2023-05-18_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf

PDF 389 KB Posted

Attached to
Fire Sprinkler Testing
Solicitation number
36C24724Q0269
Issued by

About this file

This document is a fire sprinkler inspection report for Building 131 at the Fort McPherson VA Medical Center in Atlanta, Georgia. The report details inspection and testing of the building's wet pipe, dry pipe, and alarm systems conducted on May 18, 2023. It lists all devices by type and location, along with inspection results, component details, pressure readings, and response times. An inventory section specifies the models, installation dates, and warranty periods of the various valves, switches, gauges, sprinklers, and other equipment installed between March 2012 and May 2021. Address information and scan IDs are provided for individual devices.

The related federal contract opportunity is solicitation number 36C24724Q0269 for fire sprinkler testing services at the Fort McPherson VAMC. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration VISN 7. The inspection report would inform contractors' responses by detailing the existing systems and components requiring testing and maintenance under the contract. No further salient details are provided on the opportunity in the attached document.

View the file

Other files

File Type Posted
FIRE ALARM 130.pdf PDF
2022-06-20_Fort-McPherson-VAMC-Bldg-128_Annual Report.pdf PDF
BLDG 131 ASBUILTS.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-131_Annual Report.pdf PDF
FIRE SUPPRESSION.pdf PDF
2022-06-20_Fort-McPherson-VAMC-Bldg-129_Annual Report.pdf PDF
BLDG 125 ASBUILT.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-125_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-128_SprinklerScan.pdf PDF
Ft. McPherson Bldg 128 Fire Alarm Drawings - RECORD Dwg.pdf PDF
Bldg 128 As-Builts.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
FIRE ALARM 129.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-125_SprinklerScan.pdf PDF
BLDG 129 ASBUILT.pdf PDF
2023-02-10_Fort-McPherson-VAMC-Bldg-128_SprinklerScan (1).pdf PDF
36C24724Q0269 0001.pdf PDF
03 Series LIFE SAFETY - 100 AT-130 Fort McPherson Residental Treatment.pdf PDF
03 Series LIFE SAFETY - 100 AT-131 Fort McPherson Domiciliary Care.pdf PDF
03 Series LIFE SAFETY - 100 AT-125 Fort McPherson OPC.pdf PDF
FIRE ALARM 125.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-125_Annual Report.pdf PDF
04 Series DOORS - 100 AT-130 Fort McPherson Residental Treatment.pdf PDF
04 Series DOORS - 100 AT-125 Fort McPherson OPC.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-128_SprinklerScan.pdf PDF
05 series dampers - 100 at-125 fort mcpherson opc.pdf PDF
FIRE SUPPRESSION 131.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-130_Annual Report.pdf PDF
03 Series LIFE SAFETY - 100 AT-128 Fort McPherson Homeless Program.pdf PDF
04 Series DOORS - 100 AT-128 Fort McPherson Homeless Program.pdf PDF
BLDG. 125 FIRE SUPPRESSION.pdf PDF
04 Series DOORS - 100 AT-131 Fort McPherson Domiciliary Care.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-129_SprinklerScan.pdf PDF
36C24724Q0269.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sprinkler Inspection, Testing and/or Maintenance Certificate

For

Fort McPherson VAMC Bldg 131 1701 Hardee Ave SW

Atlanta, GA 30310 Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards effective January 31, 2021

Annual Inspection Inspection Completion Date May 18, 2023

Building: Fort McPherson VAMC Bldg 131 Company: United Fire Protection - Atlanta Contact: Mike McGill Contact: Wayne Huxtable

Title: Maintenance & Operations Supervisor Title: Technician

Page of 1 31United Fire Protection - Atlanta Download Date: 05/20/2023

Executive Summary Generated by: BuildingReports.com

Building Information Building: Fort McPherson VAMC Bldg 131 Contact: Mike McGill

Address: 1701 Hardee Ave SW Phone: 14043216111

Address: Fax:

City/State/ZIP Code: Atlanta, GA 30310 Mobile:

Country: United States of America Email:

Inspection Performed By Company: United Fire Protection - Atlanta Inspector: Wayne Huxtable

