04 Series DOORS - 100 AT-128 Fort McPherson Homeless Program.pdf

PDF 1 MB Posted

Attached to
Fire Sprinkler Testing Federal contract opportunity
Solicitation number
36C24724Q0269
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7

About this file

This document package includes life safety drawings and a fire sprinkler testing solicitation. The drawings depict an existing VA medical center building and detail fire and smoke barriers, occupancy classifications, egress components, and fire door inspections. The solicitation seeks quarterly fire sprinkler inspections and testing in accordance with NFPA 25. Offerors must have a minimum of five years experience performing sprinkler inspections and testing for medical facilities. The period of performance is one base year with four option years. The location of work is VISN 7 facilities in Alabama, Florida, Georgia, and South Carolina. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7 is the contracting agency.

View the file

Other files for this federal contract opportunity

Other files attached to Fire Sprinkler Testing, newest first.
File Type Posted
FIRE ALARM 130.pdf PDF
2022-06-20_Fort-McPherson-VAMC-Bldg-128_Annual Report.pdf PDF
FIRE ALARM 129.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
Ft. McPherson Bldg 128 Fire Alarm Drawings - RECORD Dwg.pdf PDF
FIRE SUPPRESSION.pdf PDF
BLDG 131 ASBUILTS.pdf PDF
2022-06-20_Fort-McPherson-VAMC-Bldg-129_Annual Report.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-125_SprinklerScan.pdf PDF
BLDG 125 ASBUILT.pdf PDF
Bldg 128 As-Builts.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-131_Annual Report.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-128_SprinklerScan.pdf PDF
03 Series LIFE SAFETY - 100 AT-125 Fort McPherson OPC.pdf PDF
03 Series LIFE SAFETY - 100 AT-128 Fort McPherson Homeless Program.pdf PDF
BLDG 129 ASBUILT.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-125_SprinklerScan.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-130_Annual Report.pdf PDF
2023-02-10_Fort-McPherson-VAMC-Bldg-128_SprinklerScan (1).pdf PDF
BLDG. 125 FIRE SUPPRESSION.pdf PDF
04 Series DOORS - 100 AT-131 Fort McPherson Domiciliary Care.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-129_SprinklerScan.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
36C24724Q0269 0001.pdf PDF
FIRE SUPPRESSION 131.pdf PDF
03 Series LIFE SAFETY - 100 AT-131 Fort McPherson Domiciliary Care.pdf PDF
05 series dampers - 100 at-125 fort mcpherson opc.pdf PDF
04 Series DOORS - 100 AT-130 Fort McPherson Residental Treatment.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-125_Annual Report.pdf PDF
FIRE ALARM 125.pdf PDF
03 Series LIFE SAFETY - 100 AT-130 Fort McPherson Residental Treatment.pdf PDF
04 Series DOORS - 100 AT-125 Fort McPherson OPC.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-128_SprinklerScan.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
36C24724Q0269.pdf PDF
Show all 38

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INDEX OF DRAWINGSVICINITY MAP PROJECT TEAMBUILDING SUMMARYANNOTATION DRAWING SYMBOLS

OWNER

Department of Veterans Affairs Tuscaloosa VA Medical Center 3701 Loop Road East Tuscaloosa AL 35404-5088

PROJECT MANAGER

Romanyk Consulting 3308 Preston Road, Suite 350-164 Plano, TX 75093

Sherri Mitchell, Contracting Officer Sherri.mitchell@va.gov

334-272-4670, ext 2238

Joshua Leow, COR Joshua.leow@va.gov

Elijah Knight, PE, MSEM elijah.knight@romanykconsulting.com

855-424-3838 ext.323 405-640-1586 cell

MECHANICAL ENGINEER

PROJECT ARCHITECT

John Slattery, RA john.slattery@romanykconsulting.com

855-424-3838 ext.336 918-430-6020 cell

Brad Cain, PE brad.cain@romanykconsulting.com

855-424-3838 ext.335 864-908-8304 cell

Romanyk Consulting 3308 Preston Road, Suite 350-164 Plano, TX 75093

Romanyk Consulting 3308 Preston Road, Suite 350-164 Plano, TX 75093

LIFE SAFETY ENGINEER

Frank Van Overmeiren fvanovermeiren@fpc-consultants.com

317-486-5188 ext.13

FP&C Consultants, Inc.

1520 Main Street Indianapolis, IN 46224

ROOM NAME

ROOM NAME / NUMBER

NORTH ARROW

NORTH ARROW WITH TRUE

NORTH INDICATION

Name Elevation

FLOOR LEVEL &

NAME

SHEET KEYNOTE1

XXX-XXXX-XX-XXXXX DOOR TAG

1 SHEET KEYNOTE

XXX-XXX-XX-XXXXX

WALL

PENETRATION TAG

XXX-XXX-XX-DPXXX DAMPER TAG

The A/E team, including architects, engineers, surveyors, and professional consultants shall survey and inspect the following VISN 7 VA Medical Center for Life safety deficiencies according to 2015 NFPA 101 Life Safety Code and Joint Commission Standard LS.01.01.01, EP 2 and provide comprehensive as-built Life Safety Plans (LSP)

SCOPE OF WORK SUMMARY:

• Tuskegee

• Montgomery

Team shall provide a list of discrepancies based off their findings and provide recommended methods for corrections. Team shall also update the facilities current life/fire safety plans to reflect existing as-built conditions based off the survey. Team shall also survey the facility to locate existing fire dampers and provide accurate as-built drawings.

A/E shall assume all areas of the campus are, and must remain fully operational, and that inspections may require coordination with the Owner for after-hours access, accompanied access and protected access (for medically sensitive areas, etc.), and shall include all such work as part of the A/E Scope of Work (SOW).

Life Safety inspection shall include the following. Inspecting all fire walls (including doors, door frames, and hardware) smoke walls, locations of all fire extinguishers, smoke detectors, smoke compartments, and exit signs.

A/E shall reference NFPA 101 and other NFPA applicable codes and provide the follow for each deliverable.

