This document is a sprinkler inspection report for Building 125 at the Fort McPherson VA Medical Center in Atlanta, Georgia. The report was generated by United Fire Protection and details the quarterly inspection of the building's wet pipe and fire pump sprinkler systems performed on February 9, 2023. Key details include inspection and testing of 42 total items in the building, all of which passed inspection. The report provides an inventory of sprinkler system components by type, location, manufacturer, and installation date. It also lists the devices, valves, and pumps by identification number and address. The related federal contract opportunity is solicitation number 36C24724Q0269 for fire sprinkler testing services issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7. No further information is provided on the opportunity.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sprinkler Inspection Certificate For
Fort McPherson VAMC Bldg 125 1701 Hardee Ave SW
Atlanta, GA 30310
Tested to NFPA 25 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Quarterly Inspection Inspection Date Feb 9, 2023
Building: Fort McPherson VAMC Bldg 125 Company: United Fire Protection - Atlanta Contact: Mike McGill Contact: Wayne Huxtable
Title: Maintenance & Operations Supervisor Title: Technician
Page of 1 13United Fire Protection - Atlanta Download Date: 03/22/2023
Executive Summary Generated by: BuildingReports.com
Building Information Building: Fort McPherson VAMC Bldg 125 Contact: Mike McGill Address: 1701 Hardee Ave SW Phone: 404-321-6111 Address: Fax:
City/State/ZIP Code: Atlanta, GA 30310 Mobile:
Country: United States of America Email:
Inspection Performed By Company: United Fire Protection - Atlanta Inspector: Wayne Huxtable Address: 2150 Boggs Rd Bldg 100 Phone: 770-771-0999 Address: Suite 140 Fax:
City/State/ZIP Code: Duluth, GA 30096 Mobile:
Country: United States of America Email: whuxtable@united-fire.com
System Control Unit System Type System Location Protected Area Devices Fire Pump 25
Fire Pump BLDG 125 1
Wet Pipe 16
Inspection Summary
Category:
Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty % Alarm 13 30.95% 13 100.00% 13 100.00% 0 0.00%
Device 5 11.90% 0 0.00% 0 0.00% 0 0.00%
Pump 1 2.38% 1 100.00% 1 100.00% 0 0.00%
Valve 23 54.76% 20 86.96% 20 100.00% 0 0.00%
Totals 42 100% 34 80.95% 34 100.00% 0 0.00%
Certification
Company: United Fire Protection - Atlanta Building: Fort McPherson VAMC Bldg 125
Inspector: Wayne Huxtable Contact: Mike McGill
Page of 2 13United Fire Protection - Atlanta Download Date: 03/22/2023
Inspection & Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 125 The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or
. Items are listed by Category. Each item includes the services performed, and the time & date at which testing Failed/Other occurred.
Device Type Location Service Time Date
Passed Fire Pump
Tamper Switch Basement Pump Room Fire Pump Discharge
Quarterly 9:26:20 AM 02/09/2023
Tamper Switch Basement Pump Room Backflow CV2 Quarterly 9:26:25 AM 02/09/2023
Tamper Switch Basement Pump Room Backflow CV2 Quarterly 9:26:32 AM 02/09/2023
Tamper Switch Basement Pump Room Backflow CV1 Quarterly 9:26:37 AM 02/09/2023
Tamper Switch Basement Pump Room Backflow CV2 Quarterly 4:31:37 PM 02/09/2023
Tamper Switch 2nd Mechanical Room Quarterly 9:01:06 AM 02/09/2023
Waterflow Switch 2nd Mechanical Room Quarterly 9:25:47 AM 02/09/2023
Control Valve Basement Pump Room Backflow CV1 Quarterly 8:40:16 AM 02/09/2023
Control Valve Basement Pump Room Backflow CV2 Quarterly 8:41:22 AM 02/09/2023
Control Valve Basement Pump Room Jockey pump Quarterly 8:42:17 AM 02/09/2023
Control Valve Basement Pump Room Fire Pump Suction Quarterly 8:42:53 AM 02/09/2023
Control Valve Basement Pump Room City Bypass CV1 Quarterly 8:43:41 AM 02/09/2023
Control Valve Basement Pump Room Fire Pump Discharge
Quarterly 8:44:00 AM 02/09/2023
Control Valve Basement Pump Room City Bypass CV2 Quarterly 8:45:24 AM 02/09/2023
Control Valve Basement Pump Room Test Header Quarterly 8:47:15 AM 02/09/2023
Control Valve Basement Pump Room Flow Meter CV1 Quarterly 9:26:07 AM 02/09/2023
Control Valve Basement Pump Room Flow Meter CV2 Quarterly 9:26:13 AM 02/09/2023
Control Valve Basement Pump Room Jockey pump Quarterly 4:32:18 PM 02/09/2023
Control Valve 2nd Mechanical Room Quarterly 9:25:53 AM 02/09/2023
BLDG 125 Fire Pump Pump Basement Mechanical room Quarterly 4:32:08 PM 02/09/2023
Wet Pipe Tamper Switch Basement Stairwell B Quarterly 8:52:41 AM 02/09/2023
Waterflow Switch Basement Stairwell B Quarterly 8:51:03 AM 02/09/2023
Waterflow Switch 1st Stairwell B Quarterly 8:55:48 AM 02/09/2023
Waterflow Switch 1st Stairwell B Quarterly 9:01:23 AM 02/09/2023
Waterflow Switch 2nd Mechanical Room Freight Elevator Shaft Flowswitch
Quarterly 9:03:44 AM 02/09/2023 javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977772');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977774');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977775');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977776');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977845');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977844');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','5778J04');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133423');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133424');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133425');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133412');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133419');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133416');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133421');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133422');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133417');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133418');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133426');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133434');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977767');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977867');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133447');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780003');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780004');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133439');
