This document is a fire and life safety system inspection report for Building 129 at the Fort McPherson VA Medical Center in Atlanta, Georgia. The inspection was conducted by Vets Fire & Life Safety and certifies that inspection, testing and maintenance of the fire sprinkler system was performed in compliance with Joint Commission and VHA standards. Key details include that the inspection covered testing of duct detectors, heat detectors, pull stations, smoke detectors and notification appliances to ensure proper operation, as well as testing of batteries, control panels, power supplies and auxiliary functions such as elevator recall and air handler shutdown. All devices passed testing and the system was found to be in proper working order.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
For
Fort McPherson VAMC Bldg 129 1701 Hardee Ave SW
Atlanta, GA 30310
Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards effective January 31, 2021
Inspection Completion Date Jun 20, 2022
Building: Fort McPherson VAMC Bldg 129 Company: Vets Fire & Life Safety Contact: Mike McGill Contact: Mike Gill
Title: Maintenance & Operations Supervisor Title: Inspector
Page of 1 19 Executive Summary
Vets Fire & Life Safety Download Date: 06/20/2022
Executive Summary Generated by: BuildingReports.com
Building Information Building: Fort McPherson VAMC Bldg 129 Contact: Mike McGill
Address: 1701 Hardee Ave SW Phone: 4043216111
Address: Fax:
City/State/Zip: Atlanta, GA 30310 Mobile:
Country: United States of America Email:
Inspection Performed By Company: Vets Fire & Life Safety Inspector: Mike Gill
Address: 7 Sherri Ln Phone: 636-543-0165
Address: Fax:
City/State/Zip: Saint Peters, MO 63376-2142 Mobile:
Country: United States of America Email: mike.gill@vflsc.com
System Control Unit Manufacturer: Inspection Date: 06/20/2022 IDC Style:
Model Number: Install Date: 05/09/2018 SLC Style:
Software Version: Version Date: 06/20/2022 NAC Style:
Location: 1st Room 1C148 Current Protection: Breaker
Page of 2 19
Vets Fire & Life Safety Download Date: 06/20/2022
Inspection Completion Date: Jun 20, 2022 Building: Fort McPherson VAMC Bldg 129 EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
Devices Tested This
Quarter Pass Fail Tested YTD
(2022) Untested YTD
(2022) Total
Quantity Duct Detector 4 4 0 4 0 4
Heat Detector 3 3 0 3 0 3
Pull Station 6 6 0 6 0 6
Smoke Detector 13 13 0 13 0 13
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2019) Table 14.4.3.2 (22)
Devices Tested This
Quarter Pass Fail Tested YTD
(2022) Untested YTD
(2022) Total
Quantity Speaker/Strobe 20 20 0 20 0 20
Strobe 23 23 0 23 0 23
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment.
NFPA 90A (2021) 6.4.1
Devices Tested This
Quarter Pass Fail Tested YTD
(2022) Untested YTD
(2022) Total
Quantity Duct Detector 4 4 0 4 0 4
LS 02.01.34 EP 02 Protected master fire alarm control panel
Devices Tested This
Quarter Pass Fail Tested YTD
(2022) Untested YTD
(2022) Total
Quantity Control Panel 1 1 0 1 0 1
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Devices Tested This
Quarter Pass Fail Tested YTD
(2022) Untested YTD
(2022) Total
Quantity Battery 6 6 0 6 0 6
Power Supply 2 2 0 2 0 2
Total Device Count: 78
Page of 3 19
Vets Fire & Life Safety Download Date: 06/20/2022
Certification
Company: Vets Fire & Life Safety Building: Fort McPherson VAMC Bldg 129
Inspector: Mike Gill Contact: Mike McGill
Page of 4 19 Notes & Recommendations
Vets Fire & Life Safety Download Date: 06/20/2022
Notes & Recommendations Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Control Panel: 1 -
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
1 Duct Detector 1st Mech Room 104 Return Passed 46938283 Shuts Down Unit
2 Duct Detector 1st Mech Room 104 Supply Passed 46938284 Shuts Down Unit
3 Smoke Detector 1st Elevator Equipment Room 149 Passed 46938290 Recalls To Primary Floor
4 Smoke Detector 1st Elevator Lobby Passed 46938291 Recalls To Primary Floor
5 Duct Detector 2nd Mech Room 204 Return Passed 46938285 Shuts Down Unit
6 Duct Detector 2nd Mech Room 204 Supply Passed 46938286 Shuts Down Unit
7 Smoke Detector 2nd Elevator Lobby Passed 46938295 Recalls To Primary Floor
8 Smoke Detector 2nd Elevator Top Of Shaft Passed 46938296 Recalls To Primary Floor javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938283');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938284');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938290');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938291');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938285');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938286');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938295');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938296');
Page of 5 19 Inspection & Testing
Vets Fire & Life Safety Download Date: 06/20/2022
Inspection & Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 129 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Duct Detector 4 4 0 4 4
Device Type Location ScanID Address Q2/22 Duct Detector 1st Mech Room 104 Return 46938283 1-M1-23 06/20-P Duct Detector 1st Mech Room 104 Supply 46938284 1-M1-24 06/20-P Duct Detector 2nd Mech Room 204 Return 46938285 1-M1-52 06/20-P Duct Detector 2nd Mech Room 204 Supply 46938286 1-M1-53 06/20-P
Device Total: 4 Return to Executive Summary
Page of 6 19
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically.
(NFPA 72-19 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Heat Detector 3 3 0 3 3
Device Type Location ScanID Address Q2/22 Heat Detector 1st Elevator Equipment Room 149 46938272 1-M1-26 06/20-P Heat Detector 1st Elevator Pit 46938271 1-M1-15 06/20-P Heat Detector 2nd Elevator Top Of Shaft 46938273 1-M1-46 06/20-P
Device Total: 3 Return to Executive Summary
Page of 7 19
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-19 Table 14.4.3.2 (17)(5)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Pull Station 6 6 0 6 6
Device Type Location ScanID Address Q2/22 Pull Station 1st Stair 1 Exit 46938276 1-M1-25 06/20-P Pull Station 1st Stair 2 Exit 46938274 1-M1-5 06/20-P Pull Station 1st Stair 3 Exit 46938275 1-M1-17 06/20-P Pull Station 2nd Stair 1 Exit 46938279 1-M1-54 06/20-P Pull Station 2nd Stair 2 Exit 46938277 1-M1-43 06/20-P Pull Station 2nd Stair 3 Exit 46938278 1-M1-48 06/20-P
Device Total: 6 Return to Executive Summary
Page of 8 19
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Smoke Detector 13 13 0 13 13
Device Type Location ScanID Address Q2/22 Smoke Detector 1st East Wing @ Mag Doors 46938288 1-M1-57 06/20-P Smoke Detector 1st East Wing @ Mag Doors 46938287 1-M1-56 06/20-P Smoke Detector 1st Connector Corr @ Mag Doors 46938293 1-M1-20 06/20-P Smoke Detector 1st Connector Corr @ Mag Doors 46938294 1-M1-22 06/20-P Smoke Detector 1st Comm Room 145 46938292 1-M1-16 06/20-P Smoke Detector 1st Electric Room 148 46938289 1-M1-1 06/20-P Smoke Detector 1st Elevator Lobby 46938291 1-M1-15 06/20-P Smoke Detector 1st Elevator Equipment Room 149 46938290 1-M1-8 06/20-P Smoke Detector 2nd Connector Corr @ Mag Doors 46938299 1-M1-51 06/20-P Smoke Detector 2nd Connector Corr @ Mag Doors 46938298 1-M1-49 06/20-P Smoke Detector 2nd Comm Room 245 46938297 1-M1-47 06/20-P Smoke Detector 2nd Elevator Top Of Shaft 46938296 1-M1-45 06/20-P Smoke Detector 2nd Elevator Lobby 46938295 1-M1-44 06/20-P
Device Total: 13 Return to Executive Summary
Page of 9 19
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2019) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-19 Table 14.4.3.2 (22)(2)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Speaker/Strobe 20 20 0 20 20
Device Type Location ScanID Address Q2/22 Speaker/Strobe 1st Corr @ Stair 1 46938323 1 06/20-P Speaker/Strobe 1st Corr @ 1C113 46938324 1 06/20-P Speaker/Strobe 1st Corr @ 1C103 46938325 1 06/20-P Speaker/Strobe 1st Mech Room 1C104 46938326 1 06/20-P Speaker/Strobe 1st Corr @ Mech Room 1C104 46938327 1 06/20-P Speaker/Strobe 1st Corr @ 1C157 46938329 1 06/20-P Speaker/Strobe 1st Corr @ 1C150 46938328 1 06/20-P Speaker/Strobe 1st Corr @ 1C160 46938330 1 06/20-P Speaker/Strobe 1st Corr @ Stair 3 46938331 1 06/20-P Speaker/Strobe 1st Corr @ 1C129 46938332 1 06/20-P Speaker/Strobe 2nd Corr @ Stair 1 46938342 1 06/20-P Speaker/Strobe 2nd Corr @ Lounge Area 46938341 1 06/20-P Speaker/Strobe 2nd Corr @ 2C213 46938340 1 06/20-P Speaker/Strobe 2nd Mech Room 2C204 46938339 1 06/20-P Speaker/Strobe 2nd Corr @ 2C203 46938338 1 06/20-P Speaker/Strobe 2nd Corr @ Bridge To Bldg B 46938337 1 06/20-P Speaker/Strobe 2nd Corr @ Stair 2 46938335 1 06/20-P Speaker/Strobe 2nd Corr @ Conference Room 2C255 46938336 1 06/20-P Speaker/Strobe 2nd Corr @ Conference Room 2C252 46938334 1 06/20-P Speaker/Strobe 2nd Corr @ Stair 3 46938333 1 06/20-P
Device Total: 20 Return to Executive Summary
Page of 10 19
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2019) Table 14.4.3.2 (22)
For periodic testing, verify that each appliance flashes. (NFPA 72-19 Table 14.4.3.2 (22)(3)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Strobe 23 23 0 23 23
Device Type Location ScanID Address Q2/22 Strobe 1st Patient Lounge 1C127 46938300 1 06/20-P Strobe 1st Patient Lounge 1C127 46938301 1 06/20-P Strobe 1st Group Room 1C119 46938302 1 06/20-P Strobe 1st Corr @ Group Room 1C119 46938303 1 06/20-P Strobe 1st Men's Restroom 1C108 46938304 1 06/20-P Strobe 1st Waiting Room 1C105 46938306 1 06/20-P Strobe 1st Patient Computer Room 1C151 46938311 1 06/20-P Strobe 1st Conference Room 1C161 46938313 1 06/20-P Strobe 1st Copy Room 1C157 46938312 1 06/20-P Strobe 1st Telephone Room 1C145 46938307 1 06/20-P Strobe 1st Men's Restroom 1C152 46938310 1 06/20-P Strobe 1st Women's Restroom 1C150 46938309 1 06/20-P Strobe 1st Elevator Mech Room 1C149 46938308 1 06/20-P Strobe 1st Women's Restroom 1C106 46938305 1 06/20-P Strobe 2nd Staff Room 2C208 46938322 1 06/20-P Strobe 2nd Staff Room 2C206 46938321 1 06/20-P Strobe 2nd Telephone Room 2C245 46938320 1 06/20-P Strobe 2nd Women's Restroom 2C250 46938319 1 06/20-P Strobe 2nd Conference Room 2C255 46938316 1 06/20-P Strobe 2nd Mens Restroom 2C252 46938318 1 06/20-P Strobe 2nd Copy Room 2C257 46938317 1 06/20-P Strobe 2nd Staff Lounge 2C261 46938315 1 06/20-P Strobe 2nd Staff Lounge 2C261 46938314 1 06/20-P
Device Total: 23 Return to Executive Summary
Page of 11 19
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment.
NFPA 90A (2021) 6.4.1
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Duct Detector 4 4 0 4 4
Device Type Location ScanID Address Q2/22 Duct Detector 1st Mech Room 104 Return 46938283 1-M1-23 06/20-P Duct Detector 1st Mech Room 104 Supply 46938284 1-M1-24 06/20-P Duct Detector 2nd Mech Room 204 Return 46938285 1-M1-52 06/20-P Duct Detector 2nd Mech Room 204 Supply 46938286 1-M1-53 06/20-P
Device Total: 4 Return to Executive Summary
Page of 12 19
Vets Fire & Life Safety Download Date: 06/20/2022
LS 02.01.34 EP 02 Protected master fire alarm control panel
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-19 Table
14.4.3.2 (2)(1)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Control Panel 1 1 0 1 1
Device Type Location ScanID Address Q2/22 Control Panel 1st Room 1C148 46938280 1 06/20-P
Device Total: 1 Return to Executive Summary
Page of 13 19
Vets Fire & Life Safety Download Date: 06/20/2022
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-19 Table 14.4.3.2 (9)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Battery 6 6 0 6 6
Device Type Location ScanID Address Q2/22 Battery 1st Room 1C148 46938924 1 06/20-P Battery 1st Room 1C148 46938923 1 06/20-P Battery 1st Room 1C148 Main FACP 46938922 1 06/20-P Battery 1st Room 1C148 Main FACP 46938921 1 06/20-P Battery 2nd Room 2C248 46938926 1 06/20-P Battery 2nd Room 2C248 46938925 1 06/20-P
Device Total: 6 Return to Executive Summary
Page of 14 19
Vets Fire & Life Safety Download Date: 06/20/2022
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-19 Table
14.4.3.2 (2)(1)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Power Supply 2 2 0 2 2
Device Type Location ScanID Address Q2/22 Power Supply 1st Room 1C148 46938281 1 06/20-P Power Supply 2nd Room 2C248 46938282 1 06/20-P
Device Total: 2 Return to Executive Summary
Page of 15 19 Service Summary
Vets Fire & Life Safety Download Date: 06/20/2022
Service Summary Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 129 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Passed Battery Tested 6 Control Panel Tested 1 Duct Detector Tested 4 Heat Detector Tested 3 Power Supply Tested 2 Pull Station Tested 6 Smoke Detector Tested/Cleaned 13 Speaker/Strobe Tested 20 Strobe Tested 23
Total 78 Grand Total 78
Page of 16 19 Auxiliary Functions Testing
Vets Fire & Life Safety Download Date: 06/20/2022
Auxiliary Functions Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Control Panel: 1 -
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed Duct Detector
AHU Shutdown 1st Mech Room 104 Return Passed 46938283 AHU Shutdown 1st Mech Room 104 Supply Passed 46938284 AHU Shutdown 2nd Mech Room 204 Return Passed 46938285 AHU Shutdown 2nd Mech Room 204 Supply Passed 46938286
Smoke Detector Elevator Recall 1st Elevator Equipment Room 149 Passed 46938290 Elevator Recall 1st Elevator Lobby Passed 46938291 Elevator Recall 2nd Elevator Lobby Passed 46938295 Elevator Recall 2nd Elevator Top Of Shaft Passed 46938296
Heat Detector Shunt Trip 1st Elevator Equipment Room 149 Passed 46938272 Shunt Trip 1st Elevator Pit Passed 46938271 Shunt Trip 2nd Elevator Top Of Shaft Passed 46938273 javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938283');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938284');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938285');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938286');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938290');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938291');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938295');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938296');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938272');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938271');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938273');
Page of 17 19 Battery & Power Supply Testing
Vets Fire & Life Safety Download Date: 06/20/2022
Battery & Power Supply Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Control Panel: 1 -
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location Rated Ah
Rated Volts Pre Test
Post Test Min Ah Tested Ah
Battery
Passed Sealed Lead Acid 1st Room 1C148 7 12 12.46 7 Sealed Lead Acid 1st Room 1C148 7 12 12.56 6.4 Sealed Lead Acid 1st Room 1C148 Main FACP 55 12 13.24 50 Sealed Lead Acid 1st Room 1C148 Main FACP 55 12 13.25 52 Sealed Lead Acid 2nd Room 2C248 7 12 12.56 7 Sealed Lead Acid 2nd Room 2C248 12 12.71 6.8
Page of 18 19 Inventory & Warranty Report
Vets Fire & Life Safety Download Date: 06/20/2022
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Control Panel: 1 -
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Battery Control 7.69% 6
Control Panel Control 1.28% 1
Duct Detector Initiating 5.13% 4
Heat Detector Initiating 3.85% 3
Power Supply Control 2.56% 2
Pull Station Initiating 7.69% 6
Smoke Detector Initiating 16.67% 13
Speaker/Strobe Indicating 25.64% 20
Strobe Indicating 29.49% 23
Type Qty Model # Description Install Date
In Service - 3 Years to 5 Years Battery 6 Sealed Lead Acid 05/09/2018 Control Panel 1 05/09/2018 Duct Detector 4 05/09/2018 Heat Detector 3 05/09/2018 Power Supply 2 05/09/2018 Pull Station 6 05/09/2018 Smoke Detector 13 05/09/2018 Speaker/Strobe 20 05/09/2018 Strobe 23 05/09/2018
Page of 19 19 Zone Address Report
Vets Fire & Life Safety Download Date: 06/20/2022
Zone Address Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Control Panel: 1 -
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID M1-1 Smoke Detector 1st Electric Room 148 46938289 M1-5 Pull Station 1st Stair 2 Exit 46938274 M1-8 Smoke Detector 1st Elevator Equipment Room 149 46938290 M1-15 Smoke Detector 1st Elevator Lobby 46938291 M1-15 Heat Detector 1st Elevator Pit 46938271 M1-16 Smoke Detector 1st Comm Room 145 46938292 M1-17 Pull Station 1st Stair 3 Exit 46938275 M1-20 Smoke Detector 1st Connector Corr @ Mag Doors 46938293 M1-22 Smoke Detector 1st Connector Corr @ Mag Doors 46938294 M1-23 Duct Detector 1st Mech Room 104 Return 46938283 M1-24 Duct Detector 1st Mech Room 104 Supply 46938284 M1-25 Pull Station 1st Stair 1 Exit 46938276 M1-26 Heat Detector 1st Elevator Equipment Room 149 46938272 M1-43 Pull Station 2nd Stair 2 Exit 46938277 M1-44 Smoke Detector 2nd Elevator Lobby 46938295 M1-45 Smoke Detector 2nd Elevator Top Of Shaft 46938296 M1-46 Heat Detector 2nd Elevator Top Of Shaft 46938273 M1-47 Smoke Detector 2nd Comm Room 245 46938297 M1-48 Pull Station 2nd Stair 3 Exit 46938278 M1-49 Smoke Detector 2nd Connector Corr @ Mag Doors 46938298 M1-51 Smoke Detector 2nd Connector Corr @ Mag Doors 46938299 M1-52 Duct Detector 2nd Mech Room 204 Return 46938285 M1-53 Duct Detector 2nd Mech Room 204 Supply 46938286 M1-54 Pull Station 2nd Stair 1 Exit 46938279 M1-56 Smoke Detector 1st East Wing @ Mag Doors 46938287 M1-57 Smoke Detector 1st East Wing @ Mag Doors 46938288 javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938289');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938274');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938290');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938291');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938271');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938292');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938275');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938293');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938294');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938283');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938284');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938276');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938272');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938277');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938295');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938296');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938273');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938297');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938278');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938298');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938299');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938285');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938286');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938279');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938287');
javascript:openEditDevice('load-edit-f2-device','1267468','3050000','46938288');
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate