2023-05-18_Fort-McPherson-VAMC-Bldg-128_SprinklerScan.pdf
PDF 311 KB Posted
- Attached to
- Fire Sprinkler Testing
- Solicitation number
- 36C24724Q0269
About this file
This document summarizes a fire sprinkler system inspection report for Building 128 at the Fort McPherson VA Medical Center in Atlanta, Georgia. The report was prepared by United Fire Protection - Atlanta and documents inspection and testing of the wet pipe sprinkler system performed on May 18, 2023. A total of 37 devices across the building were inspected, including water flow switches, control valves, gauges, drains and inspector's test connections. All devices tested passed inspection. The report provides details on the locations and results of semi-annual water flow alarm and valve tamper switch tests, annual main drain tests, quarterly fire department connection inspections and other Life Safety Code requirements. Inventory and warranty information is included along with a zone address report cross-referencing device addresses and locations.
This opportunity appears to be for ongoing fire sprinkler system inspection, testing and maintenance services for Building 128 at the Fort McPherson VAMC. The solicitation number is 36C24724Q0269 and was issued by the Department of Veterans Affairs Veterans Health Administration VISN 7. Pricing, response date and other contractual details are not provided in the attached documents.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sprinkler Inspection, Testing and/or Maintenance Certificate
For
Fort McPherson VAMC Bldg 128 1701 Hardee Ave SW
Atlanta, GA 30310 Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards effective January 31, 2021
Inspection Completion Date May 18, 2023
Building: Fort McPherson VAMC Bldg 128 Company: United Fire Protection - Atlanta Contact: Mike McGill Contact: Wayne Huxtable
Title: Maintenance & Operations Supervisor Title: Technician
Page of 1 19United Fire Protection - Atlanta Download Date: 05/20/2023
Executive Summary Generated by: BuildingReports.com
Building Information Building: Fort McPherson VAMC Bldg 128 Contact: Mike McGill
Address: 1701 Hardee Ave SW Phone: 4043216111
Address: Fax:
City/State/ZIP Code: Atlanta, GA 30310 Mobile:
Country: United States of America Email:
Inspection Performed By Company: United Fire Protection - Atlanta Inspector: Wayne Huxtable
Address: 2150 Boggs Rd Bldg 100 Phone: 770-771-0999
Address: Suite 140 Fax:
City/State/ZIP Code: Duluth, GA 30096 Mobile:
Country: United States of America Email: whuxtable@united-fire.com
Page of 2 19United Fire Protection - Atlanta Download Date: 05/20/2023
Inspection Completion Date: May 18, 2023 Building: Fort McPherson VAMC Bldg 128 EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019)
Table 14.4.3.2 (17)(10)(a) & (17)(11)
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Tamper Switch 5 5 0 5 0 5
Waterflow Switch 5 5 0 5 0 5
EC 02.03.05 EP 09 Annual test of main drains at system low point or at all system risers. NFPA 25 (2020)
13.2.3 & 13.2.3.2
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Drain 2 2 0 2 0 2
EC 02.03.05 EP 10 Quarterly inspection of all fire department water supply connections
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Fire Dep't Connection 1 1 0 1 0 1
LS 02.01.35 EP 14 All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Check Valve 6 6 0 6 0 6
Control Valve 7 7 0 7 0 7
Gauge 7 7 0 7 0 7
Inspector's Test 4 4 0 4 0 4
Total Device Count: 37
Page of 3 19United Fire Protection - Atlanta Download Date: 05/20/2023
Certification
Company: United Fire Protection - Atlanta Building: Fort McPherson VAMC Bldg 128
Inspector: Wayne Huxtable Contact: Mike McGill
Page of 4 19United Fire Protection - Atlanta Download Date: 05/20/2023
Inspection & Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 128 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Tamper Switch 5 5 0 5 5
Device Type Location ScanID Address Q3/22 Q4/22 Q2/23 Tamper Switch 1st 1st Riser Room Backflow
CV #2
67977804 1-M1-108 05/17-P
Tamper Switch 1st 1st Riser Room Backflow
CV #2
67977806 1-M1-108 05/17-P
Tamper Switch 1st 1st Riser Room Isolation CV 1st Fl
67978997 1-M1-47 05/17-P
Tamper Switch 1st 1st Riser Room Main Feed for 1st, 2nd & Attic
