18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-2.pdf
PDF 9 MB Posted
- Solicitation number
- 36C25023B0049
About this file
This document package includes construction drawings and specifications for a federal contract opportunity with the Department of Veterans Affairs. The project involves constructing a new chiller plant addition at the VA Medical Center located in Columbus, Ohio. The drawings show the proposed site layout, demolition plans, life safety plans, and penetration firestopping details. Key requirements include installing new chillers, pumps, and associated mechanical equipment. Subcontractors will be responsible for demolition work, fire protection systems, and electrical systems. The solicitation is set aside for Service-Disabled Veteran-Owned Small Businesses and has a response due date of June 15th, 2022. The award date is slated for August 1st, 2022.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FINISHED CONTOURS
EXISTING CONTOURS
CONTRACT LIMIT LINE
PROPERTY LINE
ELEVATION INDICATORS
FINISH ELEVATION
EXISTING ELEVATION
FENCE
STRUCTURAL GRID COLUMN TAG (NEW)
STRUCTURAL GRID COLUMN TAG (EXISTING)
CENTERLINE
REVISION INDICATOR
DRAWING BREAK LINE
MATCH LINE INDICATOR
HIDDEN LINE
1. ITEMS ABOVE OR BEYOND
2. ITEMS NOT IN CONTRACT (N.I.C.)
3. ITEMS BEING DEMOLISHED
ELEVATION DATUM
WINDOW & LOUVER SYMBOL
(SEE WINDOW SCHEDULE)
DOOR SYMBOL
(SEE DOOR SCHEDULE)
EQUIPMENT SYMBOL
(SEE EQUIPMENT SCHEDULE)
WALL TYPE SYMBOL
(SEE PARTITION TYPES)
PARTITION NUMBER
WORK POINT
ROOM NUMBER SYMBOL
ELEVATION VIEW INDICATOR
DETAIL INDICATOR
SECTION INDICATOR
DRAWING TITLE
SCALE:
1 View Name 1/8" = 1'-0"A101
DETAIL NO.
DRAWING NO.
1'-0"
1'-0"
INTERIOR 01
INTERIOR 02
ELEVATION NO.
DRAWING NO. A101
ELEVATION NO.
Name Elevation
Name Elevation
A
A
NEW
EXISTING
SECTION NO.
DRAWING NO.
X
B 1
A101
A101
Room name
X
/1 A101
/1 A101
X X
NEW PARTITION
PATCH TO MATCH EXISTING PARTITION
EXISTING PARTITION TO REMAIN
EXISTING DOOR TO REMAIN
EXISTING DOOR TO BE REMOVED
NEW DOOR AND FRAME
POCKET DOOR
CASED OPENING
BIFOLD DOOR
SLIDING DOOR
Room name
Room name
AIR CONDITIONED
ACOUSTICAL CEILING TILE
AIR CONDITIONING UNIT
ABOVE FINISHED FLOOR
ALTERNATE
AUDIO VISUAL
ARCHITECTURAL WOODWORK
AC
A.C.T.
A.C.U.
A.F.F.
ALT
A.V.
A.W.
BD
BLDG
BLK
BLKG
BOT
BR
BRG
BSMT
CONC
CAB
C.B.B.
C.C.T.
C.G.
C.J.
CLR
CLG
C.M.U.
COL
COMM
CONF
CONN
CONST
CONT
CONTR
COORD
CORR
C.R.
C.W.
CYL
DBL
DEMO
DEPT
DET
D.F.
DIA
DIAG
DIM
DISP
DN
DR
D.S.
D.W.
DWG(S)
EXIST
E
EA EACH
EAST
EXISTING
DRAWING(S)
DUMBWAITER
DOWNSPOUT
DOOR
DOWN
DISPENSER
DIMENSION
DIAGONAL
DIAMETER
DRINKING FOUNTAIN
DETAIL
DEPARTMENT
DEMOLITION
DOUBLE
CYLINDER
COLD WATER
CRASH RAIL
CORRIDOR
COORDINATE
CONTRACTOR
CONTINUOUS
CONSTRUCTION
CONNECTION
CONFERENCE
COMMUNICATION
COLUMN
CONCRETE MASONRY UNIT
CEILING
CLEAR
CONTROL JOINT
CORNER GUARD
CUBICAL CURTAIN TRACK
CEMENTITIOUS BACKER BOARD
CABINET
CONCRETE
BASEMENT
BEARING
BRICK
BOTTOM
BLOCKING
BLOCK
BUILDING
BOARD
POUND OR NUMBER #
DIAMETER OR ROUND
CENTERLINE
AT
ANGLE
AND
EXPANSION JOINT
ELECTRICAL
E.I.F.S.
E.J.
ELECT
EL
ELEV
EMER
ENCL
EQ
EQUIP
E.T.R.
EVAC
E.W.C.
EXT
F.B.
F.C.
F.C.U.
F.D.
F.D.V.C.
F.E.
F.E.C.
F.H.C.
FIN
FIXT
FLR
FLEX
FLUOR
F.R.T.
FT
FTG
FURN
FUT
G
GA
GALV
G.C.
G.F.M.U.
GL
GR
GRND
GYP
H.B.
HD
HDWD
H.M.
HOSP
H.P.
HR
H.R.
HORIZ
HT
HTG
HTR
H.V.A.C.
H.W.
HW
HYD
I.D.
ILLUM
INCIN
INCAND
INCL
INFO
INSUL
INT
I.P.S.
ISOL
IV
JT
KITCH
K.O.
K.P.
K.S. KNEE SPACE
KICK PLATE
KNOCK OUT
KITCHEN
JOINT
INTRAVENOUS
ISOLATION
INSIDE PIPE SIZE
INTERIOR
INSULATION
INFORMATION
INCLUDE
INCINERATOR
INCANDESCENT
ILLUMINATION
INSIDE DIAMETER (DIM)
HYDRANT
HARDWARE
HOT WATER
HEATING, VENTILATION, AIR CONDITIONING
HEATER
HEATING
HEIGHT
HORIZONTAL
HANDRAIL
HOUR
HIGH POINT
HOSPITAL
HOLLOW METAL
HEAD
HOSE BIBB
GYPSUM
GROUND
GRADE
GLASS
GROUND FACE MASONRY UNITS
GENERAL CONTRACTOR
GALVANIZED
GAGE
GAS
FUTURE
FURNITURE
FOOTING
FOOT OR FEET
FIRE RESISTANT TREATED
FLUORESCENT
FLEXIBLE
FLOOR
FIXTURE
FINISH
FIRE HOSE CABINET
FIRE EXTINGUISHER CABINET
FIRE EXTINGUISHER
FIRE DEPARTMENT VALVE CABINET
FLOOR DRAIN
FAN COIL UNIT
FOOT CONTROL
FACE BRICK
EXTERIOR
ELECTRIC WATER COOLER
EVACUATION
EXISTING TO REMAIN
EQUIPMENT
EQUAL
ENCLOSURE
EMERGENCY
ELEVATOR
ELEVATION
L
LAB
LAM
LIB
LIN
LOC
L.P.
LT.WT.
LTG
MACH
MAS
MATL
MAX
MECH
MED
MED.CAB.
MEMB
MEZZ
MFR
MH
MIN
MISC
MKR.BD.
MLDG
M.O.
MOD
M.R.G.B.
MTD
MTL
N
N.C.
NEG
N.I.C.
NO
N.T.S.
O
O.C.
O.D.
OFF
OPNG
OPP
O.F.C.I.
PART.BD.
P.C.
P.C.D.
PERIM
PERP
PLWD
PORT
PR
PREFAB
PREFIN
PROJ
PROP
P.T.
PTD
R
R.A.