Page of 3 13United Fire Protection - Atlanta Download Date: 03/22/2023
Device Type Location Service Time Date
Waterflow Switch 2nd Mechanical Room Passenger Elevator Shaft Flowswitch
Quarterly 9:05:38 AM 02/09/2023
Control Valve Basement Stairwell B Quarterly 8:53:07 AM 02/09/2023
Control Valve 1st Stairwell B Quarterly 4:32:58 PM 02/09/2023
Control Valve 2nd Mechanical Room Quarterly 9:02:24 AM 02/09/2023
Control Valve 2nd Mechanical Room Freight Elevator Shaft CV
Quarterly 9:03:37 AM 02/09/2023
Control Valve 2nd Mechanical Room Passenger Elevator Shaft CV
Quarterly 9:05:25 AM 02/09/2023
Inspector's Test Basement Stairwell B Quarterly 4:32:48 PM 02/09/2023
Inspector's Test 1st Stairwell B Quarterly 8:56:44 AM 02/09/2023
Inspector's Test 2nd Mechanical Room Quarterly 9:01:29 AM 02/09/2023
Untested Fire Pump
Gauge Basement Pump Room Suction
Gauge Basement Pump Room Discharge
Gauge 2nd Mechanical Room
Check Valve Basement Pump Room Discharge Check
Check Valve Basement Pump Room City Bypass Check
Check Valve Basement Pump Room Jockey pump
Wet Pipe Gauge Basement Stairwell B
Gauge 1st Stairwell B javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133441');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133446');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133442');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','4413364');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133438');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133440');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133448');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133445');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133437');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977768');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977769');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780005');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133415');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133420');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133428');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780001');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780002');
Page of 4 13United Fire Protection - Atlanta Download Date: 03/22/2023
Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
OS&Y Supervisory Basement Stairwell B 1-M4-89 67977867
Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR-F 4" 1-M4-88 44133447 Vane Potter Electric VSR 4” 1-M2-22 57780003 Vane Potter Electric VSR-F 4" 1-M2-21 57780004 Vane Potter Electric VS-SP 1" 1-7-4 44133439 Vane Potter Electric VS-SP 1" 1-7-2 44133441
Components Control Valve
Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H Basement Stairwell B
4" Open Supervised 44133446
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Stockham 525H 1st Stairwell B 4" Open Supervised 44133442
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 9624 2nd Mechanical Room
4" Open Supervised 4413364
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977867');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133447');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780003');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780004');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133439');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133441');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133446');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133442');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','4413364');
Page of 5 13United Fire Protection - Atlanta Download Date: 03/22/2023
Butterfly Nibco KT-505W-8
2nd Mechanical Room Freight Elevator Shaft
CV
1" Open Supervised 44133438
Description Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Nibco KT-505W-8
2nd Mechanical Room Passenger Elevator Shaft
CV
1.25" Open Supervised 44133440
Description Isolation
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 9624 1150 44133448
Location Basement Stairwell B
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 9624 1150 44133445
Location 1st Stairwell B
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 9624 140 44133437
Location 2nd Mechanical Room
Devices Gauge
Location Service Date Basement Stairwell B 03/28/2013
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Ashcroft Ashcroft 165 1/4 57780001
Gauge Location Service Date 1st Stairwell B 03/28/2025
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 150 1/4 57780002 javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133438');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133440');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133448');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133445');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133437');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780001');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780002');
