18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-5.pdf
PDF 10 MB Posted
- Solicitation number
- 36C25023B0049
About this file
This document outlines a federal contract opportunity to construct a chiller plant for the Columbus VA Medical Center in Columbus, Ohio. The solicitation number is 36C25023B0049 and is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10 as a SDVOSB set-aside opportunity. Interested parties should review the attached drawings and respond by the specified due date. The selected contractor will be responsible for constructing a new chiller plant to support the medical center's facilities.
Key details include the solicitation number, issuing agency, opportunity type as a SDVOSB set-aside, general scope of work to construct a chiller plant, and reference to attached drawings for additional requirements. Responses are due by the specified date in the full solicitation.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
B
VAPOR BARRIER BY EIFS SYSTEM
MANUFACTURER
1/2" SEALANT JOINT WITH BACKER ROD
RIGID INSULATION BY EIFS SYSTEM
MANUFACTURER
VAPOR BARRIER BY EIFS SYSTEM
MANUFACTURER
1 1/2" EXPANSION JOINT AND COVER
GALV. L2x2x1/4" VERT. ANGLE EXPANSION
BOLTED TO EXISTING MASONRY WALL
EXISTING MASONRY WALL
EXISTING EIFS REVEAL
EXISTING EIFS SYSTEM, PROTECT
DURING CONSTRUCTION
3/4"
LIQUID APPLIED MESH REINFORCED
FLASHING MEMBRANE BY EIFS MFG. LAP
OVER EXPANSION JOINT COVER AND
METAL ANGLE
TIE-IN / OVERLAP VAPOR
BARRIER INTO EXISTING VAPOR
BARRIER
/8
EIFS (MIN. R9.5ci)
NOM. 12" REINFORCED
CMU
3.1
1 1/2" EXPANSION
JOINT AND COVER.
RIGID INSULATION BY EIFS SYSTEM
MANUFACTURER
LIQUID APPLIED MESH REINFORCED
FLASHING MEMBRANE BY EIFS MFG.
LAP OVER EXPANSION JOINT COVER
AND METAL ANGLE
VAPOR BARRIER BY EIFS SYSTEM
MANUFACTURER
EXISTING EIFS SYSTEM, PROTECT
DURING CONSTRUCTION
EXISTING REVEAL
EXISTING MASONRY WALL
EIFS SYSTEM
VAPOR BARRIER BY EIFS SYSTEM
MANUFACTURER. SEE EIFS MFG'S
REQUIREMENTS FOR PREPARATION
OF SUBSTRATE
GALV. L2x2x1/4" VERT ANGLE
EXPANSION BOLTED TO
EXISTING MASONRY WALL.
3/4"
1/2" SEALANT JOINT WITH BACKER
ROD
TIE-IN / OVERLAP VAPOR
BARRIER INTO EXISTING VAPOR
BARRIER
/8
NOM. 12" REINFORCED
CMU
EIFS (MIN. R9.5ci)
RIGID INSULATION BY EIFS SYSTEM
MANUFACTURER, MATCH EXISTING
EIFS SYTEM THICKNESS
B.2
INSULATED ROLLING
OVER HEAD DOOR
6" DIA. CONCRETE FILLED
STEEL PIPE BOLLARD. SEE
CIVIL DRAWINGS.
4"
EIFS (MIN. R9.5ci)
NOM. 12" REINFORCED
CMU
B.2
A-302
REMOVABLE METAL GUARDRAIL
WITH TOE GUARD (TYP.)
DAVIT CRANE
METAL GUARDRAIL BASE
PLATE (TYP.)
OPENING
10'-0" 5'-0"
TIE-OFF ANCHOR,
SEE STRUCT. DWGS.
METAL COPING
7'-6"
ROOF DRAIN &
OVERFLOW DRAIN
AHU-2
270°
7'-6"
6'-8"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
C U s e rs
\j c h o \D o c u m e n ts
\R e v it M o d e ls
\1
R
V A
C o lu m b u s C h ill e r
P la n t R e v is io n
C e n tr a l_ jd c h o
.r v t
/5
/2
:0
:1
A
M
A-403
ENLARGED DETAILS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 RG jdc
BID & CONSTRUCTION
(REVISED)18912
SCALE: 1 1/2" = 1'-0"A-403
1 ENLARGED PLAN DETAIL
SCALE: 1 1/2" = 1'-0"A-403
3 ENLARGED PLAN DETAIL
SCALE: 1 1/2" = 1'-0"A-403
2 PLAN DETAIL
SCALE: 1/4" = 1'-0"A-403
4 PARTIAL ENLARGED ROOF PLAN - CRANE
Revisions: Date:
FINAL BID & CONSTRUCTION 11/24/2021
FINAL BID & CONSTRUCTION (REVISED) 05/06/2022
A.8
A.8
A-405
1'-7 1/2" 6'-1"
EXISTING
SURGERY CENTER
INSULATED CHILLED WATER
PIPING, SEE PLUMBING
DRAWINGS
EXISTING
WINDOW SYSTEM
NEW MESH METAL
PANELS
NEW STRUCTURAL TUBE
SYSTEM, SEE STRUCT.
DWGS.
CONCRETE PIT WALL;
BELOW GRADE (TYP.)
F
IE
L D
V E
R
IF
Y
/4
A-404
2'-0" WIDE GRAVEL MOWER
STRIP
SURGERY CENTER METAL PANEL WALL,
PROTECT DURING CONSTRUCTION
MESH SIDE PANEL
MESH SIDE PANEL
B.4
A-405
4'-11 1/4"
5'-0"
CONCRETE PIT
A-405
A-405
8 3/4" 8'-4 1/4"
OUTLINE OF NEW CONC. SLAB
9'-1"
EXISTING CONCRETE PIT
INSULATED PIPING, SEE
MECH. DWGS.
STEEL PIT LADDER
RAILING GATE
GUARDRAIL
O U
T L
IN
E O
F N
E W
C O
N C
R E
T E
S L
A B
/8
TRENCH
DRAIN
EXISTING
TRENCH DRAIN
EXSITING
PROTECTION RAILING
A-404
FD
SLOPE 1/8"
PER FOOT
SLOPE 1/8"
PER FOOT
SLOPE 1/8"
PER FOOT
SLOPE 1/8"
PER FOOT
CHILLED WATER PIPES
REMOVED FOR CLARITY
A-405
SLOPE 1/4" PER FOOT
CHILLED WATER PIPES AND METAL MESH
PANELS, REMOVED FOR CLARITY
CONCRETE PIT SLAB,
SEE STRUCT. DWGS.
OUTLINE OF SURGERY CENTER
FOUNDATION
8'-0"
8" 5'-5" 1'-11"
CONCRETE PIT
WALLS, SEE STRUCT.
DWGS.
TUBE STEEL ABOVE,
SEE STRUCT. DWGS.
CL
CL
CLCL
6'-1"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
C U s e rs
\j c h o \D o c u m e n ts
\R e v it M o d e ls
\1
R
V A
C o lu m b u s C h ill e r
P la n t R e v is io n
C e n tr a l_ jd c h o
.r v t
/5
/2
:0
:2
A
M
A-404
ENLARGED DETAILS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 RG jdc
BID & CONSTRUCTION
(REVISED)18912
SCALE: 1/2" = 1'-0"A-404
1 PIPE ENCLOSURE - SURGERY CENTER
SCALE: 1/2" = 1'-0"A-404
2 CONCRETE PIT - BOILER PLANT
SCALE: 1/2" = 1'-0"A-404
4 CONCRETE PIT SLAB (BOILER PLANT)
SCALE: 1/2" = 1'-0"A-404
3 CONCRETE PIT SLAB (SURGERY CENTER)
Revisions: Date:
PERFORATED METAL PANEL
ENCLOSURE
FOURTH FLOOR
THIRD FLOOR
827'-0"
SECOND FLOOR
811'-0"
FIRST FLOOR
795'-0"
EXISTING DRAIN OUTLET,
FIELD VERIFY
DASHED LINE INDICATES
STRUCTURAL SYSTEM, SEE
STRUC. DWGS.