REC
RECEP
RECT
REF REFRIGERATOR
RECTANGULAR
RECEPTACLE
RECESSED
RETURN AIR
RADIUS
PAINTED
PNEUMATIC TUBE
PROPERTY
PROJECT
PREFINISHED
PREFABRICATED
PAIR
PORTABLE
PLYWOOD
PERPENDICULAR
PERIMETER
PAPER CUP DISPENSER
PRECAST CONCRETE
PARTICLEBOARD
OWNER FURNISHED, CONTRACTOR INSTALLED
OPPOSITE
OPENING
OFFICE
OUTSIDE DIAMETER(DIM)
ON CENTER
OXYGEN
NOT TO SCALE
NOMINAL
NUMBER
NOT IN CONTRACT
NEGATIVE
NURSE CALL
NITROGEN/NORTH
METAL
MOUNTED
MOISTURE RESISTANT GYPSUM BOARD
MODIFIED, MODULAR
MASONRY OPENING
MOULDING
MARKERBOARD
MISCELLANEOUS
MINIMUM
MANHOLE
MANUFACTURER
MEZZANINE
MEMBRANE
MEDICINE CABINET
MEDICINE/MEDICAL
MECHANICAL
MAXIMUM
MATERIAL
MASONRY
MACHINE
LIGHTING
LIGHTWEIGHT
LOW POINT
LOCATION/LOCATE
LINEAR
LIBRARY
LAMINATE
LABORATORY
LOCK
REFL REFLECTED
REINF REINFORCED
REM REMOVABLE
REQ'D REQUIRED
REV REVISION
R.F. RADIO FREQUENCY
RM
RND
R.O.
R.S.T. RUBBER STAIR TREADS
ROUGH OPENING
ROUND
S
S.S.
S.A.
SAN
SCHED
S.C.R.
S.D.
SECT
SGL
SH
SHR
SHT
SIM
S.O.G.
SPEC (S)
S&R
S.P.T.
SQ
S.F.
S.I.
S.Y.
S.T.C.
STD
STL
STOR
STRUCT
SURF
SUSP
T
T&B
T&G
TAN
TEL
TEMP
THRESH
THRU
TK.BD.
TLT
T.O.P.
TV
TYP
U.C.
UNFIN
U.O.N.
UTIL
V, VAC
VENT
VERT
VEST
VIT
W
W/
W/O
W.C.
W/C
WD
W.P.
YD YARD
WORKPOINT
WOOD
WHEEL CHAIR
WATER CLOSET
WITHOUT
WITH
WEST/WATER
VITREOUS
VESTIBULE
VERTICAL
VENTILATION
VACUUM
UTILITY
UNLESS OTHERWISE NOTED
UNFINISHED
UNDER COUNTER
TYPICAL
TELEVISION
TOP OF PAVEMENT
TOILET
TACKBOARD
THROUGH
THRESHOLD
TEMPERATURE
TELEPHONE
TANGENT
TONGUE AND GROOVE
TOP AND BOTTOM
THERMOSTAT
SUSPENDED
SURFACE
STRUCTURAL
STORAGE
STEEL
STANDARD
SOUND TRANSMISSION CLASS / COEFFICIENT
SQUARE YARD
SQUARE INCH
SQUARE FOOT
SQUARE
SPECIMEN PASS-THRU
SHELF & ROD
SPECIFICATION(S)
SLAB ON GRADE
SIMILAR
SHEET
SHOWER
SHELVING, SHELF
SINGLE
SECTION
SUPPLY DIFFUSER
SHOWER CURTAIN ROD
SCHEDULE
SANITARY
SUPPLY AIR
STAINLESS STEEL
SOUTH
LT LIGHT
LAV LAVATORY
W.W.F. WELDED WIRE FABRIC
EXTERIOR INSULATION FINISH SYSTEM
HARDWOOD
NOM
ROOM
V.I.F. VERIFY IN FIELD
ALUMINUMAL
F.P. FIRE PROTECTION
F.P.G. FIRE PROTECTED GLAZING
CL
O.F.O.I. OWNER FURNISHED, OWNER INSTALLED
SSM SOLID SURFACE MATERIAL
NOTE: ALL ITEMS/MATERIALS MAY NOT OCCUR IN THIS PROJECT. LIST PROVIDED FOR REFERENCE ONLY.
UNDISTURBED EARTH OR UNDISTURBED SUBGRADE
COMPACTED EARTH OR COMPACTED SUBGRADE
ROCK
POROUS FILL OR SUBBASE
IMPERVIOUS FILL
DRAINAGE FILL
CAST-IN-PLACE CONCRETE
PRECAST CONCRETE
TOPSOIL
CEMENTITIOUS DECKS AND TOPPINGS
GROUT
BRICK
GLAZED BRICK
STRUCTURAL CLAY TILE UNIT MASONRY
GLAZED STRUCTURAL CLAY TILE UNIT MASONRY
CONCRETE UNIT MASONRY
GLAZED CONCRETE UNIT MASONRY
GLAZED UNIT MASONRY
CUT STONE
FIREBRICK
CAST STONE
STEEL
ALUMINUM
ORNAMENTAL METAL/STAINLESS STEEL
CONTINUOUS WOOD FRAMING
WOOD BLOCKING
PLYWOOD
PARTICLE BOARD
FINISHED LUMBER FOR ARCHITECTURAL WORK
BATT INSULATION
RIGID INSULATION
LOOSE FILL INSULATION
EXTERIOR INSULATION AND FINISH SYSTEM
FIBROUS FIRE SAFING
GLASS
CARPET
LATH AND PLASTER
GYPSUM BOARD
PLASTIC GLAZING
TERRAZZO
ACOUSTICAL CEILING
RESILIENT TILE
CERAMIC TILE
GRAPHIC SYMBOLS
FLOOR PLAN LEGEND
STANDARD ABBREVIATIONS
MATERIALS LEGEND
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
C U s e rs
\j c h o \D o c u m e n ts
\R e v it M o d e ls
\1
R
V A
C o lu m b u s C h ill e r
P la n t R e v is io n
C e n tr a l_ jd c h o
.r v t
/5
/2
:0
:4
A
M
G-101
NOTES AND SYMBOLS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 RG jdc
BID & CONSTRUCTION
(REVISED)18912
Revisions: Date:
FINAL BID & CONSTRUCTION 11/24/2021
FINAL BID & CONSTRUCTION (REVISED) 05/06/2022
UP
DN
UP
EC-114
CHILLER PLANT
CORRIDOR
EXISTING
AREA N.I.C.
F.E.C.
T R
A V
E L D
IS
T
A N
C E
'-6
TRAVEL D
IS
TANCE -
79'-0
EXISTING
MANAGER'S
OFFICEEXISTING
BREAK ROOM
EXISTING
JANITORS
CLOSET
EXISTING
TELE/DATA
ROOM
EXISTING
TOILET /
SHOWER
EXISTING
ELECTRICAL ROOM
EXISTING
STORAGE
EXISTING
ELECTRICAL ROOM
EXISTING
STAIR 'A'
5,180 S.F. / 100 = 52 OCCUPANTS
EXISTING
STORAGE
EXISTING BOILER PLANT TRAVEL DISTANCE,
EGRESS WIDTH AND OCCUPANT LOAD NOT
AFFECTED WITH NEW CHILLER PLANT ADDITION.
26 OCC.
26 OCC.
EC-115
EXISTING CONTROL
ROOM
EC-116
EXISTING BOILER
ROOM
EXISTING
EGRESS
71 OCC
EXISTING
EGRESS
35 OCC.
EXISTING
EGRESS
15 OCC.
EXIST. F.E.C.
EXIST. F.E.C.
EXIST. F.E.C.
F.E.
EXISTING 1HR RATED PARTITION (TYP.)
EXISTING 1HR RATED
PARTITION (TYP.)
F.E.
F.E.
F.E.
F.E.
F.E.
F.E.C. FIRE EXTINGUISHER CABINET
TRAVEL DISTANCE
EXIT SIGN
EGRESS DIRECTION
F.E. FIRE EXTINGUISHER
1 HOUR RATED PARTITION
1. SEE COVER SHEET FOR CODE REVIEW
EXISTING
EGRESS
28 OCC
OPEN TO
BOILER PLANT
BELOW
OPEN TO
CHILLER PLANT
BELOW
EXISTING 1HR RATED
PARTITION (TYP.)
EXISTING 1HR RATED PARTITION (TYP.)
EXISTING 1HR RATED
PARTITION (TYP.)
EXIST.
FEC
EXIST.
FEC
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
C U s e rs
\j c h o \D o c u m e n ts
\R e v it M o d e ls
\1
R
V A
C o lu m b u s C h ill e r
P la n t R e v is io n
C e n tr a l_ jd c h o
.r v t
/5
/2
:0
:5
A
M
G-102
LIFE SAFETY PLAN CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 RG jdc
BID & CONSTRUCTION
(REVISED)18912
SCALE: 1/8" = 1'-0"G-102
1 LIFE SAFETY PLAN - FIRST FLOOR
FIRE PROTECTION LEGEND
LIFE SAFETY GENERAL NOTES
SCALE: 1/8" = 1'-0"G-102
2 LIFE SAFETY PLAN - SECOND FLOOR
Revisions: Date:
++ L RATING APPLIES ONLY TO CP 680-P DEVICES AND ONLY WHEN THE NOM DIAM OF PIPE EQUALS SIZE OF DEVICE (2 IN. DIAM PIPE IN 2"
DEVICE ETC.) L RATING DOES NOT APPLY TO CP 680N DEVICES.
