2023-02-09_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf

PDF 135 KB Posted

Attached to
Fire Sprinkler Testing
Solicitation number
36C24724Q0269
Issued by

About this file

This document is a fire sprinkler inspection report for Building 130 at the Fort McPherson VA Medical Center in Atlanta, Georgia. The report was conducted by United Fire Protection - Atlanta and documents the inspection of the building's wet pipe, dry pipe, and backflow prevention fire sprinkler systems. It provides details on all devices and components tested, including control valves, waterflow switches, gauges, dry pipe valves, check valves, sprinkler heads, and alarm devices. For each item, it records the manufacturer, model, location, inspection results, and notes any maintenance or repairs needed. The report also includes an inventory of all systems and components with installation dates and warranty information. This level of detailed system documentation provides the information necessary for facilities managers to maintain code compliance and properly service the fire protection equipment.

View the file

Other files

File Type Posted
FIRE ALARM 130.pdf PDF
2022-06-20_Fort-McPherson-VAMC-Bldg-128_Annual Report.pdf PDF
BLDG 131 ASBUILTS.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-131_Annual Report.pdf PDF
FIRE SUPPRESSION.pdf PDF
2022-06-20_Fort-McPherson-VAMC-Bldg-129_Annual Report.pdf PDF
BLDG 125 ASBUILT.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-125_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-128_SprinklerScan.pdf PDF
Ft. McPherson Bldg 128 Fire Alarm Drawings - RECORD Dwg.pdf PDF
Bldg 128 As-Builts.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
FIRE ALARM 129.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-125_SprinklerScan.pdf PDF
BLDG 129 ASBUILT.pdf PDF
2023-02-10_Fort-McPherson-VAMC-Bldg-128_SprinklerScan (1).pdf PDF
36C24724Q0269 0001.pdf PDF
03 Series LIFE SAFETY - 100 AT-130 Fort McPherson Residental Treatment.pdf PDF
03 Series LIFE SAFETY - 100 AT-131 Fort McPherson Domiciliary Care.pdf PDF
03 Series LIFE SAFETY - 100 AT-125 Fort McPherson OPC.pdf PDF
FIRE ALARM 125.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-125_Annual Report.pdf PDF
04 Series DOORS - 100 AT-130 Fort McPherson Residental Treatment.pdf PDF
04 Series DOORS - 100 AT-125 Fort McPherson OPC.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-128_SprinklerScan.pdf PDF
05 series dampers - 100 at-125 fort mcpherson opc.pdf PDF
FIRE SUPPRESSION 131.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-130_Annual Report.pdf PDF
03 Series LIFE SAFETY - 100 AT-128 Fort McPherson Homeless Program.pdf PDF
04 Series DOORS - 100 AT-128 Fort McPherson Homeless Program.pdf PDF
BLDG. 125 FIRE SUPPRESSION.pdf PDF
04 Series DOORS - 100 AT-131 Fort McPherson Domiciliary Care.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-129_SprinklerScan.pdf PDF
36C24724Q0269.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sprinkler Inspection Certificate For

Fort McPherson VAMC Bldg 130 1701 Hardee Ave SW

Atlanta, GA 30310

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Quarterly Inspection Inspection Date Feb 9, 2023

Building: Fort McPherson VAMC Bldg 130 Company: United Fire Protection - Atlanta Contact: Mike McGill Contact: Wayne Huxtable

Title: Maintenance & Operations Supervisor Title: Technician

Page of 1 16United Fire Protection - Atlanta Download Date: 03/22/2023

Executive Summary Generated by: BuildingReports.com

Building Information Building: Fort McPherson VAMC Bldg 130 Contact: Mike McGill Address: 1701 Hardee Ave SW Phone: 14043216111 Address: Fax:

City/State/ZIP Code: Atlanta, GA 30310 Mobile:

Country: United States of America Email:

Inspection Performed By Company: United Fire Protection - Atlanta Inspector: Wayne Huxtable Address: 2150 Boggs Rd Bldg 100 Phone: 770-771-0999 Address: Suite 140 Fax:

City/State/ZIP Code: Duluth, GA 30096 Mobile:

Country: United States of America Email: whuxtable@united-fire.com

System Control Unit System Type System Location Protected Area Devices Cross Conn. Control 4

Dry Pipe 8

Wet Pipe 56

Inspection Summary

Category:

Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Alarm 19 27.94% 14 73.68% 14 100.00% 0 0.00%

Device 9 13.24% 0 0.00% 0 0.00% 0 0.00%

Pump 2 2.94% 2 100.00% 2 100.00% 0 0.00%

Sprinkler 10 14.71% 0 0.00% 0 0.00% 0 0.00%

Valve 28 41.18% 17 60.71% 17 100.00% 0 0.00%

Totals 68 100% 33 48.53% 33 100.00% 0 0.00%

Certification

Company: United Fire Protection - Atlanta Building: Fort McPherson VAMC Bldg 130

Inspector: Wayne Huxtable Contact: Mike McGill

Page of 2 16United Fire Protection - Atlanta Download Date: 03/22/2023

Inspection & Testing Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 130 The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or

. Items are listed by Category. Each item includes the services performed, and the time & date at which testing Failed/Other occurred.

Device Type Location Service Time Date

Passed Cross Conn. Control

Tamper Switch Basement Boiler Room Backflow CV 2 Quarterly 10:21:10 AM 02/09/2023

Control Valve Basement Boiler Room Backflow CV 1 Quarterly 11:02:04 AM 02/09/2023

Control Valve Basement Boiler Room Backflow CV 2 Quarterly 4:33:09 PM 02/09/2023

Dry Pipe Pressure Switch 2nd Stairwell 2 Dry System High Pressure Quarterly 10:27:02 AM 02/09/2023

Pressure Switch 2nd Stairwell 2 Dry System Low Air Quarterly 10:27:32 AM 02/09/2023

Air Compressor 2nd Stairwell 2 Dry System Quarterly 10:26:04 AM 02/09/2023

Air Maintenance Device

2nd Stairwell 2 Dry System Quarterly 10:27:22 AM 02/09/2023

Dry Pipe Valve 2nd Stairwell 2 Passenger Elevator Quarterly 10:29:16 AM 02/09/2023

Wet Pipe Tamper Switch Basement Boiler Room Main Feed for bldg Quarterly 11:01:26 AM 02/09/2023

Tamper Switch Basement Boiler Room Test Header Quarterly 11:02:55 AM 02/09/2023

Tamper Switch Basement GD-002 Stairwell 2 Passenger Elevator

Quarterly 11:00:40 AM 02/09/2023

Tamper Switch Ground outside Between D and C Quarterly 11:11:06 AM 02/09/2023

Tamper Switch Ground outside @ B building Quarterly 11:11:31 AM 02/09/2023

Waterflow Switch Basement 130 Wet Quarterly 11:04:08 AM 02/09/2023

Waterflow Switch Basement Wet Quarterly 11:04:48 AM 02/09/2023

Waterflow Switch 1st Stairwell 2 Zone 1-1 Quarterly 10:22:57 AM 02/09/2023

Waterflow Switch 1st Stairwell 2 Zone 1-2 Quarterly 10:23:07 AM 02/09/2023

Waterflow Switch 2nd Stairwell 2 Zone 2-1 Quarterly 10:33:42 AM 02/09/2023

Waterflow Switch 2nd Stairwell 2 Zone 2-2 Quarterly 10:34:05 AM 02/09/2023

Control Valve Basement 130 Boiler Room Main Feed for bldg

Quarterly 11:01:10 AM 02/09/2023

Control Valve Basement 130 Wet Quarterly 11:01:33 AM 02/09/2023

Control Valve Basement Boiler Room Test Header Quarterly 11:03:06 AM 02/09/2023

Control Valve 1st Stairwell 2 Zone 1-1 Quarterly 10:21:24 AM 02/09/2023

Control Valve 1st Stairwell 2 Zone 1-2 Quarterly 10:22:26 AM 02/09/2023

Control Valve 2nd Stairwell 2 Dry System Quarterly 10:26:22 AM 02/09/2023 javascript:openEditDevice('load-edit-p2-device','736896','2792110','67977795');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133530');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133531');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133525');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133524');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','67977852');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780028');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780028');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133520');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','67977797');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','67977796');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133542');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780054');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780010');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133540');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780039');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133499');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133504');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133510');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133515');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133533');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133538');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133532');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133497');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133502');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133518');

