18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-9.pdf
PDF 10 MB Posted
- Solicitation number
- 36C25023B0049
About this file
This document outlines a federal contract opportunity to construct a chiller plant for the Columbus VA Medical Center in Ohio. The solicitation number is 36C25023B0049 and was issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10. It is a set-aside for Service-Disabled Veteran-Owned Small Businesses. Responses are due on the date specified in the solicitation to provide construction services for a new chiller plant at the Columbus VAACC in Columbus, Ohio. The contract will be awarded based on the criteria established in the solicitation to the responsible offeror whose offer conforms to the solicitation and is most advantageous to the Government, considering only price and past performance. The period of performance and pricing terms are as specified in the solicitation documentation.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Design Interior
Engineering
LM
9.2
CE CFCC CDCA CB AA AB AC AD AEXC XD
FM
XR-SCHWP-1
XR-CH-1
XR-CH-2
XR-ET-3
XR-AS-3
XR-CHWP-1
XR-CHWP-2
XR-SCHWP-2
XR-CWP-1
XR-CWP-2
XR-VFD
X-UH
XR-VFD
XR-FM
X-DOMESTIC
WATER METER
X-BACKFLOW
PREVENTER
X-DOMESTIC
WATER PUMP
X-EF
X-DWH X-DWH
X-CP
C1DEA
X
PRIMARY
SWITCH
SUB
SS4
XFMR.
MAIN
BREAKER
FEEDER
BREAKERS
PRIMARY
SWITCH
SUB
SS2
XFMR.
MAIN
BREAKER
FEEDER
BREAKERS
FEEDER
BREAKERS
FEEDER
BREAKERS
FEEDER
BREAKERS
FEEDER
BREAKERS
FIRE PUMP TAP
EOMPARTMENT
FEEDER
BREAKERS
FEEDER
BREAKERS
FEEDER
BREAKERS
MAIN
BREAKER
MAIN
BREAKER
SUB
SS3
XFMR.
PRIMARY
SWITCH
PRIMARY
SWITCH
SUB
SS1
XFMR.
C1DNA
X
X X
X
X
X
C1SBEMA
ATS
ATS ATS
X
ATS-EQ
X
ATS-CR
ATS-LS
X
C1DSA
X
C1DCA
X
C1SBEA
X
1 2
1 2
X
X
X
X X
X X
X
TCP
X
TCP
X
X C1E2
VFD
XR
VFD
XR
XR-VFDXR-VFD
VFD
XR
VFD
XR
FUTURE
SUBSTATION
SS5
X-DAMPER
TYP
TYP
TYP
TYP
TYP
TYP
M-151AM-151B
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:4
P M
ED-102
PARTIAL MAIN BUILDING FIRST FLOOR
ELECTRICAL DEMOLITION PLAN - AREA A
CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00 1
CODED NOTES:
1 PROVIDE DIGITAL METER ON WATER COOLED CHILLER AT THE START OF THE PROJECT. METER SHALL HAVE DIGITAL DISPLAY AND CONNECT TO VA BMS COMPLETE. REMOVE COMPLETE WHEN THE CHILLERS
ARE DISCONNECTED. METER SHALL PROVIDE AT MINIMUM THE FOLLOWING POINTS: VOLTAGE,
INSTANEOUS POWER PER PHASE (KW, KVAR, AND KVA), INSTANTANEOUS AMPERAGE PER PHASE, AND PEAK DEMAND POWER PER PHASE (KW, KVAR, AND KVA). ASSUME (5) ADDITIONAL MONITORING POINTS TO
BE DETERMINED BY THE VA ENERGY ENGINEER. COORDINATE WITH VA COR.
REMOVE ALL EQUIPMENT UNLESS OTHERWISE NOTED. DISCONNECT EQUIPMENT AND REMOVE ALL
ASSOCIATED ELECTRICAL STARTERS, DISCONNECT SWITCHES, VFDs, CONDUIT, SUPPORTS, WIRING, ETC.
COMPLETE BACK TO THE SOURCE. LABEL EXISTING CIRCUIT BREAKERS AS SPARES.
DEMOLITION PHASING SEQUENCE
REFER TO MECHANICAL DRAWINGS FOR DEMOLITION PHASING SEQUENCE OF ITEMS IN EXISTING MECHANICAL
ROOMS.
ELECTRICAL DEMOLITION NOTES
D1 ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC. THAT
WILL NOT BE REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION SHALL INCLUDE ALL ELECTRICAL ITEMS SHOWN ON THIS PLAN THAT ARE DESIGNATED BY "XR" OR "XB" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE REMOVED IN ORDER TO PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED ELECTRICAL SYSTEMS COMPONENTS - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT
OF ALL DEMOLITION WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.
D2 ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER
SHALL BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.
D3 DASHED WALLS ON PLAN INDICATE EXISTING CONSTRUCTION TO BE REMOVED.
D4 REFER TO ELECTRICAL LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED XB, XRR OR XN, AND REMOVE/BLANK OFF, RELOCATE OR REPLACE
THESE COMPONENTS AS REQUIRED.
D5 MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY TO
ACHIEVE SAME.
D6 THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A TIMELY
MANNER.
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
PARTIAL MAIN BUILDING FIRST FLOOR
ELECTRICAL DEMOLITION PLAN - AREA A 1N
NOT TO SCALE
ACC 1ST FLOOR KEY PLAN
AREA A
AREA B
Revisions: Date:
FINAL BID & CONSTRUCTION 11/24/2021
FINAL BID & CONSTRUCTION (REVISED) 05/06/2022
Automated Line
E2E2 X
A
ELEC.
CLOSET
2BEC
STORAGE
2B261
POINT OF CARE
TRAINING
2B261
CORRIDOR
2B260
OFFICE
2B257
OFFICE
2B255
CORRIDOR
2B250
MEN'S LOCKER
2B256 MEN'S TOILET
2B256T
WOMEN'S LOCKER
2B258
WOMEN'S TOILET
2B258T
EXG TOILET
2B262
CORRIDOR
2A020
OFFICE
2B253
CORRIDOR
2B254
MECH
2B259
CONDUITS
CONTINUED
XRX X
A
W
W
V
V
X-CU
X-CU
X-RTU-14
XR-ACC
X-EF
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:5
P M
ED-103
PARTIAL MAIN BUILDING SECOND FLOOR
DEMOLITION PLAN
CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00 1
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
PARTIAL MAIN BUILDING SECOND FLOOR
ELECTRICAL DEMOLITION PLAN 2
NOT TO SCALE
ACC 2ND FLOOR KEY PLAN
N
CODED NOTES
DEMOLITION PHASING SEQUENCE
REFER TO MECHANICAL DRAWINGS FOR DEMOLITION PHASING SEQUENCE OF ITEMS IN AREA.
ELECTRICAL DEMOLITION NOTES
D1 ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC. THAT
WILL NOT BE REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION SHALL INCLUDE ALL ELECTRICAL ITEMS SHOWN ON THIS PLAN THAT ARE DESIGNATED BY "XR" OR "XB" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE REMOVED IN ORDER TO PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED ELECTRICAL SYSTEMS COMPONENTS - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT
OF ALL DEMOLITION WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.
D2 ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER
SHALL BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.
D3 DASHED WALLS ON PLAN INDICATE EXISTING CONSTRUCTION TO BE REMOVED.
D4 REFER TO ELECTRICAL LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED XB, XRR OR XN, AND REMOVE/BLANK OFF, RELOCATE OR REPLACE
THESE COMPONENTS AS REQUIRED.
D5 MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY TO
ACHIEVE SAME.
D6 THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A TIMELY
MANNER.
SPLICE AND EXTEND EXISTING CIRCUITS IN POINT OF CARE TRAINING ROOM 2B263 FROM PANEL 'E2E2' FOR CONNECTION OF NEW MECHANICAL CHILLED WATER PIPING. PROVIDE 32" x 4" x 2-1/8" PULLBOX WITH DIVIDERS INSIDE PULLBOX EVERY 4". EACH SECTION SHALL HAVE NO MORE THAN 8 CURRENT CARRYING WIRES WITH NO MORE THAN (2) CONDUITS PER SECTION. CONDUITS SHALL BE SPLICED AND EXTENDED TO ALLOW NEW MECHANICAL PIPING CONNECTION. PROVIDE CONDUIT AND WIRING EXTENSIONS. COORDINATE SINGLE, OFF- HOURS SHUTDOWN FOR ALL WORK IN THIS AREA. REFER TO MECHANICAL PLANS FOR ADDITIONAL
INFORMATION.
A
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
PARTIAL MAIN BUILDING
SURGERY ADDITION ROOF DEMOLITION PLAN 1N
CODED NOTES
REMOVE EXISTING AIR COOLED CHILLER AND ALL ASSOCIATED CONDUIT, WIRING, CONTROLS, CURBS, ETC.
COMPLETE TO THE SOURCE.