4. FIRESTOP DEVICE* — (NOT SHOWN) -TOP SEAL PLUG FOR USE WITH CP 680-75/2.5"N DEVICES AND NOM PIPE OR CONDUIT SIZES 3/4 IN. (19 MM) TO 2 IN. (51 MM), INSTALLED IN ACCORDANCE WITH THE MANUFACTURER\'S INSTRUCTIONS. THE TOP SEAL PLUG IS OPTIONAL FOR NOM 1-1/2 IN. (38 MM) PIPES AND CONDUITS. TOP SEAL PLUGS ARE REQUIRED FOR ALL PIPES AND CONDUITS LESS THAN NOM 1-1/2 IN. (38
MM). W RATING APPLIES ONLY WHEN THE CPS OR IPS TOP SEAL PLUGS ARE USED.
4A. FIRESTOP DEVICE* - WATER BARRIER MODULE — (OPTIONAL, NOT SHOWN) - APPLIES TO NOM 2", 3" AND 4" WATER BARRIER MODULES USED IN COMBINATION WITH THE CP 680-P 2", CP 680-P 3" AND CP 680-P 4" DEVICES, RESPECTIVELY, AND SUPPLIED BY DEVICE MANUFACTURER. MODULE IS THREADED ONTO TOP OF DEVICE. W RATING APPLIES ONLY WHEN WATER BARRIER MODULE IS USED.
*BEARING THE UL CLASSIFICATION MARK
+BEARING THE UL LISTING MARK
1. FLOOR ASSEMBLY — MIN 2-1/2 IN. (64 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3)
CONCRETE.
1A. FLOOR ASSEMBLY - (OPTIONAL - NOT SHOWN) — THE FIRE RATED UNPROTECTED CONCRETE AND STEEL FLOOR ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL D900 SERIES DESIGNS IN THE UL FIRE
RESISTANCE DIRECTORY AND AS SUMMARIZED BELOW:
A. CONCRETE — MIN 2-1/2 IN (64 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3
CONCRETE.
B. STEEL FLOOR AND FORM UNITS* — COMPOSITE OR NON-COMPOSITE MAX 3 IN. (76 MM) DEEP GALV STEEL FLUTED UNITS AS
SPECIFIED IN THE INDIVIDUAL FLOOR-CEILING DESIGN
NOM PIPE DIAMETER FIRESTOP DEVICE
CP 680-75/2.5"N
CP 680 -P 2"
CP 680-P 3"
CP 680-1 10/4"N
CP 680-P 4"
CP 680-160/6"N
CP 680-P 6"
1/2 IN. TO 2 IN. (19 MM TO 51 MM)
3 IN.(76 MM)
3 IN. TO 4 IN. (76 MM TO 102 MM)
6 IN. (152 MM)
2 3
A
A
SECTION A-A
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US SYSTEM NO. F-A-2053
F RATING - 2 HR
T RATING - 0 HR
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)
W RATINGS - CLASS 1 (SEE ITEMS 3, 4, AND 4A)
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US SYSTEM NO. F-A-2054
F RATING - 3 HR
T RATING - 0 AND 3 HR (SEE ITEM 3)
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)
W RATINGS - CLASS 1 (SEE ITEMS 3, 4, AND 4A)
1. FLOOR ASSEMBLY — MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3)
CONCRETE.
1A. FLOOR ASSEMBLY - (OPTIONAL - NOT SHOWN) — THE FIRE RATED UNPROTECTED CONCRETE AND STEEL FLOOR ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL D900 SERIES DESIGNS IN THE UL FIRE RESISTANCE
DIRECTORY AND AS SUMMARIZED BELOW:
A. CONCRETE — MIN 4-1/2 IN (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3)
CONCRETE.
B. STEEL FLOOR AND FORM UNITS* — COMPOSITE OR NON-COMPOSITE MAX 3 IN. (76 MM) DEEP GALV STEEL FLUTED UNITS AS SPECIFIED
IN THE INDIVIDUAL FLOOR-CEILING DESIGN.
2. FIRESTOP DEVICE* — CAST IN PLACE FIRESTOP DEVICE PERMANENTLY EMBEDDED DURING CONCRETE PLACEMENT OR GROUTED IN CONCRETE ASSEMBLY IN ACCORDANCE WITH ACCOMPANYING INSTALLATION INSTRUCTIONS. THE DEVICES MAY EXTEND A MAX 2 IN. (51 MM)
ABOVE THE TOP SURFACE OF THE CONCRETE.
3. THROUGH PENETRANTS — ONE NONMETALLIC PIPE OR CONDUIT TO BE INSTALLED WITHIN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. FOR W RATING WITH WATER BARRIER MODULE, PIPE SHALL BE INSTALLED FROM BOTTOM OF DEVICE. THE FOLLOWING TYPES AND SIZES OF NONMETALLIC PIPES OR CONDUITS MAY BE USED:
A. POLYVINYL CHLORIDE (PVC) PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 SOLID OR CELLULAR CORE PVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS.
B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE — PIPE-NOM 6 IN. (152 MM) DIAM (OR SMALLER) SDR11 OR SDR13.5 CPVC PIPE FOR
USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS.
C. RIGID NONMETALLIC CONDUIT+ — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 PVC CONDUIT INSTALLED IN ACCORDANCE
WITH THE NATIONAL ELECTRICAL CODE (NFPA NO. 70).
THE FIRESTOP DEVICES AND NONMETALLIC PENETRANTS SHALL BE SIZED AS FOLLOWS:
+3 HR T RATING APPLIES WHEN CP 680-P 3" AND CP 680-P 4" DEVICES ARE USED. 3 HR T RATING ALSO APPLIED WHEN CP 680-110/4"N DEVICE IS USED PROVIDED THAT MIN 4 IN. (102 MM) THICKNESS OF NOM 4 PCF (64 KG.M3) MINERAL WOOL BATT INSULATION TIGHTLY PACKED WITHIN ANNULUS BETWEEN PIPE AND WALL OF CP 680-110/4"N DEVICE. ++ L RATING APPLIES ONLY TO CP 680-P DEVICES AND ONLY WHEN THE NOM DIAM OF PIPE EQUALS SIZE OF DEVICE (2 IN. DIAM PIPE IN 2" DEVICE ETC.) L RATING DOES NOT APPLY TO CP 680N DEVICES.
4. FIRESTOP DEVICE — TOP SEAL PLUG FOR USE WITH CP 680-P 2" DEVICE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. THE TOP SEAL PLUG IS OPTIONAL FOR NOM 1-1/2 IN. (38 MM) PIPES AND CONDUITS. TOP SEAL PLUGS ARE REQUIRED FOR
ALL PIPES AND CONDUITS LESS THAN NOM 1-1/2 IN. (38 MM). W RATING APPLIES ONLY TO THE IPS TOP SEAL PLUG AND NOM 2 IN. DIAM PENETRANTS AND CPS TOP SEAL PLUG FOR NOM ½ TO 2 IN. (13 TO 51 MM) DIAM PENETRANTS.
4A. FIRESTOP DEVICE* - WATER BARRIER MODULE — (OPTIONAL, NOT SHOWN) - ALTERNATE TO TOP SEAL PLUG (ITEM 4). APPLIES TO NOM 2", 3", 4" AND 6" WATER BARRIER MODULES USED IN COMBINATION WITH THE CP 680-P 2", CP 680-P 3", CP 680-P 4" AND CP 680-P 6" DEVICES, RESPECTIVELY, AND SUPPLIED BY DEVICE MANUFACTURER. MODULE IS THREADED ONTO TOP OF DEVICE. W RATING APPLIES ONLY WHEN
WATER BARRIER MODULE IS USED AND NOM DIAM OF PENETRANT EQUALS SIZE OF DEVICE.
*BEARING THE UL CLASSIFICATION MARK
+BEARING THE UL LISTING MARK
NOM PIPE DIAMETER FIRESTOP DEVICE T RATING - HR
1/2 IN. TO 2 IN.