INSULATED CHILLED WATER
PIPING, SEE PLUMB. DWGS.
A.8
INSULATED CHILLED WATER
LINE, SEE MECH. DWGS. FOR
ADDITIONAL INFORMATION
HSS 6X6 STEEL BEAM (TYP.),
SEE STRUCTURAL DRAWINGS
EXISTING METAL PANEL
EXTERIOR WALL
HSS 6X6 STEEL COLUMN, SEE
STRUCTURAL DRAWINGS
INSULATED CHILLED WATER
LINE, SEE MECH. DWGS FOR
ADDITIONAL INFORMATION
NEW MESH METAL PANELS
STRUCTURAL TUBE STYSTEM,
SEE STRUT. DWGS. FOR
ADDITIONAL INFORMATION
CONCRETE PIT FOUNDATION
WALLS, SEE STRUCT. DWGS.
EXISTING PARAPET
INSULATED CHILLED WATER
PIPING UP AND OVER PARAPET
EXISTING CONCRETE CAISSON
AND CAP
TOS ENCLOSURE
36'-6"
12" GRAVEL OVER COMPACTED
FILL WITH LANDSCAPE FABRIC
WEED BARRIER
BO CONC. PIT
787'-0"
FIRST FLOOR
795'-0"
THIRD FLOOR
827'-0"
4"
CHILLED WATER PIPE SUPPORT,
SEE MECHANICAL DRAWINGS
NEW MESH METAL PANELS
L4X4 STEEL ANGLE CROSS
BRACING (TYP.), SEE
STRUCTURAL DRAWINGS
5'-0" WIDE OPENING AT EAST
WALL ONLY
SLOPE 1/4" PER FOOT
24" WIDE GRAVEL MOWER STRIP
CONCRETE PIT SLAB, SEE
STRUCT. DWGS.
3" MIN. SAND ON BOTH SIDES,
SEE STRUCT. DWGS.
SIDE PANEL TO EXTEND
TO EXTERIOR WALL FOR
SECURITY
A-401
FIRST FLOOR
795' - 0"
A-405
A-405
BO CONC. PIT
787'-0"
INSULATED 18" CHILLED WATER
PIPES, SEE MECH. DWGS.
GUARDRAIL WITH GATE
REINFORCED CONCRETE PIT
SLAB ON GRADE, SEE
STRUCT. DWGS.
REINFORCED CONCRETE PIT
WALLS SEE STRUCT. DWGS.
INSULATED 18" CHILLED
WATER PIPES, SEE
MECH. DWGS.
REINFORCED
CONCRETE PIT WALLS,
SEE STRUCT. DWGS.
METAL LADDER
EXISTING GRADE BEAM
FIRST FLOOR
795' - 0"
A-405
A-405
METAL LADDER
GUARDRAIL
REINFORCED CONCRETE PIT
SLAB ON GRADE, SEE
STRUCT. DWGS.
B.O. CONC. PIT
787'-0"
REINFORCED CONCRETE PIT
WALLS SEE STRUCT. DWGS.
INSULATED 18" CHILLED
WATER PIPES, SEE
MECH. DWGS.
FIRST FLOOR
795' - 0"
(M
IN
TOE GUARD PLATE
STEEL MID RAIL
STEEL TOP RAIL
STEEL POST
EPOXY GROUT
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
C U s e rs
\j c h o \D o c u m e n ts
\R e v it M o d e ls
\1
R
V A
C o lu m b u s C h ill e r
P la n t R e v is io n
C e n tr a l_ jd c h o
.r v t
/5
/2
:0
:2
A
M
A-405
CHILLED WATER PIPING ENCLOSURE
ELEVATION AND SECTION
CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 RG jdc
BID & CONSTRUCTION
(REVISED)18912
SCALE: 1/8" = 1'-0"A-405
5 PARTIAL EXTERIOR EAST ELEVATION (SURGERY CENTER)
SCALE: 1/2" = 1'-0"A-405
1 SECTION - PIPE ENCLOSURE (SURGERY CENTER)
SCALE: 1/2" = 1'-0"A-405
2 CONCRETE PIT CROSS SECTION
SCALE: 1/2" = 1'-0"A-405
4 CONCRETE PIT LONGITUDINAL SECTION
SCALE: 1" = 1'-0"A-405
3 RAILING SECTION
Revisions: Date:
653.1
E.3
C.3
B.8
B.5
B.2
A
A.2
B
B.4
C
D
E
F
G
1.8
2.6 2.7 3 4
A-301
A-3013
A-401
A-302
A-302
A-302
A-302
A-302
A-302
A-402
A-401
EXISTING AREA N.I.C.
D.4
CLCL
CL
CL
CL
CL
18'-0" 18'-0" 7'-2"
CL
CL
EXTERIOR LIGHTING, SEE
ELECT. DWGS. (TYP.)
EXTERIOR LIGHTING,
SEE ELECT. DWGS.
(TYP.)
EXIT LIGHT; SEE ELECT. DWGS.
EMERGENCY LIGHT; SEE ELECT. DWGS.
SUSPENDED HIGH BAY LIGHT FIXTURE, SEE ELECT. DWGS.
1. DIFFUSERS AND RETURN GRILLES NOT SHOWN IN ROOMS WITHOUT
CEILINGS.
2. P&M DENOTES PATCH TO MATCH EXISTING CONSTRUCTION AND FINISHES.
ALL PATCHING OF EXISTING MATERIAL SHALL BE DONE WITH MATERIALS
AND WORKMANSHIP MATCHING ADJACENT SURFACES.
3. REFER TO ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION.
4. NO ATTEMPT HAS BEEN MADE TO INDICATE ALL AREAS REQUIRING CUTTING
AND PATCHING DUE TO MECHANICAL AND/OR ELECTRICAL WORK.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
C U s e rs
\j c h o \D o c u m e n ts
\R e v it M o d e ls
\1
R
V A
C o lu m b u s C h ill e r
P la n t R e v is io n
C e n tr a l_ jd c h o
.r v t
/5
/2
:0
:2
A
M
A-501
FIRST FLOOR REFLECTED CEILING PLAN CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 RG jdc
BID & CONSTRUCTION
(REVISED)18912
SCALE: 1/8" = 1'-0"A-501
1 FIRST FLOOR REFLECTED CEILING PLAN
REFLECTED CEILING PLAN LEGEND
REFLECTED CEILING PLAN GENERAL NOTES
Revisions: Date:
M
M
N
N
O
O
P
P
Q
Q
R
R
S
S
T
T
T.2
T.2
6.2
6.2
9.2
9.2
U
U
T.3
T.3
EXISTING CEILING
TO REMAIN
EXISTING CEILING TO REMAIN
MENTAL HEALTH SURGERY CENTER
EXISTING
MECHANICAL ROOM
EXIST. OFFICE EXIST. OFFICE EXIST. OFFICE EXIST. OFFICE EXIST. OFFICE EXIST. OFFICE
EXIST.
OFFICE
EXIST.
OFFICE
EXIST.
OFFICE
EXIST.
OFFICE
EXIST.
OFFICE
EXIST.
OFFICE
EXIST.
