This solicitation is for the construction of a chiller plant at the Chalmers P. Wylie VAACC in Columbus, Ohio. The solicitation is a set-aside for service-disabled veteran-owned small businesses. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 is the issuing agency. The work includes installing electrical conduits, pull boxes, and substations to support new electrical equipment for the chiller plant. Bids are due by July 27, 2023. The awarded contractor will be responsible for submitting coordination drawings for conduit routing with equipment submittals.

The related federal contract opportunity document provides additional details on the electrical scope of work. It includes specifications for low-voltage power conductors and cables, grounding diagrams, one-line diagrams, and substation details. Equipment required includes switchgear, transformers, generators, panelboards, and metering devices. The contractor must coordinate work with the existing electrical infrastructure and utility provider.

View the file

Other files

File Type Posted
36C25024C0013 SAM Award Notice 1.0.pdf PDF
36C25023B0049 - Amendment 3.docx DOCX document
36C25023B0049 - Amendment 1.docx DOCX document
Single Source Justification MPT to SAT - Wattstopper - Pricing Removed - Signed.pdf PDF
VHA Directive 1192.01, Seasonal Influenza Prevention Program for VHA Health Care Personnel.pdf PDF
18912 Columbus VAMC Chiller BC Sole Source Redacted.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-8.pdf PDF
VAAR 852.219-75 - To Be Submitted With Bid.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-5.pdf PDF
VAACC Health Requirements - Bid Ready 2023.pdf PDF
36C25023B0049 - Ready.docx DOCX document
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-4.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-1.pdf PDF
Single Source Justification MPT to SAT - Simplex - 2.0 Price Removed - Signed.pdf PDF
18912 Columbus VA Chiller Plant Revision Final B_C Re-Revised - PM Vol 1 of 2.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-2.pdf PDF
Franklin DB - Current as of 07.13.2023.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-9.pdf PDF
Single Source Justification MPT to SAT - Software House - Pricing Removed - Signed.pdf PDF
Single Source Justification MPT to SAT - Russ Electric Price Removed - Signed.pdf PDF
18912 Columbus DVAMC Chiller FB_C PM Volume 2 of 2.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-6.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-7.pdf PDF
Hca Signed NCO 10 Caterpillar - Sole Source - Pricing Removed.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-10.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-3.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5. PROJECT NUMBER (if applicable)

CODE 7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER 3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO. 1. CONTRACT ID CODE

FACILITY CODE CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office. is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER 16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30 PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243

(Type or print) (Type or print)

(Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code)

(If other than Item 6)

(Specify type of modification and authority)

(such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer)

1 15

0002 757-15-102

36C250

Department of Veterans Affairs VA Healthcare System Network Contracting Office (NCO) 10 2780 Airport Dr - Suite 340 Columbus OH 43219

36C250

Department of Veterans Affairs VA Healthcare System Network Contracting Office (NCO) 10 2780 Airport Dr - Suite 340 Columbus OH 43219

To all Offerors/Bidders 36C25023B0049

07-27-2023 X

X X

X 01

The purpose of this solicitation amendment is to provide technical documents to support the information provided in amendment 0001. Please see the continuation pages of this amendment for the technical documents.

All other terms & conditions remain unchanged and in full effect.

Brian S. Kish Contracting Officer

CONTINUATION PAGE

Construct Chiller Plant

Chalmers P. Wylie VAACC

Columbus, OH 43219

Project # 757-15-102

SDVOSB Set-Aside

See attached document: SECTION 26 05 19 - LOW-VOLTAGE ELECTRICAL POWER

CONDUCTORS AND CABLES.

See attached document: E-201 - PARTIAL SECOND FLOOR ELECTRICAL EQUIPMENT

AND RACEWAY LAYOUT PLAN - SOUTH.

See attached document: E-604 - ELECTRICAL GROUNDING SYSTEM DIAGRAM.

See attached document: E-602 - BOILER PLANT CHILLER PLANT ONE-LINE DIAGRAM.

See attached document: E-506 - SUBSTATION DETAIL AND GENERAL NOTES.

01-01-17

26 05 19 - 1

SECTION 26 05 19

LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES

PART 1 - GENERAL

1.1 DESCRIPTION

A. This section specifies the furnishing, installation, connection, and testing of the electrical conductors and cables for use in electrical systems rated 600 V and below, indicated as cable(s), conductor(s), wire, or wiring in this section.

1.2 RELATED WORK

A. Section 07 84 00, FIRESTOPPING: Sealing around penetrations to maintain the integrity of fire-resistant rated construction.

B. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS:

Requirements that apply to all sections of Division 26.

C. Section 26 05 26, GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS:

Requirements for personnel safety and to provide a low impedance path for possible ground fault currents.

D. Section 26 05 33, RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS: Conduits for conductors and cables.

E. Section 26 05 41, UNDERGROUND ELECTRICAL CONSTRUCTION: Installation of conductors and cables in manholes and ducts.

1.3 QUALITY ASSURANCE

A. Quality Assurance shall be in accordance with Paragraph, QUALIFICATIONS

(PRODUCTS AND SERVICES) in Section 26 05 11, REQUIREMENTS FOR

ELECTRICAL INSTALLATIONS.

1.4 SUBMITTALS

A. Submit in accordance with Paragraph, SUBMITTALS in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, and the following requirements:

1. Shop Drawings:

a. Submit sufficient information to demonstrate compliance with drawings and specifications.

b. Submit the following data for approval:

26 05 19 - 2

1) Electrical ratings and insulation type for each conductor and cable.

2) Splicing materials and pulling lubricant.

2. Certifications: Two weeks prior to final inspection, submit the following.

a. Certification by the manufacturer that the conductors and cables conform to the requirements of the drawings and specifications.

b. Certification by the Contractor that the conductors and cables have been properly installed, adjusted, and tested.

1.5 APPLICABLE PUBLICATIONS

A. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. Publications are reference in the text by designation only.

B. American Society of Testing Material (ASTM):

D2301-10................Standard Specification for Vinyl Chloride

Plastic Pressure-Sensitive Electrical

Insulating Tape

D2304-10................Test Method for Thermal Endurance of Rigid

Electrical Insulating Materials

D3005-10................Low-Temperature Resistant Vinyl Chloride

Plastic Pressure-Sensitive Electrical

Insulating Tape

C. National Electrical Manufacturers Association (NEMA):

WC 70-09................Power Cables Rated 2000 Volts or Less for the

Distribution of Electrical Energy

D. National Fire Protection Association (NFPA):

70-17...................National Electrical Code (NEC)

E. Underwriters Laboratories, Inc. (UL):

44-14...................Thermoset-Insulated Wires and Cables

83-14...................Thermoplastic-Insulated Wires and Cables

467-13..................Grounding and Bonding Equipment

486A-48.................6B-13 Wire Connectors

486C-13.................Splicing Wire Connectors

486D-15.................Sealed Wire Connector Systems

26 05 19 - 3

486E-15.................Equipment Wiring Terminals for Use with

Aluminum and/or Copper Conductors

493-07..................Thermoplastic-Insulated Underground Feeder and

Branch Circuit Cables

514B-12.................Conduit, Tubing, and Cable Fittings

PART 2 - PRODUCTS

2.1 CONDUCTORS AND CABLES

A. Conductors and cables shall be in accordance with ASTM, NEMA, NFPA, UL, as specified herein, and as shown on the drawings.

B. All conductors shall be copper.

C. Single Conductor and Cable:

1. No. 12 AWG: Minimum size, except where smaller sizes are specified herein or shown on the drawings.

2. All conductors #10AWG and small shall be solid copper. All conductors larger than #10AWG shall be stranded copper.

3. Insulation: THHN-THWN and XHHW-2. XHHW-2 shall be used for isolated power systems.

D. Color Code:

1. No. 10 AWG and smaller: Solid color insulation or coating.

2. No. 8 AWG and larger: Color-coded using one of the following:

a. Solid color insulation or solid color coating.

b. Stripes, bands, or hash marks of color specified.

c. Color using 19 mm (0.75 inches) wide tape.

