This document includes a fire sprinkler testing and inspection report for Building 128 at the Fort McPherson VA Medical Center in Atlanta, Georgia, as well as the related solicitation number 36C24724Q0269 for fire sprinkler testing services. The report details inspection and testing of 132 fire and life safety devices at the facility in June 2022, with all devices passing. It provides device locations, types, and individual test results. The solicitation is from the Department of Veterans Affairs Veterans Health Administration VISN 7 for fire sprinkler testing services. No further details are provided on response date, award date, pricing terms, or incumbent.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
For
Fort McPherson VAMC Bldg 128 1701 Hardee Ave SW
Atlanta, GA 30310
Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with The Joint Commission/VHA Clarification Memorandum on EC & LS Standards effective January 31, 2021
Inspection Completion Date Jun 20, 2022
Building: Fort McPherson VAMC Bldg 128 Company: Vets Fire & Life Safety Contact: Mike McGill Contact: Mike Gill
Title: Maintenance & Operations Supervisor Title: Inspector
Page of 1 23 Executive Summary
Vets Fire & Life Safety Download Date: 06/20/2022
Executive Summary Generated by: BuildingReports.com
Building Information Building: Fort McPherson VAMC Bldg 128 Contact: Mike McGill
Address: 1701 Hardee Ave SW Phone: 4043216111
Address: Fax:
City/State/Zip: Atlanta, GA 30310 Mobile:
Country: United States of America Email:
Inspection Performed By Company: Vets Fire & Life Safety Inspector: Mike Gill
Address: 7 Sherri Ln Phone: 636-543-0165
Address: Fax:
City/State/Zip: Saint Peters, MO 63376-2142 Mobile:
Country: United States of America Email: mike.gill@vflsc.com
System Control Unit Manufacturer: Inspection Date: 06/20/2022 IDC Style:
Model Number: Install Date: 05/09/2018 SLC Style:
Software Version: Version Date: 06/20/2022 NAC Style:
Location: Ground Current Protection:
Page of 2 23
Vets Fire & Life Safety Download Date: 06/20/2022
Inspection Completion Date: Jun 20, 2022 Building: Fort McPherson VAMC Bldg 128 EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
Devices Tested This
Quarter Pass Fail Tested YTD
(2022) Untested YTD
(2022) Total
Quantity Duct Detector 11 11 0 11 0 11
Heat Detector 24 24 0 24 0 24
Pull Station 8 8 0 8 0 8
Smoke Detector 47 47 0 47 0 47
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2019) Table 14.4.3.2 (22)
Devices Tested This
Quarter Pass Fail Tested YTD
(2022) Untested YTD
(2022) Total
Quantity Releasing Device 4 4 0 4 0 4
Speaker/Strobe 16 16 0 16 0 16
Strobe 16 16 0 16 0 16
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment.
NFPA 90A (2021) 6.4.1
Devices Tested This
Quarter Pass Fail Tested YTD
(2022) Untested YTD
(2022) Total
Quantity Duct Detector 11 11 0 11 0 11
LS 02.01.34 EP 02 Protected master fire alarm control panel
Devices Tested This
Quarter Pass Fail Tested YTD
(2022) Untested YTD
(2022) Total
Quantity Control Panel 1 1 0 1 0 1
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Devices Tested This
Quarter Pass Fail Tested YTD
(2022) Untested YTD
(2022) Total
Quantity Battery 4 4 0 4 0 4
Power Supply 1 1 0 1 0 1
Total Device Count: 132
Page of 3 23
Vets Fire & Life Safety Download Date: 06/20/2022
Certification
Company: Vets Fire & Life Safety Building: Fort McPherson VAMC Bldg 128
Inspector: Mike Gill Contact: Mike McGill
Page of 4 23 Notes & Recommendations
Vets Fire & Life Safety Download Date: 06/20/2022
Notes & Recommendations Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Control Panel: 1 -
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
1 Duct Detector 1st Elevator Lobby Passed 46938719 Shuts Down Unit
2 Duct Detector 1st Elevator Lobby @ Mag Doors Passed 46938720 Shuts Down Unit
3 Duct Detector 1st Mech Room 1B143 Passed 46938717 Shuts Down Unit
4 Duct Detector 1st Mech Room 1B143 Passed 46938718 Shuts Down Unit
