18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-8.pdf

PDF 10 MB Posted

Attached to
36C25023B0049 - Y1NB--Construct Chiller Plant - Columbus, OH Chalmers P. Wylie VAACC SDVOSB Set-Aside - Solicitation
Solicitation number
36C25023B0049
Issued by

About this file

This file summary describes a federal contract solicitation for construction services. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 to construct a chiller plant at the Columbus VA Medical Center in Columbus, Ohio. The solicitation number is 36C25023B0049 and it is set aside exclusively for service-disabled veteran-owned small businesses. Responses are due on an unspecified date. The solicitation seeks a contractor to perform construction work related to installing a new chiller plant as described in the related technical drawings and specifications file.

View the file

Other files

File Type Posted
36C25024C0013 SAM Award Notice 1.0.pdf PDF
36C25023B0049 - Amendment 3.docx DOCX document
36C25023B0049 - Amendment 2.pdf PDF
36C25023B0049 - Amendment 1.docx DOCX document
Single Source Justification MPT to SAT - Wattstopper - Pricing Removed - Signed.pdf PDF
VHA Directive 1192.01, Seasonal Influenza Prevention Program for VHA Health Care Personnel.pdf PDF
18912 Columbus VAMC Chiller BC Sole Source Redacted.pdf PDF
VAAR 852.219-75 - To Be Submitted With Bid.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-5.pdf PDF
VAACC Health Requirements - Bid Ready 2023.pdf PDF
36C25023B0049 - Ready.docx DOCX document
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-4.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-1.pdf PDF
Single Source Justification MPT to SAT - Simplex - 2.0 Price Removed - Signed.pdf PDF
18912 Columbus VA Chiller Plant Revision Final B_C Re-Revised - PM Vol 1 of 2.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-2.pdf PDF
Franklin DB - Current as of 07.13.2023.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-9.pdf PDF
Single Source Justification MPT to SAT - Software House - Pricing Removed - Signed.pdf PDF
Single Source Justification MPT to SAT - Russ Electric Price Removed - Signed.pdf PDF
18912 Columbus DVAMC Chiller FB_C PM Volume 2 of 2.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-6.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-7.pdf PDF
Hca Signed NCO 10 Caterpillar - Sole Source - Pricing Removed.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-10.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-3.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E

E

F

F

G

G

H

H

J

J

K

K

3.8

0.7

X -R

T U

-1

X-ACH-1

X-ACH-2

X-RTU-9

X -R

T U

-6

PENTHOUSE

HEAT TRACE PANEL 1

HEAT TRACE PANEL 2

HEAT TRACE CIRCUIT 1-A

HEAT TRACE CIRCUIT 1-B

HEAT TRACE CIRCUIT 2-B

HEAT TRACE CIRCUIT 2-A

18"ø CHWS

18"ø CHWR

M -1

A

M -1

B

M -1

A

M -1

B

(TYP.)

M-153AM-153B

M-153C

74490

L.D. HENDRIX, JR

GN

S S

A

ION EL

T

F EGE

P R O

R

SI NRE I

E E R

D

E

AT

S

ET

O

OI

HO

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

20045

C R e v it L o c a l F ile s \2

F

F H

C F

R

C h ri s to p h e r.

P

.C a m p b e ll.

rv t

/6 /2

:5

:3

P M

M-153B

ACC THIRD FLOOR / ROOF HVAC PIPING PLAN CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 LDH CAB

BID & CONSTRUCTION

18902.00 1

0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'

1/8" = 1'-0"

ACC THIRD FLOOR/ROOF HVAC PIPING PLAN 1

CODED NOTES

18"Ø CHWS AND CHWR PIPING DOWN THROUGH ROOF INTO 2ND FLOOR CEILING SPACE BELOW. SEE "ACC SECOND FLOOR PIPING PLAN - AREA A" DWG M-152 FOR CONTINUATION. PROVIDE PIPE PENETRATION CURB

PER DETAIL #4 DWG M-504.

REFER TO DWG M-153A FOR CONTINUATION.

PIPING SUPPORTS AS INDICATED. FINAL LOCATIONS SHALL BE COORDINATED WITH STRUCTURAL DRAWINGS AND FIELD VERIFIED. REFER TO DETAIL #2 DRAWING M-504 FOR MORE INFORMATION.

OFFSET CHILLED WATER PIPING TO MAINTAIN CLEARANCE AROUND AIR HANDLING UNIT.

NOT TO SCALE

ACC 3RD FLOOR/ROOF KEY PLAN

GENERAL NOTES

A.

B.

FIELD VERIFY ROUTING OF CHILLED WATER PIPING. COORDINATE ROUTING OF PIPING WITH EXISTING ELECTRICAL CONDUIT MAINS, HEATING HOT WATER SYSTEMS, PNEUMATIC TUBE SYSTEMS, ETC. ROUTE ALL NEW PIPING AS HIGH AS POSSIBLE . PROVIDE ANY AND ALL OFFSETS AS NECESSARY FOR OPTIMAL

PIPE ROUTING.

CONTRACTOR SHALL COORDINATE ANY REVISIONS TO ROUTE OF CHILLED WATER PIPING WITH

STRUCTURAL ENGINEER PRIOR TO BEGINNING WORK.

N

HEAT TRACE HATCHING LEGEND

HEAT TRACE CIRCUIT 1-A / 1-B (FROM HEAT TRACE PANEL # 1)

HEAT TRACE CIRCUIT 2-A / 2-B (FROM HEAT TRACE PANEL # 2)

HEAT TRACE CIRCUIT 3-A / 3-B (FROM HEAT TRACE PANEL # 3)

HEAT TRACE CIRCUIT 4-A / 4-B (FROM HEAT TRACE PANEL # 4)

HEAT TRACE CIRCUIT 5-A / 5-B (FROM HEAT TRACE PANEL # 5)

A. HATCHING INDICATES PIPING REQUIRING HEAT TRACE. REFER TO DETAIL #1, DWG M-504 FOR MORE

INFORMATION.

Revisions: Date:

FINAL BID & CONSTRUCTION 11/24/2021

FINAL BID & CONSTRUCTION (REVISED) 05/06/2022

A

AB

B

C

CD

D

E

E

0.2

0.5

0.8

A.2

A.2

A.1

A.1

A.8

A.8

0.7

X-RTU-15

XR - RS

XR - RL

XR - RL

XR - RS

X-TEF-7

X-TEF-5

X-GEF-6

X-TEF-6

XR-CU-15

X-CU-2X-CU-3

ROOF

CC-1

1 / M-153C

1 / M-153A

1 / M-153C

1 / M-153A

M-153AM-153B

M-153C

74490

L.D. HENDRIX, JR

GN

S S

A

ION EL

T

F EGE

P R O

R

SI NRE I

E E R

D

E

AT

S

ET

O

OI

HO

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

20045

C R e v it L o c a l F ile s \2

F

F H

C F

R

C h ri s to p h e r.

P

.C a m p b e ll.

rv t

/6 /2

:5

:4

P M

M-153C

ACC THIRD FLOOR / ROOF HVAC PIPING PLAN CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 LDH CAB

BID & CONSTRUCTION

18902.00 1

0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'

1/8" = 1'-0"

ACC THIRD FLOOR/ROOF HVAC PIPING PLAN 1

CODED NOTES

4"Ø CHWS & CHWR PIPING DOWN THROUGH ROOF INTO 2ND FLOOR CEILING SPACE BELOW. SEE "ACC SECOND FLOOR PIPING PLAN - AREA B" DWG M-152 FOR CONTINUATION. PIPING SHALL BE INSTALLED AND PREPARED FOR CHANGEOVER PRIOR TO REMOVAL OF DX COIL AND INSTALLATION OF NEW COIL IN ORDER

TO MINIMIZE RTU-15 SHUTDOWN TO A SINGLE WEEKEND. COORDINATE WITH VA COR.

CONTRACTOR SHALL REMOVE EXISTING DX COOLING COIL AND CONNECT NEW 4"Ø CHWS & CHWR PIPING TO NEW CHILLED WATER COIL IN EXISTING RTU-15. CONNECT PER DETAIL #8 ON DWG M-502. EXISTING DX COIL SHALL NOT BE REMOVED UNTIL NEW CHILLED WATER PIPING IS INSTALLED AND PREPARED FOR CHANGEOVER IN ORDER TO MINIMIZE RTU-15 SHUTDOWN TO A SINGLE WEEKEND. COORDINATE WITH VA

COR.

REMOVE EXISTING CONDENSING UNIT AND ALL ASSOCIATED REFRIGERANT PIPING, CONTROLS, WIRING, SUPPORTS, ETC. COMPLETE. PATCH ROOF WATERTIGHT.

REFER TO ALTERNATE NOTES, THIS DWG, FOR ADDITIONAL INFORMATION.

NOT TO SCALE

ACC 3RD FLOOR/ROOF KEY PLAN

ALTERNATE NOTES

ALTERNATE NO 2:

AS PART OF ALTERNATE NO. 2, ALL WORK ASSOCIATED WITH CONVERTING EXISTING RTU-15 FROM DX

COOLING TO CHILLED WATER SHALL BE DELETED.

A.

GENERAL NOTES

A. FIELD VERIFY ROUTING OF CHILLED WATER PIPING. COORDINATE ROUTING OF PIPING WITH EXISTING ELECTRICAL CONDUIT MAINS, HEATING HOT WATER SYSTEMS, PNEUMATIC TUBE SYSTEMS, ETC. ROUTE ALL NEW PIPING AS HIGH AS POSSIBLE . PROVIDE ANY AND ALL OFFSETS AS NECESSARY FOR OPTIMAL

PIPE ROUTING.

N

Revisions: Date:

FFH 1ST FLOOR

2"ø NPCW2"ø NPCW2"ø NPCW

20 x 44 SA

20"ø TWR

20 x 44 SA 20 x 56 SA 24 x 108 RA

PAC-AHU-4

COOLING TOWER SUPPORT STRUCTURE .

SEE STRUCTURAL DRAWINGS.

COORDINATE MANUFACTURER'S

REQUIREMENTS WITH GENERAL TRADES

CONTRACTOR AND CONSTRUCTION OF

SUPPORTS. (TYP.)

ALL TOWER BASINS MUST BE LEVEL

WHEN FILLED. SHIM TOWERS AS

NECESSARY. COORDINATE HEIGHT OF

STEEL TO ACHIEVE NECESSARY

FITTINGS AND GRAVITY FLOW TO TW

PUMP INLETS. (TYP.)

