ASBESTOS ASSESSMENT
ASBESTOS REINSPECTION REPORT
Jefferson Barracks Division 1 Jefferson Barracks Drive
St. Louis, Missouri
Building 61
Prepared for:
St. Louis V. A. Medical Center 1 Jefferson Barracks Drive
St. Louis, Missouri
Prepared by:
1421 Clarkview Road, Suite 100 P. O. Box 17867 Baltimore, MD 21209 Shreveport, Louisiana 71138-0867
(888) 776-0670 (318) 687-3771
INTRODUCTION
2008 ASBESTOS REINSPECTION REPORT
ST. LOUIS V. A. MEDICAL CENTER
JOHN COCHRAN AND JEFFERSON BARRACKS DIVISIONS
SCOPE OF WORK
1. The Inspector and Management Planner reviewed prior inspections and Management Plan information on file and compared this information with existing conditions for each facility.
2. This asbestos reinspection complies with the requirements of Asbestos Hazard Emergency Response Act (AHERA).
3. Each facility inspection was performed by an accredited inspector.
4. For each facility, the inspector performed the following tasks:
a. Visually reinspected and reassessed the condition of all friable known or assumed
ACBM.
b. Visually inspected material that was previously considered non-friable Asbestos- Containing Building Material (ACBM) and touched the material to determine whether it has become friable since the last inspection.
c. Identified any homogeneous areas with material that has become friable since the last inspection or reinspection.
d. The inspector collected bulk samples for analysis of newly friable material that is already assumed (not sampled) to be ACBM or collected additional bulk samples to fully assess the suspect materials.
e. Visually inspected, sampled, analyzed, and assessed the conditions of building materials that have been added to the facility since the last inspection or reinspection.
f. Assessed the condition of the newly friable material in areas where samples were collected and of newly friable material in areas assumed to be ACBM.
g. Reassessed the condition of friable known or assumed ACBM previously identified.
h. Recorded above information on field inspection forms for each facility.
5. A Management Planner reviewed the above information and performed the following required functions:
a. Reviewed each Management Plan for compliance with AHERA and verified that the plan reflects current conditions.
b. Reviewed the results of each reinspection and assessment.
c. Recommended in writing, the appropriate response actions.
d. Signed and dated the review documents, included the accreditation number of inspectors and planners, and submitted a copy to the Designated Person.
6. The following information was submitted to the Designated Person under AHERA, for inclusion in the Management Plan for each facility and, optionally, at a central office location.
a. The date of the inspection, the name and signature of the person making the inspection, state of accreditation, his or her accreditation number, and any changes in the condition of known or assumed ACBM.
b. If samples were collected, the exact locations where samples are collected during the inspection, a description of the manner used to choose sampling locations, the name and signature of each accredited inspector who collected the samples, state of accreditation, and his or her accreditation number.
c. Any assessments or reassessments made of friable material, the name and signature of the accredited inspector making the assessments, state of accreditation, and his or her accreditation number.
MANAGEMENT PLAN RECOMMENDATIONS
The following general notes are for all facilities inspected during the Asbestos Reinspection.
These notes reference any deficiencies found in prior inspections, reinspections, and the current Management Plan.
1. Removal Priorities were developed for each homogeneous area. The Removal Priorities are an indicator of priorities for future repair work or abatement work to be scheduled as financial budgets allow. Please see the 2008 Reinspection Condition and Removal Priority Table for further detail.
2. The current condition of material was listed for each homogeneous area. The condition, location, and potential for disturbance factors are used for the hazard ranking. Please see the 2008 Reinspection Condition and Removal Priority Table for the condition summaries.
3. Records for custodial, janitorial, and maintenance staff who have received two-hour awareness training should be filed in the Management Plan.
4. Any new custodial, janitorial, or maintenance staff that have the potential to come in contact with asbestos-containing materials (ACM) are required to attend a two-hour awareness training class. Records of training for new employees should be filed in the Management Plan.
5. The Designated Person is required to inform workers and building occupants at least once a year about the Management Plan. This includes information about inspections, response actions, and post-response action activities that are planned or in progress.
Provide a copy of the notification to each facility and include a copy in the Management Plan.
6. Maintenance areas (boiler rooms, janitor closets, etc.) are required to have warning labels where ACM are located. Install warning labels in these areas as needed. Some older labels may have come loose and are no longer visible. Post the labels in a prominent location.
7. Review the enclosed 2008 Reinspection Condition and Removal Priority Table for maintenance actions that may be required and to establish priorities and budgets for future repair and abatement work.
8. Periodic “Surveillance Inspections” are required every six (6) months. This inspection should indicate the condition of the material and provide recommendations for repair or potential removal. Consistency of inspections is desired and, therefore, should be performed by the same individual(s) for all facilities. An accredited inspector is not required, but is recommended. Records of Surveillance Inspections should be filed in both the administrative and facility Management Plans.
9. ”Reinspections” are required every three (3) years. Updated information should be added to the Management Plan.
10. The existing Management Plan (original) is updated by this Three-Year Reinspection.
All procedures and methods listed in the Plan are still in effect and should be followed unless specifically updated or omitted by this inspection. This includes maintenance procedures, repairs to damaged material, response actions, record keeping, surveillance inspections, and training.
11. An accredited “Supervisor” should be on staff or available on a contract basis per AHERA guidelines. Certification paperwork should be filed in the training section of the Management Plan.
12. ACBM should only be removed by licensed and accredited contractors in the State of Missouri. Response actions related to abatement activity should be filed in the Management Plan. Removal of limited amounts of asbestos is within the scope of the Management Plan by the accredited Supervisor and trained individuals.
13. Notification should be provided to “outside contractors” about ACM within the facility.
This should include such trades or services as telephone, electrical, plumbing, air conditioning, and other construction work. A form should be created for this purpose and placed in the Management Plan.
14. New building construction and portable buildings added to a facility are required to be inspected and sampled for ACM. In lieu of this, a letter from the architect, engineer, or manufacturer can be obtained that states “no ACM were specified or used in the facility”.
A copy of this letter is to be filed with the Management Plan at the facility. This letter will cancel the requirement for sampling.
15. Abatement Costs were developed for each homogeneous area and per facility. The estimated abatement cost is for budget purposes only. The cost is based on the area of material and estimated abatement costs for this material. The cost is for abatement only and does not include abatement design, air monitoring, or project observation costs.
REPORT SECTION
This report includes the following sections:
ACM Homogeneous Areas Summary Table and Drawings
This section provides a quick table reference to all asbestos-containing homogeneous areas found during the reinspection and drawings with the asbestos-containing homogeneous areas found during the 2008 asbestos reinspection.
Condition and Removal Priority Table
This section provides a table with the current condition, potential for disturbance, and removal priority for each homogeneous area.
