This document provides the results of an annual fire sprinkler system inspection and testing report for Building 130 at the Fort McPherson VA Medical Center in Atlanta, Georgia. The report details the inspection of 75 devices across the building's wet pipe, dry pipe, and backflow prevention systems. Devices tested include control valves, tamper switches, waterflow switches, gauges, dry pipe valves, and sprinkler heads. For each device, the report provides the type, manufacturer, model, location, and inspection results. It also documents the wet and dry pipe systems' components, zones, addresses, and equipment specifications in detail. This level of equipment documentation and testing would be required to respond to the attached solicitation from the VA seeking offers for fire sprinkler inspection, testing, and maintenance services.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sprinkler Inspection, Testing and/or Maintenance Certificate
For
Fort McPherson VAMC Bldg 130 1701 Hardee Ave SW
Atlanta, GA 30310 Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards effective January 31, 2021
Annual Inspection Inspection Completion Date May 18, 2023
Building: Fort McPherson VAMC Bldg 130 Company: United Fire Protection - Atlanta Contact: Mike McGill Contact: Wayne Huxtable
Title: Maintenance & Operations Supervisor Title: Technician
Page of 1 34United Fire Protection - Atlanta Download Date: 05/20/2023
Executive Summary Generated by: BuildingReports.com
Building Information Building: Fort McPherson VAMC Bldg 130 Contact: Mike McGill
Address: 1701 Hardee Ave SW Phone: 14043216111
Address: Fax:
City/State/ZIP Code: Atlanta, GA 30310 Mobile:
Country: United States of America Email:
Inspection Performed By Company: United Fire Protection - Atlanta Inspector: Wayne Huxtable
Address: 2150 Boggs Rd Bldg 100 Phone: 770-771-0999
Address: Suite 140 Fax:
City/State/ZIP Code: Duluth, GA 30096 Mobile:
Country: United States of America Email: whuxtable@united-fire.com
Page of 2 34United Fire Protection - Atlanta Download Date: 05/20/2023
Inspection Completion Date: May 18, 2023 Building: Fort McPherson VAMC Bldg 130 EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(b-g)
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Air Maintenance Device 1 1 0 1 0 1
Pressure Switch 2 2 0 2 0 2
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Tamper Switch 14 14 0 14 0 14
Waterflow Switch 8 8 0 8 0 8
LS 02.01.35 EP 07 At least six spare sprinkler heads that correspond to the types and temperature rating of the hospital's sprinkler heads, with associated wrenches, are kept in a cabinet that will not exceed 100F. NFPA 25-2020: 5.4.1
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Sprinkler Box 3 3 0 3 0 3
Sprinkler Box Spares 6 6 0 6 0 6
LS 02.01.35 EP 14 All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Devices Tested This
Quarter Pass Fail Tested YTD
(2023) Untested YTD
(2023) Total
Quantity Drain 1 1 0 1 0 1
Air Compressor 1 1 0 1 0 1
Check Valve 7 7 0 7 0 7
Control Valve 15 15 0 15 0 15
Dry Pipe Valve 1 1 0 1 0 1
Gauge 9 9 0 9 0 9
Inspector's Test 5 5 0 5 0 5
Manifold 1 1 0 1 0 1
Wrenches 1 1 0 1 0 1
Total Device Count: 75
Page of 3 34United Fire Protection - Atlanta Download Date: 05/20/2023
Certification
Company: United Fire Protection - Atlanta Building: Fort McPherson VAMC Bldg 130
Inspector: Wayne Huxtable Contact: Mike McGill
Page of 4 34United Fire Protection - Atlanta Download Date: 05/20/2023
Inspection & Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 130 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(b-g)
Automatic air pressure maintenance devices, if provided, shall be tested yearly at the time of the annual preaction or deluge valve trip test, in accordance with the manufacturer's instructions. (NFPA 25-20 13.4.3.2.13) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Air Maintenance Device 1 1 0 1 1
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Air Maintenance Device
2nd Stairwell 2 Dry System 57780028 0 08/15-P 10/28-P 02/09-P 05/17-P
Device Total: 1 Return to Executive Summary
Page of 5 34United Fire Protection - Atlanta Download Date: 05/20/2023
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(b-g)
Operate switch and verify receipt of signal is obtained where the required pressure is increased or decreased a maximum 10 psi from the required pressure level. (NFPA 72-19 Table 14.4.3.2 (17)(9b)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Pressure Switch 2 2 0 2 2
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Pressure Switch 2nd Stairwell 2 Dry System
High Pressure 44133525 1-M1-83 08/15-P 10/28-P 02/09-P 05/17-P
Pressure Switch 2nd Stairwell 2 Dry System Low Air
44133524 1-M84 08/15-P 10/28-P 02/09-P 05/17-P
Device Total: 2 Return to Executive Summary
Page of 6 34United Fire Protection - Atlanta Download Date: 05/20/2023
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Tamper Switch 14 14 0 14 14
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Tamper Switch Basement Boiler Room
Backflow CV 1 67977794 1-M1-1 08/15-P 10/28-P 05/17-P
Tamper Switch Basement Boiler Room Backflow CV 2
67977795 1-M1-2 08/15-P 10/28-P 02/09-P 05/17-P
Tamper Switch Basement Boiler Room Main Feed for bldg
67977797 1-M1-4 08/15-P 10/28-P 02/09-P 05/17-P
Tamper Switch Basement Boiler Room Test Header
67977796 1-M1- 08/15-P 10/28-P 02/09-P 05/17-P
Tamper Switch Basement 130 Wet 67978981 1-M1-7 05/17-P Tamper Switch 1st Stairwell 2 Zone 1-1 67978983 1-M1-1 05/17-P Tamper Switch 1st Stairwell 2 Zone 1-2 67978984 1-M1-33 05/17-P Tamper Switch 2nd Stairwell 2 Passenger
Elevator 44133527 1-M1-19 08/15-P 10/28-P 05/17-P
Tamper Switch 2nd Stairwell 2 Zone 2-1 67978986 1-M1-79 05/17-P Tamper Switch 2nd Stairwell 2 Zone 2-2 67978987 1-M1-80 05/17-P Tamper Switch Basement GD-002 Stairwell
2 Passenger Elevator 67978982 1-M1-5 05/17-P
Tamper Switch Basement GD-002 Stairwell 2 Passenger Elevator
44133542 1-M1-5 08/15-P 10/28-P 02/09-P 05/18-P
Tamper Switch Ground outside @ B building 57780010 1 08/15-P 10/28-P 02/09-P 05/18-P Tamper Switch Ground outside Between D and C 57780054 1 08/15-P 10/28-P 02/09-P 05/18-P
Device Total: 14 Return to Executive Summary
Page of 7 34United Fire Protection - Atlanta Download Date: 05/20/2023
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-19 Table
14.4.3.2 (17)(11)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Waterflow Switch 8 8 0 8 8
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Waterflow Switch Basement Wet 57780039 1-M1-7 08/15-P 10/28-P 02/09-P 05/17-P Waterflow Switch Basement 130 Wet 44133540 1-M1-7 08/15-P 10/28-P 02/09-P 05/17-P Waterflow Switch 1st Stairwell 2 Zone 1-1 44133499 1-M1-34 08/15-P 10/28-P 02/09-P 05/17-P Waterflow Switch 1st Stairwell 2 Zone 1-2 44133504 1-M1-33 08/15-P 10/28-P 02/09-P 05/17-P Waterflow Switch 2nd Stairwell 2 Dry System 44133526 1 08/15-P 10/28-P 05/17-P Waterflow Switch 2nd Stairwell 2 Passenger
Elevator 44133528 1-M1-18 08/15-P 10/28-P 05/17-P
Waterflow Switch 2nd Stairwell 2 Passenger Elevator
44133543 1-M1-18 08/15-P 10/28-P 05/18 Removed
Waterflow Switch 2nd Stairwell 2 Zone 2-1 44133510 1-M1-79 08/15-P 10/28-P 02/09-P 05/17-P Waterflow Switch 2nd Stairwell 2 Zone 2-2 44133515 1-M1-80 08/15-P 10/28-P 02/09-P 05/17-P
Device Total: 8 Return to Executive Summary
Page of 8 34United Fire Protection - Atlanta Download Date: 05/20/2023
LS 02.01.35 EP 07
At least six spare sprinkler heads that correspond to the types and temperature rating of the hospital's sprinkler heads, with associated wrenches, are kept in a cabinet that will not exceed 100F. NFPA 25-2020: 5.4.1
A supply of at least six spare sprinklers shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. (NFPA 25-20 5.4.1.5) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Sprinkler Box 3 3 0 3 3
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Sprinkler Box Basement Boiler Room Main
Feed for bldg 57780031 0 08/15-P 10/28-P 05/17-P
Sprinkler Box Basement Boiler Room Main Feed for bldg
57780034 0 08/15-P 10/28-P 05/17-P
Sprinkler Box Basement 130 Boiler Room Main Feed for bldg
57780029 0 08/15-P 10/28-P 05/17-P
Device Total: 3 Return to Executive Summary
Page of 9 34United Fire Protection - Atlanta Download Date: 05/20/2023
LS 02.01.35 EP 07
At least six spare sprinkler heads that correspond to the types and temperature rating of the hospital's sprinkler heads, with associated wrenches, are kept in a cabinet that will not exceed 100F. NFPA 25-2020: 5.4.1
A supply of at least six spare sprinklers shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. (NFPA 25-20 5.4.1.5) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Sprinkler Box Spares 6 6 0 6 6
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Sprinkler Box Spares Basement Boiler Room Main
Feed for bldg 57780030 0 08/15-P 10/28-P 05/17-P
Sprinkler Box Spares Basement Boiler Room Main Feed for bldg
57780032 0 08/15-P 10/28-P 05/17-P
Sprinkler Box Spares Basement Boiler Room Main Feed for bldg
57780037 0 08/15-P 10/28-P 05/17-P
Sprinkler Box Spares Basement Boiler Room Main Feed for bldg
57780035 0 08/15-P 10/28-P 05/17-P
Sprinkler Box Spares Basement Boiler Room Main Feed for bldg
57780036 0 08/15-P 10/28-P 05/17-P
Sprinkler Box Spares Basement 130 Boiler Room Main Feed for bldg
57780033 0 08/15-P 10/28-P 05/17-P
Device Total: 6 Return to Executive Summary
Page of 10 34United Fire Protection - Atlanta Download Date: 05/20/2023
LS 02.01.35 EP 14
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
A main drain test shall be conducted annually for each water supply lead-in to a building water-based fire protection system to determine whether there has been a change in the condition of the water supply. (NFPA 25-20 13.2.3) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Drain 1 1 0 1 1
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Drain Basement 130 Boiler Room
Main Feed for bldg 44133537 0 08/15-P 10/28-P 05/17-P
Page of 11 34United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Compressors used in conjunction with dry pipe sprinkler systems shall be maintained in accordance with the manufacturer's instructions. (NFPA 25-20 5.4.2.4) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Air Compressor 1 1 0 1 1
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Air Compressor 2nd Stairwell 2 Dry System 67977852 0 08/15-P 10/28-P 02/09-P 05/17-P
Page of 12 34United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Internal components shall be cleaned, repaired, or replaced as necessary in accordance with the manufacturer's instructions. (NFPA 25-20 13.4.2.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Check Valve 7 7 0 7 7
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Check Valve Basement Wet 57780040 1 08/15-P 10/28-P 05/17-P Check Valve Basement 130 Wet 44133539 1 08/15-P 10/28-P 05/17-P Check Valve Basement 130 Boiler Room
Main Feed for bldg 44133534 1 08/15-P 10/28-P 05/17-P
Check Valve 1st Stairwell 2 Zone 1-1 44133498 1 08/15-P 10/28-P 05/17-P Check Valve 1st Stairwell 2 Zone 1-2 44133503 1 08/15-P 10/28-P 05/17-P Check Valve 2nd Stairwell 2 Zone 2-1 44133508 1 08/15-P 10/28-P 05/17-P Check Valve 2nd Stairwell 2 Zone 2-2 44133513 1 08/15-P 10/28-P 05/17-P
Device Total: 7 Return to Executive Summary
Page of 13 34United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Control Valve 15 15 0 15 15
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Control Valve Basement Boiler Room
Backflow CV 1 44133530 1-M1-1 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve Basement Boiler Room Backflow CV 2
44133531 1-M1-2 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve Basement Boiler Room Test Header
44133532 1-M1- 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve Basement 130 Wet 44133538 1-M1-7 08/15-P 10/28-P 02/09-P 05/17-P Control Valve Basement 130 Boiler Room
Main Feed for bldg 44133533 1-M1-4 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve 1st Stairwell 2 Zone 1-1 44133497 1-M1-1 08/15-P 10/28-P 02/09-P 05/17-P Control Valve 1st Stairwell 2 Zone 1-2 44133502 1-M1-33 08/15-P 10/28-P 02/09-P 05/17-P Control Valve 2nd Stairwell 2 Dry System 44133518 1-M1-81 08/15-P 10/28-P 02/09-P 05/17-P Control Valve 2nd Stairwell 2 Passenger
Elevator 67978985 1-M1-18 05/17-P
Control Valve 2nd Stairwell 2 Zone 2-1 44133507 1-M1-79 08/15-P 10/28-P 02/09-P 05/17-P Control Valve 2nd Stairwell 2 Zone 2-2 44133512 1-M1-80 08/15-P 10/28-P 02/09-P 05/17-P Control Valve Basement GD-002 Stairwell
2 Passenger Elevator 44133529 1-M1-5 08/15-P 10/28-P 05/17-P
Control Valve Basement GD-002 Stairwell 2 Passenger Elevator
57780038 1-M1-5 08/15-P 10/28-P 02/09-P 05/17-P
Control Valve Ground outside @ B building 57780011 1 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Ground outside Between D and C 57780053 1 08/15-P 10/28-P 02/09-P 05/18-P
Device Total: 15 Return to Executive Summary
Page of 14 34United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Each dry pipe valve shall be trip tested annually during warm weather. (NFPA 25-20 13.4.5.2.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Dry Pipe Valve 1 1 0 1 1
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Dry Pipe Valve 2nd Stairwell 2 Passenger
Elevator 44133520 0 08/15-P 10/28-P 02/09-P 05/17-P
Page of 15 34United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. (NFPA 25- 20 13.2.5.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Gauge 9 9 0 9 9
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Gauge Basement 130 Boiler Room
Main Feed for bldg 44133536 0 08/15-P 10/28-P 05/17-P
Gauge Basement 130 Boiler Room Main Feed for bldg
44133535 0 08/15-P 10/28-P 05/17-P
Gauge 1st Stairwell 2 Zone 1-1 57780013 0 08/15-P 10/28-P 05/17-P Gauge 1st Stairwell 2 Zone 1-2 57780022 0 08/15-P 10/28-P 05/17-P Gauge 2nd Stairwell 2 Dry System 57780025 0 08/15-P 10/28-P 05/17-P Gauge 2nd Stairwell 2 Dry System 57780027 0 08/15-P 10/28-P 05/17-P Gauge 2nd Stairwell 2 Zone 2-1 57780024 0 08/15-P 10/28-P 05/17-P Gauge 2nd Stairwell 2 Zone 2-1 44133509 0 08/15-P 10/28-P 05/17-P Gauge 2nd Stairwell 2 Zone 2-2 57780023 0 05/17-P
Device Total: 9 Return to Executive Summary
Page of 16 34United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Testing of pressure switch type waterflow alarm devices on wet pipe systems shall be accomplished by opening the inspector's test connection (NFPA 25-20 5.3.3.3) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Inspector's Test 5 5 0 5 5
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Inspector's Test 1st Stairwell 2 Zone 1-1 44133501 0 08/15-P 10/28-P 05/17-P Inspector's Test 1st Stairwell 2 Zone 1-1 44133541 0 08/15-P 10/28-P 05/17-P Inspector's Test 1st Stairwell 2 Zone 1-2 44133506 0 08/15-P 10/28-P 05/17-P Inspector's Test 2nd Stairwell 2 Zone 2-1 44133511 0 08/15-P 10/28-P 02/09-P 05/17-P Inspector's Test 2nd Stairwell 2 Zone 2-2 44133516 0 08/15-P 10/28-P 02/09-P 05/17-P
Device Total: 5 Return to Executive Summary
Page of 17 34United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Manifold 1 1 0 1 1
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Manifold 2nd Stairwell 2 Passenger
Elevator 44133519 0 08/15-P 10/28-P 02/09-P 05/17-P
Page of 18 34United Fire Protection - Atlanta Download Date: 05/20/2023
All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5
One sprinkler wrench as specified by the sprinkler manufacturer shall be provided in the cabinet for each type of sprinkler installed to be used for the removal and installation of sprinklers in the system. (NFPA 25-20 5.4.1.5.5) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Wrenches 1 1 0 1 1
Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Wrenches Basement Boiler Room Main
Feed for bldg 57780055 0 08/15-P 10/28-P 05/17-P
Page of 19 34United Fire Protection - Atlanta Download Date: 05/20/2023
Service Summary Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 130 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Passed Air Compressor Annual 1 Air Maintenance Device Annual 1 Check Valve Annual 7 Control Valve Annual 15 Drain Annual 1 Dry Pipe Valve Annual 1 Gauge Annual 9 Inspector's Test Annual 5 Manifold Annual 1 Pressure Switch Annual 2 Sprinkler Box Spares Annual 6 Sprinkler Box Annual 3 Tamper Switch Annual 14 Waterflow Switch Annual 8 Wrenches Annual 1
Total 75 Grand Total 75
Page of 20 34United Fire Protection - Atlanta Download Date: 05/20/2023
Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
Control Valve Supervisory Basement 130 Wet 1-M1-7 67978981
OS&Y Supervisory Basement Boiler Room Test Header
1-M1- 67977796
OS&Y Supervisory Basement Boiler Room Main Feed for bldg
1-M1-4 67977797
OS&Y Supervisory 1st Stairwell 2 Zone 1-2 1-M1-33 67978984 OS&Y Supervisory 1st Stairwell 2 Zone 1-1 1-M1-1 67978983 OS&Y Supervisory 2nd Stairwell 2 Zone 2-2 1-M1-80 67978987 OS&Y Supervisory 2nd Stairwell 2 Zone 2-1 1-M1-79 67978986
Control Valve Supervisory 2nd Stairwell 2 Passenger Elevator
1-M1-19 44133527
Control Valve Supervisory Basement GD-002 Stairwell 2 Passenger Elevator
1-M1-5 67978982
Control Valve Supervisory Basement GD-002 Stairwell 2 Passenger Elevator
1-M1-5 44133542
Control Valve Supervisory Ground outside @ B building 1 57780010 Control Valve Supervisory Ground outside Between D and C 1 57780054
Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VS-SP 1’’ 1-M1-7 57780039 Vane Potter Electric VSR 30.37000 3 1-M1-7 44133540 Vane Potter Electric VSR 30.20999 4" 1-M1-33 44133504 Vane Potter Electric VSR 30.39999 4" 1-M1-34 44133499 Vane Potter Electric VSR 30.40999 4" 1-M1-80 44133515 Vane Potter Electric VSR 30 4" 1-M1-79 44133510 Vane Potter Electric VS-SP 1" 1-M1-18 44133528
Components Check Valve javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978981');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977796');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977797');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978984');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978983');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978987');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978986');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133527');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978982');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133542');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780010');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780054');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780039');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133540');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133504');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133499');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133515');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133510');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133528');
Page of 21 34United Fire Protection - Atlanta Download Date: 05/20/2023
Type Location Internal Date Size OK ScanID Grooved Basement 130 Wet 03/29/2018 4" 44133539 Grooved Basement Wet 03/29/2018 4" 57780040
Grooved Basement 130 Boiler Room Main Feed for bldg
03/29/2012 8" 44133534
Grooved 1st Stairwell 2 Zone 1-2 03/29/2018 4" 44133503 Grooved 1st Stairwell 2 Zone 1-1 03/29/2018 3" 44133498 Grooved 2nd Stairwell 2 Zone 2-2 03/29/2018 3" 44133513 Grooved 2nd Stairwell 2 Zone 2-1 03/29/2018 3" 44133508
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Anvil AN7722-3A Basement 130 Wet
4" Open Supervised 44133538
Description Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Kennedy KS-FW
Basement 130 Boiler Room Main Feed for bldg
4" Open Supervised 44133533
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Kennedy KS-FW Basement Boiler Room Test Header
6" Closed Supervised 44133532
Description
CV 2
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Anvil AN7722-3A 1st Stairwell 2 Zone 1-2
3" Open Supervised 44133502
Description Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Anvil AN7722-3A 1st Stairwell 2 Zone 1-1
4" Open Supervised 44133497
Description javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133539');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780040');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133534');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133503');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133498');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133513');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133508');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133538');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133533');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133532');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133502');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133497');
Page of 22 34United Fire Protection - Atlanta Download Date: 05/20/2023
Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Anvil AN7722-3A 2nd Stairwell 2 Zone 2-2
4" Open Supervised 44133512
Description Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Anvil AN7722-3A 2nd Stairwell 2 Zone 2-1
4" Open Supervised 44133507
Description Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Potter Electric VS-SP 2nd Stairwell 2 Passenger Elevator
1" Open Supervised 67978985
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Milwaukee BB-SCS
Basement GD- 002 Stairwell 2 Passenger Elevator
1" Open Supervised 44133529
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Milwaukee BB-SCS
Basement GD- 002 Stairwell 2 Passenger Elevator
1" Open Supervised 57780038
Description Isolation
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Post Indicator Valve
Mueller Ground outside Between D and C
6" Open Locked & Supervised
57780053
Description javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133512');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133507');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978985');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133529');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780038');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780053');
Page of 23 34United Fire Protection - Atlanta Download Date: 05/20/2023
Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Post Indicator Valve
Mueller Ground outside @ B building
6" Open Locked & Supervised
57780011
Description Main Control
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1324 65 30.40 44133501
Location 1st Stairwell 2 Zone 1-1
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1324 65 26 30.21 44133506
Location 1st Stairwell 2 Zone 1-2
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 100 65 45 30.37 44133541
Location 1st Stairwell 2 Zone 1-1
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1324 65 45 30.40 44133516
Location 2nd Stairwell 2 Zone 2-2
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1324 65 33 30.56 44133511
Location 2nd Stairwell 2 Zone 2-1
Devices Drain
Type Location Size Supply psi Restored psi
Residual psi Sec OK ScanID
Combination Basement 130 Boiler Room Main Feed for bldg
2" 60 60 40 30.45000 44133537
Gauge javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780011');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133501');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133506');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133541');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133516');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133511');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133537');
Page of 24 34United Fire Protection - Atlanta Download Date: 05/20/2023
Location Service Date Basement 130 Boiler Room Main Feed for bldg 03/29/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Lansdale 70 Air/Water 1/4 44133536
Gauge Location Service Date Basement 130 Boiler Room Main Feed for bldg 03/29/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Lansdale 75 Air/Water 1/4 44133535
Gauge Location Service Date 1st Stairwell 2 Zone 1-2 05/15/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID City Pressure Lansdale Wika 65 Air/Water 1/4 57780022
Gauge Location Service Date 1st Stairwell 2 Zone 1-1 03/29/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID City Pressure Lansdale 65 Air/Water 1/4 57780013
Gauge Location Service Date 2nd Stairwell 2 Zone 2-2 05/15/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 50 Air/Water 1/4 57780023
Gauge Location Service Date 2nd Stairwell 2 Zone 2-1 05/15/2026
Type Manufacturer Model # Static psi Fill Type Size OK ScanID Lansdale Wika 50 Air/Water 1/4 57780024
Gauge Location Service Date 2nd Stairwell 2 Zone 2-1 03/29/2012
Type Manufacturer Model # Static psi Fill Type Size OK ScanID Wika Wika 65 Air/Water 1/4 44133509
Sprinkler Box
Qty Tool Available?
SIN List? Size Manufacturer Location OK ScanID
6 Yes Yes 6 unit Viking Basement 130 Boiler Room Main Feed for bldg
57780029 javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133536');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133535');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780022');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780013');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780023');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780024');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133509');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780029');
Page of 25 34United Fire Protection - Atlanta Download Date: 05/20/2023
6 Yes Yes 6 unit Viking Basement Boiler Room Main Feed for bldg
57780031
6 Yes Yes 6 unit Viking Basement Boiler Room Main Feed for bldg
57780034
Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID
6 Pendant Viking Basement Boiler Room Main Feed for bldg
57780030
Temperature KFactor Size Finish Response Time 200 4.2 0.5 Chrome Fast Response
Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID
1 Horizontal Sidewall Viking Basement Boiler Room Main Feed for bldg
57780032
Temperature KFactor Size Finish Response Time 200 4.2 0.5 Chrome Fast Response
Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID
1 Horizontal Sidewall Viking Basement 130 Boiler Room Main Feed for bldg
57780033
Temperature KFactor Size Finish Response Time 200 4.2 3/4 “ Brass Fast Response
Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID
1 Upright Viking Basement Boiler Room Main Feed for bldg
57780037
Temperature KFactor Size Finish Response Time 200 4.2 0.5 Brass Fast Response
Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID
3 Attic Tyco Basement Boiler Room Main Feed for bldg
57780035
Temperature KFactor Size Finish Response Time 212* 1/2” Brass Fast Response
Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID
3 Upright Viking Basement Boiler Room Main Feed for bldg
57780036
Temperature KFactor Size Finish Response Time 212* 4.2 1/2” Brass Fast Response
Wrenches javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780031');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780034');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780030');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780032');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780033');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780037');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780035');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780036');
Page of 26 34United Fire Protection - Atlanta Download Date: 05/20/2023
Qty Type Manufacturer Location OK ScanID
1 Sprinkler Reliable Basement Boiler Room Main Feed for bldg
57780055 javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780055');
Page of 27 34United Fire Protection - Atlanta Download Date: 05/20/2023
Dry Pipe Fire Sprinkler Systems Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Building-Attic, Building-130
This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Air Compressor Location Mfr. Model # Phase On psi Off psi Serial No.
2nd Stairwell 2 Dry System
General Air
1 20 40
Type Description Rated Speed Horsepower Volts Amps OK ScanID
Automatic Tank 1723 1 120 67977852
Air Maintenance Device Type Model # Location Install Date Air Pressure ScanID Pressure Reducing Wika 2nd Stairwell 2 Dry System 07/11/2018 40 57780028
Alarms Pressure Switch Type Description Manufacturer Low High Zone/Address OK ScanID Low Supervisory Potter Electric 15 30 1-M84 44133524 High Alarm Potter Electric 0 50 1-M1-83 44133525
Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter electric VSR 4 1 44133526
Components Control Valve
Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Anvil AN7722-3A 2nd Stairwell 2 Dry System
4" Open Supervised 44133518
Description Isolation
Dry Pipe Valve Manufacturer Model # Location Internal Date OK ScanID Viking F-2 2nd Stairwell 2 Passenger Elevator 03/29/2018 44133520
Type Status Position Size Serial # Grooved Supervised Trim Open 4"
Total Timing Partial Trip javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977852');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780028');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133524');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133525');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133526');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133518');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133520');
Page of 28 34United Fire Protection - Atlanta Download Date: 05/20/2023
Water psi Air Pressure Trip Air Trip Time (sec) Date Full Trip Date 50280118 50 15 35 34 03/29/2012 05/17/2023
Manifold Location Manufacturer Size ScanID
2nd Stairwell 2 Passenger Elevator United Brass 2" 44133519
Devices Gauge
Location Service Date 2nd Stairwell 2 Dry System 05/27/2025
Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Lansdale 65 Air/Water 1/4 57780025
Gauge Location Service Date 2nd Stairwell 2 Dry System 03/29/2025
Type Manufacturer Model # Static psi Fill Type Size OK ScanID Air Pressure Wika Wika 30 Air/Water 1/4 57780027 javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133519');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780025');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780027');
Page of 29 34United Fire Protection - Atlanta Download Date: 05/20/2023
Backflow Test & Maintenance Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
This section lists out all the devices and components that have been associated with a Cross Connection Control System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Tamper Switch
Type Description Location Number of Turns
Zone /Address
OK ScanID
OS&Y Supervisory Basement Boiler Room Backflow
CV 2
1-M1-2 67977795
OS&Y Supervisory Basement Boiler Room Backflow
CV 1
1-M1-1 67977794
Components Control Valve
Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Kennedy KS-FW Basement Boiler Room Backflow CV 2
6" Open Supervised 44133531
Description
CV 2
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
OS&Y Kennedy KS-FW Basement Boiler Room Backflow CV 1
6" Open Supervised 44133530
Description
CV 1
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977795');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977794');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133531');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133530');
Page of 30 34United Fire Protection - Atlanta Download Date: 05/20/2023
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 130 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Air Compressor Pump 1.33% 1
Air Maintenance Device Pump 1.33% 1
Check Valve Valve 9.33% 7
Control Valve Valve 20.00% 15
Drain Device 1.33% 1
Dry Pipe Valve Valve 1.33% 1
Gauge Device 12.00% 9
Inspector's Test Valve 6.67% 5
Manifold Valve 1.33% 1
Pressure Switch Alarm 2.67% 2
Sprinkler Box Sprinkler 4.00% 3
Sprinkler Box Spares Sprinkler 8.00% 6
Tamper Switch Alarm 18.67% 14
Waterflow Switch Alarm 10.67% 8
Wrenches Sprinkler 1.33% 1
Device Type Qty Model # Type Description Install Date
In Service - 1 Year to 2 Years Wet Pipe
Gauge 1 City Pressure 05/28/2021 Gauge 1 Supply Pressure 05/28/2021 Gauge 1 Supply Pressure 05/27/2021
Building-Attic Dry Pipe, Building-130 Gauge 1 Supply Pressure 05/27/2021 Gauge 1 Wika Air Pressure 05/27/2021
In Service - 2 Years to 3 Years Wet Pipe
Gauge 1 System Pressure 05/15/2021 Gauge 1 Wika 05/15/2021 Gauge 1 Wika City Pressure 05/15/2021
In Service - 3 Years to 5 Years Wet Pipe
Gauge 1 Wika 07/11/2018
Page of 31 34United Fire Protection - Atlanta Download Date: 05/20/2023
Building-Attic Dry Pipe, Building-130 Air Compressor 1 Automatic Tank 07/11/2018 Waterflow Switch 1 VSR Vane Alarm 07/11/2018 Air Maintenance Device 1 Wika Pressure Reducing 07/11/2018
In Service - 5 Years to 10 Years Wet Pipe
Inspector's Test 1 100 03/29/2018 Inspector's Test 4 1324 03/29/2018 Check Valve 6 78FP Grooved 03/29/2018 Control Valve 5 AN7722-3A Butterfly Isolation 03/29/2018 Tamper Switch 1 AN7722-3A Control Valve Supervisory 03/29/2018 Tamper Switch 4 AN7722-3A OS&Y Supervisory 03/29/2018 Waterflow Switch 1 VS-SP Vane Alarm 03/29/2018 Waterflow Switch 5 VSR Vane Alarm 03/29/2018
Building-Attic Dry Pipe, Building-130 Control Valve 1 AN7722-3A Butterfly Isolation 03/29/2018
In Service - 10 Years to 15 Years Cross Conn. Control
Control Valve 1 KS-FW OS&Y CV 1 03/29/2012 Control Valve 1 KS-FW OS&Y CV 2 03/29/2012 Tamper Switch 2 OSYSU-2 OS&Y Supervisory 03/29/2012
Wet Pipe Drain 1 1000 Combination 03/29/2012 Control Valve 1 KS-FW OS&Y CV 2 03/29/2012 Control Valve 1 KS-FW OS&Y Main Control 03/29/2012 Control Valve 1 BB-SCS Butterfly Isolation 03/29/2012 Control Valve 1 BB-SCS Butterfly Main Control 03/29/2012 Tamper Switch 2 BB-SCS Control Valve Supervisory 03/29/2012 Control Valve 2 Post Indicator Valve Main Control 03/29/2012 Control Valve 1 VS-SP OS&Y Main Control 03/29/2012 Tamper Switch 1 OSYSU-2 OS&Y Supervisory 03/29/2012 Tamper Switch 2 PIVS-2 Control Valve Supervisory 03/29/2012 Tamper Switch 1 PTS-C Control Valve Supervisory 03/29/2012 Waterflow Switch 1 VS-SP Vane Alarm 03/29/2012 Tamper Switch 1 OSYSU-2 OS&Y Supervisory 03/29/2012 Wrenches 1 Sprinkler 03/29/2012 Sprinkler Box Spares 1 BB1 / TY3180 Attic 03/29/2012 Check Valve 1 F-1 Grooved 03/29/2012 Sprinkler Box 3 03/29/2012 Sprinkler Box Spares 2 Horizontal Sidewall 03/29/2012
Page of 32 34United Fire Protection - Atlanta Download Date: 05/20/2023
Sprinkler Box Spares 1 M 10 Upright 03/29/2012 Sprinkler Box Spares 1 M-10 Pendant 03/29/2012 Sprinkler Box Spares 1 m Upright 03/29/2012
Building-Attic Dry Pipe, Building-130 Pressure Switch 1 PS-10 High Alarm 03/29/2012 Pressure Switch 1 PS-40 Low Supervisory 03/29/2012 Manifold 1 F-2 03/29/2012 Dry Pipe Valve 1 F-2 Grooved 03/29/2012
Page of 33 34United Fire Protection - Atlanta Download Date: 05/20/2023
Zone Address Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 130 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
Control Panel 1 M1- Control Valve Basement Boiler Room Test Header OS&Y 44133532 M1- Tamper Switch Basement Boiler Room Test Header OS&Y 67977796
M1-1 Control Valve Basement Boiler Room Backflow CV 1 OS&Y 44133530 M1-1 Tamper Switch Basement Boiler Room Backflow CV 1 OS&Y 67977794 M1-1 Control Valve 1st Stairwell 2 Zone 1-1 Butterfly 44133497 M1-1 Tamper Switch 1st Stairwell 2 Zone 1-1 OS&Y 67978983 M1-2 Control Valve Basement Boiler Room Backflow CV 2 OS&Y 44133531 M1-2 Tamper Switch Basement Boiler Room Backflow CV 2 OS&Y 67977795 M1-4 Tamper Switch Basement Boiler Room Main Feed for bldg OS&Y 67977797 M1-4 Control Valve Basement 130 Boiler Room Main Feed for bldg
OS&Y 44133533
M1-5 Control Valve Basement GD-002 Stairwell 2 Passenger Elevator
Butterfly 44133529
M1-5 Control Valve Basement GD-002 Stairwell 2 Passenger Elevator
Butterfly 57780038
M1-5 Tamper Switch Basement GD-002 Stairwell 2 Passenger Elevator
Control Valve 44133542
M1-5 Tamper Switch Basement GD-002 Stairwell 2 Passenger Elevator
Control Valve 67978982
M1-7 Waterflow Switch Basement Wet Vane 57780039 M1-7 Control Valve Basement 130 Wet Butterfly 44133538 M1-7 Tamper Switch Basement 130 Wet Control Valve 67978981 M1-7 Waterflow Switch Basement 130 Wet Vane 44133540 M1-18 Control Valve 2nd Stairwell 2 Passenger Elevator OS&Y 67978985 M1-18 Waterflow Switch 2nd Stairwell 2 Passenger Elevator Vane 44133528 M1-19 Tamper Switch 2nd Stairwell 2 Passenger Elevator Control Valve 44133527 M1-33 Control Valve 1st Stairwell 2 Zone 1-2 Butterfly 44133502 M1-33 Tamper Switch 1st Stairwell 2 Zone 1-2 OS&Y 67978984 M1-33 Waterflow Switch 1st Stairwell 2 Zone 1-2 Vane 44133504 M1-34 Waterflow Switch 1st Stairwell 2 Zone 1-1 Vane 44133499 M1-79 Control Valve 2nd Stairwell 2 Zone 2-1 Butterfly 44133507 M1-79 Tamper Switch 2nd Stairwell 2 Zone 2-1 OS&Y 67978986 M1-79 Waterflow Switch 2nd Stairwell 2 Zone 2-1 Vane 44133510 M1-80 Control Valve 2nd Stairwell 2 Zone 2-2 Butterfly 44133512 javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133532');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977796');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133530');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977794');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133497');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978983');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133531');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977795');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977797');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133533');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133529');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780038');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133542');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978982');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780039');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133538');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978981');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133540');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978985');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133528');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133527');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133502');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978984');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133504');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133499');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133507');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978986');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133510');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133512');
Page of 34 34United Fire Protection - Atlanta Download Date: 05/20/2023
Address Device Type Location Type ScanID M1-80 Tamper Switch 2nd Stairwell 2 Zone 2-2 OS&Y 67978987 M1-80 Waterflow Switch 2nd Stairwell 2 Zone 2-2 Vane 44133515 M1-81 Control Valve 2nd Stairwell 2 Dry System Butterfly 44133518 M1-83 Pressure Switch 2nd Stairwell 2 Dry System High Pressure High 44133525 M84 Pressure Switch 2nd Stairwell 2 Dry System Low Air Low 44133524 javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978987');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133515');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133518');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133525');
javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133524');
| Sprinkler Inspection, Testing and/or Maintenance Certificate |
| Executive Summary |
| Inspection & Testing |
| Service Summary |
| Wet Pipe Fire Sprinkler Systems |
| Dry Pipe Fire Sprinkler Systems |
| Backflow Test & Maintenance Report |
| Inventory & Warranty Report |
| Zone Address Report |
File details come from the government source that posted it. Updated .