5 Smoke Detector 1st Elevator Lobby Passed 46938665 Recalls To Primary Floor
6 Smoke Detector 1st Elevator Mech Room 1B131 Passed 46938667 Recalls To Primary Floor
7 Duct Detector 2nd Mech Room 2B201 Passed 46938721 Shuts Down Unit
8 Duct Detector 2nd Mech Room 2B201 Passed 46938722 Shuts Down Unit
9 Smoke Detector 2nd Elevator Lobby Passed 46938688 Recalls To Primary Floor 10 Smoke Detector 2nd Elevator Shaft Passed 46938704
Recalls To Primary Floor 11 Duct Detector Penthouse Attic Center Damper Passed 46938724
Shuts Down Unit 12 Duct Detector Penthouse Attic Center Damper Passed 46938727
Shuts Down Unit javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938719');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938720');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938717');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938718');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938665');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938667');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938721');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938722');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938688');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938704');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938724');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938727');
Page of 5 23 Inspection & Testing
Vets Fire & Life Safety Download Date: 06/20/2022
Inspection & Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 128 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Duct Detector 11 11 0 11 11
Device Type Location ScanID Address Q2/22 Duct Detector 1st Elevator Lobby @ Mag Doors 46938720 1-M1-19 06/20-P Duct Detector 1st Elevator Lobby 46938719 1-M1-17 06/20-P Duct Detector 1st Mech Room 1B143 46938717 1-M1-9 06/20-P Duct Detector 1st Mech Room 1B143 46938718 1-M1-11 06/20-P Duct Detector 2nd Mech Room 2B201 46938721 1-M1-70 06/20-P Duct Detector 2nd Mech Room 2B201 46938722 1-M1-73 06/20-P Duct Detector Penthouse Attic Center Damper 46938727 1-M1-93 06/20-P Duct Detector Penthouse Attic Center Damper 46938726 1-M1-92 06/20-P Duct Detector Penthouse Attic Center Damper 46938724 1-M1-90 06/20-P Duct Detector Penthouse Attic Center Damper 46938723 1-M1-89 06/20-P Duct Detector Penthouse Attic Center Damper 46938725 1-M1-91 06/20-P
Device Total: 11 Return to Executive Summary
Page of 6 23
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically.
(NFPA 72-19 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Heat Detector 24 24 0 24 24
Device Type Location ScanID Address Q2/22 Heat Detector 1st Mech Room 1B143 46938730 1-M1-10 06/20-P Heat Detector 1st Storage Area 1B141 46938729 1-M1-8 06/20-P Heat Detector 1st HAC Room 1B139 46938728 1-M1-3 06/20-P Heat Detector 1st Storage Room 1B119 46938733 1-M1-41 06/20-P Heat Detector 1st Elevator Mech Room 1B131 46938732 1-M1-20 06/20-P Heat Detector 1st Fire Protection 1B142 46938731 1-M1-13 06/20-P Heat Detector 1st Elevator Pit 46938734 1-M1-48 06/20-P Heat Detector 2nd HAC Room 2B131 46938736 1-M1-59 06/20-P Heat Detector 2nd Break Room 2B202 46938738 1-M1-71 06/20-P Heat Detector 2nd Storage Room 2B228 46938737 1-M1-63 06/20-P Heat Detector 2nd Crawl Space 46938735 1-M1-49 06/20-P Heat Detector 2nd Storage Room 2B219 46938741 1-M1-81 06/20-P Heat Detector 2nd Mech Room 2B201 46938740 1-M1-72 06/20-P Heat Detector 2nd Mech Room 2B201 46938739 1-M1-69 06/20-P Heat Detector 2nd Elevator Shaft 46938742 1-M1-99 06/20-P Heat Detector Penthouse Attic South 46938748 1-M1-88 06/20-P Heat Detector Penthouse Attic North 46938751 1-M1-98 06/20-P Heat Detector Penthouse Attic North 46938750 1-M1-97 06/20-P Heat Detector Penthouse Attic North 46938749 1-M1-96 06/20-P Heat Detector Penthouse Attic South 46938746 1-M1-86 06/20-P Heat Detector Penthouse Attic South 46938747 1-M1-87 06/20-P Heat Detector Penthouse Attic Center 46938745 1-M1-95 06/20-P Heat Detector Penthouse Attic Center 46938744 1-M1-94 06/20-P Heat Detector Penthouse Attic Center 46938743 1-M1-85 06/20-P