Master Summary Table – Asbestos Bulk Samples
This table provides a listing of all asbestos bulk samples taken to date.
Asbestos-Containing Bulk Samples
This table provides a listing of all asbestos-containing bulk samples.
2008 Reinspection – Inspection Logs
This section provides the field inspection logs for samples taken during the 2008 asbestos reinspection.
Bulk Sample Location Drawings
This section provides drawings with sample locations for all asbestos bulk samples.
2008 Reinspection – Photographs
This section provides photographs of all asbestos bulk samples taken during the 2008 asbestos reinspection.
2008 Reinspection – Laboratory Reports
This section provides all laboratory analytical results.
Certifications
This section provides certifications for all Inspectors, the Management Planner who reviewed this Management Plan, and the laboratory that performed the bulk sample analysis.
Periodic Surveillance Forms
This section includes the forms completed during the periodic surveillance inspections required every six (6) months.
Management Plan Updates
This section includes the records of any asbestos abatement activities that are completed at the subject site. Notifications, daily notes, drawings, etc., should be placed in this section. This would also include air-monitoring data from asbestos abatement projects.
Response Actions
This section includes the records of any internal asbestos abatement or operation and maintenance activities that may be completed by V. A. employees. This would include any drawings, field notes, and air monitoring that was completed.
Training Documents
This section includes the records of training for the Designated Person and accredited Supervisor, as well as the two-hour awareness training for the custodial, janitorial, and maintenance staff.
Annual Notification Letters
This section includes copies of the annual Notification Letters provided to employees to inform them of the availability of the Management Plan.
Initial Inspection
This section contains the original asbestos inspection that was completed in 1994. This information was used to develop the 2008 Asbestos Reinspection.
CONTRACTORS
This 2008 Asbestos Reinspection was provided by:
Contractor: Subcontractor:
FINBACK 670, Inc. ALTEC Environmental Consultants, Inc.
1421 Clarkview Road, Suite 100 10100 Woolworth Road Baltimore, MD 21209 Keithville, LA 71047
(888) 776-0670 (Office) (318) 687-3771 (Office)
(877) 776-0670 (Fax) (318) 687-9923 (Fax)
INSPECTORS:
Brandon Odom Donald R. Joiner LA Certificate No. 9I01392 LA Certificate No. 8I01348 LA Certificate No. 9I01348
Eric Clipps Joshua Anders LA Certificate No. 9I01588 LA Certificate No. 9I01589
Justin L. Holcomb LA Certificate No. 9I00306
MANAGEMENT PLANNER:
Roy W. Dowling LA Certificate No. 9I00213 – Inspector LA Certificate No. 9P00072 – Management Planner
Accreditation Agency: Louisiana Department of Environmental Quality
ACM Homogeneous Areas Summary Table and Drawings
JEFFERSON BARRACKS DIVISION
2008 THREE-YEAR ASBESTOS REINSPECTION
ACM HOMOGENEOUS AREAS SUMMARY TABLE
Floor Flooring Materials Surfacing Materials TSI Materials Miscellaneous Materials
Service Room & Pipe Space No ACM No ACM
HMA-07 Pipe Insulation & Fittings HMA-08 Gray/White Canvas Wrap
HMA-10 Black Tar on Ductwork No ACM
Floor Flooring Materials Surfacing Materials TSI Materials Miscellaneous Materials
HMA-01 9x9 Floor Tile HMA-02 Black Mastic
HMA-03 12x12 Floor Tile & Adhesive HMA-04 12x12 Floor Tile
HMA-05 Transite Board HMA-07 Pipe Insulation & Fittings HMA-06 White Spray-On Ceiling Material HMA-11 Fire Door (Assumed)
Floor Flooring Materials Surfacing Materials TSI Materials Miscellaneous Materials
2 No ACM HMA-05 Transite Board HMA-09 Mastic on Piping No ACM
Floor Flooring Materials Surfacing Materials TSI Materials Miscellaneous Materials
Attic No ACM HMA-05 Transite Board HMA-07 Pipe Insulation & Fittings HMA-10 Black Tar on Ductwork HMA-12 Insulation on Spotlight Cords
Building 61 - Service Room & Pipe Space
Building 61 - 1st Floor
Building 61 - 2nd Floor
Building 61 - Attic
SERVICE ROOM AND PIPE SPACE
ST. LOUIS V.A. MEDICAL CENTER
2008 THREE-YEAR REINSPECTION
THERMAL SYSTEM INSULATION (TSI) SUMMARY TABLE
Room # Description Qty S/LF Ftgs TH/DI G01-61-JB cardboard wrap pipe lagging 145 lf 0 2.00 G01-61-JB cardboard wrap pipe lagging 130 lf 0 4.00 G01-61-JB magnesia pipe lagging 155 lf 0 2.00 G01-61-JB magnesia pipe lagging 135 lf 0 6.00 G01-61-JB magnesia pipe lagging 130 lf 0 8.00 G01-61-JB magnesia pipe lagging 30 lf 0 12.00 G01-61-JB mudded joint fitting on mag pipe lag 0 ea 57 2.00 G01-61-JB mudded joint fitting on mag pipe lag 0 ea 57 4.00 G01-61-JB mudded joint fitting on mag pipe lag 0 ea 17 6.00 G01-61-JB mudded joint fitting on mag pipe lag 0 ea 20 8.00 G01-61-JB mudded joint fitting on mag pipe lag 0 ea 2 12.00 G01-61-JB tank insulation (hot water tank) 90 sf 0 2.00 G01-61-JB white canvas duct connector 18 sf 0 0.00
Z001-61-JB cardboard wrap pipe lagging 1125 lf 0 2.00 Z001-61-JB magnesia pipe lagging 675 lf 0 2.00 Z001-61-JB magnesia pipe lagging 475 lf 0 4.00 Z001-61-JB magnesia pipe lagging 650 lf 0 6.00 Z001-61-JB magnesia pipe lagging 600 lf 0 8.00 Z001-61-JB mudded joint fitting on mag pipe lag 0 ea 140 2.00 Z001-61-JB mudded joint fitting on mag pipe lag 0 ea 80 4.00 Z001-61-JB mudded joint fitting on mag pipe lag 0 ea 70 6.00 Z001-61-JB mudded joint fitting on mag pipe lag 0 ea 15 8.00 Z001-61-JB mudded joint tar ftg on fiberglas 0 ea 78 4.00 Z001-61-JB tar on fiberglas duct insulation 300 sf 0 2.00
4658 536
