This document provides details of a federal solicitation for fire sprinkler testing services. The solicitation number is 36C24724Q0269 and is seeking these services for the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 7. Offerors are to provide inspection, testing, and maintenance of fire sprinkler systems in accordance with NFPA standards and The Joint Commission requirements. The period of performance and response date are not specified. Pricing terms and whether there are any set-aside provisions are also not stated.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sprinkler Inspection, Testing and/or Maintenance Certificate
For
Fort McPherson VAMC Bldg 125 1701 Hardee Ave SW
Atlanta, GA 30310 Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards effective January 31, 2021
Annual Inspection Inspection Completion Date May 18, 2023
Building: Fort McPherson VAMC Bldg 125 Company: United Fire Protection - Atlanta Contact: Mike McGill Contact: Wayne Huxtable
Title: Maintenance & Operations Supervisor Title: Technician
Page of 1 27United Fire Protection - Atlanta Download Date: 05/20/2023
Executive Summary Generated by: BuildingReports.com
Building Information Building: Fort McPherson VAMC Bldg 125 Contact: Mike McGill
Address: 1701 Hardee Ave SW Phone: 404-321-6111
Address: Fax:
City/State/ZIP Code: Atlanta, GA 30310 Mobile:
Country: United States of America Email:
Inspection Performed By Company: United Fire Protection - Atlanta Inspector: Wayne Huxtable
Address: 2150 Boggs Rd Bldg 100 Phone: 770-771-0999
Address: Suite 140 Fax:
City/State/ZIP Code: Duluth, GA 30096 Mobile:
Country: United States of America Email: whuxtable@united-fire.com
Page of 2 27United Fire Protection - Atlanta Download Date: 05/20/2023
Inspection Completion Date: May 18, 2023 Building: Fort McPherson VAMC Bldg 125 EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019)
Table 14.4.3.2 (17)(10)(a) & (17)(11)
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Tamper Switch 8 8 0 8 0 8
Waterflow Switch 6 6 0 6 0 6
EC 02.03.05 EP 11 For automatic sprinkler systems: Every 12 months, the hospital tests fire pumps under flow. Fire pump supervisory signals for pump running and pump power loss are tested annually. NFPA 25 (2020) 8.3.3
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Jockey Controller 1 1 0 1 0 1
Pump 1 0 1 1 0 1
LS 02.01.35 EP 14 All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Check Valve 4 4 0 4 0 4
Control Valve 19 19 0 19 0 19
Gauge 6 6 0 6 0 6
Inspector's Test 3 2 1 3 0 3
Total Device Count: 48
Page of 3 27United Fire Protection - Atlanta Download Date: 05/20/2023
Certification
Company: United Fire Protection - Atlanta Building: Fort McPherson VAMC Bldg 125
Inspector: Wayne Huxtable Contact: Mike McGill
Page of 4 27United Fire Protection - Atlanta Download Date: 05/20/2023
Discrepancy Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 125 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer’s replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Reference
Wet Pipe Inspector's Test
2 44133448
Basement Stairwell B Damaged/Worn NFPA25 13.2.1
Code References NFPA25 13.2.1 All system valves shall be protected from physical damage and shall be accessible.