OFFICE
EXIST.
OFFICE
EXISTING
WAITING AREA
EXIST.
VESTIBULE
EXIST.
OFFICE
EXIST.
OFFICE
EXIST.
OFFICE
EXIST. OFFICE
EXISTING CORRIDOR EXISTING CORRIDOR
EXIST.
OFFICE
EXIST.
OFFICE
EXISTING CORRIDOR
EXISTING ENTRY
CANOPY
NEW CHILLED WATER PIPING.
REFER TO MECHANCIAL DRAWINGS
FOR ADDITIONAL INFORMATION
MATCH EXISTING CEILING
GRID DIRECTION AND
LAYOUT
EXIST.
OFFICE
1. SEE SHEET A9-1 FOR GENERAL REFLECTED CEILING PLAN NOTES
2. FIELD VERIFY EXISTING LIGHT FIXTURE AND DIFFUSERS LOCATION PRIOR TO LAYING
OUT NEW CEILING GRID SYSTEM. COORDINATE WITH NEW CHILLED WATER PIPING
LAYOUT. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL INFORMATION.
3. CEILING WORK TO BE DONE OFF HOURS, COORDINATE WITH DEMOLITION, AND MEP
DRAWINGS. COORDINAT SCHEDULE WITH COR. AREA TO BE RETURNED TO
ORIGINAL CONDITION AFTER EACH WORKING DAY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
C U s e rs
\j c h o \D o c u m e n ts
\R e v it M o d e ls
\1
R
V A
C o lu m b u s C h ill e r
P la n t R e v is io n
C e n tr a l_ jd c h o
.r v t
/5
/2
:0
:3
A
M
A-502
PARTIAL FIRST FLOOR REFLECTED CEILING
PLAN (SURGERY CENTER) - BID ALTERNATE
NO. 3
CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 RG jdc
BID & CONSTRUCTION
(REVISED)18912
SCALE: 1/8" = 1'-0"A-502
1 REFLECTED CEILING PLAN - SURGERY CENTER
REFLECTED CEILING PLAN GENERAL NOTES
Revisions: Date:
UP
UP
3.1
C.3
C
A-601
A-601
A-601
9 TREADS @ 11"
8'-3"
LANDING
2'-6"
1'-5" 2'-7"
5 TREADS
@11 = 4'-7"
LANDING
3'-8 1/4"
/2
LANDING
4'-4"
/4
/4
CL4
T
R E
A D
S
/2
4'-0"
/8
P L A
T F
O R
M A
IS
L E
C E
N T
E R
S T
A
IR
S /L
A N
D
IN
G O
N C
O O
L
IN
G T
O W
E R
PATCH EXISTING ROOF INSULATION AND
MEMBRANE AFTER COLUMN INSTALLATION. FLASH
COLUMN INTO EXISTING ROOF. COORDINATE
WARRANTY REQUIREMENTS WITH OWNER.
T.O.S. CHILLER
813' - 0"
3.13
BOILER PLANT T.O.S.
822' - 5 1/2"
A-601
A-602
TYP.
A-602
E Q
R
IS
E
R S
T.O. LANDING
828'-6 1/2"
T.O. EXIST. MASONRY
827'-0" (+/-)
TYP.
A-602
1'-0"
TYP.
A-602
TYP.
A-602
A-602
T.O.S. CHILLER
813' - 0"
C.3 C
A-601
TYP.
A-602
GALV. STEEL POSTS,
GUARDRAILS AND
HANDRAILS, TYP.
GALV. STEEL HSS STAIR
SUPPORT COLUMNS, (TYP),
SEE STRUCTURAL DRAWINGS
GALV. STEEL HSS STAIR SUPPORT
COLUMNS, TYP. SEE STRUCT. DWGS.
A-601
T.O. LANDING
828'-6 1/2"
T.O. LANDING
822'-1 3/4"(+/-)
E Q
R
IS
E
R S
/4
TYP.
A-602
TYP.
A-602
TYP.
A-602
GALV. STEEL STRINGERS AND
TREADS, TYPICAL.
TYP.
A-602
A-602
T.O.S. CHILLER
813' - 0"
3.13
BOILER PLANT T.O.S.
822' - 5 1/2"
A-601
E Q
R
IS
E R
S
/4
E
Q R
IS
E
R S
/8
A-602
COOLING TOWER, SEE
MECHANICAL DRAWINGS
A-602
TYP.
T.O.S. MECH. PLATFORM
818' - 6"
TYP.
A-602
TYP.
A-602
GALV. STEEL POSTS,
GUARDRAILS AND
HANDRAILS, TYP.
GALV. STEEL STAIR SUPPORT
COLUMNS, TYP. SEE STRUCT. DWGS.
GALV. STEEL STRINGERS AND
TREADS, TYPICAL.
COOLING TOWER
PLATFORM, AND SUPPORT
BEAM AND COLUMN, SEE
STRUCTURAL DRAWINGS
SBS ROOFING SYSTEM
1 1/2"
GALV. STEEL POSTS,
GUARDRAILS AND
HANDRAILS, TYP.
GALV. STEEL STRINGERS AND
TREADS, TYPICAL.
A-602
C.3
A-402
D.4
A-601
T
R E
A D
S
L A
N D
IN
G
/4
4'-0" 4'-6 3/4"
LANDING
4'-9"
COOLING
TOWER
COOLING
TOWER
COOLING
TOWER
PLATFORM
CL
E Q
E Q
CENTER STAIR LANDING ON
COOLING TOWER AISLE
COOLING
TOWER
A-602
T.O.S. CHILLER
813' - 0"
T.O. MASONRY CHILLER
817' - 8"
E
Q U
A L
R
IS
E R
1'-0"
GALVANIZED STEEL POSTS,
GUARDRAILS AND
HANDRAILS (TYP.)
GALV. STEEL HSS STAIR
SUPPORT COLUMNS, SEE
STRUCT. DWGS.
SBS ROOFING SYSTEM
TYP.
A-602
T.O.S. MECH. PLATFORM
818' - 6"
TYP.
A-602
TYP.
A-602
A-602
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
C U s e rs
\j c h o \D o c u m e n ts
\R e v it M o d e ls
\1
R
V A
C o lu m b u s C h ill e r
P la n t R e v is io n
C e n tr a l_ jd c h o
.r v t
/5
/2
:0
:3
A
M
A-601
STAIR DETAILS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 RG jdc
BID & CONSTRUCTION
(REVISED)18912
SCALE: 1/4" = 1'-0"A-601
1 ENLARGED PLAN - STAIR
1. SEE STRUCTURAL DRAWINGS FOR SUPPORT
COLUMNS AND STAIR FRAMING.
SCALE: 1/4" = 1'-0"A-601
2 SECTION - STAIR TRANSVERSE
SCALE: 1/4" = 1'-0"A-601
3 SECTION - STAIR LONGITUDINAL
SCALE: 1/4" = 1'-0"A-601
4 STAIR SECTION
SCALE: 1/4" = 1'-0"A-601
10 ENLARGED PLAN - STAIR MECH. PLATFORM
SCALE: 1/4" = 1'-0"A-601
11 SECTION - STAIR PLATFORM
Revisions: Date:
T.O.S. CHILLER
813' - 0"
3.1
EPDM MEMBRANE. ADHERE TO
COVER BOARD. WRAP UP AND
UNDER EXISTING EIFS
METAL FLASHING
1/2" COVERBOARD, MECHANICALLY
FASTEN TO EXISTING CMU
SBS ROOFING SYSTEM WITH BASE
SHEET, CAP SHEET AND FLASHING
MEMBRANE.
