18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-8.pdf
PDF 10 MB Posted
- Solicitation number
- 36C25023B0049
About this file
This file summary describes a federal contract solicitation for construction services. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 to construct a chiller plant at the Columbus VA Medical Center in Columbus, Ohio. The solicitation number is 36C25023B0049 and it is set aside exclusively for service-disabled veteran-owned small businesses. Responses are due on an unspecified date. The solicitation seeks a contractor to perform construction work related to installing a new chiller plant as described in the related technical drawings and specifications file.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
E
E
F
F
G
G
H
H
J
J
K
K
3.8
0.7
X -R
T U
-1
X-ACH-1
X-ACH-2
X-RTU-9
X -R
T U
-6
PENTHOUSE
HEAT TRACE PANEL 1
HEAT TRACE PANEL 2
HEAT TRACE CIRCUIT 1-A
HEAT TRACE CIRCUIT 1-B
HEAT TRACE CIRCUIT 2-B
HEAT TRACE CIRCUIT 2-A
18"ø CHWS
18"ø CHWR
M -1
A
M -1
B
M -1
A
M -1
B
(TYP.)
M-153AM-153B
M-153C
74490
L.D. HENDRIX, JR
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:5
:3
P M
M-153B
ACC THIRD FLOOR / ROOF HVAC PIPING PLAN CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 LDH CAB
BID & CONSTRUCTION
18902.00 1
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
ACC THIRD FLOOR/ROOF HVAC PIPING PLAN 1
CODED NOTES
18"Ø CHWS AND CHWR PIPING DOWN THROUGH ROOF INTO 2ND FLOOR CEILING SPACE BELOW. SEE "ACC SECOND FLOOR PIPING PLAN - AREA A" DWG M-152 FOR CONTINUATION. PROVIDE PIPE PENETRATION CURB
PER DETAIL #4 DWG M-504.
REFER TO DWG M-153A FOR CONTINUATION.
PIPING SUPPORTS AS INDICATED. FINAL LOCATIONS SHALL BE COORDINATED WITH STRUCTURAL DRAWINGS AND FIELD VERIFIED. REFER TO DETAIL #2 DRAWING M-504 FOR MORE INFORMATION.
OFFSET CHILLED WATER PIPING TO MAINTAIN CLEARANCE AROUND AIR HANDLING UNIT.
NOT TO SCALE
ACC 3RD FLOOR/ROOF KEY PLAN
GENERAL NOTES
A.
B.
FIELD VERIFY ROUTING OF CHILLED WATER PIPING. COORDINATE ROUTING OF PIPING WITH EXISTING ELECTRICAL CONDUIT MAINS, HEATING HOT WATER SYSTEMS, PNEUMATIC TUBE SYSTEMS, ETC. ROUTE ALL NEW PIPING AS HIGH AS POSSIBLE . PROVIDE ANY AND ALL OFFSETS AS NECESSARY FOR OPTIMAL
PIPE ROUTING.
CONTRACTOR SHALL COORDINATE ANY REVISIONS TO ROUTE OF CHILLED WATER PIPING WITH
STRUCTURAL ENGINEER PRIOR TO BEGINNING WORK.
N
HEAT TRACE HATCHING LEGEND
HEAT TRACE CIRCUIT 1-A / 1-B (FROM HEAT TRACE PANEL # 1)
HEAT TRACE CIRCUIT 2-A / 2-B (FROM HEAT TRACE PANEL # 2)
HEAT TRACE CIRCUIT 3-A / 3-B (FROM HEAT TRACE PANEL # 3)
HEAT TRACE CIRCUIT 4-A / 4-B (FROM HEAT TRACE PANEL # 4)
HEAT TRACE CIRCUIT 5-A / 5-B (FROM HEAT TRACE PANEL # 5)
A. HATCHING INDICATES PIPING REQUIRING HEAT TRACE. REFER TO DETAIL #1, DWG M-504 FOR MORE
INFORMATION.
Revisions: Date:
FINAL BID & CONSTRUCTION 11/24/2021
FINAL BID & CONSTRUCTION (REVISED) 05/06/2022
A
AB
B
C
CD
D
E
E
0.2
0.5
0.8
A.2
A.2
A.1
A.1
A.8
A.8
0.7
X-RTU-15
XR - RS
XR - RL
XR - RL
XR - RS
X-TEF-7
X-TEF-5
X-GEF-6
X-TEF-6
XR-CU-15
X-CU-2X-CU-3
ROOF
CC-1
1 / M-153C
1 / M-153A
1 / M-153C
1 / M-153A
M-153AM-153B
M-153C
74490
L.D. HENDRIX, JR
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:5
:4
P M
M-153C
ACC THIRD FLOOR / ROOF HVAC PIPING PLAN CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 LDH CAB
BID & CONSTRUCTION
18902.00 1
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
ACC THIRD FLOOR/ROOF HVAC PIPING PLAN 1
CODED NOTES
4"Ø CHWS & CHWR PIPING DOWN THROUGH ROOF INTO 2ND FLOOR CEILING SPACE BELOW. SEE "ACC SECOND FLOOR PIPING PLAN - AREA B" DWG M-152 FOR CONTINUATION. PIPING SHALL BE INSTALLED AND PREPARED FOR CHANGEOVER PRIOR TO REMOVAL OF DX COIL AND INSTALLATION OF NEW COIL IN ORDER
TO MINIMIZE RTU-15 SHUTDOWN TO A SINGLE WEEKEND. COORDINATE WITH VA COR.
CONTRACTOR SHALL REMOVE EXISTING DX COOLING COIL AND CONNECT NEW 4"Ø CHWS & CHWR PIPING TO NEW CHILLED WATER COIL IN EXISTING RTU-15. CONNECT PER DETAIL #8 ON DWG M-502. EXISTING DX COIL SHALL NOT BE REMOVED UNTIL NEW CHILLED WATER PIPING IS INSTALLED AND PREPARED FOR CHANGEOVER IN ORDER TO MINIMIZE RTU-15 SHUTDOWN TO A SINGLE WEEKEND. COORDINATE WITH VA
COR.
REMOVE EXISTING CONDENSING UNIT AND ALL ASSOCIATED REFRIGERANT PIPING, CONTROLS, WIRING, SUPPORTS, ETC. COMPLETE. PATCH ROOF WATERTIGHT.
REFER TO ALTERNATE NOTES, THIS DWG, FOR ADDITIONAL INFORMATION.
NOT TO SCALE
ACC 3RD FLOOR/ROOF KEY PLAN
ALTERNATE NOTES
ALTERNATE NO 2:
AS PART OF ALTERNATE NO. 2, ALL WORK ASSOCIATED WITH CONVERTING EXISTING RTU-15 FROM DX
COOLING TO CHILLED WATER SHALL BE DELETED.
A.
GENERAL NOTES
A. FIELD VERIFY ROUTING OF CHILLED WATER PIPING. COORDINATE ROUTING OF PIPING WITH EXISTING ELECTRICAL CONDUIT MAINS, HEATING HOT WATER SYSTEMS, PNEUMATIC TUBE SYSTEMS, ETC. ROUTE ALL NEW PIPING AS HIGH AS POSSIBLE . PROVIDE ANY AND ALL OFFSETS AS NECESSARY FOR OPTIMAL
PIPE ROUTING.
N
Revisions: Date:
FFH 1ST FLOOR
2"ø NPCW2"ø NPCW2"ø NPCW
20 x 44 SA
20"ø TWR
20 x 44 SA 20 x 56 SA 24 x 108 RA
PAC-AHU-4
COOLING TOWER SUPPORT STRUCTURE .
SEE STRUCTURAL DRAWINGS.
COORDINATE MANUFACTURER'S
REQUIREMENTS WITH GENERAL TRADES
CONTRACTOR AND CONSTRUCTION OF
SUPPORTS. (TYP.)
ALL TOWER BASINS MUST BE LEVEL
WHEN FILLED. SHIM TOWERS AS
NECESSARY. COORDINATE HEIGHT OF
STEEL TO ACHIEVE NECESSARY
FITTINGS AND GRAVITY FLOW TO TW
PUMP INLETS. (TYP.)
A F
F
A F
F
SIDE STREAM FILTER
SYSTEM
0.5
0.5
0.8
0.8
B.4
B.4
2"ø NPCW
20"Ø TWS & TWR
20"ø TWS
18"ø CHWR
20"ø TWS 3"ø NPCW 3"ø NPCW
14"Ø
EQUALIZER
PIPING
8"ø TWS
8"ø TWS
6"Ø BRANCH TO CT BASIN
SWEEPERS. PIPE PER
MANUFACTURER'S
RECOMMENDATIONS
(TYP.)
12"ø TWR
12"ø TWS
12"ø TWS
12"ø TWR 12"ø TWR
12"ø TWS 12"ø TWS 12"ø TWR
6"Ø WATER
LEVEL SENSOR
STANDPIPE
A
F F
CHEMICAL
TREATMENT TANK
A F
F
10"Ø CHWS AND CHWR TO
EMERGENCY CONNECTION
FFH 1ST FLOOR
B.2B.5B.8C.3D.4E.3
CH-3CH-2CH-1
3"ø NPCW
3"ø NPCW
2"ø NPCW
4"ø CW
10"ø CHWR
12"ø TWR
12"ø TWS x
E
A
34 x 34
E1 3835
34 x 34
E1 3835
34 x 34
E1 3835
10"ø CHWS
FILL LINE STATION (BEHIND
CH-4). REFER TO DETAIL #5
ON DWG M-502 MORE
INFORMATION.
MOUNT CHILLER ON 6-INCH THICK
CONCRETE PAD. REFER TO
STRUCTURAL PLANS FOR ADDITIONAL
INFORMATION. PROVIDE VIBRATION
ISOLATION PER SPECIFICATIONS. (TYP.)
4" DOMESTIC COLD
WATER PIPED BACK TO
DOMESTIC COLD
WATER MAIN.
