2023-05-18_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf

PDF 396 KB Posted

Attached to
Fire Sprinkler Testing
Solicitation number
36C24724Q0269
Issued by

About this file

This document provides the results of an annual fire sprinkler system inspection and testing report for Building 130 at the Fort McPherson VA Medical Center in Atlanta, Georgia. The report details the inspection of 75 devices across the building's wet pipe, dry pipe, and backflow prevention systems. Devices tested include control valves, tamper switches, waterflow switches, gauges, dry pipe valves, and sprinkler heads. For each device, the report provides the type, manufacturer, model, location, and inspection results. It also documents the wet and dry pipe systems' components, zones, addresses, and equipment specifications in detail. This level of equipment documentation and testing would be required to respond to the attached solicitation from the VA seeking offers for fire sprinkler inspection, testing, and maintenance services.

View the file

Other files

File Type Posted
FIRE ALARM 130.pdf PDF
2022-06-20_Fort-McPherson-VAMC-Bldg-128_Annual Report.pdf PDF
BLDG 131 ASBUILTS.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-131_Annual Report.pdf PDF
FIRE SUPPRESSION.pdf PDF
2022-06-20_Fort-McPherson-VAMC-Bldg-129_Annual Report.pdf PDF
BLDG 125 ASBUILT.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-125_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-128_SprinklerScan.pdf PDF
Ft. McPherson Bldg 128 Fire Alarm Drawings - RECORD Dwg.pdf PDF
Bldg 128 As-Builts.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
FIRE ALARM 129.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-125_SprinklerScan.pdf PDF
BLDG 129 ASBUILT.pdf PDF
2023-02-10_Fort-McPherson-VAMC-Bldg-128_SprinklerScan (1).pdf PDF
36C24724Q0269 0001.pdf PDF
03 Series LIFE SAFETY - 100 AT-130 Fort McPherson Residental Treatment.pdf PDF
03 Series LIFE SAFETY - 100 AT-131 Fort McPherson Domiciliary Care.pdf PDF
03 Series LIFE SAFETY - 100 AT-125 Fort McPherson OPC.pdf PDF
FIRE ALARM 125.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-125_Annual Report.pdf PDF
04 Series DOORS - 100 AT-130 Fort McPherson Residental Treatment.pdf PDF
04 Series DOORS - 100 AT-125 Fort McPherson OPC.pdf PDF
2023-02-09_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-130_SprinklerScan.pdf PDF
2022-08-15_Fort-McPherson-VAMC-Bldg-128_SprinklerScan.pdf PDF
05 series dampers - 100 at-125 fort mcpherson opc.pdf PDF
FIRE SUPPRESSION 131.pdf PDF
2022-06-06_Fort-McPherson-VAMC-Bldg-130_Annual Report.pdf PDF
03 Series LIFE SAFETY - 100 AT-128 Fort McPherson Homeless Program.pdf PDF
04 Series DOORS - 100 AT-128 Fort McPherson Homeless Program.pdf PDF
BLDG. 125 FIRE SUPPRESSION.pdf PDF
04 Series DOORS - 100 AT-131 Fort McPherson Domiciliary Care.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-131_SprinklerScan.pdf PDF
2023-05-18_Fort-McPherson-VAMC-Bldg-129_SprinklerScan.pdf PDF
36C24724Q0269.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Sprinkler Inspection, Testing and/or Maintenance Certificate

For

Fort McPherson VAMC Bldg 130 1701 Hardee Ave SW

Atlanta, GA 30310 Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards effective January 31, 2021

Annual Inspection Inspection Completion Date May 18, 2023

Building: Fort McPherson VAMC Bldg 130 Company: United Fire Protection - Atlanta Contact: Mike McGill Contact: Wayne Huxtable

Title: Maintenance & Operations Supervisor Title: Technician

Page of 1 34United Fire Protection - Atlanta Download Date: 05/20/2023

Executive Summary Generated by: BuildingReports.com

Building Information Building: Fort McPherson VAMC Bldg 130 Contact: Mike McGill

Address: 1701 Hardee Ave SW Phone: 14043216111

Address: Fax:

City/State/ZIP Code: Atlanta, GA 30310 Mobile:

Country: United States of America Email:

Inspection Performed By Company: United Fire Protection - Atlanta Inspector: Wayne Huxtable

Address: 2150 Boggs Rd Bldg 100 Phone: 770-771-0999

Address: Suite 140 Fax:

City/State/ZIP Code: Duluth, GA 30096 Mobile:

Country: United States of America Email: whuxtable@united-fire.com

Page of 2 34United Fire Protection - Atlanta Download Date: 05/20/2023

Inspection Completion Date: May 18, 2023 Building: Fort McPherson VAMC Bldg 130 EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(b-g)

Devices Tested This

Quarter Pass Fail Tested YTD

(2023) Untested YTD

(2023) Total

Quantity Air Maintenance Device 1 1 0 1 0 1

Pressure Switch 2 2 0 2 0 2

EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)

Devices Tested This

Quarter Pass Fail Tested YTD

(2023) Untested YTD

(2023) Total

Quantity Tamper Switch 14 14 0 14 0 14

Waterflow Switch 8 8 0 8 0 8

LS 02.01.35 EP 07 At least six spare sprinkler heads that correspond to the types and temperature rating of the hospital's sprinkler heads, with associated wrenches, are kept in a cabinet that will not exceed 100F. NFPA 25-2020: 5.4.1

