2022-06-06_Fort-McPherson-VAMC-Bldg-130_Annual Report.pdf
PDF 324 KB Posted
- Attached to
- Fire Sprinkler Testing
- Solicitation number
- 36C24724Q0269
About this file
This document is a fire sprinkler testing certificate for Building 130 at the Fort McPherson VA Medical Center in Atlanta, GA. Vets Fire & Life Safety conducted inspection, testing and/or maintenance of the fire/life safety system and found 127 devices to be in proper working order, including 5 duct detectors, 3 heat detectors, 6 pull stations, 45 smoke detectors, 2 releasing devices, 26 speaker/strobes, and 31 strobes. Battery and power supply readings were also within specification. The inspection details device addresses, locations, previous testing records, and ensures components like fan shutdown, elevator recall, and door holders are functioning correctly.
Additionally, this file includes a federal contract opportunity with solicitation number 36C24724Q0269 for fire sprinkler testing services. The requirement is for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7 but no further product or service details, pricing terms, response dates or other information is provided.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
For
Fort McPherson VAMC Bldg 130 1701 Hardee Ave SW
Atlanta, GA 30310
Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards effective January 31, 2021
Inspection Completion Date Jun 6, 2022
Building: Fort McPherson VAMC Bldg 130 Company: Vets Fire & Life Safety Contact: Mike McGill Contact: Mike Gill
Title: Maintenance & Operations Supervisor Title: Inspector
Page of 1 22 Executive Summary
Vets Fire & Life Safety Download Date: 06/20/2022
Executive Summary Generated by: BuildingReports.com
Building Information Building: Fort McPherson VAMC Bldg 130 Contact: Mike McGill
Address: 1701 Hardee Ave SW Phone: 14043216111
Address: Fax:
City/State/Zip: Atlanta, GA 30310 Mobile:
Country: United States of America Email:
Inspection Performed By Company: Vets Fire & Life Safety Inspector: Mike Gill
Address: 7 Sherri Ln Phone: 636-543-0165
Address: Fax:
City/State/Zip: Saint Peters, MO 63376-2142 Mobile:
Country: United States of America Email: mike.gill@vflsc.com
System Control Unit Manufacturer: Inspection Date: 06/06/2022 IDC Style:
Model Number: Install Date: 05/23/2018 SLC Style:
Software Version: Version Date: 05/23/2018 NAC Style:
Location: 1st Current Protection: Breaker
Page of 2 22
Vets Fire & Life Safety Download Date: 06/20/2022
Inspection Completion Date: Jun 6, 2022 Building: Fort McPherson VAMC Bldg 130 EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
Devices Tested This
Quarter Pass Fail Tested YTD
(2022) Untested YTD
(2022) Total
Quantity Duct Detector 5 5 0 5 0 5
Heat Detector 3 3 0 3 0 3
Pull Station 6 6 0 6 0 6
Smoke Detector 45 45 0 45 0 45
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2019) Table 14.4.3.2 (22)
Devices Tested This
Quarter Pass Fail Tested YTD
(2022) Untested YTD
(2022) Total
Quantity Releasing Device 2 2 0 2 0 2
Speaker/Strobe 26 26 0 26 0 26
Strobe 31 31 0 31 0 31
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment.