0.5 0.8 B.4
CH-4
20 x 60 EA
20"ø TWS
(BEHIND)
10"ø CHWS 10"ø CHWS 10"ø CHWS
(BEHIND) (BEHIND) (BEHIND)
(TYP. OF 4)
(TYP. OF 4)
10"ø CHWR 10"ø CHWR 10"ø CHWR
10"Ø CHWS AND CHWR TO
EMERGENCY CONNECTION
REFRIGERANT MONITOR PANEL
10"ø CHWS
10"ø CHWR
74490
L.D. HENDRIX, JR
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:5
:5
P M
M-301
MECHANICAL SECTIONS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 LDH CAB
BID & CONSTRUCTION
18902.00
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0" A
SECTION A
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0" B
SECTION B
GENERAL NOTES
A.
B.
ALL VALVING, SENSORS , CONTROLS MAY NOT BE ILLUSTRATED ON SECTION CUTS. REFER TO DETAILS, SCHEMATICS, AND DIAGRAMS FOR SPECIFIC REQUIREMENTS FOR VALVES, DEVICES, HEAT TRACE, ETC.
PROTECT ALL EXPOSED INSULATED PIPING WITHIN 6'-0" OF FINISHED FLOOR WITH ALUMINUM JACKET.
Revisions: Date:
FFH 1ST FLOOR
PAC-AHU-4
TP-3 TP-2 TP-1 P-3 P-2 P-1AS-1 ET-1
18"ø CHWR
18"ø CHWR
1"ø CHWR
2"ø NPCW
14 x 16 SA
CHEMICAL TREATMENT
FEED TANKS AND
ASSOCIATED PUMPS.
WATER TREATMENT
AND INSTRUMENTATION
CONTROLS STATION.
0.50.8B.4
18"ø CHWR
18"ø CHWR
TP-4 P-4
8"Ø FROM COOLING TOWER
EQUALIZER PIPING TO SSF-1 INLET
8"Ø FROM SSF-1 DISCHARGE TO
COOLING TOWER BASIN SWEEPERS
3/4"ø CA
3/4"Ø COMPRESSED AIR PIPING TO
SSF-1
FTP-1
FUEL OIL DIVERTER
VALVE CONTROL
PANEL
1"ø CHWR
CHEMICAL POT FEEDER
SSF-1
"ø
T W
S
"ø
T W
S
"ø
T W
S
"ø
T W
S
"ø
T W
S
"ø
T W
S
"ø
T W
S
"ø
T W
S
"ø
C H
W R
"ø
C H
W R
"ø
C H
W R
"ø
C H
W R
"ø
C H
W R
"ø
C H
W R
"ø
C H
W R
"ø
C H
W R
20"ø TWS 20"ø TWS 20"ø TWS
20"ø TWS20"ø TWS
18"ø CHWR
(BEHIND)
VFD
(TYP. OF 8)
VFDVFD
14 x 16 SA
FUEL OIL TRANSFER
PUMP CONTROL PANEL 1
"ø
C H
W S
"ø
C H
W R
10"Ø CHWS AND CHWR
THRU WALL TO
EMERGENCY
CONNECTION.
FFH 1ST FLOOR
56 x 20 SA
108 x 24 RA
PAC-AHU-4
16 x 14 SA
FTP-1FUEL OIL DIVERTER
VALVE CONTROL
PANEL WATER TREATMENT
CONTROL PANEL
FUEL OIL PUMP
CONTROL PANEL
10"Ø CHWS AND CHWR TO
EMERGENCY CONNECTION
10"Ø CHWS AND CHWR
IN FIELD-FABRICATED
LOCKABLE ENCLOSURE
74490
L.D. HENDRIX, JR
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:5
:0
P M
M-302
MECHANICAL SECTIONS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 LDH CAB
BID & CONSTRUCTION
18902.00
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0" C
SECTION C
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0" D
SECTION D
GENERAL NOTES
A.
B.
ALL VALVING, SENSORS , CONTROLS MAY NOT BE ILLUSTRATED ON SECTION CUTS. REFER TO DETAILS, SCHEMATICS, AND DIAGRAMS FOR SPECIFIC REQUIREMENTS FOR VALVES, DEVICES, HEAT TRACE, ETC.
PROTECT ALL EXPOSED INSULATED PIPING WITHIN 6'-0" OF FINISHED FLOOR WITH ALUMINUM JACKET.
Revisions: Date:
A.8
18"Ø CHWS
& CHWR
REFER TO ARCHITECTURAL
PLANS FOR MODIFICATIONS
TO EXISTING PARAPET
AV
PROVIDE AIR VENT AT HIGH
POINT OF CHWS AND CHWR
PIPING. REFER TO DETAIL #1
DWG M-501.
ROOF CURBS AND
PIPE SUPPORTS
(TYP.)
THIRD FLOOR
FFH 1ST FLOOR
FFH ROOF
BOILER ROOM
CHILLER PLANT
EC-114
18" CHWS & CHWR
FROM CHILLER PLANT
OFFSET CHWS & CHWR AS HIGH
AS POSSIBLE IN BOILER ROOM
PIPE HANGER
SHOWN FOR
REFERENCE
AV
PROVIDE AIR VENT AT HIGH
POINT OF CHWS AND CHWR
PIPING. REFER TO DETAIL #1
DWG M-501.
18"Ø CHWS & CHWR DOWN
INSIDE BOILER ROOM
18"Ø CHWS & CHWR
PIPING DOWN IN PIT
COORDINATE PIPING INVERT
WITH SITE CIVIL PLANS
2" MANUAL DRAIN VALVE AT
LOW POINT IN CHWS &
CHWR PIPING. REFER TO
DETAIL #1 DWG M-501
X - 3"ø HPR
2"ø BD
1"ø D
2"ø BD
BOILER ROOM
PIPE HANGER
SHOWN FOR
REFERENCE
(TYP.)
VERTICAL PIPE SUPPORT
X - 6"ø G
X - 8"ø HPS
X - 6"ø HPS
X - 4"ø LPS
X - 3"ø LPS
PROVIDE MANUAL ISOLATION
VALVES IN CHWS & CHWR
PIPING. INSTALL IN ACCESSIBLE
LOCATION
AV
PROVIDE AIR VENT AT HIGH
POINT OF CHWS AND CHWR
PIPING. REFER TO DETAIL #1
DWG M-501.
SLEEVE AND SEAL CHWS &
CHWR PIPING WITH
MECHANICAL LINK SEALS.
A.8
18"Ø CHWS & CHWR UP IN NEW
ENCLOSURE
18"Ø CHWS & CHWR
BELOW GRADE
AV
PROVIDE AIR VENT AT HIGH
POINT OF CHWS AND CHWR
PIPING. REFER TO DETAIL #1
DWG M-501.
EXTERIOR CHWS AND CHWR
PIPING SHALL BE HEAT
TRACED. REFER TO M-153A
FOR MORE INFORMATION.
2" MANUAL DRAIN VALVE AT
LOW POINT IN CHWS &
CHWR PIPING. REFER TO
DETAIL #1 DWG M-501
SLEEVE AND SEAL CHWS &
CHWR PIPING WITH
MECHANICAL LINK SEALS.
THIRD FLOOR
SECOND FLOOR
REFER TO ARCHITECTURAL
PLANS FOR MODIFICATIONS
TO EXISTING PARAPET
2-SECOND FLOOR
3-THIRD FLOOR18"ø CHWR
18"ø CHWS
10"ø CHWS
10"ø CHWR
10"Ø CHWR
(OPPOSITE SIDE)
10"Ø CHWS
(OPPOSITE SIDE)
THIRD FLOOR
SECOND FLOOR
74490
L.D. HENDRIX, JR
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:5
:1
P M
M-303
MECHANICAL SECTIONS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 LDH CAB
BID & CONSTRUCTION
18902.00
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
SECTION H H
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
SECTION E E
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
SECTION F F
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
SECTION G G
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
SECTION J J
GENERAL NOTES
ALL EXTERIOR PIPING SHALL BE HEAT TRACED. REFER TO FLOOR PLANS AND DETAIL #1 & #2 ON DRAWING
M-504 FOR MORE INFORMATION.
A.
Revisions: Date:
* BY ROOFING
SUB-CONTRACTOR
WOOD BLOCKING
ALUMINUM FLASHING
ROOF MEMBRANE *
FIBER CANT. *
ROOF INSULATION *
ROOF DECK
BOLT CURB
TO DECK30" FOR 1 PIPE
COVER HEADS OF NAILS
WITH SILICON SEALANT *
4-3/4" LAG
BOLTS (TYP)
TYPE 46 ADJUSTABLE
PIPE ROLL AND STAND
W/BASE
PROTECTION SADDLE
(TYPE-39)
PIPE
INSULATION W/ ALUMINUM JACKET
(NOT REQUIRED FOR NATURAL
GAS PIPING)
3/4" THICK GAL.
STEEL PLATE
60" FOR 2 PIPES
EQUIPMENT
SUPPORT RAIL
12" HIGH
NOT TO SCALE
6" 6"
6" 6"
NOTE:
1. APPLICABLE TO PENETRATIONS OF
ALL FIRE RATED MEMBRANES, IN
ACCORDANCE WITH NFPA 101. REFER
TO SPECIFICATIONS SECTION 078400 FOR
FIRE STOPPING SYSTEMS.
INSULATED
PIPE
FLOOR
FIRESTOP MATERIAL
3/4" [19mm] APPROVED
FIRESTOP INSULATION
WITH VAPOR BARRIER
PIPE SLEEVE
WHERE SPECIFIED
1/4" [6mm]∅ ANCHOR
ROD FOR NEW
CONSTRUCTION
WELD
FLOOR OR DECK PENETRATION
PARTITION OR CHASE PENETRATION
[152mm] [152mm]
MASONRY
PARTITION
PARTITION SUPPORT
FIRESTOP
MATERIAL
[152mm] [152mm]
3/4" [19mm] APPROVED
FIRESTOP INSULATION
WITH VAPOR BARRIER
DRYWALL PARTITION
INSULATED
PIPE
NOT TO SCALE
W
MAIN EXHAUST OR RETURN
PLAN VIEW
AIR
FLOW AIR
FLOW
PROVIDE VOLUME DAMPER
WHEN SHOWN ON FLOOR
PLANS
1/4W OR 4"
[102mm]
MIN.
BRANCH DUCT
NOT TO SCALE
4" DIRT LEG
GAS FIRED
EQUIPMENT
ON ROOF
UNION
GAS
SERVICE
GAS COCK
PROVIDE GAS
REGULATOR TO
REDUCE PRESSURE
TO 10" W.C.
NOT TO SCALE
W
W1
NOTE:
1.
2.
3.
4.
ALL VANED ELBOWS SHALL BE CONSTRUCTED AND INSTALLED AS DETAILED BY SMACNA.
WHEN W1 DOES NOT EQUAL W2, VANE SHALL BE SINGLE VANE TYPE REGARDLESS OF W
DIMENSION.
ALL SINGLE THICKNESS VANES SHALL HAVE A 2" [50mm] RADIUS, 1 1/2" [40mm] MAXIMUM SPACE
BETWEEN VANES AND A 3/4" [20mm] TRAILING EDGE.
WHEN W EQUALS W2 AND W1 IS GREATER THAN 20" [500mm] VANES SHALL BE DOUBLE
VANE TYPE.
NOT TO SCALE
ROOF
OVER EXISTING
LAP NEW MEMBRANE
CONTRACTOR
FIBER CANT.
MANUFACTURER
ROOF CURB BY MECHANICAL
INSULATION BY CURB
SOLDER SEAMS
BY MECHANICAL CONTRACTOR.
COLLAR AT DUCT.
SOLDER ALL SEAMS
ALUMINUM CAP FABRICATED
WATERTIGHT.
WATERTIGHT.
DUCT
NOT TO SCALE
ABOVE 2" (50 MM) DIA. PIPE
2 1/2" (65 MM) DIA.
2" (50 MM) DIA. & SMALLER
HORIZONTAL
ABOVE 2" (50 MM) DIA. PIPE 2" (50 MM) DIA. & SMALLER
VERTICAL
2 1/2" (65 MM) DIA.
NOT TO SCALE
NOTE:
1.
2.
3.
4.
SECURE CURB CAP TO WOOD NAILING STRIP WITH 3/8" [10mm] CADMIUM PLATED LAG BOLTS
NOT OVER 12" [300mm] ON CENTER.
SECURE ROOF CURB, DUCTWORK AND DAMPER TO ROOF WITH EXPANSION BOLTS
(CONCRETE ROOF) OR RUST RESISTANT BOLTS (METAL DECK AND BAR JOIST ROOF).
RUN ELECTRICAL LINES THROUGH CLEARANCE HOLE PROVIDED IN GRAVITY DAMPER, THEN
THROUGH VENTILATOR ELECTRICAL CONDUIT GUIDE.
DETAIL NOTES APPLIES TO BOTH DOWNBLAST AND UPBLAST TYPE FANS.
GRAVITY BACKDRAFT DAMPER
RIGID CONDUIT TO
ACCOMMODATE
ELECTRICAL WIRES
SEE NOTE 2
PREFABRICATED
ROOF CURB
WOOD NAILING
STRIP
ELECTRICAL
CONDUIT GUIDE
MOTOR HOUSING
DUCT
TRANSITION DUCT TO
FULL SIZE OF DAMPER
SUPPLIED WITH ROOF
VENTILATOR
ROOF
SEE NOTE 2
SEE NOTE 1
CURB CAP
NOT TO SCALE
W
R
2/3W
/3
W
W W
1/2W
/3
W
1/6W
VANE
VANE
NOTE:
1.
2.
THE INTERIOR SURFACE OF ALL RADIUS ELBOWS SHALL BE MADE ROUND.
ALL STANDARD RADIUS ELBOWS SHOWN ON FLOOR PLANS MAY BE MADE SHORT RADIUS
ELBOWS. ALL SHORT RADIUS ELBOWS SHALL HAVE VANES. VANES SHALL BE
CONSTRUCTED, SUPPORTED AND FASTENED AS RECOMMENDED BY SMACNA.
R SHALL
EQUAL
OR BE
GREATER
THAN W.
R SHALL
EQUAL
OR BE
GREATER
THAN
1/3W.
R
R SHALL
EQUAL
OR BE
GREATER
THAN
1/6W.
STANDARD
RADIUS ELBOW
SHORT RADIUS
ELBOW WITH
ONE VANE
SHORT RADIUS
ELBOW WITH
TWO VANES
R
NOT TO SCALE
NOTE:
1.
2.
DELETE INSULATION STAND-OFF ON DUCTWORK WITHOUT EXTERIOR INSULATION.
DETAIL SHOWS SINGLE BLADE DAMPER. DAMPER INSTALLATION SHALL BE SIMILAR FOR
MULTI-BLADE DAMPERS & ROUND DAMPERS.
INSULATION
DAMPER BLADE
1/8" [6mm]
CLEARANCE
ALL AROUND
OUTSIDE END BEARING
INSIDE END BEARING
HANDLE WITH
LOCKING
QUADRANT
2" INSULATION
STAND-OFF
1/2" [15mm] ROUND
ROD PIN
DUCT
STIFFEN BLADE
AS REQUIRED
SIDE ELEVATION SECTION
NOT TO SCALE
TYPICAL CHILLED WATER
TYPICAL AIR VENT
PIPING DRAIN VALVE CONNECTIONS
VENT ALL HIGH POINTS INDICATED ABOVE.
IF AUTOMATIC AIR VENTS ARE USED, PIPE DISCHARGE TO DRAIN
NOTES:
1.
2.
PLANS LOCATE DRAIN AT BOTTOM OF SCALE POCKET.
TYPICAL WATER PIPING
REDUCER, IF REQUIRED
3/4" (20 MM) BALL VALVE
ADAPTER TO 20 MM (3/4") HOSE THREAD.
PROVIDE HOSE CAP NUT
NOTES:
ELEVATION
THREADED PIPING WELDED PIPING
ELEVATION
1/2" COPPER TUBING
1/2" BALL VALVE
1/2" x 4" NIPPLE
CIRCULATING WATER PIPING
WHERE SCALE POCKETS ARE SHOWN ON PIPE RISER DIAGRAMS AND/OR
DRAIN ALL LOW POINTS AS INDICATED ABOVE.
1.
2.
ELEVATION
NOT TO SCALE
74490
L.D. HENDRIX, JR
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:5
:2
P M
M-501
MECHANICAL DETAILS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 LDH CAB
BID & CONSTRUCTION
18902.00
TYPICAL ROOF MOUNTED PIPE SUPPORT DETAIL 2PENETRATION OF FIRE/SMOKE BARRIERS 3EXHAUST OR RETURN BRANCH DUCTWORK 4
GAS CONNECTION TO ROOFTOP AIR HANDLING UNIT DETAIL 5DUCTWORK SQUARE VANED ELBOWS 6DUCT PENETRATION THROUGH ROOF DETAIL 7
INSTALLATION OF THERMOMETER WELLS 8POWER ROOF VENTILATOR 9DUCTWORK RADIUS ELBOWS 10VOLUME DAMPER DETAIL 11
PIPE VENT AND DRAIN DETAILS 1
Revisions: Date:
M
M
CW
NPCW
2"
N P
C W
3"
FLOOR
NC
EXTEND DRAIN LINE
TO NEAREST FLOOR
DRAIN. TERMINATE
WITH AN AIR GAP.
ISOLATION
VALVE (TYP.)
4"
4"
4"
4"
2"
2"
N P
C W
2"
UNION
(TYP.)
NC
2" CHILLED
WATER MAKE-UP.
BY-PASS
3" TO TOWER WATER
RETURN MAIN.
PRESSURE
GAUGE
(TYP.)
REDUCED
PRESSURE
BACKFLOW
PREVENTER
PRESSURE
REDUCING VALVE.
SET TO 33 PSI
DIGITAL MAKE-UP
WATER METER. WIRE
TO BAS (TYP.)
STRAINER W/
BLOWDOWN
(TYP.)
N P
C W
3" TO COOLING
TOWERS
3"
REFER TO
PLUMBING
PLANS FOR
CONTINUATION.
MAKE-UP FILL
CONTROL VALVE
PRESSURE
REDUCING VALVE.
SET TO 28 PSI
BY HC
BY PC
NOTES:
1. REFER TO PLUMBING DRAWINGS AND DIVISION 22 IN
SPECIFICATIONS FOR PIPE MATERIAL, INSULATION, VALVING,
METERS, ETC.
NOT TO SCALE
FLOOR
4" CONCRETE
EQUIPMENT PAD
EXPANSION TANK
DRAIN VALVE
SHUT-OFF VALVE
AIR VENT
FROM AIR
SEPARATOR PER DETAIL
#3 ON DWG M-504
TO PUMP SUCTION
CONNECT TO
SIDE OF MAIN
EXTEND TO FLOOR DRAIN
NOT TO SCALE
NOTES:
1. CONTRACTOR SHALL FILL AIR SIDE OF EXPANSION TANK TO MATCH MAKE-UP WATER
PRESSURE AT AIR SEPARATOR.
ROOF INSULATION
ROOF
2" x 2" WOOD NAILER - SCREW TO BASE SECTION
ACRYLIC CLAD THERMOPLASTIC COVER (COUNTER FLASHING)
GALV. STEEL PIPE CURB BASE SECTION
SEE PLAN VIEW DWG. FOR PIPE CURB SIZE
3# DENSITY CURB INSULATION
NOTES:
GRADUATED STEP BOOT WITH STAINLESS STEEL CLAMPS
1. ADEQUATE PIPE CURB AREA AND BOOT OPENINGS SHALL BE PROVIDED FOR
ELECTRICAL CONDUIT ROOF PENETRATIONS WHERE REQUIRED. MECHANICAL
CONTRACTOR SHALL COORDINATE LOCATIONS AND SIZES WITH ELECTRICAL
CONTRACTOR.
2. CURB SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR TO THE
GENERAL CONTRACTOR AT THE JOB SITE. THE GENERAL CONTRACTOR SHALL
INSTALL CURB AND INCORPORATE CURB INTO ROOFING SYSTEM.
NOT TO SCALE
PIPE CLAMP TACK WELDED TO SUPPORT ANGLE
3"x3"x1/4" ANGLES WELDED TO STRUCTURE
CAULK TOP OF BOOT WEATHERTIGHT
3. FOR PIPES REQUIRING INSULATION, INSULATION SHALL BE CONTINUOUS
THROUGH PENETRATION.
HIGH LEVEL ALARM AT TOWER OVERFLOW
LOW LEVEL ALARM AT 2" BELOW TOWER OPERATING LEVEL
NOTES:
1. STANDPIPE SHALL BE 6"∅.
2. CAP SHALL ANCHOR SENSORS, PROVIDE WATERTIGHT CONNECTION TO CONTROL WIRES, AND BE VENTED.
3. FIELD SET THE LEVEL OF EACH OF THE SENSORS AND VERIFY WITH MEASURED WATER LEVELS IN THE TOWER
BASINS.
CONNECT TO BAS AND MAKE-UP WATER CONTROL VALVE
REMOVABLE VENTED CAP
CLOSE MAKE-UP WATER VALVE AT 2"
ABOVE TOWER OPERATION LEVEL
OPEN MAKE-UP VALVE AT 1"
BELOW TOWER OPERATING LEVEL
14" EQUALIZER PIPE
NOT TO SCALE
6" STANDPIPE
SEE NOTE 2
INSULATION
PIPE
BANDS TO SECURE
INSULATION IN PLACE
INSULATION
PIPE
BANDS TO SECURE
INSULATION IN PLACE
METAL JACKET WITH
TOP LAP FACING DOWN
METAL JACKET WITH
TOP LAP FACING DOWN
RIVETS OR SCREWS AT
SEAMS (DO NOT
PENETRATE INSULATION)
METAL BAND OR
BELT INSTALLED
PER MFG'S
INSTRUCTIONS
MIN OF 1"
BETWEEN FIRST
BAND AND OVER-
LAPPING JOINT
NOTES:
1. LONGITUDINAL JACKETING SEAMS POSITIONED AT
3 OR 9 O'CLOCK ONLY WITH TOP LAP FACING
DOWN FOR WEATHER PROOFING.
2. OVERLAP JACKETING A MINIMUM OF 1-1/2".
3. INSTALL HEAT TRACE PER MANUFACTURER'S RECOMMENDATIONS.
NOT TO SCALE
DIFFERENTIAL PRESSURE
SENSOR WIRED TO BAS
S U
P P
L Y
P
IP
E
R E
T U
R N
P
IP
E
NOTES:
1. INSTALL WITHIN 24" OF COIL OR EQUIPMENT.
2. DO NOT INSTALL ANY PRESSURE REDUCING VALVES OR FITTINGS BETWEEN
PRESSURE TAPS AND EQUIPMENT.
3. FLOW CONVERSION SHALL BE BASED ON ACTUAL MANUFACTURER'S PROVIDED
FLOW-PRESSURE DROP CURVES. CONTRACTOR SHALL OBTAIN CURVES FROM
MANUFACTURER.
APPLY TO THE FOLLOWING
EQUIPMENT:
1. CHILLER EVAPORATOR
2. CHILLER CONDENSER
PETE'S PLUGS (TYP.)
S
NOT TO SCALE
DRAW THRU
2" [51mm]
PLUS Y
Y
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
WHERE Y = NEGATIVE STATIC PRESSURE IN
PAN
DRAIN LINE SHALL BE AT LEAST THE SAME SIZE
AS THE NIPPLE ON THE DRAIN PAN. CONDENSATE
DRAIN PIPE SHALL BE COPPER,TYPE L.
PITCH DOWN
TOWARD DRAIN
CLEAN OUT
ROOF DRAIN
DRAIN
PAN
DESIGNER'S NOTE:
A B
BLOW THRU
1" [25mm]
MINIMUM
2X
NOT TO SCALE NOT TO SCALE
NOTES:
1. CHILLED WATER COIL SHALL BE PIPED IN COUNTER FLOW ARRANGEMENT. CHILLED WATER SHALL FLOW IN OPPOSITE DIRECTION OF AIRFLOW (CHILLED WATER SUPPLY SHALL BE CONNECTED AT AIR DISCHARGE SIDE OF
COIL, WITH CHILLED WATER RETURN CONNECTED TO AIR INLET SIDE OF COIL).
WHEN COIL IS INCLUDED IN CASING MOUNTED ON VIBRATION ISOLATORS THE FIRST 2 HANGERS FOR EACH PIPE SHALL BE SPRING & NEOPRENE TYPE. TYPE "H" FOR 4"Ø PIPE & SMALLER. TYPE "H-P" FOR 5"Ø PIPE & LARGER.
PIPING SHALL BE INSTALLED IN SUCH A MANNER THAT IT WILL NOT BLOCK THE SWING OR USE OF ACCESS DOORS OR PANELS; NEITHER SHALL IT BLOCK THE SERVICING OF FILTERS, VALVES, EQUIPMENT, OR COIL REMOVAL.
UNLESS SPECIFICALLY NOTED, SHUT-OFF VALVES INDICATED SHALL BE GATE, BUTTERFLY, OR BALL VALVES.
REFER TO MECHANICAL SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
T
T
STRAINER WITH BLOWDOWN
(TYP.)
THERMOMETER IN PIPE WELL
(TYP.)
CHILLED WATER RETURN TEMPERATURE
SENSOR TO BE TIE INTO B.A.S.
CHILLED WATER SUPPLY TEMPERATURE
SENSOR TO BE TIE INTO B.A.S.
CROSS-SECTIONAL AREA OF
COMBINED BRANCH PIPING
SHALL EQUAL OR EXCEED
CROSS-SECTIONAL AREA OF
MAINS SERVING BRANCH
PIPING AND VELOCITY THRU
BRANCH PIPING SHALL NOT
EXCEED 6 FPS [1.8 M/S]
AIR VENT
WHEN COIL
IS NOT
SELF-VENTING
TEST PLUG
(TYP.)
PIPE HANGER SHALL SUPPORT
PIPING INDEPENDENT OF COIL
REDUCER, IF
REQUIRED
DRAIN WHEN COIL IS
NOT SELF-DRAINING
DRAIN
CHWR
CHWS
CHILLED
WATER COIL
CHILLED
WATER COIL
CONCRETE
(TYPICAL)
VIBRATION ISOLATOR
1" (25 MM) MIN. DIA.
DRAIN
1/2" (15 MM)
1/2" (15 MM)
FLEXIBLE CONNECTOR
(TYPICAL)
HANGER
RIGID PIPE
HANGER
RIGID PIPE
TO PIPE ELBOW AS
POSSIBLE (TYPICAL)
INSTALL HANGER AS CLOSE
FLOOR
PUMP WITH BUILT-IN
SUCTION DIFFUSER
PRESSURE GAGE
STRAINER
PIPE STAND
INERTIA BASE
(SHUT-OFF/BALANCE) VALVE
CHECK VALVE
FIRST 3 HANGERS FOR EACH PIPE AND
BRANCH SHALL BE SPRING & NEOPRENE
TYPE. TYPE "H" FOR 4" (100 MM) DIA. PIPE
& SMALLER. TYPE "H-P" FOR 5" (125 MM)
DIA. PIPE & LARGER.
NOT TO SCALE
DRIVEN
EQUIPMENT
MOTORTYPICAL STRUCTURAL
STEEL MEMBER FOR
EQUIPMENT
TYPE"B"
WELDED STEEL BASE
TYPE "1"
CONCRETE INERTIA BASE
NUMBER OF ISOLATION
UNITS AS REQUIRED
NUMBER OF
ISOLATION
UNITS AS REQUIRED
TYPICAL
STRUCTURAL
STEEL MEMBER FOR
EQUIPMENT
ALL WELDED
STEEL
FRAMEWORK
SECTION A-A
STRUCTURAL
STEEL FRAME
SPRING
ISOLATOR
ANCHOR
BOLT
REINFORCING BARS
SLEEVE
A
SHAFT
MOTORSHAFT
DRIVEN
EQUIPMENT
A
NOT TO SCALE
74490
L.D. HENDRIX, JR
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:5
:3
P M
M-502
MECHANICAL DETAILS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 LDH CAB
BID & CONSTRUCTION
18902.00
MAKE-UP FILL LINE STATION DETAIL 5
CHILLED WATER EXPANSION TANK DETAIL 1PIPE ROOF CURB PENETRATION DETAIL 2
REMOTE WATER LEVEL SENSOR STANDPIPE DETAIL 4FIELD APPLIED METAL JACKETING OVER PIPE INSULATION 6
DIFFERENTIAL PRESSURE SENSOR DETAIL 7AIR HANDLING UNIT DRAIN TRAP DETAIL 9 CHILLED WATER COOLING COIL DETAIL 8
TYPICAL PIPING CONNECTIONS TO FLOOR MOUNTED SINGLE SUCTION WATER PUMPS 3
VIBRATION ISOLATION BASES DETAIL 10
Revisions: Date:
5 FT
THRU [20]
6 8 10
[32][25] [40]
[65]
[50]
[75]
-1312 14 -16 -
[125][100]
[150]
[250]
[200]
[300]
[400]
[350]
[450]
[600]
[500]
20 241814 16128 1064 532 2 1/21 1/21 1 1/4
[9100] [9600][8500][7600] [8200][7000][5800] [6700][5200][4100] [4900][3700][3000] [3400][2700][2100]
--- --[4900] -[4100][3700] [4000] -[3000][2400][1800][1500]
THRU 3/4
[2100] [2100]
[2100]
[2700]
[2400]
SIDE VIEW TRAPEZE HANGER FOR UP TO
1000 LB. [453KG] UNIFORM LOAD
ADJUSTABLE CLEVIS HANGER
TYPE 1 - SEE SPECIFICATIONS
ADJUSTABLE CLEVIS HANGER
TYPE 43 - SEE SPECIFICATIONS
PROVIDE INSULATION SHIELD
& INSERT FOR ALL PIPING
(8" [200mm] MIN.)
BAND
1-5/8" [43mm] 12 GAUGE CHANNEL OR 2"x2"x1/4" [50x50x6.4mm] ANGLE
1/2" [15mm] DIA.
HANGER RODS WITH
36" [900mm] MAX.