Device Total: 24 Return to Executive Summary
Page of 7 23
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-19 Table 14.4.3.2 (17)(5)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Pull Station 8 8 0 8 8
Device Type Location ScanID Address Q2/22 Pull Station 1st Exit @ Corr 46938706 1-M1-28 06/20-P Pull Station 1st Stair 3 46938709 1-M1-39 06/20-P Pull Station 1st Entry 1B1C1 46938707 1-M1-31 06/20-P Pull Station 1st Entry 1B1C1 46938708 1-M1-32 06/20-P Pull Station 1st Stair 1 46938705 1-M1-14 06/20-P Pull Station 2nd Corr @ Connector Doors 46938712 1-M1-66 06/20-P Pull Station 2nd Stair 2 46938711 1-M1-62 06/20-P Pull Station 2nd Stair 1 46938710 1-M1-56 06/20-P
Device Total: 8 Return to Executive Summary
Page of 8 23
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2019) Table 14.4.3.2 (17)
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Smoke Detector 47 47 0 47 47
Device Type Location ScanID Address Q2/22 Smoke Detector 1st Connecting Corr Doors 46938668 1-M1-27 06/20-P Smoke Detector 1st Storage Area 1B141 46938661 1-M1-6 06/20-P Smoke Detector 1st Reception 1B102 46938671 1-M1-33 06/20-P Smoke Detector 1st Connecting Corr Doors 46938669 1-M1-29 06/20-P Smoke Detector 1st Data Closest 1B115 46938677 1-M1-42 06/20-P Smoke Detector 1st Work Room 1B105 46938681 1-M1-45 06/20-P Smoke Detector 1st Work Room 1B105 46938680 1-M1-44 06/20-P Smoke Detector 1st Work Room 1B111 46938679 1-M1-43 06/20-P Smoke Detector 1st Work Room 1B111 46938678 1-M1-40 06/20-P Smoke Detector 1st Patient Corr 1C1C2 46938676 1-M1-38 06/20-P Smoke Detector 1st Patient Corr 1C1C2 46938675 1-M1-37 06/20-P Smoke Detector 1st Patient Corr 1C1C2 46938674 1-M1-36 06/20-P Smoke Detector 1st Waiting 1B104 46938673 1-M1-35 06/20-P Smoke Detector 1st Waiting 1B104 46938672 1-M1-34 06/20-P Smoke Detector 1st Entry 1B1C1 46938670 1-M1-30 06/20-P Smoke Detector 1st Corr @ Elevator Mech Room 1B131 46938666 1-M1-18 06/20-P Smoke Detector 1st Patient Corr 1B140 46938663 1-M1-5 06/20-P Smoke Detector 1st Data Closet 1B145 46938664 1-M1-15 06/20-P Smoke Detector 1st Corr @ Stair 1 46938662 1-M1-12 06/20-P Smoke Detector 1st Corr @ Group Room 1B140 46938660 1-M1-4 06/20-P Smoke Detector 1st Corr @ Electric Room 1B134 46938659 1-M1-2 06/20-P Smoke Detector 1st Electric Room 1B134 46938658 1-M1-1 06/20-P Smoke Detector 1st Elevator Lobby 46938665 1-M1-16 06/20-P Smoke Detector 1st Elevator Mech Room 1B131 46938667 1-M1-21 06/20-P Smoke Detector 2nd Patient Corr 2B2C1 46938690 1-M1-61 06/20-P Smoke Detector 2nd Corr @ Mech Room 2B221 46938695 1-M1-74 06/20-P Smoke Detector 2nd HAC Room 2B231 46938689 1-M1-60 06/20-P Smoke Detector 2nd In Stair 2 46938691 1-M1-64 06/20-P Smoke Detector 2nd Corr @ Work Room 2B214 46938698 1-M1-77 06/20-P Smoke Detector 2nd Work Room 2B214 46938703 1-M1-84 06/20-P Smoke Detector 2nd Stair 3 46938702 1-M1-83 06/20-P Smoke Detector 2nd Work Room 2B214 46938701 1-M1-80 06/20-P Smoke Detector 2nd Data Closet 2B215 46938700 1-M1-79 06/20-P Smoke Detector 2nd Corr @ Work Room 2B214 46938699 1-M1-78 06/20-P
Page of 9 23
Vets Fire & Life Safety Download Date: 06/20/2022
Device Type Location ScanID Address Q2/22 Smoke Detector 2nd Corr @ Work Room 2B209 46938697 1-M1-76 06/20-P Smoke Detector 2nd Corr @ Work Room 2B207 46938696 1-M1-75 06/20-P Smoke Detector 2nd Corr @ Break Room 2B202 46938694 1-M1-68 06/20-P Smoke Detector 2nd Connector Corr Doors 46938693 1-M1-67 06/20-P Smoke Detector 2nd Connector Corr Doors 46938692 1-M1-65 06/20-P Smoke Detector 2nd inside Stair 1 46938687 1-M1-57 06/20-P Smoke Detector 2nd Patient Corr 2B2C4 46938686 1-M1-55 06/20-P Smoke Detector 2nd Patient Corr 2B2C4 46938685 1-M1-54 06/20-P Smoke Detector 2nd Patient Corr 2B2C4 46938684 1-M1-53 06/20-P Smoke Detector 2nd Electric Room 2B234 46938682 1-M1-51 06/20-P Smoke Detector 2nd Corr @ Electric Room 2B234 46938683 1-M1-52 06/20-P Smoke Detector 2nd Elevator Lobby 46938688 1-M1-58 06/20-P Smoke Detector 2nd Elevator Shaft 46938704 1-M1-100 06/20-P