NFPA 90A (2021) 6.4.1
Devices Tested This
Quarter Pass Fail Tested YTD
(2022) Untested YTD
(2022) Total
Quantity Duct Detector 5 5 0 5 0 5
LS 02.01.34 EP 02 Protected master fire alarm control panel
Devices Tested This
Quarter Pass Fail Tested YTD
(2022) Untested YTD
(2022) Total
Quantity Control Panel 1 1 0 1 0 1
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Devices Tested This
Quarter Pass Fail Tested YTD
(2022) Untested YTD
(2022) Total
Quantity Battery 6 6 0 6 0 6
Power Supply 2 2 0 2 0 2
Total Device Count: 127
Page of 3 22
Vets Fire & Life Safety Download Date: 06/20/2022
Certification
Company: Vets Fire & Life Safety Building: Fort McPherson VAMC Bldg 130
Inspector: Mike Gill Contact: Mike McGill
Page of 4 22 Notes & Recommendations
Vets Fire & Life Safety Download Date: 06/20/2022
Notes & Recommendations Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Control Panel: 1 -
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
1 Duct Detector 1st Mech Rm 1D102 Return Passed 42020000 Shuts Down Unit
2 Duct Detector 1st Mech Rm 1D102 Return Passed 46938592 Shuts Down Unit
3 Duct Detector 1st Mech Rm 1D102 Supply Passed 46938593 Shuts Down Unit
4 Smoke Detector 1st Elevator Lobby Passed 46938610 Recalls To Alternate Floor
5 Duct Detector 2nd Mech Rm 2D202 Return Passed 46938595 Shuts Down Unit
6 Duct Detector 2nd Mech Rm 2D202 Supply Passed 46938594 Shuts Down Unit
7 Smoke Detector 2nd Elevator Lobby Passed 46938631 Recalls To Primary Floor
8 Smoke Detector 2nd Elevator Lobby Passed 46938633 Recalls To Primary Floor
9 Smoke Detector 2nd Elevator Top Of Shaft Passed 46938632 Recalls To Primary Floor 10 Smoke Detector Ground Elevator Equipment Rm G01 Passed 46938599
Recalls To Primary Floor javascript:openEditDevice('load-edit-f2-device','736896','3032788','42020000');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938592');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938593');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938610');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938595');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938594');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938631');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938633');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938632');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938599');
Page of 5 22 Inspection & Testing
Vets Fire & Life Safety Download Date: 06/20/2022
Inspection & Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 130 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Duct Detector 5 5 0 5 5
Device Type Location ScanID Address Q2/21 Q2/22 Duct Detector 1st Mech Rm 1D102 Supply 46938593 1-M1-104 05/25-P 05/24-P Duct Detector 1st Mech Rm 1D102 Return 46938592 1-M1-25 05/25-P 05/24-P Duct Detector 1st Mech Rm 1D102 Return 42020000 1-M1-24 05/25-P 05/24-P Duct Detector 2nd Mech Rm 2D202 Return 46938595 1-M1-106 05/25-P 05/24-P Duct Detector 2nd Mech Rm 2D202 Supply 46938594 1-M1-105 05/25-P 05/24-P
Device Total: 5 Return to Executive Summary
