2023-02-09_Fort-McPherson-VAMC-Bldg-125_SprinklerScan.pdf

PDF 154 KB Posted

Attached to
Fire Sprinkler Testing
Solicitation number
36C24724Q0269
Issued by

About this file

This document is a sprinkler inspection report for Building 125 at the Fort McPherson VA Medical Center in Atlanta, Georgia. The report was generated by United Fire Protection and details the quarterly inspection of the building's wet pipe and fire pump sprinkler systems performed on February 9, 2023. Key details include inspection and testing of 42 total items in the building, all of which passed inspection. The report provides an inventory of sprinkler system components by type, location, manufacturer, and installation date. It also lists the devices, valves, and pumps by identification number and address. The related federal contract opportunity is solicitation number 36C24724Q0269 for fire sprinkler testing services issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7. No further information is provided on the opportunity.

View the file

Other files

File Type Posted
FIRE ALARM 130.pdf PDF
2022-06-20_Fort-McPherson-VAMC-Bldg-128_Annual Report.pdf PDF
BLDG 131 ASBUILTS.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-131_Annual Report.pdf PDF
FIRE SUPPRESSION.pdf PDF
2022-06-20_Fort-McPherson-VAMC-Bldg-129_Annual Report.pdf PDF
BLDG 125 ASBUILT.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-128_SprinklerScan.pdf PDF
Ft. McPherson Bldg 128 Fire Alarm Drawings - RECORD Dwg.pdf PDF
Bldg 128 As-Builts.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
FIRE ALARM 129.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-125_SprinklerScan.pdf PDF
BLDG 129 ASBUILT.pdf PDF
2023-02-10_Fort-McPherson-VAMC-Bldg-128_SprinklerScan (1).pdf PDF
36C24724Q0269 0001.pdf PDF
03 Series LIFE SAFETY - 100 AT-130 Fort McPherson Residental Treatment.pdf PDF
03 Series LIFE SAFETY - 100 AT-131 Fort McPherson Domiciliary Care.pdf PDF
03 Series LIFE SAFETY - 100 AT-125 Fort McPherson OPC.pdf PDF
FIRE ALARM 125.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-125_Annual Report.pdf PDF
04 Series DOORS - 100 AT-130 Fort McPherson Residental Treatment.pdf PDF
04 Series DOORS - 100 AT-125 Fort McPherson OPC.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-128_SprinklerScan.pdf PDF
05 series dampers - 100 at-125 fort mcpherson opc.pdf PDF
FIRE SUPPRESSION 131.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-130_Annual Report.pdf PDF
03 Series LIFE SAFETY - 100 AT-128 Fort McPherson Homeless Program.pdf PDF
04 Series DOORS - 100 AT-128 Fort McPherson Homeless Program.pdf PDF
BLDG. 125 FIRE SUPPRESSION.pdf PDF
04 Series DOORS - 100 AT-131 Fort McPherson Domiciliary Care.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-129_SprinklerScan.pdf PDF
36C24724Q0269.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sprinkler Inspection Certificate For

Fort McPherson VAMC Bldg 125 1701 Hardee Ave SW

Atlanta, GA 30310

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Quarterly Inspection Inspection Date Feb 9, 2023

Building: Fort McPherson VAMC Bldg 125 Company: United Fire Protection - Atlanta Contact: Mike McGill Contact: Wayne Huxtable

Title: Maintenance & Operations Supervisor Title: Technician

Page of 1 13United Fire Protection - Atlanta Download Date: 03/22/2023

Executive Summary Generated by: BuildingReports.com

Building Information Building: Fort McPherson VAMC Bldg 125 Contact: Mike McGill Address: 1701 Hardee Ave SW Phone: 404-321-6111 Address: Fax:

City/State/ZIP Code: Atlanta, GA 30310 Mobile:

Country: United States of America Email:

Inspection Performed By Company: United Fire Protection - Atlanta Inspector: Wayne Huxtable Address: 2150 Boggs Rd Bldg 100 Phone: 770-771-0999 Address: Suite 140 Fax:

City/State/ZIP Code: Duluth, GA 30096 Mobile:

Country: United States of America Email: whuxtable@united-fire.com

System Control Unit System Type System Location Protected Area Devices Fire Pump 25