Address: 2150 Boggs Rd Bldg 100 Phone: 770-771-0999

Address: Suite 140 Fax:

City/State/ZIP Code: Duluth, GA 30096 Mobile:

Country: United States of America Email: whuxtable@united-fire.com

Page of 2 31United Fire Protection - Atlanta Download Date: 05/20/2023

Inspection Completion Date: May 18, 2023 Building: Fort McPherson VAMC Bldg 131 EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(b-g)

Devices Tested This

Quarter Pass Fail Tested YTD

(2023) Untested YTD

(2023) Total

Quantity Air Maintenance Device 1 1 0 1 0 1

Pressure Switch 2 2 0 2 0 2

EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)

Devices Tested This

Quarter Pass Fail Tested YTD

(2023) Untested YTD

(2023) Total

Quantity Tamper Switch 11 11 0 11 0 11

Waterflow Switch 6 6 0 6 0 6

EC 02.03.05 EP 09 Annual test of main drains at system low point or at all system risers. NFPA 25 (2020)

13.2.3 & 13.2.3.2

Devices Tested This

Quarter Pass Fail Tested YTD

(2023) Untested YTD

(2023) Total

Quantity Drain 1 1 0 1 0 1

LS 02.01.35 EP 07 At least six spare sprinkler heads that correspond to the types and temperature rating of the hospital's sprinkler heads, with associated wrenches, are kept in a cabinet that will not exceed 100F. NFPA 25-2020: 5.4.1

Devices Tested This

Quarter Pass Fail Tested YTD

(2023) Untested YTD

(2023) Total

Quantity Sprinkler Box 1 1 0 1 0 1

Sprinkler Box Spares 3 3 0 3 0 3

LS 02.01.35 EP 14 All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

Devices Tested This

Quarter Pass Fail Tested YTD

(2023) Untested YTD

(2023) Total

Quantity Air Compressor 1 1 0 1 0 1

Check Valve 7 7 0 7 0 7

Control Valve 11 11 0 11 0 11

Dry Pipe Valve 1 1 0 1 0 1

Gauge 8 8 0 8 0 8

Inspector's Test 6 6 0 6 0 6

Total Device Count: 59

Page of 3 31United Fire Protection - Atlanta Download Date: 05/20/2023

Certification

Company: United Fire Protection - Atlanta Building: Fort McPherson VAMC Bldg 131

Inspector: Wayne Huxtable Contact: Mike McGill

Page of 4 31United Fire Protection - Atlanta Download Date: 05/20/2023

Inspection & Testing Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 131 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 01

Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(b-g)

Automatic air pressure maintenance devices, if provided, shall be tested yearly at the time of the annual preaction or deluge valve trip test, in accordance with the manufacturer's instructions. (NFPA 25-20 13.4.3.2.13) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Air Maintenance Device 1 1 0 1 1

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Air Maintenance Device

Attic Supply Pressure 67977791 0 08/15-P 10/28-P 02/09-P 05/18-P

Device Total: 1 Return to Executive Summary

Page of 5 31United Fire Protection - Atlanta Download Date: 05/20/2023

EC 02.03.05 EP 01

Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(b-g)

Operate switch and verify receipt of signal is obtained where the required pressure is increased or decreased a maximum 10 psi from the required pressure level. (NFPA 72-19 Table 14.4.3.2 (17)(9b)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Pressure Switch 2 2 0 2 2

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Pressure Switch Attic High Pressure 44133577 1-M1-58 08/15-P 10/28-P 02/09-P 05/18-P Pressure Switch Attic Low Pressure 44133586 1 08/15-P 10/28-P 02/09-P 05/18-P

Device Total: 2 Return to Executive Summary

Page of 6 31United Fire Protection - Atlanta Download Date: 05/20/2023

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)

Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Tamper Switch 11 11 0 11 11

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Tamper Switch 1st North Zone 1-1 86195017 1-M1-155 05/18-P Tamper Switch 1st South Zone 1-2 86195014 1-M1-163 05/18-P Tamper Switch 2nd North Building 131 Zone

2-1 86195018 1-M1-157 05/18-P

Tamper Switch 2nd South Zone 2-2 86195016 1-M1-165 05/18-P Tamper Switch Attic 86195013 1-M1-159 05/18-P Tamper Switch Sectional 86195012 1 05/18-P Tamper Switch Test Header 86195009 1 05/18-P Tamper Switch Test Header 86195010 1 05/18-P Tamper Switch Test Header 86195011 1 05/18-P Tamper Switch Ground North Zone B-1 86195019 1-M1-153 05/18-P Tamper Switch Ground South Zone B-2 86195015 1-M1-160 05/18-P

Device Total: 11 Return to Executive Summary

Page of 7 31United Fire Protection - Atlanta Download Date: 05/20/2023

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)

Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-19 Table

14.4.3.2 (17)(11)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Waterflow Switch 6 6 0 6 6

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Waterflow Switch 1st North Zone 1-1 44133547 1-M1-154 08/15-P 10/28-P 02/09-P 05/18-P Waterflow Switch 1st South Zone 1-2 44133552 1-M1-162 08/15-P 10/28-P 02/09-P 05/18-P Waterflow Switch 2nd North Zone 2-1 44133557 1-M1-156 08/15-P 10/28-P 02/09-P 05/18-P Waterflow Switch 2nd South Zone 2-2 44133562 1-M1-164 08/15-P 10/28-P 02/09-P 05/18-P Waterflow Switch Ground North Zone B-1 44133567 1-M1-152 08/15-P 10/28-P 02/09-P 05/18-P Waterflow Switch Ground South Zone B-2 44133572 1-M1-161 08/15-P 10/28-P 02/09-P 05/18-P

Device Total: 6 Return to Executive Summary

Page of 8 31United Fire Protection - Atlanta Download Date: 05/20/2023

EC 02.03.05 EP 09

Annual test of main drains at system low point or at all system risers. NFPA 25 (2020)

13.2.3 & 13.2.3.2

A main drain test shall be conducted annually for each water supply lead-in to a building water-based fire protection system to determine whether there has been a change in the condition of the water supply. (NFPA 25-20 13.2.3) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Drain 1 1 0 1 1

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Drain Attic Supply Pressure 44133579 0 08/15-P 10/28-P 05/18-P

Page of 9 31United Fire Protection - Atlanta Download Date: 05/20/2023

LS 02.01.35 EP 07

At least six spare sprinkler heads that correspond to the types and temperature rating of the hospital's sprinkler heads, with associated wrenches, are kept in a cabinet that will not exceed 100F. NFPA 25-2020: 5.4.1

A supply of at least six spare sprinklers shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. (NFPA 25-20 5.4.1.5) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Sprinkler Box 1 1 0 1 1

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Sprinkler Box Attic Air Pressure 44133584 0 08/15-P 10/28-P 05/18-P

Page of 10 31United Fire Protection - Atlanta Download Date: 05/20/2023

LS 02.01.35 EP 07

At least six spare sprinkler heads that correspond to the types and temperature rating of the hospital's sprinkler heads, with associated wrenches, are kept in a cabinet that will not exceed 100F. NFPA 25-2020: 5.4.1

A supply of at least six spare sprinklers shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. (NFPA 25-20 5.4.1.5) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Sprinkler Box Spares 3 3 0 3 3

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Sprinkler Box Spares Attic Air Pressure 67977846 0 08/15-P 10/28-P 05/18-P Sprinkler Box Spares Attic Air Pressure 67977847 0 08/15-P 10/28-P 05/18-P Sprinkler Box Spares Attic Air Pressure 67977848 0 08/15-P 10/28-P 05/18-P

Device Total: 3 Return to Executive Summary

Page of 11 31United Fire Protection - Atlanta Download Date: 05/20/2023

LS 02.01.35 EP 14

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

Compressors used in conjunction with dry pipe sprinkler systems shall be maintained in accordance with the manufacturer's instructions. (NFPA 25-20 5.4.2.4) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Air Compressor 1 1 0 1 1

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Air Compressor Attic Low Pressure 44133585 0 08/15-P 10/28-P 02/09-P 05/18-P

Page of 12 31United Fire Protection - Atlanta Download Date: 05/20/2023

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

Internal components shall be cleaned, repaired, or replaced as necessary in accordance with the manufacturer's instructions. (NFPA 25-20 13.4.2.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Check Valve 7 7 0 7 7

