This drawing package is for the construction of a chiller plant project at the Chalmers P. Wylie VA Ambulatory Care Center in Columbus, Ohio. The drawings provide technical specifications for electrical systems work including details for lighting, power, fire alarm, security, and low voltage installations. Device types and locations, conduit and cable routing, communications infrastructure, and other requirements are specified. The related federal contract opportunity is a SDVOSB set-aside solicitation from the Department of Veterans Affairs for construction of the chiller plant project in accordance with the provided drawings and specifications. The solicitation number is 36C25023B0049 and responses were due by the specified date. The agency intends to award a firm fixed price contract and commence work upon project approval and funding.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
3/8" MAX
CONDUIT, TYP
MINERAL WOOL
(FIRMLY
PACKED)
FIRESTOP SEALANT
[10mm]
JUNCTION BOX
(SIZE AS REQUIRED)
CONDUIT COMPRESSION
FITTING, TYP.
SPRING
NUT,
TYP
INTEGRAL GALVANIZED
LIPPED STEAL
MOUNTING CHANNEL,
TYP.
FLOOR
SLAB, TYP.
STEEL EXPANSION
ANCHOR, TYP
CONDUIT SLEEVE
12" AFF.
HYD. CEMENT
NOT TO SCALE
GENERAL NOTES:
1. MAINTAIN A MINIMUM CLEARANCE OF 12" ON ALL SIDES OF ROOF
PENETRATION FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE
PROPER FLASHING.
2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.
3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.
4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO
ENSURE PROPER METHODS & MATERIALS ARE USED TO MAINTAIN ROOF
WARRANTY.
PREFABRICATED RUBBER BOOT
CAP WITH GRADUATED STEPS &
WEATHER-PROOF PRESSURE
SEAL TO COLLAR
SEALANT AT PENETRATION
TO MEMBRANE JUNCTURE
BY ROOFING CONTRACTOR
MULTIPLE MEMBRANE STRIPPING PLIES
FEATHERED AT FIELD OF ROOF BY ROOFING
CONTRACTOR. PRIME FLANGE BEFORE
STRIPPING.
PREFABRICATED FORMED 0.06" THICK
ALUMINUM FLASHING ROUND COLLAR WITH
MIN. 3" WIDE FLANGE. ATTACH TO ROOF PER
MANUFACTURER'S INSTRUCTIONS
CONDUIT CLAMP.
SIZE AS REQUIRED
BATT INSULATION
ROOF MEMBRANE
WATER CUT-OFF
MASTIC COMPATIBLE
WITH ROOF MEMBRANE
STAINLESS CLAMP, TYP.
3/8" MIN GALVANIZED
THREADED ROD, TYP.
SEAL-OFF
FITTING,
TYP.
ROOF
STEEL
EXPANSION
ANCHOR
INTEGRAL
GALVANIZED LIPPED
STEEL MOUNTING
CHANNEL
CONDUIT,
TYP.
CONDUIT CLAMP.
SIZE AS REQUIRED
LOCKING SQUARE
WASHER & LOCKNUT
NOT TO SCALE
FLOOR
DISCONNECT EXISTING CAT6 CABLING FROM EXISTING ACCESS CONTROL PANEL AND RECONNECT TO NEW SECURITY MANAGEMENT SYSTEM SWITCH IN THE SAME TELECOMMUNICATIONS ROOM. PROVIDE ALL
NECESSARY REPROGRAMMING REQUIRED TO MAINTAIN ACCESS CONTROL OPERATION.
CONTRACTOR SHALL RETAIN SIMPLEX GRINNELL TO SURVEY EXISTING ACCESS CONTROL PANELS AND
UPGRADE FIRMWARE TO MOST RECENT VERSION AS NECESSARY.
EX ISTAR PRO
(TYPICAL)
NEW/FUTURE IP
CAMERA
(TYPICAL)
EX. FIBER OPTIC CABLING
TO MAIN TELECOMM. ROOM
EX. RACK
NEW CAT6A CABLING
SINGLE-MODE FIBER
OPTIC PATCH CABLING
POE SWITCH
NOT TO SCALE
CODED NOTES:
C1 C2
WALL SECTION
FLOOR SECTION
WHERE CONDUIT, CABLES AND OTHER COMPONENTS PASS THROUGH FIRE OR SMOKE RATED WALLS OR FLOORS, PROVIDE NON-ASBESTOS SEAL ASSEMBLIES CLASSIFIED BY U.L. TO PROVIDE FIRE BARRIERS EQUAL TO OR GREATER THAN THE TIME RATING OF THE CONSTRUCTION BEING PENETRATED, WITH APPROPRIATE MATERIALS AND SYSTEMS THAT COMPLY WITH APPLICABLE CODES AND THAT HAVE BEEN TESTED IN ACCORDANCE WITH U.L.
1479 OR ASTM E814.
GROUT, MORTAR OR GYPSUM BASED PRODUCTS SHALL NOT BE INSTALLED IN LIEU OF FIRESTOPPING
MATERIALS AND U.L. SYSTEMS.
FOR SLEEVED PENETRATIONS, FIRESTOP ANNULAR SPACE, IF ANY, BETWEEN SLEEVE AND ADJACENT
CONSTRUCTION TO MEET U.L. SYSTEM REQUIREMENTS. SEE NOTE 2 ABOVE.
THIS CONTRACTOR SHALL FIRESTOP ALL MISCELLANEOUS OPENINGS IN FIRE-RATED CONSTRUCTION
RESULTING FROM HIS WORK.
CONTRACTOR SHALL PROVIDE SUBMITTAL DRAWINGS TO ENGINEER, INCLUDING U.L. RATED SYSTEM
NUMBER AND DETAIL FOR EACH TYPE OF PENETRATION AND CONFIGURATION.
SLEEVES USED FOR CABLE RISERS THROUGH FLOORS OR WALLS SHALL BE INSTALLED PER THE ABOVE FLOOR OR WALL SECTIONS. IN ADDITION, FIRESTOP MATERIAL SHALL BE PROVIDED INSIDE SLEEVE AFTER
CABLES ARE COMPLETELY INSTALLED.
PIPE SLEEVE
FURNISH AND INSTALL FIRESTOP
MATERIALS IN ACCORDANCE WITH
APPROPRIATE U.L. SYSTEMS TO
MAINTAIN FIRE RESISTANCE RATING
PENETRATING CONDUIT, ETC.
FLOOR SLAB; SEE
ARCHITECTURAL DRAWINGS
FOR FLOOR CONSTRUCTION
AND FIRE RATING
DAMMING MATERIAL
(PER U.L. TESTED SYSTEM DESIGN)
SEE ARCHITECTURAL DRAWINGS FOR
WALL CONSTRUCTION AND FIRE RATING
PENETRATING CONDUIT, ETC.
FURNISH AND INSTALL FIRESTOP MATERIALS IN
ACCORDANCE WITH APPROPRIATE U.L. SYSTEMS
TO MAINTAIN FIRE RESISTANCE RATING
SEAL JOINT BETWEEN SLEEVE AND FLOOR
SLAB WITH MIN. 1/2" BEAD FIRESTOP CAULK
PIPE SLEEVE (SLEEVE TO EXTEND 2" ABOVE
FLOOR IN MECHANICAL EQUIPMENT
ROOMS.)
1.
2.
3.
4.
5.
6.
GENERAL NOTES
NOT TO SCALE
PR
DC
NEW CHILLER PLANT CONTROL DEVICESEXISTING CHP DEVICES
PR
DC
#I-STAR PRO
SECURITY
PANEL
"SCP"
EXISTING
CONNECT UP TO (8)
CARD READERS TO "SCP"
NEW
PR KS
DC
X
P
X
X X
X
X
X
X
X
NEW
NEW NEW
CM
EXISTING SOFTWARE HOUSE I-STAR-PRO SECURITY SYSTEM PANEL (TYCO #STAR008W-64ANPS) "SCP" AT LOCATION AS INDICATED ON POWER PLANS. READER MODULES IN NEW "SCP" TO ACCOMMODATE UP TO (8) CARD READERS. EXISTING SYSTEM ALLOWS FOR FUTURE EXPANDABILITY TO (16) CARD READERS.
CODED NOTES
NOT TO SCALE
ELECTRICAL
EQUIPMENT
ELECTRICAL
EQUIPMENT
4"H CONCRETE PAD WITH
CHAMFERED CORNERS.
FLOOR
FRONT VIEW
CONCRETE PAD WITH 2" OVERHANG
ON EACH SIDE.
TOP VIEW
NOTE: CONTRACTOR SHALL INSTALL CONCRETE HOUSEKEEPING PAD FOR ALL ELECTRICAL
EQUIPMENT MOUNTED ON FLOOR IN ELECTRICAL ROOMS (TRANSFORMERS,
SUBSTATIONS, SWITCHBOARDS, TRANSFER SWITCHES, UPS EQUIPMENT, MOTOR
CONTROL CENTERS, ETC.).
2"
2"
1"
1"
NOT TO SCALE
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:2
P M
E-501
ELECTRICAL DETAILS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00
FLOOR PENETRATION DETAIL 2
ROOF PENETRATION DETAIL 4 CAMERA SYSTEM RISER DIAGRAM 5 FIRE STOPPING DETAIL 6
SECURITY SYSTEM RISER DIAGRAM 3TYPICAL HOUSEKEEPING CONCRETE PAD 1
Revisions: Date:
FINAL BID & CONSTRUCTION 11/24/2021
FINAL BID & CONSTRUCTION (REVISED) 05/06/2022
3"
6"
1.
2.
3.
PROVIDE AN IDENTIFICATION SIGN WHICH CLEARLY INDICATES ELECTRICAL
SYSTEM INFORMATION FOR PANELBOARDS, DISTRIBUTION PANELS,
SWITCHBOARDS, MOTOR CONTROL CENTERS, AUTOMATIC TRANSFER SWITCHES.
PROVIDE ENGRAVED 1/2"H (MIN.) LETTERING ON PHENOLIC NAMEPLATE WITH THE
FOLLOWING COLOR FORMAT:
A. 208/120 VOLTS (NORMAL) - GREEN BACKGROUND, WHITE LETTERS
B. 480/277 VOLTS (NORMAL) - BLACK BACKGROUND, WHITE LETTERS
C. 208/120 VOLTS (EMERG.) - WHITE BACKGROUND, RED LETTERS
D. 480/277 VOLTS (EMERG.) - RED BACKGROUND, WHITE LETTERS
REFER TO ELECTRICAL SPECIFICATIONS FOR ADDITIONAL INFORMATION.
