This document contains a sprinkler inspection certificate for Building 129 at the Fort McPherson VA Medical Center in Atlanta, Georgia. The inspection was conducted by United Fire Protection - Atlanta and documents the inspection of various fire sprinkler system components including wet pipe, dry pipe, alarms, valves, gauges and sprinklers. All 27 items inspected passed inspection with no failures. The attached federal contract opportunity is solicitation number 36C24724Q0269 issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7 for fire sprinkler testing services. It seeks testing of sprinkler systems like those documented in the inspection certificate for Building 129 at the Fort McPherson VAMC.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sprinkler Inspection Certificate For
Fort McPherson VAMC Bldg 129 1701 Hardee Ave SW
Atlanta, GA 30310
Tested to NFPA 25 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Annual Inspection Inspection Date May 18, 2023
Building: Fort McPherson VAMC Bldg 129 Company: United Fire Protection - Atlanta Contact: Mike McGill Contact: Wayne Huxtable
Title: Maintenance & Operations Supervisor Title: Technician Sprinkler Inspection Report
Page of 2 12United Fire Protection - Atlanta Download Date: 05/22/2023
Executive Summary Generated by: BuildingReports.com
Building Information Building: Fort McPherson VAMC Bldg 129 Contact: Mike McGill Address: 1701 Hardee Ave SW Phone: 4043216111 Address: Fax:
City/State/ZIP Code: Atlanta, GA 30310 Mobile:
Country: United States of America Email:
Inspection Performed By Company: United Fire Protection - Atlanta Inspector: Wayne Huxtable Address: 2150 Boggs Rd Bldg 100 Phone: 770-771-0999 Address: Suite 140 Fax:
City/State/ZIP Code: Duluth, GA 30096 Mobile:
Country: United States of America Email: whuxtable@united-fire.com
System Control Unit System Type System Location Protected Area Devices Dry Pipe 7
Dry Pipe Zone-Atttic 6
Wet Pipe 5
Wet Pipe Zone-1 3
Inspection Summary
Category:
Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty % Alarm 7 25.93% 7 100.00% 7 100.00% 0 0.00%
Device 5 18.52% 5 100.00% 5 100.00% 0 0.00%
Pump 2 7.41% 2 100.00% 2 100.00% 0 0.00%
Sprinkler 4 14.81% 4 100.00% 4 100.00% 0 0.00%
Valve 9 33.33% 9 100.00% 9 100.00% 0 0.00%
Totals 27 100% 27 100.00% 27 100.00% 0 0.00%
Certification
Company: United Fire Protection - Atlanta Building: Fort McPherson VAMC Bldg 129
Inspector: Wayne Huxtable Contact: Mike McGill
Page of 3 12United Fire Protection - Atlanta Download Date: 05/22/2023
Inspection & Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 129 The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or
. Items are listed by Category. Each item includes the services performed, and the time & date at which testing Failed/Other occurred.
Device Type Location Service Time Date
Passed Waterflow Switch 1st Stairwell 2 Annual 10:53:12 AM 05/18/2023
Waterflow Switch 1st Riser Room BLDG 128 Main Feed for bldg 129
Annual 10:53:24 AM 05/18/2023
Waterflow Switch 2nd Stairwell 2 Annual 11:28:13 AM 05/17/2023
Gauge 1st Riser Room BLDG 128 Main Feed for bldg 129
Annual 11:28:06 AM 05/17/2023
Check Valve 1st Stairwell 2 Annual 11:38:13 AM 05/17/2023
Inspector's Test 2nd Stairwell 2 Annual 10:53:17 AM 05/18/2023
Dry Pipe
Drain 2nd Stairwell 2 Dry System 129 Attic Annual 11:14:04 AM 05/17/2023
Gauge 2nd Stairwell 2 Dry System 129 Attic Annual 11:13:38 AM 05/17/2023
Air Compressor 2nd Stairwell 2 Dry System 129 Attic Annual 11:13:46 AM 05/17/2023
Sprinkler Box 2nd Stairwell 2 Dry System 129 Attic Annual 10:53:00 AM 05/18/2023
Sprinkler Box Spares
2nd Stairwell 2 Dry System 129 Attic Annual 10:52:46 AM 05/18/2023
Sprinkler Box Spares
2nd Stairwell 2 Dry System 129 Attic Annual 10:52:49 AM 05/18/2023
Sprinkler Box Spares
2nd Stairwell 2 Dry System 129 Attic Annual 10:52:53 AM 05/18/2023
Dry Pipe, Zone-Atttic
Pressure Switch 2nd Stairwell 2 Dry System Annual 11:07:59 AM 05/17/2023
Pressure Switch 2nd Stairwell 2 Dry System Annual 11:09:24 AM 05/17/2023