Device Total: 47 Return to Executive Summary
Page of 10 23
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2019) Table 14.4.3.2 (22)
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-19 Table 14.4.3.2 (20)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Releasing Device 4 4 0 4 4
Device Type Location ScanID Address Q2/22 Releasing Device 1st Fire Door @ 1B131 46938714 1 06/20-P Releasing Device 1st Storage Room 1B132 46938715 1 06/20-P Releasing Device 1st Fire Door @ 1B131 46938713 1 06/20-P Releasing Device 2nd EMS Closet 2B231 46938716 1 06/20-P
Device Total: 4 Return to Executive Summary
Page of 11 23
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2019) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-19 Table 14.4.3.2 (22)(2)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Speaker/Strobe 16 16 0 16 16
Device Type Location ScanID Address Q2/22 Speaker/Strobe 1st Corr @ Stair 3 46938752 1 06/20-P Speaker/Strobe 1st Corr @ 1B112 46938753 1 06/20-P Speaker/Strobe 1st Corr @ 1B110 46938754 1 06/20-P Speaker/Strobe 1st Storage Room 1B132 46938757 1 06/20-P Speaker/Strobe 1st Corr @ 1B114 46938755 1 06/20-P Speaker/Strobe 1st Main Entrance 46938756 1 06/20-P Speaker/Strobe 1st Mech Room 1B143 46938758 1 06/20-P Speaker/Strobe 1st Sprinkler Room 1B142 46938759 1 06/20-P Speaker/Strobe 2nd Corr @ Electric Room 2B234 46938767 1 06/20-P Speaker/Strobe 2nd Corr @ Open Cube Area 46938763 1 06/20-P Speaker/Strobe 2nd Corr @ Computer Class Room 46938766 1 06/20-P Speaker/Strobe 2nd Corr @ 2B240 46938765 1 06/20-P Speaker/Strobe 2nd Corr @ Open Cube Area 46938764 1 06/20-P Speaker/Strobe 2nd Corr @ 2B208 46938762 1 06/20-P Speaker/Strobe 2nd Elevator Lobby 46938760 1 06/20-P Speaker/Strobe 2nd Corr @ 2B201 46938761 1 06/20-P
Device Total: 16 Return to Executive Summary
Page of 12 23
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2019) Table 14.4.3.2 (22)
For periodic testing, verify that each appliance flashes. (NFPA 72-19 Table 14.4.3.2 (22)(3)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Strobe 16 16 0 16 16
Device Type Location ScanID Address Q2/22 Strobe 1st Women's Restroom 1B117 46938768 1 06/20-P Strobe 1st Men's Restroom 1B113 46938769 1 06/20-P Strobe 1st Men's Restroom 1B135 46938770 1 06/20-P Strobe 1st Women's Restroom 1B137 46938771 1 06/20-P Strobe 1st Storage Room 1B132 46938772 1 06/20-P Strobe 1st Group Room 1B140 46938773 1 06/20-P Strobe 2nd Group Room 2B234 46938783 1 06/20-P Strobe 2nd Group Room 2B238 46938781 1 06/20-P Strobe 2nd Computer Class Room 2B236 46938782 1 06/20-P Strobe 2nd Group Room 2B240 46938780 1 06/20-P Strobe 2nd Break Restroom 46938774 1 06/20-P Strobe 2nd Unisex Restroom 2B241 46938779 1 06/20-P Strobe 2nd Men's Restroom 2B239 46938778 1 06/20-P Strobe 2nd Women's Restroom 2B243 46938777 1 06/20-P Strobe 2nd Men's Restroom 2B213 46938775 1 06/20-P Strobe 2nd Women's Restroom 2B217 46938776 1 06/20-P
Device Total: 16 Return to Executive Summary
Page of 13 23
Vets Fire & Life Safety Download Date: 06/20/2022
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment.
NFPA 90A (2021) 6.4.1
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 19 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Duct Detector 11 11 0 11 11
Device Type Location ScanID Address Q2/22 Duct Detector 1st Elevator Lobby @ Mag Doors 46938720 1-M1-19 06/20-P Duct Detector 1st Elevator Lobby 46938719 1-M1-17 06/20-P Duct Detector 1st Mech Room 1B143 46938717 1-M1-9 06/20-P Duct Detector 1st Mech Room 1B143 46938718 1-M1-11 06/20-P Duct Detector 2nd Mech Room 2B201 46938721 1-M1-70 06/20-P Duct Detector 2nd Mech Room 2B201 46938722 1-M1-73 06/20-P Duct Detector Penthouse Attic Center Damper 46938727 1-M1-93 06/20-P Duct Detector Penthouse Attic Center Damper 46938726 1-M1-92 06/20-P Duct Detector Penthouse Attic Center Damper 46938724 1-M1-90 06/20-P Duct Detector Penthouse Attic Center Damper 46938723 1-M1-89 06/20-P Duct Detector Penthouse Attic Center Damper 46938725 1-M1-91 06/20-P