Page of 6 22
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically.
(NFPA 72-19 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Heat Detector 3 3 0 3 3
Device Type Location ScanID Address Q2/21 Q2/22 Heat Detector 2nd Elevator Top Of Shaft 46938591 1-M1-89 05/25-P 05/25-P Heat Detector Ground Elevator Pit 46938589 1-M1-9 05/25-P 05/25-P Heat Detector Ground Elevator Equipment Rm
G01 46938590 1-M1-11 05/25-P 05/25-P
Device Total: 3 Return to Executive Summary
Page of 7 22
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-19 Table 14.4.3.2 (17)(5)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Pull Station 6 6 0 6 6
Device Type Location ScanID Address Q2/21 Q2/22 Pull Station 1st Stair 3 Exit 46938583 1-M1-30 05/25-P 05/24-P Pull Station 1st Stair 1 Exit 46938585 1-M1-47 05/25-P 05/24-P Pull Station 1st Stair 2 Exit 46938584 1-M1-32 05/25-P 05/24-P Pull Station 2nd Stair 2 Exit 46938587 1-M1-78 05/25-P 05/24-P Pull Station 2nd Stair 1 Exit 46938588 1-M1-102 05/25-P 05/24-P Pull Station 2nd Stair 3 Exit 46938586 1-M1-68 05/25-P 05/24-P
Device Total: 6 Return to Executive Summary
Page of 8 22
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Smoke Detector 45 45 0 45 45
Device Type Location ScanID Address Q2/21 Q2/22 Smoke Detector 1st Elevator Lobby 46938610 1-M1-39 05/25-P 05/25-P Smoke Detector 1st Corridor @ Office 1D152 46938613 1-M1-44 05/25-P 05/24-P Smoke Detector 1st Corridor @ Stair 1 46938615 1-M1-46 05/25-P 05/24-P Smoke Detector 1st Corridor @ Large Group Rm
1D151 46938614 1-M1-45 05/25-P 05/24-P
Smoke Detector 1st Corridor by Reception 1D101 46938612 1-M1-43 05/25-P 05/24-P Smoke Detector 1st Elevator Lobby 46938611 1-M1-41 05/25-P 05/24-P Smoke Detector 1st Comm Rm 1D141 46938609 1-M1-38 05/25-P 05/24-P Smoke Detector 1st Interset Corridor West 46938608 1-M1-37 05/25-P 05/24-P Smoke Detector 1st Corridor 1D141 46938607 1-M1-35 05/25-P 05/24-P Smoke Detector 1st Corridor @ Stair 2 46938606 1-M1-31 05/25-P 05/24-P Smoke Detector 1st Corridor @ Stair 3 46938605 1-M1-29 05/25-P 05/24-P Smoke Detector 1st Corridor 1D104 46938604 1-M1-28 05/25-P 05/24-P Smoke Detector 1st Corridor @ Copy Rm 1D117 46938603 1-M1-27 05/25-P 05/24-P Smoke Detector 1st Corridor @ Mech Rm 1D102 46938601 1-M1-22 05/25-P 05/24-P Smoke Detector 1st Corridor @ Lounge 1D111 46938602 1-M1-26 05/25-P 05/24-P Smoke Detector 1st Elevator Rm 1D105 46938600 1-M1-21 05/25-P 05/24-P Smoke Detector 2nd Elevator Top Of Shaft 46938632 1-M1-88 05/25-P 05/25-P Smoke Detector 2nd Elevator Lobby 46938631 1-M1-87 05/25-P 05/25-P Smoke Detector 2nd Bed Rm 2D258 46938641 1-M1-101 05/25-P 05/24-P Smoke Detector 2nd Bed Rm 2D257 46938640 1-M1-100 05/25-P 05/24-P Smoke Detector 2nd Corridor @ Stair 1 46938642 1-M1-103 05/25-P 05/24-P Smoke Detector 2nd Bed Rm 2D252 46938637 1-M1-96 05/25-P 05/24-P Smoke Detector 2nd Corridor @ Lounge 2D253 46938639 1-M1-99 05/25-P 05/24-P Smoke Detector 2nd Corridor @ Bed Rm 2D252 46938638 1-M1-97 05/25-P 05/24-P Smoke Detector 2nd Bed Rm 2D244 46938635 1-M1-94 05/25-P 05/24-P Smoke Detector 2nd Bed Rm 2D245 46938636 1-M1-95 05/25-P 05/24-P Smoke Detector 2nd Elevator Lobby 46938633 1-M1-91 05/25-P 05/24-P Smoke Detector 2nd Corridor @ Bed Rm 2D244 46938634 1-M1-93 05/25-P 05/24-P Smoke Detector 2nd Comm Rm 2D241 46938630 1-M1-86 05/25-P 05/24-P Smoke Detector 2nd Bed Rm 2D222 46938623 1-M1-69 05/25-P 05/24-P Smoke Detector 2nd Bed Rm 2D223 46938622 1-M1-67 05/25-P 05/24-P Smoke Detector 2nd Corridor @ Stair 3 46938621 1-M1-66 05/25-P 05/24-P Smoke Detector 2nd Corridor @ Lounge 2D221 46938620 1-M1-65 05/25-P 05/24-P
Page of 9 22
Vets Fire & Life Safety Download Date: 06/20/2022
Device Type Location ScanID Address Q2/21 Q2/22 Smoke Detector 2nd Bed Rm 2D214 46938624 1-M1-70 05/25-P 05/24-P Smoke Detector 2nd Bed Rm 2D212 46938625 1-M1-71 05/25-P 05/24-P Smoke Detector 2nd Corridor @ Break Rm 2D212 46938619 1-M1-64 05/25-P 05/24-P Smoke Detector 2nd Bed Rm 2D213 46938618 1-M1-63 05/25-P 05/24-P Smoke Detector 2nd Bed Rm 2D208 46938626 1-M1-72 05/25-P 05/24-P Smoke Detector 2nd Corridor @ Break Rm 2D208 46938617 1-M1-62 05/25-P 05/24-P Smoke Detector 2nd Elect Rm 2D205 46938616 1-M1-61 05/25-P 05/24-P Smoke Detector 2nd Corridor @ Mech Rm 2D202 46938627 1-M1-74 05/25-P 05/24-P Smoke Detector 2nd Corridor @ Stair 2 46938628 1-M1-77 05/25-P 05/24-P Smoke Detector 2nd Corridor @ 2D2C1 West 46938629 1-M1-84 05/25-P 05/24-P Smoke Detector Ground Elevator Equipment Rm
G01 46938599 1-M1-10 05/25-P 05/25-P
Smoke Detector Ground Storage Rm G02 46938598 1-M1-08 05/25-P 05/24-P
Device Total: 45 Return to Executive Summary
Page of 10 22
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2019) Table 14.4.3.2 (22)
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-19 Table 14.4.3.2 (20)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Releasing Device 2 2 0 2 2
Device Type Location ScanID Address Q2/21 Q2/22 Releasing Device 1st Elevator Lobby 46938597 1 05/26-P 06/06-P Releasing Device 1st Elevator Lobby 46938596 1 05/26-P 06/06-P
Device Total: 2 Return to Executive Summary
Page of 11 22
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2019) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-19 Table 14.4.3.2 (22)(2)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Speaker/Strobe 26 26 0 26 26
Device Type Location ScanID Address Q2/21 Q2/22 Speaker/Strobe 1st Corridor @ Stair 3 46938559 1 05/26-P 06/06-P Speaker/Strobe 1st Corridor @ Nurse Station 46938557 1 05/26-P 06/06-P Speaker/Strobe 1st Corridor @ Stair 1 46938558 1 05/26-P 06/06-P Speaker/Strobe 1st Elevator Lobby 46938560 1 05/26-P 06/06-P Speaker/Strobe 1st Corridor @ 1D131 46938562 1 05/26-P 06/06-P Speaker/Strobe 1st Conference Rm 1D155 46938561 1 05/26-P 06/06-P Speaker/Strobe 1st Corridor @ Waiting Rm 1D103 46938563 1 05/26-P 06/06-P Speaker/Strobe 1st Corridor @ Reception 1D145 46938564 1 05/26-P 06/06-P Speaker/Strobe 1st Connector Corridor Bridge to
Bldg C 46938565 1 05/26-P 06/06-P