Devices Tested This

Quarter Pass Fail Tested YTD

(2023) Untested YTD

(2023) Total

Quantity Sprinkler Box 3 3 0 3 0 3

Sprinkler Box Spares 6 6 0 6 0 6

LS 02.01.35 EP 14 All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

Devices Tested This

Quarter Pass Fail Tested YTD

(2023) Untested YTD

(2023) Total

Quantity Drain 1 1 0 1 0 1

Air Compressor 1 1 0 1 0 1

Check Valve 7 7 0 7 0 7

Control Valve 15 15 0 15 0 15

Dry Pipe Valve 1 1 0 1 0 1

Gauge 9 9 0 9 0 9

Inspector's Test 5 5 0 5 0 5

Manifold 1 1 0 1 0 1

Wrenches 1 1 0 1 0 1

Total Device Count: 75

Page of 3 34United Fire Protection - Atlanta Download Date: 05/20/2023

Certification

Company: United Fire Protection - Atlanta Building: Fort McPherson VAMC Bldg 130

Inspector: Wayne Huxtable Contact: Mike McGill

Page of 4 34United Fire Protection - Atlanta Download Date: 05/20/2023

Inspection & Testing Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 130 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 01

Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(b-g)

Automatic air pressure maintenance devices, if provided, shall be tested yearly at the time of the annual preaction or deluge valve trip test, in accordance with the manufacturer's instructions. (NFPA 25-20 13.4.3.2.13) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Air Maintenance Device 1 1 0 1 1

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Air Maintenance Device

2nd Stairwell 2 Dry System 57780028 0 08/15-P 10/28-P 02/09-P 05/17-P

Device Total: 1 Return to Executive Summary

Page of 5 34United Fire Protection - Atlanta Download Date: 05/20/2023

EC 02.03.05 EP 01

Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; and room temperature supervisory. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(b-g)

Operate switch and verify receipt of signal is obtained where the required pressure is increased or decreased a maximum 10 psi from the required pressure level. (NFPA 72-19 Table 14.4.3.2 (17)(9b)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Pressure Switch 2 2 0 2 2

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Pressure Switch 2nd Stairwell 2 Dry System

High Pressure 44133525 1-M1-83 08/15-P 10/28-P 02/09-P 05/17-P

Pressure Switch 2nd Stairwell 2 Dry System Low Air

44133524 1-M84 08/15-P 10/28-P 02/09-P 05/17-P

Device Total: 2 Return to Executive Summary

Page of 6 34United Fire Protection - Atlanta Download Date: 05/20/2023

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)

Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Tamper Switch 14 14 0 14 14

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Tamper Switch Basement Boiler Room

Backflow CV 1 67977794 1-M1-1 08/15-P 10/28-P 05/17-P

Tamper Switch Basement Boiler Room Backflow CV 2

67977795 1-M1-2 08/15-P 10/28-P 02/09-P 05/17-P

Tamper Switch Basement Boiler Room Main Feed for bldg

67977797 1-M1-4 08/15-P 10/28-P 02/09-P 05/17-P

Tamper Switch Basement Boiler Room Test Header

67977796 1-M1- 08/15-P 10/28-P 02/09-P 05/17-P

Tamper Switch Basement 130 Wet 67978981 1-M1-7 05/17-P Tamper Switch 1st Stairwell 2 Zone 1-1 67978983 1-M1-1 05/17-P Tamper Switch 1st Stairwell 2 Zone 1-2 67978984 1-M1-33 05/17-P Tamper Switch 2nd Stairwell 2 Passenger

Elevator 44133527 1-M1-19 08/15-P 10/28-P 05/17-P

Tamper Switch 2nd Stairwell 2 Zone 2-1 67978986 1-M1-79 05/17-P Tamper Switch 2nd Stairwell 2 Zone 2-2 67978987 1-M1-80 05/17-P Tamper Switch Basement GD-002 Stairwell

2 Passenger Elevator 67978982 1-M1-5 05/17-P

Tamper Switch Basement GD-002 Stairwell 2 Passenger Elevator

44133542 1-M1-5 08/15-P 10/28-P 02/09-P 05/18-P

Tamper Switch Ground outside @ B building 57780010 1 08/15-P 10/28-P 02/09-P 05/18-P Tamper Switch Ground outside Between D and C 57780054 1 08/15-P 10/28-P 02/09-P 05/18-P

Device Total: 14 Return to Executive Summary

Page of 7 34United Fire Protection - Atlanta Download Date: 05/20/2023

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2019) Table 14.4.3.2 (17)(10)(a) & (17)(11)

Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-19 Table

14.4.3.2 (17)(11)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Waterflow Switch 8 8 0 8 8

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Waterflow Switch Basement Wet 57780039 1-M1-7 08/15-P 10/28-P 02/09-P 05/17-P Waterflow Switch Basement 130 Wet 44133540 1-M1-7 08/15-P 10/28-P 02/09-P 05/17-P Waterflow Switch 1st Stairwell 2 Zone 1-1 44133499 1-M1-34 08/15-P 10/28-P 02/09-P 05/17-P Waterflow Switch 1st Stairwell 2 Zone 1-2 44133504 1-M1-33 08/15-P 10/28-P 02/09-P 05/17-P Waterflow Switch 2nd Stairwell 2 Dry System 44133526 1 08/15-P 10/28-P 05/17-P Waterflow Switch 2nd Stairwell 2 Passenger