• Columbia

• Atlanta

• Augusta UD

• Augusta DD

• Dublin

• Charleston

FIRE/SMOKE DOORS - DRAWING LIST

LS0101A

LEVEL

DISCIPLINE

SECTION LETTER

WITHIN LEVEL

SERIES

01 SERIES = TJC DRAWINGS

02 SERIES = WALL PENETRATION DEFICIENCY DRAWINGS

03A SERIES = LIFE SAFETY DRAWINGS

03B SERIES = EXIT AND OCCUPANCY DRAWINGS

04 SERIES = FIRE/SMOKE DOOR DRAWINGS

05 SERIES = FIRE/SMOKE DAMPER DRAWINGS

' 6

G ra p h ic S ca le

/2

1'

-0

G ra p h ic S ca le

/3 2"

'-0

' G ra p h ic S ca le

/1 6"

'-0

' G ra p h ic

S ca le

/8

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

/8

1'

-0

' G ra p h ic

S ca le

/2

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

'-0

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

VISN 7 LIFE SAFETY SURVEY AND

DRAWING UPDATE, TASK ORDER

#13

GS-10F-0347P

Elijah Knight, PE

VISN 7 LIFE SAFETY SURVEY AND DRAWING UPDATE

BPA ORDER NO. VA247-14-A-0028 - TASK ORDER #13

EE

ES

S

OF

M

R C

D

T

T T

II

N

U A

A A

V

RAP

M

N

T

T

OF

E E

D

R S

I

FA

A

N T

S R

F

AEE

2017 LIFE SAFETY DOCUMENTATION

FINAL

Contract: GS-10F-0347P Task Order: VA247-17-F-2259

R R o m a n y k C o n s u lt in g \R

C C

A E

C

C o n s u lt in g \0

P ro je c ts

\V

IS

N

\L if e

S a fe ty \0

M o d e l\

A tl a n ta \B u ild in g s S u rv e y e d

\A T

-1

F o rt M c P h e rs o n

H o m e le s s P ro g ra m \A

T -1

F o rt

M c P h e rs o n H o m e le s s P ro g ra m

.r v t

/1

/2

:0

:0

A

M

COVER

E.K. HP

G-04

VISN 7 ATLANTA

07/31/2018

VISN 7

ATLANTA

Building 128 - FT McPHERSON - HOMELESS PROGRAM

100% SUBMITTAL

04 - GENERAL

G-04 COVER

G-04X1 GENERAL SHEET

G-04X2 GENERAL SHEET

04 - FIRE/SMOKE DOOR

LS0401 FIRE/SMOKE DOOR INSPECTION FLOOR PLAN - LEVEL 01

LS0402 FIRE/SMOKE DOOR INSPECTION FLOOR PLAN - LEVEL 02

Grand total: 5

FIRE/SMOKE DOORS

Prepared for:

100% Submission for

Fort McPherson VA Clinic Atlanta, GA

Revisions: Date:

l lllllll

OO OO O O ∅ ∅∅ ∅ ∅

' 6

G ra p h ic S ca le

/2

1'

-0

G ra p h ic S ca le

/3 2"

'-0

' G ra p h ic S ca le

/1 6"

'-0

' G ra p h ic

S ca le

/8

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

/8

1'

-0

' G ra p h ic

S ca le

/2

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

'-0

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

VISN 7 LIFE SAFETY SURVEY AND

DRAWING UPDATE, TASK ORDER

#13

GS-10F-0347P

Elijah Knight, PE

R R o m a n y k C o n s u lt in g \R

C C

A E

C

C o n s u lt in g \0

P ro je c ts

\V

IS

N

\L if e

S a fe ty \0

M o d e l\

A tl a n ta \B u ild in g s S u rv e y e d

\A T

-1

F o rt M c P h e rs o n

H o m e le s s P ro g ra m \A

T -1

F o rt

M c P h e rs o n H o m e le s s P ro g ra m

.r v t

/1

/2

:0

:0

A

M

GENERAL SHEET

E.K. HP

G-04X1

VISN 7 ATLANTA

07/31/2018

VISN 7

ATLANTA

100% SUBMITTAL

Revisions: Date:

THIS APPLIES TO OCCUPANCY SEPARATION WALLS, HORIZONTAL EXITS, AND

STAIRWELLS OF 4 OR MORE STORIES.

WALL: WALL EXTENDS FROM FLOOR TO DECK ABOVE.

DUCTS: ALL DUCT PENETRATIONS ARE PROTECTED BY FIRE DAMPERS.

PENETRATIONS: ALL NEW PENETRATIONS ARE SEALED WITH LISTED FIRESTOP

MATERIALS FOR PROTECTING 2-HOUR WALL ASSEMBLIES. WALL

PENETRATIONS ARE REQUIRED TO BE FILLED ON BOTH SIDES OF THE

WALL. FLOOR PENETRATIONS ARE ONLY REQUIRED TO BE FILLED ON

THE TOP OF THE FLOOR.

DOORS: ALL DOORS REQUIRE THE FOLLOWING:

1. LABELED FRAMES (NFPA 80 4.2.1)

2. LABELED 1 1/2 HOUR DOOR (NFPA 80 4.3.1)

3. MAXIMUM 100 SQ. IN. WINDOW (NFPA 80 4.4.5)

4. POSITIVE LATCHING (NFPA 80 6.4.1.4)

5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 80 6.4.1)

6. COORDINATING DEVICES REQUIRED (NFPA 80 6.4.1.2.1)

7. MAXIMUM 1/8" GAP (NFPA 80 6.3.1.7.3)

8. MAXIMUM 3/4" UNDERCUT (NFPA 80 4.8.4.1)

9. MAXIMUM 16" PROTECTIVE PLATE (NFPA 80 6.4.5.1)

10. SWING IN PRIMARY DIRECTION OF TRAVEL (NFPA 101 18/19.2.2.2).

11. PERIODIC INSPECTION AND TESTING SHALL BE PERFORMED AT AT

LEAST ANNUALLY (NFPA 80 5.2.4.1)

2-HOUR FIRE BARRIER

THIS APPLIES TO 1-HOUR FIRE RATED OCCUPANCY SEPERATIONS, HAZARDOUS ROOM

ENCLOSURES AND STAIRWELLS 3 STORIES OR LESS.

WALL: WALL EXTENDS FROM FLOOR TO DECK ABOVE.

DUCTS: STEEL DUCT PENETRATIONS NOT REQUIRED TO BE PROTECTED BY

FIRE DAMPERS.