Building 61 - Service Room & Pipe Space
TOTALS
1st FLOOR
2008 THREE-YEAR REINSPECTION
THERMAL SYSTEM INSULATION (TSI) SUMMARY TABLE
Room # Description Qty S/LF Ftgs TH/DI 101-61-JB cardboard wrap pipe lagging 3 lf 0 2.00 101-61-JB green canvas duct connector 10 sf 0 0.00 101-61-JB magnesia pipe lagging 10 lf 0 2.00 101-61-JB magnesia pipe lagging 7 lf 0 4.00 101-61-JB magnesia pipe lagging 18 lf 0 6.00 101-61-JB magnesia pipe lagging 23 lf 0 8.00 101-61-JB mudded joint fitting on mag pipe lag 0 ea 7 2.00 101-61-JB mudded joint fitting on mag pipe lag 0 ea 4 4.00 101-61-JB mudded joint fitting on mag pipe lag 0 ea 7 6.00
103-61-JB magnesia pipe lagging 1 lf 0 8.00 103-61-JB mudded joint fitting on mag pipe lag 0 ea 1 8.00
104-61-JB magnesia pipe lagging 20 lf 0 4.00
110-61-JB cardboard wrap pipe lagging 1 lf 0 2.00
114A-61-JB cardboard wrap pipe lagging 10 lf 0 2.00
121-61-JB magnesia pipe lagging 2 lf 0 6.00 121-61-JB mudded joint fitting on mag pipe lag 0 ea 1 6.00
128A-61-JB cardboard wrap pipe lagging 93 lf 0 2.00 128A-61-JB mudded joint tar ftg on fiberglas 0 ea 4 6.00
198 24
Building 61 - 1st Floor
2ND FLOOR
ATTIC
2008 THREE-YEAR REINSPECTION
THERMAL SYSTEM INSULATION (TSI) SUMMARY TABLE
Room # Description Qty S/LF Ftgs TH/DI A-61-JB cardboard wrap pipe lagging 40 lf 0 6.00 A-61-JB mudded joint tar ftg on fiberglas 0 ea 10 4.00 A-61-JB tar on fiberglas duct insulation 1000 sf 0 0.00 A-61-JB white canvas duct connector 2 sf 0 0.00
1042 10
Building 61 - Attic
Condition and Removal Priority Table
Qualitative Ranking Numerical Rating
Good 8, 9, 10
Fair 4, 5, 6, 7
Poor 1, 2, 3
Physical Disturbance Environmental Disturbance
Low 1, 2, 3
Medium 4, 5, 6, 7
High 8, 9, 10
Qualitative Ranking Numerical Rating High 1, 2, 3
Medium 4, 5, 6, 7
Low 8, 9, 10
1 Qualitative Rankings and Quantitative (Numerical) Ratings for Current Condition
2 Qualitative Rankings and Quantitative (Numerical) Ratings for Potential for Disturbance
Assessment FactorsQualitative Ranking Numerical Rating
Description of Current Condition Surfacing material has no visible damage or small amounts of damage; covering on thermal system insulation is intact or has small amounts of damage; miscellaneous materials intact; no visible debris or small amounts of debris.
Address with on-going maintenance procedures
Maintain in good condition
Surfacing material has moderate but not extensive amounts of visible damage; covering on thermal system insulation is cut or torn, exposing moderate but not extensive amounts of insulation; moderate but not extensive damage to miscellaneous materials such as floor tile; moderate but not extensive amounts of visible dust and debris..
3 Qualitative Rankings and Quantitative (Numerical) Ratings for Removal Priority
Description of Current Condition Address short-term
Extensive damage to surfacing material; covering on thermal system insulation is cut or torn extensively and insulation itself is damage; miscellaneous materials such as floor tile extensively damaged and underlying mastic exposed; extensive amounts of dust and debris.
Accessibility: accessibility during normal operations
Activities: activities that people do and how often they do them
Vibration: vibration from operating machinery, HVAC equipment, and so forth
Air/Dust: air currents strong enough to dislodge loose ACM; airborne dust that can erode material
Corrosive: corrosive atmosphere or liquids that can erode the covering or matrix
Water Damage: water damage from leaking roof, pipe or other source
2008 THREE-YEAR ASBESTOS REINSPECTION
CONDITION AND REMOVAL PRIORITY TABLE
Rating Based On Rating Based On
HMA-07 61 Service Room & Pipe Space Pipe Insulation & Fittings No Yes 10 Intact 2 Floor
Maintenance 7
HMA-08 61 Service Room & Pipe Space Gray/White Canvas Wrap Yes No 7 Damage 2 Access 6
HMA-10 61 Service Room & Pipe Space Black Tar on Ductwork No No 9 Condition 2 Access 9
HMA-01 61 1 9x9 Floor Tile No Yes 10 Intact 2 Floor Maintenance 7
HMA-02 61 1 Black Mastic No No 10 Intact 1 Access 9
HMA-03 61 1 12x12 Floor Tile & Adhesive No Yes 10 Intact 2 Floor Maintenance 7
HMA-04 61 1 12x12 Floor Tile No Yes 10 Intact 2 Floor Maintenance 7
HMA-05 61 1 Transite Board No No 10 Intact 1 Access 9
HMA-07 61 1 Pipe Insulation & Fittings Yes No 7 Damage 2 Access 6
HMA-06 61 1 White Spray-On Ceiling Material Yes No 10 Intact 2 Access 8
HMA-11 61 1 Fire Door (Assumed) No Restricted 10 Intact 1 Maintenance 10
HMA-05 61 2 Transite Board No No 10 Intact 1 Access 9
HMA-09 61 2 Mastic on Piping Yes No 7 Damage 2 Maintenance 6
Removal Priority 3
Building 61 - 1st Floor
Current Condition 1
Building 61 - Service Room & Pipe Space
Friable Yes/No
Accessibility Yes/No
Restricted
Potential for Disturbance 2
Homogeneous Area No. Bldg Floor Material Description
Building 61 - 2nd Floor
2008 THREE-YEAR ASBESTOS REINSPECTION
CONDITION AND REMOVAL PRIORITY TABLE
Removal Priority 3
Current Condition 1Friable Yes/No
Accessibility Yes/No
Restricted
Potential for Disturbance 2
Homogeneous Area No. Bldg Floor Material Description
HMA-05 61 Attic Transite Board No No 10 Intact 1 Access 9
HMA-07 61 Attic Pipe Insulation & Fittings Yes No 7 Damage 2 Access 6
HMA-10 61 Attic Black Tar on Ductwork No No 9 Condition 2 Access 9
HMA-12 61 Attic Insulation on Spotlight Cords Yes No 8 Condition 1 Access 9
Building 61 - Attic
Master Summary Table Asbestos Bulk Samples
2008 THREE-YEAR ASBESTOS REINSPECTION
SUMMARY OF BULK SAMPLES TAKEN TO DATE
Building Floor Room Sample ID Material Description
