18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-2.pdf

PDF 9 MB Posted

Attached to
36C25023B0049 - Y1NB--Construct Chiller Plant - Columbus, OH Chalmers P. Wylie VAACC SDVOSB Set-Aside - Solicitation
Solicitation number
36C25023B0049
Issued by

About this file

This document package includes construction drawings and specifications for a federal contract opportunity with the Department of Veterans Affairs. The project involves constructing a new chiller plant addition at the VA Medical Center located in Columbus, Ohio. The drawings show the proposed site layout, demolition plans, life safety plans, and penetration firestopping details. Key requirements include installing new chillers, pumps, and associated mechanical equipment. Subcontractors will be responsible for demolition work, fire protection systems, and electrical systems. The solicitation is set aside for Service-Disabled Veteran-Owned Small Businesses and has a response due date of June 15th, 2022. The award date is slated for August 1st, 2022.

View the file

Other files

File Type Posted
36C25024C0013 SAM Award Notice 1.0.pdf PDF
36C25023B0049 - Amendment 3.docx DOCX document
36C25023B0049 - Amendment 2.pdf PDF
36C25023B0049 - Amendment 1.docx DOCX document
Single Source Justification MPT to SAT - Wattstopper - Pricing Removed - Signed.pdf PDF
VHA Directive 1192.01, Seasonal Influenza Prevention Program for VHA Health Care Personnel.pdf PDF
18912 Columbus VAMC Chiller BC Sole Source Redacted.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-8.pdf PDF
VAAR 852.219-75 - To Be Submitted With Bid.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-5.pdf PDF
VAACC Health Requirements - Bid Ready 2023.pdf PDF
36C25023B0049 - Ready.docx DOCX document
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-4.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-1.pdf PDF
Single Source Justification MPT to SAT - Simplex - 2.0 Price Removed - Signed.pdf PDF
18912 Columbus VA Chiller Plant Revision Final B_C Re-Revised - PM Vol 1 of 2.pdf PDF
Franklin DB - Current as of 07.13.2023.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-9.pdf PDF
Single Source Justification MPT to SAT - Software House - Pricing Removed - Signed.pdf PDF
Single Source Justification MPT to SAT - Russ Electric Price Removed - Signed.pdf PDF
18912 Columbus DVAMC Chiller FB_C PM Volume 2 of 2.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-6.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-7.pdf PDF
Hca Signed NCO 10 Caterpillar - Sole Source - Pricing Removed.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-10.pdf PDF
18912 Columbus VA Chiller Plant Revision Final BC Revised - Drawings - Part-3.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FINISHED CONTOURS

EXISTING CONTOURS

CONTRACT LIMIT LINE

PROPERTY LINE

ELEVATION INDICATORS

FINISH ELEVATION

EXISTING ELEVATION

FENCE

STRUCTURAL GRID COLUMN TAG (NEW)

STRUCTURAL GRID COLUMN TAG (EXISTING)

CENTERLINE

REVISION INDICATOR

DRAWING BREAK LINE

MATCH LINE INDICATOR

HIDDEN LINE

1. ITEMS ABOVE OR BEYOND

2. ITEMS NOT IN CONTRACT (N.I.C.)

3. ITEMS BEING DEMOLISHED

ELEVATION DATUM

WINDOW & LOUVER SYMBOL

(SEE WINDOW SCHEDULE)

DOOR SYMBOL

(SEE DOOR SCHEDULE)

EQUIPMENT SYMBOL

(SEE EQUIPMENT SCHEDULE)

WALL TYPE SYMBOL

(SEE PARTITION TYPES)

PARTITION NUMBER

WORK POINT

ROOM NUMBER SYMBOL

ELEVATION VIEW INDICATOR

DETAIL INDICATOR

SECTION INDICATOR

DRAWING TITLE

SCALE:

1 View Name 1/8" = 1'-0"A101

DETAIL NO.

DRAWING NO.

1'-0"

1'-0"

INTERIOR 01

INTERIOR 02

ELEVATION NO.

DRAWING NO. A101

ELEVATION NO.

Name Elevation

Name Elevation

A

A

NEW

EXISTING

SECTION NO.

DRAWING NO.

X

B 1

A101

A101

Room name

X

/1 A101

/1 A101

X X

NEW PARTITION

PATCH TO MATCH EXISTING PARTITION

EXISTING PARTITION TO REMAIN

EXISTING DOOR TO REMAIN

EXISTING DOOR TO BE REMOVED

NEW DOOR AND FRAME

POCKET DOOR

CASED OPENING

BIFOLD DOOR

SLIDING DOOR

Room name

Room name

AIR CONDITIONED

ACOUSTICAL CEILING TILE

AIR CONDITIONING UNIT

ABOVE FINISHED FLOOR

ALTERNATE

AUDIO VISUAL

ARCHITECTURAL WOODWORK

AC

A.C.T.

A.C.U.

A.F.F.

ALT

A.V.

A.W.

BD

BLDG

BLK

BLKG

BOT

BR

BRG

BSMT

CONC

CAB

C.B.B.

C.C.T.

C.G.

C.J.

CLR

CLG

C.M.U.

COL

COMM

CONF

CONN

CONST

CONT

CONTR

COORD

CORR

C.R.

C.W.

CYL

DBL

DEMO

DEPT

DET

D.F.

DIA

DIAG

DIM

DISP

DN

DR

D.S.

D.W.

DWG(S)

EXIST

E

EA EACH

EAST

EXISTING

DRAWING(S)

DUMBWAITER

DOWNSPOUT

DOOR

DOWN

DISPENSER

DIMENSION

DIAGONAL

DIAMETER

DRINKING FOUNTAIN

DETAIL

DEPARTMENT

DEMOLITION

DOUBLE

CYLINDER

COLD WATER

CRASH RAIL

CORRIDOR

COORDINATE

CONTRACTOR

CONTINUOUS

CONSTRUCTION

CONNECTION

CONFERENCE

COMMUNICATION

COLUMN

CONCRETE MASONRY UNIT

CEILING

CLEAR

CONTROL JOINT

CORNER GUARD

CUBICAL CURTAIN TRACK

CEMENTITIOUS BACKER BOARD

CABINET

CONCRETE

BASEMENT

BEARING

BRICK

BOTTOM

BLOCKING

BLOCK

BUILDING

BOARD

POUND OR NUMBER #

DIAMETER OR ROUND

CENTERLINE

AT

ANGLE

AND

EXPANSION JOINT

ELECTRICAL

E.I.F.S.

E.J.

ELECT

EL

ELEV

EMER

ENCL

EQ

EQUIP

E.T.R.

EVAC

E.W.C.

EXT

F.B.

F.C.

F.C.U.

F.D.

F.D.V.C.

F.E.

F.E.C.

F.H.C.

FIN

FIXT

FLR

FLEX

FLUOR

F.R.T.

FT

FTG

FURN

FUT

G

GA

GALV

G.C.

G.F.M.U.

GL

GR

GRND

GYP

H.B.

HD

HDWD

H.M.

HOSP

H.P.

HR

H.R.

HORIZ

HT

HTG

HTR

H.V.A.C.

H.W.

HW

HYD

I.D.

ILLUM

INCIN

INCAND

INCL

INFO

INSUL

INT

I.P.S.

ISOL

IV

JT

KITCH

K.O.

K.P.

K.S. KNEE SPACE

KICK PLATE

KNOCK OUT

KITCHEN

JOINT

INTRAVENOUS

ISOLATION

INSIDE PIPE SIZE

INTERIOR

INSULATION

INFORMATION

INCLUDE

INCINERATOR

INCANDESCENT

ILLUMINATION

INSIDE DIAMETER (DIM)

HYDRANT

HARDWARE

HOT WATER

HEATING, VENTILATION, AIR CONDITIONING

HEATER

HEATING

HEIGHT

HORIZONTAL

HANDRAIL

HOUR

HIGH POINT

HOSPITAL

HOLLOW METAL

HEAD

HOSE BIBB

GYPSUM

GROUND

GRADE

GLASS

GROUND FACE MASONRY UNITS

GENERAL CONTRACTOR

GALVANIZED

GAGE

GAS

FUTURE

FURNITURE

FOOTING

FOOT OR FEET

FIRE RESISTANT TREATED

FLUORESCENT

FLEXIBLE

FLOOR

FIXTURE

FINISH

FIRE HOSE CABINET

FIRE EXTINGUISHER CABINET

FIRE EXTINGUISHER

FIRE DEPARTMENT VALVE CABINET

FLOOR DRAIN

FAN COIL UNIT

FOOT CONTROL

FACE BRICK

EXTERIOR

ELECTRIC WATER COOLER

EVACUATION

EXISTING TO REMAIN

EQUIPMENT

EQUAL

ENCLOSURE

EMERGENCY

ELEVATOR

ELEVATION

L

LAB

LAM

LIB

LIN

LOC

L.P.

LT.WT.

LTG

MACH

MAS

MATL

MAX

MECH

MED

MED.CAB.

MEMB

MEZZ

MFR

MH

MIN

MISC

MKR.BD.

MLDG

M.O.

MOD

M.R.G.B.

MTD

MTL

N

N.C.

NEG

N.I.C.

NO

N.T.S.

O

O.C.

O.D.

OFF

OPNG

OPP

O.F.C.I.

PART.BD.

P.C.

P.C.D.

PERIM

PERP

PLWD

PORT

PR

PREFAB

PREFIN

PROJ

PROP

P.T.

