Fire Sprinkler Testing
Solicitation number
36C24724Q0269
Issued by

About this file

This document package includes drawings and specifications for a fire sprinkler testing project at a Department of Veterans Affairs medical center. The scope of work involves inspecting and testing existing fire sprinklers, standpipes, and combination sprinkler/standpipe systems throughout various buildings on the VA campus to ensure compliance with NFPA 13 and 14. Key areas covered include patient care, office, and support facilities. Submittals are due within 30 days of award with work to be completed by December 2022. Pricing shall be on a time and materials basis not to exceed $250,000. The incumbent contractor for fire protection work at this VA location is eligible to bid.

View the file

Other files

File Type Posted
FIRE ALARM 130.pdf PDF
2022-06-20_Fort-McPherson-VAMC-Bldg-128_Annual Report.pdf PDF
BLDG 131 ASBUILTS.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-131_Annual Report.pdf PDF
FIRE SUPPRESSION.pdf PDF
2022-06-20_Fort-McPherson-VAMC-Bldg-129_Annual Report.pdf PDF
BLDG 125 ASBUILT.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-125_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-128_SprinklerScan.pdf PDF
Ft. McPherson Bldg 128 Fire Alarm Drawings - RECORD Dwg.pdf PDF
Bldg 128 As-Builts.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
FIRE ALARM 129.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-125_SprinklerScan.pdf PDF
BLDG 129 ASBUILT.pdf PDF
2023-02-10_Fort-McPherson-VAMC-Bldg-128_SprinklerScan (1).pdf PDF
36C24724Q0269 0001.pdf PDF
03 Series LIFE SAFETY - 100 AT-130 Fort McPherson Residental Treatment.pdf PDF
03 Series LIFE SAFETY - 100 AT-131 Fort McPherson Domiciliary Care.pdf PDF
03 Series LIFE SAFETY - 100 AT-125 Fort McPherson OPC.pdf PDF
FIRE ALARM 125.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-125_Annual Report.pdf PDF
04 Series DOORS - 100 AT-125 Fort McPherson OPC.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-128_SprinklerScan.pdf PDF
05 series dampers - 100 at-125 fort mcpherson opc.pdf PDF
FIRE SUPPRESSION 131.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-130_Annual Report.pdf PDF
03 Series LIFE SAFETY - 100 AT-128 Fort McPherson Homeless Program.pdf PDF
04 Series DOORS - 100 AT-128 Fort McPherson Homeless Program.pdf PDF
BLDG. 125 FIRE SUPPRESSION.pdf PDF
04 Series DOORS - 100 AT-131 Fort McPherson Domiciliary Care.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-129_SprinklerScan.pdf PDF
36C24724Q0269.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INDEX OF DRAWINGSVICINITY MAP PROJECT TEAMBUILDING SUMMARYANNOTATION DRAWING SYMBOLS

OWNER

Department of Veterans Affairs Tuscaloosa VA Medical Center 3701 Loop Road East Tuscaloosa AL 35404-5088

PROJECT MANAGER

Romanyk Consulting 3308 Preston Road, Suite 350-164 Plano, TX 75093

Sherri Mitchell, Contracting Officer Sherri.mitchell@va.gov

334-272-4670, ext 2238

Joshua Leow, COR Joshua.leow@va.gov

Elijah Knight, PE, MSEM elijah.knight@romanykconsulting.com

855-424-3838 ext.323 405-640-1586 cell

MECHANICAL ENGINEER

PROJECT ARCHITECT

John Slattery, RA john.slattery@romanykconsulting.com

855-424-3838 ext.336 918-430-6020 cell

Brad Cain, PE brad.cain@romanykconsulting.com

855-424-3838 ext.335 864-908-8304 cell

Romanyk Consulting 3308 Preston Road, Suite 350-164 Plano, TX 75093

Romanyk Consulting 3308 Preston Road, Suite 350-164 Plano, TX 75093

LIFE SAFETY ENGINEER

Frank Van Overmeiren fvanovermeiren@fpc-consultants.com

317-486-5188 ext.13

FP&C Consultants, Inc.

1520 Main Street Indianapolis, IN 46224

ROOM NAME

ROOM NAME / NUMBER

NORTH ARROW

NORTH ARROW WITH TRUE

NORTH INDICATION

Name Elevation

FLOOR LEVEL &

NAME

SHEET KEYNOTE1

XXX-XXXX-XX-XXXXX DOOR TAG

1 SHEET KEYNOTE

XXX-XXX-XX-XXXXX

WALL

PENETRATION TAG

XXX-XXX-XX-DPXXX DAMPER TAG

The A/E team, including architects, engineers, surveyors, and professional consultants shall survey and inspect the following VISN 7 VA Medical Center for Life safety deficiencies according to 2015 NFPA 101 Life Safety Code and Joint Commission Standard LS.01.01.01, EP 2 and provide comprehensive as-built Life Safety Plans (LSP)

SCOPE OF WORK SUMMARY:

• Tuskegee

• Montgomery

Team shall provide a list of discrepancies based off their findings and provide recommended methods for corrections. Team shall also update the facilities current life/fire safety plans to reflect existing as-built conditions based off the survey. Team shall also survey the facility to locate existing fire dampers and provide accurate as-built drawings.

A/E shall assume all areas of the campus are, and must remain fully operational, and that inspections may require coordination with the Owner for after-hours access, accompanied access and protected access (for medically sensitive areas, etc.), and shall include all such work as part of the A/E Scope of Work (SOW).

Life Safety inspection shall include the following. Inspecting all fire walls (including doors, door frames, and hardware) smoke walls, locations of all fire extinguishers, smoke detectors, smoke compartments, and exit signs.

A/E shall reference NFPA 101 and other NFPA applicable codes and provide the follow for each deliverable.