JB61 01 128A JB-61-001-T-128A-19 Gray TSI JB61 01 104 JB-61-01-M-104-03 4" black cove base JB61 01 104 JB-61-01-M-104-04 2x2 gray worm ceiling tile JB61 01 104 JB-61-01-M-104-05 4" brown cove base JB61 01 108 JB-61-01-M-108-02 6" black cove base JB61 01 112 JB-61-01-M-112-07 2x2 gray rough textured ceiling tile JB61 01 112 JB-61-01-M-112-08 2x2 gray worm 2/pinholes ceiling tile JB61 01 113 JB-61-01-M-113A-06 Brown/white vinyl covered gypsum drywall partition JB61 01 121 JB-61-01-M-121-09 Gray cement asbestos pegboard JB61 01 121 JB-61-01-M-121-10 6" brown cove base JB61 01 131 JB-61-01-M-131-23 1x1 off-white coarse ceiling tile JB61 01 131 JB-61-01-M-131-24 1x1 gray worm w/pinhole ceiling tile JB61 01 H103 JB-61-01-M-H103-36 Brown batt insulation JB61 01 101 JB-61-01-S-101-01 White/off-white hardwall plaster JB61 01 121 JB-61-01-S-121-28 White spray-on surfacing material JB61 01 121 JB-61-01-S-121-29 White other JB61 01 121 JB-61-01-S-121-30 Off-white other JB61 01 132 JB-61-01-S-132-25 White dented surfacing material JB61 01 132 JB-61-01-S-132-26 White other JB61 01 132 JB-61-01-S-132-27 White other JB61 01 132 JB-61-01-S-132-31 White rough surfacing material JB61 01 132 JB-61-01-S-132-32 Off-white other JB61 01 132 JB-61-01-S-132-33 Off-white other JB61 01 132 JB-61-01-S-132-34 Off-white other JB61 01 132 JB-61-01-S-132-35 Off-white other JB61 01 101 JB-61-01-T-101-11 White/blue magnesia pipe lagging JB61 01 101 JB-61-01-T-101-12 White/blue TSI JB61 01 101 JB-61-01-T-101-13 White TSI JB61 01 101 JB-61-01-T-101-14 Gray/blue mudded joint fitting on magnesia pipe lagging JB61 01 101 JB-61-01-T-101-15 Gray TSI JB61 01 101 JB-61-01-T-101-16 Gray TSI JB61 01 101 JB-61-01-T-101-17 Gray cardboard wrap pipe lagging JB61 01 101 JB-61-01-T-101-20 Gray mudded joint fitting on cardboard lagging JB61 01 114A JB-61-01-T-114A-18 Gray TSI JB61 01 114A JB-61-01-T-114A-21 Gray TSI JB61 01 128A JB-61-01-T-128A-22 Gray TSI JB61 01 128A JB-61-01-T-128A-37 Black mudded joint tar fitting on fiberglass JB61 01 128A JB-61-01-T-128A-38 Black TSI JB61 01 128A JB-61-01-T-128A-39 Black TSI JB61 02 201 JB-61-02-M-201-05 1x1 black acoustical panel JB61 02 202 JB-61-02-M-202-02 6" black cove base JB61 02 207 JB-61-02-M-207-03 Gray cement asbestos pegboard JB61 02 H201 JB-61-02-M-H201-04 Brown batt insulation JB61 02 209 JB-61-02-S-209-01 Beige hardwall plaster
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Purple = Abated ACM
1994 Initial Asbestos Inspection
2008 THREE-YEAR ASBESTOS REINSPECTION
SUMMARY OF BULK SAMPLES TAKEN TO DATE
Building Floor Room Sample ID Material Description
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Purple = Abated ACM
JB61 1 104 JB-61-01-F-104-001A Layer 1 - Green 9x9 floor tile JB61 1 104 JB-61-01-F-104-001A Layer 2 - Black mastic JB61 1 104 JB-61-01-F-104-002A Layer 1 - White 12x12 floor tile JB61 1 104 JB-61-01-F-104-002A Layer 2 - Black mastic JB61 1 104 JB-61-01-S-104-003A Black mastic JB61 1 107 JB-61-01-F-107-004A White 12x12 floor tile, black mastic JB61 1 104A JB-61-01-F-104A-005A Layer 1 - Green 9x9 floor tile JB61 1 104A JB-61-01-F-104A-005A Layer 2 - Black mastic JB61 1 104A JB-61-01-F-104A-006A Layer 1 - Green 9x9 floor tile JB61 1 104A JB-61-01-F-104A-006A Layer 2 - Black mastic JB61 1 H103 JB-61-01-F-H103-007A Layer 1 - Green 9x9 floor tile JB61 1 H103 JB-61-01-F-H103-007A Layer 2 - Black mastic JB61 1 H103 JB-61-01-F-H103-008A Layer 1 -Black 9x9 floor tile JB61 1 H103 JB-61-01-F-H103-008A Layer 2 - Black mastic JB61 1 H103 JB-61-01-F-H103-009A Layer 1 - Green 9x9 floor tile JB61 1 H103 JB-61-01-F-H103-009A Layer 2 - Black mastic JB61 1 H103 JB-61-01-F-H103-010A Layer 1 - Black 9x9 floor tile JB61 1 H103 JB-61-01-F-H103-010A Layer 2 - Black mastic JB61 1 131 JB-61-01-F-131-011A Layer 1 - White 9x9 floor tile JB61 1 131 JB-61-01-F-131-011A Layer 2 - Black mastic JB61 1 131 JB-61-01-F-131-012A Layer 1 - Black 9x9 floor tile JB61 1 131 JB-61-01-F-131-012A Layer 2 - Black mastic JB61 1 131 JB-61-01-F-131-013A Layer 1 - White 9x9 floor tile JB61 1 131 JB-61-01-F-131-013A Layer 2 - Black mastic JB61 1 131 JB-61-01-F-131-014A Layer 1 - Black 9x9 floor tile JB61 1 131 JB-61-01-F-131-014A Layer 2 - Black mastic JB61 1 131 JB-61-01-F-131-015A Layer 1 - White 9x9 floor tile JB61 1 131 JB-61-01-F-131-015A Layer 2 - Black mastic JB61 1 131 JB-61-01-F-131-016A Layer 1 - Black 9x9 floor tile JB61 1 131 JB-61-01-F-131-016A Layer 2 - Black mastic JB61 1 H101 JB-61-01-S-H101-017A White 2x2 peg board sheet of transite JB61 1 H101 JB-61-01-T-H101-018A Layer 1 - 3" vertical - black mastic JB61 1 H101 JB-61-01-T-H101-018A Layer 2 - 3" vertical - fiberglass insulation JB61 1 121 JB-61-01-F-121-019A Layer 1 - Brown 12x12 floor tile JB61 1 121 JB-61-01-F-121-019A Layer 2 - Black mastic JB61 1 125 JB-61-01-M-125-020A White vibration isolator JB61 1 132 JB-61-01-M-132-021A White spray-on material on ceiling JB61 1 133 JB-61-01-M-133-022A Green stage curtain JB61 1 133 JB-61-01-M-133-023A Brown stage curtain JB61 1 135 JB-61-01-F-135-024A Layer 1 - Red 9x9 floor tile JB61 1 135 JB-61-01-F-135-024A Layer 2 - Black mastic JB61 1 107A JB-61-01-F-107A-025A Black mastic JB61 1 101 JB-61-01-F-101-026A White 12x12 floor tile, yellow mastic JB61 1 103 JB-61-01-T-103-027A 6" elbow - white wrap, white block insulation JB61 1 101 JB-61-01-T-101-028A 2" elbow - black mastic, wrap
2008 Asbestos Reinspection
2008 THREE-YEAR ASBESTOS REINSPECTION
SUMMARY OF BULK SAMPLES TAKEN TO DATE
Building Floor Room Sample ID Material Description
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Purple = Abated ACM