(19 MM TO 51 MM)
3 IN. (76 MM)
4 IN. (102 MM)
6 IN. (152 MM)
CP 680-75/2.5"N
CP 680-P 2"
CP 680-110-P 4"
CP 680-110/4"N
CP 680-P 3", CP 680-P 4"
CP 680-P 4"
CP 680-160/6"N
CP 680-P 6"
0 AND 3+
SINGLE NON-METALLIC PIPE OR CONDUIT
A A
SECTION A-A
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US C
R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
CIRCULAR BLANK OPENINGS SINGLE NON-METALLIC PIPE OR CONDUITSINGLE INSULATED PIPES
SINGLE INSULATED PIPES
SYSTEM NO. C-BJ-2016
F RATING - 4 HR
T RATING - 2 HR
SYSTEM NO. C-BJ-5006
F RATING - 4 HR
T RATING - 1/2 HR
SYSTEM NO. C-BJ-1034
F RATING - 4 HR
T RATING - 0 HR
1. FLOOR OR WALL ASSEMBLY — MIN 5-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE FLOOR OR MIN 6 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 10-1/2 IN.SEE CONCRETE
BLOCKS (CAZT) CATEGORY IN FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
2. THROUGH-PENETRANTS — ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. AN ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN 3/4 IN. TO MAX 3 IN. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR
TUBING MAY BE USED:
A. STEEL PIPE — NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. CONDUIT — NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR STEEL CONDUIT.
3. PACKING MATERIAL — MIN 4 IN. THICKNESS OF MIN 4.0 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.
4. FILL, VOID OR CAVITY MATERIAL* — CAULK — MIN 1 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL. A MIN 1/2 IN. DIAM BEAD FILL MATERIAL TO BE INSTALLED AT INTERFACE OF PIPE, CONDUIT OR TUBING AND METAL COVER PLATE (ITEM NO. 5) AND OVER BUTTED
SEAMS OF METAL COVER PLATE.
5. METAL COVER PLATE — TWO PIECE COVER PLATE OF MIN 18 GAUGE STEEL WITH I.D. SAME AS O.D. OF PIPE, CONDUIT OR TUBING. O.D. OF COVER PLATE TO BE SIZED TO OVERLAP THE PERIPHERY OF OPENING A MIN 1-1/2 IN. INSTALLED AT TOP SURFACE OF FLOOR OR BOTH SIDES OF WALL. TWO PIECES TO BE BUTTED TOGETHER AROUND PERIMETER OF PIPE OR CONDUIT AND SECURED WITH 1/4 IN. DIAM BY MIN 1 IN. LONG STEEL EXPANSION BOLTS, OR EQUIVALENT, IN CONJUNCTION WITH STEEL NUTS AND WASHERS A MAX OF 1 IN. FROM EACH SIDE OF EACH SEAM AND A MAX OF 4 IN. OC
THROUGHOUT.
*BEARING THE UL CLASSIFICATION MARK
A
A SECTION A-A
SYSTEM NO. C-AJ-0055
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F RATING - 3 HR
FT RATING - 0 HR
FH RATINGS - 3 HR
FTH RATING - 0HR
F RATING - 3 HR
T RATING - 0 HR
1. FLOOR OR WALL ASSEMBLY- MIN 4-112 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PEL) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS'. MAX
DIAM OF OPENING IS 4 IN. (102 MM).
2. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF
MANUFACTURERS.
3. METALLIC SLEEVE- NOM 4 IN. (102 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL PIPE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH FLOOR OR WALL SURFACES. SLEEVE MAY EXTEND MAX
3 IN. (76 MM) ABOVE TOP SURFACE OF FLOOR.
4. FILL, VOID OR CAVITY MATENAL'- FIRE BLOCK MIN 2 IN. (51 MM) THICK CUT TO A DIAM 1/2 IN. (13 MM) LARGER THAN
THE OPENING, FLUSH WITH BOTTOM SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL.
*BEARING THE UL CLASSIFICATION MARK
A
A
SECTION A-A
1. FLOOR OR WALL ASSEMBLY -- MIN 6 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE.
WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAMETER OF OPENING IS 3 IN.
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS
2. STEEL SLEEVE -- NOM 3 IN. DIAM SCHEDULE 40 (OR SMALLER) STEEL PIPE CAST OR GROUTED INTO FLOOR OR WALL
ASSEMBLY, FLUSH WITH FLOOR OR WALL SURFACES.
3. POLYVINYLIDENE FLUORIDE PVDF PIPE -- NOM 2 IN. DIAM (OR SMALLER) SCHEDULE 40 PVDF FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS. ANNULAR SPACE BETWEEN PIPE AND SLEEVE TO BE MIN 0 IN. (POINT CONTACT) AND MAX 5/8 IN. PIPE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR
OR WALL ASSEMBLY.
4. FIRESTOP SYSTEM -- THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. FILL, VOID OR CAVITY MATERIALS*-SEALANT -- MIN 1/2 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTTOM SURFACE OF FLOOR OR BOTH SURFACES OF WALL.
B. B. FILL, VOID OR CAVITY MATERIAL* -- WRAP STRIP -- NOM 1/4 IN. THICK BY 2 IN. WIDE INTUMESCENT WRAP STRIP. TWO
LAYERS OF WRAP STRIP ARE CONTINUOUSLY WRAPPED AROUND THE PIPE AND HELD IN PLACE WITH TAPE. WRAP
STRIP BUTTED TIGHTLY AGAINST BOTTOM SURFACE OF FLOOR OR BOTH SURFACES OF WALL.
C. STEEL COLLAR -- COLLAR FABRICATED FROM COILS OF PRECUT MIN 0.017 IN. THICK (NO. 28 MSG) GALV STEEL AVAILABLE FROM THE SEALANT MANUFACTURER. COLLAR SHALL BE NOM 1-3/4 IN. DEEP WITH 1 IN. WIDE BY 2 IN. LONG ANCHORS TABS ON 2 IN. CENTERS FOR SECUREMENT TO FLOOR OR WALL ASSEMBLY. THE ANCHOR TABS SHALL BE BENT 90 DEGREE OUTWARD FOR SECUREMENT TO THE FLOOR OR WALL ASSEMBLY. THE OPPOSITE SIDE INCORPORATES RETAINER TABS, 1/2 IN. WIDE BY 3/16 IN. LONG, PREBENT TOWARD THE PIPE SURFACE. COLLAR SHALL BE TIGHTLY WRAPPED OVER THE WRAP STRIP, OVERLAPPING MIN. 1 IN AT SEAM. A NOM 1/2 IN. WIDE STAINLESS STEEL HOSE CLAMP SHALL BE SECURED TO THE COLLAR AT ITS MID-HEIGHT. EVERY OTHER ANCHOR TAB OF COLLAR SECURED TO CONCRETE SLAB WITH 1/4 IN. DIAM BY 1-3/4 IN. LONG STEEL EXPANSION TYPE MASONRY FASTENERS, 1-1/2 IN LONG CONCRETE SCREW ANCHORS OR 0.145 IN. DIAM BY 1-1/4 IN. LONG POWDER ACTUATED FASTENERS UTILIZING A 1-7/16 DIAM BY 1/16 IN. THICK STEEL WASHER. IN FLOOR ASSEMBLIES, ONE COLLAR TO BE USED AT THE BOTTOM OF THE CONCRETE FLOOR ONLY. IN WALL ASSEMBLIES, A COLLAR IS USED ON BOTH SURFACES.
*BEARING THE UL CLASSIFICATION MARK
4A
4B
4C
1 2
1. 1. FLOOR OR WALL ASSEMBLY — MIN 5-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE FLOOR OR MIN 6 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 29 IN.
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
2. THROUGH-PENETRANTS — ONE METALLIC PIPE TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN
THE FIRESTOP SYSTEM. PIPE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING
TYPES AND SIZES OF METALLIC PIPES MAY BE USED:
A. STEEL PIPE — NOM 20 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
3. PIPE COVERING — MAX 3 IN. THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 3.5 PCF) GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS OR FACTORY- APPLIED SELF-SEALING LAP TAPE.TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH BUTT TAPE SUPPLIED WITH THE PRODUCT. PIPE COVERING TO TERMINATE MIN 6 IN. FROM EACH SIDE OF FLOOR OR WALL ASSEMBLY. SEE PIPE AND EQUIPMENT COVERING — MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS
MAY BE USED.