Page of 3 16United Fire Protection - Atlanta Download Date: 03/22/2023

Device Type Location Service Time Date

Control Valve 2nd Stairwell 2 Zone 2-1 Quarterly 10:29:57 AM 02/09/2023

Control Valve 2nd Stairwell 2 Zone 2-2 Quarterly 10:30:12 AM 02/09/2023

Control Valve Basement GD-002 Stairwell 2 Passenger Elevator

Quarterly 11:00:24 AM 02/09/2023

Control Valve Ground outside Between D and C Quarterly 11:10:59 AM 02/09/2023

Control Valve Ground outside @ B building Quarterly 11:11:35 AM 02/09/2023

Inspector's Test 2nd Stairwell 2 Zone 2-2 Quarterly 10:34:34 AM 02/09/2023

Inspector's Test 2nd Stairwell 2 Zone 2-1 Quarterly 10:34:44 AM 02/09/2023

Manifold 2nd Stairwell 2 Passenger Elevator Quarterly 10:34:59 AM 02/09/2023

Untested Cross Conn. Control

Tamper Switch Basement Boiler Room Backflow CV 1

Dry Pipe Waterflow Switch 2nd Stairwell 2 Dry System

Gauge 2nd Stairwell 2 Dry System

Gauge 2nd Stairwell 2 Dry System

Wet Pipe Tamper Switch 2nd Stairwell 2 Passenger Elevator

Waterflow Switch 2nd Stairwell 2 Passenger Elevator

Waterflow Switch 2nd Stairwell 2 Passenger Elevator

Drain Basement 130 Boiler Room Main Feed for bldg

Gauge Basement 130 Boiler Room Main Feed for

Gauge Basement 130 Boiler Room Main Feed for

Gauge 1st Stairwell 2 Zone 1-1

Gauge 1st Stairwell 2 Zone 1-2

Gauge 2nd Stairwell 2 Zone 2-1

Gauge 2nd Stairwell 2 Zone 2-1

Sprinkler Box Basement 130 Boiler Room Main Feed for

Sprinkler Box Basement Boiler Room Main Feed for bldg

Sprinkler Box Basement Boiler Room Main Feed for bldg

Sprinkler Box Spares

Basement Boiler Room Main Feed for bldg

Sprinkler Box Spares

Basement Boiler Room Main Feed for bldg

Sprinkler Box Spares

Basement 130 Boiler Room Main Feed for javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133507');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133512');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780038');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780053');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780011');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133516');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133511');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133519');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','67977794');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133526');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780025');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780027');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133527');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133528');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133543');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133537');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133535');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133536');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780013');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780022');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133509');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780024');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780029');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780031');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780034');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780030');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780030');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780032');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780032');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780033');

Page of 4 16United Fire Protection - Atlanta Download Date: 03/22/2023

Device Type Location Service Time Date

Sprinkler Box Spares

Basement Boiler Room Main Feed for bldg

Sprinkler Box Spares

Basement Boiler Room Main Feed for bldg

Sprinkler Box Spares

Basement Boiler Room Main Feed for bldg

Wrenches Basement Boiler Room Main Feed for bldg

Check Valve Basement 130 Boiler Room Main Feed for

Check Valve Basement 130 Wet

Check Valve Basement Wet

Check Valve 1st Stairwell 2 Zone 1-1

Check Valve 1st Stairwell 2 Zone 1-2

Check Valve 2nd Stairwell 2 Zone 2-1

Check Valve 2nd Stairwell 2 Zone 2-2

Control Valve Basement GD-002 Stairwell 2 Passenger Elevator

Inspector's Test 1st Stairwell 2 Zone 1-1

Inspector's Test 1st Stairwell 2 Zone 1-2

Inspector's Test 1st Stairwell 2 Zone 1-1 javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780035');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780035');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780036');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780036');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780037');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780037');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780055');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133534');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133539');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780040');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133498');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133503');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133508');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133513');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133529');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133501');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133506');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133541');

Page of 5 16United Fire Protection - Atlanta Download Date: 03/22/2023

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Location Number of Turns

Zone /Address

OK ScanID

OS&Y Supervisory Basement Boiler Room Main Feed for bldg

1-M1-4 67977797

OS&Y Supervisory Basement Boiler Room Test Header

1-M1- 67977796

Control Valve Supervisory Basement GD-002 Stairwell 2 Passenger Elevator

1-M1-5 44133542

Control Valve Supervisory Ground outside Between D and C 1 57780054 Control Valve Supervisory Ground outside @ B building 1 57780010

Control Valve Supervisory 2nd Stairwell 2 Passenger Elevator

1-M1-19 44133527

Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 4" 1-M1-7 44133540 Vane Potter Electric VS-SP 1’’ 1-M1-7 57780039 Vane Potter Electric VSR 4" 1-M1-34 44133499 Vane Potter Electric VSR 4" 1-M1-33 44133504 Vane Potter Electric VSR 4" 1-M1-79 44133510 Vane Potter Electric VSR 4" 1-M1-80 44133515 Vane Potter Electric VS-SP 1" 1-M1-18 44133528 Vane Potter Electric VS-SP 1" 1-M1-18 44133543

Components Check Valve

Type Location Internal Date Size OK ScanID

Flanged Basement 130 Boiler Room Main Feed for bldg

03/29/2012 8" 44133534

Grooved Basement 130 Wet 03/29/2018 4" 44133539 Grooved Basement Wet 03/29/2018 4" 57780040 Grooved 1st Stairwell 2 Zone 1-1 03/29/2018 4" 44133498 Grooved 1st Stairwell 2 Zone 1-2 03/29/2018 4" 44133503 Grooved 2nd Stairwell 2 Zone 2-1 03/29/2018 4" 44133508 Grooved 2nd Stairwell 2 Zone 2-2 03/29/2018 4" 44133513 javascript:openEditDevice('load-edit-p2-device','736896','2792110','67977797');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','67977796');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133542');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780054');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780010');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133527');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133540');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780039');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133499');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133504');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133510');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133515');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133528');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133543');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133534');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133539');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780040');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133498');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133503');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133508');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133513');

Page of 6 16United Fire Protection - Atlanta Download Date: 03/22/2023

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Kennedy KS-FW

Basement 130 Boiler Room Main Feed for bldg

4" 44133533

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Anvil AN7722-3A Basement 130 Wet

4" 44133538

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Kennedy KS-FW Basement Boiler Room Test Header

6" 44133532

Description

CV 2

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Anvil AN7722-3A 1st Stairwell 2 Zone 1-1

4" Open Supervised 44133497

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Anvil AN7722-3A 1st Stairwell 2 Zone 1-2

4" Open Supervised 44133502

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Anvil AN7722-3A 2nd Stairwell 2 Dry System

4" Open Supervised 44133518

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Anvil AN7722-3A 2nd Stairwell 2 Zone 2-1

4" Open Supervised 44133507 javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133533');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133538');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133532');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133497');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133502');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133518');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133507');

Page of 7 16United Fire Protection - Atlanta Download Date: 03/22/2023

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Anvil AN7722-3A 2nd Stairwell 2 Zone 2-2

4" Open Supervised 44133512

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Milwaukee BB-SCS

Basement GD- 002 Stairwell 2 Passenger Elevator

1" 57780038

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Post Indicator Valve

Mueller Ground outside Between D and C

6" Open Supervised 57780053

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Post Indicator Valve

Mueller Ground outside @ B building

6" 57780011

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Milwaukee BB-SCS

Basement GD- 002 Stairwell 2 Passenger Elevator

1" 44133529

Description Main Control

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1324 65 45 44133516

Location 2nd Stairwell 2 Zone 2-2

Inspector's Test javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133512');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780038');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780053');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780011');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133529');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133516');

Page of 8 16United Fire Protection - Atlanta Download Date: 03/22/2023

Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1324 65 33 44133511

Location 2nd Stairwell 2 Zone 2-1

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1324 65 44133501

Location 1st Stairwell 2 Zone 1-1

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1324 65 26 44133506

Location 1st Stairwell 2 Zone 1-2

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 100 65 45 44133541

Location 1st Stairwell 2 Zone 1-1

Manifold Location Manufacturer Size ScanID

2nd Stairwell 2 Passenger Elevator United Brass 2" 44133519

Devices Drain

Type Location Size Supply psi Restored psi

Residual psi Sec OK ScanID

Combination Basement 130 Boiler Room Main Feed for bldg

2" 60 60 40 44133537

Gauge Location Service Date Basement 130 Boiler Room Main Feed for bldg 03/29/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Lansdale 75 1/4 44133535

Gauge Location Service Date Basement 130 Boiler Room Main Feed for bldg 03/29/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Lansdale 70 1/4 44133536

Gauge Location Service Date 1st Stairwell 2 Zone 1-1 03/29/2026 javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133511');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133501');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133506');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133541');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133519');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133537');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133535');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133536');

Page of 9 16United Fire Protection - Atlanta Download Date: 03/22/2023

Type Manufacturer Model # Static psi Fill Type Size OK ScanID City Pressure Lansdale 65 1/4 57780013

Gauge Location Service Date 1st Stairwell 2 Zone 1-2 03/29/2019

Type Manufacturer Model # Static psi Fill Type Size OK ScanID City Pressure Wika Wika 65 1/4 57780022

Gauge Location Service Date 2nd Stairwell 2 Zone 2-1 03/29/2012

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Wika Wika 65 1/4 44133509

Gauge Location Service Date 2nd Stairwell 2 Zone 2-1 03/29/2012

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Wika Wika 65 1/4 57780024

Sprinkler Box

Qty Tool Available?

SIN List? Size Manufacturer Location OK ScanID

6 Yes 6 unit Viking Basement 130 Boiler Room Main Feed for bldg

57780029

6 Yes Yes 6 unit Viking Basement Boiler Room Main Feed for bldg

57780031

6 Yes Yes 6 unit Viking Basement Boiler Room Main Feed for bldg

57780034

Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID

6 Pendant Viking Basement Boiler Room Main Feed for bldg

57780030

Temperature KFactor Size Finish Response Time 200 4.2 0.5 Chrome Fast Response

Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID

1 Horizontal Sidewall Viking Basement Boiler Room Main Feed for bldg

57780032

Temperature KFactor Size Finish Response Time 200 4.2 0.5 Chrome Fast Response

Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID

1 Horizontal Sidewall Viking Basement 130 Boiler Room Main Feed for bldg

57780033 javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780013');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780022');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133509');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780024');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780029');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780031');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780034');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780030');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780032');

Page of 10 16United Fire Protection - Atlanta Download Date: 03/22/2023

Temperature KFactor Size Finish Response Time 200 4.2 3/4 “ Brass Fast Response

Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID

3 Attic Tyco Basement Boiler Room Main Feed for bldg

57780035

Temperature KFactor Size Finish Response Time 212* 1/2” Brass Fast Response

Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID

3 Upright Viking Basement Boiler Room Main Feed for bldg

57780036

Temperature KFactor Size Finish Response Time 212* 4.2 1/2” Brass Fast Response

Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID

1 Upright Viking Basement Boiler Room Main Feed for bldg

57780037

Temperature KFactor Size Finish Response Time 200 4.2 0.5 Brass Fast Response

Wrenches Qty Type Manufacturer Location OK ScanID 1 Sprinkler Reliable Basement Boiler Room Main

Feed for bldg 57780055 javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780035');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780036');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780037');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780055');

Page of 11 16United Fire Protection - Atlanta Download Date: 03/22/2023

Dry Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Air Compressor Location Mfr. Model # Phase On psi Off psi Serial No.

2nd Stairwell 2 Dry System

General Air

1 20 40

Type Description Rated Speed Horsepower Volts Amps OK ScanID

Automatic Tank 1723 1 120 67977852

Air Maintenance Device Type Model # Location Install Date Air Pressure ScanID Pressure Reducing Wika 2nd Stairwell 2 Dry System 07/11/2018 40 57780028

Alarms Pressure Switch Type Description Manufacturer Low High Zone/Address OK ScanID High Alarm Potter Electric 0 50 1-M1-83 44133525 Low Supervisory Potter Electric 15 30 1-M84 44133524

Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter electric VSR 4 1 44133526

Components Dry Pipe Valve

Manufacturer Model # Location Internal Date OK ScanID Viking F-2 2nd Stairwell 2 Passenger Elevator 03/29/2018 44133520

Type Status Position Size Serial # Grooved Sealed 4"

Water psi Air Pressure Trip Air Trip Time Total Timing (sec)

Partial Trip Date

Full Trip Date

03/29/2012 03/29/2018

Devices Gauge

Location Service Date 2nd Stairwell 2 Dry System 05/27/2025

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Lansdale 65 1/4 57780025 javascript:openEditDevice('load-edit-p2-device','736896','2792110','67977852');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780028');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133525');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133524');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133526');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133520');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780025');

Page of 12 16United Fire Protection - Atlanta Download Date: 03/22/2023

Gauge Location Service Date 2nd Stairwell 2 Dry System 03/29/2025

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Air Pressure Wika Wika 30 1/4 57780027 javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780027');

Page of 13 16United Fire Protection - Atlanta Download Date: 03/22/2023

Backflow Test & Maintenance Report Generated by: BuildingReports.com

This section lists out all the devices and components that have been associated with a Cross Connection Control System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Location Number of Turns

Zone /Address

OK ScanID

Basement Boiler Room Backflow

CV 2

1-M1-2 67977795

OS&Y Supervisory Basement Boiler Room Backflow

CV 1

1-M1-1 67977794

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Kennedy KS-FW Basement Boiler Room Backflow CV 1

6" Open Supervised 44133530

Description

CV 1

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Kennedy KS-FW Basement Boiler Room Backflow CV 2

6" Open Supervised 44133531

Description

CV 2

javascript:openEditDevice('load-edit-p2-device','736896','2792110','67977795');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','67977794');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133530');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133531');

Page of 14 16United Fire Protection - Atlanta Download Date: 03/22/2023

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 130 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Air Compressor Pump 1.47% 1

Air Maintenance Device Pump 1.47% 1

Check Valve Valve 10.29% 7

Control Valve Valve 20.59% 14

Drain Device 1.47% 1

Dry Pipe Valve Valve 1.47% 1

Gauge Device 11.76% 8

Inspector's Test Valve 7.35% 5

Manifold Valve 1.47% 1

Pressure Switch Alarm 2.94% 2

Sprinkler Box Sprinkler 4.41% 3

Sprinkler Box Spares Sprinkler 8.82% 6

Tamper Switch Alarm 11.76% 8

Waterflow Switch Alarm 13.24% 9

Wrenches Sprinkler 1.47% 1

Device Type Qty Model # Type Description Install Date

In Service - 1 Year to 2 Years Wet Pipe

Gauge 1 City Pressure 05/28/2021 Gauge 1 Supply Pressure 05/28/2021

Dry Pipe Gauge 1 Supply Pressure 05/27/2021 Gauge 1 Wika Air Pressure 05/27/2021

Wet Pipe Gauge 1 Supply Pressure 05/27/2021

In Service - 3 Years to 5 Years Dry Pipe

Air Compressor 1 Automatic Tank 07/11/2018 Waterflow Switch 1 VSR Vane Alarm 07/11/2018 Air Maintenance Device 1 Wika Pressure Reducing 07/11/2018

Wet Pipe Gauge 2 Wika 07/11/2018 Gauge 1 Wika City Pressure 07/11/2018 Inspector's Test 1 100 03/29/2018

Page of 15 16United Fire Protection - Atlanta Download Date: 03/22/2023

Inspector's Test 4 1324 03/29/2018 Check Valve 6 78FP Grooved 03/29/2018 Control Valve 6 AN7722-3A Butterfly Isolation 03/29/2018 Waterflow Switch 1 VS-SP Vane Alarm 03/29/2018 Waterflow Switch 5 VSR Vane Alarm 03/29/2018

In Service - 10 Years to 15 Years Cross Conn. Control

Control Valve 1 KS-FW OS&Y CV 1 03/29/2012 Control Valve 1 KS-FW OS&Y CV 2 03/29/2012 Tamper Switch 1 OSYSU-2 03/29/2012 Tamper Switch 1 OSYSU-2 OS&Y Supervisory 03/29/2012

Dry Pipe Pressure Switch 1 PS-10 High Alarm 03/29/2012 Pressure Switch 1 PS-40 Low Supervisory 03/29/2012 Dry Pipe Valve 1 F-2 Grooved 03/29/2012

Wet Pipe Drain 1 1000 Combination 03/29/2012 Control Valve 1 KS-FW OS&Y CV 2 03/29/2012 Control Valve 1 KS-FW OS&Y Main Control 03/29/2012 Control Valve 1 BB-SCS Butterfly Isolation 03/29/2012 Control Valve 1 BB-SCS Butterfly Main Control 03/29/2012 Tamper Switch 1 BB-SCS Control Valve Supervisory 03/29/2012 Control Valve 2 Post Indicator Valve Main Control 03/29/2012 Tamper Switch 1 OSYSU-2 OS&Y Supervisory 03/29/2012 Tamper Switch 2 PIVS-2 Control Valve Supervisory 03/29/2012 Tamper Switch 1 PTS-C Control Valve Supervisory 03/29/2012 Waterflow Switch 2 VS-SP Vane Alarm 03/29/2012 Tamper Switch 1 OSYSU-2 OS&Y Supervisory 03/29/2012 Wrenches 1 Sprinkler 03/29/2012 Sprinkler Box Spares 1 BB1 / TY3180 Attic 03/29/2012 Manifold 1 F-2 03/29/2012 Check Valve 1 F-1 Flanged 03/29/2012 Sprinkler Box 3 03/29/2012 Sprinkler Box Spares 2 Horizontal Sidewall 03/29/2012 Sprinkler Box Spares 1 Upright 03/29/2012 Sprinkler Box Spares 1 M-10 Pendant 03/29/2012 Sprinkler Box Spares 1 m Upright 03/29/2012

Page of 16 16United Fire Protection - Atlanta Download Date: 03/22/2023

Zone Address Report Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 130 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID

Control Panel 1 M1- Control Valve Basement Boiler Room Test Header OS&Y 44133532 M1- Tamper Switch Basement Boiler Room Test Header OS&Y 67977796

M1-1 Control Valve Basement Boiler Room Backflow CV 1 OS&Y 44133530 M1-1 Tamper Switch Basement Boiler Room Backflow CV 1 OS&Y 67977794 M1-1 Control Valve 1st Stairwell 2 Zone 1-1 Butterfly 44133497 M1-2 Control Valve Basement Boiler Room Backflow CV 2 OS&Y 44133531 M1-2 Tamper Switch Basement Boiler Room Backflow CV 2 67977795 M1-4 Tamper Switch Basement Boiler Room Main Feed for bldg OS&Y 67977797 M1-4 Control Valve Basement 130 Boiler Room Main Feed for bldg

OS&Y 44133533

M1-5 Control Valve Basement GD-002 Stairwell 2 Passenger Elevator

Butterfly 44133529

M1-5 Control Valve Basement GD-002 Stairwell 2 Passenger Elevator

Butterfly 57780038

M1-5 Tamper Switch Basement GD-002 Stairwell 2 Passenger Elevator

Control Valve 44133542

M1-7 Waterflow Switch Basement Wet Vane 57780039 M1-7 Control Valve Basement 130 Wet Butterfly 44133538 M1-7 Waterflow Switch Basement 130 Wet Vane 44133540 M1-18 Waterflow Switch 2nd Stairwell 2 Passenger Elevator Vane 44133528 M1-18 Waterflow Switch 2nd Stairwell 2 Passenger Elevator Vane 44133543 M1-19 Tamper Switch 2nd Stairwell 2 Passenger Elevator Control Valve 44133527 M1-33 Control Valve 1st Stairwell 2 Zone 1-2 Butterfly 44133502 M1-33 Waterflow Switch 1st Stairwell 2 Zone 1-2 Vane 44133504 M1-34 Waterflow Switch 1st Stairwell 2 Zone 1-1 Vane 44133499 M1-79 Control Valve 2nd Stairwell 2 Zone 2-1 Butterfly 44133507 M1-79 Waterflow Switch 2nd Stairwell 2 Zone 2-1 Vane 44133510 M1-80 Control Valve 2nd Stairwell 2 Zone 2-2 Butterfly 44133512 M1-80 Waterflow Switch 2nd Stairwell 2 Zone 2-2 Vane 44133515 M1-81 Control Valve 2nd Stairwell 2 Dry System Butterfly 44133518 M1-83 Pressure Switch 2nd Stairwell 2 Dry System High Pressure High 44133525 M84 Pressure Switch 2nd Stairwell 2 Dry System Low Air Low 44133524 javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133532');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','67977796');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133530');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','67977794');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133497');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133531');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','67977795');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','67977797');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133533');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133529');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780038');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133542');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','57780039');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133538');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133540');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133528');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133543');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133527');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133502');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133504');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133499');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133507');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133510');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133512');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133515');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133518');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133525');

javascript:openEditDevice('load-edit-p2-device','736896','2792110','44133524');

Sprinkler Inspection Certificate
Executive Summary
Inspection & Testing
Wet Pipe Fire Sprinkler Systems
Dry Pipe Fire Sprinkler Systems
Backflow Test & Maintenance Report
Inventory & Warranty Report
Zone Address Report