PTD

R

R.A.

REC

RECEP

RECT

REF REFRIGERATOR

RECTANGULAR

RECEPTACLE

RECESSED

RETURN AIR

RADIUS

PAINTED

PNEUMATIC TUBE

PROPERTY

PROJECT

PREFINISHED

PREFABRICATED

PAIR

PORTABLE

PLYWOOD

PERPENDICULAR

PERIMETER

PAPER CUP DISPENSER

PRECAST CONCRETE

PARTICLEBOARD

OWNER FURNISHED, CONTRACTOR INSTALLED

OPPOSITE

OPENING

OFFICE

OUTSIDE DIAMETER(DIM)

ON CENTER

OXYGEN

NOT TO SCALE

NOMINAL

NUMBER

NOT IN CONTRACT

NEGATIVE

NURSE CALL

NITROGEN/NORTH

METAL

MOUNTED

MOISTURE RESISTANT GYPSUM BOARD

MODIFIED, MODULAR

MASONRY OPENING

MOULDING

MARKERBOARD

MISCELLANEOUS

MINIMUM

MANHOLE

MANUFACTURER

MEZZANINE

MEMBRANE

MEDICINE CABINET

MEDICINE/MEDICAL

MECHANICAL

MAXIMUM

MATERIAL

MASONRY

MACHINE

LIGHTING

LIGHTWEIGHT

LOW POINT

LOCATION/LOCATE

LINEAR

LIBRARY

LAMINATE

LABORATORY

LOCK

REFL REFLECTED

REINF REINFORCED

REM REMOVABLE

REQ'D REQUIRED

REV REVISION

R.F. RADIO FREQUENCY

RM

RND

R.O.

R.S.T. RUBBER STAIR TREADS

ROUGH OPENING

ROUND

S

S.S.

S.A.

SAN

SCHED

S.C.R.

S.D.

SECT

SGL

SH

SHR

SHT

SIM

S.O.G.

SPEC (S)

S&R

S.P.T.

SQ

S.F.

S.I.

S.Y.

S.T.C.

STD

STL

STOR

STRUCT

SURF

SUSP

T

T&B

T&G

TAN

TEL

TEMP

THRESH

THRU

TK.BD.

TLT

T.O.P.

TV

TYP

U.C.

UNFIN

U.O.N.

UTIL

V, VAC

VENT

VERT

VEST

VIT

W

W/

W/O

W.C.

W/C

WD

W.P.

YD YARD

WORKPOINT

WOOD

WHEEL CHAIR

WATER CLOSET

WITHOUT

WITH

WEST/WATER

VITREOUS

VESTIBULE

VERTICAL

VENTILATION

VACUUM

UTILITY

UNLESS OTHERWISE NOTED

UNFINISHED

UNDER COUNTER

TYPICAL

TELEVISION

TOP OF PAVEMENT

TOILET

TACKBOARD

THROUGH

THRESHOLD

TEMPERATURE

TELEPHONE

TANGENT

TONGUE AND GROOVE

TOP AND BOTTOM

THERMOSTAT

SUSPENDED

SURFACE

STRUCTURAL

STORAGE

STEEL

STANDARD

SOUND TRANSMISSION CLASS / COEFFICIENT

SQUARE YARD

SQUARE INCH

SQUARE FOOT

SQUARE

SPECIMEN PASS-THRU

SHELF & ROD

SPECIFICATION(S)

SLAB ON GRADE

SIMILAR

SHEET

SHOWER

SHELVING, SHELF

SINGLE

SECTION

SUPPLY DIFFUSER

SHOWER CURTAIN ROD

SCHEDULE

SANITARY

SUPPLY AIR

STAINLESS STEEL

SOUTH

LT LIGHT

LAV LAVATORY

W.W.F. WELDED WIRE FABRIC

EXTERIOR INSULATION FINISH SYSTEM

HARDWOOD

NOM

ROOM

V.I.F. VERIFY IN FIELD

ALUMINUMAL

F.P. FIRE PROTECTION

F.P.G. FIRE PROTECTED GLAZING

CL

O.F.O.I. OWNER FURNISHED, OWNER INSTALLED

SSM SOLID SURFACE MATERIAL

NOTE: ALL ITEMS/MATERIALS MAY NOT OCCUR IN THIS PROJECT. LIST PROVIDED FOR REFERENCE ONLY.

UNDISTURBED EARTH OR UNDISTURBED SUBGRADE

COMPACTED EARTH OR COMPACTED SUBGRADE

ROCK

POROUS FILL OR SUBBASE

IMPERVIOUS FILL

DRAINAGE FILL

CAST-IN-PLACE CONCRETE

PRECAST CONCRETE

TOPSOIL

CEMENTITIOUS DECKS AND TOPPINGS

GROUT

BRICK

GLAZED BRICK

STRUCTURAL CLAY TILE UNIT MASONRY

GLAZED STRUCTURAL CLAY TILE UNIT MASONRY

CONCRETE UNIT MASONRY

GLAZED CONCRETE UNIT MASONRY

GLAZED UNIT MASONRY

CUT STONE

FIREBRICK

CAST STONE

STEEL

ALUMINUM

ORNAMENTAL METAL/STAINLESS STEEL

CONTINUOUS WOOD FRAMING

WOOD BLOCKING

PLYWOOD

PARTICLE BOARD

FINISHED LUMBER FOR ARCHITECTURAL WORK

BATT INSULATION

RIGID INSULATION

LOOSE FILL INSULATION

EXTERIOR INSULATION AND FINISH SYSTEM

FIBROUS FIRE SAFING

GLASS

CARPET

LATH AND PLASTER

GYPSUM BOARD

PLASTIC GLAZING

TERRAZZO

ACOUSTICAL CEILING

RESILIENT TILE

CERAMIC TILE

GRAPHIC SYMBOLS

FLOOR PLAN LEGEND

STANDARD ABBREVIATIONS

MATERIALS LEGEND

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

C U s e rs

\j c h o \D o c u m e n ts

\R e v it M o d e ls

\1

R

V A

C o lu m b u s C h ill e r

P la n t R e v is io n

C e n tr a l_ jd c h o

.r v t

/5

/2

:0

:4

A

M

G-101

NOTES AND SYMBOLS CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 RG jdc

BID & CONSTRUCTION

(REVISED)18912

Revisions: Date:

FINAL BID & CONSTRUCTION 11/24/2021

FINAL BID & CONSTRUCTION (REVISED) 05/06/2022

UP

DN

UP

EC-114

CHILLER PLANT

CORRIDOR

EXISTING

AREA N.I.C.

F.E.C.

T R

A V

E L D

IS

T

A N

C E

'-6

TRAVEL D

IS

TANCE -

79'-0

EXISTING

MANAGER'S

OFFICEEXISTING

BREAK ROOM

EXISTING

JANITORS

CLOSET

EXISTING

TELE/DATA

ROOM

EXISTING

TOILET /

SHOWER

EXISTING

ELECTRICAL ROOM

EXISTING

STORAGE

EXISTING

ELECTRICAL ROOM

EXISTING

STAIR 'A'

5,180 S.F. / 100 = 52 OCCUPANTS

EXISTING

STORAGE

EXISTING BOILER PLANT TRAVEL DISTANCE,

EGRESS WIDTH AND OCCUPANT LOAD NOT

AFFECTED WITH NEW CHILLER PLANT ADDITION.

26 OCC.

26 OCC.

EC-115

EXISTING CONTROL

ROOM

EC-116

EXISTING BOILER

ROOM

EXISTING

EGRESS

71 OCC

EXISTING

EGRESS

35 OCC.

EXISTING

EGRESS

15 OCC.

EXIST. F.E.C.

EXIST. F.E.C.

EXIST. F.E.C.

F.E.

EXISTING 1HR RATED PARTITION (TYP.)

EXISTING 1HR RATED

PARTITION (TYP.)

F.E.

F.E.

F.E.

F.E.

F.E.

F.E.C. FIRE EXTINGUISHER CABINET

TRAVEL DISTANCE

EXIT SIGN

EGRESS DIRECTION

F.E. FIRE EXTINGUISHER

1 HOUR RATED PARTITION

1. SEE COVER SHEET FOR CODE REVIEW

EXISTING

EGRESS

28 OCC

OPEN TO

BOILER PLANT

BELOW

OPEN TO

CHILLER PLANT

BELOW

EXISTING 1HR RATED

PARTITION (TYP.)

EXISTING 1HR RATED PARTITION (TYP.)

EXISTING 1HR RATED

PARTITION (TYP.)

EXIST.

FEC

EXIST.

FEC

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

C U s e rs

\j c h o \D o c u m e n ts

\R e v it M o d e ls

\1

R

V A

C o lu m b u s C h ill e r

P la n t R e v is io n

C e n tr a l_ jd c h o

.r v t

/5

/2

:0

:5

A

M

G-102

LIFE SAFETY PLAN CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 RG jdc

BID & CONSTRUCTION

(REVISED)18912

SCALE: 1/8" = 1'-0"G-102

1 LIFE SAFETY PLAN - FIRST FLOOR

FIRE PROTECTION LEGEND

LIFE SAFETY GENERAL NOTES

SCALE: 1/8" = 1'-0"G-102

2 LIFE SAFETY PLAN - SECOND FLOOR

Revisions: Date:

++ L RATING APPLIES ONLY TO CP 680-P DEVICES AND ONLY WHEN THE NOM DIAM OF PIPE EQUALS SIZE OF DEVICE (2 IN. DIAM PIPE IN 2"

DEVICE ETC.) L RATING DOES NOT APPLY TO CP 680N DEVICES.