ROOF TO WALL EXPANSION JOINT WITH
EPDM MEMBRANE COVER. SEE
MANUFACTURER'S INSTALLATION
INSTRUCTIONS.
1/2" COVERBOARD
TAPERED INSULATION
EXISTING EIFS
BUILT-UP LAYERS OF PRESS.
TREATED 2x6 SOLID BLOCKING.
STEEL STAIR COLUMN BEYOND
OVERLAP REINFORCING MESH MIN
2.5" BETWEEN NEW AND EXISTING
EIFS WALL SYSTEMS
1 1/2"
METAL DECKING ON STRUCTURAL
SYSTEM, SEE STRUCT. DWGS.
T.O.S. CHILLER
813' - 0"
6" WIDE HORIZONTAL &
VERTICAL SCRIM MEMBRANE
FLASHING. FULLY BED IN
MEMBRANE FLASHING CEMENT.
MEMBRANE CAP FLASHING OVER
SCRIM. EXTEND MIN. 8" HORIZ.
AND UP STEEL COLUMN.
(M
IN
STEEL TUBE STAIR COLUMN.
PATCH EXISTING ROOF
INSULATION AND MEMBRANE
AFTER COLUMN INSTALLATION.
FLASH COLUMN INTO EXISTING
ROOF. COORDINATE WARRANTY
REQUIREMENTS WITH OWNER.
STEEL CHANNEL, SEE
STRUCT. DWGS.
/4
M A
X
M A
X
M A
X
M A
X
M A
X
M A
X
1 1/2" DIA. GALV. STEEL
TOP RAIL
1 1/2" DIA. GALV. STEEL
HAND RAIL
1 1/2" DIA. GALV. STEEL
BALUSTER
GALV. METAL CHANNEL
STRINGER
1" DIA. GALV. STEEL
PICKETS
CL
CL
CL
CL
CL
CL
CL
CL
3" CLCL
11" 11" 12" 1
/2
E Q
/2
E Q
/2
1"
1"
GALVANIZED STEEL CHANNEL
STRINGERS, SEE STRUCT.
DWGS.
GALVANIZED STEEL
GRIP STAIR TREADS
AND RISERS (TYP.)
12"
12"M A
X
T.O.S. MECH. PLATFORM
818' - 6"
CL
MECHANICAL PLATFORM
STRUCTURAL STEEL, SEE
STRUCT. DWGS.
STAIR GUARDRAIL AND HANDRAIL
GALV. STEEL CHANNEL
STRINGERS, SEE STRUCT.
DWGS.
GALVANIZED STEEL GRIP STAIR
TREADS AND RISERS (TYP.)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
C U s e rs
\j c h o \D o c u m e n ts
\R e v it M o d e ls
\1
R
V A
C o lu m b u s C h ill e r
P la n t R e v is io n
C e n tr a l_ jd c h o
.r v t
/5
/2
:0
:3
A
M
A-602
ENLARGED DETAILS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 RG jdc
BID & CONSTRUCTION
(REVISED)18912
SCALE: 1 1/2" = 1'-0"A-602
1 DETAIL - ROOF FLASHING
SCALE: 1 1/2" = 1'-0"A-602
3 SECTION - TYPICAL STAIR COLUMN FLASHING
SCALE: 1 1/2" = 1'-0"A-602
2 DETAIL - STAIR RAILING TYP.
SCALE: 1 1/2" = 1'-0"A-602
4 STAIR DETAIL
SCALE: 1 1/2" = 1'-0"A-602
5 STAIR DETAIL
Revisions: Date:
FLOOR
EC EPOXY COATING
ROOM FINISH LEGEND
WALL
P PAINT SEMI-GLOSS FINISH
BASE
P PAINT
CEILINGS
P PAINT - FLAT FINISH
GENERAL NOTES
1. EXP DENOTES EXPOSED STRUCTURE. ETR DENOTES EXISTING TO REMAIN
2. SEE REFLECTED CEILING PLAN FOR CEILING HEIGHTS.
3. PAINT ALL NEW METAL DOORS AND DOOR FRAMES (INCLUDING DOORS WITH
VISION PANELS) UNLESS NOTED. SEE PAINT SPECIFICATIONS FOR FINISH.
4. PAINT ALL NEW METAL COVERPLATES, ETC. UNLESS NOTED. SEE PAINT
SPECIFICATIONS FOR FINISH.
5. REFER TO SPECIFICATION SECTION 090600 FOR INTERIOR AND EXTERIOR
FINISHES, MATERIALS AND COLORS.
SUBSTRATE
C CONCRETE
CMU CONCRETE MASONRY UNITS
GYP GYPSUM BOARD
SCHEDULE NOTES
1. PAINT INTERIOR WINDOW FRAMES PER 09 06 00.
2. EPOXY PAINTING THE FLOOR SHALL BE THE BASE BID
2" 2"
1/2"
/8
1/2"
FRAME TYPE 2
APPLIED STOP
FOR GLAZING
MAY OCCUR
/8
5 3/4"
/8
2" 2"
1/2" 1/2"
/8
FRAME TYPE 1
5 3/4"
REINFORCED BLOCK
LINTEL, SEE
STRUCTURAL DWGS.
SEALANT BOTH SIDES
SEE SCHEDULE FOR
FRAME WIDTH AND TYPE
GROUT FRAME SOLID
HD-2
11 5/8" 3"
WEATHER BARRIER
EIFS (MIN. R9.5ci)
BACKER ROD AND WEEP
TUBES @ 24" O.C.
METAL FLASHING
HD-3
GROUT FRAME SOLID,
TYP.
SEALANT BOTH SIDES,
TYP.
BLOCK LINTEL, SEE
STRUCTURAL DWGS.
SEE SCHEDULE FOR
FRAME WIDTH AND TYPE
11 5/8" 3"
HD-1
OVERHEAD DOOR
EIFS (MIN. R9.5)
WEATHER BARRIER
NOM. 12" REINFORCED CMU
BLOCK, SEE STRUCT. DWGS.
STEEL LINTEL WITH BOTTOM PLATE,
SEE STRUCT. DWGS.
METAL FLASHING
BACKER ROD AND
WEEP TUBES @ 24"
O.C.
HD-4
GROUT FRAME SOLID,
TYP.
SEALANT BOTH SIDES,
TYP.
FIELD VERIFY BLOCK
LINTEL AT KOCK-OUT
PANEL
SEE SCHEDULE FOR
FRAME WIDTH AND TYPE
JD-2
/4
INSULATED ROLLING
OVERHEAD DOOR
JD-1
GALVANIZED ANGLE GUIDES
/4
GROUT FRAME
SOLID
DOOR FRAME,
SEE SCHEDULE
SEALANT
BOTH SIDES
GROUT FRAME
SOLID
DOOR FRAME,
SEE SCHEDULE
SEALANT BOTH
SIDES
MASONRY ANCHORS
EIFS (MIN. 9.5ci)
BULLNOSE
WEATHE BARRIER
PROVIDE EIFS
FINISHED END
PAINT EXPOSED
CMU (TYP.)
NOM. 12" REINFORCED
CMU BLOCK, SEE
STRUCT. DWGS.
/8
/4
JD-3
NOM. 12" REINFORCED
CMU BLOCK, SEE
STRUCT. DWGS.
5/16" HOT DIPPED GALV.
BENT PLATE JAMB
CLOSURE TRIM, BOLTED
TO MASONRY WITH 1/2"
DIA. EXPANSION BOLTS
AT 36" O.C.
WEATHER BARRIER
EIFS (MIN. R-9.5ci)
BULLNOSE,
EACH SIDE
MASONRY
ANCHORS
(2) #5 BARS AT DOOR JAMB (TYP.)