Speaker/Strobe 1st Mech Rm 1D102 46938566 1 05/26-P 06/06-P Speaker/Strobe 1st Corridor @ 1D108 46938567 1 05/26-F 06/06-P Speaker/Strobe 1st Group Rm 1D121 46938571 1 05/26-P 06/06-P Speaker/Strobe 1st Staff Lounge 1D111 46938568 1 05/26-F 06/06-P Speaker/Strobe 1st Corridor @ 1D110 46938569 1 05/26-F 06/06-P Speaker/Strobe 1st Corridor @ 1D119 46938570 1 05/26-F 06/06-P Speaker/Strobe 2nd Lounge 2D221 46938582 1 05/26-P 06/06-P Speaker/Strobe 2nd Corridor @ Lounge 2D253 46938580 1 05/26-P 06/06-P Speaker/Strobe 2nd Lounge 2D253 46938581 1 05/26-P 06/06-P Speaker/Strobe 2nd Corridor @ Stair 1 46938579 1 05/26-F 06/06-P Speaker/Strobe 2nd Corridor @ 2D252 46938578 1 05/26-P 06/06-P Speaker/Strobe 2nd Corridor @ 2D245 46938577 1 05/26-P 06/06-P Speaker/Strobe 2nd Corridor @ 2D217 46938572 1 05/26-F 06/06-P Speaker/Strobe 2nd Connector Corridor Bridge to
Bldg C 46938576 1 05/26-P 06/06-P
Speaker/Strobe 2nd Corridor @ Nurse Station 46938575 1 05/26-P 06/06-P Speaker/Strobe 2nd Corridor 2D202 46938574 1 05/26-F 06/06-P Speaker/Strobe 2nd Corridor @ 2D213 46938573 1 05/26-F 06/06-P
Device Total: 26 Return to Executive Summary
Page of 12 22
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2019) Table 14.4.3.2 (22)
For periodic testing, verify that each appliance flashes. (NFPA 72-19 Table 14.4.3.2 (22)(3)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Strobe 31 31 0 31 31
Device Type Location ScanID Address Q2/21 Q2/22 Strobe 1st Elect Rm 1D105 46938526 1 05/26-P 06/06-P Strobe 1st Staff Restroom 1D148 46938527 1 05/26-P 06/06-P Strobe 1st Staff Restroom 1D146 46938528 1 05/26-P 06/06-P Strobe 1st IT Restroom 1D141 46938529 1 05/26-P 06/06-P Strobe 1st Waiting Rm 1D103 46938530 1 05/26-P 06/06-P Strobe 1st Staff Restroom 1D106 46938531 1 05/26-P 06/06-P Strobe 1st Staff Restroom 1D108 46938532 1 05/26-P 06/06-P Strobe 2nd Rm 2D257 46938555 1 05/26-P 06/06-P Strobe 2nd Rm 2D258 46938556 1 05/26-P 06/06-P Strobe 2nd Rm 2D256 46938554 1 05/26-P 06/06-P Strobe 2nd Rm 2D254 46938552 1 05/26-P 06/06-P Strobe 2nd Rm 2D251 46938549 1 05/26-P 06/06-P Strobe 2nd Rm 2D252 46938550 1 05/26-P 06/06-P Strobe 2nd Rm 2D253 46938551 1 05/26-P 06/06-P Strobe 2nd Rm 2D255 46938553 1 05/26-P 06/06-P Strobe 2nd Rm 2D250 46938548 1 05/26-P 06/06-P Strobe 2nd Staff Restroom 2D215 46938535 1 05/26-P 06/06-P Strobe 2nd Laundry 2D225 46938533 1 05/26-P 06/06-P Strobe 2nd Rm 2D222 46938534 1 05/26-P 06/06-P Strobe 2nd Staff Restroom 2D207 46938536 1 05/26-P 06/06-P Strobe 2nd Rm 2D249 46938547 1 05/26-P 06/06-P Strobe 2nd Elect Rm 2D205 46938537 1 05/26-P 06/06-P Strobe 2nd Rm 2D247 46938545 1 05/26-P 06/06-P Strobe 2nd Rm 2D248 46938546 1 05/26-P 06/06-P Strobe 2nd Mech Rm 2D202 46938538 1 05/26-P 06/06-P Strobe 2nd Nurse station 46938539 1 05/26-P 06/06-P Strobe 2nd Rm 2D246 46938544 1 05/26-P 06/06-P Strobe 2nd Elevator Lobby 46938540 1 05/26-P 06/06-P Strobe 2nd Rm 2D245 46938543 1 05/26-P 06/06-P Strobe 2nd Laundry 2D259 46938542 1 05/26-P 06/06-P Strobe 2nd Telephone Rm 2D241 46938541 1 05/26-P 06/06-P
Device Total: 31 Return to Executive Summary
Page of 13 22
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment.