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133448');
Page of 5 27United Fire Protection - Atlanta Download Date: 05/20/2023
Proposed Solutions Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 125 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
Wet Pipe Inspector's Test
44133448 Basement Stairwell B Repair 9624 T/M
PO #: (none) T/M
Page of 6 27United Fire Protection - Atlanta Download Date: 05/20/2023
Inspection & Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 125 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Tamper Switch 8 8 0 8 8
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Tamper Switch Basement Pump Room
Backflow CV1 67977776 1-M4-98 08/15-P 10/28-P 02/09-P 05/17-P
Tamper Switch Basement Pump Room Backflow CV2
67977774 1-M4-99 08/15-P 10/28-P 02/09-P 05/17-P
Tamper Switch Basement Pump Room Backflow CV2
67977775 1-M4-99 08/15-P 10/28-P 02/09-P 05/17-P
Tamper Switch Basement Pump Room Backflow CV2
67977845 1-M4-99 08/15-P 10/28-P 02/09-P 05/17-P
Tamper Switch Basement Pump Room Fire Pump Discharge
67977772 1-M4-103 08/15-P 10/28-P 02/09-P 05/17-P
Tamper Switch Basement Stairwell B 67977867 1-M4-89 08/15-P 10/28-P 02/09-P 05/17-P Tamper Switch 1st Stairwell B 44133443 1-M2-22 05/17-P Tamper Switch 2nd Mechanical Room 67977844 1-M3-63 08/15-P 10/28-P 02/09-P 05/17-P
Device Total: 8 Return to Executive Summary
Page of 7 27United Fire Protection - Atlanta Download Date: 05/20/2023
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-19 Table
14.4.3.2 (17)(11)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Waterflow Switch 6 6 0 6 6
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Waterflow Switch Basement Stairwell B 44133447 1-M4-88 08/15-P 10/28-P 02/09-P 05/17-P Waterflow Switch 1st Stairwell B 57780003 1-M2-22 08/15-P 10/28-P 02/09-P 05/17-P Waterflow Switch 1st Stairwell B 57780004 1-M2-21 08/15-P 10/28-P 02/09-P 05/17-P Waterflow Switch 2nd Mechanical Room 5778J04 1-M3-64 08/15-P 10/28-P 02/09-P 05/17-P Waterflow Switch 2nd Mechanical Room
Freight Elevator Shaft Flowswitch
44133439 1-7-4 08/15-P 10/28-P 02/09-P 05/17-P
Waterflow Switch 2nd Mechanical Room Passenger Elevator Shaft Flowswitch
44133441 1-7-2 08/15-P 10/28-P 02/09-P 05/17-P
Device Total: 6 Return to Executive Summary
Page of 8 27United Fire Protection - Atlanta Download Date: 05/20/2023
EC 02.03.05 EP 11
For automatic sprinkler systems: Every 12 months, the hospital tests fire pumps under flow. Fire pump supervisory signals for pump running and pump power loss are tested annually. NFPA 25 (2020) 8.3.3
The purpose of inspection shall be to verify that the pump assembly appears to be in operating condition and is free from physical damage. The pump performance shall be evaluated using the unadjusted flow rates and pressures to ensure the pump can supply the system demand as supplied by the owner. (NFPA 25-20 8.2.1) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Jockey Controller 1 1 0 1 1
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Jockey Controller Basement Pump Room
Discharge Check 67978998 0 05/17-P
Device Total: 1 Return to Executive Summary
Page of 9 27United Fire Protection - Atlanta Download Date: 05/20/2023
EC 02.03.05 EP 11
For automatic sprinkler systems: Every 12 months, the hospital tests fire pumps under flow. Fire pump supervisory signals for pump running and pump power loss are tested annually. NFPA 25 (2020) 8.3.3
An annual test of each constant speed pump assembly shall be conducted by qualified personnel under no-flow (churn), rated flow, and 150 percent of the pump rated capacity flow of the fire pump by controlling the quantity of water discharged through approved test devices. Parallel and angular alignment of the pump and driver shall be inspected during the annual test and any misalignment shall be corrected. (NFPA 25-20 8.3.3.1; 8.3.6.4) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Pump 1 0 1 1 1
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Pump Basement Mechanical room 67977767 0 08/15-P 10/28-P 02/09-P 04/05-F
Device Total: 1 Return to Executive Summary
Page of 10 27United Fire Protection - Atlanta Download Date: 05/20/2023
LS 02.01.35 EP 14
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Internal components shall be cleaned, repaired, or replaced as necessary in accordance with the manufacturer's instructions. (NFPA 25-20 13.4.2.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Check Valve 4 4 0 4 4
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Check Valve Basement Pump Room City
Bypass Check 44133420 1 08/15-P 10/28-P 05/17-P
Check Valve Basement Pump Room Discharge Check
44133415 1 08/15-P 10/28-P 05/17-P
Check Valve Basement Pump Room Discharge Check
67978999 1 05/17-P
Check Valve Basement Pump Room Jockey pump
44133428 1-M4-100 08/15-P 10/28-P 05/17-P
Device Total: 4 Return to Executive Summary
Page of 11 27United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Control Valve 19 19 0 19 19
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Control Valve Basement Pump Room