3. For modifications and additions to existing wiring systems, color coding shall conform to the existing wiring system.

4. Conductors shall be color-coded as follows:

208/120 V Phase 480/277 V

Black A Brown

Red B Orange

Blue C Yellow

White Neutral Gray *

26 05 19 - 4

* or white with colored (other than green) tracer.

5. Lighting circuit "switch legs", and 3-way and 4-way switch

"traveling wires," shall have color coding that is unique and distinct (e.g., pink and purple) from the color coding indicated above. The unique color codes shall be solid and in accordance with the NEC. Coordinate color coding in the field with the COR.

6. Color code for isolated power system wiring shall be in accordance with the NEC.

2.2 SPLICES

A. Splices shall be in accordance with NEC and UL.

B. Above Ground Splices for No. 10 AWG and Smaller:

1. Solderless, screw-on, reusable pressure cable type, with integral insulation, approved for copper and aluminum conductors.

2. The integral insulator shall have a skirt to completely cover the stripped conductors.

3. The number, size, and combination of conductors used with the connector, as listed on the manufacturer's packaging, shall be strictly followed.

C. Above Ground Splices for No. 8 AWG to No. 4/0 AWG:

1. Compression, hex screw, or bolt clamp-type of high conductivity and corrosion-resistant material, listed for use with copper and aluminum conductors.

2. Insulate with materials approved for the particular use, location, voltage, and temperature. Insulation level shall be not less than the insulation level of the conductors being joined.

3. Splice and insulation shall be product of the same manufacturer.

4. All bolts, nuts, and washers used with splices shall be zinc-plated steel.

D. Above Ground Splices for 250 kcmil and Larger:

1. Long barrel "butt-splice" or "sleeve" type compression connectors, with minimum of two compression indents per wire, listed for use with copper and aluminum conductors.

26 05 19 - 5

2. Insulate with materials approved for the particular use, location, voltage, and temperature. Insulation level shall be not less than the insulation level of the conductors being joined.

3. Splice and insulation shall be product of the same manufacturer.

E. Underground Splices for No. 10 AWG and Smaller:

1. Solderless, screw-on, reusable pressure cable type, with integral insulation. Listed for wet locations, and approved for copper and aluminum conductors.

2. The integral insulator shall have a skirt to completely cover the stripped conductors.

3. The number, size, and combination of conductors used with the connector, as listed on the manufacturer's packaging, shall be strictly followed.

F. Underground Splices for No. 8 AWG and Larger:

1. Mechanical type, of high conductivity and corrosion-resistant material. Listed for wet locations, and approved for copper and aluminum conductors.

2. Insulate with materials approved for the particular use, location, voltage, and temperature. Insulation level shall be not less than the insulation level of the conductors being joined.

3. Splice and insulation shall be product of the same manufacturer.

G. Plastic electrical insulating tape: Per ASTM D2304, flame-retardant, cold and weather resistant.

2.3 CONNECTORS AND TERMINATIONS

A. Mechanical type of high conductivity and corrosion-resistant material, listed for use with copper and aluminum conductors.

B. Long barrel compression type of high conductivity and corrosion-resistant material, with minimum of two compression indents per wire, listed for use with copper and aluminum conductors.

C. All bolts, nuts, and washers used to connect connections and terminations to bus bars or other termination points shall be zinc-plated steel.

26 05 19 - 6

2.4 CONTROL WIRING

A. Unless otherwise specified elsewhere in these specifications, control wiring shall be as specified herein, except that the minimum size shall be not less than No. 14 AWG.

B. Control wiring shall be sized such that the voltage drop under in-rush conditions does not adversely affect operation of the controls.

2.5 WIRE LUBRICATING COMPOUND

A. Lubricating compound shall be suitable for the wire insulation and conduit, and shall not harden or become adhesive.

B. Shall not be used on conductors for isolated power systems.

PART 3 - EXECUTION

3.1 GENERAL

A. Installation shall be in accordance with the NEC, as shown on the drawings, and manufacturer's instructions.

B. Install all conductors in raceway systems.

C. Splice conductors only in outlet boxes, junction boxes, pullboxes, manholes, or handholes.

D. Conductors of different systems (e.g., 120 V and 277 V) shall not be installed in the same raceway.

E. Install cable supports for all vertical feeders in accordance with the

NEC. Provide split wedge type which firmly clamps each individual cable and tightens due to cable weight.

F. In panelboards, cabinets, wireways, switches, enclosures, and equipment assemblies, neatly form, train, and tie the conductors with non-metallic ties.

G. For connections to motors, transformers, and vibrating equipment, stranded conductors shall be used only from the last fixed point of connection to the motors, transformers, or vibrating equipment.

H. Use expanding foam or non-hardening duct-seal to seal conduits entering a building, after installation of conductors.

I. Conductor and Cable Pulling:

26 05 19 - 7

1. Provide installation equipment that will prevent the cutting or abrasion of insulation during pulling. Use lubricants approved for the cable.

2. Use nonmetallic pull ropes.

3. Attach pull ropes by means of either woven basket grips or pulling eyes attached directly to the conductors.

4. All conductors in a single conduit shall be pulled simultaneously.

5. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.

J. No more than three branch circuits shall be installed in any one conduit.

K. When stripping stranded conductors, use a tool that does not damage the conductor or remove conductor strands.

3.2 SPLICE AND TERMINATION INSTALLATION

A. Splices and terminations shall be mechanically and electrically secure, and tightened to manufacturer's published torque values using a torque screwdriver or wrench.

B. Where the Government determines that unsatisfactory splices or terminations have been installed, replace the splices or terminations at no additional cost to the Government.

3.3 CONDUCTOR IDENTIFICATION

A. When using colored tape to identify phase, neutral, and ground conductors larger than No. 8 AWG, apply tape in half-overlapping turns for a minimum of 75 mm (3 inches) from terminal points, and in junction boxes, and pullboxes. Apply the last two laps of tape with no tension to prevent possible unwinding. Where cable markings are covered by tape, apply tags to cable, stating size and insulation type.

3.4 FEEDER CONDUCTOR IDENTIFICATION

A. In each interior pullbox and each underground handhole, install brass tags on all feeder conductors to clearly designate their circuit identification and voltage. The tags shall be the embossed type, 40 mm

(1-1/2 inches) in diameter and 40 mils thick. Attach tags with plastic ties.

26 05 19 - 8

3.5 EXISTING CONDUCTORS

A. Unless specifically indicated on the plans, existing conductors shall not be reused.

3.6 CONTROL WIRING INSTALLATION

A. Unless otherwise specified in other sections, install control wiring and connect to equipment to perform the required functions as specified or as shown on the drawings.

B. Install a separate power supply circuit for each system, except where otherwise shown on the drawings.

3.7 CONTROL WIRING IDENTIFICATION

A. Install a permanent wire marker on each wire at each termination.

B. Identifying numbers and letters on the wire markers shall correspond to those on the wiring diagrams used for installing the systems.

C. Wire markers shall retain their markings after cleaning.

D. In each handhole, install embossed brass tags to identify the system served and function.

3.8 ACCEPTANCE CHECKS AND TESTS

A. Perform in accordance with the manufacturer's recommendations. In addition, include the following:

1. Visual Inspection and Tests: Inspect physical condition.

2. Electrical tests:

a. After installation but before connection to utilization devices, such as fixtures, motors, or appliances, test conductors phase-to-phase and phase-to-ground resistance with an insulation resistance tester. In addition, test existing re-used conductors.

b. Applied voltage shall be 500 V DC for 300 V rated cable, and 1000

V DC for 600 V rated cable. Apply test for one minute or until reading is constant for 15 seconds, whichever is longer. Minimum insulation resistance values shall not be less than 25 megohms for 300 V rated cable and 100 megohms for 600 V rated cable.

c. Perform phase rotation test on all three-phase circuits.