4. FIRESTOP DEVICE* — (NOT SHOWN) -TOP SEAL PLUG FOR USE WITH CP 680-75/2.5"N DEVICES AND NOM PIPE OR CONDUIT SIZES 3/4 IN. (19 MM) TO 2 IN. (51 MM), INSTALLED IN ACCORDANCE WITH THE MANUFACTURER\'S INSTRUCTIONS. THE TOP SEAL PLUG IS OPTIONAL FOR NOM 1-1/2 IN. (38 MM) PIPES AND CONDUITS. TOP SEAL PLUGS ARE REQUIRED FOR ALL PIPES AND CONDUITS LESS THAN NOM 1-1/2 IN. (38

MM). W RATING APPLIES ONLY WHEN THE CPS OR IPS TOP SEAL PLUGS ARE USED.

4A. FIRESTOP DEVICE* - WATER BARRIER MODULE — (OPTIONAL, NOT SHOWN) - APPLIES TO NOM 2", 3" AND 4" WATER BARRIER MODULES USED IN COMBINATION WITH THE CP 680-P 2", CP 680-P 3" AND CP 680-P 4" DEVICES, RESPECTIVELY, AND SUPPLIED BY DEVICE MANUFACTURER. MODULE IS THREADED ONTO TOP OF DEVICE. W RATING APPLIES ONLY WHEN WATER BARRIER MODULE IS USED.

*BEARING THE UL CLASSIFICATION MARK

+BEARING THE UL LISTING MARK

1. FLOOR ASSEMBLY — MIN 2-1/2 IN. (64 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3)

CONCRETE.

1A. FLOOR ASSEMBLY - (OPTIONAL - NOT SHOWN) — THE FIRE RATED UNPROTECTED CONCRETE AND STEEL FLOOR ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL D900 SERIES DESIGNS IN THE UL FIRE

RESISTANCE DIRECTORY AND AS SUMMARIZED BELOW:

A. CONCRETE — MIN 2-1/2 IN (64 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3

CONCRETE.

B. STEEL FLOOR AND FORM UNITS* — COMPOSITE OR NON-COMPOSITE MAX 3 IN. (76 MM) DEEP GALV STEEL FLUTED UNITS AS

SPECIFIED IN THE INDIVIDUAL FLOOR-CEILING DESIGN

NOM PIPE DIAMETER FIRESTOP DEVICE

CP 680-75/2.5"N

CP 680 -P 2"

CP 680-P 3"

CP 680-1 10/4"N

CP 680-P 4"

CP 680-160/6"N

CP 680-P 6"

1/2 IN. TO 2 IN. (19 MM TO 51 MM)

3 IN.(76 MM)

3 IN. TO 4 IN. (76 MM TO 102 MM)

6 IN. (152 MM)

2 3

A

A

SECTION A-A

C R

CLASSIFIED BY

UNDERWRITERS

LABORATORIES, INC.

TO UL 1479 AND CAN/ULC-

S115

US SYSTEM NO. F-A-2053

F RATING - 2 HR

T RATING - 0 HR

L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)

L RATING AT 400 F - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)

W RATINGS - CLASS 1 (SEE ITEMS 3, 4, AND 4A)

C R

CLASSIFIED BY

UNDERWRITERS

LABORATORIES, INC.

TO UL 1479 AND CAN/ULC-

S115

US SYSTEM NO. F-A-2054

F RATING - 3 HR

T RATING - 0 AND 3 HR (SEE ITEM 3)

L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)

L RATING AT 400 F - LESS THAN 1 CFM/SQ FT (SEE ITEM 3)

W RATINGS - CLASS 1 (SEE ITEMS 3, 4, AND 4A)

1. FLOOR ASSEMBLY — MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3)

CONCRETE.

1A. FLOOR ASSEMBLY - (OPTIONAL - NOT SHOWN) — THE FIRE RATED UNPROTECTED CONCRETE AND STEEL FLOOR ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL D900 SERIES DESIGNS IN THE UL FIRE RESISTANCE

DIRECTORY AND AS SUMMARIZED BELOW:

A. CONCRETE — MIN 4-1/2 IN (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M3)

CONCRETE.

B. STEEL FLOOR AND FORM UNITS* — COMPOSITE OR NON-COMPOSITE MAX 3 IN. (76 MM) DEEP GALV STEEL FLUTED UNITS AS SPECIFIED

IN THE INDIVIDUAL FLOOR-CEILING DESIGN.

2. FIRESTOP DEVICE* — CAST IN PLACE FIRESTOP DEVICE PERMANENTLY EMBEDDED DURING CONCRETE PLACEMENT OR GROUTED IN CONCRETE ASSEMBLY IN ACCORDANCE WITH ACCOMPANYING INSTALLATION INSTRUCTIONS. THE DEVICES MAY EXTEND A MAX 2 IN. (51 MM)

ABOVE THE TOP SURFACE OF THE CONCRETE.

3. THROUGH PENETRANTS — ONE NONMETALLIC PIPE OR CONDUIT TO BE INSTALLED WITHIN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. FOR W RATING WITH WATER BARRIER MODULE, PIPE SHALL BE INSTALLED FROM BOTTOM OF DEVICE. THE FOLLOWING TYPES AND SIZES OF NONMETALLIC PIPES OR CONDUITS MAY BE USED:

A. POLYVINYL CHLORIDE (PVC) PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 SOLID OR CELLULAR CORE PVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS.

B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE — PIPE-NOM 6 IN. (152 MM) DIAM (OR SMALLER) SDR11 OR SDR13.5 CPVC PIPE FOR

USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS.

C. RIGID NONMETALLIC CONDUIT+ — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 PVC CONDUIT INSTALLED IN ACCORDANCE

WITH THE NATIONAL ELECTRICAL CODE (NFPA NO. 70).

THE FIRESTOP DEVICES AND NONMETALLIC PENETRANTS SHALL BE SIZED AS FOLLOWS:

+3 HR T RATING APPLIES WHEN CP 680-P 3" AND CP 680-P 4" DEVICES ARE USED. 3 HR T RATING ALSO APPLIED WHEN CP 680-110/4"N DEVICE IS USED PROVIDED THAT MIN 4 IN. (102 MM) THICKNESS OF NOM 4 PCF (64 KG.M3) MINERAL WOOL BATT INSULATION TIGHTLY PACKED WITHIN ANNULUS BETWEEN PIPE AND WALL OF CP 680-110/4"N DEVICE. ++ L RATING APPLIES ONLY TO CP 680-P DEVICES AND ONLY WHEN THE NOM DIAM OF PIPE EQUALS SIZE OF DEVICE (2 IN. DIAM PIPE IN 2" DEVICE ETC.) L RATING DOES NOT APPLY TO CP 680N DEVICES.

4. FIRESTOP DEVICE — TOP SEAL PLUG FOR USE WITH CP 680-P 2" DEVICE INSTALLED IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. THE TOP SEAL PLUG IS OPTIONAL FOR NOM 1-1/2 IN. (38 MM) PIPES AND CONDUITS. TOP SEAL PLUGS ARE REQUIRED FOR

ALL PIPES AND CONDUITS LESS THAN NOM 1-1/2 IN. (38 MM). W RATING APPLIES ONLY TO THE IPS TOP SEAL PLUG AND NOM 2 IN. DIAM PENETRANTS AND CPS TOP SEAL PLUG FOR NOM ½ TO 2 IN. (13 TO 51 MM) DIAM PENETRANTS.

4A. FIRESTOP DEVICE* - WATER BARRIER MODULE — (OPTIONAL, NOT SHOWN) - ALTERNATE TO TOP SEAL PLUG (ITEM 4). APPLIES TO NOM 2", 3", 4" AND 6" WATER BARRIER MODULES USED IN COMBINATION WITH THE CP 680-P 2", CP 680-P 3", CP 680-P 4" AND CP 680-P 6" DEVICES, RESPECTIVELY, AND SUPPLIED BY DEVICE MANUFACTURER. MODULE IS THREADED ONTO TOP OF DEVICE. W RATING APPLIES ONLY WHEN

WATER BARRIER MODULE IS USED AND NOM DIAM OF PENETRANT EQUALS SIZE OF DEVICE.

*BEARING THE UL CLASSIFICATION MARK

+BEARING THE UL LISTING MARK

NOM PIPE DIAMETER FIRESTOP DEVICE T RATING - HR

1/2 IN. TO 2 IN.

(19 MM TO 51 MM)

3 IN. (76 MM)

4 IN. (102 MM)

6 IN. (152 MM)

CP 680-75/2.5"N

CP 680-P 2"

CP 680-110-P 4"

CP 680-110/4"N

CP 680-P 3", CP 680-P 4"

CP 680-P 4"

CP 680-160/6"N

CP 680-P 6"

0 AND 3+

SINGLE NON-METALLIC PIPE OR CONDUIT

A A

SECTION A-A

C R

CLASSIFIED BY

UNDERWRITERS

LABORATORIES, INC.

TO UL 1479 AND CAN/ULC-

S115

US C

R

CLASSIFIED BY

UNDERWRITERS

LABORATORIES, INC.

TO UL 1479 AND CAN/ULC-

S115

US

C R

CLASSIFIED BY

UNDERWRITERS

LABORATORIES, INC.