DELETE SCOPE OF WORK ON THIS SHEET.
BID ALTERNATE #4:
Revisions: Date:
5 5
A
AB
B
C
CD
D
E
E
F
F
G
G
H
H
J
J
K
K
3.8
0.2
0.5 0.5
0.8 0.8
A.2
A.2
A.1
A.1
A.8
A.8
0.7
B.4 B.4
X -R
T U
-1
X-ACH-1
X-ACH-2
X -R
T U
-1
X -R
T U
-7
X-RTU-9
X -R
T U
-6
X-RTU-8
X-RTU-15
X-RTU-12
X-GEF-5
X-TEF-7
X-TEF-5
X-GEF-6
X-TEF-6
XR-CU-15
X-CU-2X-CU-3
X -R
T U
-1
X-EF-7
X-EF-6
X-EF-2
X-EF-3
X-GEF-4 X-TEF-4
X-CU
ROOF
ROOF
CC-1
PENTHOUSE
X X X
X X
D3DEA
D3DEA
X X X X
X
XX
X
X
D D
N A
D D
E B
D C
A
D E
D
C
2 A3
A3
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:0
P M
ED-104
PARTIAL MAIN BUILDING THIRD FLOOR ROOF
ELECTRICAL DEMOLITION PLAN
CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00 1
CODED NOTES:
1 REMOVE ALL LIGHTING FIXTURES, RECEPTACLES, CONDUITS, ETC. THAT ARE MOUNTED TO EXISTING PARTITION WALL. REMOVE ALL ASSOCIATED CONDUITS, CONTROLS, WIRING, SUPPORTS, ETC. COMPLETE BACK TO THE SOURCE. MAINTAIN CONTINUITY TO CIRCUITS OUTSIDE OF THE PROJECT SCOPE AREA.
UPON INSTALLATION AND ACTIVATION OF NEW CHILLED WATER COIL IN EXISTING RTU-15, CONTRACTOR SHALL REMOVE EXISTING CONDENSING UNIT AND ALL ASSOCIATED CONDUITS, CONTROLS, WIRING, SUPPORTS, ETC. COMPLETE BACK TO THE SOURCE.
DEMOLITION PHASING SEQUENCE
REFER TO MECHANICAL DRAWINGS FOR DEMOLITION PHASING SEQUENCE OF ITEMS IN AREA.
ELECTRICAL DEMOLITION NOTES
D1 ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC. THAT
WILL NOT BE REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION SHALL INCLUDE ALL ELECTRICAL ITEMS SHOWN ON THIS PLAN THAT ARE DESIGNATED BY "XR" OR "XB" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE REMOVED IN ORDER TO PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED ELECTRICAL SYSTEMS COMPONENTS - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT
OF ALL DEMOLITION WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.
D2 ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER
SHALL BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.
D3 DASHED WALLS ON PLAN INDICATE EXISTING CONSTRUCTION TO BE REMOVED.
D4 REFER TO ELECTRICAL LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED XB, XRR OR XN, AND REMOVE/BLANK OFF, RELOCATE OR REPLACE
THESE COMPONENTS AS REQUIRED.
D5 MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY TO
ACHIEVE SAME.
D6 THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A TIMELY
MANNER.
NOT TO SCALE
ACC 3RD FLOOR/ROOF KEY PLAN
N
0' 8' 16' 32' 64'0' 8' 16' 32' 64'0' 8' 16' 32' 64'0' 8' 16' 32' 64'0' 8' 16' 32' 64'
1/16" = 1'-0"
PARTIAL MAIN BUILDING THIRD FLOOR
ELECTRICAL DEMOLITION PLAN 1
BID ALTERNATE #3:
A3 DELETE SCOPE OF WORK ASSOCIATED WITH RTU-15
Revisions: Date:
DN
UP
K
K
L
L
M
M
N
N
7.37.3
XA
XA
XC
XC XD
XR-CT-1 1 XR-CT-2 1
ELECT. RM
SY
STAIR NO. 2
4S002
MECHANICAL ROOM
4A011
CORRIDOR
4A009
ELEVATOR
MACHINE ROOM
4A010
UPS
4A008
BIOMED
4A013
STAIR NO. 6
4S006
CORRIDOR
4A007
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:1
P M
ED-105
PARTIAL MAIN BUILDING FOURTH FLOOR
ROOF ELECTRICAL DEMOLITION PLAN
CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00 1
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
PARTIAL MAIN BUILDING FOURTH FLOOR
ROOF ELECTRICAL DEMOLITION PLAN 1
N
ELECTRICAL DEMOLITION NOTES
D1 ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC. THAT
WILL NOT BE REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION SHALL INCLUDE ALL ELECTRICAL ITEMS SHOWN ON THIS PLAN THAT ARE DESIGNATED BY "XR" OR "XB" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE REMOVED IN ORDER TO PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED ELECTRICAL SYSTEMS COMPONENTS - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT
OF ALL DEMOLITION WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.
D2 ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER
SHALL BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.
D3 DASHED WALLS ON PLAN INDICATE EXISTING CONSTRUCTION TO BE REMOVED.
D4 REFER TO ELECTRICAL LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED XB, XRR OR XN, AND REMOVE/BLANK OFF, RELOCATE OR REPLACE
THESE COMPONENTS AS REQUIRED.
D5 MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY TO
ACHIEVE SAME.
D6 THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A TIMELY
MANNER.
CODED NOTES
1 EXISTING COOLING TOWER TO BE REMOVED. REMOVE ALL ASSOCIATED DISCONNECT, CONDUITS, WIRING, SUPPORTS, ETC COMPLETE BACK TO SOURCE. COORDINATE WORK ABOVE 3RD FLOOR CEILING WITH VA COR.
REMOVE ALL ASSOCIATED CONTROLS, HEAT TRACE, ETC. COMPLETELY.
DEMOLITION PHASING SEQUENCE
REFER TO MECHANICAL DRAWINGS FOR DEMOLITION PHASING SEQUENCE OF ITEMS IN AREA.
NOT TO SCALE
ACC 4TH FLOOR KEY PLAN
Revisions: Date:
J
J
X
X
X
X
X
X
X
X
X X
X
X
XR
X
XR
XR
XR
XR
XR
1 TYP
TYP
TYP
B.2 B.2
B.5 B.5
B.8 B.8
C.3 C.3
D.4 D.4
E.3 E.3
BOILER ROOM
CONTROL ROOM
STORAGE
21 3 4
0.2 0.2
0.5 0.5
0.8 0.8
IN-GRADE
ELECTRICAL BOX
X
PULLBOX
DC PANELBOARD
BATTERY RACK
PULLBOX
X
X
X
X
PSG - NORMAL
X
XR X
X
H1T1 P
S G
E
M E
R G
E N
C Y
P S
G C
O N
T R
O L S
X XX
X
X X
X
X X
X X
X
X X
X X
X
X
X
NGR
GENERATOR #2
EXISTING UNDER
PROJECT NUMBER:
757-20-205
X
2.7
B.4 B.4
5 A5
ALL DEVICES IN THE BOILER
PLANT ARE EXISTING TO
REMAIN, UNLESS OTHERWISE
NOTED.
E-103
H1E1-24
H1EA-2A - 1,3,5
A5
XRR
AIR COMPRESSOR
XX X X X
X
X
X
XXX
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:2
P M
ED-106
BOILER PLANT / CHILLER PLANT ELECTRICAL
DEMOLITION PLAN
CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00 3
CODED NOTES:
1 GROUND ROD - REFER TO DETAILS ON SUBSEQUENT SHEETS FOR ADDITIONAL INFORMATION.
GROUND CABLE FROM STRUCTURAL STEEL AND REBAR: 1#4/0 BARE COPPER. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. REFER TO TYPICAL STRUCTURAL STEEL GROUND DETAIL ON SUBSEQUENT SHEET
FOR ADDITIONAL INFORMATION.
COUNTERPOISE GROUND CABLE : 1#4/0 BARE COOPER.
REPLACE EXISTING PAGING SYSTEM AMPLIFIER WITH NEW IN THE SAME LOCATION. MAINTAIN EXISTING CIRCUIT, CONDUIT, ETC,. FOR RECONNECTION OF NEW PAGING SYSTEM AMPLIFIER. NEW AMPLIFIER SHALL BE COORDINATED WITH VA COR TO MATCH EXISTING PAGING SYSTEM SPECIFICATIONS. RECONNECT ALL
EXISTING PAGING CIRCUITS COMPLETE AND TEST OPERATION OF SYSTEM.
REMOVE EXISTING 2000kVA, 480V:13.2kV STEP-UP TRANSFORMER COMPLETE DURING DEMOLITION OF EXISTING 1750KW, 480V GENERATOR. DEMOLITION SHALL OCCUR AT THE END OF CONSTRUCTION AFTER NEW GENERATOR IS ACTIVATED, TESTED, AND IN-SERVICE. DEMOLISH CONDUIT AND CABLING FROM TRANSFORMER SECONDARY TO GENERATOR BREAKER. PRIMARY CABLING SHALL BE REMOVED FROM CONDUIT. TRANSFORMER PAD SHALL REMAIN. PRIMARY CONDUITS SHALL BE CAPPED AFTER PROVIDING NEW
PULLWIRE.