PENETRATIONS: ALL NEW PENETRATIONS ARE SEALED WITH LISTED FIRESTOP

MATERIALS FOR PROTECTING 1-HOUR WALL ASSEMBLIES. WALL

PENETRATIONS ARE REQUIRED TO BE FILLED ON BOTH SIDES OF THE

WALL. FLOOR PENETRATIONS ARE ONLY REQUIRED TO BE FILLED ON

THE TOP OF THE FLOOR.

DOORS*: ALL DOORS REQUIRE THE FOLLOWING:

1. LABELED FRAMES (NFPA 80 4.2.1)

2. LABELED 3/4 OR 1-HOUR DOOR (NFPA 80 4.3.1)*

3. MAXIMUM 100 SQ. IN. WINDOW (NFPA 80 4.4.5)

4. POSITIVE LATCHING (NFPA 80 6.4.1.4)

5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 80 6.4.1)

6. COORDINATING DEVICES REQUIRED (NFPA 80 6.4.1.2.1)

7. MAXIMUM 1/8" GAP (NFPA 80 6.3.1.7.3)

8. MAXIMUM 3/4" UNDERCUT (NFPA 80 4.8.4.1)

9. MAXIMUM 16" PROTECTIVE PLATE (NFPA 80 6.4.5.1)

10. SWING IN PRIMARY DIRECTION OF TRAVEL (NFPA 101 18/19.2.2.2).

11.PERIODIC INSPECTION AND TESTING SHALL BE PERFORMED AT

AT LEAST ANNUALLY (NFPA 80 5.2.4.1)

* 1-HOUR DOORS ARE REQUIRED IN STAIRWELLS THAT ARE 3

STORIES OR LESS.

1-HOUR FIRE BARRIER

WALL: IF THE HAZARDOUS ROOM HAS A SUSPENDED CEILING CONSTRUCTED

TO LIMIT TRANSFER OF SMOKE, THE WALL HAS NO FIRE RESISTANCE

RATING AND MAY TERMINATE AT THE CEILING. IF THE ROOM DOES NOT

HAVE A SUSPENDED CEILING, THE WALL HAS NO FIRE RESISTANCE

RATING AND SHALL EXTEND TO THE DECK ABOVE.

DUCTS: STEEL DUCT PENETRATIONS ARE NOT REQUIRED TO BE PROTECTED

BY FIRE DAMPERS OR SMOKE DAMPERS.

PENETRATIONS: SEALED WITH NON-FIRE-RATED MATERIALS TO BE RESISTIVE. USE OF

LISTED FIRESTOP MATERIALS IS NOT REQUIRED.

DOORS: EXISTING HAZARDOUS ROOMS:

1. NON-LABELED FRAME (NFPA 101 19.3.7.9)

2. 20 MINUTE OR SOLID WOOD CORE (NFPA 101 19.3.7.6)

3. MAXIMUM 1296 SQ. IN. WINDOW (NFPA 101 19.3.6.3.17)

4. POSITIVE LATCHING NOT REQUIRED (NFPA 101 19.3.6.3.5)

5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 101 19.3.2.1.3)

6. MAXIMUM 1/8" GAP (NFPA 101 19.3.6.3.1)

7. MAXIMUM 1" UNDERCUT (NFPA 101 19.3.6.3.4)

8. MAXIMUM 48" PROTECTIVE PLATE (NFPA 101 19.3.2.1.2)

9. SWING IN ANY DIRECTION

10.SMOKE DOOR ASSEMBLIES SHALL BE TESTED AT LEAST

ANNUALLY (NFPA 105 5.2.1.1)

SMOKE RESISTIVE HAZARDOUS ROOMS

THIS APPLIES TO OCCUPANCY SEPARATION WALLS, HORIZONTAL EXITS, AND STAIRWELLS

OF 4 OR MORE STORIES. THIS COMBINATION WALL IS WHERE A PORTION OF THE 2-HOUR

RATED WALL IS ALSO PART OF THE SMOKE WALL.

WALL: WALL EXTENDS FROM FLOOR TO DECK ABOVE.

DUCTS: ALL DUCT PENETRATIONS ARE PROTECTED BY COMBINATION FIRE

AND SMOKE DAMPERS. SMOKE DAMPERS ARE NOT REQUIRED

WHERE ADJACENT SMOKE COMPARTMENTS ARE PROTECTED BY

QUICK RESPONSE SPRINKLERS THROUGHOUT EACH COMPARTMENT.

PENETRATIONS: ALL NEW PENETRATIONS ARE SEALED WITH LISTED FIRESTOP

MATERIALS FOR PROTECTING 2-HOUR WALL ASSEMBLIES. WALL

PENETRATIONS ARE REQUIRED TO BE FILLED ON BOTH SIDES OF THE

WALL. FLOOR PENETRATIONS ARE ONLY REQUIRED TO BE FILLED ON

THE TOP OF THE FLOOR.

DOORS: ALL DOORS REQUIRE THE FOLLOWING:

1. LABELED FRAMES (NFPA 80 4.2.1)

2. LABELED 1 1/2 HOUR DOOR (NFPA 80 4.3.1)

3. MAXIMUM 100 SQ. IN. WINDOW (NFPA 80 4.4.5)

4. POSITIVE LATCHING (NFPA 80 6.4.1.4)

5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 80 6.4.1)

6. COORDINATING DEVICES REQUIRED (NFPA 80 6.4.1.2.1)

7. MAXIMUM 1/8" GAP (NFPA 80 6.3.1.7.3)

8. MAXIMUM 3/4" UNDERCUT (NFPA 80 4.8.4.1)

9. MAXIMUM 16" PROTECTIVE PLATE (NFPA 80 6.4.5.1)

10.SWING IN PRIMARY DIRECTION OF TRAVEL (NFPA 101 18/19.2.2.2).

11.PERIODIC INSPECTION AND TESTING SHALL BE PERFORMED AT

AT LEAST ANNUALLY (NFPA 80 5.2.4.1)

2-HOUR FIRE AND SMOKE BARRIER

SUBSTANTIAL WALLS AND DOORS TO DIVIDE EACH FLOOR INTO COMPARTMENTS FOR

DEFEND IN PLACE EMERGENCY OPERATIONS. IF THE SMOKE ZONE BARRIER WALL IS OF

MASONRY, GYPSUM BOARD, OR METAL LATH AND PLASTER CONSTRUCTION, AND THE

BARRIER WAS CONSTRUCTED POST 1948, THE SMOKE ZONE BARRIER WALLS ARE

REQUIRED TO BE OF 1 HOUR FIRE RESISTANCE RATING. (NFPA 101, 18.3.2.7.5) SMOKE ZONE

BARRIER WALLS OF WOOD LATH AND PLASTER CONSTRUCTION ARE PERMITTED TO BE OF

A 1/2 HOUR FIRE RESISTANCE RATING (NFPA 101, 19.3.7.3)

WALL: WALL EXTENDS FROM FLOOR TO DECK ABOVE.

DUCTS: ALL DUCT PENETRATIONS ARE PROTECTED BY SMOKE DAMPERS.

SMOKE DAMPERS ARE NOT REQUIRED WHERE ADJACENT SMOKE

COMPARTMENTS ARE PROTECTED BY QUICK RESPONSE SPRINKLERS

THROUGHOUT EACH COMPARTMENT.

PENETRATIONS: ALL PENETRATIONS ARE SEALED WITH LISTED FIRESTOP MATERIALS

FOR PROTECTING 1-HOUR FIRE AND SMOKE WALL ASSEMBLIES.

PENETRATIONS ARE TO BE FILLED ON BOTH SIDES OF THE WALL.

DOORS: ALL DOORS FOR SMOKE BARRIERS REQUIRE THE FOLLOWING:

1. NON-LABELED FRAME (NFPA 101 18.3.7.6)

2. 20 MINUTE OR SOLID WOOD CORE (NFPA 101 18.3.7.6)

3. MAXIMUM 1296 SQ. IN. WINDOW (NFPA 80 4.4.4)

4. POSITIVE LATCHING NOT REQUIRED (NFPA 101 18.3.7.8)

5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 101 18.3.7.8)

6. MAXIMUM 1/8" GAP (NFPA 101 18.3.7.6.)

7. MAXIMUM 1" UNDERCUT (NFPA 101 19.3.6.3.4)

8. MAXIMUM 48" PROTECTIVE PLATE (NFPA 101 18.3.7.6)

9. SWING IN DIRECTION OPPOSITE OF EACH OTHER (NFPA 101 18.3.7.6)

10.SMOKE DOOR ASSEMBLIES SHALL BE TESTED AT LEAST ANNUALLY

(NFPA 105 5.2.1.1)

SMOKE ZONE BARRIERS

IF THE SMOKE COMPARTMENT IS SPRINKLERED, THE WALL SHALL FORM A BARRIER TO LIMIT THE TRANSFER OF SMOKE. THE WALL HAS NO REQUIRED FIRE RESISTANCE RATING AND MAY TERMINATE AT A CEILING CONSTRUCTED TO LIMIT TRANSFER OF SMOKE. DOORS ARE MANUALLY CLOSED IN AN EMERGENCY NFPA 101, 18.3.6.2 & 19.3.6.2

IF THE SMOKE COMPARTMENT IS NOT SPRINKLERED, THE WALL SHALL BE CONTINUOUS FROM THE FLOOR TO THE UNDERSIDE OF THE FLOOR OR ROOF DECK ABOVE. CORRIDOR WALL SHALL HAVE A MINIMUM 1/2 HOUR FIRE RESISTANCE RATING. DOORS ARE MANUALLY CLOSED IN AN EMERGENCY NFPA 101 19.3.6.2

DOORS: DOORS THAT ARE NOT PART OF A RATED WALL:

1. NON-LABELED FRAME (NFPA 101 18.3.6.3.1, 19.3.6.3 & 19.3.6.3.3)

2. NON-RATED DOORS PERMITTED IF SPRINKLERED (NFPA 101 18.3.6.3.1, 19.3.6.3.2(2))

3. 20-MINUTE OR SOLID WOOD CORE DOOR IF NOT SPRINKLERED (NFPA 101 19.3.6.3.1)

4. POSITIVE LATCHING EXCEPT TOILETS, SHOWER AND SINK

CLOSETS (NFPA 101 18.3.6.3.6 & 19.3.6.3.6)

5. SELF-CLOSING NOT REQUIRED (NFPA 101 19.3.6.3.11)

6. NO MAXIMUM GAP (NFPA 101 18.3.6.3.1 & 19.3.6.3.3)

7. MAXIMUM 1" UNDERCUT (NFPA 101 18.3.6.3.1 & 19.3.6.3.4)

8. MAXIMUM 48" PROTECTIVE PLATE (NFPA 101 18/19.3.6.3.12)

9. TRANSFER GRILLS NOT PERMITTED EXCEPT TOILETS, SHOWER AND SINK CLOSETS

(NFPA 101 18/19.3.6.4)

10. SWING IN ANY DIRECTION

11. SMOKE DOOR ASSEMBLIES SHALL BE TESTED AT LEAST ANNUALLY (NFPA 105 5.2.1.1)

HEALTH CARE OCCUPANCY CORRIDORS

NOTE: ALL CODE REFERENCES ARE PER THE 2015 EDITION OF NFPA 101 LIFE SAFETY CODE AND THE OTHER APPLICABLE CODES. FEDERAL FACILITIES FOLLOW 2015 LIFE SAFETY CODE.

FORMER DECOMMISSIONED SMOKE BARRIER RETAINED AS FIRE ALARM/SPRINKLER ZONE.

BUILDING OCCUPANTS PERMITTED TO DEFEND IN PLACE UNTIL DIRECTED BY THE FIRE

DEPARTMENT PER SECTION 15.7.4.3 OF NFPA 99-2015 EDITION AND PRIVATE MODE AUDIBLE

REQUIREMENTS OF SECTION 18.4:4 OF NFPA 72-2016 EDITION.

WALL: WALL EXTENDS FROM FLOOR TO SUSPENDED CEILING OR DECK ABOVE.

DUCTS: NO MINIMUM REQUIREMENTS.

PENETRATIONS: NO MINIMUM REQUIREMENTS FOR WALL PENETRATIONS ABOVE A

SUSPENDED CEILING. PENETRATIONS BELOW A SUSPENDED CEILING

OR DECK SEALED WITH NON-FIRE-RATED MATERIALS TO BE SMOKE

RESISTIVE.

DOORS: NON-FIRE-RATED DOORS AND FRAMES SELF CLOSING OR AUTOMATIC

CLOSING IN AN EMERGENCY.

NON-RATED SMOKE PARTITION

SUITES

HEALTHCARE AREA OPEN TO CORRIDOR WITH 24/7 SUPERVISION - NO SMOKE DETECTION REQUIRED.

HEALTHCARE AREA OPEN TO CORRIDOR - SMOKE DETECTION PROVIDED.

(COLOR #3) (COLOR #4) (COLOR #230)

(COLOR #1) (COLOR #6) (COLOR #30)

(COLOR #2)

(COLOR #2)

(COLOR #3)

' 6

G ra p h ic S ca le

/2

1'

-0

G ra p h ic S ca le

/3 2"

'-0

' G ra p h ic S ca le

/1 6"

'-0

' G ra p h ic

S ca le

/8

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

/8

1'

-0

' G ra p h ic

S ca le

/2

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

'-0

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

VISN 7 LIFE SAFETY SURVEY AND

DRAWING UPDATE, TASK ORDER

#13

GS-10F-0347P

Elijah Knight, PE

R R o m a n y k C o n s u lt in g \R

C C

A E

C

C o n s u lt in g \0

P ro je c ts

\V

IS

N

\L if e

S a fe ty \0

M o d e l\

A tl a n ta \B u ild in g s S u rv e y e d

\A T

-1

F o rt M c P h e rs o n

H o m e le s s P ro g ra m \A

T -1

F o rt

M c P h e rs o n H o m e le s s P ro g ra m

.r v t

/1

/2

:0

:0

A

M

GENERAL SHEET

E.K. HP

G-04X2

VISN 7 ATLANTA

07/31/2018

VISN 7

ATLANTA

100% SUBMITTAL

Revisions: Date:

APPLICABLE CODES AND STANDARDS:

1. THE BUILDING WAS DESIGNED TO THE 1960 EDITION OF NFPA 101, LIFE SAFETY CODE.

2. THE 1960 PUBLIC BUILDING AMENDMENT ACT (PL100-678) REQUIRES ALL FEDERAL AGENCIES TO FOLLOW

THE LATEST EDITIONS OF NATIONALLY RECOGNIZED FIRE AND LIFE SAFETY CODES. THE VA HAS ADOPTED THE NATIONAL FIRE CODES PUBLISHED BY THE NATIONAL FIRE PROTECTION ASSOCIATION. LIFE SAFETY REQUIREMENTS ARE SPECIFICALLY ADDRESSED IN THE 2018 EDITION OF NFPA 101, LIFE SAFETY CODE.

3. ALL NEW CONSTRUCTION OR BUILDING RENOVATIONS ARE REQUIRED TO COMPLY WITH THE LATEST EDITION OF NFPA 101 OR IT'S REFERENCED STANDARDS. EXISTING BUILDING CONDITIONS ARE REQUIRED TO COMPLY WITH THE APPLICABLE CODES OR STANDARDS AT THE TIME OF BUILDING DESIGN AND THE APPLICABLE PROVISIONS FOR EXISTING BUILDINGS IN CURRENT EDITIONS OF APPLICABLE

CODES AND STANDARDS.

4. OTHER NFPA CODES AND STANDARDS:

A. NFPA 10 - PORTABLE FIRE EXTINGUISHERS, 2018 EDITION.

B. NFPA 13 - SPRINKLER SYSTEMS, 2016 EDITION.

C. NFPA 14 - STANDPIPE SYSTEMS, 2016 EDITION.

D. NFPA 20 - FIRE PUMPS, 2016 EDITION

E. NFPA 70 - NATIONAL ELECTRIC CODE, 2017 EDITION.

F. NFPA 72 - NATIONAL FIRE ALARM CODE, 2016 EDITION.

G. NFPA 75 - ELECTRONIC COMPUTER EQUIPMENT, 2017 EDITION.

H. NFPA 80 - FIRE DOORS, 2016 EDITION.

I. NFPA 90A&B - HEATING AND AIR CONDITIONING SYSTEMS, 2018 EDITION.

J. NFPA 96 - COMMERCIAL COOKING EQUIPMENT, 2017 EDITION.

K. NFPA 99 - HEALTH CARE FACILITIES CODE, 2018 EDITION.

L. NFPA 105 - SMOKE DOORS, 2016 EDITION.

M. NFPA 110 - EMERGENCY POWER SYSTEMS, 2016 EDITION.

N. NFPA 241 - CONSTITUTION AND DEMOLITION, 2013 EDITION.

PENETRATIONS:

1. PRIOR TO THE EARLY 1990'S, THE STANDARD INDUSTRY PRACTICE FOR THE SEALING OF PENETRATIONS WAS TO

USE THE SAME CONSTRUCTION MATERIALS AS HOW THE WALL/FLOOR WAS CONSTRUCTED. CONCRETE PATCH WAS USED FOR CONCRETE FLOORS. MORTAR JOINT COMPOUND WAS USED FOR MASONRY WALLS. GYPSUM

PATCH COMPOUND WAS USED USED FOR GYPSUM WALLS.

2. PRIOR TO THE EARLY 1990'S, THE MANUFACTURES PUBLISHED INSTRUCTIONS FOR FIRE RESISTIVE WALL AND FLOOD CONSTRUCTION REQUIRED THE USE OF THE SAME CONSTRUCTION MATERIALS AS HOW THE WALL/FLOOR

WAS CONSTRUCTED TO SEAL PENETRATIONS.

3. THE FIRST LISTINGS OF FIRESTOP MATERIALS WAS IN 1991. THE FIRST CODE REQUIREMENTS TO UTILIZE LISTED

FIRESTOP MATERIALS OCCURRED IN 1992 EDITIONS OF CODES AND STANDARDS.

4. ALL PENETRATIONS ARE SEALED WITH LISTED FIRESTOP MATERIALS FOR PROTECTING THE REQUIRED RATING

OF THE WALL ASSEMBLY.

5. EXISTING PENETRATIONS SEALED WITH THE SAME CONSTRUCTION MATERIAL AS THE WALL/FLOOR, MAY REMAIN

AS AN EXISTING PREVIOUSLY APPROVED CONSTRUCTION METHOD.

6. EXISTING PENETRATIONS THAT REQUIRE REPAIR OR REPLACEMENT REQUIRE THE USE OF LISTED FIRESTOP

MATERIALS.