Gauge 2nd Stairwell 2 Dry System 129 Attic Annual 11:10:09 AM 05/17/2023
Air Maintenance Device
2nd Stairwell 2 Dry System 129 Attic Annual 11:10:49 AM 05/17/2023
Alarm Valve 2nd Stairwell 2 Dry System 129 Attic Annual 11:06:39 AM 05/17/2023
Control Valve 2nd Stairwell 2 Dry System 129 Attic Annual 11:32:29 AM 05/17/2023
Wet Pipe
Gauge 1st Stairwell 2 Annual 12:13:22 PM 05/17/2023
Check Valve 2nd Stairwell 2 Annual 11:27:58 AM 05/17/2023
Control Valve 2nd Stairwell 2 Annual 11:27:47 AM 05/17/2023 javascript:editViewDevice('44133484');
javascript:editViewDevice('44133480');
javascript:editViewDevice('44133489');
javascript:editViewDevice('57780021');
javascript:editViewDevice('44133482');
javascript:editViewDevice('44133490');
javascript:editViewDevice('67977798');
javascript:editViewDevice('67977799');
javascript:editViewDevice('67977801');
javascript:editViewDevice('67977790');
javascript:editViewDevice('67977853');
javascript:editViewDevice('67977853');
javascript:editViewDevice('67977854');
javascript:editViewDevice('67977854');
javascript:editViewDevice('67977855');
javascript:editViewDevice('67977855');
javascript:editViewDevice('44133495');
javascript:editViewDevice('44133496');
javascript:editViewDevice('67977800');
javascript:editViewDevice('67977792');
javascript:editViewDevice('67977792');
javascript:editViewDevice('44133492');
javascript:editViewDevice('44133491');
javascript:editViewDevice('44133483');
javascript:editViewDevice('44133487');
javascript:editViewDevice('44133486');
Page of 4 12United Fire Protection - Atlanta Download Date: 05/22/2023
Device Type Location Service Time Date
Dry Pipe Valve 1st Riser Room BLDG 128 Main Feed for bldg 129
Annual 11:02:00 AM 05/18/2023
Inspector's Test 1st Stairwell 2 Annual 11:36:20 AM 05/17/2023
Wet Pipe, Zone-1
Tamper Switch 1st Stairwell 2 Annual 11:59:56 AM 05/17/2023
Waterflow Switch 1st Stairwell 2 Annual 11:44:18 AM 05/17/2023
Control Valve 1st Stairwell 2 Annual 11:57:48 AM 05/17/2023 javascript:editViewDevice('44133477');
javascript:editViewDevice('44133485');
javascript:editViewDevice('67978988');
javascript:editViewDevice('67977802');
javascript:editViewDevice('44133481');
Page of 5 12United Fire Protection - Atlanta Download Date: 05/22/2023
Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved 2nd Stairwell 2 03/29/2013 4" 44133487
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 2nd Stairwell 2 4" Open Supervised 44133486
Description Main Control
Dry Pipe Valve Manufacturer Model # Location Internal Date OK ScanID
Viking DN80 F2 1st Riser Room BLDG 128 Main Feed for bldg 129
03/28/2018 44133477
Type Status Position Size Serial # Flanged by Grooved Sealed Trim Open 3" 13764
Water psi Air Pressure Trip Air Trip Time Total Timing (sec)
Partial Trip Date
Full Trip Date
55 45 15 40 30 03/28/2013 03/28/2018
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1224 70 30.14 44133485
Location 1st Stairwell 2
Devices Gauge
Location Service Date 1st Stairwell 2 05/15/2027
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Reliable 55 Air/Water 1/4 44133483
Building: Fort McPherson VAMC Bldg
Zone-1 javascript:editViewDevice('44133487');
javascript:editViewDevice('44133486');
javascript:editViewDevice('44133477');
javascript:editViewDevice('44133485');
javascript:editViewDevice('44133483');
Page of 6 12United Fire Protection - Atlanta Download Date: 05/22/2023
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
OS&Y Supervisory 1st Stairwell 2 1-M1-3 67978988 Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 4” 1 67977802
Components Control Valve
Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 1st Stairwell 2 4" Open Supervised 44133481
Description Main Control javascript:editViewDevice('67978988');
javascript:editViewDevice('67977802');
javascript:editViewDevice('44133481');
Page of 7 12United Fire Protection - Atlanta Download Date: 05/22/2023
Dry Pipe Fire Sprinkler Systems Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Air Compressor Location Mfr. Model # Phase On psi Off psi Serial No.