REMOVE CIRCUIT BACK TO THE SOURCE FOR CHEMICAL FEED PUMPS FOR INSTALLATION OF NEW MECHANICAL PIPING AND TRENCHING. CONTRACTOR IS RESPONSIBLE TO MAINTAIN EQUIPMENT TO CONNECT TO NEW CIRCUIT. PROVIDE NEW CIRCUIT OVERHEAD. REFER TO POWER PLAN (E-105) FOR ADDITIONAL
INFORMATION.
REMOVE CIRCUIT BACK TO THE SOURCE FOR OVERHEAD COILING DOOR FOR INSTALLATION OF NEW MECHANICAL PIPING AND TRENCHING. PROVIDE NEW CIRCUIT OVERHEAD. REFER TO POWER PLAN (E-105)
FOR ADDITIONAL INFORMATION.
RELOCATE EXISTING BOILER AIR COMPRESSOR AND ASSOCIATED DISCONNECT SWITCH, WIRING, CONDUIT, ETC. TO LOCATION INDICATED ON NEW PLANS. PROVIDE CONDUIT AND WIRING EXTENSIONS. REFER TO
POWER PLAN (E-105) FOR ADDITIONAL INFORMATION.
N
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0" 1
BOILER PLANT / CHILLER PLANT
ELECTRICAL DEMOLITION PLAN
BID ALTERNATE #5:
A5 DELETE SCOPE OF WORK ASSOCIATED WITH THE DEMOLITION OF THE EXISTING 1750KW EMERGENCY
GENERATOR.
ELECTRICAL DEMOLITION NOTES
D1 ALL EXISTING LIGHTING FIXTURES, RECEPTACLES, SPECIAL SYSTEMS OUTLETS, CONDUIT, WIRING ETC. THAT
WILL NOT BE REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION SHALL INCLUDE ALL ELECTRICAL ITEMS SHOWN ON THIS PLAN THAT ARE DESIGNATED BY "XR" OR "XB" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE REMOVED IN ORDER TO PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED ELECTRICAL SYSTEMS COMPONENTS - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND EXTENT
OF ALL DEMOLITION WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID SUBMITTAL.
D2 ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER
SHALL BE DISPOSED OF BY THE ELECTRICAL CONTRACTOR.
D3 DASHED WALLS ON PLAN INDICATE EXISTING CONSTRUCTION TO BE REMOVED.
D4 REFER TO ELECTRICAL LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED XB, XRR OR XN, AND REMOVE/BLANK OFF, RELOCATE OR REPLACE
THESE COMPONENTS AS REQUIRED.
D5 MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING ELECTRICAL SYSTEM COMPONENTS IN AREAS NOT BEING REMODELED UNLESS OTHERWISE NOTED. PROVIDE ALL CONDUIT AND WIRING EXTENSIONS NECESSARY TO
ACHIEVE SAME.
D6 THE ELECTRICAL CONTRACTOR SHALL CLOSELY COORDINATE ALL ELECTRICAL DEMOLITION WORK WITH THE GENERAL AND MECHANICAL CONTRACTORS, AND SHALL DISCONNECT ALL REQUIRED CIRCUITS IN A TIMELY
MANNER.
Revisions: Date:
S S
S
S
D
D
DD
D
D
D
D
CB
D
D
D
D D
D
EX GATE
EXISTING 4-STORY MEDICAL
BUILDING
CO
PROPERTY LINE
EX CHAIN LINK FENCE
EX 6" DIWATER PIPE
W
10" F 8" F.
LOOP
EX 4" GAS
F
F
UP
Tectonic Copyright 2007
CHILLER PLANT
EC-114
A41
EXISTING MAIN BUILDING
(NOT IN SCOPE UNLESS OTHERWISE NOTED)
EXISTING CHILLER AND ELECTRICAL ROOMS
(REFER TO SUBSEQUENT DRAWINGS)
PROJECT SCOPE
PROJECT SCOPE
P R
O J E
C T
S C
O P
E
P R
O J E
C T
S C
O P
E
E X
IS
T
IN
G U
N D
E R
G R
O U
N D
E L E
C T R
IC
A
L
(F E
E D
E R
S T
O A
N D
F R
O M
M A
IN
B U
IL
D
IN
G
A N
D E
X
IS
T
IN
G G
E N
E R
A T O
R
E X
IS
T
IN
G
U N
D E
R G
R O
U N
D E
L E
C T
R
IC
L
(F E
E D
E R
S T
O A
N D
F R
O M
M
IN
B U
IL
D
IN
G
A N
D E
X
IS
T
IN
G G
E N
E R
A T
O R
BOILER PLANT
E.3-5E.3-3.1 E.3-6
D.4-5D.4-3.1 D.4-6
C.3-5C.3-3.1 C.3-6
B.8-5B.8-3.1 B.8-6
B.5-5B.5-3.1 B.5-6
B.2-5 B.2-6
B-3
C-3
B-2
C-2
B-1
C-1
D-3D-2D-1
E-3E-2E-1
F-1
A.2-2A.2-1
G-1.8 G-3
B.4-4
B-4
A-4A-2.7
A.2-3A.2-2.6
B.4-3B.4-2B.4-1
A-1F-1 B-1C-1D-1E-1
A-2B-2C-2D-2F-2
A-3E-3
E-2
C-3
C-4
C-5 A-5
A-4
A-6C-6 B-6
A-7B-7C-7D-7
B-5
B-4
D-5F-5G-5
B-3D-3F-3
D-4
H-5
E-4
E-5
E-7
J-4 H-4 G-4 F-4
F-6G-6H-6
H-7 G-7 F-7
E-7.3F-7.3G-7.3H-7.3J-7.3
J-6
J-5
J-3
J-2
H-3 G-3
H-2 G-2
J-1 H-1 G-1
D-6
L-4.3
M-4.3
N-4.3
K-4.3
L-6.2
M-6.2
O-6
K-7
K-6.2
K-3
K-4
K-5L-5M-5
N-6.2
O-7Q-7
L-3M-3
O-5Q-5
Q-6
Q-4
K-9.2
L-9.2
M-9.2
L-4M-4
O-4.3
P-3(3' - 9 1/4")
Q-3(12' - 7 3/4")
K-8
M-7
M-9
M-8
N-3
N-5
N-4O-4P-4
P-5
P-6
P-7 L-7
Q-10
Q-9
Q-8 P-8
P-9
P-10 O-10
O-9
O-8 N-8
N-9
N-10
L-8
L-9
L-4.9
M-4.9
N-4.9
E-0.8 D-0.8 C-0.8
B-0.5 A-0.5
A.1-0.1
A.2-0.5
A.2-0.8A-0.8B-0.8
A.2-1 A.8-1
A.2-2 A.8-2
A.2-4 A.8-4
A.2-5 A.8-5
A-0.1
B-0.1
C-0.1
D-0.1
E-0.1
F-0.1
G-0.1
A.2-3 A.8-3
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:4
P M
E-101
PARTIAL ELECTRICAL SITE PLAN CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00
0' 10' 20' 40' 80'0' 10' 20' 40' 80'0' 10' 20' 40' 80'0' 10' 20' 40' 80'0' 10' 20' 40' 80'
1" = 20'-0"
PARTIAL ELECTRICAL SITE PLAN 1N
EXISTING UNDERGROUND
ELECTRICAL CONTINUED
BID ALTERNATE #3:
A4 DELETE SCOPE OF WORK ASSOCIATED WITH THE DEMOLITION OF THE EXISTING 1750KW EMERGENCY
GENERATOR.
CODED NOTE:
1 EXISTING 1750KW, 480V GENERATOR, ENCLOSURE, SUB-BASE TANK AND ALL ASSOCIATED EQUIPMENT AND ACCESSORIES SHALL BE DEMOLISHED COMPLETE. EXISTING GENERATOR SHALL REMAIN IN PLACE AND ACTIVE UNTIL NEW CHILLER PLANT GENERATOR IS ACTIVE AND COMMISSIONED. DURING DEMOLITION OF GENERATOR, WIRING SHALL BE REMOVED COMPLETE BACK TO SOURCE. EXISTING UNDERGROUND, CONCRETE-ENCASED DUCT BANK SHALL BE CAPPED AT BOTH ENDS AND MAINTAINED IN PLACE. PROVIDE PULL-WIRE IN CONDUITS PRIOR TO CAPPING. PROVIDE CONCRETE POLYMER IN-GRADE BOX AT EXTERIOR LOCATION, FLUSH WITH GRADE, AND TRIM CONDUITS BACK TO FIT WITHIN BOX TO REDUCE TRIPPING HAZARD. REFER TO BOILER
PLANT / CHILLER PLANT ELECTRICAL DEMOLITION PLAN FOR ADDITIONAL INFORMATION.
• CONTRACTOR SHALL REMOVE THE GENERATOR, SUB-BASE TANK, AND ALL ASSOCIATED COMPONENTS COMPLETE. THE VA WILL NOT BE PARTICIPATING IN ANY SALVAGE OR RECLAMATION EFFORTS.
• CONTRACTOR SHALL REMOVE THE EXISTING STEP-UP TRANSFORMER AND NEUTRAL GROUND RESISTOR WITHIN THE BOILER PLANT BETWEEN THE GENERATOR AND THE PARALLELING SWITCHGEAR. THE VA WILL NOT BE PARTICIPATING IN ANY SALVAGE OR RECLAMATION EFFORTS. REFER TO ED-106 FOR LOCATION OF
WORK
• CONTRACTOR SHALL REMOVE EXISTING CONDUCTORS BETWEEN GENERATOR AND TRANSFORMER.
EXISTING UNDERGROUND DUCT BANK SHALL REMAIN. PROVIDE A NEW SITE BOX AT THE FORMER GENERATOR LOCATION. STUB AND CAP THE EXISTING CONDUITS THE NEW BOX AND AT THE LOCATION
WHERE THE CONDUITS ENTER THE BOILER PLANT.
• CONTRACTOR SHALL REMOVE EXISTING CONDUIT AND CONDUCTORS BETWEEN THE STEP-UP
TRANSFORMER, THE NEUTRAL GROUND RESISTOR, AND THE PARALLELING SWITCHGEAR.
• CONTRACTOR SHALL BE RESPONSIBLE FOR ANY SYSTEM REPROGRAMMING REQUIRED TO REMOVE THE
EXISTING GENERATOR FROM THE SEQUENCE OF OPERATIONS.
Revisions: Date:
5 5
6 6
A
AB
B
C
CD
D
E
E
F
F
G
G
H
H
J
J
K
K
3.8
0.2
0.5 0.5
0.8 0.8
A.2
A.2
A.1
A.1
A.8
A.8
0.7
B.4 B.4 X
-R T
U -1
X-ACH-1
X-ACH-2
X -R
T U
-1
X -R
T U
-7
X-RTU-9
X -R
T U
-6
X-RTU-8
X-RTU-15
X-RTU-12
X-GEF-5
X-TEF-7
X-TEF-5
X-GEF-6
X-TEF-6
X-CU-2X-CU-3
X -R
T U
-1
X-EF-7
X-EF-6
X-EF-2
X-EF-3
X-GEF-4 X-TEF-4
X-CU
ROOF
ROOF
CC-1
PENTHOUSE
HEAT TRACE PANEL 1
HEAT TRACE PANEL 2
X X X
X X
D3DEA
D3DEA
X X X X
X
XX
D3CA - 13
D3CA - 15
X
X
D E
D
C
D D
N A
D D
E B
D C
A
HEAT TRACE CIRCUITS
1-A AND 1-B
HEAT TRACE CIRCUIT 1-B
HEAT TRACE CIRCUITS
2-A AND 2-B
HEAT TRACE CIRCUIT 2-B
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:0
P M
E-102
PARTIAL MAIN BUILDING THIRD FLOOR
ELECTRICAL PLAN
CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00 1
CODED NOTES:
1 HEAT TRACE CONTROL PANEL - 277V-1Ø, REFER TO M-504, DETAIL #1 FOR BASIS OF DESIGN WATTAGE PER FOOT. CONNECT COMPLETE TO PANEL AND CIRCUIT INDICATED ON PLANS PER MANUFACTURER'S WIRING DIAGRAMS. ROUTE HEAT TRACE CABLES PER MECHANICAL PIPING AND CONNECT COMPLETE AT BOTH ENDS.
POWER CONDUCTORS TO HEAT TRACE CONNECTION POINTS SHALL BE PROVIDED WITH NEW ROOF
SUPPORTS ON 5'-0" CENTERS AND ARE PERMITTED TO BE MOUNTED TO PIPING SUPPORTS WHERE AVAILABLE.
HEAT TRACE CONTROL PANEL CIRCUITS SHALL BE PROVIDED WITH INTEGRAL GROUND FAULT PROTECTION FOR EQUIPMENT. CONNECT COMPLETE TO SPARE 20A-1P CIRCUIT BREAKER IN PANEL INDICATED VIA 3/4"C- 2#
12 AND 1#12RG.
PROVIDE ADDITIONAL JUNCTION BOX WITH 3/4"C AND CAT6A CABLE FOR NETWORK CONNECTION TO PANEL.
ROUTE CAT6A CABLE TO NEAREST TELECOM ROOM #4A041 AND TERMINATE PER VA STANDARDS.
NOT TO SCALE
ACC 3RD FLOOR/ROOF KEY PLAN
MECHANICAL CONNECTIONS GENERAL NOTES
M1 CONNECT MECHANICAL EQUIPMENT PER MANUFACTURER'S WIRING DIAGRAMS AND DETAILS. NOTIFY ENGINEER
OF ANY DISCREPANCIES BETWEEN MANUFACTURER'S REQUIREMENTS AND BID DOCUMENTS PRIOR TO
INSTALLATION.
M2 CONCEAL CONDUIT AND WIRING IN WALLS AND ABOVE CEILING IN FINISHED AREAS.
M3 PROVIDE LIQUID-TIGHT FLEXIBLE METAL CONDUIT FOR FINAL CONNECTION TO MOTORS AND OTHER EQUIPMENT
THAT MAY PRODUCE VIBRATION.
M4 SEAL ALL EXTERIOR PENETRATIONS WATER-TIGHT.
M5 SEAL ALL WALL PENETRATIONS TO MAINTAIN FIRE RATINGS.
M6 PROVIDE LOCAL DISCONNECTING MEANS FOR MECHANICAL EQUIPMENT, UNLESS EQUIPMENT IS FURNISHED WITH INTEGRAL SAFETY SWITCHES. LABEL ALL SAFETY SWITCHES TO INDICATE POWER SOURCE AND
EQUIPMENT SERVED.
M7 COORDINATE EXACT INSTALLATION LOCATION OF ALL MECHANICAL EQUIPMENT WITH MECHANICAL PLANS
PRIOR TO ROUGH-IN.
M8 CONDUITS SHALL BE RIGID ALUMINUM AT EXTERIOR LOCATIONS.
M9 SHARED NEUTRALS ARE NOT PERMITTED FOR BRANCH CIRCUITS.
M10 REFER TO ONE LINE DIAGRAM FOR ALL FEEDER SIZES
0' 8' 16' 32' 64'0' 8' 16' 32' 64'0' 8' 16' 32' 64'0' 8' 16' 32' 64'0' 8' 16' 32' 64'
1/16" = 1'-0"
PARTIAL MAIN BUILDING
THIRD FLOOR ELECTRICAL PLAN 1N
Revisions: Date:
T ectonic Cop yright 2007
UP
Tectonic Copyright 2007
V F
D V
F D
V F
D V
F D
V F
D V
F D
V F
D
VFDVFD
V F
D V
F D
V F
D
B.2 B.2
B.5 B.5
B.8 B.8
C.3 C.3
D.4 D.4
E.3 E.3
21 3 4
0.2 0.2
0.8 0.8
CPDP2 CPDP1
PSG - NORMAL
X
X
NEW EMERGENCY
GENERATOR CUBICLE
FUTURE GENERATOR
CUBICLE LOCATION
NEW GENERATOR
CONTROLS CUBICLE
FUTURE GENERATOR
CONTROLS CUBICLE
X
X X
X X X X
X
X X
X X
X
X X
GENERATOR
FEEDER/CONTROLS
STUB-UP LOCATION
H1TS2
H1S2
(ABOVE)
X
X
H1EC
X
X
GENERATOR INTAKE
HOOD OVERHANG
GENERATOR #2
EXISTING UNDER
PROJECT NUMBER:
757-20-205
X
X
PULLBOX
X
DC PANEL
X
X
BATTERY RACK
IN-GRADE
ELECTRICAL
BOX
X
CHILLER PLANT
EC-114
PULLBOX
X
CH-4
CH-3
CH-2
CH-1
SSF-1
SSF
P-1
PP
P-2
PP
P-3
PP
P-4
PP
AS-1
AS
ET-1
ET
TP-1
TP
TP-2
TP
TP-3
TP
TP-4
TP
NEW NEW
BOILER ROOM
CONTROL ROOM
STORAGE
XNGR
NGR
H1S3
H1TS3
(ABOVE)
GENERATOR
FEEDER/CONTROLS
STUB-UP LOCATION
GENERATOR #3
NEW
NEW
H1ED
GENERATOR INTAKE
HOOD OVERHANG
H1C2 X
EXISTING
UNDERGROUND
CONDUIT
P S
G
E M
E R
G E
N C
Y
P S
G C
O N
T R
O L S
X
2.7
B.4 B.4
X X
E-105
FTP-1
HEAT TRACE
PANEL 5
TEMPERATURE
CONTROL PNL
TEMPERATURE
CONTROL PNL
TEMPERATURE
CONTROL PNL
TEMPERATURE
CONTROL PNL
FUEL SUPPLY
PUMP SET
WATER TREATMENT
CONTROL PANEL
REFRIGERANT
MONITOR PANEL
X
CHEMICAL
TREATMENT
TANKS
CT-1 CT-2
CT-3
CT-4
EF-1
P-1
P-2
P-3
P-4
TP-1
TP-2
TP-4
TP-3
ALL DEVICES IN THE BOILER PLANT
ARE EXISTING TO REMAIN,
UNLESS OTHERWISE NOTED.