Fire Pump BLDG 125 1

Wet Pipe 16

Inspection Summary

Category:

Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Alarm 13 30.95% 13 100.00% 13 100.00% 0 0.00%

Device 5 11.90% 0 0.00% 0 0.00% 0 0.00%

Pump 1 2.38% 1 100.00% 1 100.00% 0 0.00%

Valve 23 54.76% 20 86.96% 20 100.00% 0 0.00%

Totals 42 100% 34 80.95% 34 100.00% 0 0.00%

Certification

Company: United Fire Protection - Atlanta Building: Fort McPherson VAMC Bldg 125

Inspector: Wayne Huxtable Contact: Mike McGill

Page of 2 13United Fire Protection - Atlanta Download Date: 03/22/2023

Inspection & Testing Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 125 The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or

. Items are listed by Category. Each item includes the services performed, and the time & date at which testing Failed/Other occurred.

Device Type Location Service Time Date

Passed Fire Pump

Tamper Switch Basement Pump Room Fire Pump Discharge

Quarterly 9:26:20 AM 02/09/2023

Tamper Switch Basement Pump Room Backflow CV2 Quarterly 9:26:25 AM 02/09/2023

Tamper Switch Basement Pump Room Backflow CV2 Quarterly 9:26:32 AM 02/09/2023

Tamper Switch Basement Pump Room Backflow CV1 Quarterly 9:26:37 AM 02/09/2023

Tamper Switch Basement Pump Room Backflow CV2 Quarterly 4:31:37 PM 02/09/2023

Tamper Switch 2nd Mechanical Room Quarterly 9:01:06 AM 02/09/2023

Waterflow Switch 2nd Mechanical Room Quarterly 9:25:47 AM 02/09/2023

Control Valve Basement Pump Room Backflow CV1 Quarterly 8:40:16 AM 02/09/2023

Control Valve Basement Pump Room Backflow CV2 Quarterly 8:41:22 AM 02/09/2023

Control Valve Basement Pump Room Jockey pump Quarterly 8:42:17 AM 02/09/2023

Control Valve Basement Pump Room Fire Pump Suction Quarterly 8:42:53 AM 02/09/2023

Control Valve Basement Pump Room City Bypass CV1 Quarterly 8:43:41 AM 02/09/2023

Control Valve Basement Pump Room Fire Pump Discharge

Quarterly 8:44:00 AM 02/09/2023

Control Valve Basement Pump Room City Bypass CV2 Quarterly 8:45:24 AM 02/09/2023

Control Valve Basement Pump Room Test Header Quarterly 8:47:15 AM 02/09/2023

Control Valve Basement Pump Room Flow Meter CV1 Quarterly 9:26:07 AM 02/09/2023

Control Valve Basement Pump Room Flow Meter CV2 Quarterly 9:26:13 AM 02/09/2023

Control Valve Basement Pump Room Jockey pump Quarterly 4:32:18 PM 02/09/2023

Control Valve 2nd Mechanical Room Quarterly 9:25:53 AM 02/09/2023

BLDG 125 Fire Pump Pump Basement Mechanical room Quarterly 4:32:08 PM 02/09/2023

Wet Pipe Tamper Switch Basement Stairwell B Quarterly 8:52:41 AM 02/09/2023

Waterflow Switch Basement Stairwell B Quarterly 8:51:03 AM 02/09/2023

Waterflow Switch 1st Stairwell B Quarterly 8:55:48 AM 02/09/2023

Waterflow Switch 1st Stairwell B Quarterly 9:01:23 AM 02/09/2023

Waterflow Switch 2nd Mechanical Room Freight Elevator Shaft Flowswitch

Quarterly 9:03:44 AM 02/09/2023 javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977772');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977774');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977775');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977776');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977845');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977844');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','5778J04');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133423');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133424');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133425');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133412');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133419');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133416');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133421');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133422');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133417');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133418');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133426');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133434');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977767');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977867');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133447');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780003');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780004');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133439');