TO UL 1479 AND CAN/ULC-

S115

US

C R

CLASSIFIED BY

UNDERWRITERS

LABORATORIES, INC.

TO UL 1479 AND CAN/ULC-

S115

US

CIRCULAR BLANK OPENINGS SINGLE NON-METALLIC PIPE OR CONDUITSINGLE INSULATED PIPES

SINGLE INSULATED PIPES

SYSTEM NO. C-BJ-2016

F RATING - 4 HR

T RATING - 2 HR

SYSTEM NO. C-BJ-5006

F RATING - 4 HR

T RATING - 1/2 HR

SYSTEM NO. C-BJ-1034

F RATING - 4 HR

T RATING - 0 HR

1. FLOOR OR WALL ASSEMBLY — MIN 5-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE FLOOR OR MIN 6 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 10-1/2 IN.SEE CONCRETE

BLOCKS (CAZT) CATEGORY IN FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.

2. THROUGH-PENETRANTS — ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. AN ANNULAR SPACE BETWEEN PIPE, CONDUIT OR TUBING AND PERIPHERY OF OPENING SHALL BE MIN 3/4 IN. TO MAX 3 IN. PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR

TUBING MAY BE USED:

A. STEEL PIPE — NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. CONDUIT — NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR STEEL CONDUIT.

3. PACKING MATERIAL — MIN 4 IN. THICKNESS OF MIN 4.0 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.

4. FILL, VOID OR CAVITY MATERIAL* — CAULK — MIN 1 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL. A MIN 1/2 IN. DIAM BEAD FILL MATERIAL TO BE INSTALLED AT INTERFACE OF PIPE, CONDUIT OR TUBING AND METAL COVER PLATE (ITEM NO. 5) AND OVER BUTTED

SEAMS OF METAL COVER PLATE.

5. METAL COVER PLATE — TWO PIECE COVER PLATE OF MIN 18 GAUGE STEEL WITH I.D. SAME AS O.D. OF PIPE, CONDUIT OR TUBING. O.D. OF COVER PLATE TO BE SIZED TO OVERLAP THE PERIPHERY OF OPENING A MIN 1-1/2 IN. INSTALLED AT TOP SURFACE OF FLOOR OR BOTH SIDES OF WALL. TWO PIECES TO BE BUTTED TOGETHER AROUND PERIMETER OF PIPE OR CONDUIT AND SECURED WITH 1/4 IN. DIAM BY MIN 1 IN. LONG STEEL EXPANSION BOLTS, OR EQUIVALENT, IN CONJUNCTION WITH STEEL NUTS AND WASHERS A MAX OF 1 IN. FROM EACH SIDE OF EACH SEAM AND A MAX OF 4 IN. OC

THROUGHOUT.

*BEARING THE UL CLASSIFICATION MARK

A

A SECTION A-A

SYSTEM NO. C-AJ-0055

ANSI/UL1479 (ASTM E814) CAN/ULC S115

F RATING - 3 HR

FT RATING - 0 HR

FH RATINGS - 3 HR

FTH RATING - 0HR

F RATING - 3 HR

T RATING - 0 HR

1. FLOOR OR WALL ASSEMBLY- MIN 4-112 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PEL) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS'. MAX

DIAM OF OPENING IS 4 IN. (102 MM).

2. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF

MANUFACTURERS.

3. METALLIC SLEEVE- NOM 4 IN. (102 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL PIPE CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH FLOOR OR WALL SURFACES. SLEEVE MAY EXTEND MAX

3 IN. (76 MM) ABOVE TOP SURFACE OF FLOOR.

4. FILL, VOID OR CAVITY MATENAL'- FIRE BLOCK MIN 2 IN. (51 MM) THICK CUT TO A DIAM 1/2 IN. (13 MM) LARGER THAN

THE OPENING, FLUSH WITH BOTTOM SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL.

*BEARING THE UL CLASSIFICATION MARK

A

A

SECTION A-A

1. FLOOR OR WALL ASSEMBLY -- MIN 6 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE.

WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAMETER OF OPENING IS 3 IN.

SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS

2. STEEL SLEEVE -- NOM 3 IN. DIAM SCHEDULE 40 (OR SMALLER) STEEL PIPE CAST OR GROUTED INTO FLOOR OR WALL

ASSEMBLY, FLUSH WITH FLOOR OR WALL SURFACES.

3. POLYVINYLIDENE FLUORIDE PVDF PIPE -- NOM 2 IN. DIAM (OR SMALLER) SCHEDULE 40 PVDF FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS. ANNULAR SPACE BETWEEN PIPE AND SLEEVE TO BE MIN 0 IN. (POINT CONTACT) AND MAX 5/8 IN. PIPE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR

OR WALL ASSEMBLY.

4. FIRESTOP SYSTEM -- THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:

A. FILL, VOID OR CAVITY MATERIALS*-SEALANT -- MIN 1/2 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTTOM SURFACE OF FLOOR OR BOTH SURFACES OF WALL.

B. B. FILL, VOID OR CAVITY MATERIAL* -- WRAP STRIP -- NOM 1/4 IN. THICK BY 2 IN. WIDE INTUMESCENT WRAP STRIP. TWO

LAYERS OF WRAP STRIP ARE CONTINUOUSLY WRAPPED AROUND THE PIPE AND HELD IN PLACE WITH TAPE. WRAP

STRIP BUTTED TIGHTLY AGAINST BOTTOM SURFACE OF FLOOR OR BOTH SURFACES OF WALL.

C. STEEL COLLAR -- COLLAR FABRICATED FROM COILS OF PRECUT MIN 0.017 IN. THICK (NO. 28 MSG) GALV STEEL AVAILABLE FROM THE SEALANT MANUFACTURER. COLLAR SHALL BE NOM 1-3/4 IN. DEEP WITH 1 IN. WIDE BY 2 IN. LONG ANCHORS TABS ON 2 IN. CENTERS FOR SECUREMENT TO FLOOR OR WALL ASSEMBLY. THE ANCHOR TABS SHALL BE BENT 90 DEGREE OUTWARD FOR SECUREMENT TO THE FLOOR OR WALL ASSEMBLY. THE OPPOSITE SIDE INCORPORATES RETAINER TABS, 1/2 IN. WIDE BY 3/16 IN. LONG, PREBENT TOWARD THE PIPE SURFACE. COLLAR SHALL BE TIGHTLY WRAPPED OVER THE WRAP STRIP, OVERLAPPING MIN. 1 IN AT SEAM. A NOM 1/2 IN. WIDE STAINLESS STEEL HOSE CLAMP SHALL BE SECURED TO THE COLLAR AT ITS MID-HEIGHT. EVERY OTHER ANCHOR TAB OF COLLAR SECURED TO CONCRETE SLAB WITH 1/4 IN. DIAM BY 1-3/4 IN. LONG STEEL EXPANSION TYPE MASONRY FASTENERS, 1-1/2 IN LONG CONCRETE SCREW ANCHORS OR 0.145 IN. DIAM BY 1-1/4 IN. LONG POWDER ACTUATED FASTENERS UTILIZING A 1-7/16 DIAM BY 1/16 IN. THICK STEEL WASHER. IN FLOOR ASSEMBLIES, ONE COLLAR TO BE USED AT THE BOTTOM OF THE CONCRETE FLOOR ONLY. IN WALL ASSEMBLIES, A COLLAR IS USED ON BOTH SURFACES.

*BEARING THE UL CLASSIFICATION MARK

4A

4B

4C

1 2

1. 1. FLOOR OR WALL ASSEMBLY — MIN 5-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE FLOOR OR MIN 6 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT CONCRETE WALL. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF OPENING IS 29 IN.

SEE CONCRETE BLOCKS (CAZT) CATEGORY IN FIRE RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.

2. THROUGH-PENETRANTS — ONE METALLIC PIPE TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN

THE FIRESTOP SYSTEM. PIPE TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING

TYPES AND SIZES OF METALLIC PIPES MAY BE USED:

A. STEEL PIPE — NOM 20 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

3. PIPE COVERING — MAX 3 IN. THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 3.5 PCF) GLASS FIBER UNITS JACKETED ON THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS OR FACTORY- APPLIED SELF-SEALING LAP TAPE.TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH BUTT TAPE SUPPLIED WITH THE PRODUCT. PIPE COVERING TO TERMINATE MIN 6 IN. FROM EACH SIDE OF FLOOR OR WALL ASSEMBLY. SEE PIPE AND EQUIPMENT COVERING — MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS

MAY BE USED.

4. FIRESTOP SYSTEM — THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:

A. PIPE COVERING* — MAX 3 IN. THICK HOLLOW CYLINDRICAL HEAVY DENSITY (MIN 5.2 PCF) UNFACED MINERAL WOOL

UNITS EXTENDING MIN 6 IN. BEYOND EACH SURFACE OF THE FLOOR OR WALL. PIPE COVERING SECURED WITH NO. 18 GAUGE TIE WIRE 3 IN. BEYOND EACH SURFACE OF THE CONCRETE SLAB. THE ANNULAR SPACE SHALL BE MIN 1 IN. TO MAX 2-1/4 IN. SEE PIPE AND EQUIPMENT COVERING — MATERIALS (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY PIPE COVERING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE

DEVELOPED INDEX OF 50 OR LESS MAY BE USED.