4. FIRESTOP SYSTEM — THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. PIPE COVERING* — MAX 3 IN. THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 5.2 PCF) UNFACED MINERAL WOOL
UNITS EXTENDING MIN 6 IN. BEYOND EACH SURFACE OF THE FLOOR OR WALL. PIPE COVERING SECURED WITH NO. 18 GAUGE TIE WIRE 3 IN. BEYOND EACH SURFACE OF THE CONCRETE SLAB. THE ANNULAR SPACE SHALL BE MIN 1 IN. TO MAX 2-1/4 IN. SEE PIPE AND EQUIPMENT COVERING — MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE
DEVELOPED INDEX OF 50 OR LESS MAY BE USED.
B. SHEATHING MATERIAL* — ALL SERVICE JACKET MATERIAL SHALL BE WRAPPED AROUND THE OUTER CIRCUMFERENCE OF THE PIPE COVERING MATERIAL (ITEM 4A) WITH KRAFT FACING EXPOSED. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS. SEE SHEATHING MATERIAL (BVDV) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY SHEATHING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR
LESS MAY BE USED.
C. PACKING MATERIAL — MIN 4 IN. THICKNESS OF MIN 4.0 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.
D. FILL, VOID OR CAVITY MATERIAL* — CAULK — MIN 1 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL. A MIN 1/2 IN. DIAM BEAD FILL MATERIAL TO BE INSTALLED AT INTERFACE OF PIPE COVERING AND METAL COVER PLATE (ITEM NO. 4E) AND OVER BUTTED SEAMS
OF METAL COVER PLATE.
E. METAL COVER PLATE — TWO PIECE COVER PLATE OF MIN 18 GAUGE STEEL WITH I.D. SAME AS O.D. OF PIPE, CONDUIT OR TUBING. O.D. OF COVER PLATE TO BE SIZED TO OVERLAP THE PERIPHERY OF OPENING A MIN 1-1/2 IN. INSTALLED AT TOP SURFACE OF FLOOR OR BOTH SIDES OF WALL. TWO PIECES TO BE BUTTED TOGETHER AROUND PERIMETER OF PIPE, PENETRATING THE SHEATHING MATERIAL AND PIPE COVERING (ITEM NOS. 4B AND 4A) TO FULLY CONTACT THE PIPE. SECURED WITH 1/4 IN. DIAM BY MIN 1 IN. LONG STEEL EXPANSION BOLTS, OR EQUIVALENT, IN CONJUNCTION WITH STEEL NUTS AND WASHERS A MAX OF 1 IN. FROM EACH SIDE OF EACH SEAM AND A MAX OF 4 IN. OC THROUGHOUT.
*BEARING THE UL CLASSIFICATION MARK
A
A
SECTION A-A
4E 4D
4C
4D
4A
4B
SINGLE NON-METALLIC PIPE OR CONDUIT SINGLE INSULATED PIPES
NOM PIPE DIAM, IN.
(MM)
NOM THICK. OF PIPE
INSUL., IN. (MM)
FIRESTOP DEVICE T-
RATING,
HR
1/2 (13)
1 (25)
2 (51)
2 (51)
4 (102)
1 (25)
1 (25) (SEE ITEM 5)
1 (25)
3/4 (19)
1 (25)
1 (25)
1 (25)
3/4(19)
3/4(19)
CP 680-75/2.5"N, CP 682-72/2.5"CP
680-M 2", CP 680-P 2"
CP 680-75/2.5"N CP 680-P 3"
CP 680-M 3", CP 680-P 3"
CP 682-110/4"CP 680-M 4"
CP 680 110/4"N, CP682 110/4"CP
680-M 4", CP 680-P 4"
CP 680-100/4"NCP 680-P 4"
CP 680-160/6"NCP 680-P 6
3/4
1/2
1/2
1/2
1/2
1/2
1/2
4. TUBE INSULATION - PLASTICS+ - NOM 3/4 OR 1 IN. (19 OR 25 MM) THICK ACRYONITRILE BUTADIENE/POLYVINYL CHLORIDE (AB/PVC) FLEXIBLE FOAM FURNISHED IN THE FORM OF TUBING. SEE PLASTICS+ (QMFZ2) CATEGORY IN THE PLASTICS RECOGNIZED COMPONENT DIRECTORY FOR NAMES OF MANUFACTURERS. ANY RECOGNIZED COMPONENT TUBE INSULATION MATERIAL MEETING THE ABOVE SPECIFICATIONS AND HAVING A UL94
FLAMMABILITY CLASSIFICATION OF 94-5VA MAY BE USED.
5. PACKING MATERIAL - (NOT SHOWN) - WHEN USING A 1 IN. (25 MM) DIAM PIPE WITH 1 IN. (25 MM) AB/PVC PIPE INSULATION IN A 4 IN. (102 MM) DEVICE, AND A MIN 2 IN. (51 MM) THICKNESS OF MIN 4 PCF (64 KG/M³) MINERAL WOOL BATT INSULATION SHALL BE FIRMLY PACKED INTO TOP OF DEVICES, FLUSH WITH THE TOP OF THE DEVICE.
*BEARING THE UL CLASSIFICATION MARK
THE FIRESTOP DEVICE AND METALLIC PENETRANT SHALL BE SIZED AS FOLLOWS:
1. FLOOR OR WALL ASSEMBLY - MIN 2-1/2 IN. (64 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150
PCF OR 1600-2400 KG/M³) CONCRETE.
1A. FLOOR ASSEMBLY - (OPTIONAL - NOT SHOWN) - THE FIRE RATED UNPROTECTED CONCRETE AND STEEL FLOOR ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN TEH MANNER SPECIFIED IN TEH INDIVIDUAL D900
SERIES DESIGNS IN THE FIRE RESISTANCE DIRECTORY AND AS SUMMARIZED BELOW:
A. STEEL FLOOR AND FORM UNITS* - COMPOSITE OR NON-COMPOSITE MAX 2 IN. (76 MM) DEEP GALV STEEL FLUTED
UNITS AS SPECIFIED IN THE INDIVIDUAL FLOOR-CEILING DESIGN.
B. CONCRETE - MIN 2-1/2 IN. (64 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR
1600-2400 KG/M³) CONCRETE.
2. FIRESTOP DEVICE* - CAST IN PLACE FIRESTOP DEVICE PERMANENTLY EMBEDDED DURING CONCRETE PLACEMENT OR GROUTED IN CONCRETE FLOOR ASSEMBLY IN ACCORDANCE WITH ACCOMPANYING INSTALLATION INSTRUCTIONS
WITH A MAX 2 IN. (51 MM) PROJECTION ABOVE THE TOP SURFACE OF THE CONCRETE.
3. THROUGH PENERANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED WITHIN THE FIRESTOP DEVICE.
PIPE, CONDUIT, OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. THE FOLLOWING
TYPES OF PIPE, CONDUIT OR TUBING MAY BE USED:
A. STEEL PIPE - NOM. 4 IN. (102 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. COPPER TUBING - NOM 4 IN. (102 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
C. COPPER PIPE. - NOM 4 IN. (102 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
SYSTEM NO. F-A-5015
F RATING - 2 HR
T RATING - 1/2 HR AND 3/4 HR (SEE ITEM 3)
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
SECTION A-A
A A
4 3
2. FIRESTOP DEVICE* — CAST IN PLACE FIRESTOP DEVICE PERMANENTLY EMBEDDED DURING CONCRETE PLACEMENT OR GROUTED IN CONCRETE ASSEMBLY IN ACCORDANCE WITH ACCOMPANYING INSTALLATION INSTRUCTIONS. THE 3, 4 AND 6 IN. DEVICES MAY EXTEND A MAX 2 IN. (51 MM) ABOVE THE TOP SURFACE OF THE CONCRETE. THE MAX EXTENSION ABOVE THE SLAB FOR THE 2 AND 2.5 IN. DEVICES IS
NOT RESTRICTED.
3. THROUGH PENETRANTS — ONE NONMETALLIC PIPE OR CONDUIT TO BE INSTALLED WITHIN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. FOR W RATING WITH WATER BARRIER MODULE, PIPE SHALL BE INSTALLED FROM BOTTOM OF DEVICE. THE FOLLOWING TYPES AND SIZES OF NONMETALLIC PIPES OR CONDUITS MAY BE USED:
A. POLYVINYL CHLORIDE (PVC) PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 SOLID OR CELLULAR CORE PVC PIPE FOR
USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS.
B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SDR11 OR SDR13.5 CPVC PIPE FOR USE IN
CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS.