JB61 1 101 JB-61-01-M-101-029A White fabric JB61 1 101 JB-61-01-M-101-030A Green vibration isolator fabric JB61 0 G101 JB-61-00-T-G01-031A Layer 1 - Gray/white canvas wrap JB61 0 G101 JB-61-00-T-G01-031A Layer 2 - Yellow insulation JB61 0 G101 JB-61-00-M-G01-032A Green/white vibration isolator fabric JB61 2 206 JB-61-02-T-206-033A Black mastic on piping JB61 3 AS01 JB-61-03-T-AS01-034A 8" elbow - white wrap, white block insulation JB61 3 AS01 JB-61-03-T-AS01-035A Layer 1 - 8" horizontal - white wrap JB61 3 AS01 JB-61-03-T-AS01-035A Layer 2 - White block insulation JB61 3 AS01 JB-61-03-M-AS01-036A White insulation on spotlight cord JB61 2 Roof JB-61-02-S-RF-037A Gray roof flashing, black tar JB61 3 Roof JB-61-03-S-RF-038A Black roofing tar, felt
Asbestos-Containing Bulk Samples
2008 THREE-YEAR ASBESTOS REINSPECTION
LIST OF ASBESTOS-CONTAINING SAMPLES
Building Floor Room Sample ID Material Description
JB61 01 128A JB-61-001-T-128A-19 Gray TSI JB61 01 121 JB-61-01-M-121-09 Gray cement asbestos pegboard JB61 01 101 JB-61-01-T-101-11 White/blue magnesia pipe lagging JB61 01 101 JB-61-01-T-101-12 White/blue TSI JB61 01 101 JB-61-01-T-101-13 White TSI JB61 01 101 JB-61-01-T-101-16 Gray TSI JB61 01 101 JB-61-01-T-101-17 Gray cardboard wrap pipe lagging JB61 01 114A JB-61-01-T-114A-18 Gray TSI JB61 01 128A JB-61-01-T-128A-37 Black mudded joint tar fitting on fiberglass JB61 01 128A JB-61-01-T-128A-38 Black TSI JB61 01 128A JB-61-01-T-128A-39 Black TSI JB61 02 207 JB-61-02-M-207-03 Gray cement asbestos pegboard
JB61 1 104 JB-61-01-F-104-001A Layer 1 - Green 9x9 floor tile JB61 1 104 JB-61-01-F-104-002A Layer 1 - White 12x12 floor tile JB61 1 107 JB-61-01-F-107-004A White 12x12 floor tile, black mastic JB61 1 104A JB-61-01-F-104A-005A Layer 1 - Green 9x9 floor tile JB61 1 104A JB-61-01-F-104A-006A Layer 1 - Green 9x9 floor tile JB61 1 H103 JB-61-01-F-H103-007A Layer 1 - Green 9x9 floor tile JB61 1 H103 JB-61-01-F-H103-008A Layer 1 -Black 9x9 floor tile JB61 1 H103 JB-61-01-F-H103-009A Layer 1 - Green 9x9 floor tile JB61 1 H103 JB-61-01-F-H103-010A Layer 1 - Black 9x9 floor tile JB61 1 131 JB-61-01-F-131-011A Layer 1 - White 9x9 floor tile JB61 1 131 JB-61-01-F-131-012A Layer 1 - Black 9x9 floor tile JB61 1 131 JB-61-01-F-131-013A Layer 1 - White 9x9 floor tile JB61 1 131 JB-61-01-F-131-014A Layer 1 - Black 9x9 floor tile JB61 1 131 JB-61-01-F-131-015A Layer 1 - White 9x9 floor tile JB61 1 131 JB-61-01-F-131-016A Layer 1 - Black 9x9 floor tile JB61 1 H101 JB-61-01-S-H101-017A White 2x2 peg board sheet of transite JB61 1 H101 JB-61-01-T-H101-018A Layer 1 - 3" vertical - black mastic JB61 1 121 JB-61-01-F-121-019A Layer 1 - Brown 12x12 floor tile JB61 1 132 JB-61-01-M-132-021A White spray-on material on ceiling JB61 1 135 JB-61-01-F-135-024A Layer 1 - Red 9x9 floor tile JB61 1 107A JB-61-01-F-107A-025A Black mastic JB61 0 G101 JB-61-00-T-G01-031A Layer 1 - Gray/white canvas wrap JB61 2 206 JB-61-02-T-206-033A Black mastic on piping JB61 3 AS01 JB-61-03-T-AS01-035A Layer 2 - White block insulation JB61 3 AS01 JB-61-03-M-AS01-036A White insulation on spotlight cord
1994 Initial Asbestos Inspection
2008 Asbestos Reinspection
2008 Reinspection Inspection Logs
Client: Date: September 18, 2008 Location: Inspector(s): Donald Joiner and Joshua Anders Address: 1 Jefferson Barracks Drive, St. Louis, Missouri
Note:
Sample ID Material Description Floor Room Location
JB-61-01-F-104-001A Layer 1 - Green 9x9 floor tile 1 104 Center of floor underneath access panel
JB-61-01-F-104-001A Layer 2 - Black mastic 1 104 Center of floor underneath access panel
JB-61-01-F-104-002A Layer 1 - White 12x12 floor tile 1 104 Northeast quadrant in front of door
JB-61-01-F-104-002A Layer 2 - Black mastic 1 104 Northeast quadrant in front of door
JB-61-01-S-104-003A Black mastic 1 104 Southeast quadrant above ceiling tile above window on brick wall
JB-61-01-F-107-004A White 12x12 floor tile, black mastic 1 107 Northwest corner of room 107 behind door
JB-61-01-F-104A-005A Layer 1 - Green 9x9 floor tile 1 104A South middle of wall in between both sets of windows
JB-61-01-F-104A-005A Layer 2 - Black mastic 1 104A South middle of wall in between both sets of windows
JB-61-01-F-104A-006A Layer 1 - Green 9x9 floor tile 1 104A Northwest corner of room 104A
JB-61-01-F-104A-006A Layer 2 - Black mastic 1 104A Northwest corner of room 104A
JB-61-01-F-H103-007A Layer 1 - Green 9x9 floor tile 1 H103 East end of hall H103 in corner by doors below pipes
JB-61-01-F-H103-007A Layer 2 - Black mastic 1 H103 East end of hall H103 in corner by doors below pipes
JB-61-01-F-H103-008A Layer 1 -Black 9x9 floor tile 1 H103 East end of hall H103 in corner by doors below pipes
JB-61-01-F-H103-008A Layer 2 - Black mastic 1 H103 East end of hall H103 in corner by doors below pipes
JB-61-01-F-H103-009A Layer 1 - Green 9x9 floor tile 1 H103 West end of hall H103 by doors to room 101
ASBESTOS INSPECTION LOG
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non ACM (determined by Point Count analysis)
Jefferson Barracks Division - Building 61 St. Louis V. A. Medical Center
Address: 1 Jefferson Barracks Drive, St. Louis, Missouri
Note:
Sample ID Material Description Floor Room Location
ASBESTOS INSPECTION LOG
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non ACM (determined by Point Count analysis)
Jefferson Barracks Division - Building 61 St. Louis V. A. Medical Center
JB-61-01-F-H103-009A Layer 2 - Black mastic 1 H103 West end of hall H103 by doors to room 101
JB-61-01-F-H103-010A Layer 1 - Black 9x9 floor tile 1 H103 West end of H103 by the doors to room 101
JB-61-01-F-H103-010A Layer 2 - Black mastic 1 H103 West end of H103 by the doors to room 101
JB-61-01-F-131-011A Layer 1 - White 9x9 floor tile 1 131 Northeast corner by exit door
JB-61-01-F-131-011A Layer 2 - Black mastic 1 131 Northeast corner by exit door
JB-61-01-F-131-012A Layer 1 - Black 9x9 floor tile 1 131 Northeast corner by exit door
JB-61-01-F-131-012A Layer 2 - Black mastic 1 131 Northeast corner by exit door
JB-61-01-F-131-013A Layer 1 - White 9x9 floor tile 1 131 Southwest corner beside doors
JB-61-01-F-131-013A Layer 2 - Black mastic 1 131 Southwest corner beside doors
JB-61-01-F-131-014A Layer 1 - Black 9x9 floor tile 1 131 Southwest corner beside doors
JB-61-01-F-131-014A Layer 2 - Black mastic 1 131 Southwest corner beside doors
JB-61-01-F-131-015A Layer 1 - White 9x9 floor tile 1 131 East wall underneath water fountain
JB-61-01-F-131-015A Layer 2 - Black mastic 1 131 East wall underneath water fountain
JB-61-01-F-131-016A Layer 1 - Black 9x9 floor tile 1 131 East wall underneath water fountain
JB-61-01-F-131-016A Layer 2 - Black mastic 1 131 East wall underneath water fountain
Address: 1 Jefferson Barracks Drive, St. Louis, Missouri
Note:
Sample ID Material Description Floor Room Location
ASBESTOS INSPECTION LOG
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non ACM (determined by Point Count analysis)
Jefferson Barracks Division - Building 61 St. Louis V. A. Medical Center
JB-61-01-S-H101-017A White 2x2 peg board sheet of transite 1 H101 On hallway wall straight across from entrance door
JB-61-01-T-H101-018A Layer 1 - 3" vertical - black mastic 1 H101 Above ceiling tile in H101 in front of entry door
JB-61-01-T-H101-018A Layer 2 - 3" vertical - fiberglass insulation 1 H101 Above ceiling tile in H101 in front of entry door
JB-61-01-F-121-019A Layer 1 - Brown 12x12 floor tile 1 121 Northwest corner of room 121 behind door
JB-61-01-F-121-019A Layer 2 - Black mastic 1 121 Northwest corner of room 121 behind door
JB-61-01-M-125-020A White vibration isolator 1 125 East wall behind HVAC
JB-61-01-M-132-021A White spray-on material on ceiling 1 132 Northeast corner above exit doors on ceiling in lobby
JB-61-01-M-133-022A Green stage curtain 1 133 South end of stage at the end of the curtain
JB-61-01-M-133-023A Brown stage curtain 1 133 South end of stage at the end of the curtain
JB-61-01-F-135-024A Layer 1 - Red 9x9 floor tile 1 135 South quadrant by middle of inside wall
JB-61-01-F-135-024A Layer 2 - Black mastic 1 135 South quadrant by middle of inside wall
JB-61-01-F-107A-025A Black mastic 1 107A Middle of room 107A
JB-61-01-F-101-026A White 12x12 floor tile, yellow mastic 1 101 Northwest corner beside water fountain
JB-61-01-T-103-027A 6" elbow - white wrap, white block insulation 1 103 Northeast corner of room 103 at ceiling
JB-61-01-T-101-028A 2" elbow - black mastic, wrap 1 101 South end of room 101 on HVAC unit - east side of unit
Address: 1 Jefferson Barracks Drive, St. Louis, Missouri
Note:
Sample ID Material Description Floor Room Location
ASBESTOS INSPECTION LOG
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non ACM (determined by Point Count analysis)
Jefferson Barracks Division - Building 61 St. Louis V. A. Medical Center
JB-61-01-M-101-029A White fabric 1 101 South end of room 101 on pin setting machine #2
JB-61-01-M-101-030A Green vibration isolator fabric 1 101 South end of room 101 on HVAC unit
JB-61-00-T-G01-031A Layer 1 - Gray/white canvas wrap 0 G01 Northeast quadrant on airhandler unit S61-1
JB-61-00-T-G01-031A Layer 2 - Yellow insulation 0 G01 Northeast quadrant on airhandler unit S61-1
JB-61-00-M-G01-032A Green/white vibration isolator fabric 0 G01 Northeast quadrant inside airhandler unit S61-1
JB-61-02-T-206-033A Black mastic on piping 2 206 Southwest corner by door
JB-61-03-T-AS01-034A 8" elbow - white wrap, white block insulation 3 AS01 North wall above the end of catwalk
JB-61-03-T-AS01-035A Layer 1 - 8" horizontal - white wrap 3 AS01 North wall above the end of catwalk
JB-61-03-T-AS01-035A Layer 2 - White block insulation 3 AS01 North wall above the end of catwalk
JB-61-03-M-AS01-036A White insulation on spotlight cord 3 AS01 Southwest quadrant in attic above auditorium
JB-61-02-S-RF-037A Gray roof flashing, black tar 2 Roof Middle of building roof at base of roof vent
JB-61-03-S-RF-038A Black roofing tar, felt 3 Roof Northwest quadrant of roof by green tin roof
Address: 1 Jefferson Barracks Drive, St. Louis, Missouri
Note:
Sample ID Material Description Floor Room Location
ASBESTOS INSPECTION LOG
Red = Asbestos-Containing Material (ACM) Blue = Non ACM Green = Non ACM (determined by Point Count analysis)
Jefferson Barracks Division - Building 61 St. Louis V. A. Medical Center
GOOD = Surfacing material has no visible damage or small amounts of damage; covering on thermal system insulation is intact or has small amounts of damage; miscellaneous materials intact; no visible debris or small amounts of debris. FAIR = Surfacing material has moderate but not extensive amounts of visible damage; covering on thermal system insulation is cut or torn, exposing moderate but not extensive amounts of insulation; moderate but not extensive damage to miscellaneous materials such as floor tile; moderate but not extensive amounts of visible dust and debris. POOR = Extensive damage to surfacing material; covering on thermal system insulation is cut or torn extensively and insulation itself is damaged; miscellaneous materials such as floor tile extensively damaged and underlying mastic exposed; extensive amounts of dust and debris.
Material Category: F = Flooring S = Surfacing T = TSI M = Miscellaneous Friability: F=Friable NF=Non-Friable Condition: Good = 8, 9, 10 Fair = 4, 5, 6, 7 Poor = 1, 2, 3
Red = Asbestos-Containing Material Blue = Non Asbestos-Containing MaterialPlease use the following guidelines when reading this report:
Bulk Sample Location Drawings
SERVICE ROOM AND PIPE SPACE
1st FLOOR
2ND FLOOR
ATTIC
2008 Reinspection Photographs
BUILDING 61
sample does not contain asbestos
JB-61-01-F-104-001A JB-61-01-F-104-002A
JB-61-01-S-104-003A JB-61-01-F-107-004A
sample contains asbestos
JB-61-01-F-104A-005A JB-61-01-F-104A-006A
JB-61-01-F-H103-007A JB-61-01-F-H103-008A
JB-61-01-F-H103-009A JB-61-01-F-H103-010A
JB-61-01-F-131-011A JB-61-01-F-131-012A
JB-61-01-F-131-013A JB-61-01-F-131-014A
JB-61-01-F-131-015A JB-61-01-F-131-016A
JB-61-01-S-H101-017A JB-61-01-T-H101-018A
JB-61-01-F-121-019A JB-61-01-M-125-020A
JB-61-01-S-132-021A JB-61-01-M-133-022A
JB-61-01-M-133-023A JB-61-01-F-135-024A
JB-61-01-F-107A-025A JB-61-01-F-101-026A
JB-61-01-T-103-027A JB-61-01-T-101-028A
JB-61-01-M-101-029A JB-61-01-M-101-030A
JB-61-00-T-G01-031A JB-61-00-M-G01-032A
JB-61-02-T-206-033A JB-61-03-T-A501-034A
JB-61-03-T-A501-035A JB-61-03-M-A501-036A
JB-61-03-S-RFT-037A
JB-61-03-S-RFT-038A
2008 Reinspection Laboratory Reports
Sample Location Appearance % Type
AsbestosNon-Asbestos
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804635
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
10100 Woolworth Road Keithville, LA 71047
Customer PO:
Received: 09/19/08 4:15 PM
08-14529 VAMC Reinspection JB Building 61 1st floor (Corrected report issued 10/10/08.) (Corrected report issued 11/03/08) (Corrected report issued 11/21/08)
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/20/2008Analysis Date:
Report Date: 11/21/2008
EMSL Analytical, Inc.
3029 S. Jefferson, Saint Louis, MO 63118 Phone: (314) 577-0150 Fax: (314) 776-3313 Email: saintlouislab@emsl.com
JB-61-01-F-104-
001A floortile 390804635-0001
9x9 green fl tile w/black mastic over concrete
Green Non-Fibrous
Heterogeneous
Chrysotile19%Non-fibrous (other)81%
JB-61-01-F-104-
001A adhesive 390804635-0001A
9x9 green fl tile w/black mastic over concrete
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)98% Quartz2%
JB-61-01-F-104-
002A floortile 390804635-0002 white 12x12 ft w/black mastick over concrete
White Non-Fibrous
Heterogeneous
Chrysotile6%Non-fibrous (other)94%
JB-61-01-F-104-
002A adhesive 390804635-0002A white 12x12 ft w/black mastick over concrete
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
JB-61-01-S-104-
003A 390804635-0003 black mastic on brick wall
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)96% Quartz4%
JB-61-01-F-107-
004A floortile 390804635-0004 white 12x12 ft w/black mastic over concrete
White Non-Fibrous
Heterogeneous
Chrysotile6%Non-fibrous (other)94%
JB-61-01-F-107-
004A adhesive 390804635-0004A white 12x12 ft w/black mastic over concrete
Black Non-Fibrous
Heterogeneous
Chrysotile19%Non-fibrous (other)79% Quartz2%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
Analysis performed by EMSL St. Louis (AIHA #102636, NVLAP # 200742-0, CA ELAP #2668)
Sue Ferrario (43) mailto:saintlouislab@emsl.com
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804635
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
10100 Woolworth Road Keithville, LA 71047
Customer PO:
Received: 09/19/08 4:15 PM
08-14529 VAMC Reinspection JB Building 61 1st floor (Corrected report issued 10/10/08.) (Corrected report issued 11/03/08) (Corrected report issued 11/21/08)
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/20/2008Analysis Date:
Report Date: 11/21/2008
EMSL Analytical, Inc.
3029 S. Jefferson, Saint Louis, MO 63118 Phone: (314) 577-0150 Fax: (314) 776-3313 Email: saintlouislab@emsl.com
JB-61-01-F-104A-
005A floortile 390804635-0005
9x9 green ft w/black mastic over concrete
Green Non-Fibrous
Heterogeneous
Chrysotile19%Non-fibrous (other)81%
JB-61-01-F-104A-
005A adhesive 390804635-0005A
9x9 green ft w/black mastic over concrete
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)98% Quartz2%
JB-61-01-F-104A-
006A floortile 390804635-0006
9x9 green ft w/black mastic over concrete
Green Non-Fibrous
Heterogeneous
Chrysotile19%Non-fibrous (other)81%
JB-61-01-F-104A-
006A adhesive 390804635-0006A
9x9 green ft w/black mastic over concrete
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)98% Quartz2%
JB-61-01-F-H103-
007A floortile 390804635-0007
9x9 green ft w/black mastic over concrete
Green Non-Fibrous
Heterogeneous
Chrysotile19%Non-fibrous (other)81%
JB-61-01-F-H103-
007A adhesive 390804635-0007A
9x9 green ft w/black mastic over concrete
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)98% Quartz2%
JB-61-01-F-H103-
008A floortile 390804635-0008
9x9 black ft w/black mastic over concrete
Black Non-Fibrous
Heterogeneous
Chrysotile19%Non-fibrous (other)81%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
Analysis performed by EMSL St. Louis (AIHA #102636, NVLAP # 200742-0, CA ELAP #2668)
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804635
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
10100 Woolworth Road Keithville, LA 71047
Customer PO:
Received: 09/19/08 4:15 PM
08-14529 VAMC Reinspection JB Building 61 1st floor (Corrected report issued 10/10/08.) (Corrected report issued 11/03/08) (Corrected report issued 11/21/08)
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/20/2008Analysis Date:
Report Date: 11/21/2008
EMSL Analytical, Inc.
