About this file

This document contains an amendment to a solicitation for the construction of a chiller plant at the Chalmers P. Wylie VA Ambulatory Care Center in Columbus, Ohio. Key details include that the amendment provides previously submitted questions and answers from a prior procurement effort for reference, with no changes to other terms and conditions. Products and services required include construction of the new chiller plant to the specifications provided. The solicitation number is 36C25023B0049 and it is a SDVOSB set-aside opportunity issued by the Department of Veterans Affairs Veterans Health Administration VISN 10. The response due date is not included.

View the file

Other files

File Type Posted
36C25024C0013 SAM Award Notice 1.0.pdf PDF
36C25023B0049 - Amendment 3.docx DOCX document
36C25023B0049 - Amendment 2.pdf PDF
Single Source Justification MPT to SAT - Wattstopper - Pricing Removed - Signed.pdf PDF
VHA Directive 1192.01, Seasonal Influenza Prevention Program for VHA Health Care Personnel.pdf PDF
18912 Columbus VAMC Chiller BC Sole Source Redacted.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-8.pdf PDF
VAAR 852.219-75 - To Be Submitted With Bid.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-5.pdf PDF
VAACC Health Requirements - Bid Ready 2023.pdf PDF
36C25023B0049 - Ready.docx DOCX document
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-4.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-1.pdf PDF
Single Source Justification MPT to SAT - Simplex - 2.0 Price Removed - Signed.pdf PDF
18912 Columbus VA Chiller Plant Revision Final B_C Re-Revised - PM Vol 1 of 2.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-2.pdf PDF
Franklin DB - Current as of 07.13.2023.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-9.pdf PDF
Single Source Justification MPT to SAT - Software House - Pricing Removed - Signed.pdf PDF
Single Source Justification MPT to SAT - Russ Electric Price Removed - Signed.pdf PDF
18912 Columbus DVAMC Chiller FB_C PM Volume 2 of 2.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-6.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-7.pdf PDF
Hca Signed NCO 10 Caterpillar - Sole Source - Pricing Removed.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-10.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-3.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

5. PROJECT NUMBER (if applicable)

CODE

7. ADMINISTERED BY

2. AMENDMENT/MODIFICATION NUMBER

CODE

6. ISSUED BY

8. NAME AND ADDRESS OF CONTRACTOR

4. REQUISITION/PURCHASE REQ. NUMBER

3. EFFECTIVE DATE

9A. AMENDMENT OF SOLICITATION NUMBER

9B. DATED

PAGE OF PAGES

10A. MODIFICATION OF CONTRACT/ORDER NUMBER

10B. DATED

BPA NO.

1. CONTRACT ID CODE

FACILITY CODE

CODE

Offers must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended, by one of the following methods:

The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offers

E. IMPORTANT:

is extended,

(a) By completing Items 8 and 15, and returning __________ copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted; or (c) By separate letter or electronic communication which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY is not extended.

12. ACCOUNTING AND APPROPRIATION DATA

(REV. 11/2016)

is required to sign this document and return ___________ copies to the issuing office.

is not, A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE CONTRACT ORDER NO. IN ITEM 10A.

15C. DATE SIGNED

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(b).

RESULT IN REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by letter or electronic communication, provided each letter or electronic communication makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER

Contractor

16C. DATE SIGNED

14. DESCRIPTION OF AMENDMENT/MODIFICATION

16B. UNITED STATES OF AMERICA

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER

16A. NAME AND TITLE OF CONTRACTING OFFICER

15B. CONTRACTOR/OFFEROR

STANDARD FORM 30

PREVIOUS EDITION NOT USABLE

Prescribed by GSA - FAR (48 CFR) 53.243 (Type or print) (Type or print) (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

(Number, street, county, State and ZIP Code) (If other than Item 6) (Specify type of modification and authority) (such as changes in paying office, appropriation date, etc.)

(If required)

(SEE ITEM 11)

(SEE ITEM 13)

(X)

CHECK

ONE

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS,

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

(Signature of person authorized to sign) (Signature of Contracting Officer)

757-15-102 36C250 Department of Veterans Affairs VA Healthcare System Network Contracting Office (NCO) 10 2780 Airport Dr - Suite 340 Columbus OH 43219

36C250 Department of Veterans Affairs VA Healthcare System Network Contracting Office (NCO) 10 2780 Airport Dr - Suite 340 Columbus OH 43219 To all Offerors/Bidders

36C25023B0049 07-27-2023

X

The purpose of this solicitation amendment is to provide all interested parties with the pre-bid request for information (RFI) questions and answers from previous procurement efforts. Those considering submitting RFI questions are encouraged to review the continuation pages of this amendment, prior to submitting questions.

