36C25023B0049 - Amendment 2.pdf
PDF 1 MB Posted
- Solicitation number
- 36C25023B0049
About this file
This solicitation is for the construction of a chiller plant at the Chalmers P. Wylie VAACC in Columbus, Ohio. The solicitation is a set-aside for service-disabled veteran-owned small businesses. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 is the issuing agency. The work includes installing electrical conduits, pull boxes, and substations to support new electrical equipment for the chiller plant. Bids are due by July 27, 2023. The awarded contractor will be responsible for submitting coordination drawings for conduit routing with equipment submittals.
The related federal contract opportunity document provides additional details on the electrical scope of work. It includes specifications for low-voltage power conductors and cables, grounding diagrams, one-line diagrams, and substation details. Equipment required includes switchgear, transformers, generators, panelboards, and metering devices. The contractor must coordinate work with the existing electrical infrastructure and utility provider.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
5. PROJECT NUMBER (if applicable)
CODE 7. ADMINISTERED BY
2. AMENDMENT/MODIFICATION NUMBER
CODE
6. ISSUED BY
8. NAME AND ADDRESS OF CONTRACTOR
4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE
9A. AMENDMENT OF SOLICITATION NUMBER
9B. DATED
PAGE OF PAGES
10A. MODIFICATION OF CONTRACT/ORDER NUMBER
10B. DATED
BPA NO. 1. CONTRACT ID CODE
FACILITY CODE CODE
Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:
The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers
E. IMPORTANT:
is extended,
(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.
12. ACCOUNTING AND APPROPRIATION DATA
(REV. 11/2016)
is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.
15C. DATE SIGNED
B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).
RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.
C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:
D. OTHER
Contractor
16C. DATE SIGNED
14. DESCRIPTION OF AMENDMENT/MODIFICATION
16B. UNITED STATES OF AMERICA
Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.
15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER
15B. CONTRACTOR/OFFEROR
STANDARD FORM 30 PREVIOUS EDITION NOT USABLE
Prescribed by GSA - FAR (48 CFR) 53.243
(Type or print) (Type or print)
(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)
(Number, street, county, State and ZIP Code)
(If other than Item 6)
(Specify type of modification and authority)
(such as changes in paying office, appropriation date, etc.)
(If required)
(SEE ITEM 11)
(SEE ITEM 13)
(X)
CHECK
ONE
13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,
IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.
11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS
AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT
(Signature of person authorized to sign) (Signature of Contracting Officer)
1 15
0002 757-15-102
36C250
Department of Veterans Affairs VA Healthcare System Network Contracting Office (NCO) 10 2780 Airport Dr - Suite 340 Columbus OH 43219
36C250
Department of Veterans Affairs VA Healthcare System Network Contracting Office (NCO) 10 2780 Airport Dr - Suite 340 Columbus OH 43219
To all Offerors/Bidders 36C25023B0049
07-27-2023 X
X X
X 01
The purpose of this solicitation amendment is to provide technical documents to support the information provided in amendment 0001. Please see the continuation pages of this amendment for the technical documents.
All other terms & conditions remain unchanged and in full effect.
Brian S. Kish Contracting Officer
CONTINUATION PAGE
Construct Chiller Plant
Chalmers P. Wylie VAACC
Columbus, OH 43219
Project # 757-15-102
SDVOSB Set-Aside
See attached document: SECTION 26 05 19 - LOW-VOLTAGE ELECTRICAL POWER
CONDUCTORS AND CABLES.
See attached document: E-201 - PARTIAL SECOND FLOOR ELECTRICAL EQUIPMENT
AND RACEWAY LAYOUT PLAN - SOUTH.
See attached document: E-604 - ELECTRICAL GROUNDING SYSTEM DIAGRAM.
See attached document: E-602 - BOILER PLANT CHILLER PLANT ONE-LINE DIAGRAM.
See attached document: E-506 - SUBSTATION DETAIL AND GENERAL NOTES.
01-01-17
26 05 19 - 1
SECTION 26 05 19
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies the furnishing, installation, connection, and testing of the electrical conductors and cables for use in electrical systems rated 600 V and below, indicated as cable(s), conductor(s), wire, or wiring in this section.
1.2 RELATED WORK
A. Section 07 84 00, FIRESTOPPING: Sealing around penetrations to maintain the integrity of fire-resistant rated construction.
B. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS:
Requirements that apply to all sections of Division 26.
C. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS:
Requirements for personnel safety and to provide a low impedance path for possible ground fault currents.
D. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Conduits for conductors and cables.
E. Section 26 05 41, UNDERGROUND ELECTRICAL CONSTRUCTION: Installation of conductors and cables in manholes and ducts.
1.3 QUALITY ASSURANCE
A. Quality Assurance shall be in accordance with Paragraph, QUALIFICATIONS
(PRODUCTS AND SERVICES) in Section 26 05 11, REQUIREMENTS FOR
ELECTRICAL INSTALLATIONS.
1.4 SUBMITTALS
A. Submit in accordance with Paragraph, SUBMITTALS in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, and the following requirements:
1. Shop Drawings:
a. Submit sufficient information to demonstrate compliance with drawings and specifications.
b. Submit the following data for approval:
26 05 19 - 2
1) Electrical ratings and insulation type for each conductor and cable.
2) Splicing materials and pulling lubricant.
2. Certifications: Two weeks prior to final inspection, submit the following.
a. Certification by the manufacturer that the conductors and cables conform to the requirements of the drawings and specifications.
b. Certification by the Contractor that the conductors and cables have been properly installed, adjusted, and tested.
1.5 APPLICABLE PUBLICATIONS
A. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. Publications are reference in the text by designation only.
B. American Society of Testing Material (ASTM):
D2301-10................Standard Specification for Vinyl Chloride
Plastic Pressure-Sensitive Electrical
Insulating Tape
D2304-10................Test Method for Thermal Endurance of Rigid
Electrical Insulating Materials
D3005-10................Low-Temperature Resistant Vinyl Chloride
Plastic Pressure-Sensitive Electrical
Insulating Tape
C. National Electrical Manufacturers Association (NEMA):
WC 70-09................Power Cables Rated 2000 Volts or Less for the
Distribution of Electrical Energy
D. National Fire Protection Association (NFPA):
70-17...................National Electrical Code (NEC)
E. Underwriters Laboratories, Inc. (UL):
44-14...................Thermoset-Insulated Wires and Cables
83-14...................Thermoplastic-Insulated Wires and Cables
467-13..................Grounding and Bonding Equipment
486A-48.................6B-13 Wire Connectors
486C-13.................Splicing Wire Connectors
486D-15.................Sealed Wire Connector Systems
26 05 19 - 3
486E-15.................Equipment Wiring Terminals for Use with
Aluminum and/or Copper Conductors
493-07..................Thermoplastic-Insulated Underground Feeder and
Branch Circuit Cables
514B-12.................Conduit, Tubing, and Cable Fittings
PART 2 - PRODUCTS
2.1 CONDUCTORS AND CABLES
A. Conductors and cables shall be in accordance with ASTM, NEMA, NFPA, UL, as specified herein, and as shown on the drawings.
B. All conductors shall be copper.
C. Single Conductor and Cable:
1. No. 12 AWG: Minimum size, except where smaller sizes are specified herein or shown on the drawings.
2. All conductors #10AWG and small shall be solid copper. All conductors larger than #10AWG shall be stranded copper.
3. Insulation: THHN-THWN and XHHW-2. XHHW-2 shall be used for isolated power systems.
D. Color Code:
1. No. 10 AWG and smaller: Solid color insulation or coating.
2. No. 8 AWG and larger: Color-coded using one of the following:
a. Solid color insulation or solid color coating.
b. Stripes, bands, or hash marks of color specified.
c. Color using 19 mm (0.75 inches) wide tape.