B. SHEATHING MATERIAL* — ALL SERVICE JACKET MATERIAL SHALL BE WRAPPED AROUND THE OUTER CIRCUMFERENCE OF THE PIPE COVERING MATERIAL (ITEM 4A) WITH KRAFT FACING EXPOSED. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS. SEE SHEATHING MATERIAL (BVDV) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS. ANY SHEATHING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR

LESS MAY BE USED.

C. PACKING MATERIAL — MIN 4 IN. THICKNESS OF MIN 4.0 PCF MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR FROM BOTH SURFACES OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.

D. FILL, VOID OR CAVITY MATERIAL* — CAULK — MIN 1 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL. A MIN 1/2 IN. DIAM BEAD FILL MATERIAL TO BE INSTALLED AT INTERFACE OF PIPE COVERING AND METAL COVER PLATE (ITEM NO. 4E) AND OVER BUTTED SEAMS

OF METAL COVER PLATE.

E. METAL COVER PLATE — TWO PIECE COVER PLATE OF MIN 18 GAUGE STEEL WITH I.D. SAME AS O.D. OF PIPE, CONDUIT OR TUBING. O.D. OF COVER PLATE TO BE SIZED TO OVERLAP THE PERIPHERY OF OPENING A MIN 1-1/2 IN. INSTALLED AT TOP SURFACE OF FLOOR OR BOTH SIDES OF WALL. TWO PIECES TO BE BUTTED TOGETHER AROUND PERIMETER OF PIPE, PENETRATING THE SHEATHING MATERIAL AND PIPE COVERING (ITEM NOS. 4B AND 4A) TO FULLY CONTACT THE PIPE. SECURED WITH 1/4 IN. DIAM BY MIN 1 IN. LONG STEEL EXPANSION BOLTS, OR EQUIVALENT, IN CONJUNCTION WITH STEEL NUTS AND WASHERS A MAX OF 1 IN. FROM EACH SIDE OF EACH SEAM AND A MAX OF 4 IN. OC THROUGHOUT.

*BEARING THE UL CLASSIFICATION MARK

A

A

SECTION A-A

4E 4D

4C

4D

4A

4B

SINGLE NON-METALLIC PIPE OR CONDUIT SINGLE INSULATED PIPES

NOM PIPE DIAM, IN.

(MM)

NOM THICK. OF PIPE

INSUL., IN. (MM)

FIRESTOP DEVICE T-

RATING,

HR

1/2 (13)

1 (25)

2 (51)

2 (51)

4 (102)

1 (25)

1 (25) (SEE ITEM 5)

1 (25)

3/4 (19)

1 (25)

1 (25)

1 (25)

3/4(19)

3/4(19)

CP 680-75/2.5"N, CP 682-72/2.5"CP

680-M 2", CP 680-P 2"

CP 680-75/2.5"N CP 680-P 3"

CP 680-M 3", CP 680-P 3"

CP 682-110/4"CP 680-M 4"

CP 680 110/4"N, CP682 110/4"CP

680-M 4", CP 680-P 4"

CP 680-100/4"NCP 680-P 4"

CP 680-160/6"NCP 680-P 6

3/4

1/2

1/2

1/2

1/2

1/2

1/2

4. TUBE INSULATION - PLASTICS+ - NOM 3/4 OR 1 IN. (19 OR 25 MM) THICK ACRYONITRILE BUTADIENE/POLYVINYL CHLORIDE (AB/PVC) FLEXIBLE FOAM FURNISHED IN THE FORM OF TUBING. SEE PLASTICS+ (QMFZ2) CATEGORY IN THE PLASTICS RECOGNIZED COMPONENT DIRECTORY FOR NAMES OF MANUFACTURERS. ANY RECOGNIZED COMPONENT TUBE INSULATION MATERIAL MEETING THE ABOVE SPECIFICATIONS AND HAVING A UL94

FLAMMABILITY CLASSIFICATION OF 94-5VA MAY BE USED.

5. PACKING MATERIAL - (NOT SHOWN) - WHEN USING A 1 IN. (25 MM) DIAM PIPE WITH 1 IN. (25 MM) AB/PVC PIPE INSULATION IN A 4 IN. (102 MM) DEVICE, AND A MIN 2 IN. (51 MM) THICKNESS OF MIN 4 PCF (64 KG/M³) MINERAL WOOL BATT INSULATION SHALL BE FIRMLY PACKED INTO TOP OF DEVICES, FLUSH WITH THE TOP OF THE DEVICE.

*BEARING THE UL CLASSIFICATION MARK

THE FIRESTOP DEVICE AND METALLIC PENETRANT SHALL BE SIZED AS FOLLOWS:

1. FLOOR OR WALL ASSEMBLY - MIN 2-1/2 IN. (64 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150

PCF OR 1600-2400 KG/M³) CONCRETE.

1A. FLOOR ASSEMBLY - (OPTIONAL - NOT SHOWN) - THE FIRE RATED UNPROTECTED CONCRETE AND STEEL FLOOR ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN TEH MANNER SPECIFIED IN TEH INDIVIDUAL D900

SERIES DESIGNS IN THE FIRE RESISTANCE DIRECTORY AND AS SUMMARIZED BELOW:

A. STEEL FLOOR AND FORM UNITS* - COMPOSITE OR NON-COMPOSITE MAX 2 IN. (76 MM) DEEP GALV STEEL FLUTED

UNITS AS SPECIFIED IN THE INDIVIDUAL FLOOR-CEILING DESIGN.

B. CONCRETE - MIN 2-1/2 IN. (64 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR

1600-2400 KG/M³) CONCRETE.

2. FIRESTOP DEVICE* - CAST IN PLACE FIRESTOP DEVICE PERMANENTLY EMBEDDED DURING CONCRETE PLACEMENT OR GROUTED IN CONCRETE FLOOR ASSEMBLY IN ACCORDANCE WITH ACCOMPANYING INSTALLATION INSTRUCTIONS

WITH A MAX 2 IN. (51 MM) PROJECTION ABOVE THE TOP SURFACE OF THE CONCRETE.

3. THROUGH PENERANTS - ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED WITHIN THE FIRESTOP DEVICE.

PIPE, CONDUIT, OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. THE FOLLOWING

TYPES OF PIPE, CONDUIT OR TUBING MAY BE USED:

A. STEEL PIPE - NOM. 4 IN. (102 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. COPPER TUBING - NOM 4 IN. (102 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.

C. COPPER PIPE. - NOM 4 IN. (102 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

SYSTEM NO. F-A-5015

F RATING - 2 HR

T RATING - 1/2 HR AND 3/4 HR (SEE ITEM 3)

C R

CLASSIFIED BY

UNDERWRITERS

LABORATORIES, INC.

TO UL 1479 AND CAN/ULC-

S115

US

SECTION A-A

A A

4 3

2. FIRESTOP DEVICE* — CAST IN PLACE FIRESTOP DEVICE PERMANENTLY EMBEDDED DURING CONCRETE PLACEMENT OR GROUTED IN CONCRETE ASSEMBLY IN ACCORDANCE WITH ACCOMPANYING INSTALLATION INSTRUCTIONS. THE 3, 4 AND 6 IN. DEVICES MAY EXTEND A MAX 2 IN. (51 MM) ABOVE THE TOP SURFACE OF THE CONCRETE. THE MAX EXTENSION ABOVE THE SLAB FOR THE 2 AND 2.5 IN. DEVICES IS

NOT RESTRICTED.

3. THROUGH PENETRANTS — ONE NONMETALLIC PIPE OR CONDUIT TO BE INSTALLED WITHIN THE FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR ASSEMBLY. FOR W RATING WITH WATER BARRIER MODULE, PIPE SHALL BE INSTALLED FROM BOTTOM OF DEVICE. THE FOLLOWING TYPES AND SIZES OF NONMETALLIC PIPES OR CONDUITS MAY BE USED:

A. POLYVINYL CHLORIDE (PVC) PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 SOLID OR CELLULAR CORE PVC PIPE FOR

USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE OR VENT) PIPING SYSTEMS.

B. CHLORINATED POLYVINYL CHLORIDE (CPVC) PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SDR11 OR SDR13.5 CPVC PIPE FOR USE IN

CLOSED (PROCESS OR SUPPLY) PIPING SYSTEMS.

C. RIGID NONMETALLIC CONDUIT — NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 PVC CONDUIT INSTALLED IN ACCORDANCE

WITH THE NATIONAL ELECTRICAL CODE (NFPA NO. 70).

THE FIRESTOP DEVICES AND NONMETALLIC PENETRANTS SHALL BE SIZED AS FOLLOWS:

GENERAL NOTES:

1. REFER TO SECTION 07 84 00 OF THE SPECIFICATIONS FOR QUALITY CONTROL REQUIREMENTS.

2. DETAILS SHOWN ARE FOR TYPICAL APPLICATIONS AND MAY NOT BE INCLUSIVE OF ALL PROJECT REQUIREMENTS.

SOME DETAILS COULD BE USED FOR EITHER WALL OR FLOOR APPLICATIONS. IF FIELD CONDITIONS DO NOT MATCH

REQUIREMENTS OF TYPICAL DETAILS, CONTRACTOR SELECTED MANUFACTURER APPROVED ALTERNATE DETAILS SHALL BE UTILIZED. FIELD CONDITIONS AND DIMENSIONS NEED TO BE VERIFIED FOR COMPLIANCE WITH THE

DETAILS, INCLUDING BUT NOT LIMITED TO THE FOLLOWING: * MINIMUM AND MAXIMUM WIDTH OF JOINTS * TYPE AND

THICKNESS OF FIRE-RATED CONSTRUCTION. THE MINIMUM ASSEMBLY RATING OF THE FIRESTOP ASSEMBLY SHALL

MEET OR EXCEED THE HIGHEST RATING OF THE ADJACENT CONSTRUCTION.