All other terms & conditions remain unchanged and in full effect.

Brian S. Kish Contracting Officer

CONTINUATION PAGE

Construct Chiller Plant Chalmers P. Wylie VAACC Columbus, OH 43219 Project # 757-15-102 SDVOSB Set-Aside

CONTINUATION PAGES

CONSTRUCT CHILLER PLANT FOR THE CHALMERS P. WYLIE VETERANS AFFAIRS AMBULATORY CARE CENTER (VAACC)—COLUMBUS, OH

PROJECT NUMBER: 757-15-102

QUESTIONS AND RESPONSES FROM A PREVIOUS PROCUREMENT EFFORT

1. QUESTION – Can the superintendent act as the Quality Control Manager??

Response: Yes. The superintendent can act as the Quality Control Manager.

2. QUESTION – Could I please have the following RFIs submitted for this project? All relate to Division 23. Thanks! - Please confirm the basis of design for all equipment listed on pages M-601 and M-602. Please confirm acceptable manufacturers for 23 64 00. Please confirm acceptable manufacturers for 23 65 00. Please confirm acceptable manufacturers for 23 81 00.

Response: The VA will not be providing any manufacturer information or basis of design information outside of the already provided sole source information that was included in the original solicitation posting.

3. QUESTION – N/A to this procurement

4. QUESTION - Is the coordination study for only the new equipment or is it for the entire project shown in drawings E-601, E-602?

Response: The contractor shall request the latest facility short-circuit, arc fault, and coordination study from the VA and the new equipment shall be integrated into the existing facility study. New settings and programming shall be determined and provided for all new breakers and for any existing breakers affected by the construction project. Settings and programming, including creation of the settings file, shall be provided for the new generator breaker in the paralleling switchgear for all available trip settings, including differential protection.

5. QUESTION – The one-line indicates a dual main primary, with a fuse in each switch but the notes in drawing E-506 indicates a duplex switch. Is a duplex switch with one set of load fuses acceptable?

Response: Fuse protection shall be provided for each switch.

6. QUESTION – Quoting our HVLcc switchgear in lieu of HVL. Is this acceptable?

Response: Drawings do not specify manufacturer information. Equivalent products will be evaluated on a performance basis and shall be approved if they meet the basis of design as indicated on the construction drawings and specifications. The substations must fit in the space provided and within required NEC clearances. Full size equipment is permitted if the space allows. Compact equipment may be permitted where necessary to meet space requirements.

7. QUESTION – Busway spec indicates: Busway housing is not allowed to serve as the equipment grounding conductor. Our housing does serve as the equipment integral ground, is this acceptable?

Response: Housing may serve as a redundant ground, but is not permitted to be the sole grounding means. A dedicated ground bus bar must be included.

8. QUESTION - MV transformer spec calls for 95kV BIL. The standard for a dry-type VPI transformer is 60kV BIL. Is 60kV BIL acceptable?

Response: Provide 95kV BIL for 15kV rated systems.

9. QUESTION - The MV transformer spec calls for 50 deg C rise, but the notes in drawing E-506 indicates 150 deg C rise. Which is required?
Response: Provide 80 deg C rise shall be provided per specification. A reviseddrawing will be issued.
10. QUESTION – There are existing panels that require additional breakers. Are these panelsSquare D? If not, recommend distribution furnish.
Response: An updated one-line drawing will be issued with panel manufacturersand types where new breakers are provided in existing panels.

11. QUESTION - Confirm scope SUB SS-CP1, SS-CP2, DIST PANELS CPD1, CPD2.

Response: The contractor is responsible for all new work shown on plans. All equipment shall be assumed to be new unless marked “existing” or labelled with an “x”.

12. QUESTION - N/A to this procurement

13. QUESTION - Is stranded wire acceptable for #10 and smaller?

Response: #10 wire and smaller shall be solid copper, #8 wire and larger may be stranded. See revised specification 26 05 19.

14. QUESTION - Can you give me the exact specification for the generator I am to supply?
Response: Generator specifications per the contract drawings, specifications, andincluded sole source information is to be a Caterpillar Diesel Generator, 13.2kV,2000kVA Model 3516C with custom enclosure to match the existing 2000kVAgenerator.
15. QUESTION – Would you tell me the VA regular sign vendor and can I use them to supplysigns on this project?
Response: The sign vendor that is typically used is Creative Signage and they maybe used on this project. However, the VA does not require that this vendor to be bythe contractor.