NOTE:
DOOR ANCHOR DESIGNED BY DOOR
VENDOR FOR BLAST REACTION
NOM. 12" REINFORCED
CMU BLOCK, SEE
STRUCT. DWGS.
3"
E Q
/4
E
Q
.GROUT FRAME SOLID
SEE SCHEDULE FOR
FRAME WIDTH & TYPE,
FIELD VERIFY WIDTH
3/8" MACH. SCREWS &
STEEL SHIELD ANCHORS
FOR EXISTING MASONRY
OPENING
SEALANT BOTH SIDES
EXISTING CMU MASONRY
JD-4
'A' - FLUSH DOOR 'B' - FLUSH WITH LITE
4"9"
'C' - ROLLING OVER HEAD DOOR
TG-1
MOTOR OPERATOR
S E
E S
C H
E D
U L E
2"
SCHEDULE
SEE 2"
FRAME ELEVATION A
4 7/8"
ONE HOUR RATED (U.L. #U419)
(1) LAYER OF 5/8" FIRE RESISTIVE GYP. BD. ON
EACH SIDE OF 3 5/8" STL. STUDS @ 16" O.C.
HEAD OF PARTITION
METAL DECK PARALLEL TO FLUTES
PARTITION AT FLOOR
3 1/2" SOUND ATTENUATION
BLANKET MAY OCCUR
CONTINUOUS ACOUSTICAL SEALANT
EACH SIDE
STRUCTURE ABOVE
DEFLECTION JOINT
3 1/2" SOUND ATTENUATION
BLANKET MAY OCCUR
CONTINUOUS RUNNER TRACK
CONTINUOUS RUNNER TRACK
FIRESTOP JOINT BETWEEN TOP OF FIRE-
RATED PARTITION AND STRUCTURE ABOVE
W/ U.L. OR W.H.I. PPROVED (1) HR. JOINT
FIRESTOP SYSTEM.
CONSTRUCTION SIDEPUBLIC SIDE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
C U s e rs
\j c h o \D o c u m e n ts
\R e v it M o d e ls
\1
R
V A
C o lu m b u s C h ill e r
P la n t R e v is io n
C e n tr a l_ jd c h o
.r v t
/5
/2
:0
:3
A
M
A-701
ROOM & DOOR SCHEDULES, DETAILS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 RG jdc
BID & CONSTRUCTION
(REVISED)18912
ROOM FINISH SCHEDULE
ROOM FLOOR BASE WALLS CEILING CEILING
ARCH.
WOODWORK NOTESNUMBER NAME SUBSTR. FINISH SUBSTR. FINISH
SUBSTR.
NEW
NEW FINISH SUBSTR.
NEW FINISHNORTH SOUTH EAST WEST
FIRST FLOOR
106 CORRIDOR C ETR GYP P+M GYP ETR P+M ETR ETR -- ETR --
EC-114 CHILLER PLANT C P4A CMU P4B CMU P1 P1 P1 P1 EXP P3 --
EC-115 EXISTING CONTROL ROOM C ETR CMU ETR CMU -- P1* -- -- ETR ETR -- *MATCH EXISTING ROOM COLOR / FINISH
EC-116 EXISTING BOILER ROOM C ETR CMU P4B CMU -- -- P1* -- EXP ETR -- *MATCH EXISTING ROOM COLOR / FINISH
DOOR SCHEDULE
OPENING
NUMBER
OPENING DOOR FRAME DETAILS U.L.
LABEL HDWE. SET NOTESWIDTH HEIGHT MAT. THICK. ELEV. MAT. ELEV. TYPE HEAD JAMB
FIRST FLOOR
114A 3'-8" 7'-0" HM 1 3/4" A HM A 1 HD-2 JD-2 HW-SH-4 BLAST RESISTANT, GALV. DOOR & FRAME
114B 12'-0" 12'-0" C HD-1 JD-1 DOOR JAMB GUIDE BY OVERHEAD DOOR MANUF.
114C 3'-8" 7'-0" HM 1 3/4" A HM A 1 HD-2 JD-2 HW-SH-4 BLAST RESISTANT, GALV. DOOR & FRAME
114D 3'-0" 7'-0" HM 1 3/4" B HM A 1 HD-4 JD-4 HW-1A
114E 7'-4" 7'-0" HM 1 3/4" B HM A 1 HD-3 JD-3 HW-11C
DOOR FRAME TYPES
DOOR HEAD DETAILS
DOOR JAMB DETAILS
DOOR ELEVATIONS DOOR FRAME ELEVATION
TEMPORARY CONSTRUCTION BARRIER
Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS
OHIO, 43219
05/06/2022Revisions: Date:
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
FINAL BID & CONSTRUCTION 11/24/2021
CONTRACTOR TO VERIFY ALL
DIMENSIONS, ELEVATIONS AND
CONDITIONS IN THE FIELD
S-001
GENERAL NOTES
ASK CJA
FOUNDATIONS AND SLABS ON GROUND
1. Foundations for this project are designed in accordance with the recommendations made by Terracon Consultants, Inc. All the work regarding site preparation, earth fill construction, backfill requirements, foundation preparations, etc., shall be in strict conformance to the requirements and recommendations of the Geotechnical Engineer's report. The report is part of the Contract Documents.
2. Grade beams: Elevations given are to bottom of grade beams.
3. Slab on ground: Slab elevations given are to top of structural slab.
4. In granular soils (sands and gravel) the soil shall be mechanically tamped to a hard surface immediately prior to placing footing.
5. Existing foundations:
A. Existing foundations shown on drawings are approximate. Exact conditions must be verified at time of construction.
8. Before backfill, all walls must be adequately braced. For backfill requirements, see specifications and/or geotechnical report.
9. For augercast piles, refer to augercast piles notes and details.
10. Locate existing underground utilities in areas of construction. Coordinate with utility companies for any shut-off requirements of still active lines. Call the Ohio Utilities Protection Service at 800-362-2764.
11. When excavations approach the ground water level, the water level shall be lowered by an acceptable dewatering system so that the water level is maintained continuously a minimum of 2'-0" below the excavation.
12. The bottom of foundations shall be protected against freezing until backfill or other permanent protective cover is in place.
DESIGN LOADS
Floor Live Load
First Floor ------------------------------------------------------------------------------ 150 psf Exterior Stair -------------------------------------------------------------------------- 40 psf
Roof live load
Rain Load ponded water ----------------------------------------------------------- not critical (1) (2)
Ponding Instability (IBC 1611.2) ------------------------------------------------- not critical (1)
Allowance for hanging loads for roofs------------------------------------------- 20 psf
(1) Assumes primary drainage is blocked and rain accumulates to depth of overflow (see Architect's detail) at 62.4 pcf
(2) Architect has provided scuppers and/or secondary drainage system
Roof snow load ------------------------------------------------------------------------------- 24 psf (3)
Ground snow load (ASCE 7, 7.2) ------------------------------------------------ Pg = 20 psf Flat-roof snow load (ASCE 7, 7.3) ----------------------------------------------- Pf = 24 psf (3)
Snow exposure factor (ASCE 7, Table 7.3-1) -------------------------------- Ce = 1.0 Snow importance factor (ASCE 7, Table 1.5-2) ------------------------------ Is = 1.2 Thermal factor (ASCE 7, Table 7.3-2) ------------------------------------------ Ct = 1.0
(3) Increased for snow buildup / unbalanced per ASCE 7, 7.6 to 7.9
Wind design data ----------------------------------------------------------------------------- Per ASCE 7-16
Basic wind speed (3-second gust) (ASCE 7, Figure 26.5-1D------------- V = 119 mph Risk category (IBC Table 1604.5) ----------------------------------------------- IV Wind exposure category (IBC 1609.4.3) -------------------------------------- C Internal pressure coefficient (ASCE 7, Table 26.13-1) Encl. ------------- GCpi = ± 0.18
(+) Indicates pressure acting toward the surface (-) Indicates pressure acting away from the surface
Earthquake design data -------------------------------------------------------------------- Per ASCE 7-16
Seismic Importance Factor (ASCE 7, Table 1.5-2) -------------------------- Ie =1.5 Component Importance Factor Ipe =1.5 Risk category ------------------------------------------------------------------------ IV Mapped spectral response accelerations/parameters
Short period ------------------------------------------------------------------- Ss = 0.117 g 1-second period -------------------------------------------------------------- S1 = 0.061 g
Site class (per Geotechnical Report) ------------------------------------------- D Design spectral response acceleration/parameters
Short period ------------------------------------------------------------------- Sds = 0.125 g 1-second period -------------------------------------------------------------- Sd1 = 0.098 g
Seismic design category ------------------------------------------------------------ C Basic seismic-force-resisting system (ASCE 7, Table 12.2-1) Steel systems not specifically detailed for seismic resistance, excluding cantilever column systems.