NFPA 90A (2021) 6.4.1
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Duct Detector 5 5 0 5 5
Device Type Location ScanID Address Q2/21 Q2/22 Duct Detector 1st Mech Rm 1D102 Supply 46938593 1-M1-104 05/25-P 05/24-P Duct Detector 1st Mech Rm 1D102 Return 46938592 1-M1-25 05/25-P 05/24-P Duct Detector 1st Mech Rm 1D102 Return 42020000 1-M1-24 05/25-P 05/24-P Duct Detector 2nd Mech Rm 2D202 Return 46938595 1-M1-106 05/25-P 05/24-P Duct Detector 2nd Mech Rm 2D202 Supply 46938594 1-M1-105 05/25-P 05/24-P
Device Total: 5 Return to Executive Summary
Page of 14 22
Vets Fire & Life Safety Download Date: 06/20/2022
LS 02.01.34 EP 02 Protected master fire alarm control panel
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-19 Table
14.4.3.2 (2)(1)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Control Panel 1 1 0 1 1
Device Type Location ScanID Address Q2/21 Q2/22 Control Panel 1st 46938643 1 05/25-P 06/06-P
Device Total: 1 Return to Executive Summary
Page of 15 22
Vets Fire & Life Safety Download Date: 06/20/2022
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-19 Table 14.4.3.2 (9)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Battery 6 6 0 6 6
Device Type Location ScanID Address Q2/21 Q2/22 Battery 1st 1D105 46938916 2 05/25-F 06/06-P Battery 1st 1D105 46938915 1 05/25-F 06/06-P Battery 2nd 2D205 2nd Set (105) 46938920 1 05/25-F 06/06-P Battery 2nd 2D205 2nd Set (105) 46938919 1 05/26-F 06/06-P Battery 2nd 2D205 46938918 1 05/25-F 06/06-P Battery 2nd 2D205 46938917 1 05/25-F 06/06-P
Device Total: 6 Return to Executive Summary
Page of 16 22
Vets Fire & Life Safety Download Date: 06/20/2022
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-19 Table
14.4.3.2 (2)(1)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Power Supply 2 2 0 2 2
Device Type Location ScanID Address Q2/21 Q2/22 Power Supply 1st Panel 106 46938644 1 05/25-P 06/06-P Power Supply 2nd Panel 105 46938645 1 05/25-P 06/06-P
Device Total: 2 Return to Executive Summary
Page of 17 22 Service Summary
Vets Fire & Life Safety Download Date: 06/20/2022
Service Summary Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 130 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Passed Battery Tested 6 Control Panel Tested 1 Duct Detector Tested 5 Heat Detector Tested 3 Power Supply Tested 2 Pull Station Tested 6 Releasing Device Tested 2 Smoke Detector Tested/Cleaned 45 Speaker/Strobe Tested 26 Strobe Tested 31
Total 127 Grand Total 127
Page of 18 22 Auxiliary Functions Testing
Vets Fire & Life Safety Download Date: 06/20/2022
Auxiliary Functions Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Control Panel: 1 -
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed Releasing Device
Door Holder 1st Elevator Lobby Passed 46938596 Door Holder 1st Elevator Lobby Passed 46938597
Duct Detector Fan Shut Down 1st Mech Rm 1D102 Return Passed 42020000 Fan Shut Down 1st Mech Rm 1D102 Return Passed 46938592 Fan Shut Down 1st Mech Rm 1D102 Supply Passed 46938593 Fan Shut Down 2nd Mech Rm 2D202 Return Passed 46938595 Fan Shut Down 2nd Mech Rm 2D202 Supply Passed 46938594
Smoke Detector Elevator Recall 1st Elevator Lobby Passed 46938610 Elevator Recall 2nd Elevator Lobby Passed 46938633 Elevator Recall 2nd Elevator Lobby Passed 46938631 Elevator Recall 2nd Elevator Top Of Shaft Passed 46938632 Elevator Recall Ground Elevator Equipment Rm G01 Passed 46938599
Heat Detector Shunt Trip 2nd Elevator Top Of Shaft Passed 46938591 Shunt Trip Ground Elevator Equipment Rm G01 Passed 46938590 Shunt Trip Ground Elevator Pit Passed 46938589
Smoke Detector Elevator Recall 1st Elevator Lobby Passed 46938611 Elevator Recall 1st Elevator Rm 1D105 Passed 46938600 javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938596');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938597');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','42020000');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938592');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938593');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938595');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938594');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938610');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938633');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938631');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938632');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938599');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938591');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938590');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938589');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938611');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938600');
Page of 19 22 Battery & Power Supply Testing
Vets Fire & Life Safety Download Date: 06/20/2022