HEAT TRACE
PANEL 4
HEAT TRACE
PANEL 3
E-103
E-202
DIVERTER VALVES
CONTROL PANEL
GENERATOR
DAY TANK 1
GENERATOR
DAY TANK 2
X
UP TO
SS-CP2
DOWN FROM
NPSS1
UP TO
SS-CP1
F U
E L D
E L
IV
E R
Y
M
S T
E R
A L A
M
P
N
E L
TEMPERATURE
CONTROLS ECC
LEAK
DETECTION
ALARM PANEL
FLOW METER
TEMPORARY
CHILLER
CONNECTIONS
BOX
D.4E.30.5 0.8
TEMPERATURE
CONTROL PANEL
TEMPERATURE
CONTROL PANEL
CONDUIT TO
GENERATOR
ANNUNCIATOR PANEL
3' - 0"
" 1
1' - 0"
EXHAUST
DUCT
EXHAUST
DUCT
EXHAUST
DUCT
GENERATOR
CONTROLS
PULLBOX
GENERATOR
POWER
PULLBOX
G E
N E
R A
T O
D
Y T
A N
K
EXHAUST
DUCT
GENERATOR
PANELBOARD
PULLBOXES
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:1
P M
E-103
BOILER PLANT / CHILLER PLANT ELECTRICAL
SITE PLAN
CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00 3
SITE PLAN GENERAL NOTES:
ALL SITE CONDUITS SHALL BE 18"-30" BELOW GRADE AND SHALL BE SCHEDULE 80 PVC CONDUITS (MIN. 1"C) UNLESS OTHERWISE NOTED. CONDUITS INSTALLED UNDER PAVED AREAS SHALL BE ENCASED IN CONCRETE -
3" MINIMUM COVER.
PROVIDE #8 AWG WIRING FOR ALL NEW SITE LIGHTING BRANCH CIRCUIT WIRING.
PROVIDE ALL TRENCHING, BACKFILL, SAW CUTTING, ETC. NECESSARY TO INSTALL NEW CONDUITS. PROVIDE ALL NECESSARY BACKFILL, GRAVEL, GRASS, CONCRETE, ASPHALT, ETC. TO RESTORE AREA TO EXISTING
CONDITION.
NEW ELECTRICAL CONDUIT LINES SHALL CROSS STORM SEWERS, GAS AND WATER LINES AT PERPENDICULAR
ANGLES AND SHALL NOT RUN ADJACENT TO THEM.
MAINTAIN 12" SEPARATION BETWEEN ELECTRICAL CONDUITS AND TELEPHONE LINES.
EXISTING UNDERGROUND UTILITY AND BRANCH CIRCUITS ARE SHOWN AT APPROXIMATE LOCATIONS FOR REFERENCE PURPOSES ONLY. CONTRACTOR SHALL IDENTIFY ALL UNDERGROUND SERVICE UTILITIES BY
HAND DIGGING PRIOR TO ANY EXCAVATION.
CONTRACTOR SHALL REPAIR ANY COOLING SYSTEM, IRRIGATION, DOMESTIC WATER, GAS LINES, ETC.
DAMAGED WHILE EXCAVATING AND RESTORE SYSTEMS TO EXISTING CONDITION.
THE CONTRACTOR SHALL NOTIFY OHIO UTILITIES PROTECTION SERVICE AT 1-800-362-2764 AT LEAST 48 HOURS PRIOR TO ANY EXCAVATING TO INSURE THAT PUBLIC UTILITIES WILL NOT BE DAMAGED BY CONSTRUCTION
WORK. MAKE ANY ADDITIONAL NOTIFICATIONS TO OTHER UTILITY SERVICES AS REQUIRED.
REFERENCE LANDSCAPE PLANS FOR LIMITS OF SITE WORK.
REFER TO SPECIFICATIONS FOR ANY ADDITIONAL REQUIREMENTS.
S1.
S2.
S3.
S4.
S5.
S6.
S7.
S8.
S9.
S10.
FEEDER ROUTING GENERAL NOTES:
ELECTRICAL FEEDER ROUTING LOCATIONS SHOWN ARE FOR BIDDING PURPOSE ONLY. CONTRACTOR SHALL COORDINATE EXACT ROUTING OF FEEDERS IN FIELD AND PROVIDE ALL JUNCTION BOXES, BENDS, OFFSETS, CONNECTORS, SUPPORTS, ETC. AS NECESSARY FOR A COMPLETE SYSTEM.
DRAWING DOES NOT SHOW ALL NEW FEEDERS. REFER TO POWER DISTRIBUTION ONE-LINE DIAGRAM FOR
ADDITIONAL FEEDER REQUIREMENTS.
REFER TO ELECTRICAL DETAILS DRAWINGS FOR UNDERGROUND CONDUIT INFORMATION.
F1.
F2.
F3.
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0"
BOILER PLANT / CHILLER PLANT
ELECTRICAL SITE PLAN 1N
CODED NOTES:
1 ROUTE CONDUIT TO NEW GENERATOR ANNUNCIATOR PANEL (REFER TO SHEET E-105) AND CONNECT COMPLETE. INSTALL NEW GENERATOR ALARM PANEL AT LOCATION INDICATED. COORDINATE WITH VA COR PRIOR TO ROUGH-IN. EXTEND POWER FROM LOCAL ALARM PANELS TO NEW ALARM PANEL AND CONNECT
COMPLETE. REFER TO GENERATOR CONTROLS DIAGRAM FOR ADDITIONAL INFORMATION.
GENERATOR #3 - 2MVA, 13.2KV-3Ø-3W - PROVIDE NEW EMERGENCY, DIESEL GENERATOR. PROVIDE NEW CONCRETE MOUNTING PAD PER STRUCTURAL PLANS, INSTALL NEW GENERATOR AND CONNECT COMPLETE NEW PARALLELING SWITCHGEAR AND CONTROLS. REFER TO ONE LINE DIAGRAM FOR ADDITIONAL
INFORMATION. NEW GENERATOR SHALL BE BY CATERPILLAR AND SHALL MATCH EXISTING 2MVA
GENERATOR. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION AND WORK REQUIREMENTS.
PROVIDE NEW EMERGENCY GENERATOR CIRCUIT BREAKER SECTION AND CONNECT COMPLETE TO EXISTING EMERGENCY PARALLELING SWITCHGEAR. NEW SECTION SHALL MATCH EXISTING GENERATOR SECTION (DRAW-OUT, POWER CIRCUIT BREAKER WITH ELECTRONIC POWER METER). EXISTING SWITCHGEAR IS RUSSELECTRIC. PROVIDE NEW RELAYS, ACCESSORIES, CONTROLLER UPGRADES, AND PROGRAMMING AS REQUIRED TO CONNECT NEW EMERGENCY GENERATOR COMPLETE. REFER TO ELECTRICAL ONE-LINE
DIAGRAM FOR ADDITIONAL INFORMATION AND WORK REQUIREMENTS.
PROVIDE NEW NEUTRAL GROUND RESISTOR (NGR) IN A OUTDOOR, NEMA 3R ENCLOSURE. PAD MOUNT NGR ADJACENT TO GENERATOR ENCLOSURE AND CONNECT COMPLETE TO CONCRETE-ENCASED GROUNDING
ELECTRODE (GENERATOR SUPPORT PAD) AND GENERATOR'S NEUTRAL CONNECTION.
NGR SHALL (BASIS OF PROJECT NUMBER: 757-20-205):
• BE 13.2KV RATED,
• BE 76.2 OHMS RESISTANCE,
• BE 100A CURRENT RATING,
• HAVE 15KV (200:5 RATIO) CURRENT TRANSFORMER,
• HAVE MAXIMUM ON TIME OF 10 SECONDS,
• HAVE MAXIMUM TEMPERATURE RISE OF 760 DEG C.
• HAVE AN ENCLOSURE HEATER (APPROX. 100W FOR CONDENSATION) MITIGATION
CONTRACTOR SHALL RETAIN RUSSELECTRIC FOR PROGRAMMING OF THE NEW PARALLELING SWITCHGEAR
SECTION AND REPROGRAMMING OF THE EXISTING PARALLELING SWITCHGEAR TO CONNECT NEW
EMERGENCY GENERATOR COMPLETE AND PARALLEL/LOAD SHARE WITH EXISTING GENERATOR.