Page of 3 13United Fire Protection - Atlanta Download Date: 03/22/2023

Device Type Location Service Time Date

Waterflow Switch 2nd Mechanical Room Passenger Elevator Shaft Flowswitch

Quarterly 9:05:38 AM 02/09/2023

Control Valve Basement Stairwell B Quarterly 8:53:07 AM 02/09/2023

Control Valve 1st Stairwell B Quarterly 4:32:58 PM 02/09/2023

Control Valve 2nd Mechanical Room Quarterly 9:02:24 AM 02/09/2023

Control Valve 2nd Mechanical Room Freight Elevator Shaft CV

Quarterly 9:03:37 AM 02/09/2023

Control Valve 2nd Mechanical Room Passenger Elevator Shaft CV

Quarterly 9:05:25 AM 02/09/2023

Inspector's Test Basement Stairwell B Quarterly 4:32:48 PM 02/09/2023

Inspector's Test 1st Stairwell B Quarterly 8:56:44 AM 02/09/2023

Inspector's Test 2nd Mechanical Room Quarterly 9:01:29 AM 02/09/2023

Untested Fire Pump

Gauge Basement Pump Room Suction

Gauge Basement Pump Room Discharge

Gauge 2nd Mechanical Room

Check Valve Basement Pump Room Discharge Check

Check Valve Basement Pump Room City Bypass Check

Check Valve Basement Pump Room Jockey pump

Wet Pipe Gauge Basement Stairwell B

Gauge 1st Stairwell B javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133441');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133446');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133442');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','4413364');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133438');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133440');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133448');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133445');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133437');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977768');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977769');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780005');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133415');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133420');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133428');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780001');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780002');

Page of 4 13United Fire Protection - Atlanta Download Date: 03/22/2023

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Location Number of Turns

Zone /Address

OK ScanID

OS&Y Supervisory Basement Stairwell B 1-M4-89 67977867

Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR-F 4" 1-M4-88 44133447 Vane Potter Electric VSR 4” 1-M2-22 57780003 Vane Potter Electric VSR-F 4" 1-M2-21 57780004 Vane Potter Electric VS-SP 1" 1-7-4 44133439 Vane Potter Electric VS-SP 1" 1-7-2 44133441

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Stockham 525H Basement Stairwell B

4" Open Supervised 44133446

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Stockham 525H 1st Stairwell B 4" Open Supervised 44133442

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Stockham 9624 2nd Mechanical Room

4" Open Supervised 4413364

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977867');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133447');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780003');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780004');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133439');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133441');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133446');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133442');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','4413364');

Page of 5 13United Fire Protection - Atlanta Download Date: 03/22/2023

Butterfly Nibco KT-505W-8

2nd Mechanical Room Freight Elevator Shaft

CV

1" Open Supervised 44133438

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Nibco KT-505W-8

2nd Mechanical Room Passenger Elevator Shaft

CV

1.25" Open Supervised 44133440

Description Isolation

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 9624 1150 44133448

Location Basement Stairwell B

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 9624 1150 44133445

Location 1st Stairwell B

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 9624 140 44133437

Location 2nd Mechanical Room

Devices Gauge

Location Service Date Basement Stairwell B 03/28/2013

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Ashcroft Ashcroft 165 1/4 57780001

Gauge Location Service Date 1st Stairwell B 03/28/2025

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 150 1/4 57780002 javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133438');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133440');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133448');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133445');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133437');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780001');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780002');

Page of 6 13United Fire Protection - Atlanta Download Date: 03/22/2023

Fire Pump Testing Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Location Number of Turns

Zone /Address

OK ScanID

OS&Y Supervisory Basement Pump Room Fire Pump Discharge

1-M4-103 67977772

OS&Y Supervisory Basement Pump Room Backflow

CV2

1-M4-99 67977774

OS&Y Supervisory Basement Pump Room Backflow

CV2

1-M4-99 67977775

OS&Y Supervisory Basement Pump Room Backflow

CV1

1-M4-98 67977776

OS&Y Supervisory Basement Pump Room Backflow

CV2

1-M4-99 67977845

OS&Y Supervisory 2nd Mechanical Room 1-M3-63 67977844

Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR-F 4" 1-M3-64 5778J04

Components Check Valve

Type Location Internal Date Size OK ScanID

Flanged Basement Pump Room Discharge Check

03/28/2018 6" 44133415

Flanged Basement Pump Room City Bypass Check

03/28/1996 8" 44133420

Flanged Basement Pump Room Jockey pump 03/28/2018 8" 44133428

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Stockham 525H Basement Pump Room Backflow CV1

8" Open Supervised 44133423

Description Backflow CV1

Control Valve javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977772');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977774');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977775');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977776');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977845');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977844');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','5778J04');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133415');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133420');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133428');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133423');

Page of 7 13United Fire Protection - Atlanta Download Date: 03/22/2023

Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Stockham 525H Basement Pump Room Backflow CV2

8" Open Supervised 44133424

Description Backflow CV1

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Stockham 525H Basement Pump Room Jockey pump

1.5" Open Supervised 44133425

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Stockham 525H

Basement Pump Room Fire Pump Suction

8" Open Supervised 44133412

Description Suction

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Stockham 525H

Basement Pump Room City Bypass

CV1

6" Open Supervised 44133419

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Stockham 525H

Basement Pump Room Fire Pump Discharge

8" Open Supervised 44133416

Description Suction

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Stockham 525H

Basement Pump Room City Bypass

CV2

8" Open Supervised 44133421

Description Isolation javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133424');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133425');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133412');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133419');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133416');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133421');

Page of 8 13United Fire Protection - Atlanta Download Date: 03/22/2023

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Stockham 525H Basement Pump Room Test Header

6" Closed Locked 44133422

Description Test Header

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Stockham 525H

Basement Pump Room Flow Meter

CV1

6" 44133417

Description Suction

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Stockham 525H

Basement Pump Room Flow Meter

CV2

6" 44133418

Description Suction

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Stockham 525H Basement Pump Room Jockey pump

1.5" Open Supervised 44133426

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Stockham 525H 2nd Mechanical Room

4" Open Supervised 44133434

Description Main Control

Devices Gauge

Location Service Date Basement Pump Room Suction 03/28/2025

Type Manufacturer Model # Static psi Fill Type Size OK ScanID City Pressure Lansdale 150 1/4 67977768 javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133422');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133417');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133418');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133426');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133434');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977768');

Page of 9 13United Fire Protection - Atlanta Download Date: 03/22/2023

Gauge Location Service Date Basement Pump Room Discharge 03/28/2025

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Ashcroft Ashcroft 150 1/4 67977769

Gauge Location Service Date 2nd Mechanical Room 05/27/2025

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 150 1/4 57780005

Building: Fort McPherson VAMC Bldg

BLDG 125

This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Pump Manufacturer Model Number Location Install Date ScanID Patterson Basement Mechanical room 05/30/1994 67977767

Serial Number Type Orientation Aligned? Water Supply Impeller Size FP-C6183ex Pump Primary Horizontal 8.063

Fire Pump Rating Amps Volts Net Pressure Gallons Per Minute Rotations Per Minute A B C A-B B-C A-C 85 750 3571 javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977769');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780005');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977767');

Page of 10 13United Fire Protection - Atlanta Download Date: 03/22/2023

Page of 11 13United Fire Protection - Atlanta Download Date: 03/22/2023

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 125 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Check Valve Valve 7.14% 3

Control Valve Valve 40.48% 17

Gauge Device 11.90% 5

Inspector's Test Valve 7.14% 3

Pump Pump 2.38% 1

Tamper Switch Alarm 16.67% 7

Waterflow Switch Alarm 14.29% 6

Device Type Qty Model # Type Description Install Date

In Service - 1 Year to 2 Years Fire Pump

Gauge 1 Ashcroft Supply Pressure 05/27/2021 Gauge 1 City Pressure 05/27/2021 Gauge 1 System Pressure 05/27/2021

Wet Pipe Gauge 1 System Pressure 05/27/2021

In Service - 3 Years to 5 Years Wet Pipe

Waterflow Switch 1 VS-SP Vane Alarm 07/11/2018

In Service - 5 Years to 10 Years Fire Pump

Check Valve 1 106-6 Flanged 03/28/2013

Wet Pipe Gauge 1 Ashcroft System Pressure 03/28/2013

In Service - 25 Years or Older Fire Pump

Check Valve 1 106-6 Flanged 03/28/1996

BLDG 125 Fire Pump Pump 1 Pump Primary 05/30/1994

Fire Pump Tamper Switch 1 OSYSU-2 OS&Y Supervisory 03/28/1994 Tamper Switch 1 OSYSU-3 OS&Y Supervisory 03/28/1994 Waterflow Switch 1 VSR-F Vane Alarm 03/28/1994 Tamper Switch 4 OSYSU-2 OS&Y Supervisory 03/28/1994

