ASBESTOS ASSESSMENT
ASBESTOS REINSPECTION REPORT
Jefferson Barracks Division 1 Jefferson Barracks Drive
St. Louis, Missouri
Building 2
Prepared for:
St. Louis V. A. Medical Center 1 Jefferson Barracks Drive
St. Louis, Missouri
Prepared by:
1421 Clarkview Road, Suite 100 P. O. Box 17867 Baltimore, MD 21209 Shreveport, Louisiana 71138-0867
(888) 776-0670 (318) 687-3771
INTRODUCTION
2008 ASBESTOS REINSPECTION REPORT
ST. LOUIS V. A. MEDICAL CENTER
JOHN COCHRAN AND JEFFERSON BARRACKS DIVISIONS
SCOPE OF WORK
1. The Inspector and Management Planner reviewed prior inspections and Management Plan information on file and compared this information with existing conditions for each facility.
2. This asbestos reinspection complies with the requirements of Asbestos Hazard Emergency Response Act (AHERA).
3. Each facility inspection was performed by an accredited inspector.
4. For each facility, the inspector performed the following tasks:
a. Visually reinspected and reassessed the condition of all friable known or assumed
ACBM.
b. Visually inspected material that was previously considered non-friable Asbestos- Containing Building Material (ACBM) and touched the material to determine whether it has become friable since the last inspection.
c. Identified any homogeneous areas with material that has become friable since the last inspection or reinspection.
d. The inspector collected bulk samples for analysis of newly friable material that is already assumed (not sampled) to be ACBM or collected additional bulk samples to fully assess the suspect materials.
e. Visually inspected, sampled, analyzed, and assessed the conditions of building materials that have been added to the facility since the last inspection or reinspection.
f. Assessed the condition of the newly friable material in areas where samples were collected and of newly friable material in areas assumed to be ACBM.
g. Reassessed the condition of friable known or assumed ACBM previously identified.
h. Recorded above information on field inspection forms for each facility.
5. A Management Planner reviewed the above information and performed the following required functions:
a. Reviewed each Management Plan for compliance with AHERA and verified that the plan reflects current conditions.
b. Reviewed the results of each reinspection and assessment.
c. Recommended in writing, the appropriate response actions.
d. Signed and dated the review documents, included the accreditation number of inspectors and planners, and submitted a copy to the Designated Person.
6. The following information was submitted to the Designated Person under AHERA, for inclusion in the Management Plan for each facility and, optionally, at a central office location.
a. The date of the inspection, the name and signature of the person making the inspection, state of accreditation, his or her accreditation number, and any changes in the condition of known or assumed ACBM.
b. If samples were collected, the exact locations where samples are collected during the inspection, a description of the manner used to choose sampling locations, the name and signature of each accredited inspector who collected the samples, state of accreditation, and his or her accreditation number.
c. Any assessments or reassessments made of friable material, the name and signature of the accredited inspector making the assessments, state of accreditation, and his or her accreditation number.
MANAGEMENT PLAN RECOMMENDATIONS
The following general notes are for all facilities inspected during the Asbestos Reinspection.
These notes reference any deficiencies found in prior inspections, reinspections, and the current Management Plan.
1. Removal Priorities were developed for each homogeneous area. The Removal Priorities are an indicator of priorities for future repair work or abatement work to be scheduled as financial budgets allow. Please see the 2008 Reinspection Condition and Removal Priority Table for further detail.
2. The current condition of material was listed for each homogeneous area. The condition, location, and potential for disturbance factors are used for the hazard ranking. Please see the 2008 Reinspection Condition and Removal Priority Table for the condition summaries.
3. Records for custodial, janitorial, and maintenance staff who have received two-hour awareness training should be filed in the Management Plan.
4. Any new custodial, janitorial, or maintenance staff that have the potential to come in contact with asbestos-containing materials (ACM) are required to attend a two-hour awareness training class. Records of training for new employees should be filed in the Management Plan.
5. The Designated Person is required to inform workers and building occupants at least once a year about the Management Plan. This includes information about inspections, response actions, and post-response action activities that are planned or in progress.
Provide a copy of the notification to each facility and include a copy in the Management Plan.
6. Maintenance areas (boiler rooms, janitor closets, etc.) are required to have warning labels where ACM are located. Install warning labels in these areas as needed. Some older labels may have come loose and are no longer visible. Post the labels in a prominent location.
7. Review the enclosed 2008 Reinspection Condition and Removal Priority Table for maintenance actions that may be required and to establish priorities and budgets for future repair and abatement work.
8. Periodic “Surveillance Inspections” are required every six (6) months. This inspection should indicate the condition of the material and provide recommendations for repair or potential removal. Consistency of inspections is desired and, therefore, should be performed by the same individual(s) for all facilities. An accredited inspector is not required, but is recommended. Records of Surveillance Inspections should be filed in both the administrative and facility Management Plans.
9. ”Reinspections” are required every three (3) years. Updated information should be added to the Management Plan.
10. The existing Management Plan (original) is updated by this Three-Year Reinspection.
All procedures and methods listed in the Plan are still in effect and should be followed unless specifically updated or omitted by this inspection. This includes maintenance procedures, repairs to damaged material, response actions, record keeping, surveillance inspections, and training.
11. An accredited “Supervisor” should be on staff or available on a contract basis per AHERA guidelines. Certification paperwork should be filed in the training section of the Management Plan.
12. ACBM should only be removed by licensed and accredited contractors in the State of Missouri. Response actions related to abatement activity should be filed in the Management Plan. Removal of limited amounts of asbestos is within the scope of the Management Plan by the accredited Supervisor and trained individuals.
13. Notification should be provided to “outside contractors” about ACM within the facility.
This should include such trades or services as telephone, electrical, plumbing, air conditioning, and other construction work. A form should be created for this purpose and placed in the Management Plan.
14. New building construction and portable buildings added to a facility are required to be inspected and sampled for ACM. In lieu of this, a letter from the architect, engineer, or manufacturer can be obtained that states “no ACM were specified or used in the facility”.
A copy of this letter is to be filed with the Management Plan at the facility. This letter will cancel the requirement for sampling.
15. Abatement Costs were developed for each homogeneous area and per facility. The estimated abatement cost is for budget purposes only. The cost is based on the area of material and estimated abatement costs for this material. The cost is for abatement only and does not include abatement design, air monitoring, or project observation costs.
REPORT SECTION
This report includes the following sections:
ACM Homogeneous Areas Summary Table and Drawings
This section provides a quick table reference to all asbestos-containing homogeneous areas found during the reinspection and drawings with the asbestos-containing homogeneous areas found during the 2008 asbestos reinspection.
Condition and Removal Priority Table
This section provides a table with the current condition, potential for disturbance, and removal priority for each homogeneous area.
Master Summary Table – Asbestos Bulk Samples
This table provides a listing of all asbestos bulk samples taken to date.
Asbestos-Containing Bulk Samples
This table provides a listing of all asbestos-containing bulk samples.
2008 Reinspection – Inspection Logs
This section provides the field inspection logs for samples taken during the 2008 asbestos reinspection.
Bulk Sample Location Drawings
This section provides drawings with sample locations for all asbestos bulk samples.
2008 Reinspection – Photographs
This section provides photographs of all asbestos bulk samples taken during the 2008 asbestos reinspection.
2008 Reinspection – Laboratory Reports
This section provides all laboratory analytical results.
Certifications
This section provides certifications for all Inspectors, the Management Planner who reviewed this Management Plan, and the laboratory that performed the bulk sample analysis.
Periodic Surveillance Forms
This section includes the forms completed during the periodic surveillance inspections required every six (6) months.
Management Plan Updates
This section includes the records of any asbestos abatement activities that are completed at the subject site. Notifications, daily notes, drawings, etc., should be placed in this section. This would also include air-monitoring data from asbestos abatement projects.
Response Actions
This section includes the records of any internal asbestos abatement or operation and maintenance activities that may be completed by V. A. employees. This would include any drawings, field notes, and air monitoring that was completed.
Training Documents
This section includes the records of training for the Designated Person and accredited Supervisor, as well as the two-hour awareness training for the custodial, janitorial, and maintenance staff.
Annual Notification Letters
This section includes copies of the annual Notification Letters provided to employees to inform them of the availability of the Management Plan.
Initial Inspection
This section contains the original asbestos inspection that was completed in 1994. This information was used to develop the 2008 Asbestos Reinspection.
CONTRACTORS
This 2008 Asbestos Reinspection was provided by:
Contractor: Subcontractor:
FINBACK 670, Inc. ALTEC Environmental Consultants, Inc.
1421 Clarkview Road, Suite 100 10100 Woolworth Road Baltimore, MD 21209 Keithville, LA 71047
(888) 776-0670 (Office) (318) 687-3771 (Office)
(877) 776-0670 (Fax) (318) 687-9923 (Fax)
INSPECTORS:
Brandon Odom Donald R. Joiner LA Certificate No. 9I01392 LA Certificate No. 8I01348 LA Certificate No. 9I01348
Eric Clipps Joshua Anders LA Certificate No. 9I01588 LA Certificate No. 9I01589
Justin L. Holcomb LA Certificate No. 9I00306
MANAGEMENT PLANNER:
Roy W. Dowling LA Certificate No. 9I00213 – Inspector LA Certificate No. 9P00072 – Management Planner
Accreditation Agency: Louisiana Department of Environmental Quality
ACM Homogeneous Areas Summary Table and Drawings
JEFFERSON BARRACKS DIVISION
2008 THREE-YEAR ASBESTOS REINSPECTION
ACM HOMOGENEOUS AREAS SUMMARY TABLE
Floor Flooring Materials Surfacing Materials TSI Materials Miscellaneous Materials
Basement HMA-01 9x9 Floor Tile & Adhesive No ACM HMA-05 Pipe Insulation & Fittings HMA-06 Fire Door (Assumed)
Floor Flooring Materials Surfacing Materials TSI Materials Miscellaneous Materials
1 HMA-02 12x12 Floor Tile & Adhesive HMA-03 9x9 Floor Tile No ACM HMA-05 Pipe Insulation & Fittings HMA-06 Fire Door (Assumed)
Floor Flooring Materials Surfacing Materials TSI Materials Miscellaneous Materials
HMA-02 12x12 Floor Tile & Adhesive
HMA-03 9x9 Floor Tile HMA-04 Flooring Adhesive
No ACM HMA-05 Pipe Insulation & Fittings HMA-06 Fire Door (Assumed)
Floor Flooring Materials Surfacing Materials TSI Materials Miscellaneous Materials
HMA-02 12x12 Floor Tile & Adhesive
HMA-03 9x9 Floor Tile HMA-04 Flooring Adhesive
No ACM No ACM HMA-06 Fire Door (Assumed)
Floor Flooring Materials Surfacing Materials TSI Materials Miscellaneous Materials
Attic No ACM No ACM No ACM No ACM
Building 2 - Attic
Building 2 - Basement
Building 2 - 1st Floor
Building 2 - 2nd Floor
Building 2 - 3rd Floor
BASEMENT
ST. LOUIS V.A. MEDICAL CENTER
2008 THREE-YEAR REINSPECTION
THERMAL SYSTEM INSULATION (TSI) SUMMARY TABLE
Room # Description Qty S/LF Ftgs TH/DI G02-02-JB cardboard wrap pipe lagging 45 lf 0 2.00 G02-02-JB cardboard wrap pipe lagging 75 lf 0 4.00 G02-02-JB magnesia pipe lagging 70 lf 0 4.00 G02-02-JB magnesia pipe lagging 70 lf 0 6.00 G02-02-JB magnesia pipe lagging 35 lf 0 8.00 G02-02-JB mudded joint ftg on cardboard lag 0 ea 20 2.00 G02-02-JB mudded joint ftg on cardboard lag 0 ea 20 4.00 G02-02-JB mudded joint ftg on mag pipe lagging 0 ea 38 4.00 G02-02-JB mudded joint ftg on mag pipe lagging 0 ea 11 6.00 G02-02-JB mudded joint ftg on mag pipe lagging 0 ea 5 8.00
G03-02-JB magnesia pipe lagging 10 lf 0 4.00 G03-02-JB magnesia pipe lagging 6 lf 0 6.00 G03-02-JB mudded joint ftg on mag pipe lagging 0 ea 4 4.00 G03-02-JB mudded joint ftg on mag pipe lagging 0 ea 1 6.00
G04-02-JB cardboard wrap pipe lagging 1 lf 0 2.00 G04-02-JB mudded joint ftg on cardboard lag 0 ea 1 2.00
G05-02-JB cardboard wrap pipe lagging 35 lf 0 4.00 G05-02-JB magnesia pipe lagging 5 lf 0 4.00 G05-02-JB magnesia pipe lagging 12 lf 0 6.00 G05-02-JB mudded joint ftg on cardboard lag 0 ea 6 4.00 G05-02-JB mudded joint ftg on mag pipe lagging 0 ea 2 4.00
G05A-02-JB cardboard wrap pipe lagging 2 lf 0 4.00 G05A-02-JB mudded joint ftg on cardboard lag 0 ea 1 4.00
G05B-02-JB magnesia pipe lagging 4 lf 0 6.00
G06-02-JB cardboard wrap pipe lagging 25 lf 0 4.00 G06-02-JB cardboard wrap pipe lagging 13 lf 0 6.00 G06-02-JB mudded joint ftg on cardboard lag 0 ea 2 4.00 G06-02-JB mudded joint ftg on cardboard lag 0 ea 2 6.00
G07-02-JB cardboard wrap pipe lagging 35 lf 0 2.00 G07-02-JB cardboard wrap pipe lagging 8 lf 0 4.00 G07-02-JB cardboard wrap pipe lagging 50 lf 0 6.00 G07-02-JB magnesia pipe lagging 85 lf 0 6.00 G07-02-JB mudded joint ftg on cardboard lag 0 ea 28 2.00 G07-02-JB mudded joint ftg on cardboard lag 0 ea 12 4.00 G07-02-JB mudded joint ftg on cardboard lag 0 ea 14 6.00
Building 2 - Basement
2008 THREE-YEAR REINSPECTION
THERMAL SYSTEM INSULATION (TSI) SUMMARY TABLE
Room # Description Qty S/LF Ftgs TH/DI G07-02-JB mudded joint ftg on mag pipe lagging 0 ea 14 8.00
G09-02-JB magnesia pipe lagging 10 lf 0 2.00 G09-02-JB magnesia pipe lagging 15 lf 0 6.00 G09-02-JB mudded joint ftg on cardboard lag 0 ea 2 2.00 G09-02-JB mudded joint ftg on mag pipe lagging 0 ea 2 6.00
H002-02-JB cardboard wrap pipe lagging 5 lf 0 2.00 H002-02-JB cardboard wrap pipe lagging 30 lf 0 4.00 H002-02-JB cardboard wrap pipe lagging 30 lf 0 6.00 H002-02-JB mudded joint ftg on cardboard lag 0 ea 6 2.00 H002-02-JB mudded joint ftg on cardboard lag 0 ea 2 4.00 H002-02-JB mudded joint ftg on cardboard lag 0 ea 2 6.00
676 195TOTALS
1st FLOOR
2008 THREE-YEAR REINSPECTION
THERMAL SYSTEM INSULATION (TSI) SUMMARY TABLE
Room # Description Qty S/LF Ftgs TH/DI 107-02-JB magnesia pipe lagging 30 lf 0 4.00
118A-02-JB magnesia pipe lagging 5 lf 0 4.00
120A-02-JB cardboard wrap pipe lagging 5 lf 0 4.00
40 0
Building 2 - 1st Floor
TOTALS
2ND FLOOR
2008 THREE-YEAR REINSPECTION
THERMAL SYSTEM INSULATION (TSI) SUMMARY TABLE
Room # Description Qty S/LF Ftgs TH/DI 210-02-JB magnesia pipe lagging 10 lf 0 4.00 210-02-JB mudded joint ftg on mag pipe lagging 0 ea 3 4.00
212B-02-JB magnesia pipe lagging 15 lf 0 4.00 212B-02-JB mudded joint ftg on mag pipe lagging 0 ea 8 4.00
25 11
Building 2 - 2nd Floor
TOTALS
3rd FLOOR
Condition and Removal Priority Table
Qualitative Ranking Numerical Rating
Good 8, 9, 10
Fair 4, 5, 6, 7
Poor 1, 2, 3
Physical Disturbance Environmental Disturbance
Low 1, 2, 3
Medium 4, 5, 6, 7
High 8, 9, 10
Qualitative Ranking Numerical Rating High 1, 2, 3
Medium 4, 5, 6, 7
Low 8, 9, 10
1 Qualitative Rankings and Quantitative (Numerical) Ratings for Current Condition
2 Qualitative Rankings and Quantitative (Numerical) Ratings for Potential for Disturbance
Assessment FactorsQualitative Ranking Numerical Rating
Description of Current Condition Surfacing material has no visible damage or small amounts of damage; covering on thermal system insulation is intact or has small amounts of damage; miscellaneous materials intact; no visible debris or small amounts of debris.
Address with on-going maintenance procedures
Maintain in good condition
Surfacing material has moderate but not extensive amounts of visible damage; covering on thermal system insulation is cut or torn, exposing moderate but not extensive amounts of insulation; moderate but not extensive damage to miscellaneous materials such as floor tile; moderate but not extensive amounts of visible dust and debris..
3 Qualitative Rankings and Quantitative (Numerical) Ratings for Removal Priority
Description of Current Condition Address short-term
Extensive damage to surfacing material; covering on thermal system insulation is cut or torn extensively and insulation itself is damage; miscellaneous materials such as floor tile extensively damaged and underlying mastic exposed; extensive amounts of dust and debris.
Accessibility: accessibility during normal operations
Activities: activities that people do and how often they do them
Vibration: vibration from operating machinery, HVAC equipment, and so forth
Air/Dust: air currents strong enough to dislodge loose ACM; airborne dust that can erode material
Corrosive: corrosive atmosphere or liquids that can erode the covering or matrix
Water Damage: water damage from leaking roof, pipe or other source
2008 THREE-YEAR ASBESTOS REINSPECTION
CONDITION AND REMOVAL PRIORITY TABLE
Rating Based On Rating Based On
HMA-01 2 Basement 9x9 Floor Tile & Adhesive No Yes 10 Intact 2 Floor Maintenance 7
HMA-05 2 Basement Pipe Insulation & Fittings Yes No 7 Damage 2 Access 6
HMA-06 2 Basement Fire Door (Assumed) No Restricted 10 Intact 1 Maintenance 10
HMA-02 2 1 12x12 Floor Tile & Adhesive No Yes 10 Intact 2 Floor Maintenance 7
HMA-03 2 1 9x9 Floor Tile No Yes 10 Intact 2 Floor Maintenance 7
HMA-05 2 1 Pipe Insulation & Fittings Yes No 7 Damage 2 Access 6
HMA-06 2 1 Fire Door (Assumed) No Restricted 10 Intact 1 Maintenance 10
HMA-02 2 2 12x12 Floor Tile & Adhesive No Yes 10 Intact 2 Floor Maintenance 7
HMA-03 2 2 9x9 Floor Tile No Yes 10 Intact 2 Floor Maintenance 7
HMA-04 2 2 Flooring Adhesive No No 10 Intact 1 Access 9
HMA-05 2 2 Pipe Insulation & Fittings Yes No 7 Damage 2 Access 6
HMA-06 2 2 Fire Door (Assumed) No Restricted 10 Intact 1 Maintenance 10
Friable Yes/No
Accessibility Yes/No
Restricted
Potential for Disturbance 2
Homogeneous Area No. Bldg Floor
Building 2 - 2nd Floor
Material Description Removal Priority 3
Building 2 - 1st Floor
Current Condition 1
Building 2 - Basement
2008 THREE-YEAR ASBESTOS REINSPECTION
CONDITION AND REMOVAL PRIORITY TABLE
Friable Yes/No
Accessibility Yes/No
Restricted
Potential for Disturbance 2
Homogeneous Area No. Bldg Floor Material Description
Removal Priority 3
Current Condition 1
HMA-02 2 3 12x12 Floor Tile & Adhesive No Yes 10 Intact 2 Floor Maintenance 7
HMA-03 2 3 9x9 Floor Tile No Yes 10 Intact 2 Floor Maintenance 7
HMA-04 2 3 Flooring Adhesive No No 10 Intact 1 Access 9
HMA-06 2 3 Fire Door (Assumed) No Restricted 10 Intact 1 Maintenance 10
No ACM
Building 2 - 3rd Floor
Building 2 - Attic
Master Summary Table Asbestos Bulk Samples
2008 THREE-YEAR ASBESTOS REINSPECTION
SUMMARY OF BULK SAMPLES TAKEN TO DATE
Building Floor Room Sample ID Material Description
JB2 00 G03 JB-2-00-M-G03-15 4" brown cove base JB2 00 G02 JB-2-00-M-G08-13 Gypsum drywall JB2 00 G04 JB-2-00-S-G04-14 White hardwall plaster JB2 00 G02 JB-2-00-T-G02-03 White TSI JB2 00 G02 JB-2-00-T-G02-06 Off-white TSI JB2 00 G02 JB-2-00-T-G02-08 Gray/black TSI JB2 00 G02 JB-2-00-T-G02-12 Off-white TSI JB2 00 G05 JB-2-00-T-G05-11 Off-white TSI JB2 00 G07 JB-2-00-T-G07-01 White magnesia pipe lagging JB2 00 G07 JB-2-00-T-G07-04 White mudded joint fitting on magnesia pipe lagging JB2 00 G07 JB-2-00-T-G07-09 Gray TSI JB2 00 G07 JB-2-00-T-G07-10 Off-white mudded joint fitting on cardboard lagging JB2 00 G07A JB-2-00-T-G07A-02 White TSI JB2 00 G07A JB-2-00-T-G07A-05 White TSI JB2 00 H002 JB-2-00-T-H002-07 Gray cardboard wrap pipe lagging JB2 01 118A JB-2-01-T-118A-11 Off-white TSI JB2 01 101A JB-2-01-M-101A-19 1x4 brown ceiling tile JB2 01 114 JB-2-01-M-114-06 2x4 white w/peck & fissure ceiling tile JB2 01 114 JB-2-01-M-114-08 Gypsum drywall JB2 01 124 JB-2-01-M-124-15 4" black cove base JB2 01 H104 JB-2-01-M-H104-04 2x4 white w/small fissure ceiling tile JB2 01 H105 JB-2-01-M-H104-05 gray ceiling tile JB2 01 H105 JB-2-01-M-H105-01 1x1 brown/white ceiling tile JB2 01 S103 JB-2-01-M-S103-03 4" beige cove base JB2 01 116 JB-2-01-S-116-02 White/brown hardwall plaster JB2 01 123 JB-2-01-S-123-16 Off-white stucco surfacing material JB2 01 123 JB-2-01-S-123-17 Off-white other JB2 01 123 JB-2-01-S-123-18 Off-white other JB2 01 112 JB-2-01-T-112-07 Green canvas duct connector JB2 01 112 JB-2-01-T-112-13 Gray TSI JB2 01 112 JB-2-01-T-112-14 Gray TSI JB2 01 118A JB-2-01-T-118A-09 White magnesia pipe lagging JB2 01 118A JB-2-01-T-118A-10 White TSI JB2 01 120A JB-2-01-T-120A-12 Gray/white cardboard wrap pipe lagging JB2 02 201A JB-2-02-M-201A-02 4" brown cove base JB2 02 210 JB-2-02-M-204-07 2x4 white w/small fissures ceiling tile JB2 02 210 JB-2-02-M-210-01 4" tan cove base JB2 02 212 JB-2-02-M-212-03 Brown mastic used on ceiling tile JB2 02 212 JB-2-02-M-212-05 2x4 white w/pecks ceiling tile JB2 02 212 JB-2-02-M-212-06 Gypsum drywall JB2 02 212B JB-2-02-M-212B-01A Black rubberized duct connector JB2 02 212 JB-2-02-S-212-08 White/gray hardwall plaster JB2 02 210 JB-2-02-T-210-04 Green canvas duct connector JB2 03 301 JB-2-03-M-301-06 4" black cove base JB2 03 301A JB-2-03-M-301A-01A Black rubberized duct connector
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Purple = Abated ACM
1994 Initial Asbestos Inspection
2008 THREE-YEAR ASBESTOS REINSPECTION
SUMMARY OF BULK SAMPLES TAKEN TO DATE
Building Floor Room Sample ID Material Description
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Purple = Abated ACM
JB2 03 310A JB-2-03-M-310A-05 4" gray cove base JB2 03 311A JB-2-03-M-311A-01 2x2 white w/pinholes ceiling tile JB2 03 311A JB-2-03-M-311A-03 Gypsum drywall JB2 03 S303 JB-2-03-M-S303-04 4" tan cove base JB2 03 304A JB-2-03-S-304A-02 White/gray hardwall plaster JB2 03 309 JB-2-03-T-309-07 Green canvas duct connector JB2 04 A.Attic JB-2-04-M-A-01 Black rubberized duct connector JB2 04 A.Attic JB-2-04-M-A-01A Black rubberized duct connector
JB2 Basement G02 JB-02-00-F-G02-001A Layer 2- Black mastic JB2 Basement G02 JB-02-00-F-G02-002A Layer 1 - Black 9x9 floor tile JB2 Basement G02 JB-02-00-F-G02-002A Layer 2 - Black mastic JB2 Basement G04 JB-02-00-F-G04-003A Layer 1 - Red 9x9 floor tile JB2 Basement G04 JB-02-00-F-G04-003A Layer 2 - Black mastic JB2 Basement G04 JB-02-00-F-G04-004A Layer 1 - Black 9x9 floor tile JB2 Basement G04 JB-02-00-F-G04-004A Layer 2 - Black mastic JB2 Basement G05 JB-02-00-F-G05-005A Layer 1 - Red 9x9 floor tile JB2 Basement G05 JB-02-00-F-G05-005A Layer 2 - Black mastic JB2 Basement G05 JB-02-00-F-G05-006A Layer 1 - Black 9x9 floor tile JB2 Basement G05 JB-02-00-F-G05-006A Layer 2 - Black mastic JB2 Basement G01 JB-02-00-F-G01-007A White 12x12 floor tile, black mastic JB2 1 122 JB-02-01-M-122-008A White 2x4 ceiling tile JB2 1 122 JB-02-01-M-122-009A White 12x12 ceiling tile JB2 1 122 JB-02-01-M-122-010A White plaster material JB2 1 123A JB-02-01-M-123A-011A White 2x2 ceiling tile JB2 1 123A JB-02-01-M-123A-012A White sheetrock mud JB2 1 122 JB-02-01-F-122-013A Blue 12x12 floor tile, black backing, yellow mastic JB2 1 S101 JB-02-01-F-S101-014A Layer 1 - Tan 12x12 floor tile JB2 1 S101 JB-02-01-F-S101-014A Layer 2 - Yellow mastic JB2 1 118 JB-02-01-F-118-015A Layer 1 - Tan 9x9 floor tile JB2 1 118 JB-02-01-F-118-015A Layer 2 - Black mastic JB2 1 116 JB-02-01-F-116-016A Layer 1 - Tan 9x9 floor tile JB2 1 116 JB-02-01-F-116-016A Layer 2 - Black mastic JB2 1 112 JB-02-01-M-112-017A Brown cloth material JB2 1 110 JB-02-01-M-110-018A White/brown 12x12 ceiling tile material JB2 1 H101 JB-02-01-F-H101-019A Layer 1 - Gray 9x9 floor tile JB2 1 H101 JB-02-01-F-H101-019A Layer 2 - Black mastic JB2 1 H101 JB-02-01-F-H101-019A Layer 3 - Black felt JB2 1 119 JB-02-01-F-119-020A Layer 1 - Adhesive JB2 1 119 JB-02-01-F-119-020A Layer 2 - Gray 9x9 floor tile JB2 1 119 JB-02-01-F-119-020A Layer 3 - Black mastic JB2 1 119 JB-02-01-F-119-020A Layer 4 - Felt JB2 1 119 JB-02-01-F-119-020A Layer 5 - Brown 9x9 floor tile JB2 1 119 JB-02-01-F-119-020A Layer 6 - Black mastic JB2 1 119 JB-02-01-F-119-020A Layer 7 - Felt JB2 1 119A JB-02-01-F-119A-021A Layer 1 - Adhesive
2008 Asbestos Reinspection
2008 THREE-YEAR ASBESTOS REINSPECTION
SUMMARY OF BULK SAMPLES TAKEN TO DATE
Building Floor Room Sample ID Material Description
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Purple = Abated ACM
JB2 1 119A JB-02-01-F-119A-021A Layer 2 - Gray 9x9 floor tile JB2 1 119A JB-02-01-F-119A-021A Layer 3 - Black mastic JB2 1 119A JB-02-01-F-119A-021A Layer 4 - Felt JB2 1 119A JB-02-01-F-119A-021A Layer 5 - Brown 9x9 floor tile JB2 1 119A JB-02-01-F-119A-021A Layer 6 - Black mastic JB2 1 119A JB-02-01-F-119A-021A Layer 7 - Felt JB2 1 119A JB-02-01-F-119A-022A Layer 1 - Adhesive JB2 1 119A JB-02-01-F-119A-022A Layer 2 - Gray 9x9 floor tile JB2 1 119A JB-02-01-F-119A-022A Layer 3 - Black mastic JB2 1 119A JB-02-01-F-119A-022A Layer 4 - Felt JB2 1 119A JB-02-01-F-119A-022A Layer 5 - Brown 9x9 floor tile JB2 1 119A JB-02-01-F-119A-022A Layer 6 - Black mastic JB2 1 119A JB-02-01-F-119A-022A Layer 7 - Felt JB2 1 H103 JB-02-01-F-H103-023A Blue 12x12 floor tile, yellow mastic JB2 2 H202 JB-02-02-F-H202-024A Blue 12x12 floor tile, yellow mastic JB2 2 S202 JB-02-02-F-S202-025A Layer 1 - Tan 12x12 floor tile JB2 2 S202 JB-02-02-F-S202-025A Layer 2 - Black mastic JB2 2 209 JB-02-02-F-209-026A Blue 12x12 floor tile, yellow mastic, white 12x12 floor tile, JB2 2 210 JB-02-02-F-210-027A Brown 12x12 floor tile, black mastic JB2 2 208 JB-02-02-F-208-028A White 12x12 floor tile, black mastic JB2 2 207 JB-02-02-F-207-029A Brown 12x12 floor tile, black mastic JB2 2 201A JB-02-02-F-201A-030A Layer 1 - Adhesive JB2 2 201A JB-02-02-F-201A-030A Layer 2 - White 12x12 floor tile JB2 2 201A JB-02-02-F-201A-030A Layer 3 - Black mastic JB2 2 201A JB-02-02-F-201A-030A Layer 4 - Gray 9x9 floor tile JB2 2 201A JB-02-02-F-201A-030A Layer 5 - Black mastic JB2 2 212B JB-02-02-F-212B-031A Brown 12x12 floor tile, black mastic JB2 3 H301 JB-02-03-F-H301-032A Black felt JB2 3 302 JB-02-03-F-302-033A Black felt JB2 3 H303 JB-02-03-F-H303-034A Brown linoleum, black felt JB2 3 317E JB-02-03-F-317C-035A Layer 1 - White 12X12 floor tile JB2 3 317E JB-02-03-F-317C-035A Layer 2 - Black mastic JB2 3 304 JB-02-03-F-304-036A Adhesive, felt, black mastic, gray 9x9 floor tile, black JB2 1 Exterior JB-02-01-S-EXT-037A Tan texture wall material JB2 1 Exterior JB-02-01-S-EXT-038A Tan texture wall material JB2 1 Exterior JB-02-01-S-EXT-039A Tan texture wall material
Asbestos-Containing Bulk Samples
2008 THREE-YEAR ASBESTOS REINSPECTION
LIST OF ASBESTOS-CONTAINING SAMPLES
Building Floor Room Sample ID Material Description
JB2 00 G02 JB-2-00-T-G02-03 White TSI JB2 00 G02 JB-2-00-T-G02-06 Off-white TSI JB2 00 G02 JB-2-00-T-G02-08 Gray/black TSI JB2 00 G02 JB-2-00-T-G02-12 Off-white TSI JB2 00 G05 JB-2-00-T-G05-11 Off-white TSI JB2 00 G07 JB-2-00-T-G07-01 White magnesia pipe lagging JB2 00 G07 JB-2-00-T-G07-04 White mudded joint fitting on magnesia pipe lagging JB2 00 G07 JB-2-00-T-G07-10 Off-white mudded joint fitting on cardboard lagging JB2 00 G07A JB-2-00-T-G07A-02 White TSI JB2 00 G07A JB-2-00-T-G07A-05 White TSI JB2 01 118A JB-2-01-T-118A-11 Off-white TSI JB2 01 118A JB-2-01-T-118A-09 White magnesia pipe lagging JB2 01 118A JB-2-01-T-118A-10 White TSI JB2 01 120A JB-2-01-T-120A-12 Gray/white cardboard wrap pipe lagging
JB2 Basement G02 JB-02-00-F-G02-001A Layer 2- Black mastic JB2 Basement G02 JB-02-00-F-G02-002A Layer 1 - Black 9x9 floor tile JB2 Basement G02 JB-02-00-F-G02-002A Layer 2 - Black mastic JB2 Basement G04 JB-02-00-F-G04-003A Layer 1 - Red 9x9 floor tile JB2 Basement G04 JB-02-00-F-G04-003A Layer 2 - Black mastic JB2 Basement G04 JB-02-00-F-G04-004A Layer 1 - Black 9x9 floor tile JB2 Basement G04 JB-02-00-F-G04-004A Layer 2 - Black mastic JB2 Basement G05 JB-02-00-F-G05-005A Layer 1 - Red 9x9 floor tile JB2 Basement G05 JB-02-00-F-G05-005A Layer 2 - Black mastic JB2 Basement G05 JB-02-00-F-G05-006A Layer 1 - Black 9x9 floor tile JB2 Basement G05 JB-02-00-F-G05-006A Layer 2 - Black mastic JB2 1 S101 JB-02-01-F-S101-014A Layer 1 - Tan 12x12 floor tile JB2 1 118 JB-02-01-F-118-015A Layer 1 - Tan 9x9 floor tile JB2 1 116 JB-02-01-F-116-016A Layer 1 - Tan 9x9 floor tile JB2 1 H101 JB-02-01-F-H101-019A Layer 1 - Gray 9x9 floor tile JB2 1 119 JB-02-01-F-119-020A Layer 2 - Gray 9x9 floor tile JB2 1 119A JB-02-01-F-119A-021A Layer 2 - Gray 9x9 floor tile JB2 1 119A JB-02-01-F-119A-022A Layer 2 - Gray 9x9 floor tile JB2 2 S202 JB-02-02-F-S202-025A Layer 1 - Tan 12x12 floor tile JB2 2 201A JB-02-02-F-201A-030A Layer 4 - Gray 9x9 floor tile JB2 3 317E JB-02-03-F-317C-035A Layer 2 - Black mastic
1994 Initial Asbestos Inspection
2008 Asbestos Reinspection
2008 Reinspection Inspection Logs
Client: Date: September 16, 2008 Location: Inspector(s): Donald Joiner and Joshua Anders Address: 1 Jefferson Barracks Drive, St. Louis, Missouri
Note:
Sample ID Material Description Floor Room Location
JB-02-00-F-G02-001A Red 9x9 floor tile, black mastic Basement G02 Northeast corner of G02
JB-02-00-F-G02-002A Black 9x9 floor tile, black mastic Basement G02 Northeast corner of G02
JB-02-00-F-G04-003A Red 9x9 floor tile, black mastic Basement G04 East of pipe chase
JB-02-00-F-G04-004A Black 9x9 floor tile, black mastic Basement G04 East of pipe chase
JB-02-00-F-G05-005A Red 9x9 floor tile, black mastic Basement G05 Southeast corner of room G05
JB-02-00-F-G05-006A Black 9x9 floor tile, black mastic Basement G05 Southeast corner of room G05
JB-02-00-F-G01-007A White 12x12 floor tile, black mastic Basement G01 North end of room under stairwell
JB-02-01-M-122-008A White 2x4 ceiling tile 1 122 North end of lobby by stairs door S001
JB-02-01-M-122-009A White 12x12 ceiling tile 1 122 North end of lobby by stairs door S001
JB-02-01-M-122-010A White plaster material 1 122 North end of lobby by stairs door S001
JB-02-01-M-123A-011A White 2x2 ceiling tile 1 123A Northwest corner of 123A by elevator
JB-02-01-M-123A-012A White sheetrock mud 1 123A Northwest corner of 123A by elevator
JB-02-01-F-122-013A Blue 12x12 floor tile, black backing, yellow mastic 1 122 Southeast corner of 122 under heater
JB-02-01-F-S101-014A Layer 1 - Tan 12x12 floor tile 1 S101 Southwest corner at top of S101
JB-02-01-F-S101-014A Layer 2 - Yellow mastic 1 S101 Southwest corner at top of S101
ASBESTOS INSPECTION LOG
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non ACM (determined by Point Count analysis)
Jefferson Barracks Division - Building 2 St. Louis V. A. Medical Center
Address: 1 Jefferson Barracks Drive, St. Louis, Missouri
Note:
Sample ID Material Description Floor Room Location
ASBESTOS INSPECTION LOG
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non ACM (determined by Point Count analysis)
Jefferson Barracks Division - Building 2 St. Louis V. A. Medical Center
JB-02-01-F-118-015A Layer 1 - Tan 9x9 floor tile 1 118 Northwest corner of room 118
JB-02-01-F-118-015A Layer 2 - Black mastic 1 118 Northwest corner of room 118
JB-02-01-F-116-016A Layer 1 - Tan 9x9 floor tile 1 116 Southwest corner of room 116 behind door
JB-02-01-F-116-016A Layer 2 - Black mastic 1 116 Southwest corner of room 116 behind door
JB-02-01-M-112-017A Brown cloth material 1 112 Southeast corner of room 112
JB-02-01-M-110-018A White/brown 12x12 ceiling tile material 1 110 In center of room 110 by ceiling vent
JB-02-01-F-H101-019A Layer 1 - Gray 9x9 floor tile 1 H101 Southeast corner of hallway next to door underneath carpet
JB-02-01-F-H101-019A Layer 2 - Black mastic 1 H101 Southeast corner of hallway next to door underneath carpet
JB-02-01-F-H101-019A Layer 3 - Black felt 1 H101 Southeast corner of hallway next to door underneath carpet
JB-02-01-F-119-020A Layer 1 - Adhesive 1 119 Southwest quadrant of room 119 underneath window
JB-02-01-F-119-020A Layer 2 - Gray 9x9 floor tile 1 119 Southwest quadrant of room 119 underneath window
JB-02-01-F-119-020A Layer 3 - Black mastic 1 119 Southwest quadrant of room 119 underneath window
JB-02-01-F-119-020A Layer 4 - Felt 1 119 Southwest quadrant of room 119 underneath window
JB-02-01-F-119-020A Layer 5 - Brown 9x9 floor tile 1 119 Southwest quadrant of room 119 underneath window
JB-02-01-F-119-020A Layer 6 - Black mastic 1 119 Southwest quadrant of room 119 underneath window
Address: 1 Jefferson Barracks Drive, St. Louis, Missouri
Note:
Sample ID Material Description Floor Room Location
ASBESTOS INSPECTION LOG
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non ACM (determined by Point Count analysis)
Jefferson Barracks Division - Building 2 St. Louis V. A. Medical Center
JB-02-01-F-119-020A Layer 7 - Felt 1 119 Southwest quadrant of room 119 underneath window
JB-02-01-F-119A-021A Layer 1 - Adhesive 1 119A Northeast quadrant of room 119A underneath HVAC unit
JB-02-01-F-119A-021A Layer 2 - Gray 9x9 floor tile 1 119A Northeast quadrant of room 119A underneath HVAC unit
JB-02-01-F-119A-021A Layer 3 - Black mastic 1 119A Northeast quadrant of room 119A underneath HVAC unit
JB-02-01-F-119A-021A Layer 4 - Felt 1 119A Northeast quadrant of room 119A underneath HVAC unit
JB-02-01-F-119A-021A Layer 5 - Brown 9x9 floor tile 1 119A Northeast quadrant of room 119A underneath HVAC unit
JB-02-01-F-119A-021A Layer 6 - Black mastic 1 119A Northeast quadrant of room 119A underneath HVAC unit
JB-02-01-F-119A-021A Layer 7 - Felt 1 119A Northeast quadrant of room 119A underneath HVAC unit
JB-02-01-F-119A-022A Layer 1 - Adhesive 1 119A Northwest corner of room 119A under window
JB-02-01-F-119A-022A Layer 2 - Gray 9x9 floor tile 1 119A Northwest corner of room 119A under window
JB-02-01-F-119A-022A Layer 3 - Black mastic 1 119A Northwest corner of room 119A under window
JB-02-01-F-119A-022A Layer 4 - Felt 1 119A Northwest corner of room 119A under window
JB-02-01-F-119A-022A Layer 5 - Brown 9x9 floor tile 1 119A Northwest corner of room 119A under window
JB-02-01-F-119A-022A Layer 6 - Black mastic 1 119A Northwest corner of room 119A under window
JB-02-01-F-119A-022A Layer 7 - Felt 1 119A Northwest corner of room 119A under window
Address: 1 Jefferson Barracks Drive, St. Louis, Missouri
Note:
Sample ID Material Description Floor Room Location
ASBESTOS INSPECTION LOG
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non ACM (determined by Point Count analysis)
Jefferson Barracks Division - Building 2 St. Louis V. A. Medical Center
JB-02-01-F-H103-023A Blue 12x12 floor tile, yellow mastic 1 H103 Northeast corner of hallway 103, by glass door and entrance to room 113
JB-02-02-F-H202-024A Blue 12x12 floor tile, yellow mastic 2 H202 Northwest corner of hallway by stairs and double doors
JB-02-02-F-S202-025A Layer 1 - Tan 12x12 floor tile 2 S202 Southwest corner in stairwell landing
JB-02-02-F-S202-025A Layer 2 - Black mastic 2 S202 Southwest corner in stairwell landing
JB-02-02-F-209-026A Blue 12x12 floor tile, yellow mastic, white 12x12 floor tile, black mastic 2 209 Northeast corner of kitchen below sink
JB-02-02-F-210-027A Brown 12x12 floor tile, black mastic 2 210 Northeast quadrant underneath sink
JB-02-02-F-208-028A White 12x12 floor tile, black mastic 2 208 North middle wall underneath HVAC unit
JB-02-02-F-207-029A Brown 12x12 floor tile, black mastic 2 207 Southeast corner underneath window by HVAC unit
JB-02-02-F-201A-030A Layer 1 - Adhesive 2 201A Southwest corner by door
JB-02-02-F-201A-030A Layer 2 - White 12x12 floor tile 2 201A Southwest corner by door
JB-02-02-F-201A-030A Layer 3 - Black mastic 2 201A Southwest corner by door
JB-02-02-F-201A-030A Layer 4 - Gray 9x9 floor tile 2 201A Southwest corner by door
JB-02-02-F-201A-030A Layer 5 - Black mastic 2 201A Southwest corner by door
JB-02-02-F-212B-031A Brown 12x12 floor tile, black mastic 2 212B North wall in the middle underneath HVAC unit
JB-02-03-F-H301-032A Black felt 3 H301 Southwest corner of hallway outside of door 302
Address: 1 Jefferson Barracks Drive, St. Louis, Missouri
Note:
Sample ID Material Description Floor Room Location
ASBESTOS INSPECTION LOG
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non ACM (determined by Point Count analysis)
Jefferson Barracks Division - Building 2 St. Louis V. A. Medical Center
JB-02-03-F-302-033A Black felt 3 302 Center of west wall by HVAC unit
JB-02-03-F-H303-034A Brown linoleum, black felt 3 H303 Northeast corner of hallway at exit S303
JB-02-03-F-317C-035A Layer 1 - White 12X12 floor tile 3 317C North of room behind double doors by HVAC unit in kitchen closet
JB-02-03-F-317C-035A Layer 2 - Black mastic 3 317C North of room behind double doors by HVAC unit in kitchen closet
JB-02-03-F-304-036A Adhesive, felt, black mastic, gray 9x9 floor tile, black mastic 3 304 Northwest corner behind door
JB-02-01-S-EXT-037A Tan texture wall material 1 Exterior Northwest corner of building 02 exterior
JB-02-01-S-EXT-038A Tan texture wall material 1 Exterior Northwest quadrant of building 02 exterior
JB-02-01-S-EXT-039A Tan texture wall material 1 Exterior Southeast corner at entrance at bottom by sidewalk
GOOD = Surfacing material has no visible damage or small amounts of damage; covering on thermal system insulation is intact or has small amounts of damage; miscellaneous materials intact; no visible debris or small amounts of debris. FAIR = Surfacing material has moderate but not extensive amounts of visible damage; covering on thermal system insulation is cut or torn, exposing moderate but not extensive amounts of insulation; moderate but not extensive damage to miscellaneous materials such as floor tile; moderate but not extensive amounts of visible dust and debris. POOR = Extensive damage to surfacing material; covering on thermal system insulation is cut or torn extensively and insulation itself is damaged; miscellaneous materials such as floor tile extensively damaged and underlying mastic exposed; extensive amounts of dust and debris.
Material Category: F = Flooring S = Surfacing T = TSI M = Miscellaneous Friability: F=Friable NF=Non-Friable Condition: Good = 8, 9, 10 Fair = 4, 5, 6, 7 Poor = 1, 2, 3
Red = Asbestos-Containing Material Blue = Non Asbestos-Containing MaterialPlease use the following guidelines when reading this report:
Bulk Sample Location Drawings
BASEMENT
1st FLOOR
2ND FLOOR
3rd FLOOR
ATTIC
2008 Reinspection Photographs
BUILDING 2
sample contains asbestos sample does not contain asbestos
JB-02-00-F-G02-001A JB-02-00-F-G02-002A
JB-02-00-F-G04-003A JB-02-00-F-G04-004A
BUILDING 2
JB-02-00-F-G05-005A JB-02-00-F-G05-006A
JB-02-00-F-G01-007A JB-02-01-M-122-008A
BUILDING 2
JB-02-01-M-122-009A JB-02-01-M-122-010A
JB-02-01-M-123A-011A JB-02-01-M-123A-012A
BUILDING 2
JB-02-01-F-122-013A JB-02-01-F-S101-014A
JB-02-01-F-118-015A JB-02-01-F-116-016A
BUILDING 2
JB-02-01-M-112-017A JB-02-01-M-110-018A
JB-02-01-F-H101-019A JB-02-01-F-119-020A
BUILDING 2
JB-02-01-F-119A-021A JB-02-01-F-119A-022A
JB-02-01-F-H103-023A JB-02-02-F-H202-024A
BUILDING 2
JB-02-02-F-S202-025A JB-02-02-F-209-026A
JB-02-02-F-210-027A JB-02-02-F-208-028A
BUILDING 2
JB-02-02-F-207-029A JB-02-02-F-201A-030A
JB-02-02-F-212B-031A JB-02-03-F-H301-032A
BUILDING 2
JB-02-03-F-302-033A JB-02-03-F-H303-034A
JB-02-03-F-317C-035A JB-02-03-F-304-036A
BUILDING 2
JB-02-01-S-EXT-037A JB-02-01-S-EXT-038A
JB-02-01-S-EXT-039A
2008 Reinspection Laboratory Reports
Sample Location Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804575
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
2920 Truly Lane Shreveport, LA 71138
Customer PO:
Received: 09/17/08 4:50 PM
08-14529 VAMC Reinspection - JB - Building 2 (Corrected report issued 10/10/08.)
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/18/2008Analysis Date:
Report Date: 10/10/2008
EMSL Analytical, Inc.
11040A Lin-Valle Drive, Saint Louis, MO 63123 Phone: (314) 845-8910 Fax: (314) 845-6459 Email: saintlouislab@emsl.com
JB-02-00-F-G02-
001A Floortile 390804575-0001
RED 9X9 FT
BLACK MASTIC
Red Non-Fibrous
Heterogeneous
Chrysotile29%Non-fibrous (other)71%
JB-02-00-F-G02-
001A Adhesive 390804575-0001A
RED 9X9 FT
BLACK MASTIC
Black Non-Fibrous
Heterogeneous
Chrysotile9%Non-fibrous (other)87% Quartz4%
JB-02-00-F-G02-
002A Floortile 390804575-0002
BLACK 9X9 FT
BLACK MASTIC
Black Non-Fibrous
Heterogeneous
Chrysotile29%Non-fibrous (other)71%
JB-02-00-F-G02-
002A Adhesive 390804575-0002A
BLACK 9X9 FT
BLACK MASTIC
Black Non-Fibrous
Heterogeneous
Chrysotile9%Non-fibrous (other)87% Quartz4%
JB-02-00-F-G04-
003A Floortile 390804575-0003
RED 9X9 FT
BLACK MASTIC
Red Non-Fibrous
Heterogeneous
Chrysotile29%Non-fibrous (other)71%
JB-02-00-F-G04-
003A Adhesive 390804575-0003A
RED 9X9 FT
BLACK MASTIC
Black Non-Fibrous
Heterogeneous
Chrysotile9%Non-fibrous (other)87% Quartz4%
JB-02-00-F-G04-
004A Floortile 390804575-0004
BLACK 9X9 FT
BLACK MASTIC
Black Non-Fibrous
Heterogeneous
Chrysotile29%Non-fibrous (other)71%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
Analysis performed by EMSL St. Louis (AIHA #102636, NVLAP # 200742-0, CA ELAP #2668)
Sue Ferrario (32)
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804575
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
2920 Truly Lane Shreveport, LA 71138
Customer PO:
Received: 09/17/08 4:50 PM
08-14529 VAMC Reinspection - JB - Building 2 (Corrected report issued 10/10/08.)
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/18/2008Analysis Date:
Report Date: 10/10/2008
EMSL Analytical, Inc.
11040A Lin-Valle Drive, Saint Louis, MO 63123 Phone: (314) 845-8910 Fax: (314) 845-6459 Email: saintlouislab@emsl.com
JB-02-00-F-G04-
004A Adhesive 390804575-0004A
BLACK 9X9 FT
BLACK MASTIC
Black Non-Fibrous
Heterogeneous
Chrysotile9%Non-fibrous (other)87% Quartz4%
JB-02-00-F-G05-
005A Floortile 390804575-0005
RED 9X9 FT
BLACK MASTIC
Red Non-Fibrous
Heterogeneous
Chrysotile29%Non-fibrous (other)71%
JB-02-00-F-G05-
005A Adhesive 390804575-0005A
RED 9X9 FT
BLACK MASTIC
Black Non-Fibrous
Heterogeneous
Chrysotile9%Non-fibrous (other)87% Quartz4%
JB-02-00-F-G05-
006A Floortile 390804575-0006
BLACK 9X9 FT
BLACK MASTIC
Black Non-Fibrous
Heterogeneous
Chrysotile29%Non-fibrous (other)71%
JB-02-00-F-G05-
006A Adhesive 390804575-0006A
BLACK 9X9 FT
BLACK MASTIC
Black Non-Fibrous
Heterogeneous
Chrysotile9%Non-fibrous (other)87% Quartz4%
JB-02-00-F-G01-
007A Floortile 390804575-0007
WHITE 12X12 FT
BLACK MASTIC
White None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
JB-02-00-F-G01-
007A Adhesive 390804575-0007A
WHITE 12X12 FT
BLACK MASTIC
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804575
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
2920 Truly Lane Shreveport, LA 71138
Customer PO:
Received: 09/17/08 4:50 PM
08-14529 VAMC Reinspection - JB - Building 2 (Corrected report issued 10/10/08.)
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/18/2008Analysis Date:
Report Date: 10/10/2008
EMSL Analytical, Inc.
11040A Lin-Valle Drive, Saint Louis, MO 63123 Phone: (314) 845-8910 Fax: (314) 845-6459 Email: saintlouislab@emsl.com
JB-02-01-M-122-
008A 390804575-0008
WHITE 2X4 CT White None Detected
Fibrous
Heterogeneous
Cellulose28% Min. Wool37%
Non-fibrous (other)7% Perlite28%
JB-02-01-M-122-
009A 390804575-0009
WHITE 12X12 CT White None Detected
Fibrous
Heterogeneous
Cellulose94% Non-fibrous (other)6%
JB-02-01-M-122-
010A 390804575-0010
WHITE PLASTER
MATERIAL
White None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)83% Quartz17%
JB-02-01-M-123-
011A 390804575-0011
2X2 WHITE
CEILING
White None Detected
Fibrous
Heterogeneous
Cellulose28% Min. Wool37%
Non-fibrous (other)7% Perlite28%
JB-02-01-M-123A-
012A 390804575-0012
WHITE
SHEETROCK
MUD
White None Detected
Non-Fibrous
Heterogeneous
Mica4% Non-fibrous (other)96%
JB-02-01-F-122-
013A Flooring 390804575-0013
BLUE 12X12 FT
BLACK BACKING
YELLOW MASTIC
Various None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
JB-02-01-F-122-
013A Adhesive 390804575-0013A
BLUE 12X12 FT
BLACK BACKING
YELLOW MASTIC
Yellow None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804575
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
2920 Truly Lane Shreveport, LA 71138
Customer PO:
Received: 09/17/08 4:50 PM
08-14529 VAMC Reinspection - JB - Building 2 (Corrected report issued 10/10/08.)
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/18/2008Analysis Date:
Report Date: 10/10/2008
EMSL Analytical, Inc.
11040A Lin-Valle Drive, Saint Louis, MO 63123 Phone: (314) 845-8910 Fax: (314) 845-6459 Email: saintlouislab@emsl.com
JB-02-01-F-S101-
014A Floortile 390804575-0014
TAN 12X12
FT/YLW
MASTIC/YLW
CARPET/GLUE
ON 12X12FT
Tan Non-Fibrous
Heterogeneous
Chrysotile6%Non-fibrous (other)94%
JB-02-01-F-S101-
014A Adhesive 390804575-0014A
TAN 12X12
FT/YLW
MASTIC/YLW
CARPET/GLUE
ON 12X12FT
Yellow None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
JB-02-01-F-118-
015A Floortile 390804575-0015
TAN 9X9
FT/BLACK
MASTIC/YLW
CARPET/GLUE
ON 9X9 FT
Tan Non-Fibrous
Heterogeneous
Chrysotile19%Non-fibrous (other)81%
JB-02-01-F-118-
015A Adhesive 390804575-0015A
TAN 9X9
FT/BLACK
MASTIC/YLW
CARPET/GLUE
ON 9X9 FT
Various None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)95% Quartz5%
JB-02-01-F-116-
016A Floortile 390804575-0016
TAN 9X9
FT/BLACK
MASTI/YLW
CARPET GLUE
ON 9X9 FT
Tan Non-Fibrous
Heterogeneous
Chrysotile19%Non-fibrous (other)81%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804575
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
2920 Truly Lane Shreveport, LA 71138
Customer PO:
Received: 09/17/08 4:50 PM
08-14529 VAMC Reinspection - JB - Building 2 (Corrected report issued 10/10/08.)
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EM…