Elevator 44133528 1-M1-18 08/15-P 10/28-P 05/17-P

Waterflow Switch 2nd Stairwell 2 Passenger Elevator

44133543 1-M1-18 08/15-P 10/28-P 05/18 Removed

Waterflow Switch 2nd Stairwell 2 Zone 2-1 44133510 1-M1-79 08/15-P 10/28-P 02/09-P 05/17-P Waterflow Switch 2nd Stairwell 2 Zone 2-2 44133515 1-M1-80 08/15-P 10/28-P 02/09-P 05/17-P

Device Total: 8 Return to Executive Summary

Page of 8 34United Fire Protection - Atlanta Download Date: 05/20/2023

LS 02.01.35 EP 07

At least six spare sprinkler heads that correspond to the types and temperature rating of the hospital's sprinkler heads, with associated wrenches, are kept in a cabinet that will not exceed 100F. NFPA 25-2020: 5.4.1

A supply of at least six spare sprinklers shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. (NFPA 25-20 5.4.1.5) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Sprinkler Box 3 3 0 3 3

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Sprinkler Box Basement Boiler Room Main

Feed for bldg 57780031 0 08/15-P 10/28-P 05/17-P

Sprinkler Box Basement Boiler Room Main Feed for bldg

57780034 0 08/15-P 10/28-P 05/17-P

Sprinkler Box Basement 130 Boiler Room Main Feed for bldg

57780029 0 08/15-P 10/28-P 05/17-P

Device Total: 3 Return to Executive Summary

Page of 9 34United Fire Protection - Atlanta Download Date: 05/20/2023

LS 02.01.35 EP 07

At least six spare sprinkler heads that correspond to the types and temperature rating of the hospital's sprinkler heads, with associated wrenches, are kept in a cabinet that will not exceed 100F. NFPA 25-2020: 5.4.1

A supply of at least six spare sprinklers shall be maintained on the premises so that any sprinklers that have operated or been damaged in any way can be promptly replaced. (NFPA 25-20 5.4.1.5) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Sprinkler Box Spares 6 6 0 6 6

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Sprinkler Box Spares Basement Boiler Room Main

Feed for bldg 57780030 0 08/15-P 10/28-P 05/17-P

Sprinkler Box Spares Basement Boiler Room Main Feed for bldg

57780032 0 08/15-P 10/28-P 05/17-P

Sprinkler Box Spares Basement Boiler Room Main Feed for bldg

57780037 0 08/15-P 10/28-P 05/17-P

Sprinkler Box Spares Basement Boiler Room Main Feed for bldg

57780035 0 08/15-P 10/28-P 05/17-P

Sprinkler Box Spares Basement Boiler Room Main Feed for bldg

57780036 0 08/15-P 10/28-P 05/17-P

Sprinkler Box Spares Basement 130 Boiler Room Main Feed for bldg

57780033 0 08/15-P 10/28-P 05/17-P

Device Total: 6 Return to Executive Summary

Page of 10 34United Fire Protection - Atlanta Download Date: 05/20/2023

LS 02.01.35 EP 14

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

A main drain test shall be conducted annually for each water supply lead-in to a building water-based fire protection system to determine whether there has been a change in the condition of the water supply. (NFPA 25-20 13.2.3) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Drain 1 1 0 1 1

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Drain Basement 130 Boiler Room

Main Feed for bldg 44133537 0 08/15-P 10/28-P 05/17-P

Page of 11 34United Fire Protection - Atlanta Download Date: 05/20/2023

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

Compressors used in conjunction with dry pipe sprinkler systems shall be maintained in accordance with the manufacturer's instructions. (NFPA 25-20 5.4.2.4) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Air Compressor 1 1 0 1 1

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Air Compressor 2nd Stairwell 2 Dry System 67977852 0 08/15-P 10/28-P 02/09-P 05/17-P

Page of 12 34United Fire Protection - Atlanta Download Date: 05/20/2023

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

Internal components shall be cleaned, repaired, or replaced as necessary in accordance with the manufacturer's instructions. (NFPA 25-20 13.4.2.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Check Valve 7 7 0 7 7

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Check Valve Basement Wet 57780040 1 08/15-P 10/28-P 05/17-P Check Valve Basement 130 Wet 44133539 1 08/15-P 10/28-P 05/17-P Check Valve Basement 130 Boiler Room

Main Feed for bldg 44133534 1 08/15-P 10/28-P 05/17-P

Check Valve 1st Stairwell 2 Zone 1-1 44133498 1 08/15-P 10/28-P 05/17-P Check Valve 1st Stairwell 2 Zone 1-2 44133503 1 08/15-P 10/28-P 05/17-P Check Valve 2nd Stairwell 2 Zone 2-1 44133508 1 08/15-P 10/28-P 05/17-P Check Valve 2nd Stairwell 2 Zone 2-2 44133513 1 08/15-P 10/28-P 05/17-P

Device Total: 7 Return to Executive Summary

Page of 13 34United Fire Protection - Atlanta Download Date: 05/20/2023

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-19 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Control Valve 15 15 0 15 15

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Control Valve Basement Boiler Room

Backflow CV 1 44133530 1-M1-1 08/15-P 10/28-P 02/09-P 05/17-P

Control Valve Basement Boiler Room Backflow CV 2

44133531 1-M1-2 08/15-P 10/28-P 02/09-P 05/17-P

Control Valve Basement Boiler Room Test Header

44133532 1-M1- 08/15-P 10/28-P 02/09-P 05/17-P

Control Valve Basement 130 Wet 44133538 1-M1-7 08/15-P 10/28-P 02/09-P 05/17-P Control Valve Basement 130 Boiler Room