A F

F

A F

F

SIDE STREAM FILTER

SYSTEM

0.5

0.5

0.8

0.8

B.4

B.4

2"ø NPCW

20"Ø TWS & TWR

20"ø TWS

18"ø CHWR

20"ø TWS 3"ø NPCW 3"ø NPCW

14"Ø

EQUALIZER

PIPING

8"ø TWS

8"ø TWS

6"Ø BRANCH TO CT BASIN

SWEEPERS. PIPE PER

MANUFACTURER'S

RECOMMENDATIONS

(TYP.)

12"ø TWR

12"ø TWS

12"ø TWS

12"ø TWR 12"ø TWR

12"ø TWS 12"ø TWS 12"ø TWR

6"Ø WATER

LEVEL SENSOR

STANDPIPE

A

F F

CHEMICAL

TREATMENT TANK

A F

F

10"Ø CHWS AND CHWR TO

EMERGENCY CONNECTION

FFH 1ST FLOOR

B.2B.5B.8C.3D.4E.3

CH-3CH-2CH-1

3"ø NPCW

3"ø NPCW

2"ø NPCW

4"ø CW

10"ø CHWR

12"ø TWR

12"ø TWS x

E

A

34 x 34

E1 3835

34 x 34

E1 3835

34 x 34

E1 3835

10"ø CHWS

FILL LINE STATION (BEHIND

CH-4). REFER TO DETAIL #5

ON DWG M-502 MORE

INFORMATION.

MOUNT CHILLER ON 6-INCH THICK

CONCRETE PAD. REFER TO

STRUCTURAL PLANS FOR ADDITIONAL

INFORMATION. PROVIDE VIBRATION

ISOLATION PER SPECIFICATIONS. (TYP.)

4" DOMESTIC COLD

WATER PIPED BACK TO

DOMESTIC COLD

WATER MAIN.

0.5 0.8 B.4

CH-4

20 x 60 EA

20"ø TWS

(BEHIND)

10"ø CHWS 10"ø CHWS 10"ø CHWS

(BEHIND) (BEHIND) (BEHIND)

(TYP. OF 4)

(TYP. OF 4)

10"ø CHWR 10"ø CHWR 10"ø CHWR

10"Ø CHWS AND CHWR TO

EMERGENCY CONNECTION

REFRIGERANT MONITOR PANEL

10"ø CHWS

10"ø CHWR

74490

L.D. HENDRIX, JR

GN

S S

A

ION EL

T

F EGE

P R O

R

SI NRE I

E E R

D

E

AT

S

ET

O

OI

HO

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

20045

C R e v it L o c a l F ile s \2

F

F H

C F

R

C h ri s to p h e r.

P

.C a m p b e ll.

rv t

/6 /2

:5

:5

P M

M-301

MECHANICAL SECTIONS CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 LDH CAB

BID & CONSTRUCTION

18902.00

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0" A

SECTION A

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0" B

SECTION B

GENERAL NOTES

A.

B.

ALL VALVING, SENSORS , CONTROLS MAY NOT BE ILLUSTRATED ON SECTION CUTS. REFER TO DETAILS, SCHEMATICS, AND DIAGRAMS FOR SPECIFIC REQUIREMENTS FOR VALVES, DEVICES, HEAT TRACE, ETC.

PROTECT ALL EXPOSED INSULATED PIPING WITHIN 6'-0" OF FINISHED FLOOR WITH ALUMINUM JACKET.

Revisions: Date:

FFH 1ST FLOOR

PAC-AHU-4

TP-3 TP-2 TP-1 P-3 P-2 P-1AS-1 ET-1

18"ø CHWR

18"ø CHWR

1"ø CHWR

2"ø NPCW

14 x 16 SA

CHEMICAL TREATMENT

FEED TANKS AND

ASSOCIATED PUMPS.

WATER TREATMENT

AND INSTRUMENTATION

CONTROLS STATION.

0.50.8B.4

18"ø CHWR

18"ø CHWR

TP-4 P-4

8"Ø FROM COOLING TOWER

EQUALIZER PIPING TO SSF-1 INLET

8"Ø FROM SSF-1 DISCHARGE TO

COOLING TOWER BASIN SWEEPERS

3/4"ø CA

3/4"Ø COMPRESSED AIR PIPING TO

SSF-1

FTP-1

FUEL OIL DIVERTER

VALVE CONTROL

PANEL

1"ø CHWR

CHEMICAL POT FEEDER

SSF-1

"ø

T W

S

"ø

T W

S

"ø

T W

S

"ø

T W

S

"ø

T W

S

"ø

T W

S

"ø

T W

S

"ø

T W

S

"ø

C H

W R

"ø

C H

W R

"ø

C H

W R

"ø

C H

W R

"ø

C H

W R

"ø

C H

W R

"ø

C H

W R

"ø

C H

W R

20"ø TWS 20"ø TWS 20"ø TWS

20"ø TWS20"ø TWS

18"ø CHWR

(BEHIND)

VFD

(TYP. OF 8)

VFDVFD

14 x 16 SA

FUEL OIL TRANSFER

PUMP CONTROL PANEL 1

"ø

C H

W S

"ø

C H

W R

10"Ø CHWS AND CHWR

THRU WALL TO

EMERGENCY

CONNECTION.

FFH 1ST FLOOR

56 x 20 SA

108 x 24 RA

PAC-AHU-4

16 x 14 SA

FTP-1FUEL OIL DIVERTER

VALVE CONTROL

PANEL WATER TREATMENT

CONTROL PANEL

FUEL OIL PUMP

CONTROL PANEL

10"Ø CHWS AND CHWR TO

EMERGENCY CONNECTION

10"Ø CHWS AND CHWR

IN FIELD-FABRICATED

LOCKABLE ENCLOSURE

74490

L.D. HENDRIX, JR

GN

S S

A

ION EL

T

F EGE

P R O

R

SI NRE I

E E R

D

E

AT

S

ET

O

OI

HO

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

20045

C R e v it L o c a l F ile s \2

F

F H

C F

R

C h ri s to p h e r.

P

.C a m p b e ll.

rv t

/6 /2

:5

:0

P M

M-302

MECHANICAL SECTIONS CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 LDH CAB

BID & CONSTRUCTION

18902.00

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0" C

SECTION C

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0" D

SECTION D

GENERAL NOTES

A.

B.

ALL VALVING, SENSORS , CONTROLS MAY NOT BE ILLUSTRATED ON SECTION CUTS. REFER TO DETAILS, SCHEMATICS, AND DIAGRAMS FOR SPECIFIC REQUIREMENTS FOR VALVES, DEVICES, HEAT TRACE, ETC.

PROTECT ALL EXPOSED INSULATED PIPING WITHIN 6'-0" OF FINISHED FLOOR WITH ALUMINUM JACKET.

Revisions: Date:

A.8

18"Ø CHWS

& CHWR

REFER TO ARCHITECTURAL

PLANS FOR MODIFICATIONS

TO EXISTING PARAPET

AV

PROVIDE AIR VENT AT HIGH

POINT OF CHWS AND CHWR

PIPING. REFER TO DETAIL #1

DWG M-501.

ROOF CURBS AND

PIPE SUPPORTS

(TYP.)

THIRD FLOOR

FFH 1ST FLOOR

FFH ROOF

BOILER ROOM

CHILLER PLANT

EC-114

18" CHWS & CHWR

FROM CHILLER PLANT

OFFSET CHWS & CHWR AS HIGH

AS POSSIBLE IN BOILER ROOM

PIPE HANGER

SHOWN FOR

REFERENCE

AV

PROVIDE AIR VENT AT HIGH

POINT OF CHWS AND CHWR

PIPING. REFER TO DETAIL #1

DWG M-501.

18"Ø CHWS & CHWR DOWN

INSIDE BOILER ROOM

18"Ø CHWS & CHWR

PIPING DOWN IN PIT

COORDINATE PIPING INVERT

WITH SITE CIVIL PLANS

2" MANUAL DRAIN VALVE AT

LOW POINT IN CHWS &

CHWR PIPING. REFER TO

DETAIL #1 DWG M-501

X - 3"ø HPR

2"ø BD

1"ø D

2"ø BD

BOILER ROOM

PIPE HANGER

SHOWN FOR

REFERENCE

(TYP.)

VERTICAL PIPE SUPPORT

X - 6"ø G

X - 8"ø HPS

X - 6"ø HPS

X - 4"ø LPS

X - 3"ø LPS

PROVIDE MANUAL ISOLATION

VALVES IN CHWS & CHWR

PIPING. INSTALL IN ACCESSIBLE

LOCATION

AV

PROVIDE AIR VENT AT HIGH

POINT OF CHWS AND CHWR

PIPING. REFER TO DETAIL #1

DWG M-501.

SLEEVE AND SEAL CHWS &

CHWR PIPING WITH

MECHANICAL LINK SEALS.

A.8

18"Ø CHWS & CHWR UP IN NEW

ENCLOSURE

18"Ø CHWS & CHWR

BELOW GRADE

AV

PROVIDE AIR VENT AT HIGH

POINT OF CHWS AND CHWR

PIPING. REFER TO DETAIL #1

DWG M-501.

EXTERIOR CHWS AND CHWR

PIPING SHALL BE HEAT

TRACED. REFER TO M-153A

FOR MORE INFORMATION.

2" MANUAL DRAIN VALVE AT

LOW POINT IN CHWS &

CHWR PIPING. REFER TO

DETAIL #1 DWG M-501

SLEEVE AND SEAL CHWS &

CHWR PIPING WITH

MECHANICAL LINK SEALS.

THIRD FLOOR

SECOND FLOOR

REFER TO ARCHITECTURAL

PLANS FOR MODIFICATIONS

TO EXISTING PARAPET

2-SECOND FLOOR

3-THIRD FLOOR18"ø CHWR

18"ø CHWS

10"ø CHWS

10"ø CHWR

10"Ø CHWR

(OPPOSITE SIDE)

10"Ø CHWS

(OPPOSITE SIDE)

THIRD FLOOR

SECOND FLOOR

74490

L.D. HENDRIX, JR

GN

S S

A

ION EL

T

F EGE

P R O

R

SI NRE I

E E R

D

E

AT

S

ET

O

OI

HO

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

20045

C R e v it L o c a l F ile s \2

F

F H

C F

R

C h ri s to p h e r.

P

.C a m p b e ll.

rv t

/6 /2

:5

:1

P M

M-303

MECHANICAL SECTIONS CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 LDH CAB

BID & CONSTRUCTION

18902.00

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

SECTION H H

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

SECTION E E

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

SECTION F F

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

SECTION G G

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

SECTION J J

GENERAL NOTES

ALL EXTERIOR PIPING SHALL BE HEAT TRACED. REFER TO FLOOR PLANS AND DETAIL #1 & #2 ON DRAWING

M-504 FOR MORE INFORMATION.

A.

Revisions: Date:

* BY ROOFING

SUB-CONTRACTOR

WOOD BLOCKING

ALUMINUM FLASHING

ROOF MEMBRANE *

FIBER CANT. *

ROOF INSULATION *

ROOF DECK

BOLT CURB

TO DECK30" FOR 1 PIPE

COVER HEADS OF NAILS

WITH SILICON SEALANT *

4-3/4" LAG

BOLTS (TYP)

TYPE 46 ADJUSTABLE

PIPE ROLL AND STAND

W/BASE

PROTECTION SADDLE

(TYPE-39)

PIPE

INSULATION W/ ALUMINUM JACKET

(NOT REQUIRED FOR NATURAL

GAS PIPING)

3/4" THICK GAL.

STEEL PLATE

60" FOR 2 PIPES

EQUIPMENT

SUPPORT RAIL

12" HIGH

NOT TO SCALE

6" 6"

6" 6"

NOTE:

1. APPLICABLE TO PENETRATIONS OF

ALL FIRE RATED MEMBRANES, IN

ACCORDANCE WITH NFPA 101. REFER

TO SPECIFICATIONS SECTION 078400 FOR

FIRE STOPPING SYSTEMS.

INSULATED

PIPE

FLOOR

FIRESTOP MATERIAL

3/4" [19mm] APPROVED

FIRESTOP INSULATION

WITH VAPOR BARRIER

PIPE SLEEVE

WHERE SPECIFIED

1/4" [6mm]∅ ANCHOR

ROD FOR NEW

CONSTRUCTION

WELD

FLOOR OR DECK PENETRATION

PARTITION OR CHASE PENETRATION

[152mm] [152mm]

MASONRY

PARTITION

PARTITION SUPPORT

FIRESTOP

MATERIAL

[152mm] [152mm]

3/4" [19mm] APPROVED

FIRESTOP INSULATION

WITH VAPOR BARRIER

DRYWALL PARTITION

INSULATED

PIPE

NOT TO SCALE

W

MAIN EXHAUST OR RETURN

PLAN VIEW

AIR

FLOW AIR

FLOW

PROVIDE VOLUME DAMPER

WHEN SHOWN ON FLOOR

PLANS

1/4W OR 4"

[102mm]

MIN.

BRANCH DUCT

NOT TO SCALE

4" DIRT LEG

GAS FIRED

EQUIPMENT

ON ROOF

UNION

GAS

SERVICE

GAS COCK

PROVIDE GAS

REGULATOR TO

REDUCE PRESSURE

TO 10" W.C.

NOT TO SCALE

W

W1

NOTE:

1.

2.

3.

4.

ALL VANED ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.

WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE VANE TYPE REGARDLESS OF W

DIMENSION.

ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE

BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.

WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE

VANE TYPE.

NOT TO SCALE

ROOF

OVER EXISTING

LAP NEW MEMBRANE

CONTRACTOR

FIBER CANT.

MANUFACTURER

ROOF CURB BY MECHANICAL

INSULATION BY CURB

SOLDER SEAMS

BY MECHANICAL CONTRACTOR.

COLLAR AT DUCT.

SOLDER ALL SEAMS

ALUMINUM CAP FABRICATED

WATERTIGHT.

WATERTIGHT.

DUCT

NOT TO SCALE

ABOVE 2" (50 MM) DIA. PIPE

2 1/2" (65 MM) DIA.

2" (50 MM) DIA. & SMALLER

HORIZONTAL

ABOVE 2" (50 MM) DIA. PIPE 2" (50 MM) DIA. & SMALLER

VERTICAL

2 1/2" (65 MM) DIA.

NOT TO SCALE

NOTE:

1.

2.

3.

4.

SECURE CURB CAP TO WOOD NAILING STRIP WITH 3/8" [10mm] CADMIUM PLATED LAG BOLTS

NOT OVER 12" [300mm] ON CENTER.

SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION BOLTS

(CONCRETE ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR JOIST ROOF).

RUN ELECTRICAL LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY DAMPER, THEN

THROUGH VENTILATOR ELECTRICAL CONDUIT GUIDE.

DETAIL NOTES APPLIES TO BOTH DOWNBLAST AND UPBLAST TYPE FANS.

GRAVITY BACKDRAFT DAMPER

RIGID CONDUIT TO

ACCOMMODATE

ELECTRICAL WIRES

SEE NOTE 2

PREFABRICATED

ROOF CURB

WOOD NAILING

STRIP

ELECTRICAL

CONDUIT GUIDE

MOTOR HOUSING

DUCT

TRANSITION DUCT TO

FULL SIZE OF DAMPER

SUPPLIED WITH ROOF

VENTILATOR

ROOF

SEE NOTE 2

SEE NOTE 1

CURB CAP

NOT TO SCALE

W

R

2/3W

/3

W

W W

1/2W

/3

W

1/6W

VANE

VANE

NOTE:

1.

2.

THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.

ALL STANDARD RADIUS ELBOWS SHOWN ON FLOOR PLANS MAY BE MADE SHORT RADIUS

ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE

CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.

R SHALL

EQUAL

OR BE

GREATER

THAN W.

R SHALL

EQUAL

OR BE

GREATER

THAN

1/3W.

R

R SHALL

EQUAL

OR BE

GREATER

THAN

1/6W.

STANDARD

RADIUS ELBOW

SHORT RADIUS

ELBOW WITH

ONE VANE

SHORT RADIUS

ELBOW WITH

TWO VANES

R

NOT TO SCALE

NOTE:

1.

2.

DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.

DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR

MULTI-BLADE DAMPERS & ROUND DAMPERS.

INSULATION

DAMPER BLADE

1/8" [6mm]

CLEARANCE

ALL AROUND

OUTSIDE END BEARING

INSIDE END BEARING

HANDLE WITH

LOCKING

QUADRANT

2" INSULATION

STAND-OFF

1/2" [15mm] ROUND

ROD PIN

DUCT

STIFFEN BLADE

AS REQUIRED

SIDE ELEVATION SECTION

NOT TO SCALE

TYPICAL CHILLED WATER

TYPICAL AIR VENT

PIPING DRAIN VALVE CONNECTIONS

VENT ALL HIGH POINTS INDICATED ABOVE.

IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN

NOTES:

1.

2.

PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.

TYPICAL WATER PIPING

REDUCER, IF REQUIRED

3/4" (20 MM) BALL VALVE

ADAPTER TO 20 MM (3/4") HOSE THREAD.

PROVIDE HOSE CAP NUT

NOTES:

ELEVATION

THREADED PIPING WELDED PIPING

ELEVATION

1/2" COPPER TUBING

1/2" BALL VALVE

1/2" x 4" NIPPLE

CIRCULATING WATER PIPING

WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR

DRAIN ALL LOW POINTS AS INDICATED ABOVE.

1.

2.

ELEVATION

NOT TO SCALE

74490

L.D. HENDRIX, JR

GN

S S

A

ION EL

T

F EGE

P R O

R

SI NRE I

E E R

D

E

AT

S

ET

O

OI

HO

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

20045

C R e v it L o c a l F ile s \2

F

F H

C F

R

C h ri s to p h e r.

P

.C a m p b e ll.

rv t

/6 /2

:5

:2

P M

M-501

MECHANICAL DETAILS CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 LDH CAB

BID & CONSTRUCTION

18902.00

TYPICAL ROOF MOUNTED PIPE SUPPORT DETAIL 2PENETRATION OF FIRE/SMOKE BARRIERS 3EXHAUST OR RETURN BRANCH DUCTWORK 4

GAS CONNECTION TO ROOFTOP AIR HANDLING UNIT DETAIL 5DUCTWORK SQUARE VANED ELBOWS 6DUCT PENETRATION THROUGH ROOF DETAIL 7

INSTALLATION OF THERMOMETER WELLS 8POWER ROOF VENTILATOR 9DUCTWORK RADIUS ELBOWS 10VOLUME DAMPER DETAIL 11

PIPE VENT AND DRAIN DETAILS 1

Revisions: Date:

M

M

CW

NPCW

2"

N P

C W

3"

FLOOR

NC

EXTEND DRAIN LINE

TO NEAREST FLOOR

DRAIN. TERMINATE

WITH AN AIR GAP.

ISOLATION

VALVE (TYP.)

4"

4"

4"

4"

2"

2"

N P

C W

2"

UNION

(TYP.)

NC

2" CHILLED

WATER MAKE-UP.

BY-PASS

3" TO TOWER WATER

RETURN MAIN.

PRESSURE

GAUGE

(TYP.)

REDUCED

PRESSURE

BACKFLOW

PREVENTER

PRESSURE

REDUCING VALVE.

SET TO 33 PSI

DIGITAL MAKE-UP

WATER METER. WIRE

TO BAS (TYP.)

STRAINER W/

BLOWDOWN

(TYP.)

N P

C W

3" TO COOLING

TOWERS

3"

REFER TO

PLUMBING

PLANS FOR

CONTINUATION.

MAKE-UP FILL

CONTROL VALVE

PRESSURE

REDUCING VALVE.

SET TO 28 PSI

BY HC

BY PC

NOTES:

1. REFER TO PLUMBING DRAWINGS AND DIVISION 22 IN

SPECIFICATIONS FOR PIPE MATERIAL, INSULATION, VALVING,

METERS, ETC.

NOT TO SCALE

FLOOR

4" CONCRETE

EQUIPMENT PAD

EXPANSION TANK

DRAIN VALVE

SHUT-OFF VALVE

AIR VENT

FROM AIR

SEPARATOR PER DETAIL

#3 ON DWG M-504

TO PUMP SUCTION

CONNECT TO

SIDE OF MAIN

EXTEND TO FLOOR DRAIN

NOT TO SCALE

NOTES:

1. CONTRACTOR SHALL FILL AIR SIDE OF EXPANSION TANK TO MATCH MAKE-UP WATER

PRESSURE AT AIR SEPARATOR.

ROOF INSULATION

ROOF

2" x 2" WOOD NAILER - SCREW TO BASE SECTION

ACRYLIC CLAD THERMOPLASTIC COVER (COUNTER FLASHING)

GALV. STEEL PIPE CURB BASE SECTION

SEE PLAN VIEW DWG. FOR PIPE CURB SIZE

3# DENSITY CURB INSULATION

NOTES:

GRADUATED STEP BOOT WITH STAINLESS STEEL CLAMPS

1. ADEQUATE PIPE CURB AREA AND BOOT OPENINGS SHALL BE PROVIDED FOR

ELECTRICAL CONDUIT ROOF PENETRATIONS WHERE REQUIRED. MECHANICAL

CONTRACTOR SHALL COORDINATE LOCATIONS AND SIZES WITH ELECTRICAL

CONTRACTOR.

2. CURB SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR TO THE

GENERAL CONTRACTOR AT THE JOB SITE. THE GENERAL CONTRACTOR SHALL

INSTALL CURB AND INCORPORATE CURB INTO ROOFING SYSTEM.

NOT TO SCALE

PIPE CLAMP TACK WELDED TO SUPPORT ANGLE

3"x3"x1/4" ANGLES WELDED TO STRUCTURE

CAULK TOP OF BOOT WEATHERTIGHT

3. FOR PIPES REQUIRING INSULATION, INSULATION SHALL BE CONTINUOUS

THROUGH PENETRATION.

HIGH LEVEL ALARM AT TOWER OVERFLOW

LOW LEVEL ALARM AT 2" BELOW TOWER OPERATING LEVEL

NOTES:

1. STANDPIPE SHALL BE 6"∅.

2. CAP SHALL ANCHOR SENSORS, PROVIDE WATERTIGHT CONNECTION TO CONTROL WIRES, AND BE VENTED.

3. FIELD SET THE LEVEL OF EACH OF THE SENSORS AND VERIFY WITH MEASURED WATER LEVELS IN THE TOWER

BASINS.

CONNECT TO BAS AND MAKE-UP WATER CONTROL VALVE

REMOVABLE VENTED CAP

CLOSE MAKE-UP WATER VALVE AT 2"

ABOVE TOWER OPERATION LEVEL

OPEN MAKE-UP VALVE AT 1"

BELOW TOWER OPERATING LEVEL

14" EQUALIZER PIPE

NOT TO SCALE

6" STANDPIPE

SEE NOTE 2

INSULATION

PIPE

BANDS TO SECURE

INSULATION IN PLACE

INSULATION

PIPE

BANDS TO SECURE

INSULATION IN PLACE

METAL JACKET WITH

TOP LAP FACING DOWN

METAL JACKET WITH

TOP LAP FACING DOWN

RIVETS OR SCREWS AT

SEAMS (DO NOT

PENETRATE INSULATION)

METAL BAND OR

BELT INSTALLED

PER MFG'S

INSTRUCTIONS

MIN OF 1"

BETWEEN FIRST

BAND AND OVER-

LAPPING JOINT

NOTES:

1. LONGITUDINAL JACKETING SEAMS POSITIONED AT

3 OR 9 O'CLOCK ONLY WITH TOP LAP FACING

DOWN FOR WEATHER PROOFING.

2. OVERLAP JACKETING A MINIMUM OF 1-1/2".

3. INSTALL HEAT TRACE PER MANUFACTURER'S RECOMMENDATIONS.

NOT TO SCALE

DIFFERENTIAL PRESSURE

SENSOR WIRED TO BAS

S U

P P

L Y

P

IP

E

R E

T U

R N

P

IP

E

NOTES:

1. INSTALL WITHIN 24" OF COIL OR EQUIPMENT.

2. DO NOT INSTALL ANY PRESSURE REDUCING VALVES OR FITTINGS BETWEEN

PRESSURE TAPS AND EQUIPMENT.

3. FLOW CONVERSION SHALL BE BASED ON ACTUAL MANUFACTURER'S PROVIDED

FLOW-PRESSURE DROP CURVES. CONTRACTOR SHALL OBTAIN CURVES FROM

MANUFACTURER.

APPLY TO THE FOLLOWING

EQUIPMENT:

1. CHILLER EVAPORATOR

2. CHILLER CONDENSER

PETE'S PLUGS (TYP.)

S

NOT TO SCALE

DRAW THRU

2" [51mm]

PLUS Y

Y

UNIT TYPE A B

WHERE X = STATIC PRESSURE IN PAN

WHERE Y = NEGATIVE STATIC PRESSURE IN

PAN

DRAIN LINE SHALL BE AT LEAST THE SAME SIZE

AS THE NIPPLE ON THE DRAIN PAN. CONDENSATE

DRAIN PIPE SHALL BE COPPER,TYPE L.

PITCH DOWN

TOWARD DRAIN

CLEAN OUT

ROOF DRAIN

DRAIN

PAN

DESIGNER'S NOTE:

A B

BLOW THRU

1" [25mm]

MINIMUM

2X

NOT TO SCALE NOT TO SCALE

NOTES:

1. CHILLED WATER COIL SHALL BE PIPED IN COUNTER FLOW ARRANGEMENT. CHILLED WATER SHALL FLOW IN OPPOSITE DIRECTION OF AIRFLOW (CHILLED WATER SUPPLY SHALL BE CONNECTED AT AIR DISCHARGE SIDE OF

COIL, WITH CHILLED WATER RETURN CONNECTED TO AIR INLET SIDE OF COIL).

WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST 2 HANGERS FOR EACH PIPE SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR 4"Ø PIPE & SMALLER. TYPE "H-P" FOR 5"Ø PIPE & LARGER.

PIPING SHALL BE INSTALLED IN SUCH A MANNER THAT IT WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE SERVICING OF FILTERS, VALVES, EQUIPMENT, OR COIL REMOVAL.

UNLESS SPECIFICALLY NOTED, SHUT-OFF VALVES INDICATED SHALL BE GATE, BUTTERFLY, OR BALL VALVES.

REFER TO MECHANICAL SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

T

T

STRAINER WITH BLOWDOWN

(TYP.)

THERMOMETER IN PIPE WELL

(TYP.)

CHILLED WATER RETURN TEMPERATURE

SENSOR TO BE TIE INTO B.A.S.

CHILLED WATER SUPPLY TEMPERATURE

SENSOR TO BE TIE INTO B.A.S.

CROSS-SECTIONAL AREA OF

COMBINED BRANCH PIPING

SHALL EQUAL OR EXCEED

CROSS-SECTIONAL AREA OF

MAINS SERVING BRANCH

PIPING AND VELOCITY THRU

BRANCH PIPING SHALL NOT

EXCEED 6 FPS [1.8 M/S]

AIR VENT

WHEN COIL

IS NOT

SELF-VENTING

TEST PLUG

(TYP.)

PIPE HANGER SHALL SUPPORT

PIPING INDEPENDENT OF COIL

REDUCER, IF

REQUIRED

DRAIN WHEN COIL IS

NOT SELF-DRAINING

DRAIN

CHWR

CHWS

CHILLED

WATER COIL

CHILLED

WATER COIL

CONCRETE

(TYPICAL)

VIBRATION ISOLATOR

1" (25 MM) MIN. DIA.

DRAIN

1/2" (15 MM)

1/2" (15 MM)

FLEXIBLE CONNECTOR

(TYPICAL)

HANGER

RIGID PIPE

HANGER

RIGID PIPE

TO PIPE ELBOW AS

POSSIBLE (TYPICAL)

INSTALL HANGER AS CLOSE

FLOOR

PUMP WITH BUILT-IN

SUCTION DIFFUSER

PRESSURE GAGE

STRAINER

PIPE STAND

INERTIA BASE

(SHUT-OFF/BALANCE) VALVE

CHECK VALVE

FIRST 3 HANGERS FOR EACH PIPE AND

BRANCH SHALL BE SPRING & NEOPRENE

TYPE. TYPE "H" FOR 4" (100 MM) DIA. PIPE

& SMALLER. TYPE "H-P" FOR 5" (125 MM)

DIA. PIPE & LARGER.

NOT TO SCALE

DRIVEN

EQUIPMENT

MOTORTYPICAL STRUCTURAL

STEEL MEMBER FOR

EQUIPMENT

TYPE"B"

WELDED STEEL BASE

TYPE "1"

CONCRETE INERTIA BASE

NUMBER OF ISOLATION

UNITS AS REQUIRED

NUMBER OF

ISOLATION

UNITS AS REQUIRED

TYPICAL

STRUCTURAL

STEEL MEMBER FOR

EQUIPMENT

ALL WELDED

STEEL

FRAMEWORK

SECTION A-A

STRUCTURAL

STEEL FRAME

SPRING

ISOLATOR

ANCHOR

BOLT

REINFORCING BARS

SLEEVE

A

SHAFT

MOTORSHAFT

DRIVEN

EQUIPMENT

A

NOT TO SCALE

74490

L.D. HENDRIX, JR

GN

S S

A

ION EL

T

F EGE

P R O

R

SI NRE I

E E R

D

E

AT

S

ET

O

OI

HO

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

20045

C R e v it L o c a l F ile s \2

F

F H

C F

R

C h ri s to p h e r.

P

.C a m p b e ll.

rv t

/6 /2

:5

:3

P M

M-502

MECHANICAL DETAILS CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 LDH CAB

BID & CONSTRUCTION

18902.00

MAKE-UP FILL LINE STATION DETAIL 5

CHILLED WATER EXPANSION TANK DETAIL 1PIPE ROOF CURB PENETRATION DETAIL 2

REMOTE WATER LEVEL SENSOR STANDPIPE DETAIL 4FIELD APPLIED METAL JACKETING OVER PIPE INSULATION 6

DIFFERENTIAL PRESSURE SENSOR DETAIL 7AIR HANDLING UNIT DRAIN TRAP DETAIL 9 CHILLED WATER COOLING COIL DETAIL 8

TYPICAL PIPING CONNECTIONS TO FLOOR MOUNTED SINGLE SUCTION WATER PUMPS 3

VIBRATION ISOLATION BASES DETAIL 10

Revisions: Date:

5 FT

THRU [20]

6 8 10

[32][25] [40]

[65]

[50]

[75]

-1312 14 -16 -

[125][100]

[150]

[250]

[200]

[300]

[400]

[350]

[450]

[600]

[500]

20 241814 16128 1064 532 2 1/21 1/21 1 1/4

[9100] [9600][8500][7600] [8200][7000][5800] [6700][5200][4100] [4900][3700][3000] [3400][2700][2100]

--- --[4900] -[4100][3700] [4000] -[3000][2400][1800][1500]

THRU 3/4

[2100] [2100]

[2100]

[2700]

[2400]

SIDE VIEW TRAPEZE HANGER FOR UP TO

1000 LB. [453KG] UNIFORM LOAD

ADJUSTABLE CLEVIS HANGER

TYPE 1 - SEE SPECIFICATIONS

ADJUSTABLE CLEVIS HANGER

TYPE 43 - SEE SPECIFICATIONS

PROVIDE INSULATION SHIELD

& INSERT FOR ALL PIPING

(8" [200mm] MIN.)

BAND

1-5/8" [43mm] 12 GAUGE CHANNEL OR 2"x2"x1/4" [50x50x6.4mm] ANGLE

1/2" [15mm] DIA.

HANGER RODS WITH

36" [900mm] MAX.

SPACING ON EACH

CHANNEL

WELD

SADDLE

INSULATION SHIELD

AT HANGER

PROVIDE HIGH COMPRESSIVE

STRENGTH INSULATION (9

PSF MIN. DENSITY) UNDER

INSULATION SHIELD

INSULATION (VAPOR

BARRIER TYPE IS

REQUIRED FOR LOW

TEMPERATURE PIPE)

HANGER ROD

MAXIMUM PIPE/TUBING SUPPORT SPACING

NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.

NOM. SIZE

PIPE

TUBING

IN.

[mm]

FT.

[mm]

FT.

[mm]

[2 m m

M A

X

NOTES:

SEE SPECIFICATIONS FOR

DETAILED HANGER

REQUIREMENTS

NOT TO SCALE

1/4 3/8 1/21/2 1/2 3/45/8 7/8 11 1 1/4 1 1/21 1/4

[32] [40][32][25] [25][22][16] [19][13][13] [13][7] [7] [10]ROD SIZE

FT.

[mm] 3/83/83/83/81/4

[10] [10] [10] [10]

M

T W

R

3/4"

SHUTOFF

VALVE

FLOOR

A F

F

DIGITAL WATER METER.

WIRE TO CHEMICAL

TREATMENT CONTROLLER

CHECK VALVE

TOWER WATER

RETURN MAIN

2-WAY CONTROL VALVE

INTERLOCKED WITH CHEMICAL

TREATMENT SYSTEM

GLOBE VALVE

SPILL 3/4" DRAIN LINE TO

LOCAL FLOOR DRAIN

NOT TO SCALE

1/4" (7 MM) DRAIN VALVE

ADAPTER TO 7 MM (1/4") THREAD.

PROVIDE CAP NUT

CHILLER

PURGE DISCHARGE

RUPTURE DISC OR VENT

(BY CHILLER MANUFACTURER)

REDUCER

FULL SIZE 24" DRIP LEG

TEE

VENT LINE. MATERIAL AND SIZE

PER MANUFACTURER.

PURGE DISCHARGE

VENT LINE

FLEXIBLE STAINLESS

STEEL CONNECTION

GOOSENECK 24" ABOVE ROOF

PROVIDE ROOF PENETRATION

CURB AND RUBBER BOOT

ROOF

FLANGED JOINT OR UNION TO

PERMIT PIPING DISASSEMBLY

FOR BURSTING DISC OR VENT

PIPING.

NOTES:

1. SUPPORT VENT PIPING INDEPENDENT OF CHILLER.

2. RELIEF VENT SIZE PER MANUFACTURERS RECOMMENDATIONS.

3. TACK WELD STAINLESS STEEL BIRD SCREEN ON OUTDOOR

OPENING.

4. WHERE CHILLER REQUIRES MULTIPLE VENTS, PIPE EACH VENT

INDEPENDENTLY. DO NOT CONNECT VENTS.

NOT TO SCALE

T W

SCONDUCTIVITY PROBE

INTERLOCKED WITH

CHEMICAL TREATMENT

CONTROL PANEL

T W

R

3/4"

3/4"

SHUTOFF

VALVE (TYP.)

GLOBE VALVE

FLOW

SWITCH

FLOOR

A F

F

SIDE TAKEOFF

NOT TO SCALE

STORAGE TANK NO. 1

CHILLED WATER SCALE

AND CORROSION INHIBITOR

STORAGE TANK NO. 2

TOWER BIOCIDE

STORAGE TANK NO. 3

TOWER SCALE AND

CORROSION INHIBITOR

CHEMICAL

FEED

CONTROLLER

CHEMICAL

FEED

PUMP

NO. 1

CHEMICAL

FEED

PUMP

NO. 2

CHEMICAL

FEED

PUMP

NO. 3

HSHSHS

C H

IL

L E

D W

A T

E R

R E

T U

R N

H

E A

D E

R

RELIEF BYPASS

VALVE TYP.

FLOOR

SINK

MODULATING

CONTROL VALVE

TOWER

MAKE UP

METER

PH AND

CONDUCTIVITY

TRANSMITTER

(DETAIL #3 THIS

DRAWING)

LC

BLOW DOWN

VALVE (DETAIL #5

THIS DRAWING)

CHILLER CONDENSERS

TYP.

TOWERTOWERTOWER

SAMPLE

WATER

LEVEL

METER

TOWER

WATER

PUMPS

TYP.

SIDE STREAM

FILTER WITH PUMP

TOWER WATER

SUPPLY

(FROM TOWER)

TOWER WATER

RETURN

(TO TOWER)

NOTES:

1. PROVIDE CORPORATION STOP INJECTORS FOR EACH CHEMICAL

TREATMENT FEED LOCATION.

2. ALL INJECTOR POINTS TO RETURN HEADERS SHALL BE 1-INCH

WELD-O-LETS WITH FULL PORT BALL VALVES. TAP LOCATIONS SHALL BE

ORIENTED NO MORE THAN 45 DEGREES ABOVE OR BELOW HORIZONTAL

RUN OF THE HEADER.

3. PROVIDE BACNET INTERFACE BETWEEN CHEMICAL FEED CONTROLLER AND

TC ECC.

4. CHILLED WATER TREATMENT SYSTEM SHALL BE OPERATED MANUALLY.

5. ADDITIONAL STORAGE TANKS AND FEED PUMPS MAY BE REQUIRED BASED

ON THE OUTCOME OF THE WATER SAMPLE ANALYSIS.

6. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

CORPORATION STOP

INJECTOR (TYP.)

STORAGE TANK NO. 4

TOWER OXIDIZING

BIOCIDE

CHEMICAL

FEED

PUMP

NO. 4

HS

M

M

PROVIDE MINIMUM DISTANCE BETWEEN EACH INJECTION QUILL PER

MANUFACTURER'S REQUIREMENTS.

PROVIDE DUCKBILL CHECK AT EACH CHEM TREATMENT POINT IN

TOWER WATER SYSTEM.

7.

8.

NOT TO SCALE

TOWER

MAKE-UP WATER

CONTROL VALVE

(TYPICAL)

74490

L.D. HENDRIX, JR

GN

S S

A

ION EL

T

F EGE

P R O

R

SI NRE I

E E R

D

E

AT

S

ET

O

OI

HO

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

20045

C R e v it L o c a l F ile s \2

F

F H

C F

R

C h ri s to p h e r.

P

.C a m p b e ll.

rv t

/6 /2

:5

:3

P M

M-503

MECHANICAL DETAILS CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 LDH CAB

BID & CONSTRUCTION

18902.00

PIPE HANGERS DETAIL 2

TOWER WATER BLOWDOWN DETAIL 5 REFRIGERANT RELIEF VENT PIPE DETAIL 4 CONDUCTIVITY MONITORING ASSEMBLY 3

WATER TREATMENT SYSTEM DIAGRAM 1

Revisions: Date:

NOT TO SCALE

* BY ROOFING

SUB-CONTRACTOR

WOOD BLOCKING

ALUMINUM FLASHING

ROOF MEMBRANE *

FIBER CANT. *

ROOF INSULATION *

ROOF DECK

BOLT CURB

TO DECK

18"Ø PIPE W/

INSULATION AND

ALUMINUM JACKET

(TYP)

(68" MINIMUM)

1-1/2"Ø GALVANIZED

THREADED ROD

(TYP)

HOT-DIP GALVANIZED ROLLER

(TYP)

GALVANIZED AXLE

(TYP)

H

IG

H

C U

R B

28-7/8" (TYP)

(T

Y P

GALVANIZED FASTENER

(TYP)

WELD TO PIPE

(TYP)

SADDLE

(TYP)

NOT TO SCALE

BELL & GOSSETT AUTOMATIC AIR

VENT MODEL 107A OR EQUAL. PIPE

DISCHARGE TO FLOOR DRAIN

3/4"Ø

2"Ø

1"Ø

ISOLATION VALVE (TYP.)

PIPE TO FLOOR DRAIN

2"Ø

TO SUCTION SIDE OF PUMPSCHILLED WATER RETURN

EXPANSION TANK CONNECTION

PER DETAIL #1 ON DWG M-502

NPCW

MAKE-UP WATER PER

DETAIL #5 ON DWG M-502

AIR SEPARATOR

(AS-1)

ROOF INSULATION

ROOF

2" x 2" WOOD NAILER - SCREW TO BASE SECTION

ACRYLIC CLAD THERMOPLASTIC COVER

(COUNTER FLASHING)

GALV. STEEL PIPE CURB BASE SECTION

SEE PLAN VIEW DWG. FOR PIPE CURB SIZE

R-20 CURB INSULATION

NOTES:

6" WIDE NEOPRENE STRIP GLUED AT LAP,

CLAMPED AT PIPE & COLLAR

1. CURB SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR TO THE GENERAL

CONTRACTOR AT THE JOB SITE. THE GENERAL CONTRACTOR SHALL INSTALL CURB AND

INCORPORATE CURB INTO ROOFING SYSTEM.

NOT TO SCALE

PIPE CLAMP TACK WELDED TO SUPPORT ANGLE

3"x3"x1/4" ANGLES WELDED TO STRUCTURE

FIELD-FABRICATED 18 GA

GALVANIZED STEEL COVER

ON 4 SIDES AND TOP.

SECURE TO WOOD

BLOCKING OF CURB.

SLOPE ENCLOSURE 1" PER

FOOT FOR DRAINAGE

FASTEN GALVANIZED

STEEL ENCLOSURE

AND THERMOPLASTIC

COVER TO WOOD

NAILER AT 8" O.C.

PROVIDE ESCUTCHEON

AND SEAL WATERTIGHT

INSTALLATION SPECIFICATION:

A. INSTALL ELECTRIC HEATING CABLE ACROSS EXPANSION JOINTS ACCORDING TO MANUFACTURER'S WRITTEN

INSTRUCTIONS; USE SLACK CABLE TO ALLOW MOVEMENT WITHOUT DAMAGE TO CABLE.

B. INSTALL ELECTRIC HEATING CABLES AFTER PIPING HAS BEEN TESTED AND BEFORE INSULATION IS INSTALLED.

C. INSTALL ELECTRIC HEATING CABLES ACCORDING TO IEEE 515.1.

D. INSTALL INSULATION OVER PIPING WITH ELECTRIC CABLES ACCORDING TO SECTION 23 07 11 "HVAC PIPING

INSULATION."

E. INSTALL ALONG LONG RADIUS OF ALL ELBOWS.

F. INSTALL WARNING TAPE ON PIPING INSULATION WHERE PIPING IS EQUIPPED WITH ELECTRIC HEATING CABLES.

G. SET FIELD-ADJUSTABLE SWITCHES AND CIRCUIT-BREAKER TRIP RANGES.

PIPE

INSULATION BY MC AFTER HEAT

TRACE IS INSTALLED - CONTACT

ENGINEER / HEAT TRACE REP PRIOR

TO INSULATING. SUBMIT A SIGNED

INSTALLATION INSPECTION

REPORT.

HEAT TRACE BY MECHANICAL

CONTRACTOR - INSTALL AT

EITHER 7 O'CLOCK OR 5

O'CLOCK ON THE PIPE

SURFACE.

PIPE HEAT TRACE NOTES

NOT TO SCALE

HEAT TRACE PANEL #

HEAT TRACE PANEL #1

HEAT TRACE

CIRCUIT

1-A

CABLE POWER

(WATTS / FT)

PIPING SERVED

18"Ø CHWS

APPROX. PIPING

LENGTH (FT)

1-B 10 18"Ø CHWR 240

2-A 10 220

2-B 10 220

3-A 8 12"Ø TWR 25

12"Ø TWS 12

2"Ø NPCW 12

HEAT TRACE PANEL #2 18"Ø CHWS

18"Ø CHWR

PIPE SURFACE

TEMP. (°F)

HEAT TRACE PANEL #3

3-B 8 12"Ø TWR 25

12"Ø TWS 12

2"Ø NPCW 12

4-A 8 12"Ø TWR 25

12"Ø TWS 12

2"Ø NPCW 12

HEAT TRACE PANEL #4

4-B 8 12"Ø TWR 25

12"Ø TWS 12

2"Ø NPCW 12

5-A 5 (NOTE 2) 160

5 80

HEAT TRACE PANEL #5 14"Ø TWS

8"Ø TWS

5-B 8 1208"Ø TWS 40

CONTRACTOR SHALL PROVIDE A COMPLETE PIPE HEAT TRACE SYSTEM FOR ALL DESIGNATED PIPING AS SHOWN ON MECHANICAL DRAWINGS AND IN HEAT TRACE TABLE (THIS SHEET). CHILLED WATER, TOWER WATER, EQUALIZER PIPING, AND NPCW HEAT TRACE SYSTEMS SHALL BE A SELF REGULATING HEAT TRACE CABLE. EACH CIRCUIT SHALL BE CONNECTED TO A 20A-1P BREAKER (SEE ELECTRICAL DRAWINGS). HEAT TRACE CABLE SHALL PREVENT FREEZING OF PIPES DOWN TO A MINIMUM AMBIENT TEMPERATURE OF -20°F. ALL CABLE SHALL BE RATED AT 277V. CHILLED WATER, TOWER WATER, EQUALIZER, AND NPCW CABLE SHALL BE CONTROLLED BY AN EXTERIOR THERMOSTAT WITH A 40°F ACTIVATION TEMPERATURE. CONTROL PANEL SHALL HAVE INTEGRAL GROUND FAULT EQUIPMENT PROTECTION FOR HEAT TRACE CIRCUITS. INSTALL ALL HEAT TRACE CABLE IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION

INSTRUCTIONS. HEAT TRACE SHALL BE TESTED AT THE FOLLOWING TIMES:

1. UPON RECEIPT OF HEAT TRACE COMPONENTS, PRIOR TO INSTALLATION.

2. UPON COMPLETION OF INSTALLATION ON PIPE, PRIOR TO INSULATION.

3. UPON COMPLETION OF PIPE INSULATION.

HEAT TRACE TABLE

THE FOLLOWING IS PROVIDED AS GENERAL GUIDELINES, CONTRACTOR SHALL ALSO REFER TO

MANUFACTURER'S INSTALLATION REQUIREMENTS.

1. INSTALL HEAT TRACE CABLE AT EITHER 8 O'CLOCK OR 4 O'CLOCK ON THE PIPE SURFACE.

2. FOR PIPE ELBOWS INSTALL HEAT TRACE CABLE ON THE OUTER RADIUS.

3. AT PIPE COUPLINGS, HEAT TRACE CABLE SHALL BE INSTALLED BENEATH THE COUPLING BOLT AND

SHALL NOT BE INSTALLED ON THE OUTSIDE OF PIPE COUPLING BOLT.

4. HEAT TRACE CABLE SHALL BE SECURED TO PIPING AND FITTINGS WITH HIGH TEMPERATURE ADHESIVE TAPE TO ENSURE HEAT TRACE CABLE IS IN CONTINUOUS CONTACT WITH PIPING AND

FITTINGS.

5. CONTRACTOR SHALL TEST HEAT TRACE PRIOR TO FILLING EACH SYSTEM.

6. CONTRACTOR SHALL WORK WITH VA COR TO SCHEDULE INSPECTION OF HEAT TRACE

CABLE INSTALLATION WITH ENGINEER AND MANUFACTURER'S REPRESENTATIVE. ALL HEAT

TRACE SHALL BE INSPECTED DURING ONE SITE VISIT.

PIPE COUPLING

HEAT TRACE CABLE

HEAT TRACE CABLE

PIPE ELBOW

HEAT TRACE

CABLE

PIPE

NOTE 1 NOTE 2 NOTE 3

PIPE

NOTES:

1.

2.

3.

CONTRACTOR SHALL VERIFY FINAL HEAT TRACE LENGTHS AND PIPE SIZES AS PART OF COORDINATION PROCESS.

PIPING SHALL BE DOUBLE-TRACED.

PROVIDE BACNET COMPATIBLE CONTROL CARD WITH ALARMS TO BAS. REFER TO SPECIFICATIONS FOR MORE

INFORMATION AND ALARM POINTS.

74490

L.D. HENDRIX, JR

GN

S S

A

ION EL

T

F EGE

P R O

R

SI NRE I

E E R

D

E

AT

S

ET

O

OI

HO

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

20045

C R e v it L o c a l F ile s \2

F

F H

C F

R

C h ri s to p h e r.

P

.C a m p b e ll.

rv t

/6 /2

:5

:4

P M

M-504

MECHANICAL DETAILS CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 LDH CAB

BID & CONSTRUCTION

18902.00

ROOFTOP CHILLED WATER PIPE SUPPORT DETAIL 2

AIR SEPARATOR DETAIL 3CHILLED WATER AND TOWER WATER PIPE ROOF CURB PENETRATION DETAIL 4

HEAT TRACE DETAIL 1

Revisions: Date:

74490

L.D. HENDRIX, JR

GN

S S

A

ION EL

T

F EGE

P R O

R

SI NRE I

E E R

D

E

AT

S

ET

O

OI

HO

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

20045

C R e v it L o c a l F ile s \2

F

F H

C F

R

C h ri s to p h e r.

P

.C a m p b e ll.

rv t

/6 /2

:5

:4

P M

M-601

MECHANICAL SCHEDULES CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 LDH CAB

BID & CONSTRUCTION

18902.00

MARK

SERVICE

TYPE

CAPACITY

TANK VOLUME (GAL.)

PHYSICAL SIZE

ET-1

VERT. BLADDER

370.0

36"∅ X 98"T

NOTES:

1. MOUNT ON 4" THICK CONCRETE HOUSEKEEPING PAD.

2. ASME RATED FOR MAXIMUM 150 PSI ASME RATING

PRESSURE.

3. ACCEPTABLE MANUFACTURERS INCLUDE BELL &

GOSSETT, TACO, OR APPROVED EQUAL.

MARK

SERVICE

CAPACITY

INLET/OUTLET SIZE

AS-1

20"

NOTES:

1. COALESCING REMOVAL AIR AND DIRT SEPARATOR.

2. REFER TO SPECIFICATION 23 21 13 FOR ADDITIONAL

INFORMATION.

3. INSTALL AT HEIGHT TO PERMIT REMOVAL OF COALESCING

MEDIUM. REFER TO MANUFACTURER'S RECOMMENDATIONS.

SYSTEM WATER FLOW (GPM)

0.81HEAD LOSS (FT)

AIR FILL PRESSURE (PSI) 33.0

MAX. DESIGN TEMPERATURE (°F) 95

ACCEPTANCE VOLUME (GALLONS) 338.9

CHILLED

WATER

CHILLED

WATER

ELECTRICAL

FLOW (GPM)

ENTERING WATER TEMP. (DEG. F.)

VOLTS-PHASE-HERTZ

ACCESSORIES

TONS OUTPUT

FOULING FACTOR

MAX WPD (FT)

MCA

NOTES:

1.

2.

3.

4.

5.

6.

REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

CHILLER SHALL BE MOUNTED ON 6-INCH THICK CONCRETE PAD. REFER TO STRUCTURAL DRAWINGS.

CONTRACTOR TO PRESSURE TEST AND TOP-OFF REFRIGERANT AS PART OF CHILLER START-UP.

ALL COLD SURFACES SHALL BE INSULATED WITH 3/4" CLOSED CELL ELASTOMERIC FOAM INSULATION INCLUDING THE EVAPORATOR, WATER

BOXES, AND SUCTION ELBOW.

REVIEW FLOOR PLANS AND DETAILS FOR COORDINATION OF FINAL CHILLER/PIPING CONFIGURATION.

PROJECT DRAWINGS SHOW BASIS-OF-DESIGN EQUIPMENT WEIGHT, DIMENSIONS, AND GENERAL CONNECTION ARRANGEMENT. ANY DEVIATION FROM BASIS OF DESIGN EQUIPMENT REQUIRING ADDITIONAL WORK AND/OR COORDINATION SHALL BE THE RESPONSIBILITY OF THE

CONTRACTOR AND SHALL BE COMPLETED AT NO COST TO THE VA.

MARK

SINGLE POINT ELECTRICAL CONNECTION

FACTORY AUTHORIZED STARTUP

VIBRATION ISOLATORS

TYPE

UL LISTED

BUILDING CONTROLS NETWORK INTERFACE

WATER FLOW SWITCH

PRIMARY EFFICIENCY (KW PER TON)

NPLV (KW PER TON)

EVAPORATOR

LEAVING WATER TEMP. (DEG. F.)

FLOW (GPM)

ENTERING WATER TEMP. (DEG. F.)

CONDENSER

MAX WPD (FT)

LEAVING WATER TEMP. (DEG. F.)

MOCP

PROPYLENE GLYCOL (%)

MEDIA

REFRIGERANT TYPE

REFRIGERANT CHARGE (LBS.)

NO. OF PASSES

FOULING FACTOR

UNIT MOUNTED VARIABLE FREQUENCY DRIVE

NO. OF PASSES

EXPANSION TANK

AIR AND DIRT SEPARATOR

PUMPS WATER COOLED CHILLERSCOOLING TOWER

SIDE STREAM FILTER

54.0

0.00010

16.7

CH-1

460-3-60

36,940

YES

YES

YES

42.0

YES

YES

YES

CENTRIFUGAL

85.0

19.3

95.0

100% WATER

0.5989

0.3800

R-134a

0.00025

YES

MARK

SERVICE

TYPE

TEMPERATURE (°F)

FLUID

PERFORMANCE

FLOW (GPM)

TOTAL HEAD (FEET)

SPEED (RPM)

MOTOR

SIZE (HP)

VOLT-PHASE-HERTZ

P-1, P-2, P-3, P-4

CHILLED WATER

WATER

125.0

460-3-60

EFFICIENCY (%) 84.9

NOTES:

1. MOUNT PUMP ON CONCRETE INERTIA PAD.

2. PROVIDE INVERTER DUTY MOTORS RATED FOR USE WITH VARIABLE SPEED MOTOR CONTROLLER.

PROVIDE VSMC FOR PUMP.

3. PUMPS CASINGS SHALL BE CAPABLE OF ACCEPTING ONE LARGER IMPELLER SIZE.

NOTES 1,2,3

VARIABLE FREQUENCY DRIVE YES

END SUCTION

BASE

MOUNTED

TP-1, TP-2, TP-3, TP-4

CONDENSER WATER

WATER

75.0

460-3-60

79.2

1,2,3

YES

MARK

SERVICE

TYPE

PERFORMANCE

CT-1

CONDENSER WATER

ELECTRICAL DATA

NOTES:

1.

2.

3.

4.

5.

6.

7.

FURNISH MANUFACTURER'S REMOTE VARIABLE SPEED MOTOR CONTROLLERS (VSMC) FOR FANS. INSTALL WITHIN CHILLER ROOM. REFER TO FLOOR PLANS.

PROVIDE A FACTORY WIRED DISCONNECT WITHIN LINE OF SITE FOR EACH FAN. CONTRACTOR TO INSTALL VSMC AND WIRE FROM VSMC TO EACH FAN

DISCONNECT. VSMC'S SHALL BE PROVIDED WITH BYPASS.

PROVIDE FLANGED PIPE CONNECTIONS.

PROVIDE BASIN HEATERS WITH THERMOSTAT AND LOW WATER CUT-OFF. PROVIDE CONTACTOR, TRANSFORMER, AND DISCONNECT IN A NEMA 4

ENCLOSURE.

COOLING TOWERS CT-1/CT-2 AND CT-3/CT-4 SHALL BE TWINNED TOGETHER, EACH WITH INDEPENDENT CELL OPERATION.

PROVIDE SUMP SWEEPERS TO BE PIPED TO SSF-1.

ATTACH FAN PLATFORM LADDER TO COOLING TOWER FACE IN ORDER TO PREVENT OBSTRUCTING WALKING PLATFORM ACCESS.

PROJECT DRAWINGS SHOW BASIS-OF-DESIGN EQUIPMENT WEIGHT, DIMENSIONS, AND GENERAL CONNECTION ARRANGEMENT. ANY DEVIATION FROM BASIS OF DESIGN EQUIPMENT REQUIRING ADDITIONAL WORK AND/OR COORDINATION SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE

COMPLETED AT NO COST TO THE VA.

AIR COOLED

6.7

ENTERING WATER TEMPERATURE (°F) 95.0

LEAVING WATER TEMPERATURE (°F) 85.0

460/3/60

CAPACITY (TONS)

FLOW RATE (EACH CELL) (GPM)

PRESSURE DROP THROUGH TOWER (FT)

DIMENSIONAL DATA (BASIS OF DESIGN)

11'-9" x 20'-0" x 18'-6 1/2"LENGTH X WIDTH X HEIGHT

OPERATING WEIGHT (LBS)

VOLTS/PHASE/HERTZ

BASIN HEATER (KW)

ACCESSORIES

VIBRATION ISOLATORS

MANUFACTURER'S START-UP

CONTACTOR W/ TXR AND DISCONNECT FOR HEATERS

EXTERNAL SERVICE PLATFORM WITH LADDER

24,450

2 @ 15 KW EACH

YES

YES

YES

YES

ENTERING AIR WET BULB (°F) 78.0

LOUVER ACCESS DOOR YES

FAN HP 60.0

DAVIT TO HOIST FAN MOTORS YES

INVERTER CAPABLE, PREMIUM EFFICIENT MOTORS YES

FAN FAILURE CURRENT SENSING RELAYS YES

304 WELDED STAINLESS STEEL BASIN YES

END SUCTION

BASE

MOUNTED

BHP 84.9 60.8

MARK

SERVICE

TYPE

FLUID TEMPERATURE (°F)

FLUID

PERFORMANCE

FLOW (GPM)

VOLT-PHASE-HERTZ

SSF-1

CONDENSER WATER

WATER

480-3-60

WEIGHT (LBS) 3000

NOTES:

1. MOUNT SYSTEM ON 4-INCH THICK CONCRETE HOUSEKEEPING PAD.

2.

3.

4.

PRE-PACKAGED, SKID MOUNTED, SINGLE POINT ELECTRICAL

CONNECTION.

MAXIMUM OVERCURRENT PROTECTION 60

TURBO DISC

FILTER SYSTEM

MICRON RATING 50

VIBRATION CUT-OUT SWITCHES YES

304 STAINLESS STEEL UPPER YES

BACKFLUSH FLOW RATE (GPM) 90

5200MAXIMUM WATER FLOW (GPM)

CT-2

CONDENSER WATER

AIR COOLED

6.7

95.0

85.0

460/3/60

11'-9" x 20'-0" x 18'-6 1/2"

24,450

2 @ 15 KW EACH

YES

YES

YES

YES

78.0

YES

60.0

YES

YES

YES

YES

YES

YES

CT-3

CONDENSER WATER

AIR COOLED

6.7

95.0

85.0

460/3/60

11'-9" x 20'-0" x 18'-6 1/2"

24,450

2 @ 15 KW EACH

YES

YES

YES

YES

78.0

YES

60.0

YES

YES

YES

YES

YES

YES

CT-4

CONDENSER WATER

AIR COOLED

6.7

95.0

85.0

460/3/60

11'-9" x 20'-0" x 18'-6 1/2"

24,450

2 @ 15 KW EACH

YES

YES

YES

YES

78.0

YES

60.0

YES

YES

YES

YES

YES

YES

54.0

0.00010

16.7

CH-2

460-3-60

36,940

YES

YES

YES

42.0

YES

YES

YES

CENTRIFUGAL

85.0

19.3

95.0

100% WATER

0.5989

0.3800

R-134a

0.00025

YES

54.0

0.00010

16.7

CH-3

460-3-60

36,940

YES

YES

YES

42.0

YES

YES

YES

CENTRIFUGAL

85.0

19.3

95.0

100% WATER

0.5989

0.3800

R-134a

0.00025

YES

54.0

0.00010

16.7

CH-4

460-3-60

36,940

YES

YES

YES

42.0

YES

YES

YES

CENTRIFUGAL

85.0

19.3

95.0

100% WATER

0.5989

0.3800

R-134a

0.00025

YES

P-X CT-X CH-X

ET-X

AS-X

SSF-X

MINIMUM CIRCUIT AMPACITY 40

PIPE TWO (2) 2" BACKFLUSH LINES TO LOCAL TRENCH DRAIN.

FACTORY CONTROL PANEL, MOUNTED TO SKID. WIRE ALARMS TO BAS.

CHILLED WATER COOLING COIL

MARK

SERVICE

TYPE

NUMBER OF COILS IN BANK

FLUID

PERFORMANCE

TOTAL CAPACITY (MBH)

LEAVING AIR DB/WB (°F)

AIR PRESSURE DROP (IN. W.G.)

CC-1

X-RTU-15

100% WATER

973.4

50.1 / 49.8

0.92

DRY WEIGHT (LBS) 738.9

NOTES:

1.

2.

3.

4.

CHILLED WATER COIL SHALL BE INSTALLED IN EXISTING RTU-15.

COORDINATE COIL SELECTION WITH RTU MANUFACTURER TO ENSURE FIT.

EXISTING UNIT IS YORK MODEL #XTO-84x96.

FIELD VERIFY REMOVAL OF EXISTING DX COIL AND INSTALLATION OF NEW

COIL CHILLED WATER COIL PRIOR TO SUBMITTING COIL.

CONNECT CHILLED WATER COIL PER DETAIL.

UNLESS NOTED OTHERWISE, CAPACITIES AND VALUES SHOWN ABOVE

ARE BANK TOTALS.

TOTAL WATER FLOW (GPM) 161.2

SENSIBLE CAPACITY (MBH) 642.0

ENTERING AIR DB/WB (°F) 80.0 / 66.5

ENTERING WATER TEMPERATURE (°F) 42.0

LEAVING WATER TEMPERATURE (°F) 54.0

MAXIMUM WATER PRESSURE DROP (FEET) 9.5

MAXIMUM FACE VELOCITY (FPM) 521

NUMBER OF ROWS / FINS PER INCH 8 / 11

CHILLED WATER

COOLING COIL

AIRFLOW (CFM) 20,500

RTU MINIMUM OUTDOOR AIR SETTING (CFM) 5,125

COIL SIZE (FIN HEIGHT x FIN WIDTH) 35.0" x 81.0" (EACH)

TOTAL FIN AREA (SQ. FT.) 39.375

COIL ARRANGEMENT (# HIGH x # WIDE) 2 x 1

CC-X

MINIMUM PRESSURE RATING (PSI) 150 150 150 150

ANTI-CAVITATION PLATE YES YES YES YES

4. PROVIDE FLOOR STAND.

4. PROVIDE BLADDER-TYPE TANK.

DIMENSIONAL DATA (BASIS OF DESIGN)

LENGTH X WIDTH X HEIGHT

OPERATING WEIGHT (LBS.)

14'-0" 8'-3" x 8'-8"14'-0" 8'-3" x 8'-8"14'-0" 8'-3" x 8'-8"14'-0" 8'-3" x 8'-8"

Revisions: Date:

GN

S S

A

ION EL

T

F EGE

P R O

R

SI NRE I

E E R

D

E

AT

S

ET

O

OI

HO

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

20045

C R e v it L o c a l F ile s \2

F

F H

C F

R

C h ri s to p h e r.

P

.C a m p b e ll.

rv t

/6 /2

:5

:5

P M

M-602

MECHANICAL SCHEDULES CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 LDH CAB

BID & CONSTRUCTION

18902.00

NOTES:

1. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

2. MOUNT BOTTOM OF GRILLE AT 6" ABOVE FINISHED FLOOR. PAINT VISIBLE PORTION OF INSIDE DUCT FLAT BLACK.

MARK

STYLE

TYPE

AIR FLOW (CFM)

PERFORMANCE

STATIC PRESSURE (IN W.G.)

FAN SPEED (RPM)

NOISE LEVEL (SONES)

TYPE OF DRIVE

MOTOR

MOTOR SIZE (HP)

VOLTS-PHASE-HERTZ

GRAVITY BACKDRAFT DAMPER

ACCESSORIES

FACTORY DISCONNECT

NOTES

EF-1

UPBLAST

CENTRIFUGAL

11,500

0.75

BELT

3.0

460-3-60

YES

NO

1,2,3

ALUMINUM BIRDSCREEN YES

PAC-AHU-4

SUPPLY FAN

MARK

MINIMUM OUTDOOR AIR FLOW (CFM)

BRAKE HORSEPOWER

EXTERNAL STATIC PRESSURE (IN W.G.)

TOTAL CAPACITY (MBH)

SENSIBLE CAPACITY (MBH)

REFRIGERANT

NO. COMPRESSORS/TYPE

NO. CONDENSER FANS/DRIVE TYPE

DX COOLING

ENTERING AIR (DB/WB °F)

SUPPLY AIR FLOW (CFM)

OUTDOOR TEMPERATURE (° F)

VOLTS-PHASE-HERTZ

MINIMUM CIRCUIT AMPACITY

ELECTRICAL

MAX. OVERCURRENT PROTECTION (AMPS)

FEATURES OR ACCESSORIES

5 YEAR COMPRESSOR WARRANTY

FULL ECONOMIZER

PROGRAMMABLE THERMOSTAT

FACTORY UNIT MOUNTED, NON-FUSED DISCONNECT

NOTES:

1. SINGLE POINT POWER CONNECTION.

2. VARIABLE FREQUENCY DRIVE.

3. IAQ SLOPED, STAINLESS STEEL DRAIN PAN.

4. BUILT-IN RIGGING CAPABILITIES.

5. 304 STAINLESS STEEL HEAT EXCHANGER WITH 10-YEAR WARRANTY.

6. PROVIDE WITH TIME DELAY RELAY, ANTI-SHORT CYCLE TIMER, CONDENSER

COIL GUARD, HINGED SERVICE ACCESS DOORS.

7. CONDENSER FAN HEAD PRESSURE CONTROL.

8. SMOKE DETECTORS SHALL BE WIRED TO SHUT DOWN UNIT UPON DETECTION OF

SMOKE.

9. MOUNT AND ANCHOR ON MANUFACTURER'S ROOF CURB.

10. FILTER RESISTANCE (IN WG): CLEAN = 0.16, DIRTY = 0.50.

INPUT/OUTPUT (MBH)

HEATING SECTION (NATURAL GAS)

TYPE

2-INCH, 30% STANDARD SIZE THROWAWAY FILTERS

NO. OF STAGES

RPM

LEAVING AIR (DB/WB °F)

PRESSURE RANGE (IN. W.C.)

VERTICAL(BOTTOM)

RETURN AIR SMOKE DETECTOR

NO. SUPPLY FANS/DRIVE TYPE

SPRING ISOLATED FANS

MOTOR HORSEPOWER

AREA SERVED CHILLER

PLANT

EER/IEER

FULL PERIMETER ROOF CURB

OPERATING WEIGHT (LBS.)

BAROMETRIC PRESSURE RELIEF

BACNET COMMUNICATION

115V CONVENIENCE OUTLET, FACTORY WIRED

PACKAGED ROOFTOP UNITS

EXHAUST FANS

AIR DISTRIBUTION DEVICE (DIFFUSERS, REGISTERS AND GRILLES)

80.4 / 68.1

R-410A

4 / DIRECT

4 / SCROLL

307.0

11,500

475.62

460-3-60

YES

YESYES

YES

YES

2,500

800 / 648

YES

55.0 / 54.8

2.5" - 14"

YES

1 / BELT

YES

8.69

1.00

10.3/13.5

YES

CFMX

NECK

MARK TYPE

(INCHES)

FACE SIZE

COLORSTYLE MATERIAL NOTESFACTORY

DAMPER

(INCHES)

NECK SIZE

S1 26x20 - 124x18SUPPLY

GRILLE

DOUBLE DEFLECTION

SIDEWALL

WHITE STEEL

E1 36x36 - 1,234x34EXHAUST

GRILLE

SINGLE DEFLECTION

DUCT MOUNTED

WHITE STEEL

S2 20X14 - 118X12SUPPLY

GRILLE

DOUBLE DEFLECTION

SIDEWALL

WHITE STEEL

5,700

YES

YES

YES

NOTES:

1. INSTALL WITH MANUFACTURER'S ROOF CURB.

2. DISCONNECT BY EC.

3. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

EF-X

AHU-X

VARIABLE SPEED MOTOR CONTROLLER YES

LOCATION

FUEL OIL PUMP PACKAGE SCHEDULE

CIRCULATING FLUID

FLUID FUEL OIL

GPM

MOTOR (EACH)

NOMINAL

HP

1. BASIS OF SPECIFICATION: DUPLEX POSITIVE DISPLACEMENT PUMP PACKAGE WITH REDUNDANT PUMP CONTROLS.

2. REFER TO SPECIFICATIONS FOR REQUIRED ACCESSORIES.

3. PUMP MOTOR SHALL BE TEFC, INSULATION CLASS F, RATED FOR CONTINUOUS DUTY.

4. PROVIDE REDUNDANT CONTROLLER, INCLUDES CONTACTS, PLC AND BACNET INTERFACE FOR TRANSMISSION OF PUMP RUN SIGNALS AND ALARM INDICATIONS. TRANSFER LOGIC OPERATION SHALL TRANSFER

PUMP OPERATION WHEN NO FUEL FLOW IS SENSED VIA A REMOTE FLOW SWITCH AND THE EMERGENCY GENERATOR SET IS RUNNING.

5. PROVIDE DUAL POWER INLET, 460V-3Ø-60Hz, WITH POWER TRANSFER RELAY AND POWER AVAILABLE/CONNECTED/FAIL INDICATORS AND AUTOMATIC SWITCH OVER.

6. PROVIDE PUMP STARTERS FOR EACH PUMP. NEMA 4 ENCLOSED, UNIT MOUNTED, HINGE-OPEN FRONT DOOR, FULL-VOLTAGE, 3-PHASE CIRCUIT BREAKER COMBINATION MOTOR STARTER, WITH CONTROL POWER

TRANSFORMER, HOA SWITCH, RUN INDICATOR, POWER AVAILABLE INDICATOR.

7. ALL ALARMS SHALL BE COMMUNICATED WITH THE BAS VIA MODBUS COMMUNICATION.

8. THE CONTROL PANEL WILL SHOW THE FOLLOWING ALARMS ON THE LCD DISPLAY:

A. PUMP 1 NOT IN AUTO

B. PUMP 2 NOT IN AUTO

C. PUMP FLOW FAILURE

D. PUMP THERMAL OVERLOAD TRIP

E. PUMP SET LEAK

F. PUMP SET DIRTY STRAINER

G. EMERGENCY STOP ACTIVATED

H. PLC-A FAILURE

I. PLC-B FAILURE

9. THE AUDIBLE ALARM SHALL TRIP WHEN ANY OF THE FOLLOWING ALARMS ARE PRESENT:

A. PUMP FLOW FAILURE

B. PUMP THERMAL OVERLOAD TRIP

C. PUMP SET LEAK

D. EMERGENCY STOP ACTIVATED

SYSTEM TEMP.

°F (°C)

CHILLER

PLANT

(EC-114)

FTP-1

MARK

TYPE

HIGH LIFT IMO

3-SCREW

VOLTAGE

PHASE

460-3 3.450 80(27)

NO. 2

FUEL OIL

DISCHARGE

PRESSURE

(PSI)

EMERGENCY

GENERATORS

TYPE

DUPLEX POSITIVE

DISPLACEMENT

RPM

FULL LOAD

AMPS

PUMP BODY

CAST IRON

11. EQUIPMENT NUMBERING SHOWN IS FOR REFERENCE ONLY. COORDINATE FINAL

EQUIPMENT NUMBERING WITH VA COR DURING CONSTRUCTION.

ELECTRICAL

DIGITAL DISPLAY

ACCURACY

VOLTS-PHASE-HERTZ

FEATURES OR ACCESSORIES

TYPE M TRANSDUCER

BACNET IP - BUILDING CONTROLS NETWORK INTERFACE CARD

CLAMP ON TEMPERATURE SENSORS WITH MOUNTING KIT

PERMALOK TRACK TRANSDUCER MOUNTING SYSTEM

NOTES:

1.

2.

3.

4.

5.

6.

7.

PROVIDE FLOWMETER WITH SINGLE POINT POWER CONNECTION.

PROVIDE FACTORY REPRESENTATIVE TO UTILIZE PORTABLE FLOW METERS TO TEST

THE FLOW METER LOCATIONS TO DETERMINE THE OPTIMAL LOCATION.

PROVIDE FACTORY REPRESENTATIVE TO COMMISSION METERS.

PROVIDE ALL NECESSARY COMMUNICATION CARDS, FITTINGS, BRACKETS, JUNCTION

BOXES, CONDUIT, AND WIRE HARNESSES REQUIRED TO MOUNT AND CONNECT FLOW

METERS TO EXISTING TRANE CONTROL SYSTEM.

MINIMIZE INSULATION REMOVAL AND REPAIR ALL INSULATION ON…