NAMEPLATE REQUIREMENTS:
PANELBOARD NAMEPLATE
LL21LS
100AMP, 208/120V-3P-4W
LIFE SAFETY
FED
FROM:
LOCATION:
HL21LS
2ND FL. ELECTRICAL
RM. ####
TYPICAL
NOT TO SCALE
DUPLEX RECEPTACLE WITH
WEATHERPROOF "IN-USE" COVER
SINGLE POLE TOGGLE SWITCH
WITH WEATHERPROOF COVER
3/4" RIGID
GALVANIZED STEEL
CONDUIT
3/4" RIGID
GALVANIZED
STEEL CONDUIT
HEAVY-DUTY VAPORTIGHT
LED LIGHTING FIXTURE
A B
O V
E R
O O
F
A B
O V
E R
O O
F
TWO GANG BOX
ROOF
PROVIDE STRUT SUPPORT SYSTEM
AND MOUNT DEVICES, CONDUIT, AND
LIGHTING FIXTURES.
NOT TO SCALE
AFIX STRUT SUPPORT TO
ROOF. MAINTAIN RATING AND
WARRANTY OF ROOFING
RPN-BD - 2
CIRCUIT NUMBER
PANEL (SOURCE)
1/4" H ENGRAVED
LETTERING
REFER TO COLOR
SCHEDULE FOR
FINISH TYPE
RECEPTACLE
LPN-BD - 2
CIRCUIT NUMBER
PANEL (SOURCE)
REFER TO COLOR
SCHEDULE FOR
FINISH TYPE
WALL SWITCH
PROVIDE DESCRIPTION
COVE
EACH EMERGENCY AND NORMAL WALL PLATE SHALL BE MACHINE ENGRAVED WITH THE PANEL NAME AND
CIRCUIT NUMBER OF THE POWER SOURCE THAT SUPPLIES EACH DEVICE.
"STICK-ON" LABELS ARE NOT ACCEPTABLE.
DO NOT BACKFILL ENGRAVED LETTERING WITH COLOR.
REFER TO ELECTRICAL MATERIALS AND METHODS SPECIFICATIONS SECTION FOR ADDITIONAL
CONSTRUCTION REQUIREMENTS.
REFER TO COLOR
SCHEDULE FOR
DEVICE COLOR.
REFER TO COLOR
SCHEDULE FOR
DEVICE COLOR.
METAL WITH HEAD
COLOR TO MATCH
PLATE FINISH
1/4" H ENGRAVED
LETTERING
NORMAL POWER
WHITE DEVICE/WHITE NYLON PLATE - OFFICES & ADMINISTRATIVE RMS
WHITE DEVICE/STAINLESS STEEL PLATE - PATIENT CARE (EXAM/PROCEDURE ROOMS) & PUBLIC AREAS
EMERGENCY POWER
RED DEVICE/RED NYLON PLATE - OFFICES & ADMINISTRATIVE RMS
RED DEVICE/STAINLESS STEEL PLATE - PATIENT CARE (EXAM/PROCEDURE ROOMS) & PUBLIC AREAS
NOTES:
1. REFER TO ELECTRICAL MATERIALS AND METHODS SPECIFICATION SECTION FOR ADDITIONAL CONSTRUCTION
REQUIREMENTS.
1.
2.
3.
4.
WALL PLATE DETAIL NOTES
DEVICE COLOR SCHEDULE
NOT TO SCALE
3"
6"
1.
2.
3.
PROVIDE AN IDENTIFICATION SIGN WHICH CLEARLY INDICATES INFORMATION FOR
USE AND MAINTENANCE OF DISCONNECT SWITCHES, MOTOR STARTERS,
SEPARATELY ENCLOSED CIRCUIT BREAKERS, AND CONTROL DEVICES.
PROVIDE ENGRAVED 1/2"H (MIN.) LETTERING ON PHENOLIC NAMEPLATE WITH THE
FOLLOWING COLOR FORMAT:
A. NORMAL POWER SYSTEM - BLACK BACKGROUND, WHITE LETTERS
B. EMERGENCY POWER SYSTEM - RED BACKGROUND, WHITE LETTERS
REFER TO ELECTRICAL SPECIFICATIONS FOR ADDITIONAL INFORMATION.
EQUIPMENT NAMEPLATE REQUIREMENTS:
EQUIPMENT NAMEPLATE
FED FROM:
LOCATION:
MCC-E1
1ST FL. MECHANICAL RM. S113
TYPICAL
VACUUM PUMP (VP-1)
15A-3P, 480/277V-3Ø-4W
ESSENTIAL EQUIPMENT
NOT TO SCALE
ELECTRIFIED LOCKSET - 24V. MOUNTED ON SECURED
SIDE OF THE DOOR. CONTAINS REQUEST-TO-EXIT
AND DOOR POSITION CONTACTS. LOCKSET
PROVIDED BY DOOR HARDWARE VENDOR AND
CONNECTED COMPLETE BY SECURITY CONTRACTOR.
PROXIMITY READER - MATCH EXISTING FACILITY
STANDARD. MOUNTS IN 2-GANG BOX W/SINGLE
GANG RING ON NON SECURED SIDE OF THE
DOOR. OPERATES ELECTRIFIED LOCKSET.
48"
6"SQ. x 4"D JUNCTION BOX WITH
SCREW COVER ABOVE FINISHED
CEILING. COIL AND TAG CABLES
INSIDE BOX FOR FUTURE EXTENSION.
#22/4 CABLE THROUGH DOOR
WIREWAY - TERMINATE TO LOCKSET
12/24VDC ACCESS CONTROL WIRING TO ACCESS CONTROL
PANEL. SINGLE MULTI-CONDUCTOR CABLE ASSEMBLY. ROUTE
IN 3/4"C TO NEAREST CABLE TRAY. CONDUCTORS AS REQUIRED
FOR CARD READER, 12/24VDC LOCKSET, REQUEST-TO-EXIT,
AND DOOR POSITION CONTACT.
JUNCTION BOX IN DOOR FRAME
WITH HOLES TO RECEIVE
CONDUIT. PLUG ANY UNUSED
HOLES. TERMINATE ELECTRIC
HINGE CABLES IN DOOR FRAME
JUNCTION BOX.
6" UON
(6) 18AWG SHIELDED TWISTED PAIRS
ELECTRIC POWER TRANSFER HINGE -
TRANSITIONS CABLING BETWEEN
DOOR AND FRAME.
CABLE AS REQUIRED
JB
CEILING
FLOOR
ALL ITEMS, EXCEPT THE CARD
READERS, ARE TO BE MOUNTED
ON THE SECURE SIDE OF THE
DOOR UNLESS OTHERWISE NOTED.
NOTE:
IF SUBMITTED DOOR HARDWARE IS NOT CAPABLE OF INTEGRATING DOOR POSITION CONTACTS AND REQUEST-TO-EXIT DEVICE SHALL BE ADDED TO FRAME AND ABOVE DOOR, RESPECTIVELY, TO CREATE
AN 'OR EQUAL' FUNCTION.
PR
NOT TO SCALE
VERIFY ACCESS CONTROLLED DOOR REQUIREMENTS AND EXACT CABLING REQUIREMENTS WITH
SECURITY SYSTEM AND DOOR HARDWARE VENDOR PRIOR TO ROUGH-IN. CABLING INDICATED IS FOR
REFERENCE ONLY. CONTRACTOR SHALL PROVIDE SINGLE, PLENUM-RATED COMPOSITE CABLE
DESIGNED FOR ACCESS CONTROL SYSTEMS FROM ACCESS CONTROL PANEL TO DOOR LOCATION
AND ROUTE CABLING TO INDIVIDUAL DEVICES AS REQUIRED. DO NOT PROVIDE SEPARATE ACCESS
CONTROL CABLING FOR EACH DEVICE FROM CONTROL PANEL TO DOOR LOCATIONS.
CONTRACTOR IS RESPONSIBLE FOR ALL ROUGH-INS, DEVICES, AND CABLING NECESSARY FOR A COMPLETE INSTALLATION. ACCESS CONTROL DETAILS ARE SHOWN FOR REFERENCE ONLY. DEVICES
SUBMITTED BY DOOR HARDWARE VENDOR MAY HAVE VARYING REQUIREMENTS. COORDINATE
REQUIREMENTS FOR ALL DOORS WITH DOOR HARDWARE VENDOR.
CONTRACTOR SHALL REFER TO ARCHITECTURAL PLANS AND DOOR HARDWARE SCHEDULE FOR
EXACT QUANTITY AND LOCATION OF ACCESS CONTROL DEVICES. CONTACT ENGINEER SHOULD A
DISCREPANCY ARISE BETWEEN ACCESS CONTROL DETAILS AND ARCHITECTURAL DRAWINGS.
ACCESS CONTROLLED DOORS MAY OCCUR IN CURTAIN WALL SYSTEMS. PROVIDE POST MOUNTED
PUSH BUTTONS/CARD READERS WHERE NECESSARY. COORDINATE EXACT REQUIREMENTS WITH
DOOR HARDWARE VENDOR.
ALL ACCESS CONTROL CABLING SHALL BE INSTALLED IN 3/4" MINIMUM CONDUIT. WHERE 3/4"
CONDUIT IS NOT FEASIBLE, CONTRACTOR SHALL RECEIVE WRITTEN APPROVAL FROM FACILITY
PROJECT MANAGER TO PROVIDE 1/2"C OR SMALLER. ACCESS CONTROL CABLING SHALL BE ROUTED IN CONDUIT TO NEAREST CABLE TRAY AND IS PERMITTED TO BE RUN IN CABLE TRAY BACK TO
ACCESS CONTROL PANEL.
PROVIDE VA STANDARD LABELING ON ALL ACCESS CONTROL CABLING (ROOM NAME, DEVICE AND DOOR NUMBER). LABEL RELAYS ON ACCESS CONTROL SYSTEM BOARDS WITH DEVICE BEING SERVED
AND ROOM NUMBER.
VAMC COR SHALL WITNESS COMPLETE FUNCTIONALITY TESTING OF ACCESS CONTROL, VIDEO
SURVEILLANCE, AND PANIC ALARM SYSTEMS PRIOR TO FINAL ACCEPTANCE. TESTING SHALL INCLUDE REPRESENTATIVE FROM FACILITY SECURITY. COORDINATE SCHEDULE OF TESTING WITH PROJECT
MANAGER.