Design base shear (ASCE 7, 12.8.1) -------------------------------------------- V = 32 Kips Seismic response coefficient (ASCE 7, 12.8.1.1) ---------------------------- Cs = 0.065 Response modification coefficient (ASCE 7, Table 12.2-1) --------------- R = 3 Analysis procedure ------------------------------------------------------------------ Equivalent lateral force procedure Blast Design Data
Refer to Blast Basis of Design Report by Walter P. Moore dated May 7th 2021. All information provided in drawings is in conformance with the report and information provided by the blast design engineer.
Flood design data
Building is not in a flood hazard area (IBC 1612.3)
Special loads
Handrails and guardrails (IBC 1607.8) ----------------------------------------- 50 PLF/200 Lbs Interior walls and partitions (IBC 1607.15) Horizontal --------------------- 5 psf min.
CODES AND STANDARDS
1. Building has been designed to, and shall be constructed in accordance with the following building codes and standards:
A. 2018 International Building Code (IBC 2018) B. ASCE 7-16, Minimum Design Loads for Buildings and Other Structures
2. Unless explicitly modified in the Contract Drawings and Specifications, the Contractor shall comply with provisions of:
A. ACI 301-16, Specifications for Structural Concrete B. ACI 318-14, Building Code Requirements for Structural Concrete C. ACI 530-13, Building Code Requirements for Masonry Structures D. ACI 530.1-11, Specification for Masonry Structures E. AISC 341-16, Seismic Provisions for Structural Steel Buildings F. AISC 360-16, Specification for Structural Steel Buildings G. AWS D1.1-10, Structural Welding Code - Steel H. SDI Design Manual for Composite Decks, Form Decks and Roof Decks - No. 31
GENERAL
1. All new construction shall comply with the Contract Documents and the Building Code.
2. Typical details and general notes apply to all parts of the work except where specifically detailed or unless otherwise noted.
3. The structural drawings illustrate structural members. Refer to architectural, mechanical, and electrical drawings for non-structural items which require special provisions during the construction of the structural members.
4. Drawings are not to be scaled.
5. Refer to architectural plans for floor depressions, openings, slopes, drains, curbs, pads, embedded items, non-bearing partitions, etc. Refer to mechanical and electrical plans for sleeves, openings, and hangers for pipes, ducts, and equipment.
6. The Contractor shall verify and be responsible for all dimensions and conditions which impact the work. Field verify sizes, elevations, hole locations, etc., prior to fabrication.
7. The Contractor shall carefully review the drawings to identify the scope of work required, visit the site to relate the scope of work to existing conditions and determine the extent to which those conditions and physical surroundings will impact the work.
8. Existing conditions as shown on these plans are for reference only. The Contractor is required to field verify all existing conditions prior to construction.
9. The Contractor shall resolve any conflicts on the drawings or in the specifications with the Architect/Engineer before proceeding with the work.
10. Any deviation, modification, or substitution from the approved set of structural drawings shall be submitted to the Owner, Architect, and Engineer for review/approval prior to its use or inclusion on the shop drawings.
11. The Contractor shall provide all necessary shores, braces, and guys required to support all loads to which the building structure and components, soils, other structures, and utilities may be subjected during construction. Shoring systems shall be designed, signed, and sealed by a professional engineer licensed in the jurisdiction where the project is located.
12. The Contractor shall provide means, method, techniques, sequence, and procedure of construction as required.
13. The Contractor shall protect all work, materials, and equipment from damage and shall provide proper storage facilities for materials and equipment during construction.
14. Site visits performed by the Architect/Engineer do not constitute inspections of means and methods of construction performed by the Contractor.
15. Structural observations performed by the Architect/Engineer during construction are not the continuous and special inspection services and do not waive the responsibility for the inspections required of the Building Department Inspector or the testing agency. Observations also do not guarantee the Contractor's performance and shall not be considered as supervision of construction.
16. The Contractor shall review shop drawings for completeness and compliance with contract documents. The Contractor shall stamp shop drawings prior to submission to the Architect and Engineer.
17. Review of the shop drawings by the Architect's Engineers shall not be construed as an authorization to deviate from the Contract Documents.
18. Shop drawings will not be processed if they are incomplete, lack coordination with relevant portion of contract documents, lack calculations if required, or if deviations, modifications, and substitutions are indicated without prior written approval from the Architect/Engineer.
19. No pipes or ducts shall be embedded into structural members unless so shown on the plans or approved by the Engineer.
TEMPORARY SHORING AND BRACING
1. Structure is designed to be self-supporting and stable after the building is fully completed.
2. The Contractor shall be responsible for erection procedures and sequence, shall maintain stability of the building and its component parts, and shall be responsible for adequacy of temporary or incomplete construction and connections during erection. Such responsibilities include, but are not limited to: addition of shoring as required to support forms, decks, columns, walls, and other elements as required during construction, sheeting, temporary connections, bracing, guys, or tie-downs necessary to maintain stability of parts, subassemblies, or all of the structure.
3. Contractor shall assume full design responsibility for temporary shoring and bracing, which shall be designed, signed, and sealed by a professional engineer licensed in the jurisdiction where project is located.
4. Temporary shoring shall be maintained throughout construction and shall be removed only after completion of all required supporting elements.
5. Remove any remaining temporary shoring after construction is complete.
ROOF, FLOOR, OR WALL OPENINGS
1. The Contractor shall verify and coordinate the number, size, and location of all sleeves and openings required for mechanical or electrical items.
2. Sleeves and openings shall be located in a manner that will maintain the structural integrity of the roof, floor, or wall system.
3. No structural elements are to be cut unless specifically approved by the Engineer.
AUGERCAST PILES
1. Augercast piles are to be bored in place, pressure injected concrete mortar piles (5,000 psi min.) and shall be installed by a contractor experienced in this type of work. See specifications and geotechnical report for additional requirements.
2. See specifications for load test requirements.
3. See foundation plan for extent of piles.
4. All piles shall be reinforced. Unless noted otherwise, the reinforcement of the piles shall be placed in the center of the piles, spliced where required, and installed before the mortar sets. Non-reinforced piles will not be accepted.
5. Pile size and reinforcing as shown are minimum requirements.
6. Vertical pile allowable load capacity at bearing shall not be less than 130 kips per pile at 50 foot embedment. See geotechnical report for additional requirements.