3. IF ALTERNATE DETAILS MATCHING THE FIELD CONDITIONS ARE NOT AVAILABLE, MANUFACTURER'S ENGINEERING

JUDGMENT DRAWINGS ARE ACCEPTABLE. DRAWINGS SHALL FOLLOW THE INTERNATIONAL FIRESTOP COUNCIL

(IFC) GUIDELINES FOR EVALUATING FIRESTOP SYSTEMS ENGINEERING JUDGMENTS. PROVIDE ARCHITECT WITH

REQUIRED SUBMITTALS.

4. FIRESTOP SYSTEM INSTALLATION MUST MEET REQUIREMENTS OF ASTM E-814 (UL 1479) TESTED ASSEMBLIES THAT

PROVIDE A FIRE RATING EQUAL TO THAT OF CONSTRUCTION BEING PENETRATED.

5. ALL RATED THROUGH-PENETRATION ASSEMBLIES SHALL BE PROMINENTLY LABELED.

6. FOR OUTLET BOXES REQUIRING PROTECTION, USE ONLY WALL OPENING PROTECTIVE MATERIALS, CATEGORY CLIV

AS CLASSIFIED BY UNDERWRITER'S LABORATORIES, FIRE RESISTANCE DIRECTORY.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS

321 4 5 6 7 8 9 10

757-15-102

7850 Freeway Circle

440.243.2000 t

Cleveland, OH 44130

440.243.3305 f

Arch. Proj. No.:

C U s e rs

\j c h o \D o c u m e n ts

\R e v it M o d e ls

\1

R

V A

C o lu m b u s C h ill e r

P la n t R e v is io n

C e n tr a l_ jd c h o

.r v t

/5

/2

:0

:5

A

M

G-103

PENETRATION FIRE STOPPING DETAILS CONSTRUCT CHILLER PLANT

420 N. JAMES ROAD, COLUMBUS,

OHIO 43219

05/06/2022 -- --

BID & CONSTRUCTION

(REVISED)18912

Revisions: Date:

SYSTEM NO. C-AJ-1226

F RATING - 3 HR

T RATING - 0 HR

L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT

L RATING AT 400 F - 4 CFM/SQFT

SYSTEM NO. C-AJ-3180

F RATING - 3 HR

T RATING - 0 HR

SYSTEM NO. C-AJ-7051

F RATING - 3 HR

T RATING - 1 HR

SINGLE METAL PIPES OR CONDUIT SINGLE OR BUNDLED CABLES

NON-INSULATED MECHANICAL DUCTWORK

WITHOUT DAMPERS

C R

CLASSIFIED BY

UNDERWRITERS

LABORATORIES, INC.

TO UL 1479 AND CAN/ULC-

S115

US C

R

CLASSIFIED BY

UNDERWRITERS

LABORATORIES, INC.

TO UL 1479 AND CAN/ULC-

S115

US

C R

CLASSIFIED BY

UNDERWRITERS

LABORATORIES, INC.

TO UL 1479 AND CAN/ULC-

S115

US

A

A

SECTION A-A

4B

4B 1

4A

SECTION A-A

A

A

A

A SECTION A-A

3B

3A

1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM

OF OPENING IS 32 IN.

2. METALLIC SLEEVE - (OPTIONAL) NOM 32 IN. DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL SLEEVE CST OR GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH FLOOR OR WALL SURFACES OR EXTENDING

A MAX OF 3 IN. ABOVE FLOOR OR BEYONE BOTH SURFACES OF WALL.

3. SHEET METAL SLEEVE - (OPTIONAL) MAX 6 IN. DIAM, MIN 26 GA GALV STEEL PROVIDED WITH A 26 GA GALV STEEL SQURE FLANGE SPOT WELDED TO THE SLEEVE AT A APPROX MID-HEIGHT, OR FLUSH WITH BOTTOM OF SLEEVE IN FLOORS, AND SIZED TO BE A MIN OF 2 IN. LARGER THAN THE SLEEVE DIAM. THE SLEEVE IS TO BE CAST IN PLACE AND MAY EXTEND A MAX OF 4 IN. BELOW THE BOTTOM OF THE DECK AND A MAX OF 1 IN.

ABOVE THE TOP SURFACE OF THE CONCRETE FLOOR.

4. THROUGH-PENETRANT - ONE METALLIC PIPE, TUBE OR CONDUIT TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE BETWEEN PENETRANT AND PERIPHERY OF OPENING SHALL BE MIN 0 IN. (POINT CONTACT) TO MAX 1-7/8 IN. SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PENETRANTS MAY BE USED:

A. STEEL PIPE - NOM 30 IN. DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE - NOM 30 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

C. COPPER PIPE - NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

D. COPPER TUBING - NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.

E. CONDUIT - NOM 6 IN. DIAM (OR SMALLER) STEEL CONDUIT.

F. CONDUIT - NOM 4 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING (EMT).

5. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:

A. PACKING MATERIAL - MIN 4 IN. THICKNESS OF MIN 4 PCF MINERAL WOOL BATT INSULATION FIRMLY

PACKED INTO OPENING AS A PERMANENT FORM. PACKING METERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR SLEEVE OR FROM BOTH SURFACES OF WALL OR SLEEVE AS REQUIRED TO

ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.

B. FILL, VOID, OR CAVITY MATERIAL* - SEALANT - MIN 1/4 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR SLEEVE OR WITH BOTH SURFACES OF WALL OR SLEEVE. AT THE POINT OR CONTINUOUS CONTACT LOCATIONS BEWEEN PENETRANT AND CONCRETE OR SLEEVE, A MIN 1/4 IN. DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE CONCRETE OR SLEEVE/PIPE PENETRANT INTERFACE ON THE TOP SURFACE OF FLOOR AND ON BOTH SURFACES OF

WALL.

*BEARING THE UL CLASSIFICATION MARK

1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M³) CONCRETE FLOOR OR MIN 4-3/4 IN. (152 MM). SEE CONCRETE BLOCKS*.

MAX DIAM OF OPENING IS 6 IN. (152 MM). SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE

RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.

2. STEEL SLEEVE - (OPTIONAL) - NOM 6 IN. (152 MM) DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL PIPE

CAST OR GROUTED INTO FLOOR OR WALL ASSEMBLY, FLUSH WITH FLOOR OR WALLL SURFACES.

3. CABLES - AGGREGATE CROSS-SECTIONAL AREA OF CABLES IN OPENING TO BE MAX 45% OF THE AGGREGATE CROSS-SECTIONAL AREA OF THE OPENING. CABLES TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. ANY COMBINATION OF THE FOLLOWING TYPES AND SIZES OF

METALLIC CONDUCTOR OR FIBER OPTIC CABLE MAY BE USED:

A. MAX 500 KCMIL SINGLE COPPER CONNECTOR POWER CABLE WITH THERMOPLASTIC INSULATION

AND POLYVINYL CHLORIDE ( PVC) JACKET.

B. MAX 300 KCMIL SINGLE COPPER CONDUCTOR TELECOMMUNICATION CABLES WITH POLYVINYL

CHLORIDE (PVC) INSULATION AND JACKET MATERIAL.

C. MAX 7/C COPPER CONDUTOR NO. 12 AWG MULTICONDUTOR POWER AND CONTROL CABLES

WITH POLYVNYL CHOLORIDE (PVC) OR CROSS-LINKED POLYETHYLENE (XLPE) INSULATION AND

PVC JACKET.

D. MULTIPLE FIBER OPTICAL COMMUNICATION CABLES JACKETED WITH PVC AND HAVING A MAX

OUTSIDE DIAM OF 1/2 IN. (13 MM).

E. MAX 3/C COPPER CONDUCTOR NO. 12 AWG WITH BARE ALUMINUM GROUND, POLYVINYL

CHOLRIDE (PVC) INSULATED STEEL, METAL-CLAD CABLE.

F. MAX 3/C WITH GROUND 2/0 AWG COPPER CONDUCTOR SER CABLE WITH CROSS-LINKED

POLYETHYLENE (XLPE) INSULATION AND POLYVINYL CHLORIDE (PVC) JACKET.

G. RG/U COAXIAL CABLE WITH POLYETHYLENE (PE) INSULATION AND POLYVINYL CHLORIDE (PVC)

JACKET HAVING A MAX OUTSIDE DIAMTER OF 1/2 IN. (13 MM).

H. FIRE RESISTIVE CABLES* - MAX 1-1/4 IN. (32 MM) DIAM SINGLE CONDUCTOR OR MULTI

CONDUCTOR TYPE MI CABLE. A MIN1/8 IN. (3 MM) SEPARATION SHALL BE MAINTAINED BETWEEN

MI CABLES AND ANY OTHER TYPES OF CABLE.

4. PACKING MATERIAL - MIN 4-1/4 IN. (108 MM) THICKNESS OF MIN 4 PCF (64 KG/M³) MINERAL WOOL BATT INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO BE

RECESSED FROM TOP SURFACE OF FLOOR TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL

METERIAL.

5. FILL, VOID, OR CAVITY MATERIAL* - SEALANT - MIN 1/4 IN. (6.4 MM) THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR WITH BOTH SURFACES OF WALL.