Device Total: 11 Return to Executive Summary
Page of 14 23
Vets Fire & Life Safety Download Date: 06/20/2022
LS 02.01.34 EP 02 Protected master fire alarm control panel
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-19 Table
14.4.3.2 (2)(1)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Control Panel 1 1 0 1 1
Device Type Location ScanID Address Q2/22 Control Panel Ground 46938656 1 06/20-P
Device Total: 1 Return to Executive Summary
Page of 15 23
Vets Fire & Life Safety Download Date: 06/20/2022
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-19 Table 14.4.3.2 (9)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Battery 4 4 0 4 4
Device Type Location ScanID Address Q2/22 Battery 2nd Room 2 46938902 1 06/20-P Battery 2nd Room 2 46938901 1 06/20-P Battery Ground Room 1B134 46938904 1 06/20-P Battery Ground Room 1B134 46938903 1 06/20-P
Device Total: 4 Return to Executive Summary
Page of 16 23
Vets Fire & Life Safety Download Date: 06/20/2022
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2021 18/19.3.4
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-19 Table
14.4.3.2 (2)(1)) Devices Tested Q2/22 Pass Q2/22 Fail Q2/22 Tested YTD (2022) Total Quantity Power Supply 1 1 0 1 1
Device Type Location ScanID Address Q2/22 Power Supply 2nd Room 2 46938657 1 06/20-P
Device Total: 1 Return to Executive Summary
Page of 17 23 Service Summary
Vets Fire & Life Safety Download Date: 06/20/2022
Service Summary Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 128 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Passed Battery Tested 4 Control Panel Tested 1 Duct Detector Tested 11 Heat Detector Tested 24 Power Supply Tested 1 Pull Station Tested 8 Releasing Device Tested 4 Smoke Detector Tested/Cleaned 47 Speaker/Strobe Tested 16 Strobe Tested 16
Total 132 Grand Total 132
Page of 18 23 Auxiliary Functions Testing
Vets Fire & Life Safety Download Date: 06/20/2022
Auxiliary Functions Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Control Panel: 1 -
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed Releasing Device
Door Holder 1st Fire Door @ 1B131 Passed 46938713 Door Holder 1st Fire Door @ 1B131 Passed 46938714 Door Holder 1st Storage Room 1B132 Passed 46938715 Door Holder 2nd EMS Closet 2B231 Passed 46938716
Duct Detector AHU Shutdown 1st Elevator Lobby Passed 46938719 AHU Shutdown 1st Elevator Lobby @ Mag Doors Passed 46938720 AHU Shutdown 1st Mech Room 1B143 Passed 46938718 AHU Shutdown 1st Mech Room 1B143 Passed 46938717 AHU Shutdown 2nd Mech Room 2B201 Passed 46938722 AHU Shutdown 2nd Mech Room 2B201 Passed 46938721 AHU Shutdown Penthouse Attic Center Damper Passed 46938724 AHU Shutdown Penthouse Attic Center Damper Passed 46938727
Smoke Detector Elevator Recall 1st Elevator Lobby Passed 46938665 Elevator Recall 1st Elevator Mech Room 1B131 Passed 46938667 Elevator Recall 2nd Elevator Lobby Passed 46938688 Elevator Recall 2nd Elevator Shaft Passed 46938704
Duct Detector AHU Shutdown Penthouse Attic Center Damper Passed 46938725 AHU Shutdown Penthouse Attic Center Damper Passed 46938723 AHU Shutdown Penthouse Attic Center Damper Passed 46938726
Heat Detector Shunt Trip 1st Elevator Mech Room 1B131 Passed 46938732 Shunt Trip 1st Elevator Pit Passed 46938734 Shunt Trip 2nd Elevator Shaft Passed 46938742 javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938713');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938714');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938715');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938716');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938719');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938720');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938718');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938717');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938722');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938721');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938724');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938727');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938665');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938667');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938688');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938704');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938725');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938723');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938726');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938732');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938734');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938742');
Page of 19 23 Battery & Power Supply Testing
Vets Fire & Life Safety Download Date: 06/20/2022
Battery & Power Supply Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Control Panel: 1 -
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location Rated Ah
Rated Volts Pre Test
Post Test Min Ah Tested Ah
Battery
Passed Sealed Lead Acid 2nd Room 2 7 12 12.58 6.4 Sealed Lead Acid 2nd Room 2 7 12 12.55 6.4 Sealed Lead Acid Ground Room 1B134 55 12 13.67 44 Sealed Lead Acid Ground Room 1B134 55 12 13.44 50
Page of 20 23 Inventory & Warranty Report
Vets Fire & Life Safety Download Date: 06/20/2022
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Control Panel: 1 -
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Battery Control 3.03% 4
Control Panel Control 0.76% 1
Duct Detector Initiating 8.33% 11
Heat Detector Initiating 18.18% 24
Power Supply Control 0.76% 1
Pull Station Initiating 6.06% 8
Releasing Device Auxiliary 3.03% 4
Smoke Detector Initiating 35.61% 47
Speaker/Strobe Indicating 12.12% 16
Strobe Indicating 12.12% 16
Type Qty Model # Description Install Date
In Service - 3 Years to 5 Years Battery 4 Sealed Lead Acid 05/09/2018 Control Panel 1 05/09/2018 Duct Detector 11 05/09/2018 Heat Detector 24 05/09/2018 Power Supply 1 05/09/2018 Pull Station 8 05/09/2018 Releasing Device 4 Door Holder 05/09/2018 Smoke Detector 47 05/09/2018 Speaker/Strobe 16 05/09/2018 Strobe 16 05/09/2018
Page of 21 23 Zone Address Report
Vets Fire & Life Safety Download Date: 06/20/2022
Zone Address Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Control Panel: 1 -
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID M1-1 Smoke Detector 1st Electric Room 1B134 46938658 M1-2 Smoke Detector 1st Corr @ Electric Room 1B134 46938659 M1-3 Heat Detector 1st HAC Room 1B139 46938728 M1-4 Smoke Detector 1st Corr @ Group Room 1B140 46938660 M1-5 Smoke Detector 1st Patient Corr 1B140 46938663 M1-6 Smoke Detector 1st Storage Area 1B141 46938661 M1-8 Heat Detector 1st Storage Area 1B141 46938729 M1-9 Duct Detector 1st Mech Room 1B143 46938717 M1-10 Heat Detector 1st Mech Room 1B143 46938730 M1-11 Duct Detector 1st Mech Room 1B143 46938718 M1-12 Smoke Detector 1st Corr @ Stair 1 46938662 M1-13 Heat Detector 1st Fire Protection 1B142 46938731 M1-14 Pull Station 1st Stair 1 46938705 M1-15 Smoke Detector 1st Data Closet 1B145 46938664 M1-16 Smoke Detector 1st Elevator Lobby 46938665 M1-17 Duct Detector 1st Elevator Lobby 46938719 M1-18 Smoke Detector 1st Corr @ Elevator Mech Room 1B131 46938666 M1-19 Duct Detector 1st Elevator Lobby @ Mag Doors 46938720 M1-20 Heat Detector 1st Elevator Mech Room 1B131 46938732 M1-21 Smoke Detector 1st Elevator Mech Room 1B131 46938667 M1-27 Smoke Detector 1st Connecting Corr Doors 46938668 M1-28 Pull Station 1st Exit @ Corr 46938706 M1-29 Smoke Detector 1st Connecting Corr Doors 46938669 M1-30 Smoke Detector 1st Entry 1B1C1 46938670 M1-31 Pull Station 1st Entry 1B1C1 46938707 M1-32 Pull Station 1st Entry 1B1C1 46938708 M1-33 Smoke Detector 1st Reception 1B102 46938671 M1-34 Smoke Detector 1st Waiting 1B104 46938672 M1-35 Smoke Detector 1st Waiting 1B104 46938673 M1-36 Smoke Detector 1st Patient Corr 1C1C2 46938674 M1-37 Smoke Detector 1st Patient Corr 1C1C2 46938675 M1-38 Smoke Detector 1st Patient Corr 1C1C2 46938676 M1-39 Pull Station 1st Stair 3 46938709 M1-40 Smoke Detector 1st Work Room 1B111 46938678 javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938658');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938659');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938728');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938660');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938663');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938661');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938729');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938717');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938730');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938718');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938662');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938731');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938705');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938664');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938665');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938719');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938666');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938720');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938732');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938667');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938668');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938706');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938669');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938670');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938707');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938708');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938671');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938672');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938673');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938674');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938675');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938676');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938709');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938678');
Page of 22 23
Vets Fire & Life Safety Download Date: 06/20/2022
Address Device Type Location Type ScanID M1-41 Heat Detector 1st Storage Room 1B119 46938733 M1-42 Smoke Detector 1st Data Closest 1B115 46938677 M1-43 Smoke Detector 1st Work Room 1B111 46938679 M1-44 Smoke Detector 1st Work Room 1B105 46938680 M1-45 Smoke Detector 1st Work Room 1B105 46938681 M1-48 Heat Detector 1st Elevator Pit 46938734 M1-49 Heat Detector 2nd Crawl Space 46938735 M1-51 Smoke Detector 2nd Electric Room 2B234 46938682 M1-52 Smoke Detector 2nd Corr @ Electric Room 2B234 46938683 M1-53 Smoke Detector 2nd Patient Corr 2B2C4 46938684 M1-54 Smoke Detector 2nd Patient Corr 2B2C4 46938685 M1-55 Smoke Detector 2nd Patient Corr 2B2C4 46938686 M1-56 Pull Station 2nd Stair 1 46938710 M1-57 Smoke Detector 2nd inside Stair 1 46938687 M1-58 Smoke Detector 2nd Elevator Lobby 46938688 M1-59 Heat Detector 2nd HAC Room 2B131 46938736 M1-60 Smoke Detector 2nd HAC Room 2B231 46938689 M1-61 Smoke Detector 2nd Patient Corr 2B2C1 46938690 M1-62 Pull Station 2nd Stair 2 46938711 M1-63 Heat Detector 2nd Storage Room 2B228 46938737 M1-64 Smoke Detector 2nd In Stair 2 46938691 M1-65 Smoke Detector 2nd Connector Corr Doors 46938692 M1-66 Pull Station 2nd Corr @ Connector Doors 46938712 M1-67 Smoke Detector 2nd Connector Corr Doors 46938693 M1-68 Smoke Detector 2nd Corr @ Break Room 2B202 46938694 M1-69 Heat Detector 2nd Mech Room 2B201 46938739 