• Columbia

• Atlanta

• Augusta UD

• Augusta DD

• Dublin

• Charleston

LS0101A

LEVEL

DISCIPLINE

SECTION LETTER

WITHIN LEVEL

SERIES

01 SERIES = TJC DRAWINGS

02 SERIES = WALL PENETRATION DEFICIENCY DRAWINGS

03A SERIES = LIFE SAFETY DRAWINGS

03B SERIES = EXIT AND OCCUPANCY DRAWINGS

04 SERIES = FIRE/SMOKE DOOR DRAWINGS

05 SERIES = FIRE/SMOKE DAMPER DRAWINGS

FIRE/SMOKE DOORS - DRAWING LIST

' 6

G ra p h ic S ca le

/2

1'

-0

G ra p h ic S ca le

/3 2"

'-0

' G ra p h ic S ca le

/1 6"

'-0

' G ra p h ic

S ca le

/8

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

/8

1'

-0

' G ra p h ic

S ca le

/2

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

'-0

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

VISN 7 LIFE SAFETY SURVEY AND

DRAWING UPDATE, TASK ORDER

#13

GS-10F-0347P

Elijah Knight, PE

VISN 7 LIFE SAFETY SURVEY AND DRAWING UPDATE

BPA ORDER NO. VA247-14-A-0028 - TASK ORDER #13

EE

ES

S

OF

M

R C

D

T

T T

II

N

U A

A A

V

RAP

M

N

T

T

OF

E E

D

R S

I

FA

A

N T

S R

F

AEE

2017 LIFE SAFETY DOCUMENTATION

FINAL

Contract: GS-10F-0347P Task Order: VA247-17-F-2259

R R o m a n y k C o n s u lt in g \R

C C

A E

C

C o n s u lt in g \0

P ro je c ts

\V

IS

N

\L if e

S a fe ty \0

M o d e l\

A tl a n ta \B u ild in g s S u rv e y e d

\A T

-1

F o rt M c P h e rs o n

R e s id e n ta l T re a tm e n t\ A

T -1

F o rt M c P h e rs o n R e s id e n ta l T re a tm e n t.

rv t

/1 /2

:1

:3

A

M

COVER

E.K. HP

G-04

VISN 7 ATLANTA

07/31/2018

VISN 7

ATLANTA

Building 130 - FT McPHERSON - RESIDENTAL TREATMENT

100% SUBMITTAL

FIRE/SMOKE DOORS

04 - GENERAL

G-04 COVER

G-04X1 GENERAL SHEET

G-04X2 GENERAL SHEET

04 - FIRE/SMOKE DOOR

LS0401 FIRE/SMOKE DOOR INSPECTION FLOOR PLAN - LEVEL 01

LS0402 FIRE/SMOKE DOOR INSPECTION FLOOR PLAN - LEVEL 02

Grand total: 5

Prepared for:

100% Submission for

Fort McPherson VA Clinic Atlanta, GA

Revisions: Date:

l lllllll

OO OO O O ∅ ∅∅ ∅ ∅

' 6

G ra p h ic S ca le

/2

1'

-0

G ra p h ic S ca le

/3 2"

'-0

' G ra p h ic S ca le

/1 6"

'-0

' G ra p h ic

S ca le

/8

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

/8

1'

-0

' G ra p h ic

S ca le

/2

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

'-0

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

VISN 7 LIFE SAFETY SURVEY AND

DRAWING UPDATE, TASK ORDER

#13

GS-10F-0347P

Elijah Knight, PE

R R o m a n y k C o n s u lt in g \R

C C

A E

C

C o n s u lt in g \0

P ro je c ts

\V

IS

N

\L if e

S a fe ty \0

M o d e l\

A tl a n ta \B u ild in g s S u rv e y e d

\A T

-1

F o rt M c P h e rs o n

R e s id e n ta l T re a tm e n t\ A

T -1

F o rt M c P h e rs o n R e s id e n ta l T re a tm e n t.

rv t

/1 /2

:1

:3

A

M

GENERAL SHEET

E.K. HP

G-04X1

VISN 7 ATLANTA

07/31/2018

VISN 7

ATLANTA

100% SUBMITTAL

Revisions: Date:

THIS APPLIES TO OCCUPANCY SEPARATION WALLS, HORIZONTAL EXITS, AND

STAIRWELLS OF 4 OR MORE STORIES.

WALL: WALL EXTENDS FROM FLOOR TO DECK ABOVE.

DUCTS: ALL DUCT PENETRATIONS ARE PROTECTED BY FIRE DAMPERS.

PENETRATIONS: ALL NEW PENETRATIONS ARE SEALED WITH LISTED FIRESTOP

MATERIALS FOR PROTECTING 2-HOUR WALL ASSEMBLIES. WALL

PENETRATIONS ARE REQUIRED TO BE FILLED ON BOTH SIDES OF THE

WALL. FLOOR PENETRATIONS ARE ONLY REQUIRED TO BE FILLED ON

THE TOP OF THE FLOOR.

DOORS: ALL DOORS REQUIRE THE FOLLOWING:

1. LABELED FRAMES (NFPA 80 4.2.1)

2. LABELED 1 1/2 HOUR DOOR (NFPA 80 4.3.1)

3. MAXIMUM 100 SQ. IN. WINDOW (NFPA 80 4.4.5)

4. POSITIVE LATCHING (NFPA 80 6.4.1.4)

5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 80 6.4.1)

6. COORDINATING DEVICES REQUIRED (NFPA 80 6.4.1.2.1)

7. MAXIMUM 1/8" GAP (NFPA 80 6.3.1.7.3)

8. MAXIMUM 3/4" UNDERCUT (NFPA 80 4.8.4.1)

9. MAXIMUM 16" PROTECTIVE PLATE (NFPA 80 6.4.5.1)

10. SWING IN PRIMARY DIRECTION OF TRAVEL (NFPA 101 18/19.2.2.2).

11. PERIODIC INSPECTION AND TESTING SHALL BE PERFORMED AT AT

LEAST ANNUALLY (NFPA 80 5.2.4.1)

2-HOUR FIRE BARRIER

THIS APPLIES TO 1-HOUR FIRE RATED OCCUPANCY SEPERATIONS, HAZARDOUS ROOM

ENCLOSURES AND STAIRWELLS 3 STORIES OR LESS.

WALL: WALL EXTENDS FROM FLOOR TO DECK ABOVE.

DUCTS: STEEL DUCT PENETRATIONS NOT REQUIRED TO BE PROTECTED BY

FIRE DAMPERS.

PENETRATIONS: ALL NEW PENETRATIONS ARE SEALED WITH LISTED FIRESTOP

MATERIALS FOR PROTECTING 1-HOUR WALL ASSEMBLIES. WALL

PENETRATIONS ARE REQUIRED TO BE FILLED ON BOTH SIDES OF THE

WALL. FLOOR PENETRATIONS ARE ONLY REQUIRED TO BE FILLED ON

THE TOP OF THE FLOOR.

DOORS*: ALL DOORS REQUIRE THE FOLLOWING:

1. LABELED FRAMES (NFPA 80 4.2.1)

2. LABELED 3/4 OR 1-HOUR DOOR (NFPA 80 4.3.1)*

3. MAXIMUM 100 SQ. IN. WINDOW (NFPA 80 4.4.5)

4. POSITIVE LATCHING (NFPA 80 6.4.1.4)

5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 80 6.4.1)

6. COORDINATING DEVICES REQUIRED (NFPA 80 6.4.1.2.1)

7. MAXIMUM 1/8" GAP (NFPA 80 6.3.1.7.3)

8. MAXIMUM 3/4" UNDERCUT (NFPA 80 4.8.4.1)

9. MAXIMUM 16" PROTECTIVE PLATE (NFPA 80 6.4.5.1)

10. SWING IN PRIMARY DIRECTION OF TRAVEL (NFPA 101 18/19.2.2.2).

11.PERIODIC INSPECTION AND TESTING SHALL BE PERFORMED AT

AT LEAST ANNUALLY (NFPA 80 5.2.4.1)

* 1-HOUR DOORS ARE REQUIRED IN STAIRWELLS THAT ARE 3

STORIES OR LESS.

1-HOUR FIRE BARRIER

WALL: IF THE HAZARDOUS ROOM HAS A SUSPENDED CEILING CONSTRUCTED

TO LIMIT TRANSFER OF SMOKE, THE WALL HAS NO FIRE RESISTANCE

RATING AND MAY TERMINATE AT THE CEILING. IF THE ROOM DOES NOT

HAVE A SUSPENDED CEILING, THE WALL HAS NO FIRE RESISTANCE

RATING AND SHALL EXTEND TO THE DECK ABOVE.

DUCTS: STEEL DUCT PENETRATIONS ARE NOT REQUIRED TO BE PROTECTED

BY FIRE DAMPERS OR SMOKE DAMPERS.

PENETRATIONS: SEALED WITH NON-FIRE-RATED MATERIALS TO BE RESISTIVE. USE OF

LISTED FIRESTOP MATERIALS IS NOT REQUIRED.

DOORS: EXISTING HAZARDOUS ROOMS:

1. NON-LABELED FRAME (NFPA 101 19.3.7.9)

2. 20 MINUTE OR SOLID WOOD CORE (NFPA 101 19.3.7.6)

3. MAXIMUM 1296 SQ. IN. WINDOW (NFPA 101 19.3.6.3.17)

4. POSITIVE LATCHING NOT REQUIRED (NFPA 101 19.3.6.3.5)

5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 101 19.3.2.1.3)

6. MAXIMUM 1/8" GAP (NFPA 101 19.3.6.3.1)

7. MAXIMUM 1" UNDERCUT (NFPA 101 19.3.6.3.4)

8. MAXIMUM 48" PROTECTIVE PLATE (NFPA 101 19.3.2.1.2)

9. SWING IN ANY DIRECTION

10.SMOKE DOOR ASSEMBLIES SHALL BE TESTED AT LEAST

ANNUALLY (NFPA 105 5.2.1.1)

SMOKE RESISTIVE HAZARDOUS ROOMS

THIS APPLIES TO OCCUPANCY SEPARATION WALLS, HORIZONTAL EXITS, AND STAIRWELLS

OF 4 OR MORE STORIES. THIS COMBINATION WALL IS WHERE A PORTION OF THE 2-HOUR

RATED WALL IS ALSO PART OF THE SMOKE WALL.

WALL: WALL EXTENDS FROM FLOOR TO DECK ABOVE.

DUCTS: ALL DUCT PENETRATIONS ARE PROTECTED BY COMBINATION FIRE

AND SMOKE DAMPERS. SMOKE DAMPERS ARE NOT REQUIRED

WHERE ADJACENT SMOKE COMPARTMENTS ARE PROTECTED BY

QUICK RESPONSE SPRINKLERS THROUGHOUT EACH COMPARTMENT.

PENETRATIONS: ALL NEW PENETRATIONS ARE SEALED WITH LISTED FIRESTOP

MATERIALS FOR PROTECTING 2-HOUR WALL ASSEMBLIES. WALL

PENETRATIONS ARE REQUIRED TO BE FILLED ON BOTH SIDES OF THE

WALL. FLOOR PENETRATIONS ARE ONLY REQUIRED TO BE FILLED ON

THE TOP OF THE FLOOR.

DOORS: ALL DOORS REQUIRE THE FOLLOWING:

1. LABELED FRAMES (NFPA 80 4.2.1)

2. LABELED 1 1/2 HOUR DOOR (NFPA 80 4.3.1)

3. MAXIMUM 100 SQ. IN. WINDOW (NFPA 80 4.4.5)

4. POSITIVE LATCHING (NFPA 80 6.4.1.4)

5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 80 6.4.1)

6. COORDINATING DEVICES REQUIRED (NFPA 80 6.4.1.2.1)

7. MAXIMUM 1/8" GAP (NFPA 80 6.3.1.7.3)

8. MAXIMUM 3/4" UNDERCUT (NFPA 80 4.8.4.1)

9. MAXIMUM 16" PROTECTIVE PLATE (NFPA 80 6.4.5.1)

10.SWING IN PRIMARY DIRECTION OF TRAVEL (NFPA 101 18/19.2.2.2).

11.PERIODIC INSPECTION AND TESTING SHALL BE PERFORMED AT

AT LEAST ANNUALLY (NFPA 80 5.2.4.1)

2-HOUR FIRE AND SMOKE BARRIER

SUBSTANTIAL WALLS AND DOORS TO DIVIDE EACH FLOOR INTO COMPARTMENTS FOR

DEFEND IN PLACE EMERGENCY OPERATIONS. IF THE SMOKE ZONE BARRIER WALL IS OF

MASONRY, GYPSUM BOARD, OR METAL LATH AND PLASTER CONSTRUCTION, AND THE

BARRIER WAS CONSTRUCTED POST 1948, THE SMOKE ZONE BARRIER WALLS ARE

REQUIRED TO BE OF 1 HOUR FIRE RESISTANCE RATING. (NFPA 101, 18.3.2.7.5) SMOKE ZONE

BARRIER WALLS OF WOOD LATH AND PLASTER CONSTRUCTION ARE PERMITTED TO BE OF

A 1/2 HOUR FIRE RESISTANCE RATING (NFPA 101, 19.3.7.3)

WALL: WALL EXTENDS FROM FLOOR TO DECK ABOVE.

