2023-02-10_Fort-McPherson-VAMC-Bldg-128_SprinklerScan (1).pdf

PDF 82 KB Posted

Attached to
Fire Sprinkler Testing
Solicitation number
36C24724Q0269
Issued by

About this file

This document contains a sprinkler inspection certificate for building 128 at the Fort McPherson VA Medical Center in Atlanta, Georgia. The inspection was performed by United Fire Protection - Atlanta and documents the testing of 39 items including alarms, devices, hoses, valves, gauges, and control valves. The inspection summary indicates that 29 items passed inspection with no failures. The inspection and testing section provides details on each item inspected including the type of device, location, service performed, and date and time of testing. Additional sections include information on the wet pipe fire sprinkler system components, an inventory and warranty report, and a zone address report listing the devices and items with individual addresses.

This relates to the federal contract opportunity solicitation number 36C24724Q0269 for fire sprinkler testing issued by the Department of Veterans Affairs Veterans Health Administration VISN 7. Based on the building and location specified in the sprinkler inspection certificate, this appears to be documentation of the incumbent contractor's most recent inspection of the fire sprinkler system at that site, which would need to continue to receive regular maintenance and testing under the follow-on contract.

View the file

Other files

File Type Posted
FIRE ALARM 130.pdf PDF
2022-06-20_Fort-McPherson-VAMC-Bldg-128_Annual Report.pdf PDF
BLDG 131 ASBUILTS.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-131_Annual Report.pdf PDF
FIRE SUPPRESSION.pdf PDF
2022-06-20_Fort-McPherson-VAMC-Bldg-129_Annual Report.pdf PDF
BLDG 125 ASBUILT.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-125_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-128_SprinklerScan.pdf PDF
Ft. McPherson Bldg 128 Fire Alarm Drawings - RECORD Dwg.pdf PDF
Bldg 128 As-Builts.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
FIRE ALARM 129.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-125_SprinklerScan.pdf PDF
BLDG 129 ASBUILT.pdf PDF
36C24724Q0269 0001.pdf PDF
03 Series LIFE SAFETY - 100 AT-130 Fort McPherson Residental Treatment.pdf PDF
03 Series LIFE SAFETY - 100 AT-131 Fort McPherson Domiciliary Care.pdf PDF
03 Series LIFE SAFETY - 100 AT-125 Fort McPherson OPC.pdf PDF
FIRE ALARM 125.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-125_Annual Report.pdf PDF
04 Series DOORS - 100 AT-130 Fort McPherson Residental Treatment.pdf PDF
04 Series DOORS - 100 AT-125 Fort McPherson OPC.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-128_SprinklerScan.pdf PDF
05 series dampers - 100 at-125 fort mcpherson opc.pdf PDF
FIRE SUPPRESSION 131.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-130_Annual Report.pdf PDF
03 Series LIFE SAFETY - 100 AT-128 Fort McPherson Homeless Program.pdf PDF
04 Series DOORS - 100 AT-128 Fort McPherson Homeless Program.pdf PDF
BLDG. 125 FIRE SUPPRESSION.pdf PDF
04 Series DOORS - 100 AT-131 Fort McPherson Domiciliary Care.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-129_SprinklerScan.pdf PDF
36C24724Q0269.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sprinkler Inspection Certificate For

Fort McPherson VAMC Bldg 128 1701 Hardee Ave SW

Atlanta, GA 30310

Tested to NFPA 25 Standards

This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.

Quarterly Inspection Inspection Date Feb 10, 2023

Building: Fort McPherson VAMC Bldg 128 Company: United Fire Protection - Atlanta Contact: Mike McGill Contact: Wayne Huxtable

Title: Maintenance & Operations Supervisor Title: Technician

Page of 1 10United Fire Protection - Atlanta Download Date: 03/22/2023

Executive Summary Generated by: BuildingReports.com

Building Information Building: Fort McPherson VAMC Bldg 128 Contact: Mike McGill Address: 1701 Hardee Ave SW Phone: 14043216111 Address: Fax:

City/State/ZIP Code: Atlanta, GA 30310 Mobile:

Country: United States of America Email:

Inspection Performed By Company: United Fire Protection - Atlanta Inspector: Wayne Huxtable Address: 2150 Boggs Rd Bldg 100 Phone: 770-771-0999 Address: Suite 140 Fax:

City/State/ZIP Code: Duluth, GA 30096 Mobile:

Country: United States of America Email: whuxtable@united-fire.com

System Control Unit System Type System Location Protected Area Devices Wet Pipe 39

Inspection Summary

Category:

Total Items Serviced Passed Failed/Other

Qty % Qty % Qty % Qty % Alarm 12 30.77% 12 100.00% 12 100.00% 0 0.00%

Device 8 20.51% 4 50.00% 4 100.00% 0 0.00%

Hose 1 2.56% 0 0.00% 0 0.00% 0 0.00%

Valve 18 46.15% 13 72.22% 13 100.00% 0 0.00%

Totals 39 100% 29 74.36% 29 100.00% 0 0.00%

Certification

Company: United Fire Protection - Atlanta Building: Fort McPherson VAMC Bldg 128

Inspector: Wayne Huxtable Contact: Mike McGill

Page of 2 10United Fire Protection - Atlanta Download Date: 03/22/2023

Inspection & Testing Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 128 The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or

. Items are listed by Category. Each item includes the services performed, and the time & date at which testing Failed/Other occurred.

Device Type Location Service Time Date

Passed Wet Pipe

Tamper Switch 1st Riser Room Backflow CV #1 Quarterly 1:03:08 PM 02/09/2023

Tamper Switch 1st Riser Room Backflow CV #2 Quarterly 1:03:17 PM 02/09/2023

Tamper Switch Ground outside building B Quarterly 2:08:05 PM 02/10/2023

Waterflow Switch 1st Buld 128 Riser Room System Pressure Main Feed

Quarterly 1:02:43 PM 02/09/2023

Waterflow Switch 1st building 129 Riser Room Main Feed for 1st, 2nd & Attic

Quarterly 1:02:53 PM 02/09/2023

Waterflow Switch 1st Riser Room Main Feed Quarterly 1:03:58 PM 02/09/2023

Waterflow Switch 1st Riser Room Flowswitch 1st Fl Quarterly 1:04:21 PM 02/09/2023

Waterflow Switch 1st 1st Bld 128 Riser Room Main Feed Quarterly 1:05:43 PM 02/09/2023

Waterflow Switch 2nd Stairwell 1 Check 2nd Fl Quarterly 1:00:54 PM 02/09/2023

Waterflow Switch 2nd Stairwell 1 Attic Quarterly 1:01:04 PM 02/09/2023

Waterflow Switch 2nd Stairwell 1 Flowswitch Attic Quarterly 1:01:30 PM 02/09/2023

Waterflow Switch 2nd Stairwell 1 Flowswitch 2nd Fl Quarterly 1:02:22 PM 02/09/2023

Drain 1st Riser Room Main Feed Drain Quarterly 1:06:05 PM 02/09/2023

Gauge 1st Riser Room System Pressure 1st Fl Quarterly 1:03:32 PM 02/09/2023

Gauge 1st Buld 129 Riser Room Supply Pressure Main Feed

Quarterly 1:03:39 PM 02/09/2023

Gauge 1st Buld 129 Riser Room Supply Pressure Main Feed

Quarterly 1:03:52 PM 02/09/2023

Check Valve 1st Buid 128 Riser Room Riser Check Main Feed

Annual 9:32:27 AM 02/09/2023

Control Valve 1st building 129 Riser Room Main Feed for 1st, 2nd & Attic

Quarterly 1:04:04 PM 02/09/2023

Control Valve 1st Riser Room Isolation CV 1st Fl Quarterly 1:04:34 PM 02/09/2023

Control Valve 1st Riser Room Backflow CV #1 Quarterly 1:04:45 PM 02/09/2023

Control Valve 1st Riser Room Backflow CV #2 Quarterly 1:05:20 PM 02/09/2023

Control Valve 1st Riser Room Test Header CV Quarterly 1:05:28 PM 02/09/2023

Control Valve 1st Riser Room Main Feed for 1st, 2nd & Attic

Quarterly 1:05:55 PM 02/09/2023

Control Valve 2nd Stairwell 1 Attic Quarterly 1:01:42 PM 02/09/2023 javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977806');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977804');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','57780010');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977808');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977807');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133480');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133461');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133454');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977805');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977803');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133473');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133468');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133455');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','57780018');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','57780007');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','57780006');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133451');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133476');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133460');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133459');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133458');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133457');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133450');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133471');

Page of 3 10United Fire Protection - Atlanta Download Date: 03/22/2023

Device Type Location Service Time Date

Control Valve 2nd Stairwell 1 Quarterly 1:02:33 PM 02/09/2023

Inspector's Test 1st Riser Room 1st Fl Quarterly 4:36:23 PM 02/09/2023

Inspector's Test 2nd Stairwell 1 Attic Quarterly 1:01:22 PM 02/09/2023

Inspector's Test 2nd Stairwell 1 Quarterly 1:02:14 PM 02/09/2023

Post Indicator Valve Ground outside building B Quarterly 2:15:05 PM 02/10/2023

Untested Wet Pipe

Gauge 1st Buld 128 Riser Room System Pressure Main Feed

Gauge 1st Buld 128 Riser Room Supply Pressure Main Feed

Gauge 2nd Stairwell 1 System Pressure 2nd Fl

Gauge 2nd Stairwell 1 System Pressure Attic

Fire Dep't Connection

1st Riser Room

Check Valve 1st Riser Room Check 1st Fl

Check Valve 1st Riser Room FDC Check

Check Valve 1st Buid 128 Riser Room Riser Check Main Feed

Check Valve 2nd Stairwell 1 Check 2nd Fl

Check Valve 2nd Stairwell 1 Check Attic javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133466');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133456');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133475');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133470');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','57780011');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','57780019');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','57780020');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977856');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977857');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133464');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133464');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133463');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133465');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133477');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133467');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133472');

Page of 4 10United Fire Protection - Atlanta Download Date: 03/22/2023

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Location Number of Turns

Zone /Address

OK ScanID

OS&Y Supervisory 1st Riser Room Backflow CV #1 1-M1-109 67977806 Control Valve Supervisory 1st Riser Room Backflow CV #2 1-M1-108 67977804 Control Valve Supervisory Ground outside building B 1 57780010

Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Control Valve Potter Electric VSR 4 1 67977808 Vane Potter electric VSR 4” 1-M1-107 67977807 Vane Potter Electric VSR 4" 1-M1-105 44133480 Vane Potter Electric VSR 4" 1-M1-46 44133461 Vane Potter Electric VSR 4" 1-M1-105 44133454 Vane Potter electric VSR 4 1 67977805 Vane Potter Electric VSR 4 1-M1-104 67977803 Vane Potter Electric VSR 4" 1-M1-103 44133473 Vane Potter Electric VSR 4" 1-M1-101 44133468

Components Check Valve

Type Location Internal Date Size OK ScanID

Grooved 1st Buid 128 Riser Room Riser Check Main Feed

03/28/2018 4" 44133451

Grooved 1st Riser Room Check 1st Fl 03/28/2018 4" 44133463 Grooved 1st Riser Room FDC Check 03/28/2018 4" 44133465

Grooved 1st Buid 128 Riser Room Riser Check Main Feed

03/28/2018 4" 44133477

Grooved 2nd Stairwell 1 Check 2nd Fl 03/28/2018 4" 44133467 Grooved 2nd Stairwell 1 Check Attic 03/28/2018 4" 44133472

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977806');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977804');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','57780010');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977808');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977807');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133480');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133461');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133454');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977805');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977803');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133473');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133468');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133451');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133463');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133465');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133477');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133467');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133472');

Page of 5 10United Fire Protection - Atlanta Download Date: 03/22/2023

Butterfly Anvil AN7722-3A

1st building 129 Riser Room Main Feed for 1st, 2nd & Attic

4" Open Supervised 44133476

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Anvil AN7722-3A 1st Riser Room Isolation CV 1st Fl

4" Open Supervised 44133460

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Kennedy KS-RW 1st Riser Room Backflow CV #1

4" Open Supervised 44133459

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Kennedy KS-RW 1st Riser Room Backflow CV #2

4" Open Supervised 44133458

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Kennedy KS-RW 1st Riser Room Test Header

CV

4" Open Supervised 44133457

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Anvil AN7722-3A 1st Riser Room Main Feed for 1st, 2nd & Attic

4" Open Supervised 44133450

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133476');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133460');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133459');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133458');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133457');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133450');

Page of 6 10United Fire Protection - Atlanta Download Date: 03/22/2023

Butterfly Anvil AN7722-3A 2nd Stairwell 1 Attic

4" Open Supervised 44133471

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Anvil AN7722-3A 2nd Stairwell 1 4" Open Supervised 44133466

Description Main Control

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1313 65 42 44133456

Location 1st Riser Room 1st Fl

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1313 65 28 44133475

Location 2nd Stairwell 1 Attic

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1313 65 49 44133470

Location 2nd Stairwell 1

Post Indicator Valve Manufacturer Model Location OK ScanID Mueller AN7722-3A Ground outside building B 57780011

Type Size Position Status Number of Turns Ground 8" Locked

Devices Drain

Current Inspection

Type Location Size Supply psi Restored psi

Residual psi Sec OK ScanID

Main 1st Riser Room Main Feed Drain

2" 60 60 45 44133455

Previous Inspections

October 28, 2022

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID

Main 1st Riser Room Main Feed Drain

2" 60 60 45 44133455

May 28, 2021 javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133471');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133466');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133456');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133475');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133470');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','57780011');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133455');

javascript:openEditDevice('load-edit-p2-device','0','2686311','44133455');

Page of 7 10United Fire Protection - Atlanta Download Date: 03/22/2023

Type Location Size Supply psi Static psi Residual psi Sec OK ScanID

Main 1st Riser Room Main Feed Drain

2" 60 60 45 44133455

Fire Dep't Connection Location Type BallDrip Rotating Swivels Size OK ScanID

1st Riser Room Wall Yes Yes 4" 44133464

Gauge Location Service Date 1st Riser Room System Pressure 1st Fl 03/28/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Wika Wika 65 1/4 57780018

Gauge Location Service Date 1st Buld 129 Riser Room Supply Pressure Main Feed 03/28/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Wika Wika 65 1/4 57780007

Gauge Location Service Date 1st Buld 129 Riser Room Supply Pressure Main Feed 03/28/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Wika Wika 65 1/4 57780006

Gauge Location Service Date 1st Buld 128 Riser Room System Pressure Main Feed 03/28/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika Wika 65 1/4 57780019

Gauge Location Service Date 1st Buld 128 Riser Room Supply Pressure Main Feed 03/28/2018

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Wika Wika 65 1/4 57780020

Gauge Location Service Date 2nd Stairwell 1 System Pressure 2nd Fl 03/28/2013

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika Wika 65 1/4 67977856

Gauge Location Service Date 2nd Stairwell 1 System Pressure Attic 03/28/2013

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 65 1/4 67977857 javascript:openEditDevice('load-edit-p2-device','0','2166889','44133455');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133464');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','57780018');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','57780007');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','57780006');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','57780019');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','57780020');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977856');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977857');

Page of 8 10United Fire Protection - Atlanta Download Date: 03/22/2023

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 128 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Check Valve Valve 15.38% 6

Control Valve Valve 20.51% 8

Drain Device 2.56% 1

Fire Dep't Connection Hose 2.56% 1

Gauge Device 17.95% 7

Inspector's Test Valve 7.69% 3

Post Indicator Valve Valve 2.56% 1

Tamper Switch Alarm 7.69% 3

Waterflow Switch Alarm 23.08% 9

Device Type Qty Model # Type Description Install Date

In Service - 3 Years to 5 Years Wet Pipe

Gauge 4 Wika Supply Pressure 07/11/2018 Gauge 1 Wika System Pressure 07/11/2018 Inspector's Test 3 1313 03/28/2018 Check Valve 4 78FP Grooved 03/28/2018 Control Valve 1 AN7722-3A Butterfly Isolation 03/28/2018 Control Valve 4 AN7722-3A Butterfly Main Control 03/28/2018 Waterflow Switch 1 VSR Control Valve Supervisory 03/28/2018 Waterflow Switch 6 VSR Vane Alarm 03/28/2018 Waterflow Switch 2 VSR Vane Alarm 03/28/2018 Check Valve 2 DN 100 EZR CK

VLV

Grooved 03/28/2018

Drain 1 FBV-3C Main 03/28/2018 Gauge 1 Wika System Pressure 03/28/2018

In Service - 5 Years to 10 Years Wet Pipe

Fire Dep't Connection 1 A101 Wall 03/28/2013 Control Valve 1 KS-RW OS&Y Isolation 03/28/2013 Control Valve 2 KS-RW OS&Y Main Control 03/28/2013 Gauge 1 System Pressure 03/28/2013 Tamper Switch 1 VSR Control Valve Supervisory 03/28/2013 Tamper Switch 1 KS-RW OS&Y Supervisory 03/28/2013

In Service - 10 Years to 15 Years

Page of 9 10United Fire Protection - Atlanta Download Date: 03/22/2023

Wet Pipe Post Indicator Valve 1 AN7722-3A Ground 03/28/2012 Tamper Switch 1 Control Valve Supervisory 03/28/2012

Page of 10 10United Fire Protection - Atlanta Download Date: 03/22/2023

Zone Address Report Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 128 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID

Control Panel 1 M1-46 Waterflow Switch 1st Riser Room Flowswitch 1st Fl Vane 44133461 M1-47 Control Valve 1st Riser Room Isolation CV 1st Fl Butterfly 44133460

M1-101 Waterflow Switch 2nd Stairwell 1 Flowswitch 2nd Fl Vane 44133468 M1-102 Control Valve 2nd Stairwell 1 Butterfly 44133466 M1-103 Waterflow Switch 2nd Stairwell 1 Flowswitch Attic Vane 44133473 M1-104 Control Valve 2nd Stairwell 1 Attic Butterfly 44133471 M1-104 Waterflow Switch 2nd Stairwell 1 Attic Vane 67977803 M1-105 Waterflow Switch 1st Riser Room Main Feed Vane 44133480 M1-105 Waterflow Switch 1st 1st Bld 128 Riser Room Main Feed Vane 44133454 M1-106 Control Valve 1st Riser Room Test Header CV OS&Y 44133457 M1-107 Control Valve 1st Riser Room Main Feed for 1st, 2nd &

Attic Butterfly 44133450

M1-107 Control Valve 1st building 129 Riser Room Main Feed for 1st, 2nd & Attic

Butterfly 44133476

M1-107 Waterflow Switch 1st building 129 Riser Room Main Feed for 1st, 2nd & Attic

Vane 67977807

M1-108 Control Valve 1st Riser Room Backflow CV #2 OS&Y 44133458 M1-108 Tamper Switch 1st Riser Room Backflow CV #2 Control Valve 67977804 M1-109 Control Valve 1st Riser Room Backflow CV #1 OS&Y 44133459 M1-109 Tamper Switch 1st Riser Room Backflow CV #1 OS&Y 67977806 javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133461');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133460');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133468');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133466');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133473');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133471');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977803');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133480');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133454');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133457');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133450');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133476');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977807');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133458');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977804');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','44133459');

javascript:openEditDevice('load-edit-p2-device','736898','2792912','67977806');

Sprinkler Inspection Certificate
Executive Summary
Inspection & Testing
Wet Pipe Fire Sprinkler Systems
Inventory & Warranty Report
Zone Address Report

File details come from the government source that posted it. Updated .