Main Feed for bldg 44133533 1-M1-4 08/15-P 10/28-P 02/09-P 05/17-P

Control Valve 1st Stairwell 2 Zone 1-1 44133497 1-M1-1 08/15-P 10/28-P 02/09-P 05/17-P Control Valve 1st Stairwell 2 Zone 1-2 44133502 1-M1-33 08/15-P 10/28-P 02/09-P 05/17-P Control Valve 2nd Stairwell 2 Dry System 44133518 1-M1-81 08/15-P 10/28-P 02/09-P 05/17-P Control Valve 2nd Stairwell 2 Passenger

Elevator 67978985 1-M1-18 05/17-P

Control Valve 2nd Stairwell 2 Zone 2-1 44133507 1-M1-79 08/15-P 10/28-P 02/09-P 05/17-P Control Valve 2nd Stairwell 2 Zone 2-2 44133512 1-M1-80 08/15-P 10/28-P 02/09-P 05/17-P Control Valve Basement GD-002 Stairwell

2 Passenger Elevator 44133529 1-M1-5 08/15-P 10/28-P 05/17-P

Control Valve Basement GD-002 Stairwell 2 Passenger Elevator

57780038 1-M1-5 08/15-P 10/28-P 02/09-P 05/17-P

Control Valve Ground outside @ B building 57780011 1 08/15-P 10/28-P 02/09-P 05/18-P Control Valve Ground outside Between D and C 57780053 1 08/15-P 10/28-P 02/09-P 05/18-P

Device Total: 15 Return to Executive Summary

Page of 14 34United Fire Protection - Atlanta Download Date: 05/20/2023

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

Each dry pipe valve shall be trip tested annually during warm weather. (NFPA 25-20 13.4.5.2.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Dry Pipe Valve 1 1 0 1 1

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Dry Pipe Valve 2nd Stairwell 2 Passenger

Elevator 44133520 0 08/15-P 10/28-P 02/09-P 05/17-P

Page of 15 34United Fire Protection - Atlanta Download Date: 05/20/2023

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

Gauges shall be replaced every 5 years or tested every 5 years by comparison with a calibrated gauge. (NFPA 25- 20 13.2.5.2) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Gauge 9 9 0 9 9

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Gauge Basement 130 Boiler Room

Main Feed for bldg 44133536 0 08/15-P 10/28-P 05/17-P

Gauge Basement 130 Boiler Room Main Feed for bldg

44133535 0 08/15-P 10/28-P 05/17-P

Gauge 1st Stairwell 2 Zone 1-1 57780013 0 08/15-P 10/28-P 05/17-P Gauge 1st Stairwell 2 Zone 1-2 57780022 0 08/15-P 10/28-P 05/17-P Gauge 2nd Stairwell 2 Dry System 57780025 0 08/15-P 10/28-P 05/17-P Gauge 2nd Stairwell 2 Dry System 57780027 0 08/15-P 10/28-P 05/17-P Gauge 2nd Stairwell 2 Zone 2-1 57780024 0 08/15-P 10/28-P 05/17-P Gauge 2nd Stairwell 2 Zone 2-1 44133509 0 08/15-P 10/28-P 05/17-P Gauge 2nd Stairwell 2 Zone 2-2 57780023 0 05/17-P

Device Total: 9 Return to Executive Summary

Page of 16 34United Fire Protection - Atlanta Download Date: 05/20/2023

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

Testing of pressure switch type waterflow alarm devices on wet pipe systems shall be accomplished by opening the inspector's test connection (NFPA 25-20 5.3.3.3) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Inspector's Test 5 5 0 5 5

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Inspector's Test 1st Stairwell 2 Zone 1-1 44133501 0 08/15-P 10/28-P 05/17-P Inspector's Test 1st Stairwell 2 Zone 1-1 44133541 0 08/15-P 10/28-P 05/17-P Inspector's Test 1st Stairwell 2 Zone 1-2 44133506 0 08/15-P 10/28-P 05/17-P Inspector's Test 2nd Stairwell 2 Zone 2-1 44133511 0 08/15-P 10/28-P 02/09-P 05/17-P Inspector's Test 2nd Stairwell 2 Zone 2-2 44133516 0 08/15-P 10/28-P 02/09-P 05/17-P

Device Total: 5 Return to Executive Summary

Page of 17 34United Fire Protection - Atlanta Download Date: 05/20/2023

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Manifold 1 1 0 1 1

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Manifold 2nd Stairwell 2 Passenger

Elevator 44133519 0 08/15-P 10/28-P 02/09-P 05/17-P

Page of 18 34United Fire Protection - Atlanta Download Date: 05/20/2023

All other Life Safety Code automatic extinguishing requirements related to NFPA 101- 2021 18/19.3.5

One sprinkler wrench as specified by the sprinkler manufacturer shall be provided in the cabinet for each type of sprinkler installed to be used for the removal and installation of sprinklers in the system. (NFPA 25-20 5.4.1.5.5) Devices Tested Q2/23 Pass Q2/23 Fail Q2/23 Tested YTD (2023) Total Quantity Wrenches 1 1 0 1 1

Device Type Location ScanID Address Q3/22 Q4/22 Q1/23 Q2/23 Wrenches Basement Boiler Room Main

Feed for bldg 57780055 0 08/15-P 10/28-P 05/17-P

Page of 19 34United Fire Protection - Atlanta Download Date: 05/20/2023

Service Summary Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 130 The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Passed Air Compressor Annual 1 Air Maintenance Device Annual 1 Check Valve Annual 7 Control Valve Annual 15 Drain Annual 1 Dry Pipe Valve Annual 1 Gauge Annual 9 Inspector's Test Annual 5 Manifold Annual 1 Pressure Switch Annual 2 Sprinkler Box Spares Annual 6 Sprinkler Box Annual 3 Tamper Switch Annual 14 Waterflow Switch Annual 8 Wrenches Annual 1

Total 75 Grand Total 75

Page of 20 34United Fire Protection - Atlanta Download Date: 05/20/2023

Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg

This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Location Number of Turns

Zone /Address

OK ScanID

Control Valve Supervisory Basement 130 Wet 1-M1-7 67978981

OS&Y Supervisory Basement Boiler Room Test Header

1-M1- 67977796

OS&Y Supervisory Basement Boiler Room Main Feed for bldg

1-M1-4 67977797

OS&Y Supervisory 1st Stairwell 2 Zone 1-2 1-M1-33 67978984 OS&Y Supervisory 1st Stairwell 2 Zone 1-1 1-M1-1 67978983 OS&Y Supervisory 2nd Stairwell 2 Zone 2-2 1-M1-80 67978987 OS&Y Supervisory 2nd Stairwell 2 Zone 2-1 1-M1-79 67978986

Control Valve Supervisory 2nd Stairwell 2 Passenger Elevator

1-M1-19 44133527

Control Valve Supervisory Basement GD-002 Stairwell 2 Passenger Elevator

1-M1-5 67978982

Control Valve Supervisory Basement GD-002 Stairwell 2 Passenger Elevator

1-M1-5 44133542

Control Valve Supervisory Ground outside @ B building 1 57780010 Control Valve Supervisory Ground outside Between D and C 1 57780054

Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VS-SP 1’’ 1-M1-7 57780039 Vane Potter Electric VSR 30.37000 3 1-M1-7 44133540 Vane Potter Electric VSR 30.20999 4" 1-M1-33 44133504 Vane Potter Electric VSR 30.39999 4" 1-M1-34 44133499 Vane Potter Electric VSR 30.40999 4" 1-M1-80 44133515 Vane Potter Electric VSR 30 4" 1-M1-79 44133510 Vane Potter Electric VS-SP 1" 1-M1-18 44133528

Components Check Valve javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978981');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977796');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977797');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978984');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978983');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978987');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978986');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133527');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978982');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133542');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780010');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780054');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780039');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133540');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133504');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133499');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133515');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133510');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133528');

Page of 21 34United Fire Protection - Atlanta Download Date: 05/20/2023

Type Location Internal Date Size OK ScanID Grooved Basement 130 Wet 03/29/2018 4" 44133539 Grooved Basement Wet 03/29/2018 4" 57780040

Grooved Basement 130 Boiler Room Main Feed for bldg

03/29/2012 8" 44133534

Grooved 1st Stairwell 2 Zone 1-2 03/29/2018 4" 44133503 Grooved 1st Stairwell 2 Zone 1-1 03/29/2018 3" 44133498 Grooved 2nd Stairwell 2 Zone 2-2 03/29/2018 3" 44133513 Grooved 2nd Stairwell 2 Zone 2-1 03/29/2018 3" 44133508

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Anvil AN7722-3A Basement 130 Wet

4" Open Supervised 44133538

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Kennedy KS-FW

Basement 130 Boiler Room Main Feed for bldg

4" Open Supervised 44133533

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Kennedy KS-FW Basement Boiler Room Test Header

6" Closed Supervised 44133532

Description

CV 2

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Anvil AN7722-3A 1st Stairwell 2 Zone 1-2

3" Open Supervised 44133502

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Anvil AN7722-3A 1st Stairwell 2 Zone 1-1

4" Open Supervised 44133497

Description javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133539');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780040');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133534');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133503');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133498');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133513');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133508');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133538');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133533');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133532');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133502');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133497');

Page of 22 34United Fire Protection - Atlanta Download Date: 05/20/2023

Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Anvil AN7722-3A 2nd Stairwell 2 Zone 2-2

4" Open Supervised 44133512

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Anvil AN7722-3A 2nd Stairwell 2 Zone 2-1

4" Open Supervised 44133507

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Potter Electric VS-SP 2nd Stairwell 2 Passenger Elevator

1" Open Supervised 67978985

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Milwaukee BB-SCS

Basement GD- 002 Stairwell 2 Passenger Elevator

1" Open Supervised 44133529

Description Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Milwaukee BB-SCS

Basement GD- 002 Stairwell 2 Passenger Elevator

1" Open Supervised 57780038

Description Isolation

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

Post Indicator Valve

Mueller Ground outside Between D and C

6" Open Locked & Supervised

57780053

Description javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133512');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133507');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978985');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133529');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780038');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780053');

Page of 23 34United Fire Protection - Atlanta Download Date: 05/20/2023

Main Control

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Post Indicator Valve

Mueller Ground outside @ B building

6" Open Locked & Supervised

57780011

Description Main Control

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1324 65 30.40 44133501

Location 1st Stairwell 2 Zone 1-1

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1324 65 26 30.21 44133506

Location 1st Stairwell 2 Zone 1-2

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 100 65 45 30.37 44133541

Location 1st Stairwell 2 Zone 1-1

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1324 65 45 30.40 44133516

Location 2nd Stairwell 2 Zone 2-2

Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID

AGF 1324 65 33 30.56 44133511

Location 2nd Stairwell 2 Zone 2-1

Devices Drain

Type Location Size Supply psi Restored psi

Residual psi Sec OK ScanID

Combination Basement 130 Boiler Room Main Feed for bldg

2" 60 60 40 30.45000 44133537

Gauge javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780011');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133501');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133506');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133541');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133516');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133511');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133537');

Page of 24 34United Fire Protection - Atlanta Download Date: 05/20/2023

Location Service Date Basement 130 Boiler Room Main Feed for bldg 03/29/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Lansdale 70 Air/Water 1/4 44133536

Gauge Location Service Date Basement 130 Boiler Room Main Feed for bldg 03/29/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Lansdale 75 Air/Water 1/4 44133535

Gauge Location Service Date 1st Stairwell 2 Zone 1-2 05/15/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID City Pressure Lansdale Wika 65 Air/Water 1/4 57780022

Gauge Location Service Date 1st Stairwell 2 Zone 1-1 03/29/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID City Pressure Lansdale 65 Air/Water 1/4 57780013

Gauge Location Service Date 2nd Stairwell 2 Zone 2-2 05/15/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Lansdale 50 Air/Water 1/4 57780023

Gauge Location Service Date 2nd Stairwell 2 Zone 2-1 05/15/2026

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Lansdale Wika 50 Air/Water 1/4 57780024

Gauge Location Service Date 2nd Stairwell 2 Zone 2-1 03/29/2012

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Wika Wika 65 Air/Water 1/4 44133509

Sprinkler Box

Qty Tool Available?

SIN List? Size Manufacturer Location OK ScanID

6 Yes Yes 6 unit Viking Basement 130 Boiler Room Main Feed for bldg

57780029 javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133536');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133535');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780022');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780013');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780023');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780024');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133509');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780029');

Page of 25 34United Fire Protection - Atlanta Download Date: 05/20/2023

6 Yes Yes 6 unit Viking Basement Boiler Room Main Feed for bldg

57780031

6 Yes Yes 6 unit Viking Basement Boiler Room Main Feed for bldg

57780034

Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID

6 Pendant Viking Basement Boiler Room Main Feed for bldg

57780030

Temperature KFactor Size Finish Response Time 200 4.2 0.5 Chrome Fast Response

Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID

1 Horizontal Sidewall Viking Basement Boiler Room Main Feed for bldg

57780032

Temperature KFactor Size Finish Response Time 200 4.2 0.5 Chrome Fast Response

Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID

1 Horizontal Sidewall Viking Basement 130 Boiler Room Main Feed for bldg

57780033

Temperature KFactor Size Finish Response Time 200 4.2 3/4 “ Brass Fast Response

Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID

1 Upright Viking Basement Boiler Room Main Feed for bldg

57780037

Temperature KFactor Size Finish Response Time 200 4.2 0.5 Brass Fast Response

Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID

3 Attic Tyco Basement Boiler Room Main Feed for bldg

57780035

Temperature KFactor Size Finish Response Time 212* 1/2” Brass Fast Response

Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID

3 Upright Viking Basement Boiler Room Main Feed for bldg

57780036

Temperature KFactor Size Finish Response Time 212* 4.2 1/2” Brass Fast Response

Wrenches javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780031');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780034');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780030');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780032');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780033');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780037');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780035');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780036');

Page of 26 34United Fire Protection - Atlanta Download Date: 05/20/2023

Qty Type Manufacturer Location OK ScanID

1 Sprinkler Reliable Basement Boiler Room Main Feed for bldg

57780055 javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780055');

Page of 27 34United Fire Protection - Atlanta Download Date: 05/20/2023

Dry Pipe Fire Sprinkler Systems Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg

Building-Attic, Building-130

This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Air Compressor Location Mfr. Model # Phase On psi Off psi Serial No.

2nd Stairwell 2 Dry System

General Air

1 20 40

Type Description Rated Speed Horsepower Volts Amps OK ScanID

Automatic Tank 1723 1 120 67977852

Air Maintenance Device Type Model # Location Install Date Air Pressure ScanID Pressure Reducing Wika 2nd Stairwell 2 Dry System 07/11/2018 40 57780028

Alarms Pressure Switch Type Description Manufacturer Low High Zone/Address OK ScanID Low Supervisory Potter Electric 15 30 1-M84 44133524 High Alarm Potter Electric 0 50 1-M1-83 44133525

Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter electric VSR 4 1 44133526

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID

Butterfly Anvil AN7722-3A 2nd Stairwell 2 Dry System

4" Open Supervised 44133518

Description Isolation

Dry Pipe Valve Manufacturer Model # Location Internal Date OK ScanID Viking F-2 2nd Stairwell 2 Passenger Elevator 03/29/2018 44133520

Type Status Position Size Serial # Grooved Supervised Trim Open 4"

Total Timing Partial Trip javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977852');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780028');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133524');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133525');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133526');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133518');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133520');

Page of 28 34United Fire Protection - Atlanta Download Date: 05/20/2023

Water psi Air Pressure Trip Air Trip Time (sec) Date Full Trip Date 50280118 50 15 35 34 03/29/2012 05/17/2023

Manifold Location Manufacturer Size ScanID

2nd Stairwell 2 Passenger Elevator United Brass 2" 44133519

Devices Gauge

Location Service Date 2nd Stairwell 2 Dry System 05/27/2025

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Lansdale 65 Air/Water 1/4 57780025

Gauge Location Service Date 2nd Stairwell 2 Dry System 03/29/2025

Type Manufacturer Model # Static psi Fill Type Size OK ScanID Air Pressure Wika Wika 30 Air/Water 1/4 57780027 javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133519');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780025');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780027');

Page of 29 34United Fire Protection - Atlanta Download Date: 05/20/2023

Backflow Test & Maintenance Report Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg

This section lists out all the devices and components that have been associated with a Cross Connection Control System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.

Alarms Tamper Switch

Type Description Location Number of Turns

Zone /Address

OK ScanID

OS&Y Supervisory Basement Boiler Room Backflow

CV 2

1-M1-2 67977795

OS&Y Supervisory Basement Boiler Room Backflow

CV 1

1-M1-1 67977794

Components Control Valve

Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Kennedy KS-FW Basement Boiler Room Backflow CV 2

6" Open Supervised 44133531

Description

CV 2

Control Valve Type Manufacturer Model Location Size Position Status OK ScanID

OS&Y Kennedy KS-FW Basement Boiler Room Backflow CV 1

6" Open Supervised 44133530

Description

CV 1

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977795');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977794');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133531');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133530');

Page of 30 34United Fire Protection - Atlanta Download Date: 05/20/2023

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 130 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Air Compressor Pump 1.33% 1

Air Maintenance Device Pump 1.33% 1

Check Valve Valve 9.33% 7

Control Valve Valve 20.00% 15

Drain Device 1.33% 1

Dry Pipe Valve Valve 1.33% 1

Gauge Device 12.00% 9

Inspector's Test Valve 6.67% 5

Manifold Valve 1.33% 1

Pressure Switch Alarm 2.67% 2

Sprinkler Box Sprinkler 4.00% 3

Sprinkler Box Spares Sprinkler 8.00% 6

Tamper Switch Alarm 18.67% 14

Waterflow Switch Alarm 10.67% 8

Wrenches Sprinkler 1.33% 1

Device Type Qty Model # Type Description Install Date

In Service - 1 Year to 2 Years Wet Pipe

Gauge 1 City Pressure 05/28/2021 Gauge 1 Supply Pressure 05/28/2021 Gauge 1 Supply Pressure 05/27/2021

Building-Attic Dry Pipe, Building-130 Gauge 1 Supply Pressure 05/27/2021 Gauge 1 Wika Air Pressure 05/27/2021

In Service - 2 Years to 3 Years Wet Pipe

Gauge 1 System Pressure 05/15/2021 Gauge 1 Wika 05/15/2021 Gauge 1 Wika City Pressure 05/15/2021

In Service - 3 Years to 5 Years Wet Pipe

Gauge 1 Wika 07/11/2018

Page of 31 34United Fire Protection - Atlanta Download Date: 05/20/2023

Building-Attic Dry Pipe, Building-130 Air Compressor 1 Automatic Tank 07/11/2018 Waterflow Switch 1 VSR Vane Alarm 07/11/2018 Air Maintenance Device 1 Wika Pressure Reducing 07/11/2018

In Service - 5 Years to 10 Years Wet Pipe

Inspector's Test 1 100 03/29/2018 Inspector's Test 4 1324 03/29/2018 Check Valve 6 78FP Grooved 03/29/2018 Control Valve 5 AN7722-3A Butterfly Isolation 03/29/2018 Tamper Switch 1 AN7722-3A Control Valve Supervisory 03/29/2018 Tamper Switch 4 AN7722-3A OS&Y Supervisory 03/29/2018 Waterflow Switch 1 VS-SP Vane Alarm 03/29/2018 Waterflow Switch 5 VSR Vane Alarm 03/29/2018

Building-Attic Dry Pipe, Building-130 Control Valve 1 AN7722-3A Butterfly Isolation 03/29/2018

In Service - 10 Years to 15 Years Cross Conn. Control

Control Valve 1 KS-FW OS&Y CV 1 03/29/2012 Control Valve 1 KS-FW OS&Y CV 2 03/29/2012 Tamper Switch 2 OSYSU-2 OS&Y Supervisory 03/29/2012

Wet Pipe Drain 1 1000 Combination 03/29/2012 Control Valve 1 KS-FW OS&Y CV 2 03/29/2012 Control Valve 1 KS-FW OS&Y Main Control 03/29/2012 Control Valve 1 BB-SCS Butterfly Isolation 03/29/2012 Control Valve 1 BB-SCS Butterfly Main Control 03/29/2012 Tamper Switch 2 BB-SCS Control Valve Supervisory 03/29/2012 Control Valve 2 Post Indicator Valve Main Control 03/29/2012 Control Valve 1 VS-SP OS&Y Main Control 03/29/2012 Tamper Switch 1 OSYSU-2 OS&Y Supervisory 03/29/2012 Tamper Switch 2 PIVS-2 Control Valve Supervisory 03/29/2012 Tamper Switch 1 PTS-C Control Valve Supervisory 03/29/2012 Waterflow Switch 1 VS-SP Vane Alarm 03/29/2012 Tamper Switch 1 OSYSU-2 OS&Y Supervisory 03/29/2012 Wrenches 1 Sprinkler 03/29/2012 Sprinkler Box Spares 1 BB1 / TY3180 Attic 03/29/2012 Check Valve 1 F-1 Grooved 03/29/2012 Sprinkler Box 3 03/29/2012 Sprinkler Box Spares 2 Horizontal Sidewall 03/29/2012

Page of 32 34United Fire Protection - Atlanta Download Date: 05/20/2023

Sprinkler Box Spares 1 M 10 Upright 03/29/2012 Sprinkler Box Spares 1 M-10 Pendant 03/29/2012 Sprinkler Box Spares 1 m Upright 03/29/2012

Building-Attic Dry Pipe, Building-130 Pressure Switch 1 PS-10 High Alarm 03/29/2012 Pressure Switch 1 PS-40 Low Supervisory 03/29/2012 Manifold 1 F-2 03/29/2012 Dry Pipe Valve 1 F-2 Grooved 03/29/2012

Page of 33 34United Fire Protection - Atlanta Download Date: 05/20/2023

Zone Address Report Generated by: BuildingReports.com

Building: Fort McPherson VAMC Bldg 130 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID

Control Panel 1 M1- Control Valve Basement Boiler Room Test Header OS&Y 44133532 M1- Tamper Switch Basement Boiler Room Test Header OS&Y 67977796

M1-1 Control Valve Basement Boiler Room Backflow CV 1 OS&Y 44133530 M1-1 Tamper Switch Basement Boiler Room Backflow CV 1 OS&Y 67977794 M1-1 Control Valve 1st Stairwell 2 Zone 1-1 Butterfly 44133497 M1-1 Tamper Switch 1st Stairwell 2 Zone 1-1 OS&Y 67978983 M1-2 Control Valve Basement Boiler Room Backflow CV 2 OS&Y 44133531 M1-2 Tamper Switch Basement Boiler Room Backflow CV 2 OS&Y 67977795 M1-4 Tamper Switch Basement Boiler Room Main Feed for bldg OS&Y 67977797 M1-4 Control Valve Basement 130 Boiler Room Main Feed for bldg

OS&Y 44133533

M1-5 Control Valve Basement GD-002 Stairwell 2 Passenger Elevator

Butterfly 44133529

M1-5 Control Valve Basement GD-002 Stairwell 2 Passenger Elevator

Butterfly 57780038

M1-5 Tamper Switch Basement GD-002 Stairwell 2 Passenger Elevator

Control Valve 44133542

M1-5 Tamper Switch Basement GD-002 Stairwell 2 Passenger Elevator

Control Valve 67978982

M1-7 Waterflow Switch Basement Wet Vane 57780039 M1-7 Control Valve Basement 130 Wet Butterfly 44133538 M1-7 Tamper Switch Basement 130 Wet Control Valve 67978981 M1-7 Waterflow Switch Basement 130 Wet Vane 44133540 M1-18 Control Valve 2nd Stairwell 2 Passenger Elevator OS&Y 67978985 M1-18 Waterflow Switch 2nd Stairwell 2 Passenger Elevator Vane 44133528 M1-19 Tamper Switch 2nd Stairwell 2 Passenger Elevator Control Valve 44133527 M1-33 Control Valve 1st Stairwell 2 Zone 1-2 Butterfly 44133502 M1-33 Tamper Switch 1st Stairwell 2 Zone 1-2 OS&Y 67978984 M1-33 Waterflow Switch 1st Stairwell 2 Zone 1-2 Vane 44133504 M1-34 Waterflow Switch 1st Stairwell 2 Zone 1-1 Vane 44133499 M1-79 Control Valve 2nd Stairwell 2 Zone 2-1 Butterfly 44133507 M1-79 Tamper Switch 2nd Stairwell 2 Zone 2-1 OS&Y 67978986 M1-79 Waterflow Switch 2nd Stairwell 2 Zone 2-1 Vane 44133510 M1-80 Control Valve 2nd Stairwell 2 Zone 2-2 Butterfly 44133512 javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133532');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977796');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133530');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977794');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133497');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978983');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133531');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977795');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67977797');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133533');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133529');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780038');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133542');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978982');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','57780039');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133538');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978981');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133540');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978985');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133528');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133527');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133502');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978984');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133504');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133499');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133507');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978986');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133510');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133512');

Page of 34 34United Fire Protection - Atlanta Download Date: 05/20/2023

Address Device Type Location Type ScanID M1-80 Tamper Switch 2nd Stairwell 2 Zone 2-2 OS&Y 67978987 M1-80 Waterflow Switch 2nd Stairwell 2 Zone 2-2 Vane 44133515 M1-81 Control Valve 2nd Stairwell 2 Dry System Butterfly 44133518 M1-83 Pressure Switch 2nd Stairwell 2 Dry System High Pressure High 44133525 M84 Pressure Switch 2nd Stairwell 2 Dry System Low Air Low 44133524 javascript:openEditDevice('load-edit-p2-device','736896','2902390','67978987');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133515');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133518');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133525');

javascript:openEditDevice('load-edit-p2-device','736896','2902390','44133524');

Sprinkler Inspection, Testing and/or Maintenance Certificate
Executive Summary
Inspection & Testing
Service Summary
Wet Pipe Fire Sprinkler Systems
Dry Pipe Fire Sprinkler Systems
Backflow Test & Maintenance Report
Inventory & Warranty Report
Zone Address Report

File details come from the government source that posted it. Updated .