C. RIGID NONMETALLIC CONDUIT — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 PVC CONDUIT INSTALLED IN ACCORDANCE
WITH THE NATIONAL ELECTRICAL CODE (NFPA NO. 70).
THE FIRESTOP DEVICES AND NONMETALLIC PENETRANTS SHALL BE SIZED AS FOLLOWS:
GENERAL NOTES:
1. REFER TO SECTION 07 84 00 OF THE SPECIFICATIONS FOR QUALITY CONTROL REQUIREMENTS.
2. DETAILS SHOWN ARE FOR TYPICAL APPLICATIONS AND MAY NOT BE INCLUSIVE OF ALL PROJECT REQUIREMENTS.
SOME DETAILS COULD BE USED FOR EITHER WALL OR FLOOR APPLICATIONS. IF FIELD CONDITIONS DO NOT MATCH
REQUIREMENTS OF TYPICAL DETAILS, CONTRACTOR SELECTED MANUFACTURER APPROVED ALTERNATE DETAILS SHALL BE UTILIZED. FIELD CONDITIONS AND DIMENSIONS NEED TO BE VERIFIED FOR COMPLIANCE WITH THE
DETAILS, INCLUDING BUT NOT LIMITED TO THE FOLLOWING: * MINIMUM AND MAXIMUM WIDTH OF JOINTS * TYPE AND
THICKNESS OF FIRE-RATED CONSTRUCTION. THE MINIMUM ASSEMBLY RATING OF THE FIRESTOP ASSEMBLY SHALL
MEET OR EXCEED THE HIGHEST RATING OF THE ADJACENT CONSTRUCTION.
3. IF ALTERNATE DETAILS MATCHING THE FIELD CONDITIONS ARE NOT AVAILABLE, MANUFACTURER'S ENGINEERING
JUDGMENT DRAWINGS ARE ACCEPTABLE. DRAWINGS SHALL FOLLOW THE INTERNATIONAL FIRESTOP COUNCIL
(IFC) GUIDELINES FOR EVALUATING FIRESTOP SYSTEMS ENGINEERING JUDGMENTS. PROVIDE ARCHITECT WITH
REQUIRED SUBMITTALS.
4. FIRESTOP SYSTEM INSTALLATION MUST MEET REQUIREMENTS OF ASTM E-814 (UL 1479) TESTED ASSEMBLIES THAT
PROVIDE A FIRE RATING EQUAL TO THAT OF CONSTRUCTION BEING PENETRATED.
5. ALL RATED THROUGH-PENETRATION ASSEMBLIES SHALL BE PROMINENTLY LABELED.
6. FOR OUTLET BOXES REQUIRING PROTECTION, USE ONLY WALL OPENING PROTECTIVE MATERIALS, CATEGORY CLIV
AS CLASSIFIED BY UNDERWRITER'S LABORATORIES, FIRE RESISTANCE DIRECTORY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
C U s e rs
\j c h o \D o c u m e n ts
\R e v it M o d e ls
\1
R
V A
C o lu m b u s C h ill e r
P la n t R e v is io n
C e n tr a l_ jd c h o
.r v t
/5
/2
:0
:5
A
M
G-103
PENETRATION FIRE STOPPING DETAILS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 -- --
BID & CONSTRUCTION
(REVISED)18912
Revisions: Date:
SYSTEM NO. C-AJ-1226
F RATING - 3 HR
T RATING - 0 HR
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - 4 CFM/SQFT
SYSTEM NO. C-AJ-3180
F RATING - 3 HR
T RATING - 0 HR
SYSTEM NO. C-AJ-7051
F RATING - 3 HR
T RATING - 1 HR
SINGLE METAL PIPES OR CONDUIT SINGLE OR BUNDLED CABLES
NON-INSULATED MECHANICAL DUCTWORK
WITHOUT DAMPERS
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US C
R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
A
A
SECTION A-A
4B
4B 1
4A
SECTION A-A
A
A
A
A SECTION A-A
3B
3A
1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM
OF OPENING IS 32 IN.
2. METALLIC SLEEVE - (OPTIONAL) NOM 32 IN. DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL SLEEVE CST OR GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH FLOOR OR WALL SURFACES OR EXTENDING
A MAX OF 3 IN. ABOVE FLOOR OR BEYONE BOTH SURFACES OF WALL.
3. SHEET METAL SLEEVE - (OPTIONAL) MAX 6 IN. DIAM, MIN 26 GA GALV STEEL PROVIDED WITH A 26 GA GALV STEEL SQURE FLANGE SPOT WELDED TO THE SLEEVE AT A APPROX MID-HEIGHT, OR FLUSH WITH BOTTOM OF SLEEVE IN FLOORS, AND SIZED TO BE A MIN OF 2 IN. LARGER THAN THE SLEEVE DIAM. THE SLEEVE IS TO BE CAST IN PLACE AND MAY EXTEND A MAX OF 4 IN. BELOW THE BOTTOM OF THE DECK AND A MAX OF 1 IN.
ABOVE THE TOP SURFACE OF THE CONCRETE FLOOR.
4. THROUGH-PENETRANT - ONE METALLIC PIPE, TUBE OR CONDUIT TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PENETRANT AND PERIPHERY OF OPENING SHALL BE MIN 0 IN. (POINT CONTACT) TO MAX 1-7/8 IN. SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PENETRANTS MAY BE USED:
A. STEEL PIPE - NOM 30 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE - NOM 30 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. COPPER PIPE - NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
D. COPPER TUBING - NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
E. CONDUIT - NOM 6 IN. DIAM (OR SMALLER) STEEL CONDUIT.
F. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING (EMT).
5. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. PACKING MATERIAL - MIN 4 IN. THICKNESS OF MIN 4 PCF MINERAL WOOL BATT INSULATION FIRMLY
PACKED INTO OPENING AS A PERMANENT FORM. PACKING METERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR SLEEVE OR FROM BOTH SURFACES OF WALL OR SLEEVE AS REQUIRED TO
ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.
B. FILL, VOID, OR CAVITY MATERIAL* - SEALANT - MIN 1/4 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR SLEEVE OR WITH BOTH SURFACES OF WALL OR SLEEVE. AT THE POINT OR CONTINUOUS CONTACT LOCATIONS BEWEEN PENETRANT AND CONCRETE OR SLEEVE, A MIN 1/4 IN. DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE CONCRETE OR SLEEVE/PIPE PENETRANT INTERFACE ON THE TOP SURFACE OF FLOOR AND ON BOTH SURFACES OF
WALL.
*BEARING THE UL CLASSIFICATION MARK
1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M³) CONCRETE FLOOR OR MIN 4-3/4 IN. (152 MM). SEE CONCRETE BLOCKS*.
MAX DIAM OF OPENING IS 6 IN. (152 MM). SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE
RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
2. STEEL SLEEVE - (OPTIONAL) - NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL PIPE
CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH FLOOR OR WALLL SURFACES.
3. CABLES - AGGREGATE CROSS-SECTIONAL AREA OF CABLES IN OPENING TO BE MAX 45% OF THE AGGREGATE CROSS-SECTIONAL AREA OF THE OPENING. CABLES TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. ANY COMBINATION OF THE FOLLOWING TYPES AND SIZES OF
METALLIC CONDUCTOR OR FIBER OPTIC CABLE MAY BE USED:
A. MAX 500 KCMIL SINGLE COPPER CONNECTOR POWER CABLE WITH THERMOPLASTIC INSULATION
AND POLYVINYL CHLORIDE ( PVC) JACKET.
B. MAX 300 KCMIL SINGLE COPPER CONDUCTOR TELECOMMUNICATION CABLES WITH POLYVINYL
CHLORIDE (PVC) INSULATION AND JACKET MATERIAL.
C. MAX 7/C COPPER CONDUTOR NO. 12 AWG MULTICONDUTOR POWER AND CONTROL CABLES
WITH POLYVNYL CHOLORIDE (PVC) OR CROSS-LINKED POLYETHYLENE (XLPE) INSULATION AND
PVC JACKET.
D. MULTIPLE FIBER OPTICAL COMMUNICATION CABLES JACKETED WITH PVC AND HAVING A MAX
OUTSIDE DIAM OF 1/2 IN. (13 MM).
E. MAX 3/C COPPER CONDUCTOR NO. 12 AWG WITH BARE ALUMINUM GROUND, POLYVINYL
CHOLRIDE (PVC) INSULATED STEEL, METAL-CLAD CABLE.
F. MAX 3/C WITH GROUND 2/0 AWG COPPER CONDUCTOR SER CABLE WITH CROSS-LINKED
POLYETHYLENE (XLPE) INSULATION AND POLYVINYL CHLORIDE (PVC) JACKET.
G. RG/U COAXIAL CABLE WITH POLYETHYLENE (PE) INSULATION AND POLYVINYL CHLORIDE (PVC)
JACKET HAVING A MAX OUTSIDE DIAMTER OF 1/2 IN. (13 MM).
H. FIRE RESISTIVE CABLES* - MAX 1-1/4 IN. (32 MM) DIAM SINGLE CONDUCTOR OR MULTI
CONDUCTOR TYPE MI CABLE. A MIN1/8 IN. (3 MM) SEPARATION SHALL BE MAINTAINED BETWEEN
MI CABLES AND ANY OTHER TYPES OF CABLE.
4. PACKING MATERIAL - MIN 4-1/4 IN. (108 MM) THICKNESS OF MIN 4 PCF (64 KG/M³) MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE
RECESSED FROM TOP SURFACE OF FLOOR TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL
METERIAL.
5. FILL, VOID, OR CAVITY MATERIAL* - SEALANT - MIN 1/4 IN. (6.4 MM) THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL.
*BEARING THE UL CLASSIFICATION MARK
1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M³) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UNDERWRITERS LABORATORIES INC. CLASSIFIED CONCRETE BLOCKS*. MAX AREA OF OPENING IS 1024 IN. SQ. WITH A MAX DIMENSION OF 32 IN. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR
NAMES OF MANUFACTURERS.
2. STEEL DUCT - NOM 30 BY 30 IN. (OR SMALLER) NO. 24 GAUGE (OR HEAVIER) GALV STEEL DUCT. ONE STEEL DUCT TO BE POSITIONED WITHIN THE FIRESTIP SYSTEM. THE ANNULAR SPACE SHALL BE MIN 1/4 IN. TO A MAX
1-3/4 IN. DUCT TO BE RIGIDLY SUPPORTED ON BOTH SIDES FO FLOOR OR WALL ASSEMBLY.
3. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:
A. PACKING MATERIALS - MIN 3-1/2 IN. THICKNESS OF MIN 4 PCF MINERAL WOOL BATT INSULATION FIRMLY
PACKED INTO OPENING AS A PERMANENT FORM BETWEEN TEH BARE STEEL DUCT AND THE PERIPHERY OF THE OPENING. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR BOTH SURFACES
OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL
B. FILL, VOID, OR CAVITY MATERIAL* - SEALANT - MIN 1 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN
ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL.
SYSTEM NO. W-J-8007
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
1. WALL ASSEMBLY — MIN 7-5/8 IN. (194 MM) THICK WALL ASSEMBLY CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX AREA OF OPENING IS 2496 IN. SQ. (161 M2) WITH MAX DIMENSION OF 52 IN. (1321 MM).
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF
MANUFACTURERS.
2. CABLE TRAY* — MAX 36 IN. (914 MM) WIDE BY 6 IN. (152 MM) DEEP OPEN-LADDER CABLE TRAY WITH CHANNEL- SHAPED SIDE RAILS FORMED OF 0.067 IN. (1.7MM) THICK ALUMINUM AND WITH 1-1/2 IN. (38 MM) WIDE BY 3/4 IN.
(19 MM) DEEP CHANNEL- SHAPED RUNGS SPACED 10 IN. (254 MM) OC. ONE CABLE TRAY TO BE INSTALLED IN THE OPENING. THE ANNULAR SPACE BETWEEN ADJACENT PENETRATING ITEMS SHALL BE MIN 2 IN. (51 MM) TO MAX 4-1/2 IN. (114 MM). THE MAX ANNULAR SPACE BETWEEN THE PERIPHERY OF THE OPENING SHALL BE MIN 1 IN. (25 MM) TO MAX 3 IN. (76 MM). CABLE TRAY TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.
3. CABLES — AGGREGATE CROSS-SECTIONAL AREA OF CABLES IN CABLE TRAY TO BE MAX 40 PERCENT OF THE CROSS-SECTIONAL AREA OF THE CABLE TRAY BASED ON A MAX 6 IN. (152 MM) CABLE LOADING DEPTH WITHIN THE CABLE TRAY. ANY COMBINATION OF THE FOLLOWING TYPES AND SIZES OF CABLES MAY BE USED:
A. A. 300 PAIR — NO. 24 AWG TELEPHONE CABLE WITH POLYVINYL CHLORIDE (PVC) INSULATION AND PVC
JACKET.
B. 1/C - 500 KCMIL WITH THERMOPLASTIC INSULATION AND NYLON JACKET.
C. 24 FIBER OPTIC CABLE WITH POLYVINYL CHLORIDE (PVC) OUTER AND SUBUNIT JACKET.
D. 7/C NO. 12 AWG CABLE WITH POLYVINYL CHLORIDE (PVC) INSULATION AND PVC JACKET.
4. THROUGH PENETRANTS — ONE OR MORE PIPES OR TUBES TO BE INSTALLED WITHIN THE OPENING. THE TOTAL NUMBER OF THROUGH-PENETRANTS IS DEPENDENT ON THE SIZE OF THE OPENING AND TYPES AND SIZES OF THE PENETRANTS. ANY COMBINATION OF THE PENETRANTS DESCRIBED BELOW MAY BE USED PROVIDED THAT THE FOLLOWING PARAMETERS RELATIVE TO THE ANNULAR SPACES AND THE SPACINGS BETWEEN THE PIPES ARE MAINTAINED. THE SPACE BETWEEN PIPES, CONDUITS OR TUBING SHALL BE MIN 1-1/2 IN.(38 MM) TO MAX 4-3/4 IN. (121 MM). THE SPACE BETWEEN THE PERIPHERY OF THE OPENING AND THE PIPES OR CONDUITS SHALL BE MIN 3 IN. (76 MM) TO MAX 4-1/4 IN. (108 MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING
MAY BE USED:
A. STEEL PIPE — NOM 12 IN. (305 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE — NOM 12 IN. (305 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. CONDUIT — NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRIC METALLIC TUBING OR 6 IN. (152 MM)
DIAM STEEL CONDUIT.
D. COPPER TUBING — NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
E. COPPER PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
5. PIPE COVERING* — NOM 1-1/2 IN. (38 MM) THICK HOLLOW CYLINDRICAL HEAVY DENSITY (3.5 PCFOR 56 KG/M3) GLASS FIBER UNITS JACKETED OF THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS OR FACTORY-APPLIED SELF-SEALING LAP TAPE. TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH BUTT TAPE SUPPLIED WITH THE PRODUCT. SEE PIPE EQUIPMENT COVERING — MATERIALS — (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS.
ANY PIPE COVERING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE
USED.
5A. METAL JACKET — (NOT SHOWN) — REQUIRED WHEN PIPE COVERING (ITEM 5) IS USED. MIN 6 IN. (152 MM) LONG JACKET FORMED OF MIN 0.010 IN. (0.25 MM) THICK STEEL SHEET CUT TO WRAP TIGHTLY AROUND THE PIPE INSULATION WITH A MIN 2 IN. (51 MM) LAP. JACKET SECURED WITH MIN 1/2 IN. (13 MM) WIDE STAINLESS STEEL HOSE CLAMP LOCATED AT THE CENTER OF THE JACKET. JACKET TO BE INSTALLED ON BOTH SURFACES OF
WALL AND RECESSED INTO THE OPENING 1 IN. (25 MM).
A
A
8C
8A
SECTION A-A
ANSI/UL 1479 (ASTM E814)
F RATING - 4 HR
T RATING - 0 HR
F RATING - 4 HR
FT RATING - 0 HR
FH RATING - 4 HR
FTH RATING - 0 HR
CAN/ULC S115
MIXED PENETRANTS
SYSTEM NO. W-J-3050
F RATING - 4 HR
T RATING - 1 HR
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
SINGLE OR BUNDELED CABLES
1. WALL ASSEMBLY- MIN 7-112 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150
PEL) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE
BLOCKS*. MAX DIAM OF OPENING IS 4 IN. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE
RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
2. STEEL SLEEVE- NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL PIPE SLEEVE FRICTION FIT IN NOM 4 IN. DIAM CIRCULAR OPENING CORE DRILLED THROUGH WALL. LENGTH OF
STEEL SLEEVE TO BE EQUAL TO THICKNESS OF WALL.
