ASBESTOS ASSESSMENT
ASBESTOS REINSPECTION REPORT
John Cochran Division 915 North Grand Boulevard
St. Louis, Missouri
Building 7
Prepared for:
St. Louis V. A. Medical Center 915 North Grand Boulevard
St. Louis, Missouri
Prepared by:
1421 Clarkview Road, Suite 100 P. O. Box 17867 Baltimore, MD 21209 Shreveport, Louisiana 71138-0867
(888) 776-0670 (318) 687-3771
INTRODUCTION
2008 ASBESTOS REINSPECTION REPORT
ST. LOUIS V. A. MEDICAL CENTER
JOHN COCHRAN AND JEFFERSON BARRACKS DIVISIONS
SCOPE OF WORK
1. The Inspector and Management Planner reviewed prior inspections and Management Plan information on file and compared this information with existing conditions for each facility.
2. This asbestos reinspection complies with the requirements of Asbestos Hazard Emergency Response Act (AHERA).
3. Each facility inspection was performed by an accredited inspector.
4. For each facility, the inspector performed the following tasks:
a. Visually reinspected and reassessed the condition of all friable known or assumed
ACBM.
b. Visually inspected material that was previously considered non-friable Asbestos- Containing Building Material (ACBM) and touched the material to determine whether it has become friable since the last inspection.
c. Identified any homogeneous areas with material that has become friable since the last inspection or reinspection.
d. The inspector collected bulk samples for analysis of newly friable material that is already assumed (not sampled) to be ACBM or collected additional bulk samples to fully assess the suspect materials.
e. Visually inspected, sampled, analyzed, and assessed the conditions of building materials that have been added to the facility since the last inspection or reinspection.
f. Assessed the condition of the newly friable material in areas where samples were collected and of newly friable material in areas assumed to be ACBM.
g. Reassessed the condition of friable known or assumed ACBM previously identified.
h. Recorded above information on field inspection forms for each facility.
5. A Management Planner reviewed the above information and performed the following required functions:
a. Reviewed each Management Plan for compliance with AHERA and verified that the plan reflects current conditions.
b. Reviewed the results of each reinspection and assessment.
c. Recommended in writing, the appropriate response actions.
d. Signed and dated the review documents, included the accreditation number of inspectors and planners, and submitted a copy to the Designated Person.
6. The following information was submitted to the Designated Person under AHERA, for inclusion in the Management Plan for each facility and, optionally, at a central office location.
a. The date of the inspection, the name and signature of the person making the inspection, state of accreditation, his or her accreditation number, and any changes in the condition of known or assumed ACBM.
b. If samples were collected, the exact locations where samples are collected during the inspection, a description of the manner used to choose sampling locations, the name and signature of each accredited inspector who collected the samples, state of accreditation, and his or her accreditation number.
c. Any assessments or reassessments made of friable material, the name and signature of the accredited inspector making the assessments, state of accreditation, and his or her accreditation number.
MANAGEMENT PLAN RECOMMENDATIONS
The following general notes are for all facilities inspected during the Asbestos Reinspection.
These notes reference any deficiencies found in prior inspections, reinspections, and the current Management Plan.
1. Removal Priorities were developed for each homogeneous area. The Removal Priorities are an indicator of priorities for future repair work or abatement work to be scheduled as financial budgets allow. Please see the 2008 Reinspection Condition and Removal Priority Table for further detail.
2. The current condition of material was listed for each homogeneous area. The condition, location, and potential for disturbance factors are used for the hazard ranking. Please see the 2008 Reinspection Condition and Removal Priority Table for the condition summaries.
3. Records for custodial, janitorial, and maintenance staff who have received two-hour awareness training should be filed in the Management Plan.
4. Any new custodial, janitorial, or maintenance staff that have the potential to come in contact with asbestos-containing materials (ACM) are required to attend a two-hour awareness training class. Records of training for new employees should be filed in the Management Plan.
5. The Designated Person is required to inform workers and building occupants at least once a year about the Management Plan. This includes information about inspections, response actions, and post-response action activities that are planned or in progress.
Provide a copy of the notification to each facility and include a copy in the Management Plan.
6. Maintenance areas (boiler rooms, janitor closets, etc.) are required to have warning labels where ACM are located. Install warning labels in these areas as needed. Some older labels may have come loose and are no longer visible. Post the labels in a prominent location.
7. Review the enclosed 2008 Reinspection Condition and Removal Priority Table for maintenance actions that may be required and to establish priorities and budgets for future repair and abatement work.
8. Periodic “Surveillance Inspections” are required every six (6) months. This inspection should indicate the condition of the material and provide recommendations for repair or potential removal. Consistency of inspections is desired and, therefore, should be performed by the same individual(s) for all facilities. An accredited inspector is not required, but is recommended. Records of Surveillance Inspections should be filed in both the administrative and facility Management Plans.
9. ”Reinspections” are required every three (3) years. Updated information should be added to the Management Plan.
10. The existing Management Plan (original) is updated by this Three-Year Reinspection.
All procedures and methods listed in the Plan are still in effect and should be followed unless specifically updated or omitted by this inspection. This includes maintenance procedures, repairs to damaged material, response actions, record keeping, surveillance inspections, and training.