Page of 6 13United Fire Protection - Atlanta Download Date: 03/22/2023
Fire Pump Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
OS&Y Supervisory Basement Pump Room Fire Pump Discharge
1-M4-103 67977772
OS&Y Supervisory Basement Pump Room Backflow
CV2
1-M4-99 67977774
OS&Y Supervisory Basement Pump Room Backflow
CV2
1-M4-99 67977775
OS&Y Supervisory Basement Pump Room Backflow
CV1
1-M4-98 67977776
OS&Y Supervisory Basement Pump Room Backflow
CV2
1-M4-99 67977845
OS&Y Supervisory 2nd Mechanical Room 1-M3-63 67977844
Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR-F 4" 1-M3-64 5778J04
Components Check Valve
Type Location Internal Date Size OK ScanID
Flanged Basement Pump Room Discharge Check
03/28/2018 6" 44133415
Flanged Basement Pump Room City Bypass Check
03/28/1996 8" 44133420
Flanged Basement Pump Room Jockey pump 03/28/2018 8" 44133428
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H Basement Pump Room Backflow CV1
8" Open Supervised 44133423
Description Backflow CV1
Control Valve javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977772');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977774');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977775');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977776');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977845');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977844');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','5778J04');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133415');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133420');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133428');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133423');
Page of 7 13United Fire Protection - Atlanta Download Date: 03/22/2023
Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H Basement Pump Room Backflow CV2
8" Open Supervised 44133424
Description Backflow CV1
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H Basement Pump Room Jockey pump
1.5" Open Supervised 44133425
Description Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H
Basement Pump Room Fire Pump Suction
8" Open Supervised 44133412
Description Suction
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H
Basement Pump Room City Bypass
CV1
6" Open Supervised 44133419
Description Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H
Basement Pump Room Fire Pump Discharge
8" Open Supervised 44133416
Description Suction
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H
Basement Pump Room City Bypass
CV2
8" Open Supervised 44133421
Description Isolation javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133424');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133425');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133412');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133419');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133416');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133421');
Page of 8 13United Fire Protection - Atlanta Download Date: 03/22/2023
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H Basement Pump Room Test Header
6" Closed Locked 44133422
Description Test Header
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H
Basement Pump Room Flow Meter
CV1
6" 44133417
Description Suction
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H
Basement Pump Room Flow Meter
CV2
6" 44133418
Description Suction
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H Basement Pump Room Jockey pump
1.5" Open Supervised 44133426
Description Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H 2nd Mechanical Room
4" Open Supervised 44133434
Description Main Control
Devices Gauge
Location Service Date Basement Pump Room Suction 03/28/2025
Type Manufacturer Model # Static psi Fill Type Size OK ScanID City Pressure Lansdale 150 1/4 67977768 javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133422');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133417');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133418');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133426');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133434');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977768');
Page of 9 13United Fire Protection - Atlanta Download Date: 03/22/2023
Gauge Location Service Date Basement Pump Room Discharge 03/28/2025
Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Ashcroft Ashcroft 150 1/4 67977769
Gauge Location Service Date 2nd Mechanical Room 05/27/2025
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 150 1/4 57780005
Building: Fort McPherson VAMC Bldg
BLDG 125
This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Pump Manufacturer Model Number Location Install Date ScanID Patterson Basement Mechanical room 05/30/1994 67977767
Serial Number Type Orientation Aligned? Water Supply Impeller Size FP-C6183ex Pump Primary Horizontal 8.063
Fire Pump Rating Amps Volts Net Pressure Gallons Per Minute Rotations Per Minute A B C A-B B-C A-C 85 750 3571 javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977769');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780005');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977767');
Page of 10 13United Fire Protection - Atlanta Download Date: 03/22/2023
Page of 11 13United Fire Protection - Atlanta Download Date: 03/22/2023
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 125 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Check Valve Valve 7.14% 3
Control Valve Valve 40.48% 17
Gauge Device 11.90% 5
Inspector's Test Valve 7.14% 3