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Check Valve 1st North Zone 1-1 44133545 1 08/15-P 10/28-P 05/18-P Check Valve 1st South Zone 1-2 44133550 1 08/15-P 10/28-P 05/18-P Check Valve 2nd North Zone 2-1 44133555 1 08/15-P 10/28-P 05/18-P Check Valve 2nd South Zone 2-2 44133560 1 08/15-P 10/28-P 05/18-P Check Valve Test Header 44133587 1 08/15-P 10/28-P 05/18-P Check Valve Ground North Zone B-1 44133565 1 08/15-P 10/28-P 05/18-P Check Valve Ground South Zone B-2 44133570 1 08/15-P 10/28-P 05/18-P

Device Total: 7 Return to Executive Summary

Page of 13 31United Fire Protection - Atlanta Download Date: 05/20/2023

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Control Valve 11 11 0 11 11

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Control Valve 1st North Zone 1-1 44133544 1-M1-155 08/15-P 10/28-P 02/09-P 05/18-P Control Valve 1st South Zone 1-2 44133549 1-M1-163 08/15-P 10/28-P 02/09-P 05/18-P Control Valve 2nd North Building 131 Zone

2-1 44133554 1-M1-157 08/15-P 10/28-P 02/09-P 05/18-P

Control Valve 2nd South Zone 2-2 44133559 1-M1-165 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Attic 44133574 1-M1-159 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Sectional 44133583 1 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Test Header 44133580 1 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Test Header 44133581 1 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Test Header 44133582 1 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Ground North Zone B-1 44133564 1-M1-153 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Ground South Zone B-2 44133569 1-M1-160 08/15-P 10/28-P 02/09-P 05/18-P

Device Total: 11 Return to Executive Summary

Page of 14 31United Fire Protection - Atlanta Download Date: 05/20/2023

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

Each dry pipe valve shall be trip tested annually during warm weather. (NFPA 25-20 13.4.5.2.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Dry Pipe Valve 1 1 0 1 1

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Dry Pipe Valve Attic Supply Pressure 44133578 0 08/15-P 10/28-P 02/09-P 05/18-P Dry Pipe Valve 2 second floor Sprinkler room 13765 0 08/15-P 10/28-P 02/09-P 05/18

Removed

Page of 15 31United Fire Protection - Atlanta Download Date: 05/20/2023

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. (NFPA 25- 20 13.2.5.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Gauge 8 8 0 8 8

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Gauge 1st North Zone 1-1 57780042 0 08/15-P 10/28-P 05/18-P Gauge 1st South Zone 1-2 57780045 0 08/15-P 10/28-P 05/18-P Gauge 2nd South Zone 2-1 57780043 0 08/15-P 10/28-P 05/18-P Gauge 2nd South Zone 2-2 57780046 0 08/15-P 10/28-P 05/18-P Gauge Attic Air Pressure 57780008 0 08/15-P 10/28-P 05/18-P Gauge Attic Supply Pressure 57780009 0 08/15-P 10/28-P 05/18-P Gauge Ground North Zone B-1 57780041 0 08/15-P 10/28-P 05/18-P Gauge Ground South Zone B-2 57780044 0 08/15-P 10/28-P 05/18-P

Device Total: 8 Return to Executive Summary

Page of 16 31United Fire Protection - Atlanta Download Date: 05/20/2023

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

Testing of pressure switch type waterflow alarm devices on wet pipe systems shall be accomplished by opening the inspector's test connection (NFPA 25-20 5.3.3.3) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Inspector's Test 6 6 0 6 6

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Inspector's Test 1st North Zone 1-1 44133548 0 08/15-P 10/28-P 02/09-P 05/18-P Inspector's Test 1st South Zone 1-2 44133553 0 08/15-P 10/28-P 02/09-P 05/18-P Inspector's Test 2nd North Zone 2-1 44133558 0 08/15-P 10/28-P 02/09-P 05/18-P Inspector's Test 2nd South Zone 2-2 44133563 0 08/15-P 10/28-P 02/09-P 05/18-P Inspector's Test Ground North Zone B-1 44133568 0 08/15-P 10/28-P 02/09-P 05/18-P Inspector's Test Ground South Zone B-2 44133573 0 08/15-P 10/28-P 02/09-P 05/18-P

Device Total: 6 Return to Executive Summary

Page of 17 31United Fire Protection - Atlanta Download Date: 05/20/2023

Service Summary Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 131 The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Passed Air Compressor Annual 1 Air Maintenance Device Annual 1 Check Valve Annual 7 Control Valve Annual 11 Drain Annual 1 Dry Pipe Valve Annual 1 Gauge Annual 8 Inspector's Test Annual 6 Pressure Switch Annual 2 Sprinkler Box Spares Annual 3 Sprinkler Box Annual 1 Tamper Switch Annual 11 Waterflow Switch Annual 6

Total 59 Grand Total 59

Page of 18 31United Fire Protection - Atlanta Download Date: 05/20/2023

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Location Number of Turns

Zone /Address

OK ScanID

Control Valve Supervisory Test Header 1 86195009 OS&Y Supervisory Test Header 1 86195010 OS&Y Supervisory Test Header 1 86195011 OS&Y Supervisory Sectional 1 86195012

Components Check Valve

Type Location Internal Date Size OK ScanID Grooved Test Header 05/15/2021 4" 44133587

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Test Header 6" Open Supervised 44133580

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Test Header 6" Open Supervised 44133581

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Test Header 6" Open Supervised 44133582

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Sectional 6" Open Supervised 44133583 javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195009');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195010');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195011');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195012');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133587');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133580');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133581');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133582');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133583');

Page of 19 31United Fire Protection - Atlanta Download Date: 05/20/2023

Description Main Control

Building: Fort McPherson VAMC Bldg

Zone- 1-1

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Location Number of Turns

Zone /Address

OK ScanID

Control Valve Supervisory 1st North Zone 1-1 1-M1-155 86195017

Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 36.89 3" 1-M1-154 44133547

Components Check Valve

Type Location Internal Date Size OK ScanID Grooved 1st North Zone 1-1 03/29/2018 3" 44133545

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Victaulic 705 1st North Zone 1-1

4" Open Supervised 44133544

Description Main Control

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1000 80 33 36.89 44133548

Location 1st North Zone 1-1

Devices Gauge

Location Service Date 1st North Zone 1-1 05/15/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 55 Air/Water 1/4 57780042

Building: Fort McPherson VAMC Bldg

Zone- 1-2

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195017');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133547');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133545');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133544');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133548');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780042');

Page of 20 31United Fire Protection - Atlanta Download Date: 05/20/2023 as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Location Number of Turns

Zone /Address

OK ScanID

Control Valve Supervisory 1st South Zone 1-2 1-M1-163 86195014

Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 35.30 3" 1-M1-162 44133552

Components Check Valve

Type Location Internal Date Size OK ScanID Grooved 1st South Zone 1-2 05/15/2021 3" 44133550

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Victaulic 705 1st South Zone 1-2

4" Open Supervised 44133549

Description Main Control

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1000 80 28 35.30 44133553

Location 1st South Zone 1-2

Devices Gauge

Location Service Date 1st South Zone 1-2 05/15/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 55 Air/Water 1/4 57780045

Building: Fort McPherson VAMC Bldg

Zone- 2-1

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Number of Zone javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195014');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133552');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133550');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133549');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133553');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780045');

Page of 21 31United Fire Protection - Atlanta Download Date: 05/20/2023

Type Description Location Turns /Address OK ScanID Control Valve Supervisory 2nd North Building 131 Zone 2-1 1-M1-157 86195018

Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 33.92 3" 1-M1-156 44133557

Components Check Valve

Type Location Internal Date Size OK ScanID Grooved 2nd North Zone 2-1 05/15/2021 3" 44133555

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Victaulic 705 2nd North Building 131 Zone 2-1

4" Open Supervised 44133554

Description Main Control

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1000 80 35 33.92 44133558

Location 2nd North Zone 2-1

Devices Gauge

Location Service Date 2nd South Zone 2-1 05/15/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 55 Air/Water 1/4 57780043

Building: Fort McPherson VAMC Bldg

Zone- 2-2

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Location Number of Turns

Zone /Address

OK ScanID

Control Valve Supervisory 2nd South Zone 2-2 1-M1-165 86195016

Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 31.97 3" 1-M1-164 44133562 javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195018');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133557');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133555');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133554');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133558');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780043');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195016');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133562');

Page of 22 31United Fire Protection - Atlanta Download Date: 05/20/2023

Components Check Valve

Type Location Internal Date Size OK ScanID Grooved 2nd South Zone 2-2 03/29/2018 4" 44133560

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Victaulic 705 2nd South Zone 2-2

4" Open Supervised 44133559

Description Main Control

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1000 80 22 31.96999 44133563

Location 2nd South Zone 2-2

Devices Gauge

Location Service Date 2nd South Zone 2-2 05/15/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 55 Air/Water 1/4 57780046

Building: Fort McPherson VAMC Bldg

Zone- B-1

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Location Number of Turns

Zone /Address

OK ScanID

Control Valve Supervisory Ground North Zone B-1 1-M1-153 86195019

Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 39.06 3" 1-M1-152 44133567

Components Check Valve

Type Location Internal Date Size OK ScanID Grooved Ground North Zone B-1 03/29/2018 3" 44133565

Control Valve javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133560');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133559');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133563');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780046');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195019');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133567');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133565');

Page of 23 31United Fire Protection - Atlanta Download Date: 05/20/2023

Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Victaulic 705 Ground North Zone B-1

4" Open Supervised 44133564

Description Main Control

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1000 80 41 39.06 44133568

Location Ground North Zone B-1

Devices Gauge

Location Service Date Ground North Zone B-1 05/15/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 55 Air/Water 1/4 57780041

Building: Fort McPherson VAMC Bldg

Zone- B-2

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Location Number of Turns

Zone /Address

OK ScanID

Control Valve Supervisory Ground South Zone B-2 1-M1-160 86195015

Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 39.69 3" 1-M1-161 44133572

Components Check Valve

Type Location Internal Date Size OK ScanID Grooved Ground South Zone B-2 03/29/2018 3" 44133570

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Victaulic 705 Ground South Zone B-2

4" Open Supervised 44133569

Description Main Control javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133564');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133568');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780041');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195015');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133572');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133570');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133569');

Page of 24 31United Fire Protection - Atlanta Download Date: 05/20/2023

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1000 80 51 39.68999 44133573

Location Ground South Zone B-2

Devices Gauge

Location Service Date Ground South Zone B-2 05/15/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 55 Air/Water 1/4 57780044 javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133573');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780044');

Page of 25 31United Fire Protection - Atlanta Download Date: 05/20/2023

Dry Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg

Area- Attic

This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Air Compressor Location Mfr. Model # Phase On psi Off psi Serial No.

Attic Low Pressure General

Air

LT900150B 1 35 45 LT900- 12 56 07 46

Type Description Rated Speed Horsepower Volts Amps OK ScanID

Automatic Tank 1725 1.5 208 5.4 44133585

Air Maintenance Device Type Model # Location Install Date Air Pressure ScanID Pressure Reducing Attic Supply Pressure 03/29/2017 40 67977791

Alarms Pressure Switch Type Description Manufacturer Low High Zone/Address OK ScanID Pressure Switch Alarm Potter Electric 0 10 1-M1-58 44133577 Pressure Switch Alarm Potter Electric 10 40 1 44133586

Tamper Switch

Type Description Location Number of Turns

Zone /Address

OK ScanID

Control Valve Supervisory Attic 1-M1-159 86195013

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 13765 Attic 4" Open Supervised 44133574

Description Main Control

Dry Pipe Valve Manufacturer Model # Location Internal Date OK ScanID Viking F-2 Attic Supply Pressure 03/29/2018 44133578

Type Status Position Size Serial # Grooved Sealed Trim Open 4" W552201 javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133585');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','67977791');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133577');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133586');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195013');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133574');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133578');

Page of 26 31United Fire Protection - Atlanta Download Date: 05/20/2023

Water psi Air Pressure Trip Air Trip Time Total Timing (sec)

Partial Trip Date

Full Trip Date

55 45 15 35.06 30 03/29/2017 05/18/2023

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi

Residual psi Sec OK ScanID

Main Attic Supply Pressure 2" 80 60 50 30 44133579

Previous Inspections

October 28, 2022

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Attic Supply Pressure 2" 80 60 50 44133579

August 15, 2022

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Attic Supply Pressure 2" 80 60 50 44133579

Gauge Location Service Date Attic Supply Pressure 05/15/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Lansdale 55 Air/Water 1/4 57780009

Gauge Location Service Date Attic Air Pressure 05/15/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Air Pressure Lansdale 20 Air/Water 1/4 57780008

Building: Fort McPherson VAMC Bldg

Area- Attic and rest of the

This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Sprinkler Box

Qty Tool Available?

SIN List? Size Manufacturer Location OK ScanID

6 Yes 6 unit Viking Attic Air Pressure 44133584

Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID 3 Upright Viking Attic Air Pressure 67977846

Temperature KFactor Size Finish Response Time 290 1/2 Brass Fast Response javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133579');

javascript:openEditDevice('load-edit-p2-device','0','2686313','44133579');

javascript:openEditDevice('load-edit-p2-device','0','2603990','44133579');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780009');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780008');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133584');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','67977846');

Page of 27 31United Fire Protection - Atlanta Download Date: 05/20/2023

Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID 3 Upright Viking Attic Air Pressure 67977847

Temperature KFactor Size Finish Response Time 290 5.6 1/2 Brass Fast Response

Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID 3 Upright Tyco Attic Air Pressure 67977848

Temperature KFactor Size Finish Response Time 212 5.6 1/2 Brass Standard Response javascript:openEditDevice('load-edit-p2-device','736897','2902388','67977847');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','67977848');

Page of 28 31United Fire Protection - Atlanta Download Date: 05/20/2023

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 131 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Air Compressor Pump 1.69% 1

Air Maintenance Device Pump 1.69% 1

Check Valve Valve 11.86% 7

Control Valve Valve 18.64% 11

Drain Device 1.69% 1

Dry Pipe Valve Valve 1.69% 1

Gauge Device 13.56% 8

Inspector's Test Valve 10.17% 6

Pressure Switch Alarm 3.39% 2

Sprinkler Box Sprinkler 1.69% 1

Sprinkler Box Spares Sprinkler 5.08% 3

Tamper Switch Alarm 18.64% 11

Waterflow Switch Alarm 10.17% 6

Device Type Qty Model # Type Description Install Date

In Service - 2 Years to 3 Years Dry Pipe, Area- Attic

Gauge 1 Air Pressure 05/15/2021 Gauge 1 Supply Pressure 05/15/2021

Wet Pipe, Zone- 1-1 Gauge 1 System Pressure 05/15/2021

Wet Pipe, Zone- 1-2 Gauge 1 System Pressure 05/15/2021

Wet Pipe, Zone- 2-1 Gauge 1 System Pressure 05/15/2021

Wet Pipe, Zone- 2-2 Gauge 1 System Pressure 05/15/2021

Wet Pipe, Zone- B-1 Gauge 1 System Pressure 05/15/2021

Wet Pipe, Zone- B-2 Gauge 1 System Pressure 05/15/2021

In Service - 3 Years to 5 Years Dry Pipe, Area- Attic and rest of the

Page of 29 31United Fire Protection - Atlanta Download Date: 05/20/2023

Sprinkler Box 1 07/11/2018 Sprinkler Box Spares 1 VK 300 Upright 07/11/2018 Sprinkler Box Spares 1 VK 302 Upright 07/11/2018

In Service - 5 Years to 10 Years Dry Pipe, Area- Attic

Air Compressor 1 LT900150B Automatic Tank 03/29/2018 Pressure Switch 1 PS-10 Pressure Switch Alarm 03/29/2018 Pressure Switch 1 PS-40 Pressure Switch Alarm 03/29/2018 Control Valve 1 13765 Butterfly Main Control 03/29/2018 Tamper Switch 1 13765 Control Valve Supervisory 03/29/2018

Wet Pipe Control Valve 4 705 Butterfly Main Control 03/29/2018 Tamper Switch 1 705 Control Valve Supervisory 03/29/2018 Tamper Switch 3 705 OS&Y Supervisory 03/29/2018

Wet Pipe, Zone- 1-1 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Check Valve 1 717H Grooved 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018 Tamper Switch 1 705 Control Valve Supervisory 03/29/2018

Wet Pipe, Zone- 1-2 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018 Tamper Switch 1 705 Control Valve Supervisory 03/29/2018

Wet Pipe, Zone- 2-1 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018 Tamper Switch 1 705 Control Valve Supervisory 03/29/2018

Wet Pipe, Zone- 2-2 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Check Valve 1 717H Grooved 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018 Tamper Switch 1 705 Control Valve Supervisory 03/29/2018

Wet Pipe, Zone- B-1 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Check Valve 1 717H Grooved 03/29/2018

Page of 30 31United Fire Protection - Atlanta Download Date: 05/20/2023

Control Valve 1 705 Butterfly Main Control 03/29/2018 Tamper Switch 1 705 Control Valve Supervisory 03/29/2018

Wet Pipe, Zone- B-2 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Check Valve 1 717H Grooved 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018 Tamper Switch 1 705 Control Valve Supervisory 03/29/2018

Dry Pipe, Area- Attic Drain 1 Wika Main 03/29/2017 Air Maintenance Device 1 Pressure Reducing 03/29/2017 Dry Pipe Valve 1 F-2 Grooved 03/29/2017

In Service - 10 Years to 15 Years Dry Pipe, Area- Attic and rest of the

Sprinkler Box Spares 1 TY 3180 Upright 07/11/2012

Wet Pipe Check Valve 1 705 Grooved 03/29/2012

Wet Pipe, Zone- 1-2 Check Valve 1 717H Grooved 03/29/2012

Wet Pipe, Zone- 2-1 Check Valve 1 717H Grooved 03/29/2012

Page of 31 31United Fire Protection - Atlanta Download Date: 05/20/2023

Zone Address Report Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 131 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID

Control Panel 1 M1-58 Pressure Switch Attic High Pressure Pressure Switch 44133577

M1-152 Waterflow Switch Ground North Zone B-1 Vane 44133567 M1-153 Control Valve Ground North Zone B-1 Butterfly 44133564 M1-153 Tamper Switch Ground North Zone B-1 Control Valve 86195019 M1-154 Waterflow Switch 1st North Zone 1-1 Vane 44133547 M1-155 Control Valve 1st North Zone 1-1 Butterfly 44133544 M1-155 Tamper Switch 1st North Zone 1-1 Control Valve 86195017 M1-156 Waterflow Switch 2nd North Zone 2-1 Vane 44133557 M1-157 Control Valve 2nd North Building 131 Zone 2-1 Butterfly 44133554 M1-157 Tamper Switch 2nd North Building 131 Zone 2-1 Control Valve 86195018 M1-159 Control Valve Attic Butterfly 44133574 M1-159 Tamper Switch Attic Control Valve 86195013 M1-160 Control Valve Ground South Zone B-2 Butterfly 44133569 M1-160 Tamper Switch Ground South Zone B-2 Control Valve 86195015 M1-161 Waterflow Switch Ground South Zone B-2 Vane 44133572 M1-162 Waterflow Switch 1st South Zone 1-2 Vane 44133552 M1-163 Control Valve 1st South Zone 1-2 Butterfly 44133549 M1-163 Tamper Switch 1st South Zone 1-2 Control Valve 86195014 M1-164 Waterflow Switch 2nd South Zone 2-2 Vane 44133562 M1-165 Control Valve 2nd South Zone 2-2 Butterfly 44133559 M1-165 Tamper Switch 2nd South Zone 2-2 Control Valve 86195016 javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133577');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133567');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133564');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195019');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133547');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133544');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195017');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133557');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133554');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195018');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133574');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195013');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133569');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195015');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133572');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133552');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133549');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195014');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133562');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133559');

javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195016');

Sprinkler Inspection, Testing and/or Maintenance Certificate
Executive Summary
Inspection & Testing
Service Summary
Wet Pipe Fire Sprinkler Systems
Dry Pipe Fire Sprinkler Systems
Inventory & Warranty Report
Zone Address Report