2nd Stairwell 2 Dry System 129 Attic
General Air
1 21 40
Type Description Rated Speed Horsepower Volts Amps OK ScanID
Automatic Tank 1725 .75 115 40 67977801
Devices Drain
Current Inspection
Type Location Size Supply psi Restored psi
Residual psi Sec OK ScanID
Main 2nd Stairwell 2 Dry System 129 Attic
1.5" 50 50 30 67977798
Previous Inspections
February 9, 2023
Type Location Size Supply psi Static psi Residual psi Sec OK ScanID
Main 2nd Stairwell 2 Dry System 129 Attic
1.5" 50 50 30 67977798
October 28, 2022
Type Location Size Supply psi Static psi Residual psi Sec OK ScanID
Main 2nd Stairwell 2 Dry System 129 Attic
1.5" 50 50 30 67977798
Gauge Location Service Date 2nd Stairwell 2 Dry System 129 Attic 05/28/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID City Pressure Lansdale 50 Air/Water 1/4 67977799
Sprinkler Box
Qty Tool Available?
SIN List? Size Manufacturer Location OK ScanID
12 Yes 10 unit Viking 2nd Stairwell 2 Dry System 129 Attic
67977790
Sprinkler Box Spares javascript:editViewDevice('67977801');
javascript:editViewDevice('67977798');
javascript:editViewDevice('67977798');
javascript:editViewDevice('67977798');
javascript:editViewDevice('67977799');
javascript:editViewDevice('67977790');
Page of 8 12United Fire Protection - Atlanta Download Date: 05/22/2023
Qty Type Manufacturer Location OK ScanID
6 Pendant Viking 2nd Stairwell 2 Dry System 129 Attic
67977853
Temperature KFactor Size Finish Response Time 200 5.6 1/2 Brass Fast Response
Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID
6 Horizontal Sidewall Viking 2nd Stairwell 2 Dry System 129 Attic
67977854
Temperature KFactor Size Finish Response Time 200 5.6 1/2 Brass Fast Response
Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID
6 Horizontal Sidewall Tyco 2nd Stairwell 2 Dry System 129 Attic
67977855
Temperature KFactor Size Finish Response Time 212 5.6 1/2 Brass Fast Response
Building: Fort McPherson VAMC Bldg
Zone-Atttic
This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Air Maintenance Device Type Model # Location Install Date Air Pressure ScanID Pressure Reducing 2nd Stairwell 2 Dry System 129 Attic 03/29/2013 40 67977792
Alarms Pressure Switch Type Description Manufacturer Low High Zone/Address OK ScanID Low Supervisory Potter Electric 15 30 1 44133495 Pressure Switch Alarm Potter Electric 0 50 1-M1-42 44133496
Components Alarm Valve
Type Manufacturer Model # Position Status Size OK ScanID Grooved Viking F-2 Trim Open Sealed 4" 44133492
Internal Date 03/29/2013
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Victaulic 705 2nd Stairwell 2 Dry System 129 Attic
4" Open Supervised 44133491
Description javascript:editViewDevice('67977853');
javascript:editViewDevice('67977854');
javascript:editViewDevice('67977855');
javascript:editViewDevice('67977792');
javascript:editViewDevice('44133495');
javascript:editViewDevice('44133496');
javascript:editViewDevice('44133492');
javascript:editViewDevice('44133491');
Page of 9 12United Fire Protection - Atlanta Download Date: 05/22/2023
Main Control
Devices Gauge
Location Service Date 2nd Stairwell 2 Dry System 129 Attic 03/29/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID Air Pressure Viking 40 Air/Water 1/4 67977800 javascript:editViewDevice('67977800');
Page of 10 12United Fire Protection - Atlanta Download Date: 05/22/2023
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 129 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Air Compressor Pump 3.70% 1
Air Maintenance Device Pump 3.70% 1
Alarm Valve Valve 3.70% 1
Check Valve Valve 7.41% 2
Control Valve Valve 11.11% 3
Drain Device 3.70% 1
Dry Pipe Valve Valve 3.70% 1
Gauge Device 14.81% 4
Inspector's Test Valve 7.41% 2
Pressure Switch Alarm 7.41% 2
Sprinkler Box Sprinkler 3.70% 1
Sprinkler Box Spares Sprinkler 11.11% 3
Tamper Switch Alarm 3.70% 1
Waterflow Switch Alarm 14.81% 4
Device Type Qty Model # Type Description Install Date
In Service - 1 Year to 2 Years Wet Pipe
Gauge 1 System Pressure 05/15/2022
Dry Pipe Gauge 1 City Pressure 05/28/2021
Dry Pipe, Zone-Atttic Gauge 1 Air Pressure 05/28/2021
In Service - 3 Years to 5 Years Gauge 1 System Pressure 07/11/2018
In Service - 10 Years to 15 Years Waterflow Switch 1 VSR Vane Alarm 03/29/2013 Check Valve 1 717H Grooved 03/29/2013
Dry Pipe Air Compressor 1 Automatic Tank 03/29/2013 Drain 1 F-2 Main 03/29/2013 Sprinkler Box 1 03/29/2013 Sprinkler Box Spares 1 VK302 Pendant 03/29/2013
Dry Pipe, Zone-Atttic Pressure Switch 1 PS-10 Pressure Switch Alarm 03/29/2013
Page of 11 12United Fire Protection - Atlanta Download Date: 05/22/2023
Pressure Switch 1 PS-40 Low Supervisory 03/29/2013 Air Maintenance Device 1 Pressure Reducing 03/29/2013 Control Valve 1 705 Butterfly Main Control 03/29/2013 Alarm Valve 1 F-2 Grooved 03/29/2013
Wet Pipe Check Valve 1 717H Grooved 03/29/2013 Control Valve 1 705 Butterfly Main Control 03/29/2013
Wet Pipe, Zone-1 Control Valve 1 705 Butterfly Main Control 03/29/2013 Tamper Switch 1 705 OS&Y Supervisory 03/29/2013
Wet Pipe Dry Pipe Valve 1 DN80 F2 Flanged by Grooved 03/28/2013
Inspector's Test 1 1224 03/29/2012 Waterflow Switch 2 VSR Vane Alarm 03/29/2012
Dry Pipe Sprinkler Box Spares 1 TY3180 Horizontal Sidewall 03/29/2012
Wet Pipe Inspector's Test 1 1224 03/29/2012
Wet Pipe, Zone-1 Waterflow Switch 1 VSR Vane Alarm 03/29/2012
Dry Pipe Sprinkler Box Spares 1 VK302 Horizontal Sidewall 03/29/2011
Page of 12 12United Fire Protection - Atlanta Download Date: 05/22/2023
Zone Address Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 129 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
Control Panel 1 M1-3 Control Valve 1st Stairwell 2 Butterfly 44133481 M1-3 Tamper Switch 1st Stairwell 2 OS&Y 67978988 M1-27 Waterflow Switch 1st Riser Room BLDG 128 Main Feed for bldg 129 Vane 44133480
M1-41 Control Valve 2nd Stairwell 2 Dry System 129 Attic Butterfly 44133491 M1-42 Pressure Switch 2nd Stairwell 2 Dry System Pressure Switch 44133496 M1-61 Waterflow Switch 2nd Stairwell 2 Vane 44133489 M1-62 Control Valve 2nd Stairwell 2 Butterfly 44133486 m1-4 Waterflow Switch 1st Stairwell 2 Vane 44133484 javascript:editViewDevice('44133481');
javascript:editViewDevice('67978988');
javascript:editViewDevice('44133480');
javascript:editViewDevice('44133491');
javascript:editViewDevice('44133496');
javascript:editViewDevice('44133489');
javascript:editViewDevice('44133486');
javascript:editViewDevice('44133484');