Pump Pump 2.38% 1
Tamper Switch Alarm 16.67% 7
Waterflow Switch Alarm 14.29% 6
Device Type Qty Model # Type Description Install Date
In Service - 1 Year to 2 Years Fire Pump
Gauge 1 Ashcroft Supply Pressure 05/27/2021 Gauge 1 City Pressure 05/27/2021 Gauge 1 System Pressure 05/27/2021
Wet Pipe Gauge 1 System Pressure 05/27/2021
In Service - 3 Years to 5 Years Wet Pipe
Waterflow Switch 1 VS-SP Vane Alarm 07/11/2018
In Service - 5 Years to 10 Years Fire Pump
Check Valve 1 106-6 Flanged 03/28/2013
Wet Pipe Gauge 1 Ashcroft System Pressure 03/28/2013
In Service - 25 Years or Older Fire Pump
Check Valve 1 106-6 Flanged 03/28/1996
BLDG 125 Fire Pump Pump 1 Pump Primary 05/30/1994
Fire Pump Tamper Switch 1 OSYSU-2 OS&Y Supervisory 03/28/1994 Tamper Switch 1 OSYSU-3 OS&Y Supervisory 03/28/1994 Waterflow Switch 1 VSR-F Vane Alarm 03/28/1994 Tamper Switch 4 OSYSU-2 OS&Y Supervisory 03/28/1994
Page of 12 13United Fire Protection - Atlanta Download Date: 03/22/2023
Check Valve 1 525H Flanged 03/28/1994 Control Valve 2 525H OS&Y Backflow CV1 03/28/1994 Control Valve 4 525H OS&Y Isolation 03/28/1994 Control Valve 1 525H OS&Y Main Control 03/28/1994 Control Valve 4 525H OS&Y Suction 03/28/1994 Control Valve 1 525H OS&Y Test Header 03/28/1994
Wet Pipe Inspector's Test 3 9624 03/28/1994 Control Valve 2 KT-505W-8 Butterfly Isolation 03/28/1994 Tamper Switch 1 OSYSU-2 OS&Y Supervisory 03/28/1994 Waterflow Switch 1 VS-SP Vane Alarm 03/28/1994 Waterflow Switch 1 VSR Vane Alarm 03/28/1994 Waterflow Switch 2 VSR-F Vane Alarm 03/28/1994 Control Valve 2 525H OS&Y Main Control 03/28/1994 Control Valve 1 9624 OS&Y Main Control 03/28/1994
Page of 13 13United Fire Protection - Atlanta Download Date: 03/22/2023
Zone Address Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 125 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
Control Panel 1 7-1 Control Valve 2nd Mechanical Room Passenger Elevator
Shaft CV Butterfly 44133440
7-2 Waterflow Switch 2nd Mechanical Room Passenger Elevator Shaft Flowswitch
Vane 44133441
7-3 Control Valve 2nd Mechanical Room Freight Elevator Shaft CV
Butterfly 44133438
7-4 Waterflow Switch 2nd Mechanical Room Freight Elevator Shaft Flowswitch
Vane 44133439
M2-21 Waterflow Switch 1st Stairwell B Vane 57780004 M2-22 Control Valve 1st Stairwell B OS&Y 44133442 M2-22 Waterflow Switch 1st Stairwell B Vane 57780003 M3-63 Control Valve 2nd Mechanical Room OS&Y 44133434 M3-63 Tamper Switch 2nd Mechanical Room OS&Y 67977844 M3-64 Waterflow Switch 2nd Mechanical Room Vane 5778J04
M3-102 Control Valve Basement Pump Room Fire Pump Suction OS&Y 44133412 M4-88 Waterflow Switch Basement Stairwell B Vane 44133447 M4-89 Control Valve Basement Stairwell B OS&Y 44133446 M4-89 Tamper Switch Basement Stairwell B OS&Y 67977867 M4-98 Control Valve Basement Pump Room Backflow CV1 OS&Y 44133423 M4-98 Tamper Switch Basement Pump Room Backflow CV1 OS&Y 67977776 M4-99 Control Valve Basement Pump Room Backflow CV2 OS&Y 44133424 M4-99 Tamper Switch Basement Pump Room Backflow CV2 OS&Y 67977774 M4-99 Tamper Switch Basement Pump Room Backflow CV2 OS&Y 67977775 M4-99 Tamper Switch Basement Pump Room Backflow CV2 OS&Y 67977845
M4-100 Control Valve Basement Pump Room City Bypass CV1 OS&Y 44133419 M4-100 Control Valve Basement Pump Room Jockey pump OS&Y 44133425 M4-100 Control Valve Basement Pump Room Jockey pump OS&Y 44133426 M4-101 Control Valve Basement Pump Room City Bypass CV2 OS&Y 44133421 M4-103 Control Valve Basement Pump Room Fire Pump
Discharge
OS&Y 44133416
M4-103 Tamper Switch Basement Pump Room Fire Pump Discharge
OS&Y 67977772
M4-103 Control Valve Basement Pump Room Flow Meter CV2 OS&Y 44133418 javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133440');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133441');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133438');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133439');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780004');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133442');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','57780003');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133434');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977844');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','5778J04');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133412');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133447');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133446');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977867');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133423');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977776');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133424');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977774');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977775');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977845');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133419');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133425');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133426');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133421');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133416');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','67977772');
javascript:openEditDevice('load-edit-p2-device','736893','2792112','44133418');
| Sprinkler Inspection Certificate |
| Executive Summary |
| Inspection & Testing |
| Wet Pipe Fire Sprinkler Systems |
| Fire Pump Testing |
| Inventory & Warranty Report |
| Zone Address Report |
File details come from the government source that posted it. Updated .