Backflow CV1 44133423 1-M4-98 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve Basement Pump Room Backflow CV2
44133424 1-M4-99 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve Basement Pump Room City Bypass CV1
44133419 1-M4-100 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve Basement Pump Room City Bypass CV2
44133421 1-M4-101 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve Basement Pump Room Discharge Check
67979000 1 05/17-P
Control Valve Basement Pump Room Discharge Check
67979001 1 05/17-P
Control Valve Basement Pump Room Fire Pump Discharge
44133416 1-M4-103 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve Basement Pump Room Fire Pump Suction
44133412 1-M3-102 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve Basement Pump Room Flow Meter CV1
44133417 1 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve Basement Pump Room Flow Meter CV2
44133418 1-M4-103 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve Basement Pump Room Jockey pump
44133426 1-M4-100 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve Basement Pump Room Jockey pump
44133425 1-M4-100 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve Basement Pump Room Test Header
44133422 1 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve Basement Stairwell B 44133446 1-M4-89 08/15-P 10/28-P 02/09-P 05/17-P Control Valve 1st Stairwell B 44133442 1-M2-22 08/15-P 10/28-P 02/09-P 05/17-P Control Valve 2nd Mechanical Room 44133434 1-M3-63 08/15-P 10/28-P 02/09-P 05/17-P Control Valve 2nd Mechanical Room 4413364 1 02/09-P 05/17-P Control Valve 2nd Mechanical Room
Freight Elevator Shaft CV 44133438 1-7-3 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve 2nd Mechanical Room Passenger Elevator Shaft CV
44133440 1-7-1 08/15-P 10/28-P 02/09-P 05/17-P
Device Total: 19 Return to Executive Summary
Page of 12 27United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. (NFPA 25- 20 13.2.5.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Gauge 6 6 0 6 6
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Gauge Basement Pump Room
Discharge 67977769 0 08/15-P 10/28-P 05/17-P
Gauge Basement Pump Room Discharge Check
67977770 0 05/17-P
Gauge Basement Pump Room Suction
67977768 0 08/15-P 10/28-P 05/17-P
Gauge Basement Stairwell B 57780001 0 08/15-P 10/28-P 05/17-P Gauge 1st Stairwell B 57780002 0 08/15-P 10/28-P 05/17-P Gauge 2nd Mechanical Room 57780005 0 08/15-P 10/28-P 05/17-P
Device Total: 6 Return to Executive Summary
Page of 13 27United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Testing of pressure switch type waterflow alarm devices on wet pipe systems shall be accomplished by opening the inspector's test connection (NFPA 25-20 5.3.3.3) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Inspector's Test 3 2 1 3 3
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Inspector's Test Basement Stairwell B 44133448 0 08/15-P 10/28-P 02/09-P 05/18-F Inspector's Test 1st Stairwell B 44133445 0 08/15-P 10/28-P 02/09-P 05/17-P Inspector's Test 2nd Mechanical Room 44133437 0 08/15-P 10/28-P 02/09-P 05/17-P
Device Total: 3 Return to Executive Summary
Page of 14 27United Fire Protection - Atlanta Download Date: 05/20/2023
Service Summary Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 125 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Failed/Other Inspector's Test Annual 1
Total 1
Passed Check Valve Annual 4 Control Valve Annual 19 Gauge Annual 6 Inspector's Test Annual 2 Jockey Controller Annual 1 Tamper Switch Annual 8 Waterflow Switch Annual 6
Total 46
Untested Pump 1
Total 1 Grand Total 48
Page of 15 27United Fire Protection - Atlanta Download Date: 05/20/2023
Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
OS&Y Supervisory Basement Stairwell B 4 1-M4-89 67977867 OS&Y Supervisory 1st Stairwell B 1-M2-22 44133443
Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR-F 4" 1-M4-88 44133447 Vane Potter Electric VSR 30 4” 1-M2-22 57780003 Vane Potter Electric VSR-F 30 4" 1-M2-21 57780004 Vane Potter Electric VS-SP 31.45000 1" 1-7-2 44133441 Vane Potter Electric VS-SP 30.53000 1" 1-7-4 44133439
Components Control Valve
Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H Basement Stairwell B
4" Open Supervised 44133446
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID OS&Y Stockham 525H 1st Stairwell B 4" Open Supervised 44133442
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Nibco KT-505W-8
2nd Mechanical Room Freight Elevator Shaft
CV
1" Open Supervised 44133438 javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977867');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133443');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133447');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','57780003');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','57780004');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133441');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133439');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133446');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133442');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133438');