3029 S. Jefferson, Saint Louis, MO 63118 Phone: (314) 577-0150 Fax: (314) 776-3313 Email: saintlouislab@emsl.com
JB-61-01-F-H103-
008A adhesive 390804635-0008A
9x9 black ft w/black mastic over concrete
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)98% Quartz2%
JB-61-01-F-H103-
009A floortile 390804635-0009
9x9 green ft w/black mastic
Green Non-Fibrous
Heterogeneous
Chrysotile19%Non-fibrous (other)81%
JB-61-01-F-H103-
009A adhesive 390804635-0009A
9x9 green ft w/black mastic
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)98% Quartz2%
JB-61-01-F-H103-
010A floortile 390804635-0010
9x9 black ft w/black mastic
Black Non-Fibrous
Heterogeneous
Chrysotile9%Non-fibrous (other)91%
JB-61-01-F-H103-
010A adhesive 390804635-0010A
9x9 black ft w/black mastic
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
JB-61-01-F-131-
011A floortile 390804635-0011 white 9x9 ft w/black mastic on concrete
White Non-Fibrous
Heterogeneous
Chrysotile19%Non-fibrous (other)81%
JB-61-01-F-131-
011A adhesive 390804635-0011A white 9x9 ft w/black mastic on concrete
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)98% Quartz2%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
Analysis performed by EMSL St. Louis (AIHA #102636, NVLAP # 200742-0, CA ELAP #2668)
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804635
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
10100 Woolworth Road Keithville, LA 71047
Customer PO:
Received: 09/19/08 4:15 PM
08-14529 VAMC Reinspection JB Building 61 1st floor (Corrected report issued 10/10/08.) (Corrected report issued 11/03/08) (Corrected report issued 11/21/08)
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/20/2008Analysis Date:
Report Date: 11/21/2008
EMSL Analytical, Inc.
3029 S. Jefferson, Saint Louis, MO 63118 Phone: (314) 577-0150 Fax: (314) 776-3313 Email: saintlouislab@emsl.com
JB-61-01-F-131-
012A floortile 390804635-0012 black 9x9 ft w/black mastic on concrete
Black Non-Fibrous
Heterogeneous
Chrysotile9%Non-fibrous (other)91%
JB-61-01-F-131-
012A adhesive 390804635-0012A black 9x9 ft w/black mastic on concrete
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)98% Quartz2%
JB-61-01-F-131-
013A floortile 390804635-0013 white 9x9 ft w/black mastic
White Non-Fibrous
Heterogeneous
Chrysotile19%Non-fibrous (other)81%
JB-61-01-F-131-
013A adhesive 390804635-0013A white 9x9 ft w/black mastic
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)100%
JB-61-01-F-131-
014A floortile 390804635-0014 black 9x9 ft w/black mastic
Black Non-Fibrous
Heterogeneous
Chrysotile9%Non-fibrous (other)91%
JB-61-01-F-131-
014A adhesive 390804635-0014A black 9x9 ft w/black mastic
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)98% Quartz2%
JB-61-01-131-015A
floortile 390804635-0015 white 9x9 ft w/black mastic
White Non-Fibrous
Heterogeneous
Chrysotile19%Non-fibrous (other)81%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%. The above test report relates only to the items tested and may not be reproduced in any form without the express written approval of EMSL Analytical, Inc. EMSL’s liability is limited to the cost of analysis. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation and use of test results are the responsibility of the client. Samples received in good condition unless otherwise noted. This report must not be used to claim product endorsement by NVLAP or any agency of the U.S. Government.
Analysis performed by EMSL St. Louis (AIHA #102636, NVLAP # 200742-0, CA ELAP #2668)
% Fibrous % Non-Fibrous
Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized Light Microscopy
390804635
Attn: Roy W. Dowling ALTEC Environmental Consultants, Inc.
10100 Woolworth Road Keithville, LA 71047
Customer PO:
Received: 09/19/08 4:15 PM
08-14529 VAMC Reinspection JB Building 61 1st floor (Corrected report issued 10/10/08.) (Corrected report issued 11/03/08) (Corrected report issued 11/21/08)
Customer ID: ALT50
Fax: (318) 687-9923 Phone: (318) 687-3771 Project:
EMSL Order:
EMSL Proj:
9/20/2008Analysis Date:
Report Date: 11/21/2008
EMSL Analytical, Inc.
3029 S. Jefferson, Saint Louis, MO 63118 Phone: (314) 577-0150 Fax: (314) 776-3313 Email: saintlouislab@emsl.com
JB-61-01-131-015A
adhesive 390804635-0015A white 9x9 ft w/black mastic
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)98% Quartz2%
JB-61-01-131-016A
floortile 390804635-0016 black 9x9 ft w/black mastic
Black Non-Fibrous
Heterogeneous
Chrysotile9%Non-fibrous (other)91%
JB-61-01-131-016A
adhesive 390804635-0016A black 9x9 ft w/black mastic
Black None Detected
Non-Fibrous
Heterogeneous
Non-fibrous (other)98% Quartz2%
JB-61-01-S-H101-
017A 390804635-0017 white 2x2 pegboard sheets of transite
White Non-Fibrous
Heterogeneous
Chrysotile19%Non-fibrous (other)81%
JB-61-01-T-H101-
018A adhesive 390804635-0018 black mastic on 3" pipe/white wrap/insulation
Black Non-Fibrous
Heterogeneous
Chrysotile12%Non-fibrous (other)88%
JB-61-01-T-H101-
018A insulation 390804635-0018A black mastic on 3" pipe/white wrap/insulation
White None Detected
Fibrous
Heterogeneous
Glass39% Min. Wool40%
Non-fibrous (other)21%
JB-61-01-F-121-
019A floortile 390804635-0019 brown 12x12 ft w/black mastic on concrete
Brown Non-Fibrous
Heterogeneous
Chrysotile19%Non-fibrous (other)81%
Jeff Siria, Laboratory Manager or other approved signatory
PLM-1
Analyst(s)
Due to magnification limitations inherent in PLM, asbestos fibers in dimensions below the resolution capability of PLM may not be detected. The limit of detection as stated in the method is 1%.