Battery & Power Supply Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Control Panel: 1 -
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location Rated Ah
Rated Volts Pre Test
Post Test Min Ah Tested Ah
Battery
Passed Sealed Lead Acid 1st 1D105 55 12 13.88 50 Sealed Lead Acid 2nd 2D205 7 12 12.49 7 Sealed Lead Acid 2nd 2D205 7 12 12.44 6.4 Sealed Lead Acid 2nd 2D205 2nd Set (105) 7 12 12.69 7 Sealed Lead Acid 2nd 2D205 2nd Set (105) 7 12 12.84 7
Building: Fort McPherson VAMC Bldg
Control Panel: 2
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location Rated Ah
Rated Volts Pre Test
Post Test Min Ah Tested Ah
Battery
Passed Sealed Lead Acid 1st 1D105 55 12 13.55 48
Page of 20 22 Inventory & Warranty Report
Vets Fire & Life Safety Download Date: 06/20/2022
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Control Panel: 1 -
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Battery Control 4.72% 6
Control Panel Control 0.79% 1
Duct Detector Initiating 3.94% 5
Heat Detector Initiating 2.36% 3
Power Supply Control 1.57% 2
Pull Station Initiating 4.72% 6
Releasing Device Auxiliary 1.57% 2
Smoke Detector Initiating 35.43% 45
Speaker/Strobe Indicating 20.47% 26
Strobe Indicating 24.41% 31
Type Qty Model # Description Install Date
In Service - 3 Years to 5 Years Battery 5 Sealed Lead Acid 05/23/2018 Control Panel 1 05/23/2018 Duct Detector 5 Photoelectric 05/23/2018 Heat Detector 3 05/23/2018 Power Supply 2 05/23/2018 Pull Station 6 Dual Action 05/23/2018 Releasing Device 2 Door Holder 05/23/2018 Smoke Detector 45 Photoelectric 05/23/2018 Speaker/Strobe 26 05/23/2018 Strobe 31 05/23/2018
Building: Fort McPherson VAMC Bldg
Control Panel: 2
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Type Qty Model # Description Install Date
In Service - 3 Years to 5 Years Battery 1 Sealed Lead Acid 05/23/2018
Page of 21 22 Zone Address Report
Vets Fire & Life Safety Download Date: 06/20/2022
Zone Address Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Control Panel: 1 -
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID M1-08 Smoke Detector Ground Storage Rm G02 Photoelectric 46938598 M1-9 Heat Detector Ground Elevator Pit 46938589 M1-10 Smoke Detector Ground Elevator Equipment Rm G01 Photoelectric 46938599 M1-11 Heat Detector Ground Elevator Equipment Rm G01 46938590 M1-21 Smoke Detector 1st Elevator Rm 1D105 Photoelectric 46938600 M1-22 Smoke Detector 1st Corridor @ Mech Rm 1D102 Photoelectric 46938601 M1-24 Duct Detector 1st Mech Rm 1D102 Return Photoelectric 42020000 M1-25 Duct Detector 1st Mech Rm 1D102 Return Photoelectric 46938592 M1-26 Smoke Detector 1st Corridor @ Lounge 1D111 Photoelectric 46938602 M1-27 Smoke Detector 1st Corridor @ Copy Rm 1D117 Photoelectric 46938603 M1-28 Smoke Detector 1st Corridor 1D104 Photoelectric 46938604 M1-29 Smoke Detector 1st Corridor @ Stair 3 Photoelectric 46938605 M1-30 Pull Station 1st Stair 3 Exit Dual Action 46938583 M1-31 Smoke Detector 1st Corridor @ Stair 2 Photoelectric 46938606 M1-32 Pull Station 1st Stair 2 Exit Dual Action 46938584 M1-35 Smoke Detector 1st Corridor 1D141 Photoelectric 46938607 M1-37 Smoke Detector 1st Interset Corridor West Photoelectric 46938608 M1-38 Smoke Detector 1st Comm Rm 1D141 Photoelectric 46938609 M1-39 Smoke Detector 1st Elevator Lobby Photoelectric 46938610 M1-41 Smoke Detector 1st Elevator Lobby Photoelectric 46938611 M1-43 Smoke Detector 1st Corridor by Reception 1D101 Photoelectric 46938612 M1-44 Smoke Detector 1st Corridor @ Office 1D152 Photoelectric 46938613 M1-45 Smoke Detector 1st Corridor @ Large Group Rm 1D151 Photoelectric 46938614 M1-46 Smoke Detector 1st Corridor @ Stair 1 Photoelectric 46938615 M1-47 Pull Station 1st Stair 1 Exit Dual Action 46938585 M1-61 Smoke Detector 2nd Elect Rm 2D205 Photoelectric 46938616 M1-62 Smoke Detector 2nd Corridor @ Break Rm 2D208 Photoelectric 46938617 M1-63 Smoke Detector 2nd Bed Rm 2D213 Photoelectric 46938618 M1-64 Smoke Detector 2nd Corridor @ Break Rm 2D212 Photoelectric 46938619 M1-65 Smoke Detector 2nd Corridor @ Lounge 2D221 Photoelectric 46938620 M1-66 Smoke Detector 2nd Corridor @ Stair 3 Photoelectric 46938621 M1-67 Smoke Detector 2nd Bed Rm 2D223 Photoelectric 46938622 M1-68 Pull Station 2nd Stair 3 Exit Dual Action 46938586 M1-69 Smoke Detector 2nd Bed Rm 2D222 Photoelectric 46938623 javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938598');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938589');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938599');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938590');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938600');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938601');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','42020000');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938592');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938602');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938603');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938604');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938605');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938583');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938606');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938584');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938607');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938608');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938609');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938610');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938611');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938612');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938613');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938614');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938615');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938585');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938616');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938617');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938618');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938619');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938620');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938621');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938622');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938586');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938623');
Page of 22 22 Zone Address Report
Vets Fire & Life Safety Download Date: 06/20/2022
Address Device Type Location Type ScanID M1-70 Smoke Detector 2nd Bed Rm 2D214 Photoelectric 46938624 M1-71 Smoke Detector 2nd Bed Rm 2D212 Photoelectric 46938625 M1-72 Smoke Detector 2nd Bed Rm 2D208 Photoelectric 46938626 M1-74 Smoke Detector 2nd Corridor @ Mech Rm 2D202 Photoelectric 46938627 M1-77 Smoke Detector 2nd Corridor @ Stair 2 Photoelectric 46938628 M1-78 Pull Station 2nd Stair 2 Exit Dual Action 46938587 M1-84 Smoke Detector 2nd Corridor @ 2D2C1 West Photoelectric 46938629 M1-86 Smoke Detector 2nd Comm Rm 2D241 Photoelectric 46938630 M1-87 Smoke Detector 2nd Elevator Lobby Photoelectric 46938631 M1-88 Smoke Detector 2nd Elevator Top Of Shaft Photoelectric 46938632 M1-89 Heat Detector 2nd Elevator Top Of Shaft 46938591 M1-91 Smoke Detector 2nd Elevator Lobby Photoelectric 46938633 M1-93 Smoke Detector 2nd Corridor @ Bed Rm 2D244 Photoelectric 46938634 M1-94 Smoke Detector 2nd Bed Rm 2D244 Photoelectric 46938635 M1-95 Smoke Detector 2nd Bed Rm 2D245 Photoelectric 46938636 M1-96 Smoke Detector 2nd Bed Rm 2D252 Photoelectric 46938637 M1-97 Smoke Detector 2nd Corridor @ Bed Rm 2D252 Photoelectric 46938638 M1-99 Smoke Detector 2nd Corridor @ Lounge 2D253 Photoelectric 46938639
M1-100 Smoke Detector 2nd Bed Rm 2D257 Photoelectric 46938640 M1-101 Smoke Detector 2nd Bed Rm 2D258 Photoelectric 46938641 M1-102 Pull Station 2nd Stair 1 Exit Dual Action 46938588 M1-103 Smoke Detector 2nd Corridor @ Stair 1 Photoelectric 46938642 M1-104 Duct Detector 1st Mech Rm 1D102 Supply Photoelectric 46938593 M1-105 Duct Detector 2nd Mech Rm 2D202 Supply Photoelectric 46938594 M1-106 Duct Detector 2nd Mech Rm 2D202 Return Photoelectric 46938595 javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938624');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938625');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938626');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938627');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938628');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938587');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938629');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938630');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938631');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938632');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938591');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938633');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938634');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938635');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938636');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938637');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938638');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938639');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938640');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938641');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938588');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938642');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938593');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938594');
javascript:openEditDevice('load-edit-f2-device','736896','3032788','46938595');
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate