2023-05-18_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf
PDF 389 KB Posted
- Attached to
- Fire Sprinkler Testing
- Solicitation number
- 36C24724Q0269
About this file
This document is a fire sprinkler inspection report for Building 131 at the Fort McPherson VA Medical Center in Atlanta, Georgia. The report details inspection and testing of the building's wet pipe, dry pipe, and alarm systems conducted on May 18, 2023. It lists all devices by type and location, along with inspection results, component details, pressure readings, and response times. An inventory section specifies the models, installation dates, and warranty periods of the various valves, switches, gauges, sprinklers, and other equipment installed between March 2012 and May 2021. Address information and scan IDs are provided for individual devices.
The related federal contract opportunity is solicitation number 36C24724Q0269 for fire sprinkler testing services at the Fort McPherson VAMC. The solicitation was issued by the Department of Veterans Affairs Veterans Health Administration VISN 7. The inspection report would inform contractors' responses by detailing the existing systems and components requiring testing and maintenance under the contract. No further salient details are provided on the opportunity in the attached document.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sprinkler Inspection, Testing and/or Maintenance Certificate
For
Fort McPherson VAMC Bldg 131 1701 Hardee Ave SW
Atlanta, GA 30310 Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards effective January 31, 2021
Annual Inspection Inspection Completion Date May 18, 2023
Building: Fort McPherson VAMC Bldg 131 Company: United Fire Protection - Atlanta Contact: Mike McGill Contact: Wayne Huxtable
Title: Maintenance & Operations Supervisor Title: Technician
Page of 1 31United Fire Protection - Atlanta Download Date: 05/20/2023
Executive Summary Generated by: BuildingReports.com
Building Information Building: Fort McPherson VAMC Bldg 131 Contact: Mike McGill
Address: 1701 Hardee Ave SW Phone: 14043216111
Address: Fax:
City/State/ZIP Code: Atlanta, GA 30310 Mobile:
Country: United States of America Email:
Inspection Performed By Company: United Fire Protection - Atlanta Inspector: Wayne Huxtable
Address: 2150 Boggs Rd Bldg 100 Phone: 770-771-0999
Address: Suite 140 Fax:
City/State/ZIP Code: Duluth, GA 30096 Mobile:
Country: United States of America Email: whuxtable@united-fire.com
Page of 2 31United Fire Protection - Atlanta Download Date: 05/20/2023
Inspection Completion Date: May 18, 2023 Building: Fort McPherson VAMC Bldg 131 EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(b-g)
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Air Maintenance Device 1 1 0 1 0 1
Pressure Switch 2 2 0 2 0 2
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Tamper Switch 11 11 0 11 0 11
Waterflow Switch 6 6 0 6 0 6
EC 02.03.05 EP 09 Annual test of main drains at system low point or at all system risers. NFPA 25 (2020)
13.2.3 & 13.2.3.2
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Drain 1 1 0 1 0 1
LS 02.01.35 EP 07 At least six spare sprinkler heads that correspond to the types and temperature rating of the hospital's sprinkler heads, with associated wrenches, are kept in a cabinet that will not exceed 100F. NFPA 25-2020: 5.4.1
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Sprinkler Box 1 1 0 1 0 1
Sprinkler Box Spares 3 3 0 3 0 3
LS 02.01.35 EP 14 All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Air Compressor 1 1 0 1 0 1
Check Valve 7 7 0 7 0 7
Control Valve 11 11 0 11 0 11
Dry Pipe Valve 1 1 0 1 0 1
Gauge 8 8 0 8 0 8
Inspector's Test 6 6 0 6 0 6
Total Device Count: 59
Page of 3 31United Fire Protection - Atlanta Download Date: 05/20/2023
Certification
Company: United Fire Protection - Atlanta Building: Fort McPherson VAMC Bldg 131
Inspector: Wayne Huxtable Contact: Mike McGill
Page of 4 31United Fire Protection - Atlanta Download Date: 05/20/2023
Inspection & Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 131 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(b-g)
Automatic air pressure maintenance devices, if provided, shall be tested yearly at the time of the annual preaction or deluge valve trip test, in accordance with the manufacturer's instructions. (NFPA 25-20 13.4.3.2.13) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Air Maintenance Device 1 1 0 1 1
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Air Maintenance Device
Attic Supply Pressure 67977791 0 08/15-P 10/28-P 02/09-P 05/18-P
Device Total: 1 Return to Executive Summary
Page of 5 31United Fire Protection - Atlanta Download Date: 05/20/2023
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(b-g)
Operate switch and verify receipt of signal is obtained where the required pressure is increased or decreased a maximum 10 psi from the required pressure level. (NFPA 72-19 Table 14.4.3.2 (17)(9b)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Pressure Switch 2 2 0 2 2