Page of 16 27United Fire Protection - Atlanta Download Date: 05/20/2023
Description Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Nibco KT-505W-8
2nd Mechanical Room Passenger Elevator Shaft
CV
1.25" Open Supervised 44133440
Description Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 9624 2nd Mechanical Room
4" Open Supervised 4413364
Description Main Control
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 9624 1150 30 44133445
Location 1st Stairwell B
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 9624 140 30.43000 44133437
Location 2nd Mechanical Room
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 9624 1150 30 44133448
Location Basement Stairwell B
Devices Gauge
Location Service Date Basement Stairwell B 03/28/2013
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Ashcroft Ashcroft 165 Air/Water 1/4 57780001 javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133440');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','4413364');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133445');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133437');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133448');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','57780001');
Page of 17 27United Fire Protection - Atlanta Download Date: 05/20/2023
Gauge Location Service Date 1st Stairwell B 03/28/2025
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 150 Air/Water 1/4 57780002 javascript:openEditDevice('load-edit-p2-device','736893','2902392','57780002');
Page of 18 27United Fire Protection - Atlanta Download Date: 05/20/2023
Fire Pump Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Jockey Controller Manufacturer Model # Location Install Date Serial Number Hubbell Basement Pump Room Discharge Check 03/28/2013 AC Power Time Meter Start psi Stop psi Battery Supervised Generator Backup Normal Phase 150 160 No No
Alarms Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
OS&Y Supervisory Basement Pump Room Backflow
CV2
1-M4-99 67977774
OS&Y Supervisory Basement Pump Room Backflow
CV1
1-M4-98 67977776
OS&Y Supervisory Basement Pump Room Backflow
CV2
1-M4-99 67977775
OS&Y Supervisory Basement Pump Room Backflow
CV2
1-M4-99 67977845
OS&Y Supervisory Basement Pump Room Fire Pump Discharge
1-M4-103 67977772
OS&Y Supervisory 2nd Mechanical Room 1-M3-63 67977844
Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR-F 30 4" 1-M3-64 5778J04
Components Check Valve
Type Location Internal Date Size OK ScanID
Flanged Basement Pump Room City Bypass Check
03/28/1996 8" 44133420
Flanged Basement Pump Room Discharge Check
03/28/2018 6" 44133415
Threaded Basement Pump Room Discharge Check
03/28/2018 1.5" 67978999 javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977774');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977776');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977775');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977845');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977772');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977844');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','5778J04');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133420');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133415');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67978999');
Page of 19 27United Fire Protection - Atlanta Download Date: 05/20/2023
Flanged Basement Pump Room Jockey pump 03/28/2018 8" 44133428
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H
Basement Pump Room Flow Meter
CV1
6" Closed Sealed 44133417
Description Suction
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H
Basement Pump Room City Bypass
CV1
6" Open Supervised 44133419
Description Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H Basement Pump Room Backflow CV1
8" Open Supervised 44133423
Description Backflow CV1
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H Basement Pump Room Backflow CV2
8" Open Supervised 44133424
Description Backflow CV1
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H
Basement Pump Room Fire Pump Suction
8" Open Supervised 44133412
Description Suction
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Basement javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133428');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133417');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133419');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133423');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133424');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133412');
Page of 20 27United Fire Protection - Atlanta Download Date: 05/20/2023
OS&Y Stockham 525H Pump Room Flow Meter
CV2
6" Open Supervised 44133418
Description Suction
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H
Basement Pump Room Fire Pump Discharge
8" Open Supervised 44133416
Description Suction