Page of 12 13United Fire Protection - Atlanta Download Date: 03/22/2023

Check Valve 1 525H Flanged 03/28/1994 Control Valve 2 525H OS&Y Backflow CV1 03/28/1994 Control Valve 4 525H OS&Y Isolation 03/28/1994 Control Valve 1 525H OS&Y Main Control 03/28/1994 Control Valve 4 525H OS&Y Suction 03/28/1994 Control Valve 1 525H OS&Y Test Header 03/28/1994

Wet Pipe Inspector's Test 3 9624 03/28/1994 Control Valve 2 KT-505W-8 Butterfly Isolation 03/28/1994 Tamper Switch 1 OSYSU-2 OS&Y Supervisory 03/28/1994 Waterflow Switch 1 VS-SP Vane Alarm 03/28/1994 Waterflow Switch 1 VSR Vane Alarm 03/28/1994 Waterflow Switch 2 VSR-F Vane Alarm 03/28/1994 Control Valve 2 525H OS&Y Main Control 03/28/1994 Control Valve 1 9624 OS&Y Main Control 03/28/1994

Page of 13 13United Fire Protection - Atlanta Download Date: 03/22/2023

Zone Address Report Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 125 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID

Control Panel 1 7-1 Control Valve 2nd Mechanical Room Passenger Elevator

Shaft CV Butterfly 44133440

7-2 Waterflow Switch 2nd Mechanical Room Passenger Elevator Shaft Flowswitch

Vane 44133441

7-3 Control Valve 2nd Mechanical Room Freight Elevator Shaft CV

Butterfly 44133438

7-4 Waterflow Switch 2nd Mechanical Room Freight Elevator Shaft Flowswitch

Vane 44133439

M2-21 Waterflow Switch 1st Stairwell B Vane 57780004 M2-22 Control Valve 1st Stairwell B OS&Y 44133442 M2-22 Waterflow Switch 1st Stairwell B Vane 57780003 M3-63 Control Valve 2nd Mechanical Room OS&Y 44133434 M3-63 Tamper Switch 2nd Mechanical Room OS&Y 67977844 M3-64 Waterflow Switch 2nd Mechanical Room Vane 5778J04

M3-102 Control Valve Basement Pump Room Fire Pump Suction OS&Y 44133412 M4-88 Waterflow Switch Basement Stairwell B Vane 44133447 M4-89 Control Valve Basement Stairwell B OS&Y 44133446 M4-89 Tamper Switch Basement Stairwell B OS&Y 67977867 M4-98 Control Valve Basement Pump Room Backflow CV1 OS&Y 44133423 M4-98 Tamper Switch Basement Pump Room Backflow CV1 OS&Y 67977776 M4-99 Control Valve Basement Pump Room Backflow CV2 OS&Y 44133424 M4-99 Tamper Switch Basement Pump Room Backflow CV2 OS&Y 67977774 M4-99 Tamper Switch Basement Pump Room Backflow CV2 OS&Y 67977775 M4-99 Tamper Switch Basement Pump Room Backflow CV2 OS&Y 67977845

M4-100 Control Valve Basement Pump Room City Bypass CV1 OS&Y 44133419 M4-100 Control Valve Basement Pump Room Jockey pump OS&Y 44133425 M4-100 Control Valve Basement Pump Room Jockey pump OS&Y 44133426 M4-101 Control Valve Basement Pump Room City Bypass CV2 OS&Y 44133421 M4-103 Control Valve Basement Pump Room Fire Pump

Discharge

OS&Y 44133416

M4-103 Tamper Switch Basement Pump Room Fire Pump Discharge

OS&Y 67977772

M4-103 Control Valve Basement Pump Room Flow Meter CV2 OS&Y 44133418 javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133440');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133441');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133438');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133439');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780004');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133442');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780003');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133434');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977844');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','5778J04');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133412');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133447');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133446');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977867');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133423');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977776');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133424');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977774');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977775');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977845');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133419');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133425');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133426');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133421');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133416');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977772');

javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133418');

Sprinkler Inspection Certificate
Executive Summary
Inspection & Testing
Wet Pipe Fire Sprinkler Systems
Fire Pump Testing
Inventory & Warranty Report
Zone Address Report