3. CABLES- AGGREGATE CROSS SECTIONAL AREA OF CABLES IN OPENING TO BE MAX 33 PERCENT
OF THE CROSS SECTIONAL AREA OF THE OPENING. CABLES INSTALLED EITHER
CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE
BETEWEEN CABLES AND THE STEEL SLEEVE SHALL BE MIN 1/4 IN. TO MAX 1 IN. CABLES TO BE
RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES
OF CABLES MAY BE USED:
A. 7/C (WITH GROUND) NO. 12 AWG CABLE, WITH PVC INSULATION AND OUTER JACKET.
B. MAX 25 PAIR NO. 24 AWG (OR SMALLER) COPPER CONDUCTOR TELEPHONE CABLE WITH
PVC INSULATION, WITH PVC JACKET.
C. MAX RG59/U (OR SMALLER) COAXIAL CABLE WITH FLUORINATED ETHYLENE INSULATION
AND JACKETING.
D. 3/C (WITH GROUND) NO. 10 AWG BARE COPPER GROUND METAL CLAD CABLE WITH A PVC
JACKET.
E. MULTIPLE 24 FIBER-<JPTICAL COMMUNICATION CABLES JACKETED WITH POLYVINYL
CHLORIDE AND HAVING A MAX OUTSIDE DIAM OF 1/2 IN.
4. FILL, VOID OR CAVITY MATERIAL*-5EALANT- MIN 2 IN. THICKNESS OF FILL MATERIAL APPLIED
WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF THE WALL.
*BEARING THE UL CLASSIFICATION MARK
A
A
SECTION A-A
1B
1A A
SECTION A-A
A
C R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US SYSTEM NO. W-L-3065
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F RATINGS - 1 AND 2 HR (SEE ITEM1)
FT RATING - 0 AND 3/4 HR (SEE ITEM 3)
FH RATING - 1 AND 2 HR ( SEE ITEM 1)
FTH RATING - 0 AND 3/4 HR (SEE ITEM 3)
L RATING AT AMBIENT - 15 CFM/SQ FT
L RATING AT 400 F - 8 CFM/SQ FT
F RATINGS - 1 AND 2 HR (SEE ITEM 1)
T RATING - 0 AND 3/4 HR (SEE ITEM 3)
L RATING AT AMBIENT - 15 CFM/SQ FT
L RATING AT 400 F - 8 CFM/SQ FT
1. WALL ASSEMBLY — THE 1 OR 2 FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300, U400 OR V400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE
RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS — WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2
BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC. STEEL STUDS TO BE MIN 2-1/2 IN. (64 MM) WIDE AND SPACED MAX 24 IN.
(610 MM) OC.
B. GYPSUM BOARD* — NOM 5/8 IN. (16 MM) THICK GYPSUM BOARD, WITH SQUARE OR TAPERED EDGES. THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300, U400 OR V400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 5-1/2 IN. (138 MM) WHEN SLEEVE (ITEM
2) IS EMPLOYED. MAX DIAM OF OPENING IS 4 IN. (102 MM) WHEN SLEEVE (ITEM 2) IS NOT EMPLOYED. THE F RATING OF THE
FIRESTOP SYSTEM IS EQUAL TO THE FIRE RATING OF THE WALL ASSEMBLY.
SINGLE OR BUNDLED CABLES
A 3
1A
1B
A
SECTION A-A
1. WALL ASSEMBLY — THE 1 OR 2 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE
DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:
A. STUDS — WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY
4 IN. LUMBER SPACED 16 IN. OC. STEEL STUDS TO BE MIN 2-1/2 IN. WIDE AND SPACED MAX 24 IN. OC. WHEN STEEL STUDS ARE USED AND THE DIAM OF OPENING EXCEEDS THE WIDTH OF STUD CAVITY, THE OPENING SHALL BE FRAMED ON ALL SIDES USING LENGTHS OF STEEL STUD INSTALLED BETWEEN THE VERTICAL STUDS AND SCREW-ATTACHED TO THE STEEL STUDS AT EACH END. THE FRAMED OPENING IN THE WALL SHALL BE 4 TO 6 IN. WIDER AND 4 TO 6 IN. HIGHER THAN THE DIAM OF THE PENETRATING ITEM SUCH THAT, WHEN THE PENETRATING ITEM IS INSTALLED IN THE OPENING, A 2 TO 3 IN. CLEARANCE IS PRESENT BETWEEN THE PENETRATING ITEM
AND THE FRAMING ON ALL FOUR SIDES.
B. GYPSUM BOARD* — 5/8 IN. THICK, 4 FT WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 32-1/4 IN. FOR STEEL STUD WALLS. MAX DIAM OF OPENING IS 14-1/2 IN.
FOR WOOD STUD WALLS. THE F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE FIRE RATING OF THE WALL ASSEMBLY.
ANSI/UL1479 (ASTM E814) CAN/ULC S115
F RATINGS - 1 AND 2 HR
(SEE ITEMS 1 ANS 3)
FT RATING - 0 HR
FH RATINGS - 1 AND 2 HR
(SEE ITEMS 1 AND 3)
FTH RATING - 0 HR
FTH RATING - 0HR
L ARATING AT ABIENT - LESS THAN
1 CFM/SQ FT
L RATING A 400 F - LESS THAN
1CFM/SQ FT
SYSTEM NO. W-L-1054
C
R
CLASSIFIED BY
UNDERWRITERS
LABORATORIES, INC.
TO UL 1479 AND CAN/ULC-
S115
US
F RATINGS - 1 AND 2 HR
(SEE ITEMS 1 AND 3)
T RATING - 0 HR
L RATING AT AMBIENT - LESS THAN
1 CFM/SQ FT
L RATING AT 400 F - LESS THAN
CFM/SQ FT
METAL PIPES OR CONDUIT
4. STEEL RETAINING ANGLE - NOM 2 IN. BY 2 IN. BY NO. 16 GUAGE (OR HEAVIER) STEEL ANGLES ATTACHED TO ALL FOUR SIDES OF THE STEEL DUCT ON THE TOP SURFACE OR BOTH SURFACES OF THE WALL. THE ANGLES SHALL BE ATTACHED WITH NO. 8 (OR LARGER) STEEL SHEET METAL SCREWS SPACED MAX OF 1 IN. FROM EACH END
AND A MAX OF 3 IN. O.C.
*BEARING THE UL CLASSIFICATION MARK
2. THROUGH-PENETRANTS — ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY
WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE SHALL BE MIN 0 IN. TO MAX 2-1/4 IN. PIPE MAY BE INSTALLED WITH CONTINUOUS POINT CONTACT. PIPE, CONDUIT OR TUBING MAY BE INSTALLED AT AN ANGLE NOT GREATER THAN 45 DEGREES FROM PERPENDICULAR.
PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF
METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:
A. STEEL PIPE — NOM 30 IN DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.
B. IRON PIPE — NOM 30 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. CONDUIT — NOM 4 IN DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR 6 IN. DIAM STEEL CONDUIT.
D. COPPER TUBING — NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.
E. COPPER PIPE — NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.
3. FILL, VOID OR CAVITY MATERIAL* — SEALANT — MIN 5/8 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. AT THE POINT OR CONTINUOUS CONTACT LOCATIONS BETWEEN PIPE AND WALL, A MIN 1/2 IN. DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE PIPE WALL INTERFACE ON BOTH SURFACES OF WALL .
*BEARING THE UL CLASSIFICATION MARK
4. FILL, VOID OR CAVITY MATERIAL*— SEALANT OR PUTTY — FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH EACH END OF THE STEEL SLEEVE OR WALL SURFACE. FILL MATERIAL INSTALLED SYMMETRICALLY ON BOTH SIDES OF THE WALL. A MIN 5/8 IN. (16 MM) THICKNESS OF SEALANT IS REQUIRED FOR THE 1 OR 2 HR F RATING . AN ADDITIONAL 1/2 IN. (13 MM) DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AROUND THE PERIMETER OF SLEEVE ON BOTH SIDES OF THE WALL WHEN SLEEVE EXTENDS BEYOND SURFACE OF
WALL.
*BEARING THE UL CLASSIFICATION MARK
+BEARING THE UL LISTING MARK
2. METALLIC SLEEVE — (OPTIONAL) - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING (EMT) OR SCHEDULE 5 (OR HEAVIER) STEEL PIPE OR MIN 0.016 IN. THICK (0.41 MM, NO.
This is the start of the file's text. The full file is on GovTribe.