SPACING ON EACH
CHANNEL
WELD
SADDLE
INSULATION SHIELD
AT HANGER
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION (9
PSF MIN. DENSITY) UNDER
INSULATION SHIELD
INSULATION (VAPOR
BARRIER TYPE IS
REQUIRED FOR LOW
TEMPERATURE PIPE)
HANGER ROD
MAXIMUM PIPE/TUBING SUPPORT SPACING
NOTE: FOR TRAPEZE HANGER TAKE SPACING OF SMALLEST SIZE ON TRAPEZE.
NOM. SIZE
PIPE
TUBING
IN.
[mm]
FT.
[mm]
FT.
[mm]
[2 m m
M A
X
NOTES:
SEE SPECIFICATIONS FOR
DETAILED HANGER
REQUIREMENTS
NOT TO SCALE
1/4 3/8 1/21/2 1/2 3/45/8 7/8 11 1 1/4 1 1/21 1/4
[32] [40][32][25] [25][22][16] [19][13][13] [13][7] [7] [10]ROD SIZE
FT.
[mm] 3/83/83/83/81/4
[10] [10] [10] [10]
M
T W
R
3/4"
SHUTOFF
VALVE
FLOOR
A F
F
DIGITAL WATER METER.
WIRE TO CHEMICAL
TREATMENT CONTROLLER
CHECK VALVE
TOWER WATER
RETURN MAIN
2-WAY CONTROL VALVE
INTERLOCKED WITH CHEMICAL
TREATMENT SYSTEM
GLOBE VALVE
SPILL 3/4" DRAIN LINE TO
LOCAL FLOOR DRAIN
NOT TO SCALE
1/4" (7 MM) DRAIN VALVE
ADAPTER TO 7 MM (1/4") THREAD.
PROVIDE CAP NUT
CHILLER
PURGE DISCHARGE
RUPTURE DISC OR VENT
(BY CHILLER MANUFACTURER)
REDUCER
FULL SIZE 24" DRIP LEG
TEE
VENT LINE. MATERIAL AND SIZE
PER MANUFACTURER.
PURGE DISCHARGE
VENT LINE
FLEXIBLE STAINLESS
STEEL CONNECTION
GOOSENECK 24" ABOVE ROOF
PROVIDE ROOF PENETRATION
CURB AND RUBBER BOOT
ROOF
FLANGED JOINT OR UNION TO
PERMIT PIPING DISASSEMBLY
FOR BURSTING DISC OR VENT
PIPING.
NOTES:
1. SUPPORT VENT PIPING INDEPENDENT OF CHILLER.
2. RELIEF VENT SIZE PER MANUFACTURERS RECOMMENDATIONS.
3. TACK WELD STAINLESS STEEL BIRD SCREEN ON OUTDOOR
OPENING.
4. WHERE CHILLER REQUIRES MULTIPLE VENTS, PIPE EACH VENT
INDEPENDENTLY. DO NOT CONNECT VENTS.
NOT TO SCALE
T W
SCONDUCTIVITY PROBE
INTERLOCKED WITH
CHEMICAL TREATMENT
CONTROL PANEL
T W
R
3/4"
3/4"
SHUTOFF
VALVE (TYP.)
GLOBE VALVE
FLOW
SWITCH
FLOOR
A F
F
SIDE TAKEOFF
NOT TO SCALE
STORAGE TANK NO. 1
CHILLED WATER SCALE
AND CORROSION INHIBITOR
STORAGE TANK NO. 2
TOWER BIOCIDE
STORAGE TANK NO. 3
TOWER SCALE AND
CORROSION INHIBITOR
CHEMICAL
FEED
CONTROLLER
CHEMICAL
FEED
PUMP
NO. 1
CHEMICAL
FEED
PUMP
NO. 2
CHEMICAL
FEED
PUMP
NO. 3
HSHSHS
C H
IL
L E
D W
A T
E R
R E
T U
R N
H
E A
D E
R
RELIEF BYPASS
VALVE TYP.
FLOOR
SINK
MODULATING
CONTROL VALVE
TOWER
MAKE UP
METER
PH AND
CONDUCTIVITY
TRANSMITTER
(DETAIL #3 THIS
DRAWING)
LC
BLOW DOWN
VALVE (DETAIL #5
THIS DRAWING)
CHILLER CONDENSERS
TYP.
TOWERTOWERTOWER
SAMPLE
WATER
LEVEL
METER
TOWER
WATER
PUMPS
TYP.
SIDE STREAM
FILTER WITH PUMP
TOWER WATER
SUPPLY
(FROM TOWER)
TOWER WATER
RETURN
(TO TOWER)
NOTES:
1. PROVIDE CORPORATION STOP INJECTORS FOR EACH CHEMICAL
TREATMENT FEED LOCATION.
2. ALL INJECTOR POINTS TO RETURN HEADERS SHALL BE 1-INCH
WELD-O-LETS WITH FULL PORT BALL VALVES. TAP LOCATIONS SHALL BE
ORIENTED NO MORE THAN 45 DEGREES ABOVE OR BELOW HORIZONTAL
RUN OF THE HEADER.
3. PROVIDE BACNET INTERFACE BETWEEN CHEMICAL FEED CONTROLLER AND
TC ECC.
4. CHILLED WATER TREATMENT SYSTEM SHALL BE OPERATED MANUALLY.
5. ADDITIONAL STORAGE TANKS AND FEED PUMPS MAY BE REQUIRED BASED
ON THE OUTCOME OF THE WATER SAMPLE ANALYSIS.
6. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
CORPORATION STOP
INJECTOR (TYP.)
STORAGE TANK NO. 4
TOWER OXIDIZING
BIOCIDE
CHEMICAL
FEED
PUMP
NO. 4
HS
M
M
PROVIDE MINIMUM DISTANCE BETWEEN EACH INJECTION QUILL PER
MANUFACTURER'S REQUIREMENTS.
PROVIDE DUCKBILL CHECK AT EACH CHEM TREATMENT POINT IN
TOWER WATER SYSTEM.
7.
8.
NOT TO SCALE
TOWER
MAKE-UP WATER
CONTROL VALVE
(TYPICAL)
74490
L.D. HENDRIX, JR
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:5
:3
P M
M-503
MECHANICAL DETAILS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 LDH CAB
BID & CONSTRUCTION
18902.00
PIPE HANGERS DETAIL 2
TOWER WATER BLOWDOWN DETAIL 5 REFRIGERANT RELIEF VENT PIPE DETAIL 4 CONDUCTIVITY MONITORING ASSEMBLY 3
WATER TREATMENT SYSTEM DIAGRAM 1
Revisions: Date:
NOT TO SCALE
* BY ROOFING
SUB-CONTRACTOR
WOOD BLOCKING
ALUMINUM FLASHING
ROOF MEMBRANE *
FIBER CANT. *
ROOF INSULATION *
ROOF DECK
BOLT CURB
TO DECK
18"Ø PIPE W/
INSULATION AND
ALUMINUM JACKET
(TYP)
(68" MINIMUM)
1-1/2"Ø GALVANIZED
THREADED ROD
(TYP)
HOT-DIP GALVANIZED ROLLER
(TYP)
GALVANIZED AXLE
(TYP)
H
IG
H
C U
R B
28-7/8" (TYP)
(T
Y P
GALVANIZED FASTENER
(TYP)
WELD TO PIPE
(TYP)
SADDLE
(TYP)
NOT TO SCALE
BELL & GOSSETT AUTOMATIC AIR
VENT MODEL 107A OR EQUAL. PIPE
DISCHARGE TO FLOOR DRAIN
3/4"Ø
2"Ø
1"Ø
ISOLATION VALVE (TYP.)
PIPE TO FLOOR DRAIN
2"Ø
TO SUCTION SIDE OF PUMPSCHILLED WATER RETURN
EXPANSION TANK CONNECTION
PER DETAIL #1 ON DWG M-502
NPCW
MAKE-UP WATER PER
DETAIL #5 ON DWG M-502
AIR SEPARATOR
(AS-1)
ROOF INSULATION
ROOF
2" x 2" WOOD NAILER - SCREW TO BASE SECTION
ACRYLIC CLAD THERMOPLASTIC COVER
(COUNTER FLASHING)
GALV. STEEL PIPE CURB BASE SECTION
SEE PLAN VIEW DWG. FOR PIPE CURB SIZE
R-20 CURB INSULATION
NOTES:
6" WIDE NEOPRENE STRIP GLUED AT LAP,
CLAMPED AT PIPE & COLLAR
1. CURB SHALL BE FURNISHED BY THE MECHANICAL CONTRACTOR TO THE GENERAL
CONTRACTOR AT THE JOB SITE. THE GENERAL CONTRACTOR SHALL INSTALL CURB AND
INCORPORATE CURB INTO ROOFING SYSTEM.
NOT TO SCALE
PIPE CLAMP TACK WELDED TO SUPPORT ANGLE
3"x3"x1/4" ANGLES WELDED TO STRUCTURE
FIELD-FABRICATED 18 GA
GALVANIZED STEEL COVER
ON 4 SIDES AND TOP.
SECURE TO WOOD
BLOCKING OF CURB.
SLOPE ENCLOSURE 1" PER
FOOT FOR DRAINAGE
FASTEN GALVANIZED
STEEL ENCLOSURE
AND THERMOPLASTIC
COVER TO WOOD
NAILER AT 8" O.C.
PROVIDE ESCUTCHEON
AND SEAL WATERTIGHT
INSTALLATION SPECIFICATION:
A. INSTALL ELECTRIC HEATING CABLE ACROSS EXPANSION JOINTS ACCORDING TO MANUFACTURER'S WRITTEN
INSTRUCTIONS; USE SLACK CABLE TO ALLOW MOVEMENT WITHOUT DAMAGE TO CABLE.
B. INSTALL ELECTRIC HEATING CABLES AFTER PIPING HAS BEEN TESTED AND BEFORE INSULATION IS INSTALLED.
C. INSTALL ELECTRIC HEATING CABLES ACCORDING TO IEEE 515.1.
D. INSTALL INSULATION OVER PIPING WITH ELECTRIC CABLES ACCORDING TO SECTION 23 07 11 "HVAC PIPING
INSULATION."
E. INSTALL ALONG LONG RADIUS OF ALL ELBOWS.
F. INSTALL WARNING TAPE ON PIPING INSULATION WHERE PIPING IS EQUIPPED WITH ELECTRIC HEATING CABLES.
G. SET FIELD-ADJUSTABLE SWITCHES AND CIRCUIT-BREAKER TRIP RANGES.
PIPE
INSULATION BY MC AFTER HEAT
TRACE IS INSTALLED - CONTACT
ENGINEER / HEAT TRACE REP PRIOR
TO INSULATING. SUBMIT A SIGNED
INSTALLATION INSPECTION
REPORT.
HEAT TRACE BY MECHANICAL
CONTRACTOR - INSTALL AT
EITHER 7 O'CLOCK OR 5
O'CLOCK ON THE PIPE
SURFACE.
PIPE HEAT TRACE NOTES
NOT TO SCALE
HEAT TRACE PANEL #
HEAT TRACE PANEL #1
HEAT TRACE
CIRCUIT
1-A
CABLE POWER
(WATTS / FT)
PIPING SERVED
18"Ø CHWS
APPROX. PIPING
LENGTH (FT)
1-B 10 18"Ø CHWR 240
2-A 10 220
2-B 10 220
3-A 8 12"Ø TWR 25
12"Ø TWS 12
2"Ø NPCW 12
HEAT TRACE PANEL #2 18"Ø CHWS
18"Ø CHWR
PIPE SURFACE
TEMP. (°F)
HEAT TRACE PANEL #3
3-B 8 12"Ø TWR 25
12"Ø TWS 12
2"Ø NPCW 12
4-A 8 12"Ø TWR 25
12"Ø TWS 12
2"Ø NPCW 12
HEAT TRACE PANEL #4
4-B 8 12"Ø TWR 25
12"Ø TWS 12
2"Ø NPCW 12
5-A 5 (NOTE 2) 160
5 80
HEAT TRACE PANEL #5 14"Ø TWS
8"Ø TWS
5-B 8 1208"Ø TWS 40
CONTRACTOR SHALL PROVIDE A COMPLETE PIPE HEAT TRACE SYSTEM FOR ALL DESIGNATED PIPING AS SHOWN ON MECHANICAL DRAWINGS AND IN HEAT TRACE TABLE (THIS SHEET). CHILLED WATER, TOWER WATER, EQUALIZER PIPING, AND NPCW HEAT TRACE SYSTEMS SHALL BE A SELF REGULATING HEAT TRACE CABLE. EACH CIRCUIT SHALL BE CONNECTED TO A 20A-1P BREAKER (SEE ELECTRICAL DRAWINGS). HEAT TRACE CABLE SHALL PREVENT FREEZING OF PIPES DOWN TO A MINIMUM AMBIENT TEMPERATURE OF -20°F. ALL CABLE SHALL BE RATED AT 277V. CHILLED WATER, TOWER WATER, EQUALIZER, AND NPCW CABLE SHALL BE CONTROLLED BY AN EXTERIOR THERMOSTAT WITH A 40°F ACTIVATION TEMPERATURE. CONTROL PANEL SHALL HAVE INTEGRAL GROUND FAULT EQUIPMENT PROTECTION FOR HEAT TRACE CIRCUITS. INSTALL ALL HEAT TRACE CABLE IN ACCORDANCE WITH MANUFACTURER'S INSTALLATION
INSTRUCTIONS. HEAT TRACE SHALL BE TESTED AT THE FOLLOWING TIMES:
1. UPON RECEIPT OF HEAT TRACE COMPONENTS, PRIOR TO INSTALLATION.
2. UPON COMPLETION OF INSTALLATION ON PIPE, PRIOR TO INSULATION.
3. UPON COMPLETION OF PIPE INSULATION.
HEAT TRACE TABLE
THE FOLLOWING IS PROVIDED AS GENERAL GUIDELINES, CONTRACTOR SHALL ALSO REFER TO
MANUFACTURER'S INSTALLATION REQUIREMENTS.
1. INSTALL HEAT TRACE CABLE AT EITHER 8 O'CLOCK OR 4 O'CLOCK ON THE PIPE SURFACE.
2. FOR PIPE ELBOWS INSTALL HEAT TRACE CABLE ON THE OUTER RADIUS.
3. AT PIPE COUPLINGS, HEAT TRACE CABLE SHALL BE INSTALLED BENEATH THE COUPLING BOLT AND
SHALL NOT BE INSTALLED ON THE OUTSIDE OF PIPE COUPLING BOLT.
4. HEAT TRACE CABLE SHALL BE SECURED TO PIPING AND FITTINGS WITH HIGH TEMPERATURE ADHESIVE TAPE TO ENSURE HEAT TRACE CABLE IS IN CONTINUOUS CONTACT WITH PIPING AND
FITTINGS.
5. CONTRACTOR SHALL TEST HEAT TRACE PRIOR TO FILLING EACH SYSTEM.
6. CONTRACTOR SHALL WORK WITH VA COR TO SCHEDULE INSPECTION OF HEAT TRACE
CABLE INSTALLATION WITH ENGINEER AND MANUFACTURER'S REPRESENTATIVE. ALL HEAT
TRACE SHALL BE INSPECTED DURING ONE SITE VISIT.
PIPE COUPLING
HEAT TRACE CABLE
HEAT TRACE CABLE
PIPE ELBOW
HEAT TRACE
CABLE
PIPE
NOTE 1 NOTE 2 NOTE 3
PIPE
NOTES:
1.
2.
3.
CONTRACTOR SHALL VERIFY FINAL HEAT TRACE LENGTHS AND PIPE SIZES AS PART OF COORDINATION PROCESS.
PIPING SHALL BE DOUBLE-TRACED.
PROVIDE BACNET COMPATIBLE CONTROL CARD WITH ALARMS TO BAS. REFER TO SPECIFICATIONS FOR MORE
INFORMATION AND ALARM POINTS.
74490
L.D. HENDRIX, JR
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:5
:4
P M
M-504
MECHANICAL DETAILS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 LDH CAB
BID & CONSTRUCTION
18902.00
ROOFTOP CHILLED WATER PIPE SUPPORT DETAIL 2
AIR SEPARATOR DETAIL 3CHILLED WATER AND TOWER WATER PIPE ROOF CURB PENETRATION DETAIL 4
HEAT TRACE DETAIL 1
Revisions: Date:
74490
L.D. HENDRIX, JR
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:5
:4
P M
M-601
MECHANICAL SCHEDULES CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 LDH CAB
BID & CONSTRUCTION
18902.00
MARK
SERVICE
TYPE
CAPACITY
TANK VOLUME (GAL.)
PHYSICAL SIZE
ET-1
VERT. BLADDER
370.0
36"∅ X 98"T
NOTES:
1. MOUNT ON 4" THICK CONCRETE HOUSEKEEPING PAD.
2. ASME RATED FOR MAXIMUM 150 PSI ASME RATING
PRESSURE.
3. ACCEPTABLE MANUFACTURERS INCLUDE BELL &
GOSSETT, TACO, OR APPROVED EQUAL.
MARK
SERVICE
CAPACITY
INLET/OUTLET SIZE
AS-1
20"
NOTES:
1. COALESCING REMOVAL AIR AND DIRT SEPARATOR.
2. REFER TO SPECIFICATION 23 21 13 FOR ADDITIONAL
INFORMATION.
3. INSTALL AT HEIGHT TO PERMIT REMOVAL OF COALESCING
MEDIUM. REFER TO MANUFACTURER'S RECOMMENDATIONS.
SYSTEM WATER FLOW (GPM)
0.81HEAD LOSS (FT)
AIR FILL PRESSURE (PSI) 33.0
MAX. DESIGN TEMPERATURE (°F) 95
ACCEPTANCE VOLUME (GALLONS) 338.9
CHILLED
WATER
CHILLED
WATER
ELECTRICAL
FLOW (GPM)
ENTERING WATER TEMP. (DEG. F.)
VOLTS-PHASE-HERTZ
ACCESSORIES
TONS OUTPUT
FOULING FACTOR
MAX WPD (FT)
MCA
NOTES:
1.
2.
3.
4.
5.
6.
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
CHILLER SHALL BE MOUNTED ON 6-INCH THICK CONCRETE PAD. REFER TO STRUCTURAL DRAWINGS.
CONTRACTOR TO PRESSURE TEST AND TOP-OFF REFRIGERANT AS PART OF CHILLER START-UP.
ALL COLD SURFACES SHALL BE INSULATED WITH 3/4" CLOSED CELL ELASTOMERIC FOAM INSULATION INCLUDING THE EVAPORATOR, WATER
BOXES, AND SUCTION ELBOW.
REVIEW FLOOR PLANS AND DETAILS FOR COORDINATION OF FINAL CHILLER/PIPING CONFIGURATION.
PROJECT DRAWINGS SHOW BASIS-OF-DESIGN EQUIPMENT WEIGHT, DIMENSIONS, AND GENERAL CONNECTION ARRANGEMENT. ANY DEVIATION FROM BASIS OF DESIGN EQUIPMENT REQUIRING ADDITIONAL WORK AND/OR COORDINATION SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR AND SHALL BE COMPLETED AT NO COST TO THE VA.
MARK
SINGLE POINT ELECTRICAL CONNECTION
FACTORY AUTHORIZED STARTUP
VIBRATION ISOLATORS
TYPE
UL LISTED
BUILDING CONTROLS NETWORK INTERFACE
WATER FLOW SWITCH
PRIMARY EFFICIENCY (KW PER TON)
NPLV (KW PER TON)
EVAPORATOR
LEAVING WATER TEMP. (DEG. F.)
FLOW (GPM)
ENTERING WATER TEMP. (DEG. F.)
CONDENSER
MAX WPD (FT)
LEAVING WATER TEMP. (DEG. F.)
MOCP
PROPYLENE GLYCOL (%)
MEDIA
REFRIGERANT TYPE
REFRIGERANT CHARGE (LBS.)
NO. OF PASSES
FOULING FACTOR
UNIT MOUNTED VARIABLE FREQUENCY DRIVE
NO. OF PASSES
EXPANSION TANK
AIR AND DIRT SEPARATOR
PUMPS WATER COOLED CHILLERSCOOLING TOWER
SIDE STREAM FILTER
54.0
0.00010
16.7
CH-1
460-3-60
36,940
YES
YES
YES
42.0
YES
YES
YES
CENTRIFUGAL
85.0
19.3
95.0
100% WATER
0.5989
0.3800
R-134a
0.00025
YES
MARK
SERVICE
TYPE
TEMPERATURE (°F)
FLUID
PERFORMANCE
FLOW (GPM)
TOTAL HEAD (FEET)
SPEED (RPM)
MOTOR
SIZE (HP)
VOLT-PHASE-HERTZ
P-1, P-2, P-3, P-4
CHILLED WATER
WATER
125.0
460-3-60
EFFICIENCY (%) 84.9
NOTES:
1. MOUNT PUMP ON CONCRETE INERTIA PAD.
2. PROVIDE INVERTER DUTY MOTORS RATED FOR USE WITH VARIABLE SPEED MOTOR CONTROLLER.
PROVIDE VSMC FOR PUMP.
3. PUMPS CASINGS SHALL BE CAPABLE OF ACCEPTING ONE LARGER IMPELLER SIZE.
NOTES 1,2,3
VARIABLE FREQUENCY DRIVE YES
END SUCTION
BASE
MOUNTED
TP-1, TP-2, TP-3, TP-4
CONDENSER WATER
WATER
75.0
460-3-60
79.2
1,2,3
YES
MARK
SERVICE
TYPE
PERFORMANCE
CT-1
CONDENSER WATER
ELECTRICAL DATA
NOTES:
1.
2.
3.
4.
5.
6.
7.
FURNISH MANUFACTURER'S REMOTE VARIABLE SPEED MOTOR CONTROLLERS (VSMC) FOR FANS. INSTALL WITHIN CHILLER ROOM. REFER TO FLOOR PLANS.
PROVIDE A FACTORY WIRED DISCONNECT WITHIN LINE OF SITE FOR EACH FAN. CONTRACTOR TO INSTALL VSMC AND WIRE FROM VSMC TO EACH FAN
DISCONNECT. VSMC'S SHALL BE PROVIDED WITH BYPASS.
PROVIDE FLANGED PIPE CONNECTIONS.
PROVIDE BASIN HEATERS WITH THERMOSTAT AND LOW WATER CUT-OFF. PROVIDE CONTACTOR, TRANSFORMER, AND DISCONNECT IN A NEMA 4
ENCLOSURE.
COOLING TOWERS CT-1/CT-2 AND CT-3/CT-4 SHALL BE TWINNED TOGETHER, EACH WITH INDEPENDENT CELL OPERATION.
PROVIDE SUMP SWEEPERS TO BE PIPED TO SSF-1.
ATTACH FAN PLATFORM LADDER TO COOLING TOWER FACE IN ORDER TO PREVENT OBSTRUCTING WALKING PLATFORM ACCESS.
PROJECT DRAWINGS SHOW BASIS-OF-DESIGN EQUIPMENT WEIGHT, DIMENSIONS, AND GENERAL CONNECTION ARRANGEMENT. ANY DEVIATION FROM BASIS OF DESIGN EQUIPMENT REQUIRING ADDITIONAL WORK AND/OR COORDINATION SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL BE
COMPLETED AT NO COST TO THE VA.
AIR COOLED
6.7
ENTERING WATER TEMPERATURE (°F) 95.0
LEAVING WATER TEMPERATURE (°F) 85.0
460/3/60
CAPACITY (TONS)
FLOW RATE (EACH CELL) (GPM)
PRESSURE DROP THROUGH TOWER (FT)
DIMENSIONAL DATA (BASIS OF DESIGN)
11'-9" x 20'-0" x 18'-6 1/2"LENGTH X WIDTH X HEIGHT
OPERATING WEIGHT (LBS)
VOLTS/PHASE/HERTZ
BASIN HEATER (KW)
ACCESSORIES
VIBRATION ISOLATORS
MANUFACTURER'S START-UP
CONTACTOR W/ TXR AND DISCONNECT FOR HEATERS
EXTERNAL SERVICE PLATFORM WITH LADDER
24,450
2 @ 15 KW EACH
YES
YES
YES
YES
ENTERING AIR WET BULB (°F) 78.0
LOUVER ACCESS DOOR YES
FAN HP 60.0
DAVIT TO HOIST FAN MOTORS YES
INVERTER CAPABLE, PREMIUM EFFICIENT MOTORS YES
FAN FAILURE CURRENT SENSING RELAYS YES
304 WELDED STAINLESS STEEL BASIN YES
END SUCTION
BASE
MOUNTED
BHP 84.9 60.8
MARK
SERVICE
TYPE
FLUID TEMPERATURE (°F)
FLUID
PERFORMANCE
FLOW (GPM)
VOLT-PHASE-HERTZ
SSF-1
CONDENSER WATER
WATER
480-3-60
WEIGHT (LBS) 3000
NOTES:
1. MOUNT SYSTEM ON 4-INCH THICK CONCRETE HOUSEKEEPING PAD.
2.
3.
4.
PRE-PACKAGED, SKID MOUNTED, SINGLE POINT ELECTRICAL
CONNECTION.
MAXIMUM OVERCURRENT PROTECTION 60
TURBO DISC
FILTER SYSTEM
MICRON RATING 50
VIBRATION CUT-OUT SWITCHES YES
304 STAINLESS STEEL UPPER YES
BACKFLUSH FLOW RATE (GPM) 90
5200MAXIMUM WATER FLOW (GPM)
CT-2
CONDENSER WATER
AIR COOLED
6.7
95.0
85.0
460/3/60
11'-9" x 20'-0" x 18'-6 1/2"
24,450
2 @ 15 KW EACH
YES
YES
YES
YES
78.0
YES
60.0
YES
YES
YES
YES
YES
YES
CT-3
CONDENSER WATER
AIR COOLED
6.7
95.0
85.0
460/3/60
11'-9" x 20'-0" x 18'-6 1/2"
24,450
2 @ 15 KW EACH
YES
YES
YES
YES
78.0
YES
60.0
YES
YES
YES
YES
YES
YES
CT-4
CONDENSER WATER
AIR COOLED
6.7
95.0
85.0
460/3/60
11'-9" x 20'-0" x 18'-6 1/2"
24,450
2 @ 15 KW EACH
YES
YES
YES
YES
78.0
YES
60.0
YES
YES
YES
YES
YES
YES
54.0
0.00010
16.7
CH-2
460-3-60
36,940
YES
YES
YES
42.0
YES
YES
YES
CENTRIFUGAL
85.0
19.3
95.0
100% WATER
0.5989
0.3800
R-134a
0.00025
YES
54.0
0.00010
16.7
CH-3
460-3-60
36,940
YES
YES
YES
42.0
YES
YES
YES
CENTRIFUGAL
85.0
19.3
95.0
100% WATER
0.5989
0.3800
R-134a
0.00025
YES
54.0
0.00010
16.7
CH-4
460-3-60
36,940
YES
YES
YES
42.0
YES
YES
YES
CENTRIFUGAL
85.0
19.3
95.0
100% WATER
0.5989
0.3800
R-134a
0.00025
YES
P-X CT-X CH-X
ET-X
AS-X
SSF-X
MINIMUM CIRCUIT AMPACITY 40
PIPE TWO (2) 2" BACKFLUSH LINES TO LOCAL TRENCH DRAIN.
FACTORY CONTROL PANEL, MOUNTED TO SKID. WIRE ALARMS TO BAS.
CHILLED WATER COOLING COIL
MARK
SERVICE
TYPE
NUMBER OF COILS IN BANK
FLUID
PERFORMANCE
TOTAL CAPACITY (MBH)
LEAVING AIR DB/WB (°F)
AIR PRESSURE DROP (IN. W.G.)
CC-1
X-RTU-15
100% WATER
973.4
50.1 / 49.8
0.92
DRY WEIGHT (LBS) 738.9
NOTES:
1.
2.
3.
4.
CHILLED WATER COIL SHALL BE INSTALLED IN EXISTING RTU-15.
COORDINATE COIL SELECTION WITH RTU MANUFACTURER TO ENSURE FIT.
EXISTING UNIT IS YORK MODEL #XTO-84x96.
FIELD VERIFY REMOVAL OF EXISTING DX COIL AND INSTALLATION OF NEW
COIL CHILLED WATER COIL PRIOR TO SUBMITTING COIL.
CONNECT CHILLED WATER COIL PER DETAIL.
UNLESS NOTED OTHERWISE, CAPACITIES AND VALUES SHOWN ABOVE
ARE BANK TOTALS.
TOTAL WATER FLOW (GPM) 161.2
SENSIBLE CAPACITY (MBH) 642.0
ENTERING AIR DB/WB (°F) 80.0 / 66.5
ENTERING WATER TEMPERATURE (°F) 42.0
LEAVING WATER TEMPERATURE (°F) 54.0
MAXIMUM WATER PRESSURE DROP (FEET) 9.5
MAXIMUM FACE VELOCITY (FPM) 521
NUMBER OF ROWS / FINS PER INCH 8 / 11
CHILLED WATER
COOLING COIL
AIRFLOW (CFM) 20,500
RTU MINIMUM OUTDOOR AIR SETTING (CFM) 5,125
COIL SIZE (FIN HEIGHT x FIN WIDTH) 35.0" x 81.0" (EACH)
TOTAL FIN AREA (SQ. FT.) 39.375
COIL ARRANGEMENT (# HIGH x # WIDE) 2 x 1
CC-X
MINIMUM PRESSURE RATING (PSI) 150 150 150 150
ANTI-CAVITATION PLATE YES YES YES YES
4. PROVIDE FLOOR STAND.
4. PROVIDE BLADDER-TYPE TANK.
DIMENSIONAL DATA (BASIS OF DESIGN)
LENGTH X WIDTH X HEIGHT
OPERATING WEIGHT (LBS.)