ACCESS CONTROL INSTALLER IS REQUIRED TO BE CERTIFIED. PROGRAMMING MUST BE COMPLETED BY A LENEL “MASTER” CERTIFIED PROGRAMMER. DELL EQUIPMENT MUST BE INSTALLED BY A DELL CERTIFIED TECHNICIAN. CISCO EQUIPMENT MUST BE INSTALLED BY A CISCO CERTIFIED TECHNICIAN.
REFER TO ARCHITECTURAL PLANS FOR QUANTITY AND LOCATION OF AUTODOOR PUSH PLATES.
LOCATE ALL POWER SUPPLIES (ACCESS CONTROL, ELECTRIC STRIKE LATCH RETRACTION,
MAGLOCKS, ETC) AT A CENTRAL LOCATION, ADJACENT TO ACCESS CONTROL PANEL IN IRM ROOM.
CONTRACTOR SHALL RECEIVE WRITTEN APPROVAL BY VAMC COR FOR ALL EXCEPTIONS.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
NOT TO SCALE
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:3
P M
E-502
ELECTRICAL DETAILS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00
DISTRIBUTION EQUIPMENT NAMEPLATE DETAIL 1 EXTERIOR EQUIPMENT LIGHT/ RECEPTACLE DETAIL 2 DEVICE AND WALL PLATE DETAIL 3
EQUIPMENT NAMEPLATE DETAIL 4 ACCESS CONTROLLED DOOR TYPE 1 5 ACCESS CONTROLLED DOOR GENERAL NOTES 6
Revisions: Date:
STEEL COLUMN, TYPICAL
EXOTHERMIC CONNECTION
EXOTHERMIC CONNECTION
CONCRETE ENCASED REBAR
BARE COPPER CABLE
EXOTHERMIC CONNECTION
TO GROUND LOOP
BARE COPPER CABLE
1" PVC CONCEALED IN
CONSTRUCTION
NOT TO SCALE
NOT TO SCALE
CONDUIT SCHEDULE
TAG SIZE FROM TO
FOR
' M
IN
IM
U M
FINISHED PAD ELEVATION
RIGID STEEL
CONDUIT
(TYPICAL)
PROVIDE DETECTABLE
UNDERGROUND TAPE.
TAPE SHALL READ
"CAUTION BURIED
ELECTRICAL LINE",
6" WIDE.
PREMIUM FILL
UNDER CONCRETE
SLAB ON GRADE
7.5" 6"
5 64
7.5"
CONCRETE
GENERATOR
SUPPORT PAD
6"
PSG-E
NEW GEN. CUBICLE
GENERATOR MAIN
1-1/2" H1SA
GEN. ACC.
STUB UP
4"
PSG CONTROLS
GENERATOR
CONTROL PANEL
4"
INTERIOR OF
BOILER PLANT
GENERATOR
ENCLOSURE
4"
GENERATOR
OUTPUT
PRIMARY GEN.
ACC. XFMR FEED
FUEL CONTROLS *
GENERATOR
CONTROLS
1-1/2" H1EA
GEN. ACC.
STUB UP
480V GEN. ACC.
PANEL FEED
SPARE SPARE2" SPARE3
DUCT SPACER
* - CONDUIT PROVIDED FOR FUTURE FUEL OIL TRANSFER SYSTEM.
PROVIDE (4) 1.5" INNER DUCT WITH (1) PULLWIRE IN EACH. UP TO (2)
INNER DUCTS MAY BE USED FOR GENERATOR CONTROLS OVERFLOW
WIRING AS NECESSARY. MAINTAIN (2) SPARE INNER DUCT FOR
FUTURE USE.
(4) CONCRETE BRICKS 2"x8"x16"
CONDUIT(S) WITH BELL ENDS
(TYP). SIZE, QUANTITY AND
WIRING AS INDICATED ON
PLANS
CLEAN 3/4" CRUSHED ROCK
GRADE,FEATHER, AND TAMPED
BACKFILL TO CREATE FLUSH
INSTALLATION AND POSITIVE
DRAINAGE AWAY FROM BOX
V A
R
IE
S
PULLBOX (SEE PLANS)
12"
NOT TO SCALE
FINISHED FLOOR
1" EMT CONDUIT WITH CAT 6 CABLE AND PULLWIRE TO
CABLE TRAY (IN SAME ROOM OR IN CORRIDOR AS
SHOWN) ABOVE ACCESSIBLE CEILING. EXTEND CABLE
TO LOCAL TELE/DATA ROOM AND TERMINATE. EXTEND
CONDUIT AS HIGH AS POSSIBLE AND AVOID OTHER
SYSTEMS ABOVE CEILING.
FINISHED CEILING
(GRID OR GYPSUM)
EXTERIOR WALL
(WALL CONSTRUCTION VARIES.
FIELD VERIFY WALL TYPE
PRIOR TO ROUGH-IN)
SURVEILLANCE CAMERA MOUNTED PER
MANUFACTURER'S DOCUMENTATION
(REFER TO PLANS AND SCHEDULES FOR
TYPE)
2-GANG SURFACE MOUNTED BACKBOX
WITH A BLANK COVER FOR SURFACE MO
UNT BISCUIT JACK.
PROVIDE GROMMETTED
OPENING FOR PATCH CORD TO CAMERA.
1" CONDUIT STUB BETWEEN BOXES
WITH CAT6 PATCH CORD TO CAMERA.
INSULATED BUSHING
CAT6 CABLE
EXISTING CABLE TRAY
OR NEW J-HOOKS
SINGLE GANG, FLUSH-MOUNTED,
WEATHER PROOF BACKBOX AT
EXTERIOR CAMERA LOCATION
MOUNTING ARM - COORDINATE
ARM REQUIREMENTS WITH
MOUNTING LOCATION AND
DESIRED COVERAGE. SUBMIT
MOUNTING ARM SELECTIONS WITH
SHOP DRAWINGS FOR REVIEW.
NOT TO SCALE
FINISHED FLOOR
1" EMT CONDUIT WITH CAT 6A CABLE AND PULLWIRE TO
EXISTING CABLE TRAY OR NEW J-HOOKS ABOVE
ACCESSIBLE CEILING. EXTEND CABLE TO LOCAL
TELE/DATA ROOM AND TERMINATE. EXTEND CONDUIT
AS HIGH AS POSSIBLE AND AVOID OTHER SYSTEMS
ABOVE CEILING.
INTERIOR WALL
(WALL
CONSTRUCTION
VARIES. FIELD VERIFY
WALL TYPE PRIOR TO
ROUGH-IN)
SURVEILLANCE CAMERA MOUNTED PER
MANUFACTURER'S DOCUMENTATION
(REFER TO PLANS AND SCHEDULES FOR
TYPE)
2-GANG BACKBOX
WITH A BLANK COVER FOR SURFACE
MOUNT BISCUIT JACK.
PROVIDE GROMMETTED
OPENING FOR PATCH CORD TO CAMERA
INSULATED BUSHING
CAT6A CABLE
EXISTING CABLE TRAY
OR NEW J-HOOKS
NOT TO SCALE
DUCT SMOKE DETECTOR
IN
IT
IA
T
E G
E N
E R
A L S
Y S
T E
M A
L A
R M
IN
IT
IA
T
E S
U P
E R
V
IS
O R
Y S
IG
N
A L
OUTPUT ACTION
IN
IT
IA
T
E T
R O
U B
L E
S
IG
N A
L
C L O
S E
H V
A C
S Y
S T
E M
D A
M P
E R
S
S H
U T
D O
W N
A
IR
H A
N D
L
IN
G U
N
IT
W A
T E
R F
L O
W E
L E
C T
R
IC
B E
L L
AREA PHOTOELECTRIC
SMOKE DETECTOR
MANUAL PULL STATION
FIRE ALARM AC POWER FAILURE
SPRINKLER WATER FLOW
WATER CONTROL
VALVE TAMPER SWITCH
FIRE ALARM SYSTEM OPEN CIRCUIT
FIRE ALARM SYSTEM GROUND FAULT
NOTIFICATION APPLIANCE
CIRCUIT SHORT
NOT TO SCALE
FIRE ALARM SYSTEM LOW BATTERY
FF
F
TS
FS
MAIN FACP
(EXISTING)
SIMPLEX-GRINNELL
4100ES
FIRST FLOOR MAIN
SECURITY OFFICE
CHILLER PLANT
FACP
(EXISTING)
SIMPLEX-GRINNELL
4100ES
MAIN OFFICE
INITIATION
NOTIFICATION
EOL
EOL
FIRE ALARM SYSTEM GENERAL INPUT
OUTPUT MATRIX
FIRE ALARM RISER
X
NEW
NEW
N O
T
IF
Y F
IR
E
D E
P A
R T
M E
N T
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:3
P M
E-503
ELECTRICAL DETAILS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00
TYPICAL STRUCTURAL STEEL GROUNDING DETAIL 2
GENERATOR DUCT BANK DETAIL 4 UNDERGROUND CONCRETE PULLBOX 5
NEW EXTERIOR WALL MOUNTED SURVEILLANCE CAMERA MOUNTING DETAIL 1 INTERIOR CEILING MOUNTED SURVEILLANCE CAMERA MOUNTING DETAIL 3
FIRE ALARM SYSTEM DETAIL 6
Revisions: Date:
1. BRANCH CIRCUIT FROM POWER SOURCE TO VARIABLE SPEED DRIVE (VSD) SHALL BE THHN CONDUCTORS AND ROUTED IN EMT (OR RIGID METAL CONDUIT WHERE REQUIRED PER DRAWINGS OR SPECIFICATIONS).
FLOOR
120VAC
POWER SOURCE
PROVIDE 600V, 20A TOGGLE SWITCH
WITH LED PILOT LIGHT AND LEXAN
COVER. SWITCH SHALL BE LABELED
"CONTROL POWER DISCONNECT".
TEMPERATURE CONTROL WIREWAY
TEMPERATURE CONTROL PANEL
(QUANTITY AS REQUIRED PER TEMPERATURE
CONTROLS CONTRACTOR)
TO LOAD
FROM POWER SOURCE
(REFER TO PLANS FOR
FEEDER/BRANCH CIRCUIT
INFORMATION)
78" AFF MAX.
EMT
P O
W E
R I N
C O
N T
R
L
A D
O U
T
P
W E
R I N
C
N T
R
A D
O U
T
VARIABLE
SPEED DRIVE (VSD)
(SIZED PER MOTOR
HORSEPOWER, TYPICAL.
REFER TO MOTOR
CONTROLLERS
SPECIFICATION SECTION
FOR ADDITIONAL
INFORMATION AND
REQUIREMENTS)
VSD
INPUT POWER, LOAD, AND CONTROL CONDUCTORS SHALL BE ROUTED IN SEPARATE CONDUITS.
LINE AND LOAD WIRING SHALL CROSS PERPENDICULAR WHEN CROSSING IN WIREWAY. PARALLEL WIRING IS
NOT ACCEPTABLE.
LINE AND LOAD GROUND CONDUCTORS SHALL BE SEPARATE. GROUND CONDUCTORS SHALL TERMINATE
TO PROPER LUGS WITHIN VSD.
ALL CONDUCTORS SHALL BE COPPER.
REFER TO POWER AND/OR MECHANICAL CONNECTIONS PLANS FOR INFORMATION REGARDING
BRANCH/FEEDER CIRCUITS FOR EQUIPMENT OR TEMPERATURE CONTROLS POWER.
GENERAL NOTES
1.
2.
3.
4.
5.
3/4" FIREPROOF PLYWOOD OR UNISTRUT FRAME
TOTAL DISTANCE FROM VSF TO MECHANICAL EQUIPMENT BEING SERVED SHALL BE <100 FT
EQUIPMENT LOCATION
FLEXIBLE
WATERTIGHT
CONNECTION.
PROVIDE LOCAL SERVICE DISCONNECTING MEANS MOUNTED ON A GALVANIZED STRUT SUPPORT SYSTEM ADJACENT TO EQUIPMENT. COORDINATE LOCATION WITH DUCTWORK, PIPING, AND OTHER MECHANICAL SYSTEMS TO MAINTAIN ACCESSIBILITY TO SWITCH AS REQUIRED PER NEC. SWITCH SHALL BE FUSED OR
NON-FUSED AS INDICATED ON PLANS AND ONE-LINE DIAGRAM.
DISCONNECTING MEANS SHALL BE PROVIDED WITH (2) AUXILIARY CONTACTS (1) NORMALLY OPEN AND (1) NORMALLY CLOSED. CONTACT SHALL INDICATE SWITCH POSITION AND SHALL BE WIRED TO SHUT DOWN VSD WHEN DISCONNECT IS OFF. CONDUCTORS SHALL BE SHIELDED AND ROUTED BACK TO VFD IN LOAD
CONDUIT OR ROUTED COMPLETE IN A SEPARATE CONDUIT.
PROVIDE PHENOLIC ENGRAVED FACEPLATE. REFER TO EQUIPMENT NAMEPLATE DETAIL FOR ADDITIONAL
INFORMATION.
# CODED NOTES
MINIMUM 6"
BETWEEN
VSDs
4"SQ.
JUNCTION
BOX
4"SQ.
JUNCTION
BOX
WIRING REQUIREMENTS:
6"SQ.
JUNCTION BOX
(MINIMUM)
TYPICAL LOW-VOLTAGE CONTROL POWER
TRANSFORMERS (PER TEMPERATURE
CONTROLS VENDOR REQUIREMENTS)
4"SQ.
JUNCTION
BOX
4"SQ.
JUNCTION
BOX
4"SQ.
JUNCTION
BOX
4"SQ.
JUNCTION
BOX
MECHANICAL
EQUIPMENT
(TYPICAL)
EQUIPMENT SUPPLY
CONNECTION POINT
LOCAL SERVICE
DISCONNECTING
MEANS
VSD/CONTROL LOCATION
NOT TO SCALE
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:4
P M
E-504
ELECTRICAL DETAILS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00
GROUP MOUNTED VSD DETAIL 1
Revisions: Date:
GENERAL NOTES:
1. COORDINATE LABELING SEQUENCE AND FORMAT WITH VA OIT DEPT.
POSITION
JACK
TYPE
JACK
COLOR
CABLE
TYPE
CABLE
COLOR
CAT 6A
RJ 45
ORANGE (WAP)
GREEN (CAMERA)
CAT 6A
PROVIDE SURFACE
MOUNT BOX WITH
DUAL PORT MOUNTED
ABOVE FINISHED
CEILING.
N/AN/AN/A
XXX-XX-XX
PORT ID
XXX-XX-XX
PORT NUMBER
PATCH PANEL IDENTIFIER
TR ROOM IDENTIFIER
POSITION
JACK
TYPE
JACK
COLOR
CABLE
TYPE
CABLE
COLOR
CAT 6A
RJ 45
BLUE CAT 6A BLUE
1-PORT STAINLESS
STEEL FACEPLATE
WITH PHONE
MOUNTING PEGS
XXX-XX-XX PORT ID
XXX-XX-XX
PORT NUMBER
PATCH PANEL IDENTIFIER
TR ROOM IDENTIFIER
TYPICAL WALLPHONE FACEPLATETYPICAL TCO FACEPLATE
POSITION
JACK
TYPE
JACK
COLOR
CABLE
TYPE
CABLE
COLOR
3 BLANK N/A N/A N/A
CAT 6A
RJ 45
BLUE CAT 6A BLUE
CAT 6A
RJ 45
BLUE CAT 6A
2*
BLUE
XXX-XX-XX
4-PORT IVORY
WALLPLATE WITH
LABEL WINDOWS
XXX-XX-XX
TYPICAL WIRELESS ACCESS POINT /
SURVEILLANCE CAMERA FACEPLATE
PORT ID
XXX-XX-XX
PORT NUMBER
PATCH PANEL IDENTIFIER
TR ROOM IDENTIFIER
NOT TO SCALE
CAT 6A
RJ 45
PURPLE CAT 6A PURPLE
* PROVIDE PORT IN POSITION #2 ONLY WHERE NECESSARY
TO SUPPORT A PANIC ALARM BUTTON AT THE LOCATION.
ORANGE (WAP)
GREEN (CAMERA)
N/A
A F
F U
N L E
S S
O T
H E
R W
IS
E
N O
T E
D
FINISHED FLOOR
1-1/2" CONDUIT
INSULATED BUSHING
5" SQ. x 2-7/8"D BACK
BOX WITH SINGLE
GANG PLASTER RING.
NOT TO SCALE
18" AFF UNLESS
OTHERWISE
NOTED
1-1/2" CONDUIT
INSULATED BUSHING
5" SQ. x 2-7/8"D BACK
BOX WITH SINGLE
GANG PLASTER RING.
A B
O V
E C
O U
N T
E R
(I N
-L
IN
E W
IT
H
E
E
C T
R
IC
A L R
E C
E P
T A
C L E
COUNTER
1-1/2" CONDUIT
INSULATED BUSHING
5" SQ. x 2-7/8"D BACK
BOX WITH SINGLE
GANG PLASTER RING.
ACCESSIBLE CEILING
WALL PHONE TYPICAL TCO TYPICAL TCO "ABOVE COUNTER"
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:4
P M
E-505
TECHNOLOGY DETAILS CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00
TYPICAL TECHNOLOGY FACEPLATE DETAILS 1
TYPICAL TECHNOLOGY ROUGH-IN DETAIL 2
Revisions: Date:
INSTRUCTIONAL EQUIPMENT PLACARD:
BASIS OF DESIGN EQUIPMENT NOTES:
EPM
EPM
EPM
NEW SUBSTATION 'SS-CP1'
4000A, 13.2KV:480/277V-3∅-4W
NEW SUBSTATION 'SS-CP2'
4000A, 13.2KV:480/277V-3∅-4W
DISTRIBUTION
BREAKERS
TIE BREAKER
GROUND
FAULT
SCHEME
PRIMARY SWITCH
TRANSFORMER
FEEDER
TERMINATIONS
ELECTRIC
POWER METER
KEY
INTERLOCKING
TVSS
NAMEPLATE
ENCLOSURE
MAIN BUS
MAIN BREAKER
DISTRIBUTION
BREAKERS
GROUND
FAULT
SCHEME
PRIMARY SWITCH
TRANSFORMER
FEEDER
TERMINATIONS
ELECTRIC
POWER METER
KEY
INTERLOCKING
TVSS
NAMEPLATE
ENCLOSURE
MAIN BUS
MAIN BREAKER
EPM
PRIMARY
DUPLEX
PRIMARY
DUPLEX
14.75"W 14.75"W
DRY-TYPE TRANSFORMER
96"W 36"W 22"W 36"W
BREAKER
BREAKER
BREAKER
EPM
EPM
EPM
TVSS PROVISION
EPM
DRY-TYPE TRANSFORMER
96"W 36"W 22"W 36"W
BREAKER
PROVISION
BREAKER
EPM
EPM
TVSS PROVISION
PRIMARY
DUPLEX
PRIMARY
DUPLEX
14.75"W 14.75"W
EPM
K
K K K
K K K K
EPM
K
A1 A1
A1
A2
A2
A3
A3 A3 A3 B1 B1 B2 B3 B3 B3
B1
B2
B3
MB1
4000AF
4000AT
100%
250E
4000A, 480/277V-3∅-4W, SILVER-PLATED COPPER AT 1000AMPS PER SQUARE INCH - MIN. 65,000A RMS SYMMETRICAL SHORT CIRCUIT BRACING - FULL LENGTH GROUND BUS. EXTEND BUS THROUGH
ENTIRE SECTION TO ALLOW FOR BUS CONNECTION TO FUTURE DISTRIBUTION SECTIONS.
CH1
1600AF
1000AT
100%
CH2
1600AF
1000AT
100%
A1
800AF
800AT
100%
A2 1600A
TIE
4000AF
4000AT
100%
MB2
4000AF
4000AT
100%
CH3
1600AF
1000AT
100%
FUTURE CH4
1600A
B1
800AF
800AT
100%
B2 1600A
N.O.
PROVIDE (8) 17"x22" ENGRAVED PLACARDS FOR SWITCHGEAR BREAKER INSTRUCTIONS. CONTRACTOR SHALL PROVIDE ITEMS AS FOLLOWS:
1.
2.
3.
4.
ENGRAVED 1/4" MICARTA PLACARD MOUNTED ON EQUIPMENT WITH SCREWS.
ASSUME 1000 CHARACTERS/SYMBOLS PER INSTRUCTIONAL PLACARD. CHARACTER/SYMBOLS SHALL BE ASSUMED TO BE OF VARIOUS
HEIGHTS AND STYLES.
VERIFY EXACT SIZE, TEXT STYLE, COLOR AND MOUNTING LOCATION OF INSTRUCTIONAL PLACARDS WITH VAMC COTR PRIOR TO
ORDERING.
INSTRUCTION PLACARD WORDING SHALL BE PROVIDED BY THE VAMC THROUGH THE COMMISSIONING PROCESS. CONTRACTOR SHALL PROVIDE FINAL ENGRAVED PLACARDS WITHIN (4) WEEKS OF RECEIVING FINAL WORDING.
250E 250E250E
600A-15,000V - PRIMARY DUPLEX SWITCH, MAXIMUM 36"W x 92"H x 62"D PER SECTION, 25KAIC, 150E-
RATED CURRENT LIMITING FUSES (ONE PER INCOMING LINE). MANUAL OPERATION, INDOOR
ENCLOSURE, PROVISIONS FOR PADLOCKING FULL HEIGHT MAIN DOOR WITH INSPECTION WINDOW, DOOR AND SWITCH INTERLOCK. PROVIDE KEY INTERLOCKING SUCH THAT ONLY (1) PRIMARY
FEEDER CAN BE CLOSED AT A TIME. BASIS OF DESIGN DIMENSIONS: 14.75"L x 37.25"D x 90"H
1.
2.
DIMENSIONS ARE PROVIDED FOR REFERENCE. SQUARE D PZ4 SWITCHGEAR BY SCHEIDER ELECTRIC USED AS A BASIS OF DESIGN.
WHERE SUBMITTED DIMENSIONS DIFFER FROM THE BASIS OF DESIGN, CONTRACTOR SHALL SUBMIT A NEW EQUIPMENT LAYOUT FOR REVIEW AND APPROVAL. LAYOUT SHALL BE SUBMITTED ALONG WITH EQUIPMENT SHOP DRAWINGS. EQUIPMENT SHALL NOT BE PURCHASED UNTIL LAYOUT IS APPROVED. EQUIPMENT MAY BE REJECTED IF PHYSICAL DIMENSIONS EXCEED BASIS-OF-DESIGN.
NEMA 1, SELF SUPPORTING STRUCTURE - FRONT AND REAR ACCESS SWITCHBOARD. BUILT TO UL
1558 STANDARDS. PROVIDE FRONT HINGED DOORS FOR POWER BREAKERS AND METERING
COMPARTMENTS. REAR COMPARTMENTS SHALL HAVE BOLTED COVERS. PROVIDE UNIT BREAKER
LIFT FOR DRAW-OUT BREAKERS. BASIS OF DESIGN DIMENSIONS: 92"H x 75.25"D, MAIN/TIE SECTIONS:
36"W, DISTRIBUTION SECTIONS: 22"W.
2000kVA, 13,200V DELTA PRIMARY, 480/277V-3Ø-4W WYE SECONDARY, DRY-TYPE, FORCED-AIR COOLED (133% OVERCURRENT RATING), 150°C RISE RATING, 5.75% MIN IMPEDANCE. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. BASIS OF DESIGN DIMENSIONS: 96"L x 60"D x
100"H, 12,400LB.
DRAW-OUT, LOW-VOLTAGE, 4000A-3P, POWER CIRCUIT BREAKER WITH DIGITAL, SOLID STATE
TRIP UNIT (100% RATED). TRIP UNIT SHALL HAVE FIELD INSTALLABLE, FRONT-MOUNTED RATING
PLUG AND ADJUSTABLE LONG-TIME, SHORT-TIME, INSTANTANEOUS, AND GROUND FAULT
SETTINGS. PROVIDE KEY INTERLOCKING DEVICE AND CONNECT PER ONE-LINE DIAGRAM.
DRAW-OUT, LOW-VOLTAGE, POWER CIRCUIT BREAKER WITH DIGITAL, SOLID STATE TRIP UNIT (100% RATED). FRAME AND TRIP UNIT SIZE AS INDICATED. TRIP UNIT SHALL HAVE FIELD INSTALLABLE, FRONT-MOUNTED RATING PLUG AND ADJUSTABLE LONG-TIME, SHORT-TIME, INSTANTANEOUS, AND
GROUND FAULT SETTINGS.
FURNISH AND INSTALL NEW CT'S FOR EACH BREAKER/PROVISION AND A COMMON SET OF PT'S TO
SUPPLY A COMMON LINE-SIDE VOLTAGE INPUT TO ALL METERS. PROVIDE NEW EPM'S FOR EACH BREAKER. MATCH EXISTING FACILITY TYPE(SCHNEIDER POWERLOGIC - PM8244) . CONNECT METERS
TO EXISTING FACILITIES MANAGEMENT SYSTEM.
PROVIDE INTEGRAL TRANSIENT VOLTAGE SURGE SUPPRESSION FOR 480/277V DISTRIBUTION. REFER
TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
ALL FEEDER TERMINATIONS SHALL BE MADE WITH 2-HOLE, LONG BARRELL COMPRESSION LUGS.
REFER TO POWER DISTRIBUTION ONE-LINE DIAGRAM FOR FEEDER SIZES.
PROVIDE GROUND FAULT RELAY SYSTEM FOR MAIN-TIE-MAIN BREAKER SCHEME (SIMILAR TO
MAGNUM DS MOD - RESIDUAL GROUND FAULT WITH ZONE INTERLOCKING). PROVIDE AUXILIARY
CONTACTS ON MAIN AND TIE BREAKERS. PROVIDE CT ON NEUTRAL OF ALL BREAKERS FOR NEUTRAL
CURRENT SENSING.
PROVIDE (2) FORM C AUX. CONTACTS FOR TIE BREAKER. PROVIDE 3/4" CONDUIT - 6#14 FROM TIE
BREAKER TO A LOCAL TEMPERATURE CONTROL PANEL TO MONITOR POSITION. PROVIDE KEY
INTERLOCKING DEVICE AND CONNECT PER ONE-LINE DIAGRAM.
ENGRAVED PHENOLIC NAMEPLATES FOR ALL BREAKERS, METERS, ETC. PROVIDE PHENOLIC MIMIC BUS FOR ALL SWITCHGEAR BUS, BREAKERS, METERING, ETC. VERIFY EXACT SIZE, TEXT STYLE, COLOR AND MOUNTING LOCATION WITH VAMC COR PRIOR TO ORDERING.
PROVIDE MANUAL KEY INTERLOCKING DEVICE BETWEEN (2) MAIN BREAKERS AND (1) TIE BREAKER.
SUBMIT MECHANICAL INTERLOCKING SCHEME WITH SHOP DRAWINGS FOR APPROVAL.
4000A, 480/277V-3∅-4W, SILVER-PLATED COPPER AT 1000AMPS PER SQUARE INCH - MIN. 65,000A RMS SYMMETRICAL SHORT CIRCUIT BRACING - FULL LENGTH GROUND BUS. EXTEND BUS THROUGH
ENTIRE SECTION TO ALLOW FOR BUS CONNECTION TO FUTURE DISTRIBUTION SECTIONS.
600A-15,000V - PRIMARY DUPLEX SWITCH, MAXIMUM 36"W x 92"H x 62"D PER SECTION, 25KAIC, 150E-
RATED CURRENT LIMITING FUSES (ONE PER INCOMING LINE). MANUAL OPERATION, INDOOR
ENCLOSURE, PROVISIONS FOR PADLOCKING FULL HEIGHT MAIN DOOR WITH INSPECTION WINDOW, DOOR AND SWITCH INTERLOCK. PROVIDE KEY INTERLOCKING SUCH THAT ONLY (1) PRIMARY
FEEDER CAN BE CLOSED AT A TIME. BASIS OF DESIGN DIMENSIONS: 14.75"L x 37.25"D x 90"H
NEMA 1, SELF SUPPORTING STRUCTURE - FRONT AND REAR ACCESS SWITCHBOARD. BUILT TO UL
1558 STANDARDS. PROVIDE FRONT HINGED DOORS FOR POWER BREAKERS AND METERING
COMPARTMENTS. REAR COMPARTMENTS SHALL HAVE BOLTED COVERS. PROVIDE UNIT BREAKER
LIFT FOR DRAW-OUT BREAKERS. BASIS OF DESIGN DIMENSIONS: 92"H x 75.25"D, MAIN/TIE SECTIONS:
36"W, DISTRIBUTION SECTIONS: 22"W.
2000kVA, 13,200V DELTA PRIMARY, 480/277V-3Ø-4W WYE SECONDARY, DRY-TYPE, FORCED-AIR COOLED (133% OVERCURRENT RATING), 150°C RISE RATING, 5.75% MIN IMPEDANCE. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. BASIS OF DESIGN DIMENSIONS: 96"L x 60"D x
100"H, 12,400LB.
DRAW-OUT, LOW-VOLTAGE, 4000A-3P, POWER CIRCUIT BREAKER WITH DIGITAL, SOLID STATE
TRIP UNIT (100% RATED). TRIP UNIT SHALL HAVE FIELD INSTALLABLE, FRONT-MOUNTED RATING
PLUG AND ADJUSTABLE LONG-TIME, SHORT-TIME, INSTANTANEOUS, AND GROUND FAULT
SETTINGS. PROVIDE KEY INTERLOCKING DEVICE AND CONNECT PER ONE-LINE DIAGRAM.
DRAW-OUT, LOW-VOLTAGE, POWER CIRCUIT BREAKER WITH DIGITAL, SOLID STATE TRIP UNIT (100% RATED). FRAME AND TRIP UNIT SIZE AS INDICATED. TRIP UNIT SHALL HAVE FIELD INSTALLABLE, FRONT-MOUNTED RATING PLUG AND ADJUSTABLE LONG-TIME, SHORT-TIME, INSTANTANEOUS, AND
GROUND FAULT SETTINGS.
FURNISH AND INSTALL NEW CT'S FOR EACH BREAKER/PROVISION AND A COMMON SET OF PT'S TO
SUPPLY A COMMON LINE-SIDE VOLTAGE INPUT TO ALL METERS. PROVIDE NEW EPM'S FOR EACH BREAKER. MATCH EXISTING FACILITY TYPE(SCHNEIDER POWERLOGIC - PM8244) . CONNECT METERS
TO EXISTING FACILITIES MANAGEMENT SYSTEM.
PROVIDE INTEGRAL TRANSIENT VOLTAGE SURGE SUPPRESSION FOR 480/277V DISTRIBUTION. REFER
TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
ALL FEEDER TERMINATIONS SHALL BE MADE WITH 2-HOLE, LONG BARRELL COMPRESSION LUGS.
REFER TO POWER DISTRIBUTION ONE-LINE DIAGRAM FOR FEEDER SIZES.
PROVIDE GROUND FAULT RELAY SYSTEM FOR MAIN-TIE-MAIN BREAKER SCHEME (SIMILAR TO
MAGNUM DS MOD - RESIDUAL GROUND FAULT WITH ZONE INTERLOCKING). PROVIDE AUXILIARY
CONTACTS ON MAIN AND TIE BREAKERS. PROVIDE CT ON NEUTRAL OF ALL BREAKERS FOR NEUTRAL
CURRENT SENSING.