EARTHWORK SHORING
1. Temporary shoring for grade beams, pile caps, and utility pit structures shall be provided when required by local, state, or OSHA officials or codes at no additional cost to the Owner.
2. Where forces from existing structures, roadways, walks, utility lines, or other encumbrances required for construction come onto shoulders of foundations, utility pit, footing, or grade beam excavations, the Contractor shall provide shoring of adequate size and strength to resist the combined earth and adjacent surcharge pressures.
3. The Contractor shall be responsible for design and placement of shoring and bracing of temporary earth retaining structures required for foundation and footing construction.
4. Local, state, and OSHA safety requirements for personnel working in trenches shall be enforced by the Contractor. The Contractor shall hold the Owner, Architect, and Engineers harmless from claims due to injury from violation of safety requirements resulting from work persons or others working in foundations, trench, or grade beam excavations.
CONCRETE CONSTRUCTION
1. All concrete construction shall be in accordance with the latest Building Code Requirements for Structural Concrete ACI 318 and ACI Detailing Manual, except that construction and removal of forms and reshoring shall be inspected by the Contractor's engineer.
2. Reinforcing steel shall have the following minimum coverage. Place bars as near to the concrete surface as these minima permit wherever possible, unless noted otherwise:
A. Concrete poured against earth: 3" B. Formed concrete in contact with earth: 2" C. Exterior face of walls: 2" D. All other wall faces, slabs: 3/4" (#11 and smaller), 1 1/2" (#14 and #18)
3. Furnish bar supports where necessary during construction.
4. Provide pipe sleeves and inserts in concrete work where required. See architectural and mechanical drawings.
5. Obtain approval of Engineer before locating sleeves, holes, or inserts in slabs within
2'-0" of face of columns or anywhere in beams.
6. Construction joints shall be positioned so as not to change the structural design requirements. The location and size of all construction joints shall be approved by the Engineer. Submit proposed pour layout for Engineer's review and approval two weeks prior to placing concrete.
7. Welding of reinforcing bars (including tack welding) is not permitted without permission of Engineer in writing. Where and when permitted, welded rebars shall comply with ASTM A706 (Fy=60 ksi) and welding shall conform to AWS D1.4.
Welding shall be performed by certified welders.
8. Drawings show typical reinforcing conditions. Contractor shall prepare detailed placement drawings of all conditions showing quantity, spacing, sizes, clearances, laps, intersections, and coverage required by the structural details, applicable code, and trade standards. Contractor shall notify reinforcing inspector of any adjustments from typical conditions which are proposed in placement drawings to facilitate field placement of reinforcing steel and concrete.
9. Bar bends shall be made cold. Bars shall not be bent after any portion of the bar is encased in concrete.
10. Splices (grade 60 deformed bars):
A. Lap all compression splices 30 bar diameters of the larger bar.
B. Lap all tension splices in accordance with the following tables. Provide Class
B Tension Lap Splices unless otherwise noted.
C. Increase tension or compression splice lengths by the following factors.
Increases are Cumulative:
1) Epoxy-coated top bars: 1.3
2) Epoxy-coated other bars: 1.5
D. Top bars are defined as horizontal bars with more than 12” of fresh concrete below.
43"
Other 22" 29"
36"
81" 72"
63"
49"
71"
81" 91"
Top
33" 24"
41"
#4
#6
#3
Size
#5
#9 #8
#7
Bar
56"
81"
93" 105"
37" 28"
Top
47" 37"
54"
62" 70"
Other
25" 19"
31" 43"
63"
72" 81"
Top
29" 22"
36" 34"
49"
56" 63"
23" 17"
28"
Class B Tension Lap Splice
91" 102"#10 118" 79" 92" 70"
101" 113"#11 131" 87" 102" 78"
Other f'c = 3000 psi f'c = 4000 psi f'c = 5000 psi
33"
Other 17" 22"
28"
62" 55"
48" 37" 54"
62" 70"
Top
25" 19"
31"
#4
#6
#3
Size
#5
#9 #8
#7
Bar
43" 63"
72" 81"
29" 22"
Top
36"
29" 42"
48" 54"
Other
19" 15"
24"
34" 49"
56" 63"
Top
23" 17"
28"
26" 38"
43" 48"
17" 13"
22"
Class A Development Length, ld
70" 79"#10 91" 61" 70" 54"
78" 87"#11 101" 67" 78" 60"
Other f'c = 3000 psi f'c = 4000 psi f'c = 5000 psi
MASONRY CONSTRUCTION
1. Masonry walls shown on structural drawings have been designed in accordance with ACI 530, Building Code Requirements for Masonry Structures.
2. Masonry walls shown on structural drawings shall be constructed in accordance with ACI 530.1, Specifications for Masonry Structures, and the project specifications.
3. Determine compressive strength of masonry (f'm) by the unit strength method (Section 1.4,B.2 of ACI 530.1).
A. Mortar shall meet the Property Specifications' requirements of ASTM C270, and shall be field tested according to ASTM C780.
B. The strength of grout shall be determined by tests in accordance with ASTM
C1019.
4. The use of masonry cement shall not be permitted.
5. Provide corner bars in bond beams at wall intersections and corners to match bond beam reinforcing.
6. Provide a minimum of 24" depth of solid masonry under the bearing ends of all beam lintels, and 8" of solid masonry under the bearing ends of loose lintels.
7. Provide horizontal joint reinforcement per ASTM A82, galvanized, at 16" on center vertically. See specifications. Unless otherwise noted, provide a galvanized ladder type joint reinforcement.
8. Welding of reinforcing bars (including tack welding) is not permitted without permission of Engineer in writing.
9. Provide shop drawings which indicate size, spacing, bending details, and type of all reinforcing bars placed in masonry walls.
10. Provide dowels from supporting member (grade beam) for all reinforced walls same size, location, and spacing as wall reinforcing.
11. Wall reinforcing shall be held in position during grouting.
12. For bars at face of wall, maintain 1/2" clearance from inside face of CMU to reinforcing.
13. Splices (grade 60 deformed bars, f'm=1,500psi):
A. Lap all splices in accordance with the following table.
B. Increase splice length by 50% for epoxy-coated reinforcing.
C. Splice lengths greater than 60" require high lift grouting. The Contractor, at his option, may use open-ended masonry units or mechanical splices for ease of construction.
43"
8" 18"
24"
30"
92"
60"
40"
46"
71" 82"
10"
24"
18"
30"
#4
#6
#3 Size
#5
#9 #8
#7
Bar
61"
24"
18" 6"
32" 40"
46"
61" 74"
12"
24"
18"
30" 40"
46"
61" 69"
16"
24"
18"
30" 54"
63"
72" 82"
26"
18"
40"
Reinforcing at Face of Wall
Reinforcing Centered in Wall Nominal Wall Width
LOOSE LINTEL SCHEDULE
1. Interior lintels shall be shop painted. Lintels exposed to weather shall be 3/8" minimum thickness and hot-dip galvanized.
2. Bottom plates in beam/plate assemblies shall be 1/2" less in width than the supported masonry wall. Stop bottom plates at face of masonry opening.
3. Weld bottom plates to lintels with continuous fillet welds (each side).
4. Steel lintels and lintel plates in exterior walls shall be fabricated, followed by hot-dip galvanizing of the complete assembly.
5. Lintels shall have minimum bearing at each end of 1" per foot of opening (6" minimum) except as detailed.
6. Lintels shall have 8" minimum solid masonry below bearing points and shall extend beyond the full bearing area.
7. Lintel bearing plates shall be held back 1/2" minimum from face of masonry at opening. Provide flexible caulk between lintel and masonry at this location. Match mortar color.