11. An accredited “Supervisor” should be on staff or available on a contract basis per AHERA guidelines. Certification paperwork should be filed in the training section of the Management Plan.
12. ACBM should only be removed by licensed and accredited contractors in the State of Missouri. Response actions related to abatement activity should be filed in the Management Plan. Removal of limited amounts of asbestos is within the scope of the Management Plan by the accredited Supervisor and trained individuals.
13. Notification should be provided to “outside contractors” about ACM within the facility.
This should include such trades or services as telephone, electrical, plumbing, air conditioning, and other construction work. A form should be created for this purpose and placed in the Management Plan.
14. New building construction and portable buildings added to a facility are required to be inspected and sampled for ACM. In lieu of this, a letter from the architect, engineer, or manufacturer can be obtained that states “no ACM were specified or used in the facility”.
A copy of this letter is to be filed with the Management Plan at the facility. This letter will cancel the requirement for sampling.
15. Abatement Costs were developed for each homogeneous area and per facility. The estimated abatement cost is for budget purposes only. The cost is based on the area of material and estimated abatement costs for this material. The cost is for abatement only and does not include abatement design, air monitoring, or project observation costs.
REPORT SECTION
This report includes the following sections:
ACM Homogeneous Areas Summary Table and Drawings
This section provides a quick table reference to all asbestos-containing homogeneous areas found during the reinspection and drawings with the asbestos-containing homogeneous areas found during the 2008 asbestos reinspection.
Condition and Removal Priority Table
This section provides a table with the current condition, potential for disturbance, and removal priority for each homogeneous area.
Master Summary Table – Asbestos Bulk Samples
This table provides a listing of all asbestos bulk samples taken to date.
Asbestos-Containing Bulk Samples
This table provides a listing of all asbestos-containing bulk samples.
2008 Reinspection – Inspection Logs
This section provides the field inspection logs for samples taken during the 2008 asbestos reinspection.
Bulk Sample Location Drawings
This section provides drawings with sample locations for all asbestos bulk samples.
2008 Reinspection – Photographs
This section provides photographs of all asbestos bulk samples taken during the 2008 asbestos reinspection.
2008 Reinspection – Laboratory Reports
This section provides all laboratory analytical results.
Certifications
This section provides certifications for all Inspectors, the Management Planner who reviewed this Management Plan, and the laboratory that performed the bulk sample analysis.
Periodic Surveillance Forms
This section includes the forms completed during the periodic surveillance inspections required every six (6) months.
Management Plan Updates
This section includes the records of any asbestos abatement activities that are completed at the subject site. Notifications, daily notes, drawings, etc., should be placed in this section. This would also include air-monitoring data from asbestos abatement projects.
Response Actions
This section includes the records of any internal asbestos abatement or operation and maintenance activities that may be completed by V. A. employees. This would include any drawings, field notes, and air monitoring that was completed.
Training Documents
This section includes the records of training for the Designated Person and accredited Supervisor, as well as the two-hour awareness training for the custodial, janitorial, and maintenance staff.
Annual Notification Letters
This section includes copies of the annual Notification Letters provided to employees to inform them of the availability of the Management Plan.
Initial Inspection
This section contains the original asbestos inspection that was completed in 1994. This information was used to develop the 2008 Asbestos Reinspection.
CONTRACTORS
This 2008 Asbestos Reinspection was provided by:
Contractor: Subcontractor:
FINBACK 670, Inc. ALTEC Environmental Consultants, Inc.
1421 Clarkview Road, Suite 100 10100 Woolworth Road Baltimore, MD 21209 Keithville, LA 71047
(888) 776-0670 (Office) (318) 687-3771 (Office)
(877) 776-0670 (Fax) (318) 687-9923 (Fax)
INSPECTORS:
Brandon Odom Donald R. Joiner LA Certificate No. 9I01392 LA Certificate No. 8I01348 LA Certificate No. 9I01348
Eric Clipps Joshua Anders LA Certificate No. 9I01588 LA Certificate No. 9I01589
Justin L. Holcomb LA Certificate No. 9I00306
MANAGEMENT PLANNER:
Roy W. Dowling LA Certificate No. 9I00213 – Inspector LA Certificate No. 9P00072 – Management Planner
Accreditation Agency: Louisiana Department of Environmental Quality
ACM Homogeneous Areas Summary Table and Drawings
JOHN COCHRAN DIVISION
2008 THREE-YEAR ASBESTOS REINSPECTION
ACM HOMOGENEOUS AREAS SUMMARY TABLE
Floor Flooring Materials Surfacing Materials TSI Materials Miscellaneous Materials
Basement No ACM No ACM HMA-02 Pipe Insulation & Fittings HMA-06 Tank Insulation No ACM
Floor Flooring Materials Surfacing Materials TSI Materials Miscellaneous Materials
1 HMA-01 12x12 Floor Tile & Adhesive No ACM No ACM HMA-03 Black Pegboard
HAM-04 Transite Vent Hoods HMA-05 Lab Countertops
Building 7 - Basement
Building - 1st Floor
BASEMENT
ST. LOUIS V.A. MEDICAL CENTER
2008 THREE-YEAR REINSPECTION
THERMAL SYSTEM INSULATION (TSI) SUMMARY TABLE
Room # Description Qty S/LF Ftgs TH/DI 1 magnesia pipe lagging 226 lf 0 4.00 1 magnesia pipe lagging 3 lf 0 8.00 1 magnesia pipe lagging 3 lf 0 10.00 1 magnesia pipe lagging 20 lf 0 12.00 1 magnesia pipe lagging 3 lf 0 14.00 1 mudded joint fitting on mag pipe la 0 ea 12 12.00 1 mudded joint fitting on paperwrap l 0 ea 3 6.00 1 paper wrap pipe lagging 3 lf 0 6.00 1 tank insulation 0 sf 0 2.00 1 tank insulation 22 sf 0 2.00
001A magnesia pipe lagging 42 lf 0 4.00 001A magnesia pipe lagging 26 lf 0 12.00 001A mudded joint fitting on mag pipe la 0 ea 8 4.00 001A mudded joint fitting on mag pipe la 0 ea 4 12.00
2 magnesia pipe lagging 782 lf 0 4.00 2 magnesia pipe lagging 85 lf 0 6.00 2 mudded joint fitting on mag pipe la 0 ea 165 4.00 2 mudded joint fitting on mag pipe la 0 ea 13 6.00
1215 205
Building 7 - Basement
TOTALS
1st FLOOR
Condition and Removal Priority Table
Qualitative Ranking Numerical Rating
Good 8, 9, 10
Fair 4, 5, 6, 7
Poor 1, 2, 3
Physical Disturbance Environmental Disturbance
Low 1, 2, 3
Medium 4, 5, 6, 7
High 8, 9, 10
Qualitative Ranking Numerical Rating High 1, 2, 3
Medium 4, 5, 6, 7
Low 8, 9, 10
1 Qualitative Rankings and Quantitative (Numerical) Ratings for Current Condition
2 Qualitative Rankings and Quantitative (Numerical) Ratings for Potential for Disturbance
Assessment FactorsQualitative Ranking Numerical Rating
Description of Current Condition Surfacing material has no visible damage or small amounts of damage; covering on thermal system insulation is intact or has small amounts of damage; miscellaneous materials intact; no visible debris or small amounts of debris.
Address with on-going maintenance procedures
Maintain in good condition
Surfacing material has moderate but not extensive amounts of visible damage; covering on thermal system insulation is cut or torn, exposing moderate but not extensive amounts of insulation; moderate but not extensive damage to miscellaneous materials such as floor tile; moderate but not extensive amounts of visible dust and debris..
3 Qualitative Rankings and Quantitative (Numerical) Ratings for Removal Priority
Description of Current Condition Address short-term
Extensive damage to surfacing material; covering on thermal system insulation is cut or torn extensively and insulation itself is damage; miscellaneous materials such as floor tile extensively damaged and underlying mastic exposed; extensive amounts of dust and debris.
Accessibility: accessibility during normal operations
Activities: activities that people do and how often they do them
Vibration: vibration from operating machinery, HVAC equipment, and so forth
Air/Dust: air currents strong enough to dislodge loose ACM; airborne dust that can erode material
Corrosive: corrosive atmosphere or liquids that can erode the covering or matrix
Water Damage: water damage from leaking roof, pipe or other source
2008 THREE-YEAR ASBESTOS REINSPECTION
CONDITION AND REMOVAL PRIORITY TABLE
Rating Based On Rating Based On
HMA-02 7 Basement Pipe Insulation & Fittings Yes No 7 Damage 2 Access 6
HMA-06 7 Basement Tank Insulation Yes No 7 Damage 2 Maintenance 6
HMA-01 7 1 12x12 Floor Tile & Adhesive No Yes 10 Intact 2 Floor Maintenance 7
HMA-03 7 1 Black Pegboard No No 9 Minor Penetrations 2 Access 9
HAM-04 7 1 Transite Vent Hoods No No 10 Intact 1 Access 9
HMA-05 7 1 Lab Countertops No Yes 10 Intact 1 Maintenance 10
Building 7 - 1st Floor
Current Condition 1
Building 7 - Basement
Friable Yes/No
Accessibility Yes/No
Restricted
Potential for Disturbance 2
Homogeneous Area No. Bldg Floor Material Description
Removal Priority 3
Master Summary Table Asbestos Bulk Samples
2008 THREE-YEAR ASBESTOS REINSPECTION
SUMMARY OF BULK SAMPLES TAKEN TO DATE
Building Floor Room Sample ID Material Description
JC07 00 001 JC-07-00-T-001-02 Tank insulation JC07 00 002 JC-07-00-T-002-08 Magnesia pipe lagging JC07 00 002 JC-07-00-T-002-07 Mudded joint fitting on magnesia pipe lagging
JC07 1 107 JC-7-01-F-107-001A White 12x12 floor tile, black mastic JC07 1 107 JC-7-01-M-107-002A Transite vent hood JC07 1 107 JC-7-01-M-107-003A Black lab countertop JC07 1 106 JC-7-01-F-106-004A White 12x12 floor tile, black mastic JC07 1 106 JC-7-01-M-106-005A Brown baseboard, adhesive JC07 1 103 JC-7-01-F-103-006A White 12x12 floor tile, black mastic JC07 1 103 JC-7-01-M-103-007A Brown baseboard, adhesive JC07 1 102 JC-7-01-M-102-008A Brown baseboard, adhesive JC07 1 21 JC-7-01-F-21-009A Green 12x12 floor tile, black mastic JC07 1 10 JC-7-01-F-10-010A Gray 12x12 floor tile, black mastic JC07 1 21 JC-7-01-M-21-011A 2x2 ceiling tile JC07 1 7A JC-7-01-M-7A-012A Gray baseboard, adhesive JC07 1 7A JC-7-01-F-7A-013A Gray 12x12 floor tile, black mastic JC07 1 10 JC-7-01-M-10-014A Black lab countertop JC07 1 10 JC-7-01-M-10-015A Black peg board JC07 1 21 JC-7-01-T-21-016A 3" elbow - white wrap, white block insulation JC07 1 21 JC-7-01-T-21-017A 3" horizontal - white wrap, yellow insulation JC07 1 6 JC-7-01-M-6-018A Black lab countertop JC07 1 6 JC-7-01-M-6-019A Transite vent hood JC07 1 6 JC-7-01-F-6-020A Gray 12x12 floor tile, black mastic JC07 1 102 JC-7-01-M-102-021A 2x4 ceiling tile JC07 1 108 JC-7-01-M-108-022A 2x4 ceiling tile JC07 1 108 JC-7-01-M-108-023A 2x4 ceiling tile JC07 1 16 JC-7-01-M-16-024A Gray baseboard, adhesive JC07 1 22 JC-7-01-F-22-025A Green 12x12 floor tile, black mastic JC07 1 22 JC-7-01-M-22-026A 2x2 ceiling tile JC07 1 23 JC-7-01-M-23-027A 2x2 ceiling tile JC07 1 22 JC-7-01-F-22-028A Green 12x12 floor tile, black mastic JC07 1 23 JC-7-01-M-23-029A Gray baseboard, adhesive JC07 1 1A JC-7-01-M-1A-030A Sheetrock mud JC07 1 1 JC-7-01-M-1-031A Black peg board JC07 1 2 JC-7-01-M-2-032A Black peg board JC07 1 2 JC-7-01-M-2-033A Sheetrock mud JC07 1 19 JC-7-01-M-19-034A Sheetrock mud JC07 1 Attic JC-7-01-T-AT-035A 4" T - white wrap, white block insulation JC07 1 Attic JC-7-01-T-AT-036A 4" horizontal - white wrap, yellow insulation
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Purple = Abated ACM
1994 Initial Asbestos Inspection
2008 Asbestos Reinspection
Asbestos-Containing Bulk Samples
2008 THREE-YEAR ASBESTOS REINSPECTION
LIST OF ASBESTOS-CONTAINING SAMPLES
Building Floor Room Sample ID Material Description
JC07 00 001 JC-07-00-T-001-02 Tank insulation JC07 00 002 JC-07-00-T-002-08 Magnesia pipe lagging JC07 00 002 JC-07-00-T-002-07 Mudded joint fitting on magnesia pipe lagging
JC07 1 21 JC-7-01-F-21-009A Green 12x12 floor tile, black mastic JC07 1 10 JC-7-01-F-10-010A Gray 12x12 floor tile, black mastic JC07 1 7A JC-7-01-F-7A-013A Gray 12x12 floor tile, black mastic JC07 1 10 JC-7-01-M-10-014A Black lab countertop JC07 1 10 JC-7-01-M-10-015A Black peg board JC07 1 6 JC-7-01-M-6-019A Transite vent hood JC07 1 6 JC-7-01-F-6-020A Gray 12x12 floor tile, black mastic JC07 1 22 JC-7-01-F-22-025A Green 12x12 floor tile, black mastic JC07 1 22 JC-7-01-F-22-028A Green 12x12 floor tile, black mastic JC07 1 1 JC-7-01-M-1-031A Black peg board JC07 1 2 JC-7-01-M-2-032A Black peg board
1994 Initial Asbestos Inspection
2008 Asbestos Reinspection
2008 Reinspection Inspection Logs
Client: Date: September 17, 2008 Location: Inspector(s): Brandon Odom and Eric Clipps Address: 915 North Grand Boulevard, St. Louis, Missouri
Note:
Sample ID Material Description Floor Room Location