ENGRAVED PHENOLIC NAMEPLATES FOR ALL BREAKERS, METERS, ETC. PROVIDE PHENOLIC MIMIC BUS FOR ALL SWITCHGEAR BUS, BREAKERS, METERING, ETC. VERIFY EXACT SIZE, TEXT STYLE, COLOR AND MOUNTING LOCATION WITH VAMC COR PRIOR TO ORDERING.
PROVIDE MANUAL KEY INTERLOCKING DEVICE BETWEEN (2) MAIN BREAKERS AND (1) TIE BREAKER.
SUBMIT MECHANICAL INTERLOCKING SCHEME WITH SHOP DRAWINGS FOR APPROVAL.
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:5
P M
E-506
SUBSTATION DETAIL AND GENERAL NOTES CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00
NOT TO SCALE
SUBSTATION DETAIL AND GENERAL NOTES 1
Revisions: Date:
FEEDER SCHEDULE - COPPER (NEC TABLE 310.15(B)16))
DESIGNATION CONDUIT AND CONDUCTOR SIZEDESIGNATION CONDUIT AND CONDUCTOR SIZE
20N
30N
40N
60N
70N
100N
125N
150N
225N
175N
200N
250N
300N
400N
500N
600N
800N
1000N
1200N
1600N
2000N
2500N
3000N
4000N
3/4"C - 4#12 AND 1#12 EG
3/4"C - 4#10 AND 1#10 EG
1"C - 4#8 AND 1#10 EG
1"C - 4#6 AND 1#10 EG
1 1/2"C - 4#4 AND 1#8 EG
1 1/2"C - 4#2 AND 1#8 EG
2"C - 4#1/0 AND 1#6 EG
2"C - 4#1 AND 1#6 EG
2"C - 4#2/0 AND 1#6 EG
2 1/2"C - 4#3/0 AND 1#6 EG
2 1/2"C - 4#4/0 AND 1#4 EG
2 1/2"C - 4#250 AND 1#4 EG
3"C - 4#350 AND 1#4 EG
4"C - 4#500 AND 1#2 EG
(2) 2 1/2"C - 4#250 AND 1#2 EG
(2) 3"C - 4#350 AND 1#1 EG
(2) 4"C - 4#500AND 1#1/0 EG
(3) 4"C - 4#400AND 1#2/0 EG
(4) 4"C - 4#350 AND 1#3/0 EG
(6) 4"C - 4#500 AND 1#250 EG
(5) 4"C - 4#500 AND 1#4/0 EG
(7) 4"C - 4#500 AND 1#350 EG
(8) 4"C - 4#500 AND 1#500 EG
(11) 4"C - 4#500 AND 1#500 EG
3/4"C - 3#12 AND 1#12 EG
3/4"C - 3#10 AND 1#10 EG
1"C - 3#8 AND 1#10 EG
1"C - 3#6 AND 1#10 EG
1 1/2"C - 3#4 AND 1#8 EG
1 1/2"C - 3#2 AND 1#8 EG
2"C - 3#1/0 AND 1#6 EG
2"C - 3#1 AND 1#6 EG
2"C - 3#2/0 AND 1#6 EG
2 1/2"C - 3#3/0 AND 1#6 EG
2 1/2"C - 3#4/0 AND 1#4 EG
2 1/2"C - 3#250 AND 1#4 EG
3"C - 3#350 AND 1#4 EG
3"C - 3#500 AND 1#2 EG
(2) 2 1/2"C - 3#250 AND 1#2 EG
(2) 3"C - 3#350 AND 1#1 EG
(2) 4"C - 3#500AND 1#1/0 EG
(3) 4"C - 3#400 AND 1#2/0 EG
(4) 4"C - 3#350 AND 1#3/0 EG
(6) 4"C - 3#500 AND 1#250 EG
(5) 4"C - 3#500 AND 1#4/0 EG
225A
EXISTING EQUIPMENT, FEEDER/CIRCUIT - TO BE DEMOLISHED
NEW FEEDER/CIRCUIT AND FEEDER TAG
EXISTING EQUIPMENT, FEEDER/CIRCUIT - TO REMAIN
EQUIPMENT OUTLINE
BOLTED STATIONARY CIRCUIT BREAKER - 3-POLE UNLESS OTHERWISE NOTED
GF - EQUIP BREAKER WITH GROUND FAULT TRIP
GFA - EQUIP BREAKER WITH GROUND FAULT ALARM
LSI - EQUIP BREAKER WITH ADJUSTABLE LONG, SHORT AND INSTANTANEOUS
SETTINGS
400A-3Ø-4W
FUTURE EQUIPMENT, FEEDER/CIRCUIT - N.I.C.
NAME
POWER DISTRIBUTION ONE-LINE LEGEND
X
XR
NEW
1600AF
DRAW OUT CIRCUIT BREAKER - 3-POLE UNLESS OTHERWISE NOTED
GF - EQUIP BREAKER WITH GROUND FAULT TRIP
GFA - EQUIP BREAKER WITH GROUND FAULT ALARM
LSI -
NAME
RATING
PRI:SEC
VOLTAGE
TEMPERATURE
RISE
VOLTAGE
MAIN
AMPS
NAME
PANELBOARD.
REFER TO PANELBOARD SCHEDULES AND SPECIFICATIONS FOR ADDITIONAL INFORMATION.
TRANSFORMER. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
AF - AMP FRAME
AT - AMP TRIP
LSIG - EQUIP BREAKER WITH ADJUSTABLE LONG, SHORT AND INSTANTANEOUS
SETTINGS AND GROUND FAULT.
EQUIP BREAKER WITH ADJUSTABLE LONG, SHORT AND INSTANTANEOUS
SETTINGS
LSIG - EQUIP BREAKER WITH ADJUSTABLE LONG, SHORT AND INSTANTANEOUS
SETTINGS AND GROUND FAULT.
800 AT
GROUNDING TERMINATION POINT FOR AN EQUIPMENT GROUNDING CONDUCTOR. CONNECTION
SHALL BE MADE BY BONDING THE EQUIPMENT GROUNDING CONDUCTOR TO THE GROUNDED
SERVICE CONDUCTOR AND THE GROUNDING ELECTRODE CONDUCTOR.
AF - AMP FRAME
AT - AMP TRIP
NAME NAME
XXHPXXHP
VFD
NAME
XXHP
EQUIPMENT (MOTOR, AIR-HANDLING UNIT, PACKAGED EQUIPMENT, ETC.) AS INDICATED. VFD, DISCONNECT, OR STARTER SHOWN WITHIN EQUIPMENT IS PROVIDED WITH EQUIPMENT.
HORSEPOWER SHOWN WHERE AVAILABLE FOR SINGLE-MOTOR APPLICATIONS. CONNECT
EQUIPMENT COMPLETE TO FEEDER INDICATED PER MANUFACTURER'S WIRING DIAGRAMS.
NAME
XXHP
DISCONNECT SWITCH - 600V RATED, PROVIDE AMPERAGE AS INDICATED. COORDINATE WITH
EQUIPMENT AS SUBMITTED, REVIEWED, AND APPROVED. ADJUST RATING AS REQUIRED. CONNECT
COMPLETE TO FEEDER AND EQUIPMENT INDICATED PER MANUFACTURER'S WIRING DIAGRAMS.
XXA
RATED
VFD
VARIABLE FREQUENCY DRIVE - REFER TO MOTOR CONTROLLER SPECIFICATIONS FOR ADDITIONAL
INFORMATION AND WORK REQUIREMENTS. COORDINATE WITH EQUIPMENT AS SUBMITTED,
REVIEWED, AND APPROVED. ADJUST RATING AS REQUIRED. CONNECT COMPLETE TO FEEDER AND
EQUIPMENT INDICATED PER MANUFACTURER'S WIRING DIAGRAMS.
COMBINATION MAGNETIC MOTOR STARTER AND DISCONNECTING MEANS - MINIMUM SIZE NEMA 0.
COORDINATE WITH EQUIPMENT AS SUBMITTED, REVIEWED, AND APPROVED. ADJUST RATING AS
REQUIRED. - REFER TO MOTOR CONTROLLER SPECIFICATIONS FOR ADDITIONAL INFORMATION AND
WORK REQUIREMENTS. CONNECT COMPLETE TO FEEDER AND EQUIPMENT INDICATED PER
MANUFACTURER'S WIRING DIAGRAMS.
1.
2.
3.
4.
FOR #10 AWG CONDUCTORS AND SMALLER, JOINTS AND SPLICES SHALL BE MADE WITH SCREW-ON WIRE CONNECTORS. CONNECTOR
JOINTS SHALL BE INSULATED WITH TAPE.
FOR #8 AWG AND LARGER WIRES SHALL BE MADE WITH COMPRESSION TYPE MECHANICAL CONNECTORS AND INSULATED WITH HEAT
SHRINK TUBING TO A 600V INSULATION LEVEL.
LABEL BOX COVER WITH SOURCE, CIRCUIT, AND LOAD INFORMATION. LABEL SHALL BE MADE WITH PERMANENT MARKER. STICK ON
LABELS ARE NOT ACCEPTABLE.
VERIFY PHASE ROTATION OF ALL LOADS PRIOR TO STARTING. CREATE REPORT OF PHASE ROTATION FOR EACH LOAD WITH 1) EXISTING PHASE ROTATION, 2) RECONNECTED PHASE ROTATION, 3) TIME AND DATE OF PHASE ROTATION TEST, 4) IDENTIFICATION INFORMATION
OF TECHNICIAN VERIFYING PHASE ROTATION.
JOINTS AND SPLICES SPECIFICATION
CONDUIT ROUTING INDICATED ON DRAWINGS IS FOR REFERENCE ONLY, UNLESS OTHERWISE NOTED. CONTRACTOR IS RESPONSIBLE FOR SUBMITTING CONDUIT ROUTING COORDINATION DRAWINGS WITH ELECTRICAL EQUIPMENT SUBMITTAL FOR APPROVAL. ROUTING DRAWINGS SHALL INCLUDE FIELD VERIFIED ROUTING, BENDS, PULLBOXES, CONDUIT BODIES, PENETRATIONS, ETC. CONTRACTOR SHALL INCLUDE EXISTING CONDITIONS WHERE NECESSARY TO CONVEY ROUTING INFORMATION, MAINTAIN NEC REQUIRED ACCESSIBILITY TO ALL EXISTING PULLBOXES, JUNCTION BOXES, ETC. TO REMAIN. ELECTRICAL EQUIPMENT SUBMITTAL WILL NOT BE APPROVED WITHOUT CONDUIT ROUTING SHOP
DRAWINGS.