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Pressure Switch Attic High Pressure 44133577 1-M1-58 08/15-P 10/28-P 02/09-P 05/18-P Pressure Switch Attic Low Pressure 44133586 1 08/15-P 10/28-P 02/09-P 05/18-P
Device Total: 2 Return to Executive Summary
Page of 6 31United Fire Protection - Atlanta Download Date: 05/20/2023
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Tamper Switch 11 11 0 11 11
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Tamper Switch 1st North Zone 1-1 86195017 1-M1-155 05/18-P Tamper Switch 1st South Zone 1-2 86195014 1-M1-163 05/18-P Tamper Switch 2nd North Building 131 Zone
2-1 86195018 1-M1-157 05/18-P
Tamper Switch 2nd South Zone 2-2 86195016 1-M1-165 05/18-P Tamper Switch Attic 86195013 1-M1-159 05/18-P Tamper Switch Sectional 86195012 1 05/18-P Tamper Switch Test Header 86195009 1 05/18-P Tamper Switch Test Header 86195010 1 05/18-P Tamper Switch Test Header 86195011 1 05/18-P Tamper Switch Ground North Zone B-1 86195019 1-M1-153 05/18-P Tamper Switch Ground South Zone B-2 86195015 1-M1-160 05/18-P
Device Total: 11 Return to Executive Summary
Page of 7 31United Fire Protection - Atlanta Download Date: 05/20/2023
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-19 Table
14.4.3.2 (17)(11)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Waterflow Switch 6 6 0 6 6
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Waterflow Switch 1st North Zone 1-1 44133547 1-M1-154 08/15-P 10/28-P 02/09-P 05/18-P Waterflow Switch 1st South Zone 1-2 44133552 1-M1-162 08/15-P 10/28-P 02/09-P 05/18-P Waterflow Switch 2nd North Zone 2-1 44133557 1-M1-156 08/15-P 10/28-P 02/09-P 05/18-P Waterflow Switch 2nd South Zone 2-2 44133562 1-M1-164 08/15-P 10/28-P 02/09-P 05/18-P Waterflow Switch Ground North Zone B-1 44133567 1-M1-152 08/15-P 10/28-P 02/09-P 05/18-P Waterflow Switch Ground South Zone B-2 44133572 1-M1-161 08/15-P 10/28-P 02/09-P 05/18-P
Device Total: 6 Return to Executive Summary
Page of 8 31United Fire Protection - Atlanta Download Date: 05/20/2023
EC 02.03.05 EP 09
Annual test of main drains at system low point or at all system risers. NFPA 25 (2020)
13.2.3 & 13.2.3.2
A main drain test shall be conducted annually for each water supply lead-in to a building water-based fire protection system to determine whether there has been a change in the condition of the water supply. (NFPA 25-20 13.2.3) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Drain 1 1 0 1 1
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Drain Attic Supply Pressure 44133579 0 08/15-P 10/28-P 05/18-P
Page of 9 31United Fire Protection - Atlanta Download Date: 05/20/2023
LS 02.01.35 EP 07
At least six spare sprinkler heads that correspond to the types and temperature rating of the hospital's sprinkler heads, with associated wrenches, are kept in a cabinet that will not exceed 100F. NFPA 25-2020: 5.4.1
A supply of at least six spare sprinklers shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. (NFPA 25-20 5.4.1.5) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Sprinkler Box 1 1 0 1 1
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Sprinkler Box Attic Air Pressure 44133584 0 08/15-P 10/28-P 05/18-P
Page of 10 31United Fire Protection - Atlanta Download Date: 05/20/2023
LS 02.01.35 EP 07
At least six spare sprinkler heads that correspond to the types and temperature rating of the hospital's sprinkler heads, with associated wrenches, are kept in a cabinet that will not exceed 100F. NFPA 25-2020: 5.4.1
A supply of at least six spare sprinklers shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. (NFPA 25-20 5.4.1.5) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Sprinkler Box Spares 3 3 0 3 3
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Sprinkler Box Spares Attic Air Pressure 67977846 0 08/15-P 10/28-P 05/18-P Sprinkler Box Spares Attic Air Pressure 67977847 0 08/15-P 10/28-P 05/18-P Sprinkler Box Spares Attic Air Pressure 67977848 0 08/15-P 10/28-P 05/18-P
Device Total: 3 Return to Executive Summary
Page of 11 31United Fire Protection - Atlanta Download Date: 05/20/2023
LS 02.01.35 EP 14
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Compressors used in conjunction with dry pipe sprinkler systems shall be maintained in accordance with the manufacturer's instructions. (NFPA 25-20 5.4.2.4) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Air Compressor 1 1 0 1 1
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Air Compressor Attic Low Pressure 44133585 0 08/15-P 10/28-P 02/09-P 05/18-P
Page of 12 31United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Internal components shall be cleaned, repaired, or replaced as necessary in accordance with the manufacturer's instructions. (NFPA 25-20 13.4.2.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Check Valve 7 7 0 7 7
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Check Valve 1st North Zone 1-1 44133545 1 08/15-P 10/28-P 05/18-P Check Valve 1st South Zone 1-2 44133550 1 08/15-P 10/28-P 05/18-P Check Valve 2nd North Zone 2-1 44133555 1 08/15-P 10/28-P 05/18-P Check Valve 2nd South Zone 2-2 44133560 1 08/15-P 10/28-P 05/18-P Check Valve Test Header 44133587 1 08/15-P 10/28-P 05/18-P Check Valve Ground North Zone B-1 44133565 1 08/15-P 10/28-P 05/18-P Check Valve Ground South Zone B-2 44133570 1 08/15-P 10/28-P 05/18-P
Device Total: 7 Return to Executive Summary
Page of 13 31United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Control Valve 11 11 0 11 11
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Control Valve 1st North Zone 1-1 44133544 1-M1-155 08/15-P 10/28-P 02/09-P 05/18-P Control Valve 1st South Zone 1-2 44133549 1-M1-163 08/15-P 10/28-P 02/09-P 05/18-P Control Valve 2nd North Building 131 Zone
2-1 44133554 1-M1-157 08/15-P 10/28-P 02/09-P 05/18-P
Control Valve 2nd South Zone 2-2 44133559 1-M1-165 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Attic 44133574 1-M1-159 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Sectional 44133583 1 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Test Header 44133580 1 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Test Header 44133581 1 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Test Header 44133582 1 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Ground North Zone B-1 44133564 1-M1-153 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Ground South Zone B-2 44133569 1-M1-160 08/15-P 10/28-P 02/09-P 05/18-P
Device Total: 11 Return to Executive Summary
Page of 14 31United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Each dry pipe valve shall be trip tested annually during warm weather. (NFPA 25-20 13.4.5.2.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Dry Pipe Valve 1 1 0 1 1
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Dry Pipe Valve Attic Supply Pressure 44133578 0 08/15-P 10/28-P 02/09-P 05/18-P Dry Pipe Valve 2 second floor Sprinkler room 13765 0 08/15-P 10/28-P 02/09-P 05/18
Removed
Page of 15 31United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. (NFPA 25- 20 13.2.5.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Gauge 8 8 0 8 8
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Gauge 1st North Zone 1-1 57780042 0 08/15-P 10/28-P 05/18-P Gauge 1st South Zone 1-2 57780045 0 08/15-P 10/28-P 05/18-P Gauge 2nd South Zone 2-1 57780043 0 08/15-P 10/28-P 05/18-P Gauge 2nd South Zone 2-2 57780046 0 08/15-P 10/28-P 05/18-P Gauge Attic Air Pressure 57780008 0 08/15-P 10/28-P 05/18-P Gauge Attic Supply Pressure 57780009 0 08/15-P 10/28-P 05/18-P Gauge Ground North Zone B-1 57780041 0 08/15-P 10/28-P 05/18-P Gauge Ground South Zone B-2 57780044 0 08/15-P 10/28-P 05/18-P
Device Total: 8 Return to Executive Summary
Page of 16 31United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Testing of pressure switch type waterflow alarm devices on wet pipe systems shall be accomplished by opening the inspector's test connection (NFPA 25-20 5.3.3.3) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Inspector's Test 6 6 0 6 6
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Inspector's Test 1st North Zone 1-1 44133548 0 08/15-P 10/28-P 02/09-P 05/18-P Inspector's Test 1st South Zone 1-2 44133553 0 08/15-P 10/28-P 02/09-P 05/18-P Inspector's Test 2nd North Zone 2-1 44133558 0 08/15-P 10/28-P 02/09-P 05/18-P Inspector's Test 2nd South Zone 2-2 44133563 0 08/15-P 10/28-P 02/09-P 05/18-P Inspector's Test Ground North Zone B-1 44133568 0 08/15-P 10/28-P 02/09-P 05/18-P Inspector's Test Ground South Zone B-2 44133573 0 08/15-P 10/28-P 02/09-P 05/18-P
Device Total: 6 Return to Executive Summary
Page of 17 31United Fire Protection - Atlanta Download Date: 05/20/2023
Service Summary Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 131 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Passed Air Compressor Annual 1 Air Maintenance Device Annual 1 Check Valve Annual 7 Control Valve Annual 11 Drain Annual 1 Dry Pipe Valve Annual 1 Gauge Annual 8 Inspector's Test Annual 6 Pressure Switch Annual 2 Sprinkler Box Spares Annual 3 Sprinkler Box Annual 1 Tamper Switch Annual 11 Waterflow Switch Annual 6
Total 59 Grand Total 59
Page of 18 31United Fire Protection - Atlanta Download Date: 05/20/2023
Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
Control Valve Supervisory Test Header 1 86195009 OS&Y Supervisory Test Header 1 86195010 OS&Y Supervisory Test Header 1 86195011 OS&Y Supervisory Sectional 1 86195012
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved Test Header 05/15/2021 4" 44133587
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Test Header 6" Open Supervised 44133580
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Test Header 6" Open Supervised 44133581
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Test Header 6" Open Supervised 44133582
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Sectional 6" Open Supervised 44133583 javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195009');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195010');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195011');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195012');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133587');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133580');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133581');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133582');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133583');
Page of 19 31United Fire Protection - Atlanta Download Date: 05/20/2023
Description Main Control
Building: Fort McPherson VAMC Bldg
Zone- 1-1
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
Control Valve Supervisory 1st North Zone 1-1 1-M1-155 86195017
Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 36.89 3" 1-M1-154 44133547
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved 1st North Zone 1-1 03/29/2018 3" 44133545
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Victaulic 705 1st North Zone 1-1
4" Open Supervised 44133544
Description Main Control
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1000 80 33 36.89 44133548
Location 1st North Zone 1-1
Devices Gauge
Location Service Date 1st North Zone 1-1 05/15/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 55 Air/Water 1/4 57780042
Building: Fort McPherson VAMC Bldg
Zone- 1-2
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195017');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133547');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133545');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133544');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133548');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780042');
Page of 20 31United Fire Protection - Atlanta Download Date: 05/20/2023 as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
Control Valve Supervisory 1st South Zone 1-2 1-M1-163 86195014
Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 35.30 3" 1-M1-162 44133552
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved 1st South Zone 1-2 05/15/2021 3" 44133550
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Victaulic 705 1st South Zone 1-2
4" Open Supervised 44133549
Description Main Control
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1000 80 28 35.30 44133553
Location 1st South Zone 1-2
Devices Gauge
Location Service Date 1st South Zone 1-2 05/15/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 55 Air/Water 1/4 57780045
Building: Fort McPherson VAMC Bldg
Zone- 2-1
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Tamper Switch
Number of Zone javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195014');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133552');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133550');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133549');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133553');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780045');
Page of 21 31United Fire Protection - Atlanta Download Date: 05/20/2023
Type Description Location Turns /Address OK ScanID Control Valve Supervisory 2nd North Building 131 Zone 2-1 1-M1-157 86195018
Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 33.92 3" 1-M1-156 44133557
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved 2nd North Zone 2-1 05/15/2021 3" 44133555
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Victaulic 705 2nd North Building 131 Zone 2-1
4" Open Supervised 44133554
Description Main Control
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1000 80 35 33.92 44133558
Location 2nd North Zone 2-1
Devices Gauge
Location Service Date 2nd South Zone 2-1 05/15/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 55 Air/Water 1/4 57780043
Building: Fort McPherson VAMC Bldg
Zone- 2-2
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
Control Valve Supervisory 2nd South Zone 2-2 1-M1-165 86195016
Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 31.97 3" 1-M1-164 44133562 javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195018');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133557');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133555');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133554');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133558');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780043');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195016');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133562');
Page of 22 31United Fire Protection - Atlanta Download Date: 05/20/2023
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved 2nd South Zone 2-2 03/29/2018 4" 44133560
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Victaulic 705 2nd South Zone 2-2
4" Open Supervised 44133559
Description Main Control
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1000 80 22 31.96999 44133563
Location 2nd South Zone 2-2
Devices Gauge
Location Service Date 2nd South Zone 2-2 05/15/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 55 Air/Water 1/4 57780046
Building: Fort McPherson VAMC Bldg
Zone- B-1
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
Control Valve Supervisory Ground North Zone B-1 1-M1-153 86195019
Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 39.06 3" 1-M1-152 44133567
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved Ground North Zone B-1 03/29/2018 3" 44133565