*BEARING THE UL CLASSIFICATION MARK

1. FLOOR OR WALL ASSEMBLY - MIN 4-1/2 IN. (114 MM) THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF OR 1600-2400 KG/M³) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UNDERWRITERS LABORATORIES INC. CLASSIFIED CONCRETE BLOCKS*. MAX AREA OF OPENING IS 1024 IN. SQ. WITH A MAX DIMENSION OF 32 IN. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR

NAMES OF MANUFACTURERS.

2. STEEL DUCT - NOM 30 BY 30 IN. (OR SMALLER) NO. 24 GAUGE (OR HEAVIER) GALV STEEL DUCT. ONE STEEL DUCT TO BE POSITIONED WITHIN THE FIRESTIP SYSTEM. THE ANNULAR SPACE SHALL BE MIN 1/4 IN. TO A MAX

1-3/4 IN. DUCT TO BE RIGIDLY SUPPORTED ON BOTH SIDES FO FLOOR OR WALL ASSEMBLY.

3. FIRESTOP SYSTEM - THE FIRESTOP SYSTEM SHALL CONSIST OF THE FOLLOWING:

A. PACKING MATERIALS - MIN 3-1/2 IN. THICKNESS OF MIN 4 PCF MINERAL WOOL BATT INSULATION FIRMLY

PACKED INTO OPENING AS A PERMANENT FORM BETWEEN TEH BARE STEEL DUCT AND THE PERIPHERY OF THE OPENING. PACKING MATERIAL TO BE RECESSED FROM TOP SURFACE OF FLOOR OR BOTH SURFACES

OF WALL AS REQUIRED TO ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL

B. FILL, VOID, OR CAVITY MATERIAL* - SEALANT - MIN 1 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN

ANNULUS, FLUSH WITH TOP SURFACE OF FLOOR OR BOTH SURFACES OF WALL.

SYSTEM NO. W-J-8007

C R

CLASSIFIED BY

UNDERWRITERS

LABORATORIES, INC.

TO UL 1479 AND CAN/ULC-

S115

US

1. WALL ASSEMBLY — MIN 7-5/8 IN. (194 MM) THICK WALL ASSEMBLY CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX AREA OF OPENING IS 2496 IN. SQ. (161 M2) WITH MAX DIMENSION OF 52 IN. (1321 MM).

SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE DIRECTORY FOR NAMES OF

MANUFACTURERS.

2. CABLE TRAY* — MAX 36 IN. (914 MM) WIDE BY 6 IN. (152 MM) DEEP OPEN-LADDER CABLE TRAY WITH CHANNEL- SHAPED SIDE RAILS FORMED OF 0.067 IN. (1.7MM) THICK ALUMINUM AND WITH 1-1/2 IN. (38 MM) WIDE BY 3/4 IN.

(19 MM) DEEP CHANNEL- SHAPED RUNGS SPACED 10 IN. (254 MM) OC. ONE CABLE TRAY TO BE INSTALLED IN THE OPENING. THE ANNULAR SPACE BETWEEN ADJACENT PENETRATING ITEMS SHALL BE MIN 2 IN. (51 MM) TO MAX 4-1/2 IN. (114 MM). THE MAX ANNULAR SPACE BETWEEN THE PERIPHERY OF THE OPENING SHALL BE MIN 1 IN. (25 MM) TO MAX 3 IN. (76 MM). CABLE TRAY TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY.

3. CABLES — AGGREGATE CROSS-SECTIONAL AREA OF CABLES IN CABLE TRAY TO BE MAX 40 PERCENT OF THE CROSS-SECTIONAL AREA OF THE CABLE TRAY BASED ON A MAX 6 IN. (152 MM) CABLE LOADING DEPTH WITHIN THE CABLE TRAY. ANY COMBINATION OF THE FOLLOWING TYPES AND SIZES OF CABLES MAY BE USED:

A. A. 300 PAIR — NO. 24 AWG TELEPHONE CABLE WITH POLYVINYL CHLORIDE (PVC) INSULATION AND PVC

JACKET.

B. 1/C - 500 KCMIL WITH THERMOPLASTIC INSULATION AND NYLON JACKET.

C. 24 FIBER OPTIC CABLE WITH POLYVINYL CHLORIDE (PVC) OUTER AND SUBUNIT JACKET.

D. 7/C NO. 12 AWG CABLE WITH POLYVINYL CHLORIDE (PVC) INSULATION AND PVC JACKET.

4. THROUGH PENETRANTS — ONE OR MORE PIPES OR TUBES TO BE INSTALLED WITHIN THE OPENING. THE TOTAL NUMBER OF THROUGH-PENETRANTS IS DEPENDENT ON THE SIZE OF THE OPENING AND TYPES AND SIZES OF THE PENETRANTS. ANY COMBINATION OF THE PENETRANTS DESCRIBED BELOW MAY BE USED PROVIDED THAT THE FOLLOWING PARAMETERS RELATIVE TO THE ANNULAR SPACES AND THE SPACINGS BETWEEN THE PIPES ARE MAINTAINED. THE SPACE BETWEEN PIPES, CONDUITS OR TUBING SHALL BE MIN 1-1/2 IN.(38 MM) TO MAX 4-3/4 IN. (121 MM). THE SPACE BETWEEN THE PERIPHERY OF THE OPENING AND THE PIPES OR CONDUITS SHALL BE MIN 3 IN. (76 MM) TO MAX 4-1/4 IN. (108 MM). PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING

MAY BE USED:

A. STEEL PIPE — NOM 12 IN. (305 MM) DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE — NOM 12 IN. (305 MM) DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

C. CONDUIT — NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRIC METALLIC TUBING OR 6 IN. (152 MM)

DIAM STEEL CONDUIT.

D. COPPER TUBING — NOM 6 IN. (152 MM) DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.

E. COPPER PIPE — NOM 6 IN. (152 MM) DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

5. PIPE COVERING* — NOM 1-1/2 IN. (38 MM) THICK HOLLOW CYLINDRICAL HEAVY DENSITY (3.5 PCFOR 56 KG/M3) GLASS FIBER UNITS JACKETED OF THE OUTSIDE WITH AN ALL SERVICE JACKET. LONGITUDINAL JOINTS SEALED WITH METAL FASTENERS OR FACTORY-APPLIED SELF-SEALING LAP TAPE. TRANSVERSE JOINTS SECURED WITH METAL FASTENERS OR WITH BUTT TAPE SUPPLIED WITH THE PRODUCT. SEE PIPE EQUIPMENT COVERING — MATERIALS — (BRGU) CATEGORY IN THE BUILDING MATERIALS DIRECTORY FOR NAMES OF MANUFACTURERS.

ANY PIPE COVERING MATERIAL MEETING THE ABOVE SPECIFICATIONS AND BEARING THE UL CLASSIFICATION MARKING WITH A FLAME SPREAD INDEX OF 25 OR LESS AND A SMOKE DEVELOPED INDEX OF 50 OR LESS MAY BE

USED.

5A. METAL JACKET — (NOT SHOWN) — REQUIRED WHEN PIPE COVERING (ITEM 5) IS USED. MIN 6 IN. (152 MM) LONG JACKET FORMED OF MIN 0.010 IN. (0.25 MM) THICK STEEL SHEET CUT TO WRAP TIGHTLY AROUND THE PIPE INSULATION WITH A MIN 2 IN. (51 MM) LAP. JACKET SECURED WITH MIN 1/2 IN. (13 MM) WIDE STAINLESS STEEL HOSE CLAMP LOCATED AT THE CENTER OF THE JACKET. JACKET TO BE INSTALLED ON BOTH SURFACES OF

WALL AND RECESSED INTO THE OPENING 1 IN. (25 MM).

A

A

8C

8A

SECTION A-A

ANSI/UL 1479 (ASTM E814)

F RATING - 4 HR

T RATING - 0 HR

F RATING - 4 HR

FT RATING - 0 HR

FH RATING - 4 HR

FTH RATING - 0 HR

CAN/ULC S115

MIXED PENETRANTS

SYSTEM NO. W-J-3050

F RATING - 4 HR

T RATING - 1 HR

C R

CLASSIFIED BY

UNDERWRITERS

LABORATORIES, INC.

TO UL 1479 AND CAN/ULC-

S115

US

SINGLE OR BUNDELED CABLES

1. WALL ASSEMBLY- MIN 7-112 IN. THICK REINFORCED LIGHTWEIGHT OR NORMAL WEIGHT (100-150

PEL) CONCRETE. WALL MAY ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE

BLOCKS*. MAX DIAM OF OPENING IS 4 IN. SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE

RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.

2. STEEL SLEEVE- NOM 4 IN. DIAM (OR SMALLER) SCHEDULE 40 (OR HEAVIER) STEEL PIPE SLEEVE FRICTION FIT IN NOM 4 IN. DIAM CIRCULAR OPENING CORE DRILLED THROUGH WALL. LENGTH OF

STEEL SLEEVE TO BE EQUAL TO THICKNESS OF WALL.

3. CABLES- AGGREGATE CROSS SECTIONAL AREA OF CABLES IN OPENING TO BE MAX 33 PERCENT

OF THE CROSS SECTIONAL AREA OF THE OPENING. CABLES INSTALLED EITHER

CONCENTRICALLY OR ECCENTRICALLY WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE

BETEWEEN CABLES AND THE STEEL SLEEVE SHALL BE MIN 1/4 IN. TO MAX 1 IN. CABLES TO BE

RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES

OF CABLES MAY BE USED:

A. 7/C (WITH GROUND) NO. 12 AWG CABLE, WITH PVC INSULATION AND OUTER JACKET.

B. MAX 25 PAIR NO. 24 AWG (OR SMALLER) COPPER CONDUCTOR TELEPHONE CABLE WITH

PVC INSULATION, WITH PVC JACKET.

C. MAX RG59/U (OR SMALLER) COAXIAL CABLE WITH FLUORINATED ETHYLENE INSULATION

AND JACKETING.

D. 3/C (WITH GROUND) NO. 10 AWG BARE COPPER GROUND METAL CLAD CABLE WITH A PVC

JACKET.

E. MULTIPLE 24 FIBER-<JPTICAL COMMUNICATION CABLES JACKETED WITH POLYVINYL

CHLORIDE AND HAVING A MAX OUTSIDE DIAM OF 1/2 IN.

4. FILL, VOID OR CAVITY MATERIAL*-5EALANT- MIN 2 IN. THICKNESS OF FILL MATERIAL APPLIED

WITHIN ANNULUS, FLUSH WITH BOTH SURFACES OF THE WALL.

*BEARING THE UL CLASSIFICATION MARK

A

A

SECTION A-A

1B

1A A

SECTION A-A

A

C R

CLASSIFIED BY

UNDERWRITERS

LABORATORIES, INC.

TO UL 1479 AND CAN/ULC-

S115

US SYSTEM NO. W-L-3065

ANSI/UL1479 (ASTM E814) CAN/ULC S115

F RATINGS - 1 AND 2 HR (SEE ITEM1)

FT RATING - 0 AND 3/4 HR (SEE ITEM 3)

FH RATING - 1 AND 2 HR ( SEE ITEM 1)

FTH RATING - 0 AND 3/4 HR (SEE ITEM 3)

L RATING AT AMBIENT - 15 CFM/SQ FT

L RATING AT 400 F - 8 CFM/SQ FT

F RATINGS - 1 AND 2 HR (SEE ITEM 1)

T RATING - 0 AND 3/4 HR (SEE ITEM 3)

L RATING AT AMBIENT - 15 CFM/SQ FT

L RATING AT 400 F - 8 CFM/SQ FT

1. WALL ASSEMBLY — THE 1 OR 2 FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300, U400 OR V400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE

RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS — WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2

BY 4 IN. (51 BY 102 MM) LUMBER SPACED 16 IN. (406 MM) OC. STEEL STUDS TO BE MIN 2-1/2 IN. (64 MM) WIDE AND SPACED MAX 24 IN.

(610 MM) OC.

B. GYPSUM BOARD* — NOM 5/8 IN. (16 MM) THICK GYPSUM BOARD, WITH SQUARE OR TAPERED EDGES. THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300, U400 OR V400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 5-1/2 IN. (138 MM) WHEN SLEEVE (ITEM

2) IS EMPLOYED. MAX DIAM OF OPENING IS 4 IN. (102 MM) WHEN SLEEVE (ITEM 2) IS NOT EMPLOYED. THE F RATING OF THE

FIRESTOP SYSTEM IS EQUAL TO THE FIRE RATING OF THE WALL ASSEMBLY.

SINGLE OR BUNDLED CABLES

A 3

1A

1B

A

SECTION A-A

1. WALL ASSEMBLY — THE 1 OR 2 HR FIRE-RATED GYPSUM WALLBOARD/STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL AND PARTITION DESIGNS IN THE UL FIRE RESISTANCE

DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES:

A. STUDS — WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM 2 BY

4 IN. LUMBER SPACED 16 IN. OC. STEEL STUDS TO BE MIN 2-1/2 IN. WIDE AND SPACED MAX 24 IN. OC. WHEN STEEL STUDS ARE USED AND THE DIAM OF OPENING EXCEEDS THE WIDTH OF STUD CAVITY, THE OPENING SHALL BE FRAMED ON ALL SIDES USING LENGTHS OF STEEL STUD INSTALLED BETWEEN THE VERTICAL STUDS AND SCREW-ATTACHED TO THE STEEL STUDS AT EACH END. THE FRAMED OPENING IN THE WALL SHALL BE 4 TO 6 IN. WIDER AND 4 TO 6 IN. HIGHER THAN THE DIAM OF THE PENETRATING ITEM SUCH THAT, WHEN THE PENETRATING ITEM IS INSTALLED IN THE OPENING, A 2 TO 3 IN. CLEARANCE IS PRESENT BETWEEN THE PENETRATING ITEM

AND THE FRAMING ON ALL FOUR SIDES.

B. GYPSUM BOARD* — 5/8 IN. THICK, 4 FT WIDE WITH SQUARE OR TAPERED EDGES. THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM OF OPENING IS 32-1/4 IN. FOR STEEL STUD WALLS. MAX DIAM OF OPENING IS 14-1/2 IN.

FOR WOOD STUD WALLS. THE F RATING OF THE FIRESTOP SYSTEM IS EQUAL TO THE FIRE RATING OF THE WALL ASSEMBLY.

ANSI/UL1479 (ASTM E814) CAN/ULC S115

F RATINGS - 1 AND 2 HR

(SEE ITEMS 1 ANS 3)

FT RATING - 0 HR

FH RATINGS - 1 AND 2 HR

(SEE ITEMS 1 AND 3)

FTH RATING - 0 HR

FTH RATING - 0HR

L ARATING AT ABIENT - LESS THAN

1 CFM/SQ FT

L RATING A 400 F - LESS THAN

1CFM/SQ FT

SYSTEM NO. W-L-1054

C

R

CLASSIFIED BY

UNDERWRITERS

LABORATORIES, INC.

TO UL 1479 AND CAN/ULC-

S115

US

F RATINGS - 1 AND 2 HR

(SEE ITEMS 1 AND 3)

T RATING - 0 HR

L RATING AT AMBIENT - LESS THAN

1 CFM/SQ FT

L RATING AT 400 F - LESS THAN

CFM/SQ FT

METAL PIPES OR CONDUIT

4. STEEL RETAINING ANGLE - NOM 2 IN. BY 2 IN. BY NO. 16 GUAGE (OR HEAVIER) STEEL ANGLES ATTACHED TO ALL FOUR SIDES OF THE STEEL DUCT ON THE TOP SURFACE OR BOTH SURFACES OF THE WALL. THE ANGLES SHALL BE ATTACHED WITH NO. 8 (OR LARGER) STEEL SHEET METAL SCREWS SPACED MAX OF 1 IN. FROM EACH END

AND A MAX OF 3 IN. O.C.

*BEARING THE UL CLASSIFICATION MARK

2. THROUGH-PENETRANTS — ONE METALLIC PIPE, CONDUIT OR TUBING TO BE INSTALLED EITHER CONCENTRICALLY OR ECCENTRICALLY

WITHIN THE FIRESTOP SYSTEM. THE ANNULAR SPACE SHALL BE MIN 0 IN. TO MAX 2-1/4 IN. PIPE MAY BE INSTALLED WITH CONTINUOUS POINT CONTACT. PIPE, CONDUIT OR TUBING MAY BE INSTALLED AT AN ANGLE NOT GREATER THAN 45 DEGREES FROM PERPENDICULAR.

PIPE, CONDUIT OR TUBING TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF WALL ASSEMBLY. THE FOLLOWING TYPES AND SIZES OF

METALLIC PIPES, CONDUITS OR TUBING MAY BE USED:

A. STEEL PIPE — NOM 30 IN DIAM (OR SMALLER) SCHEDULE 10 (OR HEAVIER) STEEL PIPE.

B. IRON PIPE — NOM 30 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.

C. CONDUIT — NOM 4 IN DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING OR 6 IN. DIAM STEEL CONDUIT.

D. COPPER TUBING — NOM 6 IN. DIAM (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING.

E. COPPER PIPE — NOM 6 IN. DIAM (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE.

3. FILL, VOID OR CAVITY MATERIAL* — SEALANT — MIN 5/8 IN. THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. AT THE POINT OR CONTINUOUS CONTACT LOCATIONS BETWEEN PIPE AND WALL, A MIN 1/2 IN. DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE PIPE WALL INTERFACE ON BOTH SURFACES OF WALL .

*BEARING THE UL CLASSIFICATION MARK

4. FILL, VOID OR CAVITY MATERIAL*— SEALANT OR PUTTY — FILL MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH EACH END OF THE STEEL SLEEVE OR WALL SURFACE. FILL MATERIAL INSTALLED SYMMETRICALLY ON BOTH SIDES OF THE WALL. A MIN 5/8 IN. (16 MM) THICKNESS OF SEALANT IS REQUIRED FOR THE 1 OR 2 HR F RATING . AN ADDITIONAL 1/2 IN. (13 MM) DIAM BEAD OF FILL MATERIAL SHALL BE APPLIED AROUND THE PERIMETER OF SLEEVE ON BOTH SIDES OF THE WALL WHEN SLEEVE EXTENDS BEYOND SURFACE OF

WALL.

*BEARING THE UL CLASSIFICATION MARK

+BEARING THE UL LISTING MARK

2. METALLIC SLEEVE — (OPTIONAL) - NOM 4 IN. (102 MM) DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC TUBING (EMT) OR SCHEDULE 5 (OR HEAVIER) STEEL PIPE OR MIN 0.016 IN. THICK (0.41 MM, NO.

This is the start of the file's text. The full file is on GovTribe.