67978996 1-M1-107 05/17-P
Tamper Switch 2nd 2nd Stairwell 1 67978989 1-M1-102 05/17-P
Device Total: 5 Return to Executive Summary
Page of 5 19United Fire Protection - Atlanta Download Date: 05/20/2023
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-19 Table
14.4.3.2 (17)(11)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Waterflow Switch 5 5 0 5 5
Device Type Location ScanID Address Q3/22 Q4/22 Q2/23 Waterflow Switch 1st 1st Riser Room Flowswitch
1st Fl 44133461 1-M1-46 08/15-P 10/28-P 05/17-P
Waterflow Switch 1st 1st Riser Room Main Feed 67977808 1-M1-105 08/15-P 10/28-P 05/17-P The above device replaced ScanID 44133454:
Waterflow Switch 1st 1st Riser Room Main Feed 44133454 1-M1-105 08/15-R Waterflow Switch 2nd 2nd Stairwell 1 67977805 1-M1-102 05/17-P Waterflow Switch 2nd 2nd Stairwell 1 Flowswitch 44133468 1-M1-101 08/15-P 10/28-P 05/18
Removed Waterflow Switch Attic 2nd Stairwell 1 Attic 67977803 1 05/17-P Waterflow Switch Attic 2nd Stairwell 1 Flowswitch 44133473 1-M1-103 08/15-P 10/28-P 05/17-P
Device Total: 5 Return to Executive Summary
Page of 6 19United Fire Protection - Atlanta Download Date: 05/20/2023
EC 02.03.05 EP 09
Annual test of main drains at system low point or at all system risers. NFPA 25 (2020)
13.2.3 & 13.2.3.2
A main drain test shall be conducted annually for each water supply lead-in to a building water-based fire protection system to determine whether there has been a change in the condition of the water supply. (NFPA 25-20 13.2.3) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Drain 2 2 0 2 2
Device Type Location ScanID Address Q3/22 Q4/22 Q2/23 Drain 1st 1st Riser Room Main Feed
Drain 44133455 0 08/15-P 10/28-P 05/17-P
Drain 1st 1st Riser Room Main Feed Drain
67978995 0 05/17-P
Device Total: 2 Return to Executive Summary
Page of 7 19United Fire Protection - Atlanta Download Date: 05/20/2023
EC 02.03.05 EP 10 Quarterly inspection of all fire department water supply connections
Fire department connections shall be inspected quarterly to verify the following: Connections are visible and accessible, couplings or swivels are not damaged and rotate smoothly, plugs or caps are in place and undamaged, gaskets are in place and in good condition, identification signs are in place, the check valve is not leaking, the automatic drain valve is in place and operating properly, the clapper is in place and operating properly, there are no obstructions, and visible piping supplying the fire department connection is undamaged. (NFPA 25-20 13.8.1) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Fire Dep't Connection 1 1 0 1 1
Device Type Location ScanID Address Q3/22 Q4/22 Q2/23 Fire Dep't Connection 1st 1st Riser Room 44133464 0 08/15-P 10/28-P 05/17-P
Device Total: 1 Return to Executive Summary
Page of 8 19United Fire Protection - Atlanta Download Date: 05/20/2023
LS 02.01.35 EP 14
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Internal components shall be cleaned, repaired, or replaced as necessary in accordance with the manufacturer's instructions. (NFPA 25-20 13.4.2.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Check Valve 6 6 0 6 6
Device Type Location ScanID Address Q3/22 Q4/22 Q2/23 Check Valve 1st 1st Riser Room Check 1st Fl 44133477 1 08/15-P 10/28-P 05/18-P Check Valve 1st 1st Riser Room FDC Check 44133465 1 08/15-P 10/28-P 05/17-P Check Valve 1st 1st Riser Room Isolation CV
1st Fl 44133463 1-M1-47 05/17-P
Check Valve 1st 1st Riser Room Riser Check Main Feed
44133451 1 08/15-P 10/28-P 05/17-P
Check Valve 2nd 2nd Stairwell 1 Check 2nd Fl 44133467 1 08/15-P 10/28-P 05/17-P Check Valve 2nd 2nd Stairwell 1 Check Attic 44133472 1 08/15-P 10/28-P 05/17-P
Device Total: 6 Return to Executive Summary
Page of 9 19United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Control Valve 7 7 0 7 7
Device Type Location ScanID Address Q3/22 Q4/22 Q2/23 Control Valve 1st 1st Riser Room Backflow
CV #1
44133459 1-M1-109 08/15-P 10/28-P 05/17-P
Control Valve 1st 1st Riser Room Backflow
CV #2
44133458 1-M1-108 08/15-P 10/28-P 05/17-P
Control Valve 1st 1st Riser Room Isolation CV 1st Fl
44133460 1-M1-47 08/15-P 10/28-P 05/17-P
Control Valve 1st 1st Riser Room Main Feed for 1st, 2nd & Attic
44133450 1-M1-107 08/15-P 10/28-P 05/17-P
Control Valve 1st 1st Riser Room Test Header
CV
44133457 1-M1-106 08/15-P 10/28-P 05/18-P
Control Valve 2nd 2nd Stairwell 1 44133466 1-M1-102 08/15-P 10/28-P 05/17-P Control Valve Attic 2nd Stairwell 1 Attic 44133471 1-M1-104 08/15-P 10/28-P 05/17-P
Device Total: 7 Return to Executive Summary
Page of 10 19United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. (NFPA 25- 20 13.2.5.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Gauge 7 7 0 7 7
Device Type Location ScanID Address Q3/22 Q4/22 Q2/23 Gauge 1st 1st Riser Room Isolation CV
1st Fl 57780018 0 05/17-P
Gauge 1st 1st Riser Room Supply Pressure Main Feed
57780019 0 08/15-P 10/28-P 05/17-P
The above device replaced ScanID 44133452:
Gauge 1st 1st Riser Room Supply Pressure Main Feed
44133452 1 08/15-R
Gauge 1st 1st Riser Room System Pressure 1st Fl
57780020 0 08/15-P 10/28-P 05/17-P
The above device replaced ScanID 44133462:
Gauge 1st 1st Riser Room System Pressure 1st Fl
44133462 1 08/15-R
Gauge 1st 1st Riser Room System Pressure Main Feed
57780007 0 08/15-P 10/28-P 05/18-P
The above device replaced ScanID 44133453:
Gauge 1st 1st Riser Room System Pressure Main Feed
44133453 1 08/15-R
Gauge 2nd 2nd Stairwell 1 System Pressure 2nd Fl
44133469 0 08/15-P 10/28-P 05/18-P
Gauge Attic 2nd Stairwell 1 Attic 67977857 0 05/17-P Gauge Attic 2nd Stairwell 1 System
Pressure Attic 44133474 0 08/15-P 10/28-P 05/18-P
Device Total: 7 Return to Executive Summary
Page of 11 19United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Testing of pressure switch type waterflow alarm devices on wet pipe systems shall be accomplished by opening the inspector's test connection (NFPA 25-20 5.3.3.3) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Inspector's Test 4 4 0 4 4
Device Type Location ScanID Address Q3/22 Q4/22 Q2/23 Inspector's Test 1st 1st Riser Room 1st Fl 44133456 0 08/15-P 10/28-P 05/18-P Inspector's Test 1st 1st Riser Room Main Feed
Drain 67978994 0 05/17-P
Inspector's Test 2nd 2nd Stairwell 1 44133470 0 08/15-P 10/28-P 05/17-P Inspector's Test Attic 2nd Stairwell 1 Attic 44133475 0 08/15-P 10/28-P 05/17-P
Device Total: 4 Return to Executive Summary
Page of 12 19United Fire Protection - Atlanta Download Date: 05/20/2023
Service Summary Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 128 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Passed Check Valve Annual 6 Control Valve Annual 7 Drain Annual 2 Fire Dep't Connection Annual 1 Gauge Annual 7 Inspector's Test Annual 4 Tamper Switch Annual 5 Waterflow Switch Annual 5
Total 37 Grand Total 37
Page of 13 19United Fire Protection - Atlanta Download Date: 05/20/2023
Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Attic, Zone-128
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Simplex 30 4” 1-M1-103 44133473 Vane Potter Electric VSR 30 4 1 67977803
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved 2nd 2nd Stairwell 1 Check Attic 08/15/2022 4" 44133472
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Simplex Attic 2nd Stairwell 1 Attic
4" Open Supervised 44133471
Description Main Control
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Simplex 50 34 44133475
Location Attic 2nd Stairwell 1 Attic
Devices Gauge
Location Service Date Attic 2nd Stairwell 1 Attic 12/31/1969
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 50 Air/Water 1/4 67977857
Building: Fort McPherson VAMC Bldg
Building- 2nd, Zone-128
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133473');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67977803');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133472');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133471');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133475');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67977857');
Page of 14 19United Fire Protection - Atlanta Download Date: 05/20/2023 that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
Control Valve Supervisory 2nd 2nd Stairwell 1 1-M1-102 67978989
Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 30 4 1-M1-102 67977805
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved 2nd 2nd Stairwell 1 Check 2nd Fl 08/15/2022 4" 44133467
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Simplex 2nd 2nd Stairwell 1
4" Open Supervised 44133466
Description Main Control
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID Simplex 50 30 44133470
Location 2nd 2nd Stairwell 1
Building: Fort McPherson VAMC Bldg
Zone-128
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
Control Valve Supervisory 1st 1st Riser Room Isolation CV 1st Fl
1-M1-47 67978997
Control Valve Supervisory 1st 1st Riser Room Main Feed for 1st, 2nd & Attic
1-M1-107 67978996
OS&Y Supervisory 1st 1st Riser Room Backflow CV #2
1-M1-108 67977804
1st 1st Riser Room Backflow CV javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67978989');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67977805');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133467');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133466');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133470');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67978997');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67978996');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67977804');
Page of 15 19United Fire Protection - Atlanta Download Date: 05/20/2023
OS&Y Supervisory #2 1-M1-108 67977806
Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Simplex 30 4” 1-M1-46 44133461 Vane Simplex 30 4” 1-M1-105 67977808
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved 1st 1st Riser Room Isolation CV 1st Fl 12/31/1969 4" 44133463 Grooved 1st 1st Riser Room FDC Check 08/15/2022 4" 44133465
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Simplex 1st 1st Riser Room Isolation CV 1st Fl
4" Open Supervised 44133460
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Simplex
1st 1st Riser Room Main Feed for 1st, 2nd & Attic
4" Open Supervised 44133450
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Simplex 1st 1st Riser Room Backflow
CV #2
4" Open Supervised 44133458
Description Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Simplex 1st 1st Riser Room Backflow
CV #1
4" Open Supervised 44133459
Description Main Control
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67977806');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133461');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67977808');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133463');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133465');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133460');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133450');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133458');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133459');
Page of 16 19United Fire Protection - Atlanta Download Date: 05/20/2023
Simplex 50 34 67978994
Location 1st 1st Riser Room Main Feed Drain
Devices Drain
Current Inspection
Type Location Size Supply psi Restored psi
Residual psi Sec OK ScanID
Main 1st 1st Riser Room Main Feed Drain
2" 50 50 40 39 44133455
Current Inspection
Type Location Size Supply psi Restored psi
Residual psi Sec OK ScanID
Main 1st 1st Riser Room Main Feed Drain
2" 50 50 40 39 67978995
Fire Dep't Connection Location Type BallDrip Rotating Swivels Size OK ScanID
1st 1st Riser Room Siamese Yes Yes 2.5" 44133464
Gauge Location Service Date 1st 1st Riser Room Isolation CV 1st Fl 12/31/2027
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 50 Air/Water 1/4 57780018
Gauge Location Service Date 1st 1st Riser Room System Pressure 1st Fl 08/15/2027
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 60 Air/Water 1/4 57780020
Gauge Location Service Date 1st 1st Riser Room Supply Pressure Main Feed 08/15/2022
Type Manufacturer Model # Static psi Fill Type Size OK ScanID City Pressure Lansdale 60 Air/Water 1/4 57780019 javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67978994');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133455');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67978995');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133464');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','57780018');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','57780020');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','57780019');
Page of 17 19United Fire Protection - Atlanta Download Date: 05/20/2023
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 128 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Check Valve Valve 16.22% 6
Control Valve Valve 18.92% 7
Drain Device 5.41% 2
Fire Dep't Connection Hose 2.70% 1
Gauge Device 18.92% 7
Inspector's Test Valve 10.81% 4
Tamper Switch Alarm 13.51% 5
Waterflow Switch Alarm 13.51% 5
Device Type Qty Model # Type Description Install Date
In Service - 90 Days - 1 Year Check Valve 1 08/15/2022 Control Valve 1 08/15/2022 Gauge 3 08/15/2022 Inspector's Test 1 08/15/2022 Check Valve 1 Grooved 08/15/2022
Wet Pipe, Zone-128 Gauge 1 City Pressure 08/15/2022 Gauge 2 System Pressure 08/15/2022 Tamper Switch 2 OSYSI-2 OS&Y Supervisory 08/15/2022 Check Valve 1 Grooved 08/15/2022 Control Valve 2 Butterfly Main Control 08/15/2022 Control Valve 1 OS&Y Isolation 08/15/2022 Control Valve 1 OS&Y Main Control 08/15/2022 Drain 2 Main 08/15/2022 Fire Dep't Connection 1 Siamese 08/15/2022 Inspector's Test 1 08/15/2022 Tamper Switch 2 Control Valve Supervisory 08/15/2022 Waterflow Switch 2 Vane Alarm 08/15/2022 Check Valve 1 Grooved 08/15/2022
Attic Wet Pipe, Zone-128 Check Valve 1 Grooved 08/15/2022 Gauge 1 System Pressure 08/15/2022
Page of 18 19United Fire Protection - Atlanta Download Date: 05/20/2023
Waterflow Switch 1 VSR Vane Alarm 08/15/2022 Control Valve 1 Butterfly Main Control 08/15/2022 Inspector's Test 1 08/15/2022 Waterflow Switch 1 Vane Alarm 08/15/2022
Building- 2nd Wet Pipe, Zone-128 Waterflow Switch 1 VSR Vane Alarm 08/15/2022 Check Valve 1 Grooved 08/15/2022 Control Valve 1 Butterfly Main Control 08/15/2022 Inspector's Test 1 08/15/2022 Tamper Switch 1 Control Valve Supervisory 08/15/2022
Page of 19 19United Fire Protection - Atlanta Download Date: 05/20/2023
Zone Address Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 128 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
Control Panel 1 M1-46 Waterflow Switch 1st 1st Riser Room Flowswitch 1st Fl Vane 44133461 M1-47 Control Valve 1st 1st Riser Room Isolation CV 1st Fl Butterfly 44133460 M1-47 Tamper Switch 1st 1st Riser Room Isolation CV 1st Fl Control Valve 67978997
M1-102 Control Valve 2nd 2nd Stairwell 1 Butterfly 44133466 M1-102 Tamper Switch 2nd 2nd Stairwell 1 Control Valve 67978989 M1-102 Waterflow Switch 2nd 2nd Stairwell 1 Vane 67977805 M1-103 Waterflow Switch Attic 2nd Stairwell 1 Flowswitch Vane 44133473 M1-104 Control Valve Attic 2nd Stairwell 1 Attic Butterfly 44133471 M1-105 Waterflow Switch 1st 1st Riser Room Main Feed Vane 67977808 M1-106 Control Valve 1st 1st Riser Room Test Header CV 44133457 M1-107 Control Valve 1st 1st Riser Room Main Feed for 1st, 2nd
& Attic Butterfly 44133450
M1-107 Tamper Switch 1st 1st Riser Room Main Feed for 1st, 2nd & Attic
Control Valve 67978996
M1-108 Control Valve 1st 1st Riser Room Backflow CV #2 OS&Y 44133458 M1-108 Tamper Switch 1st 1st Riser Room Backflow CV #2 OS&Y 67977804 M1-108 Tamper Switch 1st 1st Riser Room Backflow CV #2 OS&Y 67977806 M1-109 Control Valve 1st 1st Riser Room Backflow CV #1 OS&Y 44133459 javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133461');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133460');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67978997');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133466');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67978989');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67977805');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133473');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133471');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67977808');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133457');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133450');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67978996');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133458');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67977804');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','67977806');
javascript:openEditDevice('load-edit-p2-device','1267466','2902387','44133459');
| Sprinkler Inspection, Testing and/or Maintenance Certificate |
| Executive Summary |
| Inspection & Testing |
| Service Summary |
| Wet Pipe Fire Sprinkler Systems |
| Inventory & Warranty Report |
| Zone Address Report |