3. For modifications and additions to existing wiring systems, color coding shall conform to the existing wiring system.
4. Conductors shall be color-coded as follows:
208/120 V Phase 480/277 V
Black A Brown
Red B Orange
Blue C Yellow
White Neutral Gray *
26 05 19 - 4
* or white with colored (other than green) tracer.
5. Lighting circuit "switch legs", and 3-way and 4-way switch
"traveling wires," shall have color coding that is unique and distinct (e.g., pink and purple) from the color coding indicated above. The unique color codes shall be solid and in accordance with the NEC. Coordinate color coding in the field with the COR.
6. Color code for isolated power system wiring shall be in accordance with the NEC.
2.2 SPLICES
A. Splices shall be in accordance with NEC and UL.
B. Above Ground Splices for No. 10 AWG and Smaller:
1. Solderless, screw-on, reusable pressure cable type, with integral insulation, approved for copper and aluminum conductors.
2. The integral insulator shall have a skirt to completely cover the stripped conductors.
3. The number, size, and combination of conductors used with the connector, as listed on the manufacturer's packaging, shall be strictly followed.
C. Above Ground Splices for No. 8 AWG to No. 4/0 AWG:
1. Compression, hex screw, or bolt clamp-type of high conductivity and corrosion-resistant material, listed for use with copper and aluminum conductors.
2. Insulate with materials approved for the particular use, location, voltage, and temperature. Insulation level shall be not less than the insulation level of the conductors being joined.
3. Splice and insulation shall be product of the same manufacturer.
4. All bolts, nuts, and washers used with splices shall be zinc-plated steel.
D. Above Ground Splices for 250 kcmil and Larger:
1. Long barrel "butt-splice" or "sleeve" type compression connectors, with minimum of two compression indents per wire, listed for use with copper and aluminum conductors.
26 05 19 - 5
2. Insulate with materials approved for the particular use, location, voltage, and temperature. Insulation level shall be not less than the insulation level of the conductors being joined.
3. Splice and insulation shall be product of the same manufacturer.
E. Underground Splices for No. 10 AWG and Smaller:
1. Solderless, screw-on, reusable pressure cable type, with integral insulation. Listed for wet locations, and approved for copper and aluminum conductors.
2. The integral insulator shall have a skirt to completely cover the stripped conductors.
3. The number, size, and combination of conductors used with the connector, as listed on the manufacturer's packaging, shall be strictly followed.
F. Underground Splices for No. 8 AWG and Larger:
1. Mechanical type, of high conductivity and corrosion-resistant material. Listed for wet locations, and approved for copper and aluminum conductors.
2. Insulate with materials approved for the particular use, location, voltage, and temperature. Insulation level shall be not less than the insulation level of the conductors being joined.
3. Splice and insulation shall be product of the same manufacturer.
G. Plastic electrical insulating tape: Per ASTM D2304, flame-retardant, cold and weather resistant.
2.3 CONNECTORS AND TERMINATIONS
A. Mechanical type of high conductivity and corrosion-resistant material, listed for use with copper and aluminum conductors.
B. Long barrel compression type of high conductivity and corrosion-resistant material, with minimum of two compression indents per wire, listed for use with copper and aluminum conductors.
C. All bolts, nuts, and washers used to connect connections and terminations to bus bars or other termination points shall be zinc-plated steel.
26 05 19 - 6
2.4 CONTROL WIRING
A. Unless otherwise specified elsewhere in these specifications, control wiring shall be as specified herein, except that the minimum size shall be not less than No. 14 AWG.
B. Control wiring shall be sized such that the voltage drop under in-rush conditions does not adversely affect operation of the controls.
2.5 WIRE LUBRICATING COMPOUND
A. Lubricating compound shall be suitable for the wire insulation and conduit, and shall not harden or become adhesive.
B. Shall not be used on conductors for isolated power systems.
PART 3 - EXECUTION
3.1 GENERAL
A. Installation shall be in accordance with the NEC, as shown on the drawings, and manufacturer's instructions.
B. Install all conductors in raceway systems.
C. Splice conductors only in outlet boxes, junction boxes, pullboxes, manholes, or handholes.
D. Conductors of different systems (e.g., 120 V and 277 V) shall not be installed in the same raceway.
E. Install cable supports for all vertical feeders in accordance with the
NEC. Provide split wedge type which firmly clamps each individual cable and tightens due to cable weight.
F. In panelboards, cabinets, wireways, switches, enclosures, and equipment assemblies, neatly form, train, and tie the conductors with non-metallic ties.
G. For connections to motors, transformers, and vibrating equipment, stranded conductors shall be used only from the last fixed point of connection to the motors, transformers, or vibrating equipment.
H. Use expanding foam or non-hardening duct-seal to seal conduits entering a building, after installation of conductors.
I. Conductor and Cable Pulling:
26 05 19 - 7
1. Provide installation equipment that will prevent the cutting or abrasion of insulation during pulling. Use lubricants approved for the cable.
2. Use nonmetallic pull ropes.
3. Attach pull ropes by means of either woven basket grips or pulling eyes attached directly to the conductors.
4. All conductors in a single conduit shall be pulled simultaneously.
5. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.
J. No more than three branch circuits shall be installed in any one conduit.
K. When stripping stranded conductors, use a tool that does not damage the conductor or remove conductor strands.
3.2 SPLICE AND TERMINATION INSTALLATION
A. Splices and terminations shall be mechanically and electrically secure, and tightened to manufacturer's published torque values using a torque screwdriver or wrench.
B. Where the Government determines that unsatisfactory splices or terminations have been installed, replace the splices or terminations at no additional cost to the Government.
3.3 CONDUCTOR IDENTIFICATION
A. When using colored tape to identify phase, neutral, and ground conductors larger than No. 8 AWG, apply tape in half-overlapping turns for a minimum of 75 mm (3 inches) from terminal points, and in junction boxes, and pullboxes. Apply the last two laps of tape with no tension to prevent possible unwinding. Where cable markings are covered by tape, apply tags to cable, stating size and insulation type.
3.4 FEEDER CONDUCTOR IDENTIFICATION
A. In each interior pullbox and each underground handhole, install brass tags on all feeder conductors to clearly designate their circuit identification and voltage. The tags shall be the embossed type, 40 mm
(1-1/2 inches) in diameter and 40 mils thick. Attach tags with plastic ties.
26 05 19 - 8
3.5 EXISTING CONDUCTORS
A. Unless specifically indicated on the plans, existing conductors shall not be reused.
3.6 CONTROL WIRING INSTALLATION
A. Unless otherwise specified in other sections, install control wiring and connect to equipment to perform the required functions as specified or as shown on the drawings.
B. Install a separate power supply circuit for each system, except where otherwise shown on the drawings.
3.7 CONTROL WIRING IDENTIFICATION
A. Install a permanent wire marker on each wire at each termination.
B. Identifying numbers and letters on the wire markers shall correspond to those on the wiring diagrams used for installing the systems.
C. Wire markers shall retain their markings after cleaning.
D. In each handhole, install embossed brass tags to identify the system served and function.
3.8 ACCEPTANCE CHECKS AND TESTS
A. Perform in accordance with the manufacturer's recommendations. In addition, include the following:
1. Visual Inspection and Tests: Inspect physical condition.
2. Electrical tests:
a. After installation but before connection to utilization devices, such as fixtures, motors, or appliances, test conductors phase-to-phase and phase-to-ground resistance with an insulation resistance tester. In addition, test existing re-used conductors.
b. Applied voltage shall be 500 V DC for 300 V rated cable, and 1000
V DC for 600 V rated cable. Apply test for one minute or until reading is constant for 15 seconds, whichever is longer. Minimum insulation resistance values shall not be less than 25 megohms for 300 V rated cable and 100 megohms for 600 V rated cable.
c. Perform phase rotation test on all three-phase circuits.
26 05 19 - 9
---END---
UP
B.8 B.8
C.3 C.3
D.4 D.4
E.3 E.3
NEW
SS-CP2
NEW
SS-CP1
EXISTING
NPSS-1
EXISTING
GPSS-1
ATS-HLS
X
ATS-HEQ
X
ATS-HCR
X
X
F R
O N
T
F R
O N
T
/4
2000KVA/2660KVA
13.2KV:480/277V
XFMR
W/FORCED AIR
480V
DIST.
NORMAL
PRIMARY
EM.
PRIMARY
MAIN
TIE BUS
SECTION
10' - 4 13/16"
7' - 2"
6' - 3 1/4" 4' - 0"
2000KVA/2660KVA
13.2KV:480/277V
XFMR
W/FORCED AIR
480V
DIST.
NORMAL
PRIMARY
MAIN
TIE
BREAKER
SECTION
7' - 2"
6' - 3 1/4"4' - 0"
4' - 9 1/4" 5' - 6"
/4
M
IN
7' - 0"
7' - 0"
7' - 0"
F R
O N
T
PRIMARY
750KVA
13.2KV:480/277V
XFMR
MAIN
480V
DISTRIBUTION
480V
DISTRIBUTION
4' - 0 9/16" 3' - 9 3/4" 11' - 4 13/16"
5' - 6" 4' - 9 1/4"
X
X
X
X
X
480V
DISTRIBUTION
480V
DISTRIBUTION
480V
DISTRIBUTION
MAIN
2500KVA
13.2KV:480/277V
XFMR
PRIMARY
EM.
PRIMARY
3' - 1 1/4"
21 3 4
0.8 0.8
2.7
BUSBAR
FEEDER
CT-3
CT
CT-4
CT
CT-2
CT
CT-1
CT
EF-1
EF
NORMAL POWER
ELECTRICAL
ROOM
CORRIDOR
MECH. ROOM
STAIR A
ESSENTIAL
POWER
ELECTRICAL
ROOM
TYP
TYP
3"C3"C 4"C
4"C 4"C 3"C 3"C
3"C 3"C 3"C 3"C
4"C4"C4"C
PAN HEATERS
PAN HEATERS
CT-1
CT-2
CT-3
CT-4
E-202
WALKING CLEARANCE WALKING CLEARANCE
WALKING CLEARANCE
REFER TO E-202
3"C 3"C 3"C
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/8 /2
:5
:0
A
M
E-201
PARTIAL SECOND FLOOR ELECTRICAL
EQUIPMENT AND RACEWAY LAYOUT PLAN -
SOUTH
CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00 3
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
ENLARGED SECOND FLOOR ELECTRICAL
EQUIPMENT AND RACEWAY LAYOUT PLAN 1N
# CODED NOTES
PROVIDE 4'(L) x 4'(H) x 1'-6"(D) NEMA 4X PULLBOX ON EXISTING WALL WITH GASKETED COVER FOR ELECTRICAL CONDUITS. REFER TO PLANS FOR CONDUIT DIMENSIONS. VERIFY MOUNTING HEIGHT AND EXACT CONDUIT ROUTE IN FIELD PRIOR TO INSTALLATION.
EXISTING LIGHTING FIXTURES IN THE ESSENTIAL POWER ELECTRICAL ROOM AND NORMAL POWER ELECTRICAL ROOM THAT INTERFERE WITH THE NEW ELECTRICAL SUBSTATIONS AND CONDUIT ROUTES SHALL BE REMOVED AND RELOCATED TO LIGHT EXISTING AND NEW PATHS WITHIN THE ROOM. PROVIDE CONDUIT AND WIRES EXTENSIONS VIA 3/4"C - 3#12 AND 1#12EG.
PROVIDE 4'-8"(L) x 4'(H) x 1-6"(D) NEMA 4X PULLBOX ON EXISTING WALL WITH GASKETED COVER FOR ELECTRICAL CONDUITS. REFER TO PLANS FOR CONDUIT DIMENSIONS. VERIFY MOUNTING HEIGHT AND EXACT CONDUIT ROUTE IN FIELD PRIOR TO INSTALLATION.
PROVIDE 2'(L) x 2'(H) x 1'-6"(D) NEMA 4X PULLBOX ON EXISTING WALL WITH GASKETED COVER FOR ELECTRICAL CONDUITS. REFER TO PLANS FOR CONDUIT DIMENSIONS. VERIFY MOUNTING HEIGHT AND EXACT CONDUIT ROUTE IN FIELD PRIOR TO INSTALLATION.
ROUTE CONDUITS DOWN THROUGH ROOF INTO CHILLER PLANT CEILING SPACE. PROVIDE PRE-FABRICATED ROOF PENETRATION BELOW
PULL-BOX.
CONDUIT ROUTING INDICATED FOR REFERENCE ONLY. CONTRACTOR IS RESPONSIBLE FOR SUBMITTING CONDUIT ROUTING COORDINATION DRAWINGS WITH ELECTRICAL EQUIPMENT SUBMITTAL FOR APPROVAL. ROUTING DRAWINGS SHALL INCLUDE FIELD VERIFIED ROUTING, BENDS, PULLBOXES, CONDUIT BODIES, PENETRATIONS, ETC. CONTRACTOR SHALL INCLUDE EXISTING CONDITIONS WHERE NECESSARY TO CONVEY ROUTING INFORMATION. MAINTAIN NEC REQUIRED ACCESSIBILITY TO ALL EXISTING PULLBOXES, JUNCTION BOXES, ETC. TO REMAIN. ELECTRICAL
EQUIPMENT SUBMITTAL WILL NOT BE APPROVED WITHOUT CONDUIT ROUTING DRAWINGS.
CONDUIT ROUTING GENERAL NOTE
SECOND FLOOR CONDUIT IN
EXISTING BUILDING
CONDUIT TIGHT TO BOTTOM OF
STRUCTURE IN NEW CHILLER
PLANT
CONDUIT LEGEND
Revisions: Date:
FINAL BID & CONSTRUCTION 11/24/2021
FINAL BID & CONSTRUCTION (REVISED) 05/06/2022
AMEDMENT 1 08/05/2022
GEC - GROUNDING ELECTRODE CONDUCTOR (NEC ARTICLE 250, TABLE 250.66)
MBJ - MAIN BONDING JUMPER (NEC ARTICLE 250.28, TABLE 250.102(C)(1))
SSBJ - SUPPLY SIDE BONDING JUMPER (NEC ARTICLE 250.30 (B)(2), TABLE 250.102(C)(1))
SBJ - SYSTEM BONDING JUMPER (NEC ARTICLE 250.30(1), TABLE 250.102(C)(1))
EG - EQUIPMENT GROUNDING CONDUCTOR (NEC ARTICLE 250, TABLE 250.122)
N - GROUNDED CIRCUIT CONDUCTOR (NEUTRAL)
GECT - GROUNDING ELECTRODE CONDUCTOR TAP (NEC 250.30(A)(6), TABLE 250.66)
NGR - NEUTRAL GROUNDING RESISTOR
ABBREVIATIONS/CODE REFERENCES
EXISTING
UTILITY
TRANSFORMER
SERVICE
PRIMARY
(BY UTILITY)
G
N
G
X
X
EXISTING
NORMAL
PARALLELING
SWITCHGEAR
GX
G
EXISTING
EMERGENCY
PARALLELING
SWITCHGEAR
G G
D
EG
X XR
EXISTING
TYPICAL UNIT
SUBSTATION
TYPICAL
480/277V PANEL BOARD
N
GG
N
SBJ
ELECTRICAL ROOM
EQUIPMENT GROUND BAR
EXISTING
TELECOMMUNICATIONS ROOM
EQUIPMENT GROUND BAR
EXISTING
X
X X XX X
X
X
X
X
X
TO EXISTING
GROUNDING ELECTRODE SYSTEM
(STRUCTURAL STEEL FRAMING, GAS
AND METAL WATER PIPING, WATER
SERVICE, GROUND RING, ETC.)
NEW BUILDING STEEL SHALL BE
BONDED TO EXISTING BUILDING
STEEL. REFER TO INSET DETAIL
BELOW.
EXISTING
TYPICAL UNIT
SUBSTATION
TYPICAL
480/277V PANEL BOARD
N
GG
N
SBJ X
X
X
X X
G
XR
1750KW, 480V-3PH-3W
EMERGENCY GENERATOR
N
XR
480V:13.2KV TRANSFORMER
G G
SSBJ
XR
XR
XR
XR
XR
G
SBJ
C
B
GEC
NON-METALLIC
PROTECTIVE SLEEVE
CONNECTION LISTED
FOR PURPOSE
NEW 2000KW, 13.2KV-3PH-3W
EMERGENCY GENERATOR
N
CONCRETE ENCASED ELECTRODE
(GENERATOR SUPPORT PAD)
A
CONCRETE FOUNDATION
(MIN OF 20FT) IN DIRECT
CONTACT WITH EARTH.
NEUTRAL GROUNDING
RESISTOR
MBJ
CONSTRUCT GENERATOR SUPPORT PAD AS A CONCRETE ENCASED ELECTRODE. GENERATOR PAD SHALL
MEET ALL THE REQUIREMENTS OF NEC 250.52(A)(3).
PROVIDE NEW GEC AND CONNECT COMPLETE TO CONCRETE ENCASED ELECTRODE THROUGH NEW NGR.
REFER TO "PARTIAL SITE ELECTRICAL PLAN" FOR NGR SPECIFICATION INFORMATION.
PROVIDE SYSTEM BONDING JUMPER (SIZED PER NEC, REFER TO ABOVE FOR REFERENCES)
PROVIDE EG FROM NEW GENERATOR GROUNDING CONNECTION POINT TO EMERGENCY PARALLELING SWITCHGEAR GROUNDING POINT. COORDINATE EXACT TERMINATION LOCATION IN FIELD AND WITH
GENERATOR MANUFACTURER. EG SHALL BE SIZED AS INDICATED ON ONE-LINE DIAGRAM.
GROUNDING ELECTRODE CONDUCTOR [GEC] (NEC ARTICLE 250, TABLE 250.66)
CODED NOTES
A
B
C
D
XX
NOT TO SCALE
G
NON-METALLIC
PROTECTIVE SLEEVE
CONNECTION LISTED
FOR PURPOSE
EXISTING 2000KW, 13.2KV-3PH-3W
EMERGENCY GENERATOR
N
CONCRETE ENCASED ELECTRODE
(GENERATOR SUPPORT PAD)
CONCRETE FOUNDATION
(MIN OF 20FT) IN DIRECT
CONTACT WITH EARTH.
NEUTRAL GROUNDING
RESISTOR
X XR
BOND STEEL
ACROSS BUILDING
EXPANSION JOINT
EXISTING BUILDING STEEL
EFFECTIVELY GROUNDED
BUILDING STEEL COLUMN
NEW BUILDING STEEL
STEEL BASE PLATE
BASE PLATE NUT AND ANCHOR BOLT
INTO REINFORCED CONCRETE PIER OR
FOOTING. ANCHOR BOLT BONDED TO
CONCRETE REINFORCING.
50% OF NEW COLUMNS
ALONG SEPARATION
CAD WELDED CAD WELDED
E
GEC
E
#4AWG
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/7 /2
:0
:2
P M
E-604
ELECTRICAL GROUNDING SYSTEM DIAGRAM CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00
GROUNDING ELECTRODE SYSTEM DETAIL 1
Revisions: Date:
FINAL BID & CONSTRUCTION 11/24/2021
FINAL BID & CONSTRUCTION (REVISED) 05/06/2022
SEL700G
EXISTING
UNDER
PROJECT
NUMBER:
757-20-205
NEW
1200AF
FUTURE
G
NEW
GENERATOR "GEN #3"
2000kW-13.2kV-3∅-3W
DIESEL
NEW SUBSTATION SS-CP1
4000A, 480/277V, 3Ø, 4W, 65kAIC
K K
NEW SUBSTATION SS-CP2
4000A, 480/277V, 3Ø, 4W, 65kAIC
K
NEW DISTRIBUTION CPDP1
1000A, 480/277V, 3Ø, 4W, 65kAIC
NEW DISTRIBUTION CPDP2
1000A, 480/277V, 3Ø, 4W, 65kAIC
EPM EPM EPM EPM
EPM
EPM EPM EPM EPM
EPM
TVSSTVSS
SEL700G
86868686
SEL700GT
52 52
SEL751ASEL751ASEL751AASEL751AA
SEL751AB
UTILITY #1
1200AF
1200AF
(N.O.)
BUSSED SPACE
(FUTURE LOOP
SS-1/SS-4)
1200AF
(N.C.)
1200AF
X
CONTROL
SECTION
TIE #2
1200AF
1200AF
GEN1-MCB
XR
GENERATOR "GEN #1"
1750kW-480/277V-3∅-4W
DIESEL
H1T1 2000kVA
480V:13.2kV
EXISTING PARALLELING SWITCHGEAR 'PSG'
1200A, 13.5kV, 3Ø, 3W, 500MVA
4"GRC -
3#2 (MV-105 15kV SHIELDED) & 1#4 EG (600V)
B2
EXISTING SUBSTATION NPSS1 - NORMAL POWER
1200A, 480/277V, 3Ø, 4W, 35kAIC
A
F A
T
750kVA 13,200V:4 80/277V 3Ø-4W
1200AF
1200AT
A
F A
T
400AF
400AT
A
P R
O V
IS
IO
N
A
P R
O V
IS
IO
N
A
P R
O V
IS
IO
N
A
P R
O V
IS
IO
N
225AF
225AT
225AF
225AT
100AF
100AT
SPARE SPARE
225AF
225AT
800AF
800AT
EXISTING SUBSTATION GPSS1 - EMERGENCY POWER
4000A, 480/277V, 3Ø, 4W, 65kAIC
A
F A
T
2500kVA 13,200V:480/277V
3Ø-4W
4000AF
4000AT
A
F A
T
225AF
225AT
A
P R
O V
IS
IO
N
A
P R
O V
IS
IO
N
A
P R
O V
IS
IO
N
225AF
225AT
100AF
100AT
225AF
225AT
SPARE SPARE
800AF
800AT
N E
ATS-HEQ1
800A, 4-POLE
X
N E
ATS-HCR
225A, 4-POLE
X
N E
ATS-HLS
100A, 4-POLE
X
TO EXISTING UTILITY SERVICE
DISCONNECT 13.2kV,3W
TO EXISTING UNIT
SUBSTATION SS-4
TO EXISTING UNIT
SUBSTATION SS-1 (FUTURE LOOP -
CONDUIT ONLY)
480/277V
MLO
225A
H1NA
208/120V
MCB
175A
H1N1
H1TN1
45kVA 480V:208 /120V X
X
X
480/277V
MLO
100A
H1SA
208/120V
MCB
60A
H1S1
H1TS1
15kVA 480V:208/120V X
X
X
480/277V
MLO
225A
H1CA
208/120V
MCB
175A
H1C1
H1TC1
45kVA 480V:208/120V X
X
X
480/277V
MLO
800A
H1EA
208/120V
MCB
175A
H1E1
H1TE1
45kVA 480V:208/120V X
X
X
2500AF
2500AT
TO EXISTING EMERGENCY
SWITCHBOARD 'CISBEMA'
(SUPPLIES MAIN BUILDING ATS)
X
T2
TIE #1
1200AF
EXISTING UNDER
PROJECT NUMBER: 757-20-205
GENERATOR "GEN #2"
2000kW-13.2kV-3∅-3W
DIESEL
NEW
PULLBOX
1200AF
G G
XR
XR
XR
TVSS TVSS
X
X
X X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
L O
O P
A
L O
O P
B
XR X XXXXXXX
X
2'PSG-N'
EXISTING UNDER
PROJECT
NUMBER:
757-20-205
H1TS2
30kVA 480V:208/120V X
208/120V
MCB
100A
H1S2 X
X
NON-FUSED DISC. SW.
X
EXISTING
86 1200AF52
VFD VFDVFD
CHILLER
CH-1
CHILLER
CH-2
PP1 PP2 TP1
125A-3P
LSI
TP2
125A-3P
LSI
CT1
110A-3P
LSI
CT2
110A-3P
LSI
225A-3P
LSI
225A-3P
LSI
100A-3P
VFDVFD VFD
C P
L O
O P
A
C P
L O
O P
B
4000A, 3Ø, 4W BUSDUCT
"G
R C
M V
-1 k V
S H
IE
L D
E D
/0
E G
V
"G
R C
M V
-1 k V
S H
IE
L D
E D
/0
E G
V
4"GRC - 3#350 (MV-105 15kV SHIELDED) & 1#1/0 EG (600V)CP - EMERG.
4"GRC - 3#350 (MV-105 15kV SHIELDED) & 1#1/0 EG (600V)CP - EMERG.
1200AF
1200AT
LSIG
100%
VFD VFD VFD VFD VFDVFD
1200AF
1200AT
LSIG
100%
1200AF
1000AT
LSIG
100%
1200AF
PROV.
1200AF
1200AT
LSIG
100%
1200AF
1200AT
LSIG
100%
1200AF
1000AT
LSIG
100%
1200AF
1000AT
LSIG
100%
2000kVA/2660kVA
(AA/FA)
13,200V:480/277V 3Ø-4W
MAIN
4000AF
4000AT
100% LSIG
N .O
A
S
250E
N .C
A
S
250E
TIE
4000AF
4000AT
LSIG
100%
2000kVA/2660kVA
(AA/FA)
13,200V:480/277V 3Ø-4W
MAIN
4000AF
4000AT
100%
N .O
A
S
250E
N .C
A
S
250E
225 125 125 125 125 100
EXISTING PAD NEW PAD
CHILLER
PLANT WALL
TO EXISTING
GENERATOR
"GEN #2"
SECTION
TO EXISTING
GENERATOR
"GEN #2"
H1TS3
30kVA 480V:208/120V
NEW
(PROVIDED WITH
GENERATOR)
208/120V
MCB
100A
H1S3 (PROVIDED WITH
GENERATOR)
(PROVIDED WITH
GENERATOR)
NON-FUSED DISC. SW.
(PROVIDED WITH
GENERATOR)
(PROVIDED WITH
GENERATOR)
125A-3P
LSI
125A-3P
LSI
110A-3P
LSI
110A-3P
LSI
225A-3P
LSI
225A-3P
LSI
225 225 125 125 125 125
1000N8008001000N800800
X
X
X
800 TON
(784 MCA)
800 TON
(784 MCA)
CHILLER
CH-3
CHILLER
CH-4
SEL751AB SEL700G
SEL700G
PP4 TP4 CT4PP3 TP3 CT3
EF-1
75HP75HP125HP125HP60HP60HP 60HP60HP75HP75HP125HP125HP
200A
RATED
200A
RATED
PAN
HEATERS
CT-1 & 2
100A
RATED
200A
RATED
200A
RATED
VFD VFD
800 TON
(784 MCA)
800 TON
(784MCA)
VFD VFD
SEL751A
1200AF
(N.O.)
X X
'PSG-E'
52 86
SEL751AA
1200AF
EXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTING
1200AF
(N.C.)
SEL751AB
SEL751AA
52 86
NEW
1200AF
(N.O.)
1200AF
(N.O.)
SEL751AB
XR
EMERG. NORMAL EMERG. NORMAL
60A-3P
SSF-1
60A
RATED
30A
RATED
3HP
PAC-
AHU-4
110A-3P
LSI
VFD
100A-3P
PAN
HEATERS
CT-3 & 4
100A
RATED
K K K K
EXISTING H1EB - SQUARE D - NF
400A, 480/277V, 3Ø, 4W, 65kAIC
20A-3P 20A-1P15A-3P 15A-3P 15A-3P 60A-3P 60A-3P
NEW
480/277V
MLO
100A
H1EC
EXISTING
UNDER
PROJECT
NUMBER:
757-20-205
480/277V
MLO
100A
H1ED
(PROVIDED
WITH
GENERATOR)
660NX
20A-1P 20A-1P 15A-3P
NEW
HEAT
TRACE
PANEL
#5
HEAT
TRACE
PANEL
#3
HEAT
TRACE
PANEL
#4
(6)20A-1P
SPARE
X
ROP-1 DA-1
PUMP
#1
DA-1
PUMP
#2
DA-1
PUMP
#3
XXXX
20A-3P
NEW
20A-3P
NEW
20A-3P
NEW
FUEL
OIL
PUMPS
GEN DAY
TANK 1
GEN DAY
TANK 2
2HP 1HP 1HP
15A-3P
NEW
BOILER
PLANT
DOOR
1HP
B1
U1 A2
A1 T1 T2 T3 E1 E2
C1 E3 E4 LB G1 G2 G3 G4
LOAD BANK
& TEMP GEN
NP1 NP2 GP1 GP2
CP1E CP1N CP1M CP1T CP2E CP2N CP2M
B BBB
TEMP.
CHILLER
CONNECTION
BOX
ISC 3P: 45,911A
ISC SLG: 44,265A
ISC 3P: 51,188A
ISC SLG: 47,407A
ISC 3P: 32,756A
ISC SLG: 26,137A
ISC 3P: 40,374A
ISC SLG: 33,033A
ISC 3P: 2,477A
ISC SLG: 2,556A
ISC 3P: 629A
ISC SLG: 629A
ADDITIONAL
PROVISIONS NOT
SHOWN. REFER
TO BREAKER
SCHEDULE.
ADDITIONAL
PROVISIONS NOT
SHOWN. REFER
TO BREAKER
SCHEDULE.
SQUARE D - NF
REMOVE EXISTING 20A-1P CIRCUIT BREAKERS AS REQUIRED TO ACCOMMODATE NEW BREAKERS.
SQUARE D - NF
SQUARE D - NF
SQUARE D - NF
SQUARE D - NF SQUARE D - HCP
SQUARE D - NQ
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/7 /2
:0
:1
P M
E-602
BOILER PLANT / CHILLER PLANT ONE-LINE
DIAGRAM
CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00
# ONE-LINE CODED NOTES
1 EXISTING IN-GRADE, CONCRETE POLYMER ELECTRICAL BOX. REFER TO ELECTRICAL PLANS FOR LOCATION.
CONTRACTOR SHALL BE PERMITTED TO UTILIZE (1) OF EXISTING CONDUITS FOR NEW GENERATOR FEEDER TO EXISTING PSG LOCATION IN LIEU OF PROVIDING NEW GENERATOR FEEDER CONDUIT SHOWN ON PLANS.
THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE STRUCTURAL INTEGRITY OF THE EXISTING CONDUITS. OWNER SHALL NOT BE RESPONSIBLE FOR ELECTRICAL CABLE PULL FAILURE IN EXISTING CONDUITS AND RESULTING NEW UNDERGROUND FEEDER SHALL BE PROVIDED AT NO ADDITIONAL COST TO
THE GOVERNMENT.
PROVIDE A NEW GENERATOR BREAKER CUBICLE AND ASSOCIATED GENERATOR FEEDER CIRCUIT BREAKER IN EXISTING 'PSG-E' LINEUP. EXISTING MANUFACTURER IS RUSSELECTRIC. CUBICLE, BREAKER, METERING, RELAYS, ETC. SHALL MATCH EXISTING GENERATOR BREAKERS. ROUTE GENERATOR FEEDER TO NEW
BREAKER CUBICLE AND CONNECT COMPLETE.
RETAIN RUSSELECTRIC MANUFACTURER REPRESENTATIVE TO REPROGRAM EXISTING RUSSELECTRIC PARALLELING SWITCHGEAR TO CONNECT NEW GENERATOR #2 AS A NEW EMERGENCY GENERATOR AND PROGRAM PROTECTION (INCLUDING DIFFERENTIAL PROTECTION), CONTROL, PARALLELING AND LOAD
SHARING CAPABILITIES WITH EXISTING GENERATOR.
PROVIDE PULLBOX AS INDICATED ON SITE ELECTRICAL PLAN. REFER TO DRAWING FOR ADDITIONAL
INFORMATION AND WORK REQUIREMENTS.
REMOVE (3) EXISTING 20A-1P CIRCUIT BREAKERS AND PROVIDE (1) NEW 60A-3P CIRCUIT BREAKER IN EXISTING LIFE SAFETY PANEL AND CONNECT COMPLETE TO NEW TRANSFORMER PROVIDED WITH GENERATOR.
CIRCUIT BREAKER SHALL BE LOCKABLE AND TRANSFORMER SHALL BE FIELD-MARKED WITH DISCONNECTING
MEANS LOCATION PER NEC 450.14.
REMOVE (3) EXISTING 20A-1P CIRCUIT BREAKERS AND PROVIDE NEW BREAKER IN EXISTING ESSENTIAL EQUIPMENT PANEL. CONNECT COMPLETE TO NEW PANELBOARD PROVIDED WITH GENERATOR. REFER TO
ONE LINE DIAGRAM FOR BREAKER SIZE.
PROVIDE NEW LOAD BREAKER IN EXISTING CUBICLE. BREAKER, METERING, RELAYS, ETC. SHALL MATCH EXISTING LOAD BREAKERS. ROUTE GENERATOR FEEDER TO NEW BREAKER CUBICLE AND CONNECT
COMPLETE. COORDINATE REQUIREMENTS WITH RUSSELECTRIC.
EACH GENERATOR DAY TANK WILL HAVE (2) REDUNDANT POWER FEEDS. REFER TO GENERATOR PUMP
SYSTEM DETAIL AND MECHANICAL CONNECTIONS PLAN FOR ADDITIONAL INFORMATION.
PROVIDE NEW FACTORY-ASSEMBLED TEMPORARY CHILLER ELECTRICAL CONNECTIONS BOX AND CONNECT COMPLETE TO TEMPORARY CHILLER FEEDER INDICATED. REFER TO FLOOR PLAN AND NOTES FOR LOCATION AND BASIS OF DESIGN INFORMATION. COORDINATE WITH VENDOR TO ENSURE COMPATIBILITY WITH
EQUIPMENT SELECTED FOR CONSTRUCTION.
ONE-LINE GENERAL NOTES
REFER TO ONE-LINE LEGEND AND NOTES ON ELECTRICAL LEGEND SHEET FOR ADDITIONAL INFORMATION AND
WORK REQUIREMENTS.
CIRCUIT BREAKERS SHALL BE ASSUMED TO BE 3-POLE UNLESS OTHERWISE NOTED.
RETAIN RUSSELECTRIC TO PROVIDE EQUIPMENT INFORMATION, PROGRAMMING, TESTING, AND ADDITIONAL
SUPPORT DURING CONSTRUCTION PERIOD.
1.
2.
3.
METER SUBMITTAL REQUIREMENTS
CONTRACTOR SHALL BE RESPONSIBLE FOR METERING EACH EXISTING FACILITY TRANSFER SWITCH AND PROVIDE A REPORT TO VA COR AND ENGINEER. REPORT WILL BE USED FOR PARALLELING SWITCHGEAR SMART
LOADING PROGRAMMING.
REPORT SHALL BE PERFORMED DURING PEAK USAGE MONTHS (JULY OR AUGUST) FOR A 30-DAY DURATION.
REPORT SHALL INCLUDE PEAK DEMAND (KVA, KW, KVAR), VOLTAGE (PHASE TO PHASE AND PHASE TO NEUTRAL), CURRENT PER PHASE, POWER FACTOR, AND FREQUENCY
1.
2.
3.
Revisions: Date:
FINAL BID & CONSTRUCTION 11/24/2021
FINAL BID & CONSTRUCTION (REVISED) 05/06/2022
AMEDMENT 1 08/05/2022
INSTRUCTIONAL EQUIPMENT PLACARD:
BASIS OF DESIGN EQUIPMENT NOTES:
EPM
EPM
EPM
NEW SUBSTATION 'SS-CP1'
4000A, 13.2KV:480/277V-3∅-4W
NEW SUBSTATION 'SS-CP2'
4000A, 13.2KV:480/277V-3∅-4W
DISTRIBUTION
BREAKERS
TIE BREAKER
GROUND
FAULT
SCHEME
PRIMARY SWITCH
TRANSFORMER
FEEDER
TERMINATIONS
ELECTRIC
POWER METER
KEY
INTERLOCKING
TVSS
NAMEPLATE
ENCLOSURE
MAIN BUS
MAIN BREAKER
DISTRIBUTION
BREAKERS
GROUND
FAULT
SCHEME
PRIMARY SWITCH
TRANSFORMER
FEEDER
TERMINATIONS
ELECTRIC
POWER METER
KEY
INTERLOCKING
TVSS
NAMEPLATE
ENCLOSURE
MAIN BUS
MAIN BREAKER
EPM
PRIMARY
DUPLEX
PRIMARY
DUPLEX
20"W MAX 20"W MAX
DRY-TYPE TRANSFORMER
108"W 36"W 22"W 36"W
BREAKER
BREAKER
BREAKER
EPM
EPM
EPM
TVSS PROVISION
EPM
DRY-TYPE TRANSFORMER
108"W 36"W 22"W 36"W
BREAKER
PROVISION
BREAKER
EPM
EPM
TVSS PROVISION
PRIMARY
DUPLEX
PRIMARY
DUPLEX
20"W MAX 20"W MAX
EPM
K
K K K
K K K K
EPM
K
A1 A1
A1
A2
A2
A3
A3 A3 A3 B1 B1 B2 B3 B3 B3
B1
B2
B3
MB1
4000AF
4000AT
100%
250E
4000A, 480/277V-3∅-4W, SILVER-PLATED COPPER AT 1000AMPS PER SQUARE INCH - MIN. 65,000A RMS SYMMETRICAL SHORT CIRCUIT BRACING - FULL LENGTH GROUND BUS. EXTEND BUS THROUGH
ENTIRE SECTION TO ALLOW FOR BUS CONNECTION TO FUTURE DISTRIBUTION SECTIONS.
CH1
1600AF
1000AT
100%
CH2
1600AF
1000AT
100%
A1
800AF
800AT
100%
A2 1600A
TIE
4000AF
4000AT
100%
MB2
4000AF
4000AT
100%
CH3
1600AF
1000AT
100%
FUTURE CH4
1600A
B1
800AF
800AT
100%
B2 1600A
N.O.
PROVIDE (8) 17"x22" ENGRAVED PLACARDS FOR SWITCHGEAR BREAKER INSTRUCTIONS. CONTRACTOR SHALL PROVIDE ITEMS AS FOLLOWS:
1.
2.
3.
4.
ENGRAVED 1/4" MICARTA PLACARD MOUNTED ON EQUIPMENT WITH SCREWS.
ASSUME 1000 CHARACTERS/SYMBOLS PER INSTRUCTIONAL PLACARD. CHARACTER/SYMBOLS SHALL BE ASSUMED TO BE OF VARIOUS
HEIGHTS AND STYLES.
VERIFY EXACT SIZE, TEXT STYLE, COLOR AND MOUNTING LOCATION OF INSTRUCTIONAL PLACARDS WITH VAMC COTR PRIOR TO
ORDERING.
INSTRUCTION PLACARD WORDING SHALL BE PROVIDED BY THE VAMC THROUGH THE COMMISSIONING PROCESS. CONTRACTOR SHALL PROVIDE FINAL ENGRAVED PLACARDS WITHIN (4) WEEKS OF RECEIVING FINAL WORDING.
250E 250E250E
600A-15,000V - PRIMARY SWITCH, 25KAIC, 150E-RATED CURRENT LIMITING FUSES (ONE PER INCOMING LINE). MANUAL OPERATION, INDOOR ENCLOSURE, PROVISIONS FOR PADLOCKING FULL
HEIGHT MAIN DOOR WITH INSPECTION WINDOW, DOOR AND SWITCH INTERLOCK. PROVIDE KEY
INTERLOCKING SUCH THAT ONLY (1) PRIMARY FEEDER CAN BE CLOSED AT A TIME. BASIS OF DESIGN DIMENSIONS: 14.75"L x 37.25"D x 90"H
1.
2.
DIMENSIONS ARE PROVIDED FOR REFERENCE. SQUARE D PZ4 SWITCHGEAR BY SCHEIDER ELECTRIC USED AS A BASIS OF DESIGN.
WHERE SUBMITTED DIMENSIONS DIFFER FROM THE BASIS OF DESIGN, CONTRACTOR SHALL SUBMIT A NEW EQUIPMENT LAYOUT FOR REVIEW AND APPROVAL. LAYOUT SHALL BE SUBMITTED ALONG WITH EQUIPMENT SHOP DRAWINGS. EQUIPMENT SHALL NOT BE PURCHASED UNTIL LAYOUT IS APPROVED. EQUIPMENT MAY BE REJECTED IF PHYSICAL DIMENSIONS EXCEED BASIS-OF-DESIGN.
NEMA 1, SELF SUPPORTING STRUCTURE - FRONT AND REAR ACCESS SWITCHBOARD. BUILT TO UL
1558 STANDARDS. PROVIDE FRONT HINGED DOORS FOR POWER BREAKERS AND METERING
COMPARTMENTS. REAR COMPARTMENTS SHALL HAVE BOLTED COVERS. PROVIDE UNIT BREAKER
LIFT FOR DRAW-OUT BREAKERS. BASIS OF DESIGN DIMENSIONS: 92"H x 75.25"D, MAIN/TIE SECTIONS:
36"W, DISTRIBUTION SECTIONS: 22"W.
2000kVA, 13,200V DELTA PRIMARY, 480/277V-3Ø-4W WYE SECONDARY, DRY-TYPE, FORCED-AIR COOLED (133% OVERCURRENT RATING), 80°C RISE RATING, 95KV BIL, 5.75% MIN IMPEDANCE. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. BASIS OF DESIGN DIMENSIONS: 108"L x 66"D x
108"H, 13,400LB.
DRAW-OUT, LOW-VOLTAGE, 4000A-3P, POWER CIRCUIT BREAKER WITH DIGITAL, SOLID STATE
TRIP UNIT (100% RATED). TRIP UNIT SHALL HAVE FIELD INSTALLABLE, FRONT-MOUNTED RATING
PLUG AND ADJUSTABLE LONG-TIME, SHORT-TIME, INSTANTANEOUS, AND GROUND FAULT
SETTINGS. PROVIDE KEY INTERLOCKING DEVICE AND CONNECT PER ONE-LINE DIAGRAM.
DRAW-OUT, LOW-VOLTAGE, POWER CIRCUIT BREAKER WITH DIGITAL, SOLID STATE TRIP UNIT (100% RATED). FRAME AND TRIP UNIT SIZE AS INDICATED. TRIP UNIT SHALL HAVE FIELD INSTALLABLE, FRONT-MOUNTED RATING PLUG AND ADJUSTABLE LONG-TIME, SHORT-TIME, INSTANTANEOUS, AND
GROUND FAULT SETTINGS.
FURNISH AND INSTALL NEW CT'S FOR EACH BREAKER/PROVISION AND A COMMON SET OF PT'S TO
SUPPLY A COMMON LINE-SIDE VOLTAGE INPUT TO ALL METERS. PROVIDE NEW EPM'S FOR EACH BREAKER. MATCH EXISTING FACILITY TYPE(SCHNEIDER POWERLOGIC - PM8244) . CONNECT METERS
TO EXISTING FACILITIES MANAGEMENT SYSTEM.
PROVIDE INTEGRAL TRANSIENT VOLTAGE SURGE SUPPRESSION FOR 480/277V DISTRIBUTION. REFER
TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
ALL FEEDER TERMINATIONS SHALL BE MADE WITH 2-HOLE, LONG BARRELL COMPRESSION LUGS.
REFER TO POWER DISTRIBUTION ONE-LINE DIAGRAM FOR FEEDER SIZES.
PROVIDE GROUND FAULT RELAY SYSTEM FOR MAIN-TIE-MAIN BREAKER SCHEME (SIMILAR TO
MAGNUM DS MOD - RESIDUAL GROUND FAULT WITH ZONE INTERLOCKING). PROVIDE AUXILIARY
CONTACTS ON MAIN AND TIE BREAKERS. PROVIDE CT ON NEUTRAL OF ALL BREAKERS FOR NEUTRAL
CURRENT SENSING.
PROVIDE (2) FORM C AUX. CONTACTS FOR TIE BREAKER. PROVIDE 3/4" CONDUIT - 6#14 FROM TIE
BREAKER TO A LOCAL TEMPERATURE CONTROL PANEL TO MONITOR POSITION. PROVIDE KEY
INTERLOCKING DEVICE AND CONNECT PER ONE-LINE DIAGRAM.
ENGRAVED PHENOLIC NAMEPLATES FOR ALL BREAKERS, METERS, ETC. PROVIDE PHENOLIC MIMIC BUS FOR ALL SWITCHGEAR BUS, BREAKERS, METERING, ETC. VERIFY EXACT SIZE, TEXT STYLE, COLOR AND MOUNTING LOCATION WITH VAMC COR PRIOR TO ORDERING.
PROVIDE MANUAL KEY INTERLOCKING DEVICE BETWEEN (2) MAIN BREAKERS AND (1) TIE BREAKER.
SUBMIT MECHANICAL INTERLOCKING SCHEME WITH SHOP DRAWINGS FOR APPROVAL.
4000A, 480/277V-3∅-4W, SILVER-PLATED COPPER AT 1000AMPS PER SQUARE INCH - MIN. 65,000A RMS SYMMETRICAL SHORT CIRCUIT BRACING - FULL LENGTH GROUND BUS. EXTEND BUS THROUGH
ENTIRE SECTION TO ALLOW FOR BUS CONNECTION TO FUTURE DISTRIBUTION SECTIONS.
600A-15,000V - PRIMARY SWITCH, 25KAIC, 150E-RATED CURRENT LIMITING FUSES (ONE PER INCOMING LINE). MANUAL OPERATION, INDOOR ENCLOSURE, PROVISIONS FOR PADLOCKING FULL
HEIGHT MAIN DOOR WITH INSPECTION WINDOW, DOOR AND SWITCH INTERLOCK. PROVIDE KEY
INTERLOCKING SUCH THAT ONLY (1) PRIMARY FEEDER CAN BE CLOSED AT A TIME. BASIS OF DESIGN DIMENSIONS: 14.75"L x 37.25"D x 90"H
NEMA 1, SELF SUPPORTING STRUCTURE - FRONT AND REAR ACCESS SWITCHBOARD. BUILT TO UL
1558 STANDARDS. PROVIDE FRONT HINGED DOORS FOR POWER BREAKERS AND METERING
COMPARTMENTS. REAR COMPARTMENTS SHALL HAVE BOLTED COVERS. PROVIDE UNIT BREAKER
LIFT FOR DRAW-OUT BREAKERS. BASIS OF DESIGN DIMENSIONS: 92"H x 75.25"D, MAIN/TIE SECTIONS:
36"W, DISTRIBUTION SECTIONS: 22"W.
2000kVA, 13,200V DELTA PRIMARY, 480/277V-3Ø-4W WYE SECONDARY, DRY-TYPE, FORCED-AIR COOLED (133% OVERCURRENT RATING), 80°C RISE RATING, 95KV BIL, 5.75% MIN IMPEDANCE. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. BASIS OF DESIGN DIMENSIONS: 108"L x 66"D x
108"H, 13,400LB.
DRAW-OUT, LOW-VOLTAGE, 4000A-3P, POWER CIRCUIT BREAKER WITH DIGITAL, SOLID STATE
TRIP UNIT (100% RATED). TRIP UNIT SHALL HAVE FIELD INSTALLABLE, FRONT-MOUNTED RATING
PLUG AND ADJUSTABLE LONG-TIME, SHORT-TIME, INSTANTANEOUS, AND GROUND FAULT
SETTINGS. PROVIDE KEY INTERLOCKING DEVICE AND CONNECT PER ONE-LINE DIAGRAM.
DRAW-OUT, LOW-VOLTAGE, POWER CIRCUIT BREAKER WITH DIGITAL, SOLID STATE TRIP UNIT (100% RATED). FRAME AND TRIP UNIT SIZE AS INDICATED. TRIP UNIT SHALL HAVE FIELD INSTALLABLE, FRONT-MOUNTED RATING PLUG AND ADJUSTABLE LONG-TIME, SHORT-TIME, INSTANTANEOUS, AND
GROUND FAULT SETTINGS.
FURNISH AND INSTALL NEW CT'S FOR EACH BREAKER/PROVISION AND A COMMON SET OF PT'S TO
SUPPLY A COMMON LINE-SIDE VOLTAGE INPUT TO ALL METERS. PROVIDE NEW EPM'S FOR EACH BREAKER. MATCH EXISTING FACILITY TYPE(SCHNEIDER POWERLOGIC - PM8244) . CONNECT METERS
TO EXISTING FACILITIES MANAGEMENT SYSTEM.
PROVIDE INTEGRAL TRANSIENT VOLTAGE SURGE SUPPRESSION FOR 480/277V DISTRIBUTION. REFER
TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
ALL FEEDER TERMINATIONS SHALL BE MADE WITH 2-HOLE, LONG BARRELL COMPRESSION LUGS.
REFER TO POWER DISTRIBUTION ONE-LINE DIAGRAM FOR FEEDER SIZES.
PROVIDE GROUND FAULT RELAY SYSTEM FOR MAIN-TIE-MAIN BREAKER SCHEME (SIMILAR TO
MAGNUM DS MOD - RESIDUAL GROUND FAULT WITH ZONE INTERLOCKING). PROVIDE AUXILIARY
CONTACTS ON MAIN AND TIE BREAKERS. PROVIDE CT ON NEUTRAL OF ALL BREAKERS FOR NEUTRAL
CURRENT SENSING.
ENGRAVED PHENOLIC NAMEPLATES FOR ALL BREAKERS, METERS, ETC. PROVIDE PHENOLIC MIMIC BUS FOR ALL SWITCHGEAR BUS, BREAKERS, METERING, ETC. VERIFY EXACT SIZE, TEXT STYLE, COLOR AND MOUNTING LOCATION WITH VAMC COR PRIOR TO ORDERING.
PROVIDE MANUAL KEY INTERLOCKING DEVICE BETWEEN (2) MAIN BREAKERS AND (1) TIE BREAKER.
SUBMIT MECHANICAL INTERLOCKING SCHEME WITH SHOP DRAWINGS FOR APPROVAL.
33 3 3
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/8 /2
:1
:3
A
M
E-506
SUBSTATION DETAIL AND GENERAL NOTES CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00
NOT TO SCALE
SUBSTATION DETAIL AND GENERAL NOTES 1
Revisions: Date:
FINAL BID & CONSTRUCTION 11/24/2021
FINAL BID & CONSTRUCTION (REVISED) 05/06/2022
| E-201 - PARTIAL SECOND FLOOR ELECTRICAL EQUIPMENT AND RACEWAY LAYOUT PLAN - SOUTH.pdf |
| 20045 FFH CF R2020_Christopher.P.Campbell |
| E-201 - PARTIAL SECOND FLOOR ELECTRICAL EQUIPMENT AND RACEWAY LAYOUT PLAN - SOUTH |
| E-604 - ELECTRICAL GROUNDING SYSTEM DIAGRAM.pdf |
| 20045 FFH CF R2020_Christopher.P.Campbell |
| E-604 - ELECTRICAL GROUNDING SYSTEM DIAGRAM |
| E-602 - BOILER PLANT CHILLER PLANT ONE-LINE DIAGRAM.pdf |
| 20045 FFH CF R2020_Christopher.P.Campbell |
| E-602 - BOILER PLANT / CHILLER PLANT ONE-LINE DIAGRAM |
| E-506 - SUBSTATION DETAIL AND GENERAL NOTES.pdf |
| 20045 FFH CF R2020_Christopher.P.Campbell |
| E-506 - SUBSTATION DETAIL AND GENERAL NOTES |
File details come from the government source that posted it. Updated .