14'-0" 8'-3" x 8'-8"14'-0" 8'-3" x 8'-8"14'-0" 8'-3" x 8'-8"14'-0" 8'-3" x 8'-8"
Revisions: Date:
GN
S S
A
ION EL
T
F EGE
P R O
R
SI NRE I
E E R
D
E
AT
S
ET
O
OI
HO
F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:5
:5
P M
M-602
MECHANICAL SCHEDULES CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 LDH CAB
BID & CONSTRUCTION
18902.00
NOTES:
1. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
2. MOUNT BOTTOM OF GRILLE AT 6" ABOVE FINISHED FLOOR. PAINT VISIBLE PORTION OF INSIDE DUCT FLAT BLACK.
MARK
STYLE
TYPE
AIR FLOW (CFM)
PERFORMANCE
STATIC PRESSURE (IN W.G.)
FAN SPEED (RPM)
NOISE LEVEL (SONES)
TYPE OF DRIVE
MOTOR
MOTOR SIZE (HP)
VOLTS-PHASE-HERTZ
GRAVITY BACKDRAFT DAMPER
ACCESSORIES
FACTORY DISCONNECT
NOTES
EF-1
UPBLAST
CENTRIFUGAL
11,500
0.75
BELT
3.0
460-3-60
YES
NO
1,2,3
ALUMINUM BIRDSCREEN YES
PAC-AHU-4
SUPPLY FAN
MARK
MINIMUM OUTDOOR AIR FLOW (CFM)
BRAKE HORSEPOWER
EXTERNAL STATIC PRESSURE (IN W.G.)
TOTAL CAPACITY (MBH)
SENSIBLE CAPACITY (MBH)
REFRIGERANT
NO. COMPRESSORS/TYPE
NO. CONDENSER FANS/DRIVE TYPE
DX COOLING
ENTERING AIR (DB/WB °F)
SUPPLY AIR FLOW (CFM)
OUTDOOR TEMPERATURE (° F)
VOLTS-PHASE-HERTZ
MINIMUM CIRCUIT AMPACITY
ELECTRICAL
MAX. OVERCURRENT PROTECTION (AMPS)
FEATURES OR ACCESSORIES
5 YEAR COMPRESSOR WARRANTY
FULL ECONOMIZER
PROGRAMMABLE THERMOSTAT
FACTORY UNIT MOUNTED, NON-FUSED DISCONNECT
NOTES:
1. SINGLE POINT POWER CONNECTION.
2. VARIABLE FREQUENCY DRIVE.
3. IAQ SLOPED, STAINLESS STEEL DRAIN PAN.
4. BUILT-IN RIGGING CAPABILITIES.
5. 304 STAINLESS STEEL HEAT EXCHANGER WITH 10-YEAR WARRANTY.
6. PROVIDE WITH TIME DELAY RELAY, ANTI-SHORT CYCLE TIMER, CONDENSER
COIL GUARD, HINGED SERVICE ACCESS DOORS.
7. CONDENSER FAN HEAD PRESSURE CONTROL.
8. SMOKE DETECTORS SHALL BE WIRED TO SHUT DOWN UNIT UPON DETECTION OF
SMOKE.
9. MOUNT AND ANCHOR ON MANUFACTURER'S ROOF CURB.
10. FILTER RESISTANCE (IN WG): CLEAN = 0.16, DIRTY = 0.50.
INPUT/OUTPUT (MBH)
HEATING SECTION (NATURAL GAS)
TYPE
2-INCH, 30% STANDARD SIZE THROWAWAY FILTERS
NO. OF STAGES
RPM
LEAVING AIR (DB/WB °F)
PRESSURE RANGE (IN. W.C.)
VERTICAL(BOTTOM)
RETURN AIR SMOKE DETECTOR
NO. SUPPLY FANS/DRIVE TYPE
SPRING ISOLATED FANS
MOTOR HORSEPOWER
AREA SERVED CHILLER
PLANT
EER/IEER
FULL PERIMETER ROOF CURB
OPERATING WEIGHT (LBS.)
BAROMETRIC PRESSURE RELIEF
BACNET COMMUNICATION
115V CONVENIENCE OUTLET, FACTORY WIRED
PACKAGED ROOFTOP UNITS
EXHAUST FANS
AIR DISTRIBUTION DEVICE (DIFFUSERS, REGISTERS AND GRILLES)
80.4 / 68.1
R-410A
4 / DIRECT
4 / SCROLL
307.0
11,500
475.62
460-3-60
YES
YESYES
YES
YES
2,500
800 / 648
YES
55.0 / 54.8
2.5" - 14"
YES
1 / BELT
YES
8.69
1.00
10.3/13.5
YES
CFMX
NECK
MARK TYPE
(INCHES)
FACE SIZE
COLORSTYLE MATERIAL NOTESFACTORY
DAMPER
(INCHES)
NECK SIZE
S1 26x20 - 124x18SUPPLY
GRILLE
DOUBLE DEFLECTION
SIDEWALL
WHITE STEEL
E1 36x36 - 1,234x34EXHAUST
GRILLE
SINGLE DEFLECTION
DUCT MOUNTED
WHITE STEEL
S2 20X14 - 118X12SUPPLY
GRILLE
DOUBLE DEFLECTION
SIDEWALL
WHITE STEEL
5,700
YES
YES
YES
NOTES:
1. INSTALL WITH MANUFACTURER'S ROOF CURB.
2. DISCONNECT BY EC.
3. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
EF-X
AHU-X
VARIABLE SPEED MOTOR CONTROLLER YES
LOCATION
FUEL OIL PUMP PACKAGE SCHEDULE
CIRCULATING FLUID
FLUID FUEL OIL
GPM
MOTOR (EACH)
NOMINAL
HP
1. BASIS OF SPECIFICATION: DUPLEX POSITIVE DISPLACEMENT PUMP PACKAGE WITH REDUNDANT PUMP CONTROLS.
2. REFER TO SPECIFICATIONS FOR REQUIRED ACCESSORIES.
3. PUMP MOTOR SHALL BE TEFC, INSULATION CLASS F, RATED FOR CONTINUOUS DUTY.
4. PROVIDE REDUNDANT CONTROLLER, INCLUDES CONTACTS, PLC AND BACNET INTERFACE FOR TRANSMISSION OF PUMP RUN SIGNALS AND ALARM INDICATIONS. TRANSFER LOGIC OPERATION SHALL TRANSFER
PUMP OPERATION WHEN NO FUEL FLOW IS SENSED VIA A REMOTE FLOW SWITCH AND THE EMERGENCY GENERATOR SET IS RUNNING.
5. PROVIDE DUAL POWER INLET, 460V-3Ø-60Hz, WITH POWER TRANSFER RELAY AND POWER AVAILABLE/CONNECTED/FAIL INDICATORS AND AUTOMATIC SWITCH OVER.
6. PROVIDE PUMP STARTERS FOR EACH PUMP. NEMA 4 ENCLOSED, UNIT MOUNTED, HINGE-OPEN FRONT DOOR, FULL-VOLTAGE, 3-PHASE CIRCUIT BREAKER COMBINATION MOTOR STARTER, WITH CONTROL POWER
TRANSFORMER, HOA SWITCH, RUN INDICATOR, POWER AVAILABLE INDICATOR.
7. ALL ALARMS SHALL BE COMMUNICATED WITH THE BAS VIA MODBUS COMMUNICATION.
8. THE CONTROL PANEL WILL SHOW THE FOLLOWING ALARMS ON THE LCD DISPLAY:
A. PUMP 1 NOT IN AUTO
B. PUMP 2 NOT IN AUTO
C. PUMP FLOW FAILURE
D. PUMP THERMAL OVERLOAD TRIP
E. PUMP SET LEAK
F. PUMP SET DIRTY STRAINER
G. EMERGENCY STOP ACTIVATED
H. PLC-A FAILURE
I. PLC-B FAILURE
9. THE AUDIBLE ALARM SHALL TRIP WHEN ANY OF THE FOLLOWING ALARMS ARE PRESENT:
A. PUMP FLOW FAILURE
B. PUMP THERMAL OVERLOAD TRIP
C. PUMP SET LEAK
D. EMERGENCY STOP ACTIVATED
SYSTEM TEMP.
°F (°C)
CHILLER
PLANT
(EC-114)
FTP-1
MARK
TYPE
HIGH LIFT IMO
3-SCREW
VOLTAGE
PHASE
460-3 3.450 80(27)
NO. 2
FUEL OIL
DISCHARGE
PRESSURE
(PSI)
EMERGENCY
GENERATORS
TYPE
DUPLEX POSITIVE
DISPLACEMENT
RPM
FULL LOAD
AMPS
PUMP BODY
CAST IRON
11. EQUIPMENT NUMBERING SHOWN IS FOR REFERENCE ONLY. COORDINATE FINAL
EQUIPMENT NUMBERING WITH VA COR DURING CONSTRUCTION.
ELECTRICAL
DIGITAL DISPLAY
ACCURACY
VOLTS-PHASE-HERTZ
FEATURES OR ACCESSORIES
TYPE M TRANSDUCER
BACNET IP - BUILDING CONTROLS NETWORK INTERFACE CARD
CLAMP ON TEMPERATURE SENSORS WITH MOUNTING KIT
PERMALOK TRACK TRANSDUCER MOUNTING SYSTEM
NOTES:
1.
2.
3.
4.
5.
6.
7.
PROVIDE FLOWMETER WITH SINGLE POINT POWER CONNECTION.
PROVIDE FACTORY REPRESENTATIVE TO UTILIZE PORTABLE FLOW METERS TO TEST
THE FLOW METER LOCATIONS TO DETERMINE THE OPTIMAL LOCATION.
PROVIDE FACTORY REPRESENTATIVE TO COMMISSION METERS.
PROVIDE ALL NECESSARY COMMUNICATION CARDS, FITTINGS, BRACKETS, JUNCTION
BOXES, CONDUIT, AND WIRE HARNESSES REQUIRED TO MOUNT AND CONNECT FLOW
METERS TO EXISTING TRANE CONTROL SYSTEM.
MINIMIZE INSULATION REMOVAL AND REPAIR ALL INSULATION ON…