RFI LOG AMENDMENT 0013_ SEED 1 AND 2.pdf

PDF 153 KB Posted

Attached to
VISN 7 CONSTRUCTION MATOC 36C24726R0026 - SOLICITATION
Solicitation number
36C24726R0026
Issued by

About this file

This is a Request for Information (RFI) Log for the VISN 7 Construction MATOC (Multiple Award Task Order Contract) solicitation 36C24726R0026, Amendment #0013, covering Seed 1 and Seed 2 projects.

The log documents four clarification questions and government responses regarding two construction projects. For Seed 1, Project #534-23-910, three questions addressed Specification Section 28 31 00 regarding a five-year inspection, testing, maintenance, and repair service requirement for the fire alarm system. The Government clarified that the five-year service requirement applies only to fire alarm system components touched in the project scope (4th Floor Nursing Station, restrooms, and stairwells), not the entire building fire alarm system. The service will be administered through the General Contractor rather than a direct contractual relationship with the Government. For Seed 2, Project #557-20-101, one question addressed fiber optic backbone and cross-connect scope requirements. The Government response specified that the exact fiber routing path will be determined in coordination with the Contracting Officer Representative (COR) and OIT representative, with the contractor planning for an 800-foot distance between the telecommunications room (D127/D129-5) and Building 40 Server Room, with requirements complying with revised Section 27 10 00 and attached Section 27 13 23. The document notes that the question submission deadline has closed and the Government is no longer accepting questions, with the electronic technical and price proposal due date remaining unchanged.

View the file

Other files

File Type Posted
36C24726R0026 0012.pdf PDF
36C24726R0026 0010.pdf PDF
36C24726R0026 0009.pdf PDF
36C24726R0026 0007.pdf PDF
RFI LOG AMENDMENT 0007_Seed 3 - 619A4-25-102.pdf PDF
Seed 3_ 619A4-25-102 - Correct Egress Door Deficiencies Final Drawings.pdf PDF
RFI LOG AMENDMENT 0006_SEED 2 - Revised.pdf PDF
ATTACHMENT 11 - SEED 1_WAGE DETERMINATION SC20260023 05 18 2026.pdf PDF
Seed 1_534-23-910 SOW Rev1 - Final.pdf PDF
Seed 3_619A4-25-102 Wage Rates AL20260078 01 02 2026.pdf PDF
Seed 2_557-20-101 - Photos_RFI 262 263.docx DOCX document
Seed 2_557-20-101 -5418654-1EN Rev 22.pdf PDF
Seed 2_557-20-101 -GEHC-SP_SIGNA-VOYAGER_8-278F.pdf PDF
Seed 2_557-20-101 - 2024-06-19_SD Rpt_ GC85A_Physicist Rp.pdf PDF
Seed 2_557-20-101 -HME_DR_GM85_Datasheet_v42_230209_FDA.pdf PDF
Seed 2_557-20-101 -Typical - Symbia Intevo Bold.pdf PDF
RFI LOG AMENDMENT 0006_MATOC RFP.pdf PDF
Seed 2_557-20-101 - VA Radiology - CD100 Final Bid Documents - Combined Set - SIGNED.pdf PDF
Seed 2_557-20-101 - Med Gas Master Alarm Panel.jpg JPG image
Seed 2_557-20-101 -Probe Cabinet specs.pdf PDF
36C24726R0026 0005.pdf PDF
RFI 182 PICS.docx DOCX document
RFI LOG AMENDMENT 0005_Seed 1.pdf PDF
534-23-910 VA Charleston Stairwells Restrooms and Doors - Revision 2.pdf PDF
36C24726R0026 0003.pdf PDF
534-23-910 VA Charleston Stairwells Restrooms and Doors - Revision 1- General pages.pdf PDF
534-23-910 - Environmental Survey Report.pdf PDF
NCS-VISN 7-MATOC-SEED 2-RFI 1 - 2 A600.pdf PDF
Seed 3 - 619A4-25-102 Site Visit Attendance Roster_4 23 26.pdf PDF
36C24726R0026 0002.pdf PDF
RFI LOG AMENDMENT 0002.pdf PDF
ATTACHMENT 8R - SEED 1_PROJECT 534-23-910_SPECIFICATIONS REV 4.pdf PDF
36C24726R0026 0001.docx DOCX document
36C24726R0026 AMENDMENT 0001 RFI LOG.pdf PDF
36C24726R0026_VISN 7 CONSTRUCTION MATOC.pdf PDF
ATTACHMENT 4 - SUBCONTRACTOR CONSENT FOR PAST PERFORMANCE.docx DOCX document
ATTACHMENT 5 - EXPERIENCE MODIFICATION RATE FORM.docx DOCX document
ATTACHMENT 11 - SEED 1_WAGE DETERMINATION SC20260023 01 02 26.pdf PDF
ATTACHMENT 15 - SEED 3_PROJECT 619A4-25-102_SPECS 100 FINAL rev1.pdf PDF
ATTACHMENT 17 - SEED 3_PROJECT 619A4-25-102_PIC BOOK 100 FINAL.pdf PDF
ATTACHMENT 1 - CONTRACTOR EXPERIENCE FORM.docx DOCX document
ATTACHMENT 2 - CONTRACTOR SURETY LIMITATION.docx DOCX document
ATTACHMENT 7 - ITEMIZED COST BREAKDOWN.xlsx XLSX spreadsheet
ATTACHMENT 19 - VAAR 852.219-75 VA Notice of Limitations on Subcontracting Jan 2023 Deviation.pdf PDF
ATTACHMENT 3 - PAST PERFORMANCE QUESTIONAIRE.docx DOCX document
ATTACHMENT 6 - INVOICING.pdf PDF
ATTACHMENT 8 - SEED 1_PROJECT 534-23-910_SPECIFICATIONS.pdf PDF
ATTACHMENT 9 - SEED 1_PROJECT 534-23-910_ FINAL CONSTRUCTION DOCUMENTS VOL I.pdf PDF
ATTACHMENT 12 - SEED 2_PROJECT 557-20-101 SPECS FINAL.pdf PDF
ATTACHMENT 16 - SEED 3_PROJECT 619A4-25-102_100 FINAL DWGs.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

36C24726R0026

VISN 7 CONSTRUCTION MATOC

REQUEST FOR INFORMATION (RFI) LOG

AMENDMENT #0013

SEED 1 AND 2

QUESTION #

RELATED

SECTION

REQUESTED CLARIFICATION/INFORMATION GOVERNMENT RESPONSE

Seed 1, Project #534-23-910, Section 28 31 00

Specification Section 28 31 00, Paragraph 1.6.A requires five years of inspection, testing, maintenance, and repair service for the fire alarm system.field and must be provided for all offerors to bid the work fairly. Given the limited fire alarm scope associated with this project, which appears to consist primarily of modifications within select restrooms and the 4th Floor Nurse Station, this requirement appears disproportionate to the scope of work and will increase project cost $3-5 million, reduce competition, and result in unnecessary contingency pricing. a. Five-year service agreements are typically associated with campus-wide fire alarm replacements or major system upgrades. Is the five-year service requirement included in this project, yes or no?

Only Fire Alarms System Components touched in the project scope which aligned to 4th Floor Nursing Station, Restrooms listed in Scope, and Stairwells listed in Scope.

This is not intended to perform five year years of inspection, testing, maintenance, and repair of the entire building fire alarm system.

Seed 1, Project #534-23-910, Section 28 31 00

Specification Section 28 31 00, Paragraph 1.6.A requires five years of inspection, testing, maintenance, and repair service for the fire alarm system. a. The entire Ralph H. Johnson VAMC fire alarm system; or b.Only the fire alarm devices and system modifications installed under this contract.

Only Fire Alarms System Components touched in the project scope which aligned to 4th Floor Nursing Station, Restrooms listed in Scope, and Stairwells listed in Scope.

This is not intended to perform five year years of inspection, testing, maintenance, and repair of the entire building fire alarm system.

Seed 1, Project #534-23-910, Section 28 31 00

Specification Section 28 31 00, Paragraph 1.6.A requires five years of inspection, testing, maintenance, and repair service for the fire alarm system. a. If the requirement remains, please clarify whether the five-year service agreement is intended to be administered through the General Contractor or through a direct contractual relationship between the Government and the fire alarm service provider following project acceptance.

Only Fire Alarms System Components touched in the project scope which aligned to 4th Floor Nursing Station, Restrooms listed in Scope, and Stairwells listed in Scope.

This is not intended to perform five year years of inspection, testing, maintenance, and repair of the entire building fire alarm system. This will be administered through the General Contractor.

36C24726R0026

VISN 7 CONSTRUCTION MATOC

REQUEST FOR INFORMATION (RFI) LOG

AMENDMENT #0013

SEED 1 AND 2

QUESTION #

RELATED

SECTION

REQUESTED CLARIFICATION/INFORMATION GOVERNMENT RESPONSE

Seed 2, Project #557-20-101 - Fiber optic backbone / cross-connect scope

The below question and response issued in the attached amendment [Reference #2 on "RFI Log_Seed 2 Revised" issued with Amendment #0012] needs additional details and the routing of the new fiber should be shown on an overall site plan with route identified through existing site and should include conduit and raceway details as needed. Please advise.

Exact path to be determined in coordination with COR and OIT representative. Contractor should plan for 800 ft distance between telecommunications room (D127/D129-

5) and Building 40 Server Room. Requirements shall comply with revised 27 10 00 and attached 27 13 23.

Please be advised that the due date for submitting questions has passed. The Government is not longer accepting questions. We appreciate your understanding and look forward to your proposal submission. DUE DATE FOR ELECTRONIC TECHNICAL AND PRICE PROPOSAL REMAINS

UNCHANGED.

RFI LOG