JC-7-01-F-107-001A White 12x12 floor tile, black mastic 1 107 Northeast corner of room 107
JC-7-01-M-107-002A Transite vent hood 1 107 Southwest corner of room 107
JC-7-01-M-107-003A Black lab countertop 1 107 Northwest corner of room107
JC-7-01-F-106-004A White 12x12 floor tile, black mastic 1 106 Northwest corner of room 106
JC-7-01-M-106-005A Brown baseboard, adhesive 1 106 Southwest corner of room 106
JC-7-01-F-103-006A White 12x12 floor tile, black mastic 1 103 Southwest quadrant of room 103
JC-7-01-M-103-007A Brown baseboard, adhesive 1 103 Northwest quadrant of room 103
JC-7-01-M-102-008A Brown baseboard, adhesive 1 102 North side of room 102
JC-7-01-F-21-009A Green 12x12 floor tile, black mastic 1 21 Southeast quadrant of room 21
JC-7-01-F-10-010A Gray 12x12 floor tile, black mastic 1 10 North side of room 10
JC-7-01-M-21-011A 2x2 ceiling tile 1 21 Center of room 21
JC-7-01-M-7A-012A Gray baseboard, adhesive 1 7A North side of room 7A
JC-7-01-F-7A-013A Gray 12x12 floor tile, black mastic 1 7A Northwest quadrant of room 7A
JC-7-01-M-10-014A Black lab countertop 1 10 Southeast quadrant of room 10
JC-7-01-M-10-015A Black pegboard 1 10 East side of room 10
ASBESTOS INSPECTION LOG
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non ACM (determined by Point Count analysis)
John Cochran Division - Building 7 St. Louis V. A. Medical Center
Address: 915 North Grand Boulevard, St. Louis, Missouri
Note:
Sample ID Material Description Floor Room Location
ASBESTOS INSPECTION LOG
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non ACM (determined by Point Count analysis)
John Cochran Division - Building 7 St. Louis V. A. Medical Center
JC-7-01-T-21-016A 3" elbow - white wrap, white block insulation 1 21 Center of room 21
JC-7-01-T-21-017A 3" horizontal - white wrap, yellow insulation 1 21 Center of room 21
JC-7-01-M-6-018A Black lab countertop 1 6 Northwest corner of room 6
JC-7-01-M-6-019A Transite vent hood 1 6 Northwest corner of room 6
JC-7-01-F-6-020A Gray 12x12 floor tile, black mastic 1 6 Northwest corner of room 6
JC-7-01-M-102-021A 2x4 ceiling tile 1 102 West side of room 102
JC-7-01-M-108-022A 2x4 ceiling tile 1 108 North side of room 108
JC-7-01-M-108-023A 2x4 ceiling tile 1 108 South side of room 108
JC-7-01-M-16-024A Gray baseboard, adhesive 1 16 Northeast corner of room 16
JC-7-01-F-22-025A Green 12x12 floor tile, black mastic 1 22 At threshold to room 16 in room 22
JC-7-01-M-22-026A 2x2 ceiling tile 1 22 Center of room 22
JC-7-01-M-23-027A 2x2 ceiling tile 1 23 Center of room 23
JC-7-01-F-22-028A Green 12x12 floor tile, black mastic 1 22 South side of room 22
JC-7-01-M-23-029A Gray baseboard, adhesive 1 23 South side of room 23
JC-7-01-M-1A-030A Sheetrock mud 1 1A North side of room 1A
Address: 915 North Grand Boulevard, St. Louis, Missouri
Note:
Sample ID Material Description Floor Room Location
ASBESTOS INSPECTION LOG
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non ACM (determined by Point Count analysis)
John Cochran Division - Building 7 St. Louis V. A. Medical Center
JC-7-01-M-1-031A Black pegboard 1 1 Center of room 1
JC-7-01-M-2-032A Black pegboard 1 2 West side of room 2
JC-7-01-M-2-033A Sheetrock mud 1 2 North side of room 2
JC-7-01-M-19-034A Sheetrock mud 1 19 Southeast corner of room 19
JC-7-01-T-AT-035A 4" T - white wrap, white block insulation 1 Attic In attic above room 4
JC-7-01-T-AT-036A 4" horizontal - white wrap, yellow insulation 1 Attic In attic above room 4
GOOD = Surfacing material has no visible damage or small amounts of damage; covering on thermal system insulation is intact or has small amounts of damage; miscellaneous materials intact; no visible debris or small amounts of debris. FAIR = Surfacing material has moderate but not extensive amounts of visible damage; covering on thermal system insulation is cut or torn, exposing moderate but not extensive amounts of insulation; moderate but not extensive damage to miscellaneous materials such as floor tile; moderate but not extensive amounts of visible dust and debris. POOR = Extensive damage to surfacing material; covering on thermal system insulation is cut or torn extensively and insulation itself is damaged; miscellaneous materials such as floor tile extensively damaged and underlying mastic exposed; extensive amounts of dust and debris.
Material Category: F = Flooring S = Surfacing T = TSI M = Miscellaneous Friability: F=Friable NF=Non-Friable Condition: Good = 8, 9, 10 Fair = 4, 5, 6, 7 Poor = 1, 2, 3
Red = Asbestos-Containing Material Blue = Non Asbestos-Containing MaterialPlease use the following guidelines when reading this report:
Bulk Sample Location Drawings
BASEMENT
1st FLOOR
2008 Reinspection Photographs
BUILDING 7
sample does not contain asbestos
JC-7-01-F-107-001A JC-7-01-M-107-002A
JC-7-01-M-107-003A JC-7-01-F-106-004A
sample contains asbestos
JC-7-01-M-106-005A JC-7-01-F-103-006A
JC-7-01-M-103-007A JC-7-01-M-102-008A
JC-7-01-F-21-009A JC-7-01-F-10-010A
JC-7-01-M-21-011A JC-7-01-M-7A-012A
JC-7-01-F-7A-013A JC-7-01-M-10-014A
JC-7-01-M-10-015A JC-7-01-T-21-016A and JC-7-01-T-21-017A
JC-7-01-M-6-018A, JC-7-01-M-6-019A, and JC-7-01-F-6-020A JC-7-01-M-102-021A
JC-7-01-M-108-022A JC-7-01-M-108-023A
JC-7-01-M-16-024A JC-7-01-F-22-025A
JC-7-01-M-22-026A JC-7-01-M-23-027A
JC-7-01-F-22-028A JC-7-01-M-23-029A
JC-7-01-M-1A-030A JC-7-01-M-1-031A
JC-7-01-M-2-032A JC-7-01-M-2-033A
JC-7-01-M-19-034A JC-7-01-T-AT-035A and JC-7-01-T-AT-036A
2008 Reinspection Laboratory Reports
Sample Location Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804605
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
2920 Truly Lane Shreveport, LA 71138
Customer PO:
Received: 09/18/08 4:50 PM
08-14529 VAMC Reinspection JC Building 7
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/18/2008Analysis Date:
Report Date: 9/19/2008
EMSL Analytical, Inc.
11040A Lin-Valle Drive, Saint Louis, MO 63123 Phone: (314) 845-8910 Fax: (314) 845-6459 Email: saintlouislab@emsl.com
JC-7-01-F-107-
001A floortile 390804605-0001
WHT 12X12 FT
W/BLK MASTIC
White None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
JC-7-01-F-107-
001A adhesive 390804605-0001A
WHT 12X12 FT
W/BLK MASTIC
Black None Detected
Non-Fibrous
Heterogeneous
Cellulose9% Non-fibrous (other)91%
JC-7-01-M-107-
002A 390804605-0002
TRANSITE VENT
HOOD
Gray None Detected
Non-Fibrous
Heterogeneous
Cellulose10% Wollastonite9%
Non-fibrous (other)81%
JC-7-01-M-107-
003A 390804605-0003
BLK LAB
COUNTERTOP
Black None Detected
Non-Fibrous
Heterogeneous
Cellulose10% Wollastonite9%
Non-fibrous (other)81%
JC-7-01-F-106-
004A floortile 390804605-0004
WHT 12X12 FT
W/BLK MASTIC
White None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
JC-7-01-F-106-
004A adhesive 390804605-0004A
WHT 12X12 FT
W/BLK MASTIC
Black None Detected
Non-Fibrous
Heterogeneous
Cellulose9% Non-fibrous (other)91%
JC-7-01-M-106-
005A covebase 390804605-0005
BRN
BASEBOARD
AND ADHESIVE
Brown None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
Analysis performed by EMSL St. Louis (AIHA #102636, NVLAP # 200742-0, CA ELAP #2668)
Sue Ferrario (51) mailto:saintlouislab@emsl.com
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804605
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
2920 Truly Lane Shreveport, LA 71138
Customer PO:
Received: 09/18/08 4:50 PM
08-14529 VAMC Reinspection JC Building 7
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/18/2008Analysis Date:
Report Date: 9/19/2008
EMSL Analytical, Inc.
11040A Lin-Valle Drive, Saint Louis, MO 63123 Phone: (314) 845-8910 Fax: (314) 845-6459 Email: saintlouislab@emsl.com
JC-7-01-M-106-
005A adhesive 390804605-0005A
BRN
BASEBOARD
AND ADHESIVE
Yellow None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
JC-7-01-F-103-
006A floortile 390804605-0006
WHT 12X12 FT
W/BLK MASTIC
White None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
JC-7-01-F-103-
006A adhesive 390804605-0006A
WHT 12X12 FT
W/BLK MASTIC
Black None Detected
Non-Fibrous
Heterogeneous
Cellulose9% Non-fibrous (other)91%
JC-7-01-M-103-
007A covebase 390804605-0007
BRN
BASEBOARD
AND ADHESIVE
Brown None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
JC-7-01-M-103-
007A adhesive 390804605-0007A
BRN
BASEBOARD
AND ADHESIVE
Yellow None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
JC-7-01-M-102-
008A covebase 390804605-0008
BRN
BASEBOARD
AND ADHESIVE
Brown None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
JC-7-01-M-102-
008A adhesive 390804605-0008A
BRN
BASEBOARD
AND ADHESIVE
Yellow None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
Analysis performed by EMSL St. Louis (AIHA #102636, NVLAP # 200742-0, CA ELAP #2668)
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804605
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
2920 Truly Lane Shreveport, LA 71138
Customer PO:
Received: 09/18/08 4:50 PM
08-14529 VAMC Reinspection JC Building 7
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/18/2008Analysis Date:
Report Date: 9/19/2008
EMSL Analytical, Inc.
11040A Lin-Valle Drive, Saint Louis, MO 63123 Phone: (314) 845-8910 Fax: (314) 845-6459 Email: saintlouislab@emsl.com
JC-7-01-F-21-009A
floortile 390804605-0009
GRN 12X12 FT
W/BLK MASTIC
Green Non-Fibrous
Heterogeneous
Chrysotile6%Non-fibrous (other)94%
JC-7-01-F-21-009A
adhesive 390804605-0009A
GRN 12X12 FT
W/BLK MASTIC
Black Non-Fibrous
Heterogeneous
Chrysotile9%Non-fibrous (other)89% Quartz2%
JC-7-01-F-10-010A
floortile 390804605-0010
GREY 12X12 FT
W/BLK MASTIC
Gray Non-Fibrous
Heterogeneous
Chrysotile9%Non-fibrous (other)91%
JC-7-01-F-10-010A
adhesive 390804605-0010A
GREY 12X12 FT
W/BLK MASTIC
Black Non-Fibrous
Heterogeneous
Chrysotile12%Non-fibrous (other)86% Quartz2%
JC-7-01-M-21-011A
390804605-0011
2X2 CT Various None Detected
Fibrous Heterogeneous
Cellulose28% Min. Wool37%
Non-fibrous (other)7% Perlite28%
JC-7-01-M-7A-
012A covebase 390804605-0012
GREY
BASEBOARD
AND ADHESIVE
Gray None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
JC-7-01-M-7A-
012A adhesive 390804605-0012A
GREY
BASEBOARD
AND ADHESIVE
Brown None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)98% Quartz2%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
Analysis performed by EMSL St. Louis (AIHA #102636, NVLAP # 200742-0, CA ELAP #2668)
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804605
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
2920 Truly Lane Shreveport, LA 71138
Customer PO:
Received: 09/18/08 4:50 PM
08-14529 VAMC Reinspection JC Building 7
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/18/2008Analysis Date:
Report Date: 9/19/2008
EMSL Analytical, Inc.
11040A Lin-Valle Drive, Saint Louis, MO 63123 Phone: (314) 845-8910 Fax: (314) 845-6459 Email: saintlouislab@emsl.com
JC-7-01-F-7A-013A
floortile 390804605-0013
GREY 12X12 FT
W/BLK MASTIC
Gray Non-Fibrous
Heterogeneous
Chrysotile9%Non-fibrous (other)91%
JC-7-01-F-7A-013A
adhesive 390804605-0013A
GREY 12X12 FT
W/BLK MASTIC
Black Non-Fibrous
Heterogeneous
Chrysotile9%Non-fibrous (other)89% Quartz2%
JC-7-01-M-10-014A
390804605-0014
BLK LAB
COUNTERTOP
Black Non-Fibrous Heterogeneous
Amosite<1% Chrysotile19%
Non-fibrous (other)81%
JC-7-01-M-10-015A
390804605-0015
BLK PEG BOARD Black Non-Fibrous Heterogeneous
Chrysotile29%Non-fibrous (other)71%
JC-7-01-T-21-016A
390804605-0016
3" ELBOW, WHT
WRAP, WHT
BLOCK INS
White None Detected
Non-Fibrous Heterogeneous
Fibrous (other)18% Min. Wool27%
Non-fibrous (other)55%
JC-7-01-T-21-017A
390804605-0017
3" HZ, WHT
WRAP, YLW INS
Various None Detected
Fibrous Heterogeneous
Cellulose4% Glass2% Min. Wool86%
Non-fibrous (other)8%
JC-7-01-M-6-018A
390804605-0018
BLK LAB
COUNTERTOP
Black None Detected
Non-Fibrous Heterogeneous
Non-fibrous (other)81% Quartz19%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
Analysis performed by EMSL St. Louis (AIHA #102636, NVLAP # 200742-0, CA ELAP #2668)
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804605
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
2920 Truly Lane Shreveport, LA 71138
Customer PO:
Received: 09/18/08 4:50 PM
08-14529 VAMC Reinspection JC Building 7
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/18/2008Analysis Date:
Report Date: 9/19/2008
EMSL Analytical, Inc.
11040A Lin-Valle Drive, Saint Louis, MO 63123 Phone: (314) 845-8910 Fax: (314) 845-6459 Email: saintlouislab@emsl.com
JC-7-01-M-6-019A
390804605-0019
TRANSITE VENT
HOOD
Gray Non-Fibrous Heterogeneous
Chrysotile19%Non-fibrous (other)81%
JC-7-01-F-6-020A
floortile 390804605-0020
GREY 12X12 FT
W/BLK MASTIC
Gray Non-Fibrous
Heterogeneous
Chrysotile12%Non-fibrous (other)88%
JC-7-01-F-6-020A
adhesive 390804605-0020A
GREY 12X12 FT
W/BLK MASTIC
Black Non-Fibrous
Heterogeneous
Chrysotile12%Non-fibrous (other)88%
JC-7-01-M-102-
021A 390804605-0021
2X4 CT Various None Detected
Fibrous
Heterogeneous
Cellulose28% Min. Wool37%
Non-fibrous (other)7% Perlite28%
JC-7-01-M-108-
022A 390804605-0022
2X4 CT Various None Detected
Fibrous
Heterogeneous
Cellulose28% Min. Wool37%
Non-fibrous (other)7% Perlite28%
JC-7-01-M-108-
023A 390804605-0023
2X4 CT Various None Detected
Fibrous
Heterogeneous
Cellulose28% Min. Wool37%
Non-fibrous (other)7% Perlite28%
JC-7-01-M-16-024A
covebase 390804605-0024
GREY
BASEBOARD
AND ADHESIVE
Gray None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
Analysis performed by EMSL St. Louis (AIHA #102636, NVLAP # 200742-0, CA ELAP #2668)
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804605
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
2920 Truly Lane Shreveport, LA 71138
Customer PO:
Received: 09/18/08 4:50 PM
08-14529 VAMC Reinspection JC Building 7
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/18/2008Analysis Date:
Report Date: 9/19/2008
EMSL Analytical, Inc.
11040A Lin-Valle Drive, Saint Louis, MO 63123 Phone: (314) 845-8910 Fax: (314) 845-6459 Email: saintlouislab@emsl.com
JC-7-01-M-16-024A
adhesive 390804605-0024A
GREY
BASEBOARD
AND ADHESIVE
Brown None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)98% Quartz2%
JC-7-01-F-22-025A
floortile 390804605-0025
GRN 12X12 FT
W/BLK MASTIC
Green Non-Fibrous
Heterogeneous
Chrysotile6%Non-fibrous (other)94%
JC-7-01-F-22-025A
adhesive 390804605-0025A
GRN 12X12 FT
W/BLK MASTIC
Black Non-Fibrous
Heterogeneous
Chrysotile19%Non-fibrous (other)79% Quartz2%
JC-7-01-M-22-026A
390804605-0026
2X2 CT Various None Detected
Fibrous Heterogeneous
Cellulose28% Min. Wool37%
Non-fibrous (other)7% Perlite28%
JC-7-01-M-23-027A
390804605-0027
2X2 CT Various None Detected
Fibrous Heterogeneous
Cellulose28% Min. Wool37%
Non-fibrous (other)7% Perlite28%
JC-7-01-F-22-028A
floortile 390804605-0028
GRN 12X12 FT
W/BLK MASTIC
Green Non-Fibrous
Heterogeneous
Chrysotile6%Non-fibrous (other)94%
JC-7-01-F-22-028A
adhesive 390804605-0028A
GRN 12X12 FT
W/BLK MASTIC
Black Non-Fibrous
Heterogeneous
Chrysotile12%Non-fibrous (other)86% Quartz2%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
Analysis performed by EMSL St. Louis (AIHA #102636, NVLAP # 200742-0, CA ELAP #2668)
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804605
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
2920 Truly Lane Shreveport, LA 71138
Customer PO:
Received: 09/18/08 4:50 PM
08-14529 VAMC Reinspection JC Building 7
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/18/2008Analysis Date:
Report Date: 9/19/2008
EMSL Analytical, Inc.
11040A Lin-Valle Drive, Saint Louis, MO 63123 Phone: (314) 845-8910 Fax: (314) 845-6459 Email: saintlouislab@emsl.com
JC-7-01-M-23-029A
covebase 390804605-0029
GREY
BASEBOARD
AND ADHESIVE
Gray None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
JC-7-01-M-23-029A
adhesive 390804605-0029A
GREY
BASEBOARD
AND ADHESIVE
Brown None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)94% Quartz6%
JC-7-01-M-1A-030A
390804605-0030
SHEETROCK
MUD
White None Detected
Non-Fibrous Heterogeneous
Mica4% Non-fibrous (other)96%
JC-7-01-M-1-031A
390804605-0031
BLK PEG BOARD Black Non-Fibrous Heterogeneous
Amosite<1% Chrysotile19%
Non-fibrous (other)81%
JC-7-01-M-2-032A
390804605-0032
BLK PEG BOARD Black Non-Fibrous Heterogeneous
Amosite<1% Chrysotile19%
Non-fibrous (other)81%
JC-7-01-M-2-033A
390804605-0033
SHEETROCK
MUD
White Non-Fibrous Heterogeneous
Chrysotile<1%Mica4% Non-fibrous (other)96%
JC-7-01-M-19-034A
390804605-0034
SHEETROCK
MUD
White Non-Fibrous Heterogeneous
Chrysotile<1%Mica4% Non-fibrous (other)96%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
Analysis performed by EMSL St. Louis (AIHA #102636, NVLAP # 200742-0, CA ELAP #2668)
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804605
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
2920 Truly Lane Shreveport, LA 71138
Customer PO:
Received: 09/18/08 4:50 PM
08-14529 VAMC Reinspection JC Building 7
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/18/2008Analysis Date:
Report Date: 9/19/2008
EMSL Analytical, Inc.
11040A Lin-Valle Drive, Saint Louis, MO 63123 Phone: (314) 845-8910 Fax: (314) 845-6459 Email: saintlouislab@emsl.com
JC-7-01-T-AT-035A
390804605-0035
4" T, WHT
WRAP, WHT
BLOCK INS
White None Detected
Non-Fibrous Heterogeneous
Fibrous (other)18% Min. Wool27%
Non-fibrous (other)55%
JC-7-01-T-AT-036A
390804605-0036
4" HZ, WHT
WRAP, YLW INS
Various None Detected
Fibrous Heterogeneous
Cellulose4% Glass2% Min. Wool86%
Non-fibrous (other)8%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
THIS IS THE LAST PAGE OF THE REPORT.
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.