DUCTS: ALL DUCT PENETRATIONS ARE PROTECTED BY SMOKE DAMPERS.

SMOKE DAMPERS ARE NOT REQUIRED WHERE ADJACENT SMOKE

COMPARTMENTS ARE PROTECTED BY QUICK RESPONSE SPRINKLERS

THROUGHOUT EACH COMPARTMENT.

PENETRATIONS: ALL PENETRATIONS ARE SEALED WITH LISTED FIRESTOP MATERIALS

FOR PROTECTING 1-HOUR FIRE AND SMOKE WALL ASSEMBLIES.

PENETRATIONS ARE TO BE FILLED ON BOTH SIDES OF THE WALL.

DOORS: ALL DOORS FOR SMOKE BARRIERS REQUIRE THE FOLLOWING:

1. NON-LABELED FRAME (NFPA 101 18.3.7.6)

2. 20 MINUTE OR SOLID WOOD CORE (NFPA 101 18.3.7.6)

3. MAXIMUM 1296 SQ. IN. WINDOW (NFPA 80 4.4.4)

4. POSITIVE LATCHING NOT REQUIRED (NFPA 101 18.3.7.8)

5. SELF CLOSING OR AUTOMATIC CLOSING (NFPA 101 18.3.7.8)

6. MAXIMUM 1/8" GAP (NFPA 101 18.3.7.6.)

7. MAXIMUM 1" UNDERCUT (NFPA 101 19.3.6.3.4)

8. MAXIMUM 48" PROTECTIVE PLATE (NFPA 101 18.3.7.6)

9. SWING IN DIRECTION OPPOSITE OF EACH OTHER (NFPA 101 18.3.7.6)

10.SMOKE DOOR ASSEMBLIES SHALL BE TESTED AT LEAST ANNUALLY

(NFPA 105 5.2.1.1)

SMOKE ZONE BARRIERS

IF THE SMOKE COMPARTMENT IS SPRINKLERED, THE WALL SHALL FORM A BARRIER TO LIMIT THE TRANSFER OF SMOKE. THE WALL HAS NO REQUIRED FIRE RESISTANCE RATING AND MAY TERMINATE AT A CEILING CONSTRUCTED TO LIMIT TRANSFER OF SMOKE. DOORS ARE MANUALLY CLOSED IN AN EMERGENCY NFPA 101, 18.3.6.2 & 19.3.6.2

IF THE SMOKE COMPARTMENT IS NOT SPRINKLERED, THE WALL SHALL BE CONTINUOUS FROM THE FLOOR TO THE UNDERSIDE OF THE FLOOR OR ROOF DECK ABOVE. CORRIDOR WALL SHALL HAVE A MINIMUM 1/2 HOUR FIRE RESISTANCE RATING. DOORS ARE MANUALLY CLOSED IN AN EMERGENCY NFPA 101 19.3.6.2

DOORS: DOORS THAT ARE NOT PART OF A RATED WALL:

1. NON-LABELED FRAME (NFPA 101 18.3.6.3.1, 19.3.6.3 & 19.3.6.3.3)

2. NON-RATED DOORS PERMITTED IF SPRINKLERED (NFPA 101 18.3.6.3.1, 19.3.6.3.2(2))

3. 20-MINUTE OR SOLID WOOD CORE DOOR IF NOT SPRINKLERED (NFPA 101 19.3.6.3.1)

4. POSITIVE LATCHING EXCEPT TOILETS, SHOWER AND SINK

CLOSETS (NFPA 101 18.3.6.3.6 & 19.3.6.3.6)

5. SELF-CLOSING NOT REQUIRED (NFPA 101 19.3.6.3.11)

6. NO MAXIMUM GAP (NFPA 101 18.3.6.3.1 & 19.3.6.3.3)

7. MAXIMUM 1" UNDERCUT (NFPA 101 18.3.6.3.1 & 19.3.6.3.4)

8. MAXIMUM 48" PROTECTIVE PLATE (NFPA 101 18/19.3.6.3.12)

9. TRANSFER GRILLS NOT PERMITTED EXCEPT TOILETS, SHOWER AND SINK CLOSETS

(NFPA 101 18/19.3.6.4)

10. SWING IN ANY DIRECTION

11. SMOKE DOOR ASSEMBLIES SHALL BE TESTED AT LEAST ANNUALLY (NFPA 105 5.2.1.1)

HEALTH CARE OCCUPANCY CORRIDORS

NOTE: ALL CODE REFERENCES ARE PER THE 2015 EDITION OF NFPA 101 LIFE SAFETY CODE AND THE OTHER APPLICABLE CODES. FEDERAL FACILITIES FOLLOW 2015 LIFE SAFETY CODE.

FORMER DECOMMISSIONED SMOKE BARRIER RETAINED AS FIRE ALARM/SPRINKLER ZONE.

BUILDING OCCUPANTS PERMITTED TO DEFEND IN PLACE UNTIL DIRECTED BY THE FIRE

DEPARTMENT PER SECTION 15.7.4.3 OF NFPA 99-2015 EDITION AND PRIVATE MODE AUDIBLE

REQUIREMENTS OF SECTION 18.4:4 OF NFPA 72-2016 EDITION.

WALL: WALL EXTENDS FROM FLOOR TO SUSPENDED CEILING OR DECK ABOVE.

DUCTS: NO MINIMUM REQUIREMENTS.

PENETRATIONS: NO MINIMUM REQUIREMENTS FOR WALL PENETRATIONS ABOVE A

SUSPENDED CEILING. PENETRATIONS BELOW A SUSPENDED CEILING

OR DECK SEALED WITH NON-FIRE-RATED MATERIALS TO BE SMOKE

RESISTIVE.

DOORS: NON-FIRE-RATED DOORS AND FRAMES SELF CLOSING OR AUTOMATIC

CLOSING IN AN EMERGENCY.

NON-RATED SMOKE PARTITION

SUITES

HEALTHCARE AREA OPEN TO CORRIDOR WITH 24/7 SUPERVISION - NO SMOKE DETECTION REQUIRED.

HEALTHCARE AREA OPEN TO CORRIDOR - SMOKE DETECTION PROVIDED.

(COLOR #3) (COLOR #4) (COLOR #230)

(COLOR #1) (COLOR #6) (COLOR #30)

(COLOR #2)

(COLOR #2)

(COLOR #3)

' 6

G ra p h ic S ca le

/2

1'

-0

G ra p h ic S ca le

/3 2"

'-0

' G ra p h ic S ca le

/1 6"

'-0

' G ra p h ic

S ca le

/8

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

/8

1'

-0

' G ra p h ic

S ca le

/2

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

'-0

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

VISN 7 LIFE SAFETY SURVEY AND

DRAWING UPDATE, TASK ORDER

#13

GS-10F-0347P

Elijah Knight, PE

R R o m a n y k C o n s u lt in g \R

C C

A E

C

C o n s u lt in g \0

P ro je c ts

\V

IS

N

\L if e

S a fe ty \0

M o d e l\

A tl a n ta \B u ild in g s S u rv e y e d

\A T

-1

F o rt M c P h e rs o n

R e s id e n ta l T re a tm e n t\ A

T -1

F o rt M c P h e rs o n R e s id e n ta l T re a tm e n t.

rv t

/1 /2

:1

:3

A

M

GENERAL SHEET

E.K. HP

G-04X2

VISN 7 ATLANTA

07/31/2018

VISN 7

ATLANTA

100% SUBMITTAL

Revisions: Date:

APPLICABLE CODES AND STANDARDS:

1. THE BUILDING WAS DESIGNED TO THE 1960 EDITION OF NFPA 101, LIFE SAFETY CODE.

2. THE 1960 PUBLIC BUILDING AMENDMENT ACT (PL100-678) REQUIRES ALL FEDERAL AGENCIES TO FOLLOW

THE LATEST EDITIONS OF NATIONALLY RECOGNIZED FIRE AND LIFE SAFETY CODES. THE VA HAS ADOPTED THE NATIONAL FIRE CODES PUBLISHED BY THE NATIONAL FIRE PROTECTION ASSOCIATION. LIFE SAFETY REQUIREMENTS ARE SPECIFICALLY ADDRESSED IN THE 2018 EDITION OF NFPA 101, LIFE SAFETY CODE.

3. ALL NEW CONSTRUCTION OR BUILDING RENOVATIONS ARE REQUIRED TO COMPLY WITH THE LATEST EDITION OF NFPA 101 OR IT'S REFERENCED STANDARDS. EXISTING BUILDING CONDITIONS ARE REQUIRED TO COMPLY WITH THE APPLICABLE CODES OR STANDARDS AT THE TIME OF BUILDING DESIGN AND THE APPLICABLE PROVISIONS FOR EXISTING BUILDINGS IN CURRENT EDITIONS OF APPLICABLE

CODES AND STANDARDS.

4. OTHER NFPA CODES AND STANDARDS:

A. NFPA 10 - PORTABLE FIRE EXTINGUISHERS, 2018 EDITION.

B. NFPA 13 - SPRINKLER SYSTEMS, 2016 EDITION.

C. NFPA 14 - STANDPIPE SYSTEMS, 2016 EDITION.

D. NFPA 20 - FIRE PUMPS, 2016 EDITION

E. NFPA 70 - NATIONAL ELECTRIC CODE, 2017 EDITION.

F. NFPA 72 - NATIONAL FIRE ALARM CODE, 2016 EDITION.

G. NFPA 75 - ELECTRONIC COMPUTER EQUIPMENT, 2017 EDITION.

H. NFPA 80 - FIRE DOORS, 2016 EDITION.

I. NFPA 90A&B - HEATING AND AIR CONDITIONING SYSTEMS, 2018 EDITION.

J. NFPA 96 - COMMERCIAL COOKING EQUIPMENT, 2017 EDITION.

K. NFPA 99 - HEALTH CARE FACILITIES CODE, 2018 EDITION.

L. NFPA 105 - SMOKE DOORS, 2016 EDITION.

M. NFPA 110 - EMERGENCY POWER SYSTEMS, 2016 EDITION.

N. NFPA 241 - CONSTITUTION AND DEMOLITION, 2013 EDITION.

PENETRATIONS:

1. PRIOR TO THE EARLY 1990'S, THE STANDARD INDUSTRY PRACTICE FOR THE SEALING OF PENETRATIONS WAS TO

USE THE SAME CONSTRUCTION MATERIALS AS HOW THE WALL/FLOOR WAS CONSTRUCTED. CONCRETE PATCH WAS USED FOR CONCRETE FLOORS. MORTAR JOINT COMPOUND WAS USED FOR MASONRY WALLS. GYPSUM

PATCH COMPOUND WAS USED USED FOR GYPSUM WALLS.

2. PRIOR TO THE EARLY 1990'S, THE MANUFACTURES PUBLISHED INSTRUCTIONS FOR FIRE RESISTIVE WALL AND FLOOD CONSTRUCTION REQUIRED THE USE OF THE SAME CONSTRUCTION MATERIALS AS HOW THE WALL/FLOOR

WAS CONSTRUCTED TO SEAL PENETRATIONS.

3. THE FIRST LISTINGS OF FIRESTOP MATERIALS WAS IN 1991. THE FIRST CODE REQUIREMENTS TO UTILIZE LISTED

FIRESTOP MATERIALS OCCURRED IN 1992 EDITIONS OF CODES AND STANDARDS.

4. ALL PENETRATIONS ARE SEALED WITH LISTED FIRESTOP MATERIALS FOR PROTECTING THE REQUIRED RATING

OF THE WALL ASSEMBLY.

5. EXISTING PENETRATIONS SEALED WITH THE SAME CONSTRUCTION MATERIAL AS THE WALL/FLOOR, MAY REMAIN

AS AN EXISTING PREVIOUSLY APPROVED CONSTRUCTION METHOD.

6. EXISTING PENETRATIONS THAT REQUIRE REPAIR OR REPLACEMENT REQUIRE THE USE OF LISTED FIRESTOP

MATERIALS.

FIRE SPRINKLER SYSTEM:

1. THE COMBINATION STANDPIPE AND FIRE SPRINKLER SYSTEM WAS DESIGNED TO THE 2016 EDITION OF NFPA 13.

2. QUICK RESPONSE TYPE SPRINKLERS ARE INSTALLED THROUGHOUT MOST OF THE BUILDING. STANDARD

RESPONSE TYPE SPRINKLERS ARE INSTALLED IN THE ELEVATOR MACHINE ROOMS.

3. SPRINKLERS WERE INSTALLED IN LIGHT HAZARD AREAS INCLUDING; CORRIDORS, OFFICES, PATIENT CARE AND

PATIENT SLEEPING ROOMS AT LIGHT HAZARD 0.10 GPM/1500 SQ. FT. DENSITY.

4. SPRINKLERS WERE INSTALLED IN ORDINARY HAZARD GROUP I AREAS INCLUDING; LABORATORIES (WITHOUT

FLAMMABLE LIQUIDS), MECHANICAL EQUIPMENT ROOMS, ELECTRICAL SWITCH GEAR ROOMS, REPAIR SHOPS AND

STORAGE ROOMS UNDER 250 SQ. FT. AT A 0.15 GPM/1500 SQ. FT. DENSITY.

5. SPRINKLERS WERE INSTALLED IN ORDINARY HAZARD GROUP II AREAS INCLUDING GENERAL STORAGE ROOMS OVER 250 SQ. FT. AND LABORATORIES (WITH THE USE OF FLAMMABLE LIQUIDS) AT A 0.20 GPM/1500 SQ. FT.

DENSITY.

FIRE ALARM SYSTEM:

1. THE FIRE ALARM SYSTEM WAS DESIGNED TO THE 2013 EDITION OF NFPA 72, NATIONAL FIRE ALARM CODE.

2. PRIVATE MODE BUILDING OCCUPANT NOTIFICATION IS INSTALLED PER SECTIONS 19.3.4.3.1 AND 9.6.3.6.3 OF NFPA

101-2015 EDITION.

3. PRIVATE MODE AUDIBLE DEVICES (SPEAKERS) ARE INSTALLED IN CORRIDORS AND LARGER ROOMS OR SUITES

PER SECTION 18.4.4.1 OF NFPA 72-2016 EDITION.

4. PRIVATE MODE VISIBLE DEVICES (STROBES) ARE INSTALLED AT REDUCED QUANTITY AND SPACING PER SECTION

18.6 OF THE NFPA 72-2016 EDITION.

5. STROBE CIRCUITS ARE REQUIRED TO BE SYNCHRONIZED IN ACCORDANCE WITH SECTION 18.5.5.4.2 OF NFPA

72-2016 EDITION.

SUITES:

1. SUITES ARE UTILIZED TO ILLUSTRATE AREAS WITH THE SAME FUNCTION, USE OF HALLWAYS OR AISLES AND THE

END OF PUBLIC EXIT CORRIDORS. NO EXIT SIGNS OUTSIDE OF THE SUITE DIRECT OCCUPANTS INTO A SUITE TO

REACH AN EXIT.

2. HEALTH CARE OCCUPANCY SUITES ARE REGULATED BY FUNCTION AND SIZE.

3. HEALTH CARE OCCUPANCY PATIENT SLEEPING SUITES:

A. SINGLE EXIT SUITE - 1,000 SQ. FT. (NFPA 101 -19.2.5.7.2.2)

B. MULTI EXIT SUITE - 5,000 SQ. FT. (NFPA 101 - 19.2.5.7.2.3.A)

C. MULTI EXIT SUITE WITH STANDARD RESPONSE SPRINKLERS OR COMPLETE SMOKE DETECTION - 7,500 SQ.

FT. (NFPA 101 - 19.2.5.7.2.3.B)

D. MULTI EXIT SUITE WITH DIRECT VISUAL SUPERVISION, QUICK RESPONSE SPRINKLERS AND COMPLETE

SMOKE DETECTION - 10,000 SQ. FT. (NFPA 101 - 19.2.5.7.2.3.C)

4. PATIENT CARE NON - SLEEPING SUITES:

A. SINGLE EXIT SUITE - 2,500 SQ. FT. (NFPA 101 - 19.2.5.7.3.1.B)

B. MULTI EXIT SUITE - 10,000 SQ. FT. (NFPA 101 - 19.2.5.7.3.2)

C. MULTI EXIT SUITE WITH STANDARD RESPONSE SPRINKLERS AND COMPLETE SMOKE DETECTION OR QUICK

RESPONSE SPRINKLERS - 12,500 SQ. FT. (NFPA 101 - 19.2.5.7.3.2.A)

D. MULTI EXIT SUITE WITH QUICK RESPONSE SPRINKLERS AND COMPLETE SMOKE DETECTION (NFPA 101 -

19.2.5.7.3.2.B)

5. HEALTH CARE OCCUPANCY NON - PATIENT - CARE SUITES FOLLOW THE TRAVEL DISTANCE REQUIREMENTS

AS LISTED IN TABLE A.7.6 OF NFPA 101.

6. SUITES IN OTHER OCCUPANCIES ARE NOT REGULATED IN SIZE BUT STILL FOLLOW THE TRAVEL DISTANCE

REQUIREMENTS AS LISTED IN TABLE A.7.6 OF NFPA 101.

BUILDING # FLOOR

HEALTH CARE

OCCUPANCY

TOTAL

508C 1 49,031 0 22,513 0 71,544

AMBULATORY HEALTH

CARE OCCUPANCY

BUSINESS

OCCUPANCY

INDUSTRIAL

OCCUPANCY

508ASCA 2 0 0 56,228 0 56,228

508ASCA 1 0 0 56,573 0 56,573

125 2 0 0 22,258 0 22,258

125 1 0 0 41,126 0 41,126

128 2 0 0 8,723 0 8,723

128 1 0 0 8,723 0 8,723

SUB TOTAL 0 0 17,446 0 17,446

129 2 0 0 8,696 0 8,696

129 1 0 0 8,692 0 8,692

SUB TOTAL 0 0 17,388 0 17,388

130 1 0 0 8,721 0 8,721

131 2 0 0 0 0 9,517

SUB TOTAL 0 0 8,721 0 17,442

131 GROUND 0 0 9,516 0 9,516

SUB TOTAL 0 0 9,516 0 28,551

GRAND TOTAL 49,031 0 263,657 0 340,444

OCCUPANCY TABLE

DORMITORY

OCCUPANCY

9,517

8,721

19,035

27,756

SUB TOTAL

SUB TOTAL 0 0 112,801 0 112,8010

125 BASEMENT 0 0 11,888 0 11,8880

SUB TOTAL 0 0 75,272 0 75,2720

130 2 0 0 0 0 8,7218,721

131 1 0 0 0 0 9,5189,518

49,031 0 22,513 0 71,5440

LEGEND

l lllllll

O OO

OO OO

KEY NOTES

KEY NOTES

l ll l l l l l l l l ll llll l l l l l

DOOR FAILS INSPECTION TEST

DOOR PASSES INSPECTION TEST

FB1 = FIRE BARRIER 1HR

FB2 = FIRE BARRIER 2HR

FB1/2 = FIRE BARRIER 30 MIN

FSB1 = FIRE / SMOKE BARRIER 1HR

FSB2 = FIRE / SMOKE BARRIER 2HR

SP0 = SMOKE PARTITION NON-RATED

SB0 = SMOKE BARRIER NON-RATED

EHR = EXISTING HAZARDOUS ROOMS

HCO = HEALTH CARE OCCUPANCY

NON-RATED

NON-RATED INTERIOR PARTITION WALL

XXX-XXXX-XX-XXXXX DOOR TAG

275 SF

CORR

1D1C1

190 SF

CORR

1D1C5

290 SF

CORR

1D1C2

593 SF

CORR

1D1C3

100 SF

CORR

1D1C4

200 SF

CORR

1D1C6

361 SF

CORR

1D1C7

68 SF

CORR

1D1C8

79 SF

RECEPTION

1D101

262 SF

MECH

1D102

103 SF

WAIT

1D103

98 SF

ELEC

1D105

68 SF

VISITOR TLT

1D106

204 SF

STAFF LOUNGE

1D107

61 SF

VISITOR TLT

1D108

111 SF

OFF

1D110

8 SF

NOT KNOWN

RCC101R

5 SF

NOT KNOWN

RCC102R

98 SF

OFF

1D112

138 SF

OFF

1D113

116 SF

OFF

1D114

108 SF

OFF

1D115

108 SF

OFF

1D116

76 SF

COPY

1D117

127 SF

OFF

1D118

104 SF

OFF

1D120

137 SF

OFF

1D122

81 SF

STOR

1D123

102 SF

OFF

1D125

221 SF

DIRS OFF

1D127

190 SF

STAIR 3

1D130

124 SF

OFF

1D119

269 SF

SMALL GROUP RM

1D121

82 SF

COMM

1D14191 SF

ELEV

1D143

125 SF

OFF/EXAM

1D144

87 SF

RECEPTION

1D145

66 SF

STAFF TLT

1D146

125 SF

OFF

1D147

62 SF

STAFF TLT

1D148

98 SF

OFF

1D149

40 SF

JC

1D150

425 SF

LARGE GROUP RM

1D151

135 SF

OFF

1D152

85 SF

OFF

1D153

93 SF

OFF

1D154

194 SF

VTEL CONF

1D155

92 SF

OFF

1D156

125 SF

OFF

1D158

220 SF

DIRS OFF

1D159

188 SF

STAIR 2

1D140

186 SF

STAIR 1

1D160

508-130-01-DRF001

508-130-01-DRF002

508-130-01-DRF003

508-130-01-DRF004

508-130-01-DRF005

' 6

G ra p h ic S ca le

/2

1'

-0

G ra p h ic S ca le

/3 2"

'-0

' G ra p h ic S ca le

/1 6"

'-0

' G ra p h ic

S ca le

/8

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

/8

1'

-0

' G ra p h ic

S ca le

/2

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

'-0

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

VISN 7 LIFE SAFETY SURVEY AND

DRAWING UPDATE, TASK ORDER

#13

GS-10F-0347P

Elijah Knight, PE

R R o m a n y k C o n s u lt in g \R

C C

A E

C

C o n s u lt in g \0

P ro je c ts

\V

IS

N

\L if e

S a fe ty \0

M o d e l\

A tl a n ta \B u ild in g s S u rv e y e d

\A T

-1

F o rt M c P h e rs o n

R e s id e n ta l T re a tm e n t\ A

T -1

F o rt M c P h e rs o n R e s id e n ta l T re a tm e n t.

rv t

/1 /2

:1

:3

A

M

FIRE/SMOKE DOOR INSPECTION FLOOR PLAN -

LEVEL 01

E.K. HP

LS0401

VISN 7 ATLANTA

07/31/2018

VISN 7

ATLANTA

100% SUBMITTAL

Note Number Fire Door Note

1 VISIBLE SIGN OF DAMAGE

2 PARTS MISSING OR BROKEN

3 SURFACE HOLES IN DOOR OR FRAME

4a DOOR LABELS CLEARLY NOT VISIBLE AND LEGIBLE

4b FRAME LABELS CLEARLY NOT VISIBLE AND LEGIBLE

5 FAILED GLAZING AND FRAME INSPECTION

6 SELF-CLOSING DEVICE NOT OPERATIONAL

7 COORDINATOR NOT OPERATIONAL

8 LATCHING HARDWARE NOT OPERATIONAL

9 AUXILIARY HARDWARE INTERFERENCE

10 EDGE CLEARANCE NOT ACCEPTABLE

11 DOOR CLEARANCE NOT ACCEPTABLE

12 SIGNAGE DOES NOT MEET REQUIREMENTS

13 FIELD MODIFICATIONS VOID LABEL

Note Number Fire Smoke Door Note

1 VISIBLE SIGN OF DAMAGE

2 PARTS MISSING OR BROKEN

3 SURFACE HOLES IN DOOR OR FRAME

4a DOOR LABELS CLEARLY NOT VISIBLE AND LEGIBLE

4b FRAME LABELS CLEARLY NOT VISIBLE AND LEGIBLE

5 FAILED METAL DOOR FRAME INSPECTION

6 FAILDED GLAZING AND FRAME INSPECTION

7 SELF-CLOSING DEVICE NOT OPERATIONAL

8 COORDINATOR NOT OPERATIONAL

9 LATCHING HARDWARE NOT OPERATIONAL

10 AUXILIARY HARDWARE INTERFERENCE

11 EDGE CLEARANCE NOT ACCEPTABLE

12 DOOR CLEARANCE NOT ACCEPTABLE

NORTH ARROW

FIRE/SMOKE DOOR INSPECTION FLOOR PLAN - LEVEL 01

1/8" = 1'-0"

LEGEND

l lllllll

O OO

OO OO

KEY NOTES

KEY NOTES

DOOR FAILS INSPECTION TEST

DOOR PASSES INSPECTION TEST

FB1 = FIRE BARRIER 1HR

FB2 = FIRE BARRIER 2HR

FB1/2 = FIRE BARRIER 30 MIN

FSB1 = FIRE / SMOKE BARRIER 1HR

FSB2 = FIRE / SMOKE BARRIER 2HR

SP0 = SMOKE PARTITION NON-RATED

SB0 = SMOKE BARRIER NON-RATED

EHR = EXISTING HAZARDOUS ROOMS

HCO = HEALTH CARE OCCUPANCY

NON-RATED

NON-RATED INTERIOR PARTITION WALL

XXX-XXXX-XX-XXXXX DOOR TAG

241 SF

CORR

2D2C1

370 SF

CORR

2D2C2

539 SF

CORR

2D2C3

100 SF

CORR

2D2C4

187 SF

CORR

2D2C5

202 SF

CORR

2D2C6

358 SF

CORR

2D2C7

71 SF

CORR

2D2C8

190 SF

STAIR 1

2D260

95 SF

ELEV

2D243

195 SF

STAIR 2

2D240

190 SF

STAIR 3

2D224

125 SF

NRS STATION

2D201

253 SF

MECH

2D202

79 SF

MED RM

2D201A

102 SF

ELEC

2D205

78 SF

TESTING TLT

2D207

200 SF

BEDRM DOUBLE (ADA)

2D208

67 SF

TLT

2D208A

147 SF

NRS MGR OFF

2D209

156 SF

BEDRM DOUBLE

2D212

155 SF

BEDRM SINGLE (ADA)

2D213

157 SF

BEDRM DOUBLE

2D214

55 SF

STAFF

2D215

40 SF

STOR

2D217

124 SF

OFF

2D219 269 SF

LOUNGE

2D221

154 SF

BEDRM DOUBLE

2D222

192 SF

BEDRM DOUBLE

2D223

71 SF

TLT

2D223A

68 SF

TLT

2D222A

68 SF

TLT

2D214A

75 SF

TLT

2D212A

66 SF

TLT

2D213A

141 SF

LAUNDRY

2D225

85 SF

COMM

2D241

211 SF

BEDRM DOUBLE (ADA)

2D244

163 SF

BEDRM

DOUBLE

2D245

75 SF

SOILED LINEN

2D249

67 SF

TLT

2D244A

40 SF

JC

2D250

71 SF

TLT

2D245A

89 SF

CLEAN LINEN

2D251

155 SF

BEDRM DOUBLE

2D252

199 SF

BEDRM DOUBLE

2D257

154 SF

BEDRM DOUBLE

2D258

140 SF

LAUNDRY

2D259

69 SF

TLT

2D257A

68 SF

TLT

2D258A

68 SF

TLT

2D252A

424 SF

LOUNGE

2D253

508-130-02-DRF001

508-130-02-DRF002 508-130-02-DRF003

508-130-02-DRF004

508-130-02-DRF005 508-130-02-DRF006

508-130-02-DRF007 508-130-02-DRF008

508-130-02-DRF009

4a

4b 7 10

' 6

G ra p h ic S ca le

/2

1'

-0

G ra p h ic S ca le

/3 2"

'-0

' G ra p h ic S ca le

/1 6"

'-0

' G ra p h ic

S ca le

/8

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

/8

1'

-0

' G ra p h ic

S ca le

/2

1' -0

G ra p h ic S ca le

/4

1'

-0

G ra p h ic S ca le

'-0

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

8910 7 6 5 4 3 2 1 of Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

NOT FOR

PERMITTING OR

CONSTRUCTION

A/E:Consultant:

VISN 7 LIFE SAFETY SURVEY AND

DRAWING UPDATE, TASK ORDER

#13

GS-10F-0347P

Elijah Knight, PE

R R o m a n y k C o n s u lt in g \R

C C

A E

C

C o n s u lt in g \0

P ro je c ts

\V

IS

N

\L if e

S a fe ty \0

M o d e l\

A tl a n ta \B u ild in g s S u rv e y e d

\A T

-1

F o rt M c P h e rs o n

R e s id e n ta l T re a tm e n t\ A

T -1

F o rt M c P h e rs o n R e s id e n ta l T re a tm e n t.

rv t

/1 /2

:1

:3

A

M

FIRE/SMOKE DOOR INSPECTION FLOOR PLAN -

LEVEL 02

E.K. HP

LS0402

VISN 7 ATLANTA

07/31/2018

VISN 7

ATLANTA

100% SUBMITTAL

Note Number Fire Door Note

1 VISIBLE SIGN OF DAMAGE

2 PARTS MISSING OR BROKEN

3 SURFACE HOLES IN DOOR OR FRAME

4a DOOR LABELS CLEARLY NOT VISIBLE AND LEGIBLE

4b FRAME LABELS CLEARLY NOT VISIBLE AND LEGIBLE

5 FAILED GLAZING AND FRAME INSPECTION

6 SELF-CLOSING DEVICE NOT OPERATIONAL

7 COORDINATOR NOT OPERATIONAL

8 LATCHING HARDWARE NOT OPERATIONAL

9 AUXILIARY HARDWARE INTERFERENCE

10 EDGE CLEARANCE NOT ACCEPTABLE

11 DOOR CLEARANCE NOT ACCEPTABLE

12 SIGNAGE DOES NOT MEET REQUIREMENTS

13 FIELD MODIFICATIONS VOID LABEL

Note Number Fire Smoke Door Note

1 VISIBLE SIGN OF DAMAGE

2 PARTS MISSING OR BROKEN

3 SURFACE HOLES IN DOOR OR FRAME

4a DOOR LABELS CLEARLY NOT VISIBLE AND LEGIBLE

4b FRAME LABELS CLEARLY NOT VISIBLE AND LEGIBLE

5 FAILED METAL DOOR FRAME INSPECTION

6 FAILDED GLAZING AND FRAME INSPECTION

7 SELF-CLOSING DEVICE NOT OPERATIONAL

8 COORDINATOR NOT OPERATIONAL

9 LATCHING HARDWARE NOT OPERATIONAL

10 AUXILIARY HARDWARE INTERFERENCE

11 EDGE CLEARANCE NOT ACCEPTABLE

12 DOOR CLEARANCE NOT ACCEPTABLE

NORTH ARROW

FIRE/SMOKE DOOR INSPECTION FLOOR PLAN - LEVEL 02

1/8" = 1'-0"

Sheets
G-04 - COVER
G-04X1 - GENERAL SHEET
G-04X2 - GENERAL SHEET
LS0401 - FIRE/SMOKE DOOR INSPECTION FLOOR PLAN - LEVEL 01
LS0402 - FIRE/SMOKE DOOR INSPECTION FLOOR PLAN - LEVEL 02