Control Valve javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133560');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133559');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133563');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780046');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195019');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133567');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133565');
Page of 23 31United Fire Protection - Atlanta Download Date: 05/20/2023
Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Victaulic 705 Ground North Zone B-1
4" Open Supervised 44133564
Description Main Control
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1000 80 41 39.06 44133568
Location Ground North Zone B-1
Devices Gauge
Location Service Date Ground North Zone B-1 05/15/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 55 Air/Water 1/4 57780041
Building: Fort McPherson VAMC Bldg
Zone- B-2
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
Control Valve Supervisory Ground South Zone B-2 1-M1-160 86195015
Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 39.69 3" 1-M1-161 44133572
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved Ground South Zone B-2 03/29/2018 3" 44133570
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Victaulic 705 Ground South Zone B-2
4" Open Supervised 44133569
Description Main Control javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133564');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133568');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780041');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195015');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133572');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133570');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133569');
Page of 24 31United Fire Protection - Atlanta Download Date: 05/20/2023
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1000 80 51 39.68999 44133573
Location Ground South Zone B-2
Devices Gauge
Location Service Date Ground South Zone B-2 05/15/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 55 Air/Water 1/4 57780044 javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133573');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780044');
Page of 25 31United Fire Protection - Atlanta Download Date: 05/20/2023
Dry Pipe Fire Sprinkler Systems Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Area- Attic
This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Air Compressor Location Mfr. Model # Phase On psi Off psi Serial No.
Attic Low Pressure General
Air
LT900150B 1 35 45 LT900- 12 56 07 46
Type Description Rated Speed Horsepower Volts Amps OK ScanID
Automatic Tank 1725 1.5 208 5.4 44133585
Air Maintenance Device Type Model # Location Install Date Air Pressure ScanID Pressure Reducing Attic Supply Pressure 03/29/2017 40 67977791
Alarms Pressure Switch Type Description Manufacturer Low High Zone/Address OK ScanID Pressure Switch Alarm Potter Electric 0 10 1-M1-58 44133577 Pressure Switch Alarm Potter Electric 10 40 1 44133586
Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
Control Valve Supervisory Attic 1-M1-159 86195013
Components Control Valve
Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 13765 Attic 4" Open Supervised 44133574
Description Main Control
Dry Pipe Valve Manufacturer Model # Location Internal Date OK ScanID Viking F-2 Attic Supply Pressure 03/29/2018 44133578
Type Status Position Size Serial # Grooved Sealed Trim Open 4" W552201 javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133585');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','67977791');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133577');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133586');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195013');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133574');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133578');
Page of 26 31United Fire Protection - Atlanta Download Date: 05/20/2023
Water psi Air Pressure Trip Air Trip Time Total Timing (sec)
Partial Trip Date
Full Trip Date
55 45 15 35.06 30 03/29/2017 05/18/2023
Devices Drain
Current Inspection
Type Location Size Supply psi Restored psi
Residual psi Sec OK ScanID
Main Attic Supply Pressure 2" 80 60 50 30 44133579
Previous Inspections
October 28, 2022
Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Attic Supply Pressure 2" 80 60 50 44133579
August 15, 2022
Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Attic Supply Pressure 2" 80 60 50 44133579
Gauge Location Service Date Attic Supply Pressure 05/15/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Lansdale 55 Air/Water 1/4 57780009
Gauge Location Service Date Attic Air Pressure 05/15/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID Air Pressure Lansdale 20 Air/Water 1/4 57780008
Building: Fort McPherson VAMC Bldg
Area- Attic and rest of the
This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Sprinkler Box
Qty Tool Available?