8. The following schedules apply to all non-bearing masonry walls where lintels are not indicated on the structural drawings.
A. For 4", 8", 12", and 16" walls, provide one angle for each 4" of masonry wall thickness with 3 1/2" leg horizontal as follows:
Span Limits Angle Size 0'-0" to 4'-0" L3 x 3 1/2 x 1/4 4'-1" to 5'-6" L4 x 3 1/2 x 5/16 5'-7" to 7'-6" L5 x 3 1/2 x 5/16 7'-7" to 9'-6" L6 x 3 1/2 x 3/8
B. For 6" walls provide:
Span Limits Lintel Size 0'-0" to 4'-0" WT5x6 4'-1" to 5'-6" WT5x8.5 5'-7" to 9'-6" WT7x11 (interior)
WT7x13 (exterior)
STEEL CONSTRUCTION
1. Steel detailing, fabrication, and erection shall conform to the AISC Specification for Structural Steel Buildings and Code of Standard Practice, and the AWS Structural Welding Code.
2. Stresses occurring during fabrication, shipment, and erection shall be temporary and not excessive. Stresses at all times shall be less than design and allowable stresses. The full design and load-carrying capacity of the steel work shall not be impaired due to fabrication, shipment, or erection procedures. Throughout the complete process, the stability of all individual members and assembles shall be maintained.
3. The Contractor shall be responsible for the control of all erection procedures and sequences with relation to temperature differentials and weld shrinkage.
4. All additional steel required for erection purposes shall be provided at no additional cost and shall be removed unless approved by the Owner in writing.
5. Connections - welded or high strength bolted:
A. High-strength bolts shall be installed in accordance with "Specifications for
Structural Joints Using ASTM A325 or A490 Bolts".
B. A325N or A490N with hardened washers: use for all connections other than slip critical connections.
C. Provide hardened washers under nuts at all high-strength bolts, except where plate washers are used per AISC Specifications.
D. Unless snug tight connections are noted on the drawings as being permitted, all bolts should be tightened to full pretensioning load.
E. Use standard holes with the following exceptions: oversize holes are permitted when bolts are loaded in tension; short slotted holes are permitted for shear loading perpendicular to the slot.
F. Where minimum AISC fillet weld thickness requirement exceeds welds shown on details, or weld size is not specified, provide minimum AISC weld.
G. Wherever possible, use framed beam connections as listed in Tables 10-1 to 10-3 of AISC Manual of Steel Construction, 13th edition. The length of connection shall not be less than one-half of the T distance of the beam web.
H. Where reaction is noted, develop same. Where not noted, for non-composite beams, connections shall develop one-half of the total uniform load capacity of the beam.
6. Welding electrodes shall be E70XX except where other electrodes are required for compatibility with material being welded.
7. All slip connections shall be provided with a means of preventing the nuts from unthreading.
8. Shop drawings are required and shall note type of electrodes, size of all welds, and type and size of all bolts. Shop drawings shall be prepared under the supervision of a professional engineer licensed in the jurisdiction where the project is located.
9. Primer, see specifications.
10. Provide galvanized flexible masonry anchors (lateral ties) on all column faces that abut masonry wall. Anchor spacing to be 2'-0" o.c.
11. See all contract drawings for miscellaneous steel requirements.
12. All shop and field welding shall be performed by a recently certified welder.
13. All welding and high strength bolting must be inspected by a qualified testing laboratory. Laboratory shall be approved by the Architect and/or Engineer.
14. Provide fills at splices of parts differing by more than 1/8" in thickness.
15. Provide 1/4" closure plates at all open ends of HSS members.
16. Miscellaneous hanging loads such as stair stringers, pipes, mechanical units, etc., supported by steel members shall be applied in such a manner that no torsional forces are induced in the steel members, i.e., loads shall pass through the centerline of wide flange sections and through the shear center of channels.
STRUCTURAL STEEL WELDING
1. All welding shall be in strict conformance with the latest building code and AWS D1.1.
2. All welding electrodes (filler metal) shall be E70XX (70 ksi), unless otherwise noted.
3. Complete penetration groove welds shall have filler metal with Charpy V-notch toughness of 20 ft.-lbs. average at 0° F.
4. Certify conformance to Charpy V-notch toughness requirements with tests by an independent testing laboratory for each AWS classification, manufacturer, and trade name. The sizes as specified by AWS shall be tested.
5. Lengths of welds are effective lengths. Where length of weld is not shown, it shall be full length of joint. All butt welds shall be full penetration unless otherwise noted.
6. Welders shall be qualified and certified for the work they will be performing and shall have current certifications.
7. Faces of fillet welds exposed to view shall have as-welded surfaces that are reasonably smooth and uniform. No finishing or grinding shall be required, except where clearances or fit of other items may so necessitate.
8. All partial and full penetration welds which are exposed to view shall be ground smooth and flush with finish surface of steel. Holes shall be filled with weld metal or body solder and smoothed by grinding or filing.
9. Clean groove preparation thermal cuts by grinding.
10. Welds shall be terminated at the end of a joint in a manner that will ensure sound welds. Whenever necessary, this shall be done by the use of extension bars and run-off tabs.
11. To assure the proper amperage and voltage of the welding process, a hand-held calibrated amp and volt meter shall be used. This equipment shall be used by the fabricator, erector, and inspectors. Amperage and voltage shall be measured at the arc with this equipment. Travel speed and electrode stick out shall be verified to be in compliance with the electrode manufacturer's recommendations and with the approved WPS.
STEEL DECK
1. The metal decking shall be of the type and gauge as indicated on the drawings.
Decking and all accessories shall be formed from steel sheets conforming to ASTM A653. The steel shall be zinc coated conforming to ASTM A924, Class G60 as required in the specifications. Deck units shall be continuous over three or more spans where possible.
2. Diaphragm action shall be provided for in all areas with welding pattern in accordance with manufacturer's recommendations.
3. All welding of metal deck shall be in accordance with AWS D1.3.
4. All metal deck shall be welded to structural steel by qualified welders experienced in welding light-gauge steel, and using prequalified procedures. The erector shall establish a welding procedure for the arc spot welding weld of the steel decking to the structural steel of a particular gauge used. Prior to the start of erection of steel deck, each welder shall be qualified using this procedure and witnessed by the Contractor's testing agency.
5. Section properties shall be determined according to the Light Gauge Steel Institute.
6. Comply with Steel Deck Institute Specifications for deck attachment and connectors.
7. Steel deck shall be erected and fastened in accordance with the manufacturer's specifications and erection layouts.
ADHESIVE AND EXPANSION ANCHORS
1. For connections to existing concrete, use expansion bolts (HILTI KWIK TZ, or other approved) or adhesive anchors (HILTI HIT-Z rods or rebar with HILTI HIT-HY 200 adhesive, or other approved), with diameter and embedment length as noted on the drawings.
2. For connections to existing hollow solid or grout filled masonry, use adhesive anchors (HILTI HAS-E rods with HILTI HY 270 adhesive, or other approved), with diameter and embedment length as noted on the drawings. Screen tubes shall be used for all connections to hollow masonry.
3. Locate existing reinforcing by means of a rebar detector prior to drilling. Adjust the connection as required to avoid damaging any reinforcing.
4. Notify the Architect or Engineer if the existing concrete or masonry is cracked in the vicinity of the anchors prior to drilling.
ABBREVIATIONS
@ At A.B. Anchor Bolt AESS Architecturally Exposed
Structural Steel ARCH. Architect or Architectural BLDG. Building BLKG. Blocking B.O.F.