ROUTE POWER AND CONTROL CONDUITS FROM CEILING SPACE OF EXISTING BOILER AND CHILLER PLANT, DOWN WALL TO BELOW CONCRETE SLAB AND OVER TO STUB-UP LOCATION WITHIN GENERATOR
ENCLOSURE. COORDINATE EXACT STUB-UP LOCATION WITH GENERATOR MANUFACTURER PRIOR TO ROUGH-IN. SLEEVE CONDUITS THROUGH SLAB FOOTERS AS REQUIRED. CONDUITS AND BOXES SHALL BE MOUNTED AS HIGH AS POSSIBLE IN CEILING SPACE. PULLBOXES SHALL BE SIZED PER NEC. PROVIDE (4) FLEXIBLE INNER DUCTS IN CONTROLS CONDUITS TO SEPARATE CONTROLS BY TERMINATION LOCATION AND
PRESERVE SPACE FOR FUTURE PULLS. PROVIDE PULL WIRE IN SPARE INNER DUCT(S).
PROVIDE CONDUIT AND WIRING AS INDICATED ON GENERATOR CONTROL DIAGRAM ON E-603 FOR CONNECTION TO FUEL OIL TRANSFER SYSTEM. TERMINATE CONDUIT TO FUEL OIL TRANSFER SYSTEM. REFER TO ONE LINE DIAGRAM ON E-602 AND MECHANICAL CONNECTION SCHEDULE FOR ADDITIONAL INFORMATION.
PROVIDE FEEDERS FROM EXISTING EQUIPMENT PANELBOARD 'H1EB' AND LIFE SAFETY PANELBOARD 'H1SA' TO NEW PANELBOARD AND TRANSFORMER, RESPECTIVELY, THAT ARE PROVIDED WITH GENERATOR ENCLOSURE. REFER TO ONE-LINE DIAGRAM FOR FEEDER SIZING. COORDINATE STUB UP LOCATION WITH
GENERATOR MANUFACTURER.
FUEL OIL CONTROL WIRING FROM EXISTING GENERATOR #2 PROVIDED UNDER A SEPARATE CONTRACT TO THIS POINT. SPLICE AND EXTEND CONDUIT AND WIRING AS INDICATED ON GENERATOR CONTROL DIAGRAM
ON E-603. TO NEW GENERATOR FUEL OIL TRANSFER SYSTEM AND CONNECT COMPLETE PER
MANUFACTURER'S WIRING DIAGRAMS.
PROVIDE 36"SQ. x 12"D (MINIMUM) NEMA 1 RATED PULLBOX FOR GENERATOR POWER IN LOCATION INDICATED ON PLANS. PULLBOX IS SIZED BASED ON A MEDIUM VOLTAGE CABLE WITH A 1" OUTER DIAMETER.
THE CONTRACTOR IS RESPONSIBLE TO VERIFY THE OUTER DIAMETER OF THE APPROVED MEDIUM VOLTAGE CONDUCTOR PRIOR TO CONSTRUCTION AND MODIFY PULLBOX SIZE AS REQUIRED PER NEC. BOX SHALL BE SIZED SUCH THAT THE DISTANCE BETWEEN THE EXIT AND ENTRY CONDUITS MUST BE 36x THE
CABLE DIAMETER. COORDINATE THE EXACT CONDUIT ROUTE PRIOR TO INSTALLATION.
PROVIDE 36"SQ. x 12"D (MINIMUM) NEMA 1 RATED PULLBOX FOR GENERATOR CONTROL WIRING IN LOCATION INDICATED ON PLANS. PROVIDE FLEXIBLE INNER DUCT IN CONTROLS CONDUITS TO SEPARATE CONTROLS BY TERMINATION LOCATION AND PRESERVE SPACE FOR FUTURE PULLS. PROVIDE PULL WIRE IN
SPARE INNER DUCT(S). COORDINATE THE EXACT CONDUIT ROUTE PRIOR TO INSTALLATION.
PROVIDE 12"SQ. x 6"D (MINIMUM) NEMA 1 RATED PULLBOX FOR PANELBOARD FEEDERS IN LOCATION
INDICATED ON PLANS. COORDINATE THE EXACT CONDUIT ROUTE PRIOR TO INSTALLATION.
CONDUIT ROUTING INDICATED FOR REFERENCE ONLY. CONTRACTOR IS RESPONSIBLE FOR SUBMITTING CONDUIT ROUTING COORDINATION DRAWINGS WITH ELECTRICAL EQUIPMENT SUBMITTAL FOR APPROVAL. ROUTING DRAWINGS SHALL INCLUDE FIELD VERIFIED ROUTING, BENDS, PULLBOXES, CONDUIT BODIES, PENETRATIONS, ETC. ALONG WITH NEW SYSTEMS (MECHANICAL, ELECTRICAL, PLUMBING, STRUCTURAL, ETC.) CONTRACTOR SHALL INCLUDE EXISTING CONDITIONS WHERE NECESSARY TO CONVEY ROUTING INFORMATION. MAINTAIN NEC REQUIRED ACCESSIBILITY TO ALL EXISTING PULLBOXES, JUNCTION BOXES, ETC. TO REMAIN. ELECTRICAL EQUIPMENT
SUBMITTAL WILL NOT BE APPROVED WITHOUT CONDUIT ROUTING DRAWINGS.
CONDUIT ROUTING GENERAL NOTE
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0"
EQUIPMENT CONDUIT SECTION VIEW 2
UNDERGROUND
ABOVE GROUND
CONDUIT LEGEND
Revisions: Date:
F
F
F
F
F
LVF
F
TS WF
L V
LV
RC
F
F
AA
A A A
A A A
AA
A A a
H1SA -4
D
DX
H1CA -15,a
H1CA -15,aH1CA -15,a
H1SA -4
H1SA -4 H1CA -15,a
H1SA -4 H1CA -15,a
H1CA -15,a
H1CA -15,a
H1SA -4
CPDP2 CPDP1
a
H1CA -15,a
A a
NEW
SECTION
EL
EL
EL
EL
EL
H1CA -15
H1CA -15
H1CA -15
H1CA -15
H1CA -15
A
B.2 B.2
B.5 B.5
B.8 B.8
C.3 C.3
D.4 D.4
E.3 E.3
H1CA -15,a
H1SA -4
H1SA -4
a
PSG - NORMAL
P S
G C
O N
T R
O L S
X
X
P S
G
E M
E R
G E
N C
Y
NEW
CONTROLS
X
EL
H1CA -15
21 3 4
0.2 0.2
0.5 0.5
0.8 0.8X X X X X X
XX
X
X
X
XX
X X
X
X
FUTURE
CONTROLS
FUTURE
SECTION
X
XX
X
X
X
X
GENERATOR #2
EXISTING UNDER
PROJECT NUMBER:
757-20-205
GENERATOR #3
NEW
NEW NEW
NL
NL
NL
NL
NL
STORAGE
CONTROL ROOM
BOILER ROOM
2.7
B.4 B.4
TYP
TYP
X
H1SA -4
TYP
TYP
TYP
TYP
96"
96"
E-105
NEWNEW
B 156"
D 96"
EL EL
H1S3
H1ED
NEW
NEW
120"
120"
120"
120"120"
120"
ALL DEVICES IN THE BOILER
PLANT ARE EXISTING TO
REMAIN, UNLESS OTHERWISE
NOTED.
TYP
TYP
H1CA -15
E-202
D 96"
D 96"
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:2
P M
E-104
BOILER PLANT / CHILLER PLANT LIGHTING AND
FIRE ALARM PLAN
CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00 3
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0" 1
BOILER PLANT / CHILLER PLANT
LIGHTING AND FIRE ALARM PLAN
N
LIGHTING GENERAL NOTES
L1 REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR FINAL LOCATION OF ALL NEW CEILING MOUNTED
LIGHTING FIXTURES. CLOSELY COORDINATE LOCATION OF LIGHTING FIXTURES AND SMOKE DETECTORS WITH HVAC DUCTS, DIFFUSERS, SPRINKLERS, PLUMBING, ETC. AND ADJUST LOCATIONS OF SELECTED ELECTRICAL
EQUIPMENT IN ACCORDANCE WITH ENGINEER'S INSTRUCTIONS.
L2 REFER TO THE ARCHITECTURAL PLANS FOR EQUIPMENT LAYOUT. CLOSELY COORDINATE THE EXACT LOCATION OF ALL OUTLETS AND DEVICES WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AND MOUNTING HEIGHTS WHERE NECESSARY TO PREVENT INTERFERENCE WITH FURNITURE, FIXED CASEWORK, EQUIPMENT, ETC. VERIFY ALL CHANGES PRIOR TO ROUGH-IN.
L3 REFER TO ELECTRICAL DETAILS PLANS FOR OCCUPANCY SENSOR WIRING DIAGRAMS AND PROGRAM SCHEDULE
FOR ADDITIONAL INFORMATION.
L4 A DEDICATED NEUTRAL SHALL BE PROVIDED FOR EACH AND EVERY 120V AND 277V BRANCH CIRCUIT. MULTIWIRE
BRANCH CIRCUITS WITH SHARED NEUTRALS ARE NOT PERMITTED.
L5 NO MORE THAN (3) SINGLE-PHASE BRANCH CIRCUITS SHALL BE INSTALLED IN ANY ONE CONDUIT. DIFFERENT POWER SYSTEMS (NORMAL, CRITICAL, LIFE SAFETY) SHALL NOT BE INSTALLED IN THE SAME CONDUIT.
CODED NOTES:
1 CONNECT LIFE SAFETY LIGHTING FIXTURES AND EXIT SIGNS TO PANEL AND CIRCUIT INDICATED ON PLANS
COMPLETE VIA 3/4"C - 2#12 AND 1#12EG.
MOUNT LIGHTING FIXTURE BELOW MECHANICAL PIPING AND DUCTWORK. COORDINATE LIGHTING FIXTURE HEIGHT WITH MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN AND CONNECT COMPLETE TO PANEL AND
CIRCUIT INDICATED ON PLANS VIA 3/4"C - 2#12 AND 1#12EG.
PROVIDE NEW EXTERIOR LIGHTING FIXTURE ABOVE BOILER PLANT/CHILLER PLANT DOORS AND GENERATOR PAD AS SHOWN. LIGHTING FIXTURE SHALL MATCH EXISTING EXTERIOR LIGHTING FIXTURE AND SHALL BE MOUNTED AT THE SAME HEIGHT AND CONNECT COMPLETE TO EXISTING LIGHTING CONTROLS AND CIRCUIT.
EXISTING BOILER PLANT LIGHTING IS CONTROLLED BY EXISTING LIGHTING CONTROL PANEL IN ELECTRICAL
ROOM 109.
CONNECT CHILLER PLANT LIGHTING TO EXISTING BOILER PLANT LIGHTING CONTROL PANEL. EXISTING EQUIPMENT IS WATTSTOPPER. USE EXISTING SPARE RELAYS FOR LIGHTING CONTROLS AND CONNECT COMPLETE TO PANEL AND CIRCUIT INDICATED ON PLANS VIA 3/4"C - 2#12 AND 1#12EG. REFER TO LIGHTING
CONTROL PANEL FOR ADDITIONAL INFORMATION.
FIRE ALARM GENERAL NOTES
F1. ALL FIRE ALARM SYSTEM DEVICES SHALL BE CONNECTED COMPLETE TO THE MAIN FIRE ALARM SYSTEM
CONTROL PANEL IN ACCORDANCE WITH ENGINEER APPROVED MANUFACTURER'S SHOP DRAWING WIRING
DIAGRAMS AND DETAILS.
F2. ALL FIRE ALARM SYSTEM CONDUCTORS SHALL BE INSTALLED IN 3/4" MINIMUM SIZE CONDUIT SYSTEM.
F3. IN GENERAL ALL MANUAL PULL STATIONS SHALL BE INSTALLED AT 48" ABOVE FINISHED FLOOR. MANUAL PULL STATIONS SHALL BE INSTALLED WITHIN 5'-0" OF ALL EXIT DOORWAY OPENINGS AT EACH EXIT ON EACH FLOOR.
ADDITIONAL MANUAL PULL STATIONS SHALL BE PROVIDED SO THAT THE TRAVEL DISTANCE TO THE NEAREST
PULL STATION WILL NOT EXCEED 200' MEASURED HORIZONTALLY ON THE SAME FLOOR.
F4. ALL AUDIO/VISUAL AND VISUAL ONLY FIRE ALARM SYSTEM DEVICES SHALL BE ADA TYPE. IN ALL CASES VISUAL DEVICES SHALL BE WALL MOUNTED AT 80" ABOVE FINISHED FLOOR. VISUAL DEVICES SHALL BE LOCATED NOT MORE THAN 15' FROM THE END OF ALL CORRIDORS WITH A SEPARATION NOT GREATER THAN 100' BETWEEN DEVICES. AUDIO DEVICES SHALL BE INSTALLED THROUGHOUT THE BUILDING TO ATTAIN MINIMUM DECIBEL LEVELS REQUIRED BY CODE. COMBINATION AUDIO/VISUAL DEVICES AND ADDITIONAL VISUAL ONLY DEVICES
SHALL BE INSTALLED AT LOCATIONS AS INDICATED ON FLOOR PLANS.
F5. IN GENERAL SMOKE DETECTORS SHALL BE INSTALLED ON CEILINGS WITH SPACING NOT TO EXCEED
MANUFACTURER'S RECOMMENDATION.
F6. SPRINKLER SYSTEM WATERFLOW ALARM INITIATING DEVICES SHALL BE CONNECTED COMPLETE TO THE FIRE
ALARM SYSTEM.
F7. DUCT TYPE SMOKE DETECTORS SHALL BE PROVIDED FOR ALL HVAC RETURN AIR SYSTEMS WITH DESIGN CAPACITY GREATER THAN 2,000 CFM. WHERE RETURN AIR RISERS SERVE TWO OR MORE STORIES, AND ARE PART OF A RETURN AIR SYSTEM HAVING A DESIGN CAPACITY GREATER THAN 15,000 CFM, DUCT DETECTORS SHALL BE PROVIDED AT EACH STORY. COORDINATE EXACT DETECTOR LOCATIONS AND PROVISION OF
ADEQUATE DUCT LENGTHS WITH THE MECHANICAL CONTRACTOR PRIOR TO ROUGH-IN.
F8. PROVIDE ALL FIRE ALARM SYSTEM COMPONENTS NECESSARY FOR SHUT DOWN OF HVAC EQUIPMENT BY THE
FIRE ALARM SYSTEM WHERE SAME IS REQUIRED.
F9. PROVIDE ALL FIRE ALARM SYSTEM COMPONENTS NECESSARY FOR ELEVATOR CAPTURE BY THE FIRE ALARM
SYSTEM WHERE SAME IS REQUIRED.
F10. SMOKE DETECTORS SHALL BE INSTALLED WITHIN 5'-0" OF CENTERLINE OF SMOKE DOORS ON HOLD-OPEN.
F11. SMOKE DETECTORS SHALL NOT BE LOCATED CLOSER THAN 3'-0" FROM AN AIR SUPPLY DIFFUSER.
F12. AUTOMATIC DOORS LOCATED ON A 2-HOUR FIRE RATED WALL SHALL HAVE A FIRE ALARM INTERFACE THAT INTERRUPTS 120V POWER FOR THE AUTOMATIC DOOR OPENER UNDER A FIRE ALARM CONDITION. PROVIDE (1) CONTROL MODULE FROM EACH BUILDING FIRE ALARM SYSTEM IF LOCATED ALONG THE BORDER OF TWO
BUILDINGS.
F13. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ADDITIONAL AUDIBLE NOTIFICATION APPLIANCES AS REQUIRED TO ACHEIVE NFPA 72 REQUIREMENT FOR SOUND LEVELS A MINIMUM OF 15db ABOVE AMBIENT.
ADDITIONAL LOCATIONS SHALL BE NOTED AND ESTIMATED SOUND PRESSURE LEVEL OF SYSTEM IN CHILLER
PLANT SHALL BE STATED ON SHOP DRAWING SUBMITTAL FOR REVIEW.
F14 CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING FIRE WATCH FOR ANY FIRE ALARM OR SPRINKLER SHUTDOWN GREATER THAN FOUR HOURS. ALL SHUTDOWNS MUST BE DONE OFF HOURS AND SCHEDULED (21) DAYS IN ADVANCE IF LESS THAN (8) HOURS. ANY SHUTDOWN GREATER THAN (8) HOURS SHALL BE SCHEDULED
(40) DAYS IN ADVANCE.
Revisions: Date:
P
P
P
P
W
W
W
D1
D1
PR
PR
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
C1
J
J
C2
C2
C1
J
J
JJ
J
E-105
PSG - NORMAL
P S
G C
O N
T R
O L S
E-105
X
X
WP
H1N1-28
H1N1-30
H1N1-28
H1N1-28
H1N1-28
H1N1-30
H1N1-32
WP
WP
H1N1-32
H1N1-32
X
H1N1-30
H1N1-30
H1N1-32
WP
B.2 B.2
B.5
B.5
B.8
B.8
C.3 C.3
D.4 D.4
E.3 E.3
P S
G
E M
E R
G E
N C
Y
X
NEWNEW
ALL DEVICES IN THE BOILER
PLANT ARE EXISTING TO
REMAIN, UNLESS OTHERWISE
NOTED.
21 3 4
0.2
0.5
0.8 X
X X X X
X
X X X
X X
X
X X
XX
X
NEW
SECTION
NEW
CONTROLS
FUTURE
CONTROLS
FUTURE
SECTION
PULLBOX
DC PANELBOARD
BATTERY RACK
X
X
X
GENERATOR #2
EXISTING UNDER
PROJECT NUMBER:
757-20-205
GENERATOR #3
NEW
X
X
CPDP2 CPDP1
BOILER ROOM
CONTROL ROOM
STORAGE
2.7
B.4
X
H1N1-34
DOOR
X NEW
TYP
NGR
H1S3-10
H1E1-33
H1E1-31
WP
H1N1-32
TYP
TYP
TYP
HEAT TRACE
PANEL 5
HEAT TRACE
PANEL 4
HEAT TRACE
PANEL 3
H1E1-26
CHEMICAL
FEED PUMP
X
X
X
X
XXX
X X
XX
E-202
H1ED
H1S3
XL
COMPRESSOR
H1EB-26,28,30
H1S3-11
H1S2
H1EC
H1S2-9
TCP
TCP
TCP
TCP
DAY TANK CONTROLLERS
DOOR
TEMPORARY
CHILLER
CONNECTIONS
BOX
H1E1-35
RMP
D.4
0.8
UPS-1
H1TS1
H1S1 H1SA
LIGHTING CONTROL PANEL
LIGHTING CONTROL PANEL
H1EA SEC 1 H1E1 H1EB
H1TE1
H1N1 H1NA
H1TN1
H1CA
H1C1
H1TC1
X
X
X X X X X X
X X
X
X
XX
XX
X
2.7
ELEC. ROOM
H1EA SEC 2
H1C2 4 5 6
7 8
X
X X
X X
X X XN
B.2
32.7
TELE/ DATA ROOM
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:3
P M
E-105
BOILER PLANT / CHILLER PLANT POWER AND
TECHNOLOGY PLAN
CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00 3
0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'0' 4' 8' 16' 32'
1/8" = 1'-0" 1
BOILER PLANT / CHILLER PLANT
POWER AND TECHNOLOGY PLAN
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0" 2 Enlarged Electrical Room 109
0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'
1/4" = 1'-0" 3 Enlarged Telecom Room 104
CODED NOTES:
1 PROVIDE NEW GENERATOR REMOTE ANNUNCIATOR ALARM PANEL. COORDINATE WITH VA COR PRIOR TO ROUGH-IN. EXTEND POWER FROM LOCAL ALARM PANELS TO NEW ALARM PANEL AND CONNECT COMPLETE.
EXISTING GENERATOR REMOTE ALARM PANEL.
EXISTING PARALLELING SWITCHGEAR REMOTE ALARM PANEL. PROVIDE MODIFICATIONS AS REQUIRED TO
ACCOMMODATE NEW GENERATOR.
EXISTING CCTV CONTROL PANEL.
EXISTING CATV AMPLIFIER.
PROVIDE NEW PAGING SYSTEM AMPLIFIER AT LOCATION AND CONNECT COMPLETE TO NEW SPEAKERS WITHIN PROJECT AREA. EXTEND EXISTING PAGING SYSTEM CIRCUIT OUTSIDE OF THE PROJECT AREA TO THE NEW PAGING SYSTEM AMPLIFIER. CONNECT COMPLETE TO EXISTING PAGING ELECTRICAL CIRCUIT. VA
SHALL PROVIDE AMPLIFIER REQUIREMENTS TO MATCH SYSTEM UPGRADE.
EXISTING INTERCOM CONTROL PANEL.
EXISTING ACCESS CONTROL PANEL.
MOTOR OPERATED DOOR - 120V-1Ø-3/4HP, PROVIDE POWER FOR NEW MOTOR OPERATED DOOR AND CONTROL BOX. CONNECT COMPLETE VIA 3/4"C - 2#12 AND 1#12EG PER MANUFACTURE'S WIRING DIAGRAM.
COORDINATE EXACT LOCATION OF CONTROL BOX IN FIELD PRIOR TO ROUGH-IN.
EXISTING SIMPLEX-GRINNELL FIRE ALARM CONTROL PANEL
PROVIDE NEW SOFTWARE LICENSES AS REQUIRED FOR ALL NEW VIDEO SURVEILLANCE CAMERAS AND
CARD READER DEVICES.
PROVIDE 120V-50A NEMA 5-50R RECEPTACLE FOR WELDING EQUIPMENT. COORDINATE LOCATION WITH VA
COR PRIOR TO ROUGH-IN AND CONNECT COMPLETE VIA 3/4"C - 2#6 AND 1#10EG.
PROVIDE DATA OUTLET FOR ALL MECHANICAL EQUIPMENT CONTROL PANELS. ROUTE CAT6A CABLE TO TELE/DATA ROOM 104 FOR BUILDING AUTOMATION SYSTEM MONITORING. TERMINATE PER VA STANDARDS.
PROVIDE NEW CIRCUIT FOR OVERHEAD COILING DOOR, 15A-3P-3/4HP-480V-3PH RECONNECT COMPLETE TO CIRCUIT AND PANEL INDICATED ON PLAN VIA 3/4"C - 3#12 AND 1#12. PROVIDE WIRING FOR INTERIOR AND
EXTERIOR CONTROL STATIONS, SAFETY DEVICES AND ANCILLARY DEVICES FOR A COMPLETE
INSTALLATION.
PROVIDE NEW CIRCUIT FOR CHEMICAL FEED PUMP(S). RECONNECT COMPLETE TO CIRCUIT AND PANEL
INDICATED ON PLAN VIA 3/4"C - 3#12 AND 1#12.
MOUNT PANELBOARDS ON STRUT SUPPORT SYSTEM.
PROVIDE CIRCUIT FOR NEUTRAL GROUND RESISTOR (NGR) HEATER AND CONNECT TO PANEL AND CIRCUIT INDICATED ON PLAN VIA 3/4"C - 2#12 AND 1#12 EG. REFER TO ELECTRICAL SITE PLAN FOR ADDITIONAL
INFORMATION.
NEW LOCATION FOR EXISTING BOILER AIR COMPRESSOR. COORDINATE EXACT LOCATION WITH VA COR PRIOR TO ROUGH-IN. RELOCATE EXISTING DISCONNECTING MEANS ALONG WITH EQUIPMENT. REFER TO
DEMOLITION PLAN FOR ADDITIONAL INFORMATION.
PROVIDE 120V-20A DEDICATED CIRCUIT FOR FUEL POLISHER. MOUNT PANEL ON STRUT SUPPORTS IN GENERATOR VESTIBULE. COORDINATE LOCATION WITH VA COR PRIOR TO ROUGH-IN AND CONNECT
COMPLETE TO PANEL AND CIRCUIT INDICATED ON PLANS VIA 3/4"C - 2#12 AND 1#12EG.
PROVIDE 120V-20A DEDICATED LIFE SAFETY CIRCUIT FOR EMERGENCY GENERATOR FUEL DELIVERY SYSTEM MASTER ALARM AND DATA COMMUNICATION PANEL. COORDINATE LOCATION WITH VA COR PRIOR TO ROUGH-IN AND CONNECT COMPLETE TO PANEL AND CIRCUIT INDICATED ON PLANS VIA 3/4"C - 2#12 AND 1
#12EG. REFER TO FUEL OIL TRANSFER PUMP PACKAGE.
POWER GENERAL NOTES
P1 REFER TO THE ARCHITECTURAL PLANS FOR EQUIPMENT LAYOUT. CLOSELY COORDINATE THE EXACT LOCATION
OF ALL OUTLETS AND DEVICES WITH ARCHITECTURAL ELEVATIONS. ADJUST LOCATIONS AND MOUNTING HEIGHTS WHERE NECESSARY TO PREVENT INTERFERENCE WITH FURNITURE, FIXED CASEWORK, EQUIPMENT, ETC. VERIFY ALL CHANGES PRIOR TO ROUGH-IN.
P2 ELECTRICAL CONTRACTOR SHALL VERIFY ALL EQUIPMENT LOCATIONS, MOUNTING HEIGHTS, AND CONNECTION REQUIREMENTS (RECEPTACLES, SWITCHES, DISCONNECTS) WITH EQUIPMENT VENDOR PRIOR TO ROUGH-IN.
P3 A DEDICATED NEUTRAL SHALL BE PROVIDED FOR EACH AND EVERY 120V AND 277V BRANCH CIRCUIT. MULTIWIRE
BRANCH CIRCUITS WITH SHARED NEUTRALS ARE NOT PERMITTED.
P4 PROVIDE #10 SIZE CONDUCTORS FOR 20A-120V CIRCUITS WITH DISTANCE LENGTHS THAT EXCEED 100 FT.
N
Revisions: Date:
C
C
C
NEW
SS-CP2
NEW
SS-CP1
EXISTING
NPSS-1
EXISTING
GPSS-1
ATS-HLS ATS-
HEQ
ATS-
HCR
X X X
EF-1
EF
C
C
C
H1N1…