SIN List? Size Manufacturer Location OK ScanID
6 Yes 6 unit Viking Attic Air Pressure 44133584
Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID 3 Upright Viking Attic Air Pressure 67977846
Temperature KFactor Size Finish Response Time 290 1/2 Brass Fast Response javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133579');
javascript:openEditDevice('load-edit-p2-device','0','2686313','44133579');
javascript:openEditDevice('load-edit-p2-device','0','2603990','44133579');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780009');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','57780008');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133584');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','67977846');
Page of 27 31United Fire Protection - Atlanta Download Date: 05/20/2023
Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID 3 Upright Viking Attic Air Pressure 67977847
Temperature KFactor Size Finish Response Time 290 5.6 1/2 Brass Fast Response
Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID 3 Upright Tyco Attic Air Pressure 67977848
Temperature KFactor Size Finish Response Time 212 5.6 1/2 Brass Standard Response javascript:openEditDevice('load-edit-p2-device','736897','2902388','67977847');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','67977848');
Page of 28 31United Fire Protection - Atlanta Download Date: 05/20/2023
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 131 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Air Compressor Pump 1.69% 1
Air Maintenance Device Pump 1.69% 1
Check Valve Valve 11.86% 7
Control Valve Valve 18.64% 11
Drain Device 1.69% 1
Dry Pipe Valve Valve 1.69% 1
Gauge Device 13.56% 8
Inspector's Test Valve 10.17% 6
Pressure Switch Alarm 3.39% 2
Sprinkler Box Sprinkler 1.69% 1
Sprinkler Box Spares Sprinkler 5.08% 3
Tamper Switch Alarm 18.64% 11
Waterflow Switch Alarm 10.17% 6
Device Type Qty Model # Type Description Install Date
In Service - 2 Years to 3 Years Dry Pipe, Area- Attic
Gauge 1 Air Pressure 05/15/2021 Gauge 1 Supply Pressure 05/15/2021
Wet Pipe, Zone- 1-1 Gauge 1 System Pressure 05/15/2021
Wet Pipe, Zone- 1-2 Gauge 1 System Pressure 05/15/2021
Wet Pipe, Zone- 2-1 Gauge 1 System Pressure 05/15/2021
Wet Pipe, Zone- 2-2 Gauge 1 System Pressure 05/15/2021
Wet Pipe, Zone- B-1 Gauge 1 System Pressure 05/15/2021
Wet Pipe, Zone- B-2 Gauge 1 System Pressure 05/15/2021
In Service - 3 Years to 5 Years Dry Pipe, Area- Attic and rest of the
Page of 29 31United Fire Protection - Atlanta Download Date: 05/20/2023
Sprinkler Box 1 07/11/2018 Sprinkler Box Spares 1 VK 300 Upright 07/11/2018 Sprinkler Box Spares 1 VK 302 Upright 07/11/2018
In Service - 5 Years to 10 Years Dry Pipe, Area- Attic
Air Compressor 1 LT900150B Automatic Tank 03/29/2018 Pressure Switch 1 PS-10 Pressure Switch Alarm 03/29/2018 Pressure Switch 1 PS-40 Pressure Switch Alarm 03/29/2018 Control Valve 1 13765 Butterfly Main Control 03/29/2018 Tamper Switch 1 13765 Control Valve Supervisory 03/29/2018
Wet Pipe Control Valve 4 705 Butterfly Main Control 03/29/2018 Tamper Switch 1 705 Control Valve Supervisory 03/29/2018 Tamper Switch 3 705 OS&Y Supervisory 03/29/2018
Wet Pipe, Zone- 1-1 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Check Valve 1 717H Grooved 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018 Tamper Switch 1 705 Control Valve Supervisory 03/29/2018
Wet Pipe, Zone- 1-2 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018 Tamper Switch 1 705 Control Valve Supervisory 03/29/2018
Wet Pipe, Zone- 2-1 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018 Tamper Switch 1 705 Control Valve Supervisory 03/29/2018
Wet Pipe, Zone- 2-2 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Check Valve 1 717H Grooved 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018 Tamper Switch 1 705 Control Valve Supervisory 03/29/2018
Wet Pipe, Zone- B-1 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Check Valve 1 717H Grooved 03/29/2018
Page of 30 31United Fire Protection - Atlanta Download Date: 05/20/2023
Control Valve 1 705 Butterfly Main Control 03/29/2018 Tamper Switch 1 705 Control Valve Supervisory 03/29/2018
Wet Pipe, Zone- B-2 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Check Valve 1 717H Grooved 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018 Tamper Switch 1 705 Control Valve Supervisory 03/29/2018
Dry Pipe, Area- Attic Drain 1 Wika Main 03/29/2017 Air Maintenance Device 1 Pressure Reducing 03/29/2017 Dry Pipe Valve 1 F-2 Grooved 03/29/2017
In Service - 10 Years to 15 Years Dry Pipe, Area- Attic and rest of the
Sprinkler Box Spares 1 TY 3180 Upright 07/11/2012
Wet Pipe Check Valve 1 705 Grooved 03/29/2012
Wet Pipe, Zone- 1-2 Check Valve 1 717H Grooved 03/29/2012
Wet Pipe, Zone- 2-1 Check Valve 1 717H Grooved 03/29/2012
Page of 31 31United Fire Protection - Atlanta Download Date: 05/20/2023
Zone Address Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 131 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
Control Panel 1 M1-58 Pressure Switch Attic High Pressure Pressure Switch 44133577
M1-152 Waterflow Switch Ground North Zone B-1 Vane 44133567 M1-153 Control Valve Ground North Zone B-1 Butterfly 44133564 M1-153 Tamper Switch Ground North Zone B-1 Control Valve 86195019 M1-154 Waterflow Switch 1st North Zone 1-1 Vane 44133547 M1-155 Control Valve 1st North Zone 1-1 Butterfly 44133544 M1-155 Tamper Switch 1st North Zone 1-1 Control Valve 86195017 M1-156 Waterflow Switch 2nd North Zone 2-1 Vane 44133557 M1-157 Control Valve 2nd North Building 131 Zone 2-1 Butterfly 44133554 M1-157 Tamper Switch 2nd North Building 131 Zone 2-1 Control Valve 86195018 M1-159 Control Valve Attic Butterfly 44133574 M1-159 Tamper Switch Attic Control Valve 86195013 M1-160 Control Valve Ground South Zone B-2 Butterfly 44133569 M1-160 Tamper Switch Ground South Zone B-2 Control Valve 86195015 M1-161 Waterflow Switch Ground South Zone B-2 Vane 44133572 M1-162 Waterflow Switch 1st South Zone 1-2 Vane 44133552 M1-163 Control Valve 1st South Zone 1-2 Butterfly 44133549 M1-163 Tamper Switch 1st South Zone 1-2 Control Valve 86195014 M1-164 Waterflow Switch 2nd South Zone 2-2 Vane 44133562 M1-165 Control Valve 2nd South Zone 2-2 Butterfly 44133559 M1-165 Tamper Switch 2nd South Zone 2-2 Control Valve 86195016 javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133577');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133567');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133564');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195019');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133547');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133544');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195017');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133557');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133554');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195018');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133574');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195013');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133569');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195015');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133572');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133552');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133549');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195014');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133562');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','44133559');
javascript:openEditDevice('load-edit-p2-device','736897','2902388','86195016');
| Sprinkler Inspection, Testing and/or Maintenance Certificate |
| Executive Summary |
| Inspection & Testing |
| Service Summary |
| Wet Pipe Fire Sprinkler Systems |
| Dry Pipe Fire Sprinkler Systems |
| Inventory & Warranty Report |
| Zone Address Report |
File details come from the government source that posted it. Updated .