CONDUIT ROUTING GENERAL NOTE:
MECHANICAL KEY INTERLOCKING DEVICE. REFER TO SUBSTATION DETAILS FOR ADDITIONAL
INFORMATION.
K
VFD - NON-BYPASS VFD
VFD - BYPASS VFDB
VFD - NON-BYPASS VFD
VFD - BYPASS VFDB
SHUTDOWN GENERAL NOTE
ELECTRICAL CONTRACTOR SHALL OBTAIN WRITTEN APPROVAL FROM FACILITY FOR ALL SCHEDULED SHUTDOWNS A MINIMUM OF (60) DAYS FOR ALL DAYTIME WORK FOR ALL WEEKENDS AND WEEKDAYS, (14) DAYS PRIOR TO ACTUAL SHUTDOWN FOR ALL NIGHTTIME WORK. CONTRACTOR SHALL COORDINATE WITH FACILITY WHICH CRITICAL LOADS MUST RECEIVED TEMPORARY POWER, IF ANY. CONDUCT SHUTDOWNS AFTER TYPICAL BUSINESS HOURS. CONTRACTOR SHALL SUBMIT AT A MINIMUM THE FOLLOWING INFORMATION FOR A
REQUESTED ELECTRICAL POWER SYSTEM SHUTDOWN.
• IDENTIFY ALL CONNECTED LOADS AFFECTED BY THE SHUTDOWN. CONTRACTOR SHALL VERIFY WITH FACILITY'S MAINTENANCE DEPARTMENT THE ACCURACY OF EXISTING PANELBOARD CONNECTIONS
DIRECTORY.
• PROPOSED DATE, TIME, AND ESTIMATED DURATION OF THE SHUTDOWN.
• METHOD OF TEMPORARY FEEDING OF CRITICAL LOADS THAT MUST BE MAINTAINED DURING SHUTDOWN.
CONTRACTOR SHALL MINIMIZE POTENTIAL SHUTDOWNS OF EQUIPMENT BY FURNISHING AND INSTALLING NEW FEEDERS PRIOR TO SHUTDOWN WHENEVER POSSIBLE AND UTILIZING SHUTDOWNS FOR CUT-OVER TO NEW
FEEDER.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING FIRE WATCH OF ENTIRE FACILITY FOR ANY FIRE ALARM OR
SPRINKLER SHUTDOWN GREATER THAN (4) HOURS.
1.
2.
3.
S
59459
M.P. LONG
R
E
S
O F
I
R
G E
NO
I
S
P
E
N
E
D
ERT
L EA
E I N
G
R
T
S
TEA
H
F OO
IO
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANTS
321 4 5 6 7 8 9 10
757-15-102
7850 Freeway Circle
440.243.2000 t
Cleveland, OH 44130
440.243.3305 f
Arch. Proj. No.:
20045
C R e v it L o c a l F ile s \2
F
F H
C F
R
C h ri s to p h e r.
P
.C a m p b e ll.
rv t
/6 /2
:4
:5
P M
E-600
ELECTRICAL ONE LINE LEGEND AND GENERAL
NOTES
CONSTRUCT CHILLER PLANT
420 N. JAMES ROAD, COLUMBUS,
OHIO 43219
05/06/2022 CPC LV
BID & CONSTRUCTION
18902.00
PRIORITY 1 ATS – AUTOMATIC TRANSFER SWITCH THAT SERVES NFPA 110 EMERGENCY LOADS THAT ARE REQUIRED TO BE
ENERGIZED WITHIN 10 SECONDS OF A LOSS OF POWER PER NFPA 110.
PRIORITY 2 ATS – AUTOMATIC TRANSFER SWITCH THAT SERVES LEGALLY REQUIRED STANDBY LOADS THAT ARE REQUIRED TO BE
ENERGIZED WITHIN 60 SECONDS OF A LOSS OF POWER PER NFPA 110.
THE SYSTEM – THE RUSSELECTRIC PARALLELING SYSTEM
BAS – BUILDING AUTOMATION SYSTEM
PSG-N – THE NORMAL RUSSELECTRIC PARALLELING SWITCHGEAR
PSG-E – THE EMERGENCY RUSSELECTRIC PARALLELING SWITCHGEAR
U1 – THE MAIN UTILITY BREAKER IN PSG-N
A1, A2, B1, B2 – DISTRIBUTION BREAKERS IN PSG-N.
T1, T2, AND T3 – RUSSELECTRIC PARALLELING SWITCHGEAR TIE BREAKERS
NP1 AND NP2 – MAIN PRIMARY CIRCUIT BREAKERS ON SUBSTATION NPSS1
CP1N AND CP2N – NORMAL MEDIUM-VOLTAGE PRIMARY SWITCHES ON SUBSTATIONS SS-CP1 AND SS-CP2
CP1E AND CP2E – EMERGENCY MEDIUM-VOLTAGE PRIMARY SWITCHES ON SUBSTATIONS SS-CP1 AND SS-CP2
CP1M AND CP2M – MAIN 480V SECONDARY CIRCUIT BREAKERS ON SUBSTATIONS SS-CP1 AND SS-CP2
CPT – 480V TIE BREAKER BETWEEN SUBSTATIONS SS-CP1 AND SS-CP2
INSTALLATION AND UTILITY OPERATION - NORMAL SEQUENCE
THE NORMAL OPERATING MODE WHEN UTILITY POWER IS AVAILABLE.
A. MODIFY EXISTING B1 AND A1 SUCH THAT BOTH ARE NORMALLY CLOSED TO PROVIDE MEDIUM-VOLTAGE SUPPLY TO
SUBSTATIONS NPSS1, SS-CP1, AND SS-CP2.
1. PER RECORD DRAWINGS PROVIDED BY MANUFACTURER, NP1 AND NP2 ARE MECHANICALLY INTERLOCKED SO THAT
ONLY (1) BREAKER MAY BE CLOSED AT ANY GIVEN TIME.
a. AUTHORIZED PERSONNEL MUST MANUALLY OPEN AND CLOSE NP1 AND NP2 AS A PAIR TO ENERGIZE
SUBSTATION SHOULD THE PRIMARY FEEDER BECOME DE-ENERGIZED.
B. MECHANICALLY INTERLOCK CP1N AND CP1E SUCH THAT ONLY (1) SWITCH MAY BE CLOSED AT ANY GIVEN TIME.
C. MECHANICALLY INTERLOCK CP2N AND CP2E SUCH THAT ONLY (1) SWITCH MAY BE CLOSED AT ANY GIVEN TIME.
D. MECHANICALLY INTERLOCK CP1M AND CP2M WITH CPT IN A MAIN-TIE-MAIN SEQUENCE WITH DOUBLE-ENDED GROUND
FAULT PROTECTION SCHEME.
E. REMAINING SYSTEM UTILITY POWER OPERATION SHALL BE UNCHANGED.
EMERGENCY SEQUENCE #1
THE EMERGENCY SEQUENCE WHEN UTILITY POWER IS UNAVAILABLE TO A SUBSET OF TRANSFER SWITCHES AS SENSED AT THE
TRANSFER SWITCH LEVEL.
A. PER STANDARD PROGRAMMING, IF AN ATS SENSES LOSS OF PRIMARY SOURCE, THE START SIGNAL IS SENT TO ALL
GENERATORS.
1. CLOSE THE FIRST GENERATOR TO REACH RATED VOLTAGE AND FREQUENCY TO THE PSG-E BUS.
2. ENERGIZE PRIORITY 1 ATSs.
3. ENERGIZE PRIORITY 2 ATSs.
4. ENERGIZE REMAINING NON-ESSENTIAL ATSs PER PRIORITY SCHEDULE AND AS ALLOWED PER RUSSELECTRIC
SMART LOADING MANAGEMENT SYSTEM.
a. INHIBIT TRANSFER SWITCHES FROM RETURNING TO PRIMARY (NORMAL) SOURCE UNTIL RUSSELECTRIC
PARALLELING EQUIPMENT DETERMINES THAT UTILITY IS AVAILABLE.
5. SYNCHRONIZE AND CLOSE ANY REMAINING GENERATORS TO THE PSG-E BUS AT ANY POINT, IF AND WHEN THEY
REACH RATED VOLTAGE AND FREQUENCY.
B. U1 WILL REMAIN CLOSED AND ATSs THAT MAINTAIN THE PRIMARY POWER SOURCE REMAIN ON THEIR PRIMARY FEEDER
AND CONTINUE TO OPERATE AS NORMAL.
C. THE SYSTEM CONTINUOUSLY MONITORS VOLTAGE AT U1.
1. OPEN A1, B1, AND A2 IF THE SYSTEM DETERMINES THAT POWER HAS BEEN LOST TO THE ENTIRE FACILITY AT U1.
a. AFTER 15 MINUTES OF LOAD STABILIZATION, MEASURE THE GENERATOR PLANT TOTAL LOAD.
1. T2 AND T3 WILL REMAIN OPEN IF LOAD EXCEEDS 2400KVA
2. CLOSE B1, A1, T2, AND T3, IF LOAD IS LESS THAN OR EQUAL TO 2400KVA.
b. SEND A CONTACT CLOSURE FROM THE SYSTEM TO THE BAS THAT CHILLER PLANT WILL BE OPERATING ON
THE EMERGENCY SEQUENCE.
1. (1) CHILLER AND ASSOCIATED PUMP EQUIPMENT SHALL BE PERMITTED TO START.
2. SYSTEM SHALL MONITOR CHILLED WATER DEMAND.
c. AFTER 15 MINUTES OF STABILIZATION, MEASURE THE GENERATOR PLANT TOTAL LOAD.
1. A 2ND CHILLER AND ASSOCIATED PUMP EQUIPMENT SHALL BE PERMITTED TO START IF LOAD ON
GENERATORS IS LESS THAN OR EQUAL TO 2400KVA AFTER STARTUP OF LOADS IN 3(a)(ii).
d. ONLY (2) CHILLERS SHALL BE PERMITTED TO OPERATE ON EMERGENCY SEQUENCE.
1. SEND A “CHILLED WATER DEMAND IS SATISFIED” CONTACT CLOSURE FROM THE BAS TO THE SYSTEM
ONCE THE DEMAND IS MET OR 2ND CHILLER IS RUNNING 100%, WHICHEVER COMES FIRST.
e. SEND A CONTACT CLOSURE FROM THE SYSTEM TO BAS SYSTEM IF TOTAL PLANT LOAD REACHES 85% OF
CAPACITY.
1. THIS SIGNAL SHALL RESTRICT CHILLER PLANT FROM INCREASING CAPACITY UNLESS SIGNAL IS
REMOVED.
2. MEASURE GENERATOR PLANT TOTAL ONCE CHILLER LOAD HAS STABILIZED FOR 15 MINUTES,
a. A2 WILL REMAIN OPEN AND MAIN BUILDING NORMAL SUBSTATIONS WILL REMAIN DE-ENERGIZED IF LOAD
EXCEEDS PREDETERMINE KVA.
b. CLOSE A2 TO ENERGIZE MAIN BUILDING NORMAL SUBSTATIONS IF LOAD IS LESS THAN PREDETERMINED KVA.
D. INITIATE THE RETURN TO NORMAL SEQUENCE WHEN POWER IS AVAILABLE AT U1 FOR 15 CONSECUTIVE MINUTES.
1. THE SYSTEM WILL SYNCHRONIZE THE UTILITY WITH THE GENERATORS IF NORMAL BUS IS ENERGIZED AND THEN
CLOSE U1, A1, B1, AND A2 (AS REQUIRED) AND OPEN T2 AND T3 IF THE NORMAL BUS IS DE-ENERGIZED.
2. THE SYSTEM WILL CLOSE U1 AND T2 AND T3 WILL REMAIN OPEN IF NORMAL BUS IS DE-ENERGIZED.
3. TRANSFER SWITCHES WILL TRANSFER TO PRIMARY SOURCE AFTER PROGRAMMED DELAYS
4. GENERATORS WILL SHUTDOWN AFTER PROGRAMMED ENGINE COOL-DOWN TIME DELAY.
DEFINITIONS:
TRANSFER SWITCH LOCATION EST. LOAD BRANCH PRIORITY
ATS-EQ
ATS-LS
ATS-CR
ATS-C1DEA
ATS-D3DEB
ATS-CH
ATS-HEQ1
ATS-HCR
ATS-HLS
MB - 1A360 * EQUIPMENT PRIORITY 2
MB - 1A360 * LIFE SAFETY PRIORITY 1
* CRITICAL PRIORITY 1
* EQUIPMENT PRIORITY 2
* EQUIPMENT PRIORITY 2
0 KVA EQUIPMENT PRIORITY 2
275 KVA EQUIPMENT PRIORITY 2
70 KVA CRITICAL PRIORITY 1
30 KVA LIFE SAFETY PRIORITY 1
MB - 1A360
MB - 1A360
MB - 1A360
MB - 1A360
BP - 203
BP - 203
BP - 203
EMERGENCY SEQUENCE #2 - NORMAL PARALLELING EQUIPMENT FAILURE
THE EMERGENCY SEQUENCE WHEN UTILITY POWER IS UNAVAILABLE AND STANDARD EMERGENCY SEQUENCE IS UNAVAILABLE
DUE TO FAILURE OF THE NORMAL PARALLELING EQUIPMENT.
A. THE SYSTEM SENSES UTILITY POWER IS UNAVAILABLE AT U1 VIA THE RUSSELECTRIC PARALLELING SWITCHGEAR.
B. THE SYSTEM ATTEMPTS TO PERFORM EMERGENCY SEQUENCE #1 FUNCTIONS.
1. THE GENERATORS SUCCESSFULLY START AND ENERGIZE PSG-E BUS.
2. PSG-N BUS FAILS TO ENERGIZE OR BREAKERS THAT FEED SS-CP1 AND/OR SS-CP2 FAIL TO ENERGIZE DESPITE
LOAD MEASUREMENTS WITHIN THE REQUIRED PARAMETERS.
C. PLANT OPERATOR WILL MANUALLY OPEN CP1N AND CP2N.
D. ONCE OPEN, PLANT OPERATOR WILL MANUALLY CLOSE CP1E AND CP2E AND E3.
E. ONCE CLOSED, REFER TO STEP #3 OF EMERGENCY SEQUENCE TO ENERGIZE CHILLED WATER EQUIPMENT BASED ON
GENERATOR PLANT CAPACITY.
F. WHEN UTILITY POWER AND PSG-N FUNCTIONALITY IS RESTORED
1. SHUT DOWN THE CHILLED WATER PLANT TO PREPARE FOR A CUTOVER.
2. PLANT OPERATOR WILL MANUALLY OPEN CP1E AND CP2E AND E3.
3. PLANT OPERATOR WILL MANUALLY CLOSE CP1N AND CP2N.
4. THE GENERATORS PARALLEL WITH UTILITY AND UTILITY CIRCUIT BREAKER U1 CLOSES
5. TIE BREAKERS T1, T2, AND T3 OPEN.
6. GENERATORS WILL SHUTDOWN AFTER PROGRAMMED ENGINE COOL-DOWN TIME DELAY.
7. THE CHILLER PLANT RETURNS TO NORMAL OPERATING SEQUENCE.
BACKOUT PROCEDURES
A. IF, AT ANY POINT, ONLY A SINGLE GENERATOR IS AVAILABLE, OPEN T2 AND T3.
1. GENERATOR SUPPLIES ONLY THE PSG-E BUS.
2. A CHILLER MAY BE PERMITTED TO RUN MANUALLY THROUGH EMERGENCY SEQUENCE #2. ALL OTHER CHILLERS
SHALL BE LOCKED OUT.
B. IF THE TOTAL GENERATOR LOAD EXCEEDS 95% OF TOTAL GENERATOR RATING FOR 30 CONSECUTIVE SECONDS, OPEN
A2.
1. IF LOAD CONSTINUES TO EXCEED 95%, SIGNAL THE CHILLER PLANT TO SHUT DOWN CHILLED WATER EQUIPMENT
AND OPEN E3.
2. IF LOAD CONTINUES TO EXCEED 95%, SHED NON-ESSENTIAL TRANSFER SWITCHES PER THEIR PRIORITY
SCHEDULE AND SMART LOADING MANAGEMENT SYSTEM AS NECESSARY TO MAINTAIN GENERATOR
AVAILABILITY.
C. IF THE GENERATOR PLANT REACHES UNDER-FREQUENCY SETTING,
1. OPEN T2, T3, AND E3 TO SHED NORMAL BUILDING LOADS AND CHILLER PLANT.
D. WHEN UTILITY POWER IS AVAILABLE FOR 15 CONSECUTIVE MINUTES, RUSSELECTRIC EQUIPMENT WILL SYNCHRONIZE UTILITY POWER WITH GENERATORS, CLOSE U1, A1, B1, AND A2 (AS REQUIRED), AND OPEN T2 AND T3.
1. RETURN TRANSFER SWITCHES TO PRIMARY FEEDER ONCE EXISTING TIME DELAYS ARE SATISFIED.
SUBSTATION MAINTENANCE SEQUENCE
THE MAINTENANCE SEQUENCE WHEN UTILITY POWER IS AVAILABLE, BUT EITHER SUBSTATION TRANSFORMER MUST BE DE-
ENERGIZED FOR MAINTENANCE PURPOSES. FOR THE PURPOSE OF THIS SEQUENCE:
A. THE SYSTEM OPERATES UNDER THE NORMAL SEQUENCE.
B. IF (2) CHILLERS OR LESS ARE REQUIRED TO MEET FACILITY DEMAND,
1. THE PLANT OPERATOR WILL SHUT DOWN THE EQUIPMENT ON THE SUBSTATION REQUIRING MAINTENANCE
2. THE BAS SHALL ENERGIZE THE CHILLERS ON THE REMAINING SUBSTATION.
C. IF (3) CHILLERS ARE REQUIRED TO MEET THE FACILITY DEMAND,
1. THE PLANT OPERATOR WILL SHUT DOWN THE EQUIPMENT ON THE SUBSTATION REQUIRING MAINTENANCE AND
TRANSFER THE EQUIPMENT TO THE SECONDARY SUBSTATION VIA THE MAIN-TIE-MAIN SEQUENCE OF
OPERATIONS.
a. OPEN THE MAIN CIRCUIT BREAKER OF THE SUBSTATION REQUIRING MAINTENANCE.
b. CLOSE CPT.
c. SEND A SIGNAL TO BAS WHEN CPT IS CLOSED THAT THE BAS LOCKS OUT (1) CHILLER TO PREVENT ALL
(4) CHILLERS FROM BEING ENERGIZED ON A SINGLE SUBSTATION.
d. START THE CHILLER PLANT EQUIPMENT AS REQUIRED TO MEET CHILLED WATER DEMAND.
D. THE FORCED-AIR FAN ON THE SUBSTATION SHALL BE UTILIZED DURING THE MAINTENANCE SEQUENCE SHOULD THE
TRANSFORMER EXCEED RATED AMBIENT AIR RATINGS VIA LOAD OR TEMPERATURE.
1. THIS CONTROL IS INTEGRAL TO THE SUBSTATION AND REQUIRES NO MANUAL INTERVENTION.
E. CHILLER(S) THAT ARE OPERATING ON THEIR SECONDARY SUBSTATION SHALL BE SHUT DOWN ONCE MAINTENANCE HAS
BEEN COMPLETED.
1. ONCE THE CHILLERS ARE SHUT DOWN, OPEN CPT AND CLOSE THE MAIN SUBSTATION BREAKER.
2. REMOVE CHILLER LOCKOUT SIGNAL FROM BAS.
3. THE BAS SHALL START CHILLER PLANT EQUIPMENT AS REQUIRED TO MEET THE CHILLED WATER DEMAND.
PROGRAMMING REQUIREMENTS
1. PROVIDE COMMUNICATIONS BETWEEN EXISTING THE SYSTEM AND THE EXISTING BAS.
2. ASSUME (100) POINTS OF PROGRAMMING
3. ASSUME (16) HOURS OF MEETINGS WITH VA AND DESIGN TEAM TO DISCUSS PROGRAMMING REQUIREMENTS FOR THE
SYSTEM AND THE BAS.
4. ASSUME (4) SAMPLE SCREENS WILL BE PROVIDED FOR REVIEW AND REVISIONS WILL BE MADE FOR FINAL SCREEN DESIGN.
EQUIPMENT PRIMARY SUBSTATION SECONDARY SUBSTATION
CHILLER #1 AND ASSOCIATED EQUIPMENT SS-CP1 SS-CP2
SS-CP2
SS-CP1
SS-CP1
SS-CP1
SS-CP2
SS-CP2
CHILLER…