FIRE SPRINKLER SYSTEM:

1. THE COMBINATION STANDPIPE AND FIRE SPRINKLER SYSTEM WAS DESIGNED TO THE 2016 EDITION OF NFPA 13.

2. QUICK RESPONSE TYPE SPRINKLERS ARE INSTALLED THROUGHOUT MOST OF THE BUILDING. STANDARD

RESPONSE TYPE SPRINKLERS ARE INSTALLED IN THE ELEVATOR MACHINE ROOMS.

3. SPRINKLERS WERE INSTALLED IN LIGHT HAZARD AREAS INCLUDING; CORRIDORS, OFFICES, PATIENT CARE AND

PATIENT SLEEPING ROOMS AT LIGHT HAZARD 0.10 GPM/1500 SQ. FT. DENSITY.

4. SPRINKLERS WERE INSTALLED IN ORDINARY HAZARD GROUP I AREAS INCLUDING; LABORATORIES (WITHOUT

FLAMMABLE LIQUIDS), MECHANICAL EQUIPMENT ROOMS, ELECTRICAL SWITCH GEAR ROOMS, REPAIR SHOPS AND

STORAGE ROOMS UNDER 250 SQ. FT. AT A 0.15 GPM/1500 SQ. FT. DENSITY.

5. SPRINKLERS WERE INSTALLED IN ORDINARY HAZARD GROUP II AREAS INCLUDING GENERAL STORAGE ROOMS OVER 250 SQ. FT. AND LABORATORIES (WITH THE USE OF FLAMMABLE LIQUIDS) AT A 0.20 GPM/1500 SQ. FT.

DENSITY.

FIRE ALARM SYSTEM:

1. THE FIRE ALARM SYSTEM WAS DESIGNED TO THE 2013 EDITION OF NFPA 72, NATIONAL FIRE ALARM CODE.

2. PRIVATE MODE BUILDING OCCUPANT NOTIFICATION IS INSTALLED PER SECTIONS 19.3.4.3.1 AND 9.6.3.6.3 OF NFPA

101-2015 EDITION.

3. PRIVATE MODE AUDIBLE DEVICES (SPEAKERS) ARE INSTALLED IN CORRIDORS AND LARGER ROOMS OR SUITES

PER SECTION 18.4.4.1 OF NFPA 72-2016 EDITION.

4. PRIVATE MODE VISIBLE DEVICES (STROBES) ARE INSTALLED AT REDUCED QUANTITY AND SPACING PER SECTION

18.6 OF THE NFPA 72-2016 EDITION.

5. STROBE CIRCUITS ARE REQUIRED TO BE SYNCHRONIZED IN ACCORDANCE WITH SECTION 18.5.5.4.2 OF NFPA

72-2016 EDITION.

SUITES:

1. SUITES ARE UTILIZED TO ILLUSTRATE AREAS WITH THE SAME FUNCTION, USE OF HALLWAYS OR AISLES AND THE

END OF PUBLIC EXIT CORRIDORS. NO EXIT SIGNS OUTSIDE OF THE SUITE DIRECT OCCUPANTS INTO A SUITE TO

REACH AN EXIT.

2. HEALTH CARE OCCUPANCY SUITES ARE REGULATED BY FUNCTION AND SIZE.

3. HEALTH CARE OCCUPANCY PATIENT SLEEPING SUITES:

A. SINGLE EXIT SUITE - 1,000 SQ. FT. (NFPA 101 -19.2.5.7.2.2)

B. MULTI EXIT SUITE - 5,000 SQ. FT. (NFPA 101 - 19.2.5.7.2.3.A)

C. MULTI EXIT SUITE WITH STANDARD RESPONSE SPRINKLERS OR COMPLETE SMOKE DETECTION - 7,500 SQ.

FT. (NFPA 101 - 19.2.5.7.2.3.B)

D. MULTI EXIT SUITE WITH DIRECT VISUAL SUPERVISION, QUICK RESPONSE SPRINKLERS AND COMPLETE

SMOKE DETECTION - 10,000 SQ. FT. (NFPA 101 - 19.2.5.7.2.3.C)

4. PATIENT CARE NON - SLEEPING SUITES:

A. SINGLE EXIT SUITE - 2,500 SQ. FT. (NFPA 101 - 19.2.5.7.3.1.B)

B. MULTI EXIT SUITE - 10,000 SQ. FT. (NFPA 101 - 19.2.5.7.3.2)

C. MULTI EXIT SUITE WITH STANDARD RESPONSE SPRINKLERS AND COMPLETE SMOKE DETECTION OR QUICK

RESPONSE SPRINKLERS - 12,500 SQ. FT. (NFPA 101 - 19.2.5.7.3.2.A)

D. MULTI EXIT SUITE WITH QUICK RESPONSE SPRINKLERS AND COMPLETE SMOKE DETECTION (NFPA 101 -

19.2.5.7.3.2.B)

5. HEALTH CARE OCCUPANCY NON - PATIENT - CARE SUITES FOLLOW THE TRAVEL DISTANCE REQUIREMENTS

AS LISTED IN TABLE A.7.6 OF NFPA 101.

6. SUITES IN OTHER OCCUPANCIES ARE NOT REGULATED IN SIZE BUT STILL FOLLOW THE TRAVEL DISTANCE

REQUIREMENTS AS LISTED IN TABLE A.7.6 OF NFPA 101.

BUILDING # FLOOR

HEALTH CARE

OCCUPANCY

TOTAL

508C 1 49,031 0 22,513 0 71,544

AMBULATORY HEALTH

CARE OCCUPANCY

BUSINESS

OCCUPANCY

INDUSTRIAL

OCCUPANCY

508ASCA 2 0 0 56,228 0 56,228

508ASCA 1 0 0 56,573 0 56,573

125 2 0 0 22,258 0 22,258

125 1 0 0 41,126 0 41,126

128 2 0 0 8,723 0 8,723

128 1 0 0 8,723 0 8,723

SUB TOTAL 0 0 17,446 0 17,446

129 2 0 0 8,696 0 8,696

129 1 0 0 8,692 0 8,692

SUB TOTAL 0 0 17,388 0 17,388

130 1 0 0 8,721 0 8,721

131 2 0 0 0 0 9,517

SUB TOTAL 0 0 8,721 0 17,442

131 GROUND 0 0 9,516 0 9,516

SUB TOTAL 0 0 9,516 0 28,551

GRAND TOTAL 49,031 0 263,657 0 340,444

OCCUPANCY TABLE

DORMITORY

OCCUPANCY

9,517

8,721

19,035

27,756

SUB TOTAL

SUB TOTAL 0 0 112,801 0 112,8010

125 BASEMENT 0 0 11,888 0 11,8880

SUB TOTAL 0 0 75,272 0 75,2720

130 2 0 0 0 0 8,7218,721

131 1 0 0 0 0 9,5189,518

49,031 0 22,513 0 71,5440 l ll l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l l ll l ll l l l l l l l

LEGEND

l lllllll

O OO

OO OO

KEY NOTES

KEY NOTES

278 SF

EGRESS STAIR

1A001

185 SF

EGRESS STAIR 2

1A002

204 SF

EGRESS STAIR

1A003

95 SF

ELEV SHAFT

RCC101C

352 SF

ENTRY

1A100 421 SF

PAT CORR

1A100B

560 SF

PAT CORR

1A100C

54 SF

PAT CORR

1A100D

387 SF

WAIT

1A101

66 SF

RECEPTION

1A102

73 SF

INTAKE

CONSULT RM

1A103

64 SF

SECURITY

1A104

120 SF

CONSULT RM

1A105

114 SF

CONSULT RM

1A106

113 SF

CONSULT RM

1A107 123 SF

CONSULT RM

1A108

132 SF

PSYCHIATRIST'S

OFF

1A109

131 SF

SUPV'S OFF

1A110

131 SF

SUPV'S OFF

1A111

132 SF

SUPV'S OFF

1A112

95 SF

STOR

1A113

136 SF

WOMEN'S STAFF TLT

1A114

127 SF

DATA CLO

1A115

124 SF

MEN'S STAFF TLT

1A116

715 SF

WRKRM

1A117

301 SF

WRKRM

1A118

82 SF

ELEV MACH

ROOM

1A119

79 SF

ADA MEN'S

ROOM

1A120

106 SF

ADA WOMEN'S

RM

1A121

72 SF

HAC

1A122

386 SF

STOR

1A141

302 SF

MECH RM

1A125

124 SF

DATA CLO

1A126

217 SF

PLUMBING/FIRE PROTECTION RM

1A127

247 SF

GROUP RM

1A128

115 SF

OFF / CONSULT

1A129

111 SF

OFF / CONSULT

1A130

142 SF

ELEC RM

1A131

DN

178 SF

CONNECTING

CORR

RCC101R

508-128-01-DRF001

508-128-01-DRF002

508-128-01-DRF003

508-128-01-DRF004

508-128-01-DRS001

508-128-01-DRS002

508-128-01-DRS003

3 10

DOOR FAILS INSPECTION TEST

DOOR PASSES INSPECTION TEST

FB1 = FIRE BARRIER 1HR

FB2 = FIRE BARRIER 2HR

FB1/2 = FIRE BARRIER 30 MIN

FSB1 = FIRE / SMOKE BARRIER 1HR

FSB2 = FIRE / SMOKE BARRIER 2HR

SP0 = SMOKE PARTITION NON-RATED

SB0 = SMOKE BARRIER NON-RATED

EHR = EXISTING HAZARDOUS ROOMS

HCO = HEALTH CARE OCCUPANCY

NON-RATED

NON-RATED INTERIOR PARTITION WALL

XXX-XXXX-XX-XXXXX DOOR TAG

' 6

G ra p h ic S ca le

/2

1'

-0

G ra p h ic S ca le

/3 2"

'-0

' G ra p h ic S ca le

/1 6"

'-0

' G ra p h ic

S ca le

/8

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

/8

1'

-0

' G ra p h ic

S ca le

/2

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

'-0

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

VISN 7 LIFE SAFETY SURVEY AND

DRAWING UPDATE, TASK ORDER

#13

GS-10F-0347P

Elijah Knight, PE

R R o m a n y k C o n s u lt in g \R

C C

A E

C

C o n s u lt in g \0

P ro je c ts

\V

IS

N

\L if e

S a fe ty \0

M o d e l\

A tl a n ta \B u ild in g s S u rv e y e d

\A T

-1

F o rt M c P h e rs o n

H o m e le s s P ro g ra m \A

T -1

F o rt

M c P h e rs o n H o m e le s s P ro g ra m

.r v t

/1

/2

:0

:0

A

M

FIRE/SMOKE DOOR INSPECTION FLOOR PLAN -

LEVEL 01

E.K. HP

LS0401

VISN 7 ATLANTA

07/31/2018

VISN 7

ATLANTA

100% SUBMITTAL

NORTH ARROW

FIRE/SMOKE DOOR INSPECTION FLOOR PLAN - LEVEL 01

1/8" = 1'-0"

Note Number Fire Door Note

1 VISIBLE SIGN OF DAMAGE

2 PARTS MISSING OR BROKEN

3 SURFACE HOLES IN DOOR OR FRAME

4a DOOR LABELS CLEARLY NOT VISIBLE AND LEGIBLE

4b FRAME LABELS CLEARLY NOT VISIBLE AND LEGIBLE

5 FAILED GLAZING AND FRAME INSPECTION

6 SELF-CLOSING DEVICE NOT OPERATIONAL

7 COORDINATOR NOT OPERATIONAL

8 LATCHING HARDWARE NOT OPERATIONAL

9 AUXILIARY HARDWARE INTERFERENCE

10 EDGE CLEARANCE NOT ACCEPTABLE

11 DOOR CLEARANCE NOT ACCEPTABLE

12 SIGNAGE DOES NOT MEET REQUIREMENTS

13 FIELD MODIFICATIONS VOID LABEL

Note Number Fire Smoke Door Note

1 VISIBLE SIGN OF DAMAGE

2 PARTS MISSING OR BROKEN

3 SURFACE HOLES IN DOOR OR FRAME

4a DOOR LABELS CLEARLY NOT VISIBLE AND LEGIBLE

4b FRAME LABELS CLEARLY NOT VISIBLE AND LEGIBLE

5 FAILED METAL DOOR FRAME INSPECTION

6 FAILDED GLAZING AND FRAME INSPECTION

7 SELF-CLOSING DEVICE NOT OPERATIONAL

8 COORDINATOR NOT OPERATIONAL

9 LATCHING HARDWARE NOT OPERATIONAL

10 AUXILIARY HARDWARE INTERFERENCE

11 EDGE CLEARANCE NOT ACCEPTABLE

12 DOOR CLEARANCE NOT ACCEPTABLE

l ll l l l l l l l l l l l l l

LEGEND

l lllllll

O OO

OO OO

KEY NOTES

KEY NOTES

629 SF

STAFF MEETING/GROUP RM

2A219

120 SF

WOMEN'S RM

2A218

109 SF

ADA TLT

2A217

139 SF

MEN'S RM

2A216

239 SF

PAT CORR

2A200D

318 SF

CLASSRM

2A220

424 SF

DEDICATED COMP CLASSRM

2A221

277 SF

EGRESS STAIR

RCC201R

151 SF

EGRESS STAIR 2

RCC203R 168 SF

EGRESS STAIR

RCC202R

407 SF

PAT CORR

2A200C

115 SF

ELEC RM

2A222

106 SF

ELEV SHAFT

RCC205C

79 SF

HAC

2A215

220 SF

PAT CORR

2A200A

71 SF

STOR

2A223

427 SF

STAFF CORR

2A200B

348 SF

MECH RM

2A214

187 SF

BRK RM

2A201

89 SF

DEDICATED

CUBICLE

2A202

151 SF

SUPV'S OFF

2A203

111 SF

SUPV'S OFF

2A204

137 SF

SUPV'S OFF

2A205

108 SF

SUPV'S OFF

2A206

1,342 SF

WRKRM

2A211

91 SF

STOR

2A207

136 SF

WOMEN'S STAFF TLT

2A208

126 SF

DATA CLO

2A209

125 SF

MEN'S STAFF TLT

2A210

142 SF

SUPV'S OFF

2A212

138 SF

WRKRM

2A213

DN

178 SF

CONNECTING

CORR

RCC204R

508-128-02-DRS001

508-128-02-DRS002508-128-02-DRF001

508-128-02-DRF002

508-128-02-DRF003

508-128-02-DRF004

DOOR FAILS INSPECTION TEST

DOOR PASSES INSPECTION TEST

FB1 = FIRE BARRIER 1HR

FB2 = FIRE BARRIER 2HR

FB1/2 = FIRE BARRIER 30 MIN

FSB1 = FIRE / SMOKE BARRIER 1HR

FSB2 = FIRE / SMOKE BARRIER 2HR

SP0 = SMOKE PARTITION NON-RATED

SB0 = SMOKE BARRIER NON-RATED

EHR = EXISTING HAZARDOUS ROOMS

HCO = HEALTH CARE OCCUPANCY

NON-RATED

NON-RATED INTERIOR PARTITION WALL

XXX-XXXX-XX-XXXXX DOOR TAG

' 6

G ra p h ic S ca le

/2

1'

-0

G ra p h ic S ca le

/3 2"

'-0

' G ra p h ic S ca le

/1 6"

'-0

' G ra p h ic

S ca le

/8

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

/8

1'

-0

' G ra p h ic

S ca le

/2

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

'-0

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

VISN 7 LIFE SAFETY SURVEY AND

DRAWING UPDATE, TASK ORDER

#13

GS-10F-0347P

Elijah Knight, PE

R R o m a n y k C o n s u lt in g \R

C C

A E

C

C o n s u lt in g \0

P ro je c ts

\V

IS

N

\L if e

S a fe ty \0

M o d e l\

A tl a n ta \B u ild in g s S u rv e y e d

\A T

-1

F o rt M c P h e rs o n

H o m e le s s P ro g ra m \A

T -1

F o rt

M c P h e rs o n H o m e le s s P ro g ra m

.r v t

/1

/2

:0

:0

A

M

FIRE/SMOKE DOOR INSPECTION FLOOR PLAN -

LEVEL 02

E.K. HP

LS0402

VISN 7 ATLANTA

07/31/2018

VISN 7

ATLANTA

100% SUBMITTAL

NORTH ARROW

FIRE/SMOKE DOOR INSPECTION FLOOR PLAN - LEVEL 02

1/8" = 1'-0"

Note Number Fire Door Note

1 VISIBLE SIGN OF DAMAGE

2 PARTS MISSING OR BROKEN

3 SURFACE HOLES IN DOOR OR FRAME

4a DOOR LABELS CLEARLY NOT VISIBLE AND LEGIBLE

4b FRAME LABELS CLEARLY NOT VISIBLE AND LEGIBLE

5 FAILED GLAZING AND FRAME INSPECTION

6 SELF-CLOSING DEVICE NOT OPERATIONAL

7 COORDINATOR NOT OPERATIONAL

8 LATCHING HARDWARE NOT OPERATIONAL

9 AUXILIARY HARDWARE INTERFERENCE

10 EDGE CLEARANCE NOT ACCEPTABLE

11 DOOR CLEARANCE NOT ACCEPTABLE

12 SIGNAGE DOES NOT MEET REQUIREMENTS

13 FIELD MODIFICATIONS VOID LABEL

Note Number Fire Smoke Door Note

1 VISIBLE SIGN OF DAMAGE

2 PARTS MISSING OR BROKEN

3 SURFACE HOLES IN DOOR OR FRAME

4a DOOR LABELS CLEARLY NOT VISIBLE AND LEGIBLE

4b FRAME LABELS CLEARLY NOT VISIBLE AND LEGIBLE

5 FAILED METAL DOOR FRAME INSPECTION

6 FAILDED GLAZING AND FRAME INSPECTION

7 SELF-CLOSING DEVICE NOT OPERATIONAL

8 COORDINATOR NOT OPERATIONAL

9 LATCHING HARDWARE NOT OPERATIONAL

10 AUXILIARY HARDWARE INTERFERENCE

11 EDGE CLEARANCE NOT ACCEPTABLE

12 DOOR CLEARANCE NOT ACCEPTABLE

Sheets
G-04 - COVER
G-04X1 - GENERAL SHEET
G-04X2 - GENERAL SHEET
LS0401 - FIRE/SMOKE DOOR INSPECTION FLOOR PLAN - LEVEL 01
LS0402 - FIRE/SMOKE DOOR INSPECTION FLOOR PLAN - LEVEL 02

File details come from the government source that posted it. Updated .