26 05 19 - 9

---END---

UP

B.8 B.8

C.3 C.3

D.4 D.4

E.3 E.3

NEW

SS-CP2

NEW

SS-CP1

EXISTING

NPSS-1

EXISTING

GPSS-1

ATS-HLS

X

ATS-HEQ

X

ATS-HCR

X

X

F R

O N

T

F R

O N

T

/4

2000KVA/2660KVA

13.2KV:480/277V

XFMR

W/FORCED AIR

480V

DIST.

NORMAL

PRIMARY

EM.

PRIMARY

MAIN

TIE BUS

SECTION

10' - 4 13/16"

7' - 2"

6' - 3 1/4" 4' - 0"

2000KVA/2660KVA

13.2KV:480/277V

XFMR

W/FORCED AIR

480V

DIST.

NORMAL

PRIMARY

MAIN

TIE

BREAKER

SECTION

7' - 2"

6' - 3 1/4"4' - 0"

4' - 9 1/4" 5' - 6"

/4

M

IN

7' - 0"

7' - 0"

7' - 0"

F R

O N

T

PRIMARY

750KVA

13.2KV:480/277V

XFMR

MAIN

480V

DISTRIBUTION

480V

DISTRIBUTION

4' - 0 9/16" 3' - 9 3/4" 11' - 4 13/16"

5' - 6" 4' - 9 1/4"

X

X

X

X

X

480V

DISTRIBUTION

480V

DISTRIBUTION

480V

DISTRIBUTION

MAIN

2500KVA

13.2KV:480/277V

XFMR

PRIMARY

EM.

PRIMARY

3' - 1 1/4"

21 3 4

0.8 0.8

2.7

BUSBAR

FEEDER

CT-3

CT

CT-4

CT

CT-2

CT

CT-1

CT

EF-1

EF

NORMAL POWER

ELECTRICAL

ROOM

CORRIDOR

MECH. ROOM

STAIR A

ESSENTIAL

POWER

ELECTRICAL

ROOM

TYP

TYP

3"C3"C 4"C

4"C 4"C 3"C 3"C

3"C 3"C 3"C 3"C

4"C4"C4"C

PAN HEATERS

PAN HEATERS

CT-1

CT-2

CT-3

CT-4

E-202

WALKING CLEARANCE WALKING CLEARANCE

WALKING CLEARANCE

REFER TO E-202

3"C 3"C 3"C

S

59459

M.P. LONG

R

E

S

O F

I

R

G E

NO

I

S

P

E

N

E

D

ERT

L EA

E I N

G

R

T

S

TEA

H

F OO

IO

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

20045

C R e v it L o c a l F ile s \2

F

F H

C F

R

C h ri s to p h e r.

P

.C a m p b e ll.

rv t

/8 /2

:5

:0

A

M

E-201

PARTIAL SECOND FLOOR ELECTRICAL

EQUIPMENT AND RACEWAY LAYOUT PLAN -

SOUTH

CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 CPC LV

BID & CONSTRUCTION

18902.00 3

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

ENLARGED SECOND FLOOR ELECTRICAL

EQUIPMENT AND RACEWAY LAYOUT PLAN 1N

# CODED NOTES

PROVIDE 4'(L) x 4'(H) x 1'-6"(D) NEMA 4X PULLBOX ON EXISTING WALL WITH GASKETED COVER FOR ELECTRICAL CONDUITS. REFER TO PLANS FOR CONDUIT DIMENSIONS. VERIFY MOUNTING HEIGHT AND EXACT CONDUIT ROUTE IN FIELD PRIOR TO INSTALLATION.

EXISTING LIGHTING FIXTURES IN THE ESSENTIAL POWER ELECTRICAL ROOM AND NORMAL POWER ELECTRICAL ROOM THAT INTERFERE WITH THE NEW ELECTRICAL SUBSTATIONS AND CONDUIT ROUTES SHALL BE REMOVED AND RELOCATED TO LIGHT EXISTING AND NEW PATHS WITHIN THE ROOM. PROVIDE CONDUIT AND WIRES EXTENSIONS VIA 3/4"C - 3#12 AND 1#12EG.

PROVIDE 4'-8"(L) x 4'(H) x 1-6"(D) NEMA 4X PULLBOX ON EXISTING WALL WITH GASKETED COVER FOR ELECTRICAL CONDUITS. REFER TO PLANS FOR CONDUIT DIMENSIONS. VERIFY MOUNTING HEIGHT AND EXACT CONDUIT ROUTE IN FIELD PRIOR TO INSTALLATION.

PROVIDE 2'(L) x 2'(H) x 1'-6"(D) NEMA 4X PULLBOX ON EXISTING WALL WITH GASKETED COVER FOR ELECTRICAL CONDUITS. REFER TO PLANS FOR CONDUIT DIMENSIONS. VERIFY MOUNTING HEIGHT AND EXACT CONDUIT ROUTE IN FIELD PRIOR TO INSTALLATION.

ROUTE CONDUITS DOWN THROUGH ROOF INTO CHILLER PLANT CEILING SPACE. PROVIDE PRE-FABRICATED ROOF PENETRATION BELOW

PULL-BOX.

CONDUIT ROUTING INDICATED FOR REFERENCE ONLY. CONTRACTOR IS RESPONSIBLE FOR SUBMITTING CONDUIT ROUTING COORDINATION DRAWINGS WITH ELECTRICAL EQUIPMENT SUBMITTAL FOR APPROVAL. ROUTING DRAWINGS SHALL INCLUDE FIELD VERIFIED ROUTING, BENDS, PULLBOXES, CONDUIT BODIES, PENETRATIONS, ETC. CONTRACTOR SHALL INCLUDE EXISTING CONDITIONS WHERE NECESSARY TO CONVEY ROUTING INFORMATION. MAINTAIN NEC REQUIRED ACCESSIBILITY TO ALL EXISTING PULLBOXES, JUNCTION BOXES, ETC. TO REMAIN. ELECTRICAL

EQUIPMENT SUBMITTAL WILL NOT BE APPROVED WITHOUT CONDUIT ROUTING DRAWINGS.

CONDUIT ROUTING GENERAL NOTE

SECOND FLOOR CONDUIT IN

EXISTING BUILDING

CONDUIT TIGHT TO BOTTOM OF

STRUCTURE IN NEW CHILLER

PLANT

CONDUIT LEGEND

Revisions: Date:

FINAL BID & CONSTRUCTION 11/24/2021

FINAL BID & CONSTRUCTION (REVISED) 05/06/2022

AMEDMENT 1 08/05/2022

GEC - GROUNDING ELECTRODE CONDUCTOR (NEC ARTICLE 250, TABLE 250.66)

MBJ - MAIN BONDING JUMPER (NEC ARTICLE 250.28, TABLE 250.102(C)(1))

SSBJ - SUPPLY SIDE BONDING JUMPER (NEC ARTICLE 250.30 (B)(2), TABLE 250.102(C)(1))

SBJ - SYSTEM BONDING JUMPER (NEC ARTICLE 250.30(1), TABLE 250.102(C)(1))

EG - EQUIPMENT GROUNDING CONDUCTOR (NEC ARTICLE 250, TABLE 250.122)

N - GROUNDED CIRCUIT CONDUCTOR (NEUTRAL)

GECT - GROUNDING ELECTRODE CONDUCTOR TAP (NEC 250.30(A)(6), TABLE 250.66)

NGR - NEUTRAL GROUNDING RESISTOR

ABBREVIATIONS/CODE REFERENCES

EXISTING

UTILITY

TRANSFORMER

SERVICE

PRIMARY

(BY UTILITY)

G

N

G

X

X

EXISTING

NORMAL

PARALLELING

SWITCHGEAR

GX

G

EXISTING

EMERGENCY

PARALLELING

SWITCHGEAR

G G

D

EG

X XR

EXISTING

TYPICAL UNIT

SUBSTATION

TYPICAL

480/277V PANEL BOARD

N

GG

N

SBJ

ELECTRICAL ROOM

EQUIPMENT GROUND BAR

EXISTING

TELECOMMUNICATIONS ROOM

EQUIPMENT GROUND BAR

EXISTING

X

X X XX X

X

X

X

X

X

TO EXISTING

GROUNDING ELECTRODE SYSTEM

(STRUCTURAL STEEL FRAMING, GAS

AND METAL WATER PIPING, WATER

SERVICE, GROUND RING, ETC.)

