
EXPOSED EXTERIOR PENETRATIONS AND
SEAL COMPLETELY.
PIPE
SIZE
MIN. PIPE
SLEEVE (ID)
1/2" 1 1/4"
1 1/2"3/4" - 1"
1 1/4"
1 1/2"
2"
2 1/2"
2" - 2 1/2" 4"
6" 10"
3" - 4" 6"
OAKUM
LEAD
CAULKING
(E) CONCRETE /
MASONRY WALL
(N) PIPE THROUGH
WALL
FILL HOLE WITH
APPROPRIATE
INSULATING MATERIAL
CORE-DRILLED PIPE
PENETRATION
EXISTING MASONRY,
CONCRETE SIMILAR
EXISTING GYP BD
FILL HOLE WITH APPROPRIATE
INSULATING MATERIAL WHERE
(E) WALL IS INSULATED
PROVIDE ESCUTCHEN AT ALL
EXPOSED INTERIOR
PENETRATION
(N) PIPE THROUGH WALL
PROVIDE ESCUTCHEN
AT ALL EXPOSED
INTERIOR PENETRATION
7301TS (MAIN BEAM
SLOTTED 6" OC)
7341TS
(4' CROSS TEE
SLOTTED AT 4
LOCATIONS)
7341 (STANDARD
4' CROSS TEE)
4' -0
" 2'-0"
NOTE: 7301TS AND 7341TS REFER
TO FRAME PRODUCTS BY
ARMSTRONG CEILINGS
"METALWORKS TORSION SPRING"
PRODUCT LINE, USED AS THE
BASIS OF DESIGN.