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 106-6
Basement Pump Room Discharge Check
2" Open Sealed 67979000
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 106-6
Basement Pump Room Discharge Check
2" Open Sealed 67979001
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H Basement Pump Room Jockey pump
1.5" Open Supervised 44133426
Description Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H Basement Pump Room Jockey pump
1.5" Open Supervised 44133425
Description javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133418');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133416');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67979000');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67979001');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133426');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133425');
Page of 21 27United Fire Protection - Atlanta Download Date: 05/20/2023
Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H Basement Pump Room Test Header
6" Open Supervised 44133422
Description Test Header
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H
Basement Pump Room City Bypass
CV2
8" Open Supervised 44133421
Description Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Stockham 525H 2nd Mechanical Room
4" Open Supervised 44133434
Description Main Control
Devices Gauge
Location Service Date Basement Pump Room Suction 03/28/2025
Type Manufacturer Model # Static psi Fill Type Size OK ScanID City Pressure Lansdale 150 Air/Water 1/4 67977768
Gauge Location Service Date Basement Pump Room Discharge 03/28/2025
Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Ashcroft Ashcroft 150 Air/Water 1/4 67977769
Gauge Location Service Date Basement Pump Room Discharge Check 03/28/2028
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Hubbell 170 Air/Water 1/4 67977770
Gauge javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133422');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133421');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133434');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977768');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977769');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977770');
Page of 22 27United Fire Protection - Atlanta Download Date: 05/20/2023
Location Service Date 2nd Mechanical Room 05/27/2025
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 150 Air/Water 1/4 57780005
Building: Fort McPherson VAMC Bldg
BLDG 125
This section lists out all the devices and components that have been associated with a Fire Pump and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Pump Manufacturer Model Number Location Install Date ScanID
Patterson 750 Gpm 3551 Rpm
Basement Mechanical room 05/30/1994 67977767
Serial Number Type Orientation Aligned? Water Supply Impeller Size FP-C6183ex Pump Primary Horizontal 8.063
Fire Pump Rating Amps Volts Net Pressure Gallons Per Minute Rotations Per Minute A B C A-B B-C A-C 95 750 3542 javascript:openEditDevice('load-edit-p2-device','736893','2902392','57780005');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977767');
Page of 23 27United Fire Protection - Atlanta Download Date: 05/20/2023
Page of 24 27United Fire Protection - Atlanta Download Date: 05/20/2023
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 125 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Check Valve Valve 8.33% 4
Control Valve Valve 39.58% 19
Gauge Device 12.50% 6
Inspector's Test Valve 6.25% 3
Jockey Controller Pump 2.08% 1
Pump Pump 2.08% 1
Tamper Switch Alarm 16.67% 8
Waterflow Switch Alarm 12.50% 6
Device Type Qty Model # Type Description Install Date
New (under 90 days) Fire Pump
Gauge 1 System Pressure 03/28/2023
In Service - 1 Year to 2 Years Fire Pump
Gauge 1 Ashcroft Supply Pressure 05/27/2021 Gauge 1 City Pressure 05/27/2021 Gauge 1 System Pressure 05/27/2021
Wet Pipe Gauge 1 System Pressure 05/27/2021
In Service - 3 Years to 5 Years Wet Pipe
Waterflow Switch 1 VS-SP Vane Alarm 07/11/2018
In Service - 10 Years to 15 Years Fire Pump
Jockey Controller 1 03/28/2013 Check Valve 1 Threaded 03/28/2013 Check Valve 1 106-6 Flanged 03/28/2013 Control Valve 2 106-6 OS&Y Main Control 03/28/2013
Wet Pipe Gauge 1 Ashcroft System Pressure 03/28/2013
In Service - 25 Years or Older
Page of 25 27United Fire Protection - Atlanta Download Date: 05/20/2023
Fire Pump Check Valve 1 106-6 Flanged 03/28/1996
BLDG 125 Fire Pump Pump 1 750 Gpm 3551 Rpm Pump Primary 05/30/1994
Fire Pump Tamper Switch 1 OSYSU-2 OS&Y Supervisory 03/28/1994 Tamper Switch 1 OSYSU-3 OS&Y Supervisory 03/28/1994 Waterflow Switch 1 VSR-F Vane Alarm 03/28/1994 Tamper Switch 4 OSYSU-2 OS&Y Supervisory 03/28/1994 Check Valve 1 525H Flanged 03/28/1994 Control Valve 2 525H OS&Y Backflow CV1 03/28/1994 Control Valve 4 525H OS&Y Isolation 03/28/1994 Control Valve 1 525H OS&Y Main Control 03/28/1994 Control Valve 4 525H OS&Y Suction 03/28/1994 Control Valve 1 525H OS&Y Test Header 03/28/1994
Wet Pipe Inspector's Test 3 9624 03/28/1994 Control Valve 2 KT-505W-8 Butterfly Isolation 03/28/1994 Tamper Switch 1 OSYSU-2 OS&Y Supervisory 03/28/1994 Tamper Switch 1 VSR OS&Y Supervisory 03/28/1994 Waterflow Switch 1 VS-SP Vane Alarm 03/28/1994 Waterflow Switch 1 VSR Vane Alarm 03/28/1994 Waterflow Switch 2 VSR-F Vane Alarm 03/28/1994 Control Valve 2 525H OS&Y Main Control 03/28/1994 Control Valve 1 9624 OS&Y Main Control 03/28/1994
Page of 26 27United Fire Protection - Atlanta Download Date: 05/20/2023
Zone Address Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 125 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
Control Panel 1 7-1 Control Valve 2nd Mechanical Room Passenger Elevator
Shaft CV Butterfly 44133440
7-2 Waterflow Switch 2nd Mechanical Room Passenger Elevator Shaft Flowswitch
Vane 44133441
7-3 Control Valve 2nd Mechanical Room Freight Elevator Shaft CV
Butterfly 44133438
7-4 Waterflow Switch 2nd Mechanical Room Freight Elevator Shaft Flowswitch
Vane 44133439
M2-21 Waterflow Switch 1st Stairwell B Vane 57780004 M2-22 Control Valve 1st Stairwell B OS&Y 44133442 M2-22 Tamper Switch 1st Stairwell B OS&Y 44133443 M2-22 Waterflow Switch 1st Stairwell B Vane 57780003 M3-63 Control Valve 2nd Mechanical Room OS&Y 44133434 M3-63 Tamper Switch 2nd Mechanical Room OS&Y 67977844 M3-64 Waterflow Switch 2nd Mechanical Room Vane 5778J04
M3-102 Control Valve Basement Pump Room Fire Pump Suction OS&Y 44133412 M4-88 Waterflow Switch Basement Stairwell B Vane 44133447 M4-89 Control Valve Basement Stairwell B OS&Y 44133446 M4-89 Tamper Switch Basement Stairwell B OS&Y 67977867 M4-98 Control Valve Basement Pump Room Backflow CV1 OS&Y 44133423 M4-98 Tamper Switch Basement Pump Room Backflow CV1 OS&Y 67977776 M4-99 Control Valve Basement Pump Room Backflow CV2 OS&Y 44133424 M4-99 Tamper Switch Basement Pump Room Backflow CV2 OS&Y 67977774 M4-99 Tamper Switch Basement Pump Room Backflow CV2 OS&Y 67977775 M4-99 Tamper Switch Basement Pump Room Backflow CV2 OS&Y 67977845
M4-100 Control Valve Basement Pump Room City Bypass CV1 OS&Y 44133419 M4-100 Control Valve Basement Pump Room Jockey pump OS&Y 44133425 M4-100 Control Valve Basement Pump Room Jockey pump OS&Y 44133426 M4-101 Control Valve Basement Pump Room City Bypass CV2 OS&Y 44133421 M4-103 Control Valve Basement Pump Room Fire Pump
Discharge
OS&Y 44133416
M4-103 Tamper Switch Basement Pump Room Fire Pump Discharge
OS&Y 67977772
M4-103 Control Valve Basement Pump Room Flow Meter CV2 OS&Y 44133418 javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133440');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133441');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133438');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133439');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','57780004');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133442');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133443');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','57780003');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133434');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977844');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','5778J04');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133412');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133447');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133446');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977867');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133423');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977776');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133424');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977774');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977775');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977845');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133419');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133425');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133426');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133421');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133416');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','67977772');
javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133418');
Page of 27 27United Fire Protection - Atlanta Download Date: 05/20/2023
Notes & Recommendations Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 125 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by SystemID.
Note Device Type Location Comment ScanID Wet Pipe
1 Inspector's Test Basement Stairwell B Damaged/Worn 44133448 05/17/2023: Inspected test drain leaking require a 1” x 4” nipple steel pipe javascript:openEditDevice('load-edit-p2-device','736893','2902392','44133448');
| Sprinkler Inspection, Testing and/or Maintenance Certificate |
| Executive Summary |
| Discrepancy Report |
| Proposed Solutions Report |
| Inspection & Testing |
| Service Summary |
| Wet Pipe Fire Sprinkler Systems |
| Fire Pump Testing |
| Inventory & Warranty Report |
| Zone Address Report |
| Notes & Recommendations |