NEW BUILDING STEEL SHALL BE

BONDED TO EXISTING BUILDING

STEEL. REFER TO INSET DETAIL

BELOW.

EXISTING

TYPICAL UNIT

SUBSTATION

TYPICAL

480/277V PANEL BOARD

N

GG

N

SBJ X

X

X

X X

G

XR

1750KW, 480V-3PH-3W

EMERGENCY GENERATOR

N

XR

480V:13.2KV TRANSFORMER

G G

SSBJ

XR

XR

XR

XR

XR

G

SBJ

C

B

GEC

NON-METALLIC

PROTECTIVE SLEEVE

CONNECTION LISTED

FOR PURPOSE

NEW 2000KW, 13.2KV-3PH-3W

EMERGENCY GENERATOR

N

CONCRETE ENCASED ELECTRODE

(GENERATOR SUPPORT PAD)

A

CONCRETE FOUNDATION

(MIN OF 20FT) IN DIRECT

CONTACT WITH EARTH.

NEUTRAL GROUNDING

RESISTOR

MBJ

CONSTRUCT GENERATOR SUPPORT PAD AS A CONCRETE ENCASED ELECTRODE. GENERATOR PAD SHALL

MEET ALL THE REQUIREMENTS OF NEC 250.52(A)(3).

PROVIDE NEW GEC AND CONNECT COMPLETE TO CONCRETE ENCASED ELECTRODE THROUGH NEW NGR.

REFER TO "PARTIAL SITE ELECTRICAL PLAN" FOR NGR SPECIFICATION INFORMATION.

PROVIDE SYSTEM BONDING JUMPER (SIZED PER NEC, REFER TO ABOVE FOR REFERENCES)

PROVIDE EG FROM NEW GENERATOR GROUNDING CONNECTION POINT TO EMERGENCY PARALLELING SWITCHGEAR GROUNDING POINT. COORDINATE EXACT TERMINATION LOCATION IN FIELD AND WITH

GENERATOR MANUFACTURER. EG SHALL BE SIZED AS INDICATED ON ONE-LINE DIAGRAM.

GROUNDING ELECTRODE CONDUCTOR [GEC] (NEC ARTICLE 250, TABLE 250.66)

CODED NOTES

A

B

C

D

XX

NOT TO SCALE

G

NON-METALLIC

PROTECTIVE SLEEVE

CONNECTION LISTED

FOR PURPOSE

EXISTING 2000KW, 13.2KV-3PH-3W

EMERGENCY GENERATOR

N

CONCRETE ENCASED ELECTRODE

(GENERATOR SUPPORT PAD)

CONCRETE FOUNDATION

(MIN OF 20FT) IN DIRECT

CONTACT WITH EARTH.

NEUTRAL GROUNDING

RESISTOR

X XR

BOND STEEL

ACROSS BUILDING

EXPANSION JOINT

EXISTING BUILDING STEEL

EFFECTIVELY GROUNDED

BUILDING STEEL COLUMN

NEW BUILDING STEEL

STEEL BASE PLATE

BASE PLATE NUT AND ANCHOR BOLT

INTO REINFORCED CONCRETE PIER OR

FOOTING. ANCHOR BOLT BONDED TO

CONCRETE REINFORCING.

50% OF NEW COLUMNS

ALONG SEPARATION

CAD WELDED CAD WELDED

E

GEC

E

#4AWG

S

59459

M.P. LONG

R

E

S

O F

I

R

G E

NO

I

S

P

E

N

E

D

ERT

L EA

E I N

G

R

T

S

TEA

H

F OO

IO

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

20045

C R e v it L o c a l F ile s \2

F

F H

C F

R

C h ri s to p h e r.

P

.C a m p b e ll.

rv t

/7 /2

:0

:2

P M

E-604

ELECTRICAL GROUNDING SYSTEM DIAGRAM CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 CPC LV

BID & CONSTRUCTION

18902.00

GROUNDING ELECTRODE SYSTEM DETAIL 1

Revisions: Date:

FINAL BID & CONSTRUCTION 11/24/2021

FINAL BID & CONSTRUCTION (REVISED) 05/06/2022

SEL700G

EXISTING

UNDER

PROJECT

NUMBER:

757-20-205

NEW

1200AF

FUTURE

G

NEW

GENERATOR "GEN #3"

2000kW-13.2kV-3∅-3W

DIESEL

NEW SUBSTATION SS-CP1

4000A, 480/277V, 3Ø, 4W, 65kAIC

K K

NEW SUBSTATION SS-CP2

4000A, 480/277V, 3Ø, 4W, 65kAIC

K

NEW DISTRIBUTION CPDP1

1000A, 480/277V, 3Ø, 4W, 65kAIC

NEW DISTRIBUTION CPDP2

1000A, 480/277V, 3Ø, 4W, 65kAIC

EPM EPM EPM EPM

EPM

EPM EPM EPM EPM

EPM

TVSSTVSS

SEL700G

86868686

SEL700GT

52 52

SEL751ASEL751ASEL751AASEL751AA

SEL751AB

UTILITY #1

1200AF

1200AF

(N.O.)

BUSSED SPACE

(FUTURE LOOP

SS-1/SS-4)

1200AF

(N.C.)

1200AF

X

CONTROL

SECTION

TIE #2

1200AF

1200AF

GEN1-MCB

XR

GENERATOR "GEN #1"

1750kW-480/277V-3∅-4W

DIESEL

H1T1 2000kVA

480V:13.2kV

EXISTING PARALLELING SWITCHGEAR 'PSG'

1200A, 13.5kV, 3Ø, 3W, 500MVA

4"GRC -

3#2 (MV-105 15kV SHIELDED) & 1#4 EG (600V)

B2

EXISTING SUBSTATION NPSS1 - NORMAL POWER

1200A, 480/277V, 3Ø, 4W, 35kAIC

A

F A

T

750kVA 13,200V:4 80/277V 3Ø-4W

1200AF

1200AT

A

F A

T

400AF

400AT

A

P R

O V

IS

IO

N

A

P R

O V

IS

IO

N

A

P R

O V

IS

IO

N

A

P R

O V

IS

IO

N

225AF

225AT

225AF

225AT

100AF

100AT

SPARE SPARE

225AF

225AT

800AF

800AT

EXISTING SUBSTATION GPSS1 - EMERGENCY POWER

4000A, 480/277V, 3Ø, 4W, 65kAIC

A

F A

T

2500kVA 13,200V:480/277V

3Ø-4W

4000AF

4000AT

A

F A

T

225AF

225AT

A

P R

O V

IS

IO

N

A

P R

O V

IS

IO

N

A

P R

O V

IS

IO

N

225AF

225AT

100AF

100AT

225AF

225AT

SPARE SPARE

800AF

800AT

N E

ATS-HEQ1

800A, 4-POLE

X

N E

ATS-HCR

225A, 4-POLE

X

N E

ATS-HLS

100A, 4-POLE

X

TO EXISTING UTILITY SERVICE

DISCONNECT 13.2kV,3W

TO EXISTING UNIT

SUBSTATION SS-4

TO EXISTING UNIT

SUBSTATION SS-1 (FUTURE LOOP -

CONDUIT ONLY)

480/277V

MLO

225A

H1NA

208/120V

MCB

175A

H1N1

H1TN1

45kVA 480V:208 /120V X

X

X

480/277V

MLO

100A

H1SA

208/120V

MCB

60A

H1S1

H1TS1

15kVA 480V:208/120V X

X

X

480/277V

MLO

225A

H1CA

208/120V

MCB

175A

H1C1

H1TC1

45kVA 480V:208/120V X

X

X

480/277V

MLO

800A

H1EA

208/120V

MCB

175A

H1E1

H1TE1

45kVA 480V:208/120V X

X

X

2500AF

2500AT

TO EXISTING EMERGENCY

SWITCHBOARD 'CISBEMA'

(SUPPLIES MAIN BUILDING ATS)

X

T2

TIE #1

1200AF

EXISTING UNDER

PROJECT NUMBER: 757-20-205

GENERATOR "GEN #2"

2000kW-13.2kV-3∅-3W

DIESEL

NEW

PULLBOX

1200AF

G G

XR

XR

XR

TVSS TVSS

X

X

X X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

L O

O P

A

L O

O P

B

XR X XXXXXXX

X

2'PSG-N'

EXISTING UNDER

PROJECT

NUMBER:

757-20-205

H1TS2

30kVA 480V:208/120V X

208/120V

MCB

100A

H1S2 X

X

NON-FUSED DISC. SW.

X

EXISTING

86 1200AF52

VFD VFDVFD

CHILLER

CH-1

CHILLER

CH-2

PP1 PP2 TP1

125A-3P

LSI

TP2

125A-3P

LSI

CT1

110A-3P

LSI

CT2

110A-3P

LSI

225A-3P

LSI

225A-3P

LSI

100A-3P

VFDVFD VFD

C P

L O

O P

A

C P

L O

O P

B

4000A, 3Ø, 4W BUSDUCT

"G

R C

M V

-1 k V

S H

IE

L D

E D

/0

E G

V

"G

R C

M V

-1 k V

S H

IE

L D

E D

/0

E G

V

4"GRC - 3#350 (MV-105 15kV SHIELDED) & 1#1/0 EG (600V)CP - EMERG.

4"GRC - 3#350 (MV-105 15kV SHIELDED) & 1#1/0 EG (600V)CP - EMERG.

1200AF

1200AT

LSIG

100%

VFD VFD VFD VFD VFDVFD

1200AF

1200AT

LSIG

100%

1200AF

1000AT

LSIG

100%

1200AF

PROV.

1200AF

1200AT

LSIG

100%

1200AF

1200AT

LSIG

100%

1200AF

1000AT

LSIG

100%

1200AF

1000AT

LSIG

100%

2000kVA/2660kVA

(AA/FA)

13,200V:480/277V 3Ø-4W

MAIN

4000AF

4000AT

100% LSIG

N .O

A

S

250E

N .C

A

S

250E

TIE

4000AF

4000AT

LSIG

100%

2000kVA/2660kVA

(AA/FA)

13,200V:480/277V 3Ø-4W

MAIN

4000AF

4000AT

100%

N .O

A

S

250E

N .C

A

S

250E

225 125 125 125 125 100

EXISTING PAD NEW PAD

CHILLER

PLANT WALL

TO EXISTING

GENERATOR

"GEN #2"

SECTION

TO EXISTING

GENERATOR

"GEN #2"

H1TS3

30kVA 480V:208/120V

NEW

(PROVIDED WITH

GENERATOR)

208/120V

MCB

100A

H1S3 (PROVIDED WITH

GENERATOR)

(PROVIDED WITH

GENERATOR)

NON-FUSED DISC. SW.

(PROVIDED WITH

GENERATOR)

(PROVIDED WITH

GENERATOR)

125A-3P

LSI

125A-3P

LSI

110A-3P

LSI

110A-3P

LSI

225A-3P

LSI

225A-3P

LSI

225 225 125 125 125 125

1000N8008001000N800800

X

X

X

800 TON

(784 MCA)

800 TON

(784 MCA)

CHILLER

CH-3

CHILLER

CH-4

SEL751AB SEL700G

SEL700G

PP4 TP4 CT4PP3 TP3 CT3

EF-1

75HP75HP125HP125HP60HP60HP 60HP60HP75HP75HP125HP125HP

200A

RATED

200A

RATED

PAN

HEATERS

CT-1 & 2

100A

RATED

200A

RATED

200A

RATED

VFD VFD

800 TON

(784 MCA)

800 TON

(784MCA)

VFD VFD

SEL751A

1200AF

(N.O.)

X X

'PSG-E'

52 86

SEL751AA

1200AF

EXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTINGEXISTING

1200AF

(N.C.)

SEL751AB

SEL751AA

52 86

NEW

1200AF

(N.O.)

1200AF

(N.O.)

SEL751AB

XR

EMERG. NORMAL EMERG. NORMAL

60A-3P

SSF-1

60A

RATED

30A

RATED

3HP

PAC-

AHU-4

110A-3P

LSI

VFD

100A-3P

PAN

HEATERS

CT-3 & 4

100A

RATED

K K K K

EXISTING H1EB - SQUARE D - NF

400A, 480/277V, 3Ø, 4W, 65kAIC

20A-3P 20A-1P15A-3P 15A-3P 15A-3P 60A-3P 60A-3P

NEW

480/277V

MLO

100A

H1EC

EXISTING

UNDER

PROJECT

NUMBER:

757-20-205

480/277V

MLO

100A

H1ED

(PROVIDED

WITH

GENERATOR)

660NX

20A-1P 20A-1P 15A-3P

NEW

HEAT

TRACE

PANEL

#5

HEAT

TRACE

PANEL

#3

HEAT

TRACE

PANEL

#4

(6)20A-1P

SPARE

X

ROP-1 DA-1

PUMP

#1

DA-1

PUMP

#2

DA-1

PUMP

#3

XXXX

20A-3P

NEW

20A-3P

NEW

20A-3P

NEW

FUEL

OIL

PUMPS

GEN DAY

TANK 1

GEN DAY

TANK 2

2HP 1HP 1HP

15A-3P

NEW

BOILER

PLANT

DOOR

1HP

B1

U1 A2

A1 T1 T2 T3 E1 E2

C1 E3 E4 LB G1 G2 G3 G4

LOAD BANK

& TEMP GEN

NP1 NP2 GP1 GP2

CP1E CP1N CP1M CP1T CP2E CP2N CP2M

B BBB

TEMP.

CHILLER

CONNECTION

BOX

ISC 3P: 45,911A

ISC SLG: 44,265A

ISC 3P: 51,188A

ISC SLG: 47,407A

ISC 3P: 32,756A

ISC SLG: 26,137A

ISC 3P: 40,374A

ISC SLG: 33,033A

ISC 3P: 2,477A

ISC SLG: 2,556A

ISC 3P: 629A

ISC SLG: 629A

ADDITIONAL

PROVISIONS NOT

SHOWN. REFER

TO BREAKER

SCHEDULE.

ADDITIONAL

PROVISIONS NOT

SHOWN. REFER

TO BREAKER

SCHEDULE.

SQUARE D - NF

REMOVE EXISTING 20A-1P CIRCUIT BREAKERS AS REQUIRED TO ACCOMMODATE NEW BREAKERS.

SQUARE D - NF

SQUARE D - NF

SQUARE D - NF

SQUARE D - NF SQUARE D - HCP

SQUARE D - NQ

S

59459

M.P. LONG

R

E

S

O F

I

R

G E

NO

I

S

P

E

N

E

D

ERT

L EA

E I N

G

R

T

S

TEA

H

F OO

IO

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

20045

C R e v it L o c a l F ile s \2

F

F H

C F

R

C h ri s to p h e r.

P

.C a m p b e ll.

rv t

/7 /2

:0

:1

P M

E-602

BOILER PLANT / CHILLER PLANT ONE-LINE

DIAGRAM

CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 CPC LV

BID & CONSTRUCTION

18902.00

# ONE-LINE CODED NOTES

1 EXISTING IN-GRADE, CONCRETE POLYMER ELECTRICAL BOX. REFER TO ELECTRICAL PLANS FOR LOCATION.

CONTRACTOR SHALL BE PERMITTED TO UTILIZE (1) OF EXISTING CONDUITS FOR NEW GENERATOR FEEDER TO EXISTING PSG LOCATION IN LIEU OF PROVIDING NEW GENERATOR FEEDER CONDUIT SHOWN ON PLANS.

THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING THE STRUCTURAL INTEGRITY OF THE EXISTING CONDUITS. OWNER SHALL NOT BE RESPONSIBLE FOR ELECTRICAL CABLE PULL FAILURE IN EXISTING CONDUITS AND RESULTING NEW UNDERGROUND FEEDER SHALL BE PROVIDED AT NO ADDITIONAL COST TO

THE GOVERNMENT.

PROVIDE A NEW GENERATOR BREAKER CUBICLE AND ASSOCIATED GENERATOR FEEDER CIRCUIT BREAKER IN EXISTING 'PSG-E' LINEUP. EXISTING MANUFACTURER IS RUSSELECTRIC. CUBICLE, BREAKER, METERING, RELAYS, ETC. SHALL MATCH EXISTING GENERATOR BREAKERS. ROUTE GENERATOR FEEDER TO NEW

BREAKER CUBICLE AND CONNECT COMPLETE.

RETAIN RUSSELECTRIC MANUFACTURER REPRESENTATIVE TO REPROGRAM EXISTING RUSSELECTRIC PARALLELING SWITCHGEAR TO CONNECT NEW GENERATOR #2 AS A NEW EMERGENCY GENERATOR AND PROGRAM PROTECTION (INCLUDING DIFFERENTIAL PROTECTION), CONTROL, PARALLELING AND LOAD

SHARING CAPABILITIES WITH EXISTING GENERATOR.

PROVIDE PULLBOX AS INDICATED ON SITE ELECTRICAL PLAN. REFER TO DRAWING FOR ADDITIONAL

INFORMATION AND WORK REQUIREMENTS.

REMOVE (3) EXISTING 20A-1P CIRCUIT BREAKERS AND PROVIDE (1) NEW 60A-3P CIRCUIT BREAKER IN EXISTING LIFE SAFETY PANEL AND CONNECT COMPLETE TO NEW TRANSFORMER PROVIDED WITH GENERATOR.

CIRCUIT BREAKER SHALL BE LOCKABLE AND TRANSFORMER SHALL BE FIELD-MARKED WITH DISCONNECTING

MEANS LOCATION PER NEC 450.14.

REMOVE (3) EXISTING 20A-1P CIRCUIT BREAKERS AND PROVIDE NEW BREAKER IN EXISTING ESSENTIAL EQUIPMENT PANEL. CONNECT COMPLETE TO NEW PANELBOARD PROVIDED WITH GENERATOR. REFER TO

ONE LINE DIAGRAM FOR BREAKER SIZE.

PROVIDE NEW LOAD BREAKER IN EXISTING CUBICLE. BREAKER, METERING, RELAYS, ETC. SHALL MATCH EXISTING LOAD BREAKERS. ROUTE GENERATOR FEEDER TO NEW BREAKER CUBICLE AND CONNECT

COMPLETE. COORDINATE REQUIREMENTS WITH RUSSELECTRIC.

EACH GENERATOR DAY TANK WILL HAVE (2) REDUNDANT POWER FEEDS. REFER TO GENERATOR PUMP

SYSTEM DETAIL AND MECHANICAL CONNECTIONS PLAN FOR ADDITIONAL INFORMATION.

PROVIDE NEW FACTORY-ASSEMBLED TEMPORARY CHILLER ELECTRICAL CONNECTIONS BOX AND CONNECT COMPLETE TO TEMPORARY CHILLER FEEDER INDICATED. REFER TO FLOOR PLAN AND NOTES FOR LOCATION AND BASIS OF DESIGN INFORMATION. COORDINATE WITH VENDOR TO ENSURE COMPATIBILITY WITH

EQUIPMENT SELECTED FOR CONSTRUCTION.

ONE-LINE GENERAL NOTES

REFER TO ONE-LINE LEGEND AND NOTES ON ELECTRICAL LEGEND SHEET FOR ADDITIONAL INFORMATION AND

WORK REQUIREMENTS.

CIRCUIT BREAKERS SHALL BE ASSUMED TO BE 3-POLE UNLESS OTHERWISE NOTED.

RETAIN RUSSELECTRIC TO PROVIDE EQUIPMENT INFORMATION, PROGRAMMING, TESTING, AND ADDITIONAL

SUPPORT DURING CONSTRUCTION PERIOD.

1.

2.

3.

METER SUBMITTAL REQUIREMENTS

CONTRACTOR SHALL BE RESPONSIBLE FOR METERING EACH EXISTING FACILITY TRANSFER SWITCH AND PROVIDE A REPORT TO VA COR AND ENGINEER. REPORT WILL BE USED FOR PARALLELING SWITCHGEAR SMART

LOADING PROGRAMMING.

REPORT SHALL BE PERFORMED DURING PEAK USAGE MONTHS (JULY OR AUGUST) FOR A 30-DAY DURATION.

REPORT SHALL INCLUDE PEAK DEMAND (KVA, KW, KVAR), VOLTAGE (PHASE TO PHASE AND PHASE TO NEUTRAL), CURRENT PER PHASE, POWER FACTOR, AND FREQUENCY

1.

2.

3.

Revisions: Date:

FINAL BID & CONSTRUCTION 11/24/2021

FINAL BID & CONSTRUCTION (REVISED) 05/06/2022

AMEDMENT 1 08/05/2022

INSTRUCTIONAL EQUIPMENT PLACARD:

BASIS OF DESIGN EQUIPMENT NOTES:

EPM

EPM

EPM

NEW SUBSTATION 'SS-CP1'

4000A, 13.2KV:480/277V-3∅-4W

NEW SUBSTATION 'SS-CP2'

4000A, 13.2KV:480/277V-3∅-4W

DISTRIBUTION

BREAKERS

TIE BREAKER

GROUND

FAULT

SCHEME

PRIMARY SWITCH

TRANSFORMER

FEEDER

TERMINATIONS

ELECTRIC

POWER METER

KEY

INTERLOCKING

TVSS

NAMEPLATE

ENCLOSURE

MAIN BUS

MAIN BREAKER

DISTRIBUTION

BREAKERS

GROUND

FAULT

SCHEME

PRIMARY SWITCH

TRANSFORMER

FEEDER

TERMINATIONS

ELECTRIC

POWER METER

KEY

INTERLOCKING

TVSS

NAMEPLATE

ENCLOSURE

MAIN BUS

MAIN BREAKER

EPM

PRIMARY

DUPLEX

PRIMARY

DUPLEX

20"W MAX 20"W MAX

DRY-TYPE TRANSFORMER

108"W 36"W 22"W 36"W

BREAKER

BREAKER

BREAKER

EPM

EPM

EPM

TVSS PROVISION

EPM

DRY-TYPE TRANSFORMER

108"W 36"W 22"W 36"W

BREAKER

PROVISION

BREAKER

EPM

EPM

TVSS PROVISION

PRIMARY

DUPLEX

PRIMARY

DUPLEX

20"W MAX 20"W MAX

EPM

K

K K K

K K K K

EPM

K

A1 A1

A1

A2

A2

A3

A3 A3 A3 B1 B1 B2 B3 B3 B3

B1

B2

B3

MB1

4000AF

4000AT

100%

250E

4000A, 480/277V-3∅-4W, SILVER-PLATED COPPER AT 1000AMPS PER SQUARE INCH - MIN. 65,000A RMS SYMMETRICAL SHORT CIRCUIT BRACING - FULL LENGTH GROUND BUS. EXTEND BUS THROUGH

ENTIRE SECTION TO ALLOW FOR BUS CONNECTION TO FUTURE DISTRIBUTION SECTIONS.

CH1

1600AF

1000AT

100%

CH2

1600AF

1000AT

100%

A1

800AF

800AT

100%

A2 1600A

TIE

4000AF

4000AT

100%

MB2

4000AF

4000AT

100%

CH3

1600AF

1000AT

100%

FUTURE CH4

1600A

B1

800AF

800AT

100%

B2 1600A

N.O.

PROVIDE (8) 17"x22" ENGRAVED PLACARDS FOR SWITCHGEAR BREAKER INSTRUCTIONS. CONTRACTOR SHALL PROVIDE ITEMS AS FOLLOWS:

1.

2.

3.

4.

ENGRAVED 1/4" MICARTA PLACARD MOUNTED ON EQUIPMENT WITH SCREWS.

ASSUME 1000 CHARACTERS/SYMBOLS PER INSTRUCTIONAL PLACARD. CHARACTER/SYMBOLS SHALL BE ASSUMED TO BE OF VARIOUS

HEIGHTS AND STYLES.

VERIFY EXACT SIZE, TEXT STYLE, COLOR AND MOUNTING LOCATION OF INSTRUCTIONAL PLACARDS WITH VAMC COTR PRIOR TO

ORDERING.

INSTRUCTION PLACARD WORDING SHALL BE PROVIDED BY THE VAMC THROUGH THE COMMISSIONING PROCESS. CONTRACTOR SHALL PROVIDE FINAL ENGRAVED PLACARDS WITHIN (4) WEEKS OF RECEIVING FINAL WORDING.

250E 250E250E

600A-15,000V - PRIMARY SWITCH, 25KAIC, 150E-RATED CURRENT LIMITING FUSES (ONE PER INCOMING LINE). MANUAL OPERATION, INDOOR ENCLOSURE, PROVISIONS FOR PADLOCKING FULL

HEIGHT MAIN DOOR WITH INSPECTION WINDOW, DOOR AND SWITCH INTERLOCK. PROVIDE KEY

INTERLOCKING SUCH THAT ONLY (1) PRIMARY FEEDER CAN BE CLOSED AT A TIME. BASIS OF DESIGN DIMENSIONS: 14.75"L x 37.25"D x 90"H

1.

2.

DIMENSIONS ARE PROVIDED FOR REFERENCE. SQUARE D PZ4 SWITCHGEAR BY SCHEIDER ELECTRIC USED AS A BASIS OF DESIGN.

WHERE SUBMITTED DIMENSIONS DIFFER FROM THE BASIS OF DESIGN, CONTRACTOR SHALL SUBMIT A NEW EQUIPMENT LAYOUT FOR REVIEW AND APPROVAL. LAYOUT SHALL BE SUBMITTED ALONG WITH EQUIPMENT SHOP DRAWINGS. EQUIPMENT SHALL NOT BE PURCHASED UNTIL LAYOUT IS APPROVED. EQUIPMENT MAY BE REJECTED IF PHYSICAL DIMENSIONS EXCEED BASIS-OF-DESIGN.

NEMA 1, SELF SUPPORTING STRUCTURE - FRONT AND REAR ACCESS SWITCHBOARD. BUILT TO UL

1558 STANDARDS. PROVIDE FRONT HINGED DOORS FOR POWER BREAKERS AND METERING

COMPARTMENTS. REAR COMPARTMENTS SHALL HAVE BOLTED COVERS. PROVIDE UNIT BREAKER

LIFT FOR DRAW-OUT BREAKERS. BASIS OF DESIGN DIMENSIONS: 92"H x 75.25"D, MAIN/TIE SECTIONS:

36"W, DISTRIBUTION SECTIONS: 22"W.

2000kVA, 13,200V DELTA PRIMARY, 480/277V-3Ø-4W WYE SECONDARY, DRY-TYPE, FORCED-AIR COOLED (133% OVERCURRENT RATING), 80°C RISE RATING, 95KV BIL, 5.75% MIN IMPEDANCE. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. BASIS OF DESIGN DIMENSIONS: 108"L x 66"D x

108"H, 13,400LB.

DRAW-OUT, LOW-VOLTAGE, 4000A-3P, POWER CIRCUIT BREAKER WITH DIGITAL, SOLID STATE

TRIP UNIT (100% RATED). TRIP UNIT SHALL HAVE FIELD INSTALLABLE, FRONT-MOUNTED RATING

PLUG AND ADJUSTABLE LONG-TIME, SHORT-TIME, INSTANTANEOUS, AND GROUND FAULT

SETTINGS. PROVIDE KEY INTERLOCKING DEVICE AND CONNECT PER ONE-LINE DIAGRAM.

DRAW-OUT, LOW-VOLTAGE, POWER CIRCUIT BREAKER WITH DIGITAL, SOLID STATE TRIP UNIT (100% RATED). FRAME AND TRIP UNIT SIZE AS INDICATED. TRIP UNIT SHALL HAVE FIELD INSTALLABLE, FRONT-MOUNTED RATING PLUG AND ADJUSTABLE LONG-TIME, SHORT-TIME, INSTANTANEOUS, AND

GROUND FAULT SETTINGS.

FURNISH AND INSTALL NEW CT'S FOR EACH BREAKER/PROVISION AND A COMMON SET OF PT'S TO

SUPPLY A COMMON LINE-SIDE VOLTAGE INPUT TO ALL METERS. PROVIDE NEW EPM'S FOR EACH BREAKER. MATCH EXISTING FACILITY TYPE(SCHNEIDER POWERLOGIC - PM8244) . CONNECT METERS

TO EXISTING FACILITIES MANAGEMENT SYSTEM.

PROVIDE INTEGRAL TRANSIENT VOLTAGE SURGE SUPPRESSION FOR 480/277V DISTRIBUTION. REFER

TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

ALL FEEDER TERMINATIONS SHALL BE MADE WITH 2-HOLE, LONG BARRELL COMPRESSION LUGS.

REFER TO POWER DISTRIBUTION ONE-LINE DIAGRAM FOR FEEDER SIZES.

PROVIDE GROUND FAULT RELAY SYSTEM FOR MAIN-TIE-MAIN BREAKER SCHEME (SIMILAR TO

MAGNUM DS MOD - RESIDUAL GROUND FAULT WITH ZONE INTERLOCKING). PROVIDE AUXILIARY

CONTACTS ON MAIN AND TIE BREAKERS. PROVIDE CT ON NEUTRAL OF ALL BREAKERS FOR NEUTRAL

CURRENT SENSING.

PROVIDE (2) FORM C AUX. CONTACTS FOR TIE BREAKER. PROVIDE 3/4" CONDUIT - 6#14 FROM TIE

BREAKER TO A LOCAL TEMPERATURE CONTROL PANEL TO MONITOR POSITION. PROVIDE KEY

INTERLOCKING DEVICE AND CONNECT PER ONE-LINE DIAGRAM.

ENGRAVED PHENOLIC NAMEPLATES FOR ALL BREAKERS, METERS, ETC. PROVIDE PHENOLIC MIMIC BUS FOR ALL SWITCHGEAR BUS, BREAKERS, METERING, ETC. VERIFY EXACT SIZE, TEXT STYLE, COLOR AND MOUNTING LOCATION WITH VAMC COR PRIOR TO ORDERING.

PROVIDE MANUAL KEY INTERLOCKING DEVICE BETWEEN (2) MAIN BREAKERS AND (1) TIE BREAKER.

SUBMIT MECHANICAL INTERLOCKING SCHEME WITH SHOP DRAWINGS FOR APPROVAL.

4000A, 480/277V-3∅-4W, SILVER-PLATED COPPER AT 1000AMPS PER SQUARE INCH - MIN. 65,000A RMS SYMMETRICAL SHORT CIRCUIT BRACING - FULL LENGTH GROUND BUS. EXTEND BUS THROUGH

ENTIRE SECTION TO ALLOW FOR BUS CONNECTION TO FUTURE DISTRIBUTION SECTIONS.

600A-15,000V - PRIMARY SWITCH, 25KAIC, 150E-RATED CURRENT LIMITING FUSES (ONE PER INCOMING LINE). MANUAL OPERATION, INDOOR ENCLOSURE, PROVISIONS FOR PADLOCKING FULL

HEIGHT MAIN DOOR WITH INSPECTION WINDOW, DOOR AND SWITCH INTERLOCK. PROVIDE KEY

INTERLOCKING SUCH THAT ONLY (1) PRIMARY FEEDER CAN BE CLOSED AT A TIME. BASIS OF DESIGN DIMENSIONS: 14.75"L x 37.25"D x 90"H

NEMA 1, SELF SUPPORTING STRUCTURE - FRONT AND REAR ACCESS SWITCHBOARD. BUILT TO UL

1558 STANDARDS. PROVIDE FRONT HINGED DOORS FOR POWER BREAKERS AND METERING

COMPARTMENTS. REAR COMPARTMENTS SHALL HAVE BOLTED COVERS. PROVIDE UNIT BREAKER

LIFT FOR DRAW-OUT BREAKERS. BASIS OF DESIGN DIMENSIONS: 92"H x 75.25"D, MAIN/TIE SECTIONS:

36"W, DISTRIBUTION SECTIONS: 22"W.

2000kVA, 13,200V DELTA PRIMARY, 480/277V-3Ø-4W WYE SECONDARY, DRY-TYPE, FORCED-AIR COOLED (133% OVERCURRENT RATING), 80°C RISE RATING, 95KV BIL, 5.75% MIN IMPEDANCE. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. BASIS OF DESIGN DIMENSIONS: 108"L x 66"D x

108"H, 13,400LB.

DRAW-OUT, LOW-VOLTAGE, 4000A-3P, POWER CIRCUIT BREAKER WITH DIGITAL, SOLID STATE

TRIP UNIT (100% RATED). TRIP UNIT SHALL HAVE FIELD INSTALLABLE, FRONT-MOUNTED RATING

PLUG AND ADJUSTABLE LONG-TIME, SHORT-TIME, INSTANTANEOUS, AND GROUND FAULT

SETTINGS. PROVIDE KEY INTERLOCKING DEVICE AND CONNECT PER ONE-LINE DIAGRAM.

DRAW-OUT, LOW-VOLTAGE, POWER CIRCUIT BREAKER WITH DIGITAL, SOLID STATE TRIP UNIT (100% RATED). FRAME AND TRIP UNIT SIZE AS INDICATED. TRIP UNIT SHALL HAVE FIELD INSTALLABLE, FRONT-MOUNTED RATING PLUG AND ADJUSTABLE LONG-TIME, SHORT-TIME, INSTANTANEOUS, AND

GROUND FAULT SETTINGS.

FURNISH AND INSTALL NEW CT'S FOR EACH BREAKER/PROVISION AND A COMMON SET OF PT'S TO

SUPPLY A COMMON LINE-SIDE VOLTAGE INPUT TO ALL METERS. PROVIDE NEW EPM'S FOR EACH BREAKER. MATCH EXISTING FACILITY TYPE(SCHNEIDER POWERLOGIC - PM8244) . CONNECT METERS

TO EXISTING FACILITIES MANAGEMENT SYSTEM.

PROVIDE INTEGRAL TRANSIENT VOLTAGE SURGE SUPPRESSION FOR 480/277V DISTRIBUTION. REFER

TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

ALL FEEDER TERMINATIONS SHALL BE MADE WITH 2-HOLE, LONG BARRELL COMPRESSION LUGS.

REFER TO POWER DISTRIBUTION ONE-LINE DIAGRAM FOR FEEDER SIZES.

PROVIDE GROUND FAULT RELAY SYSTEM FOR MAIN-TIE-MAIN BREAKER SCHEME (SIMILAR TO

MAGNUM DS MOD - RESIDUAL GROUND FAULT WITH ZONE INTERLOCKING). PROVIDE AUXILIARY

CONTACTS ON MAIN AND TIE BREAKERS. PROVIDE CT ON NEUTRAL OF ALL BREAKERS FOR NEUTRAL

CURRENT SENSING.

ENGRAVED PHENOLIC NAMEPLATES FOR ALL BREAKERS, METERS, ETC. PROVIDE PHENOLIC MIMIC BUS FOR ALL SWITCHGEAR BUS, BREAKERS, METERING, ETC. VERIFY EXACT SIZE, TEXT STYLE, COLOR AND MOUNTING LOCATION WITH VAMC COR PRIOR TO ORDERING.

PROVIDE MANUAL KEY INTERLOCKING DEVICE BETWEEN (2) MAIN BREAKERS AND (1) TIE BREAKER.

SUBMIT MECHANICAL INTERLOCKING SCHEME WITH SHOP DRAWINGS FOR APPROVAL.

33 3 3

S

59459

M.P. LONG

R

E

S

O F

I

R

G E

NO

I

S

P

E

N

E

D

ERT

L EA

E I N

G

R

T

S

TEA

H

F OO

IO

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

20045

C R e v it L o c a l F ile s \2

F

F H

C F

R

C h ri s to p h e r.

P

.C a m p b e ll.

rv t

/8 /2

:1

:3

A

M

E-506

SUBSTATION DETAIL AND GENERAL NOTES CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 CPC LV

BID & CONSTRUCTION

18902.00

NOT TO SCALE

SUBSTATION DETAIL AND GENERAL NOTES 1

Revisions: Date:

FINAL BID & CONSTRUCTION 11/24/2021

FINAL BID & CONSTRUCTION (REVISED) 05/06/2022

E-201 - PARTIAL SECOND FLOOR ELECTRICAL EQUIPMENT AND RACEWAY LAYOUT PLAN - SOUTH.pdf
20045 FFH CF R2020_Christopher.P.Campbell
E-201 - PARTIAL SECOND FLOOR ELECTRICAL EQUIPMENT AND RACEWAY LAYOUT PLAN - SOUTH
E-604 - ELECTRICAL GROUNDING SYSTEM DIAGRAM.pdf
20045 FFH CF R2020_Christopher.P.Campbell
E-604 - ELECTRICAL GROUNDING SYSTEM DIAGRAM
E-602 - BOILER PLANT CHILLER PLANT ONE-LINE DIAGRAM.pdf
20045 FFH CF R2020_Christopher.P.Campbell
E-602 - BOILER PLANT / CHILLER PLANT ONE-LINE DIAGRAM
E-506 - SUBSTATION DETAIL AND GENERAL NOTES.pdf
20045 FFH CF R2020_Christopher.P.Campbell
E-506 - SUBSTATION DETAIL AND GENERAL NOTES