M1-70 Duct Detector 2nd Mech Room 2B201 46938721 M1-71 Heat Detector 2nd Break Room 2B202 46938738 M1-72 Heat Detector 2nd Mech Room 2B201 46938740 M1-73 Duct Detector 2nd Mech Room 2B201 46938722 M1-74 Smoke Detector 2nd Corr @ Mech Room 2B221 46938695 M1-75 Smoke Detector 2nd Corr @ Work Room 2B207 46938696 M1-76 Smoke Detector 2nd Corr @ Work Room 2B209 46938697 M1-77 Smoke Detector 2nd Corr @ Work Room 2B214 46938698 M1-78 Smoke Detector 2nd Corr @ Work Room 2B214 46938699 M1-79 Smoke Detector 2nd Data Closet 2B215 46938700 M1-80 Smoke Detector 2nd Work Room 2B214 46938701 M1-81 Heat Detector 2nd Storage Room 2B219 46938741 M1-83 Smoke Detector 2nd Stair 3 46938702 M1-84 Smoke Detector 2nd Work Room 2B214 46938703 M1-85 Heat Detector Penthouse Attic Center 46938743 M1-86 Heat Detector Penthouse Attic South 46938746 M1-87 Heat Detector Penthouse Attic South 46938747 javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938733');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938677');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938679');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938680');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938681');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938734');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938735');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938682');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938683');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938684');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938685');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938686');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938710');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938687');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938688');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938736');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938689');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938690');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938711');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938737');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938691');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938692');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938712');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938693');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938694');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938739');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938721');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938738');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938740');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938722');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938695');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938696');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938697');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938698');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938699');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938700');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938701');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938741');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938702');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938703');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938743');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938746');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938747');
Page of 23 23
Vets Fire & Life Safety Download Date: 06/20/2022
Address Device Type Location Type ScanID M1-88 Heat Detector Penthouse Attic South 46938748 M1-89 Duct Detector Penthouse Attic Center Damper 46938723 M1-90 Duct Detector Penthouse Attic Center Damper 46938724 M1-91 Duct Detector Penthouse Attic Center Damper 46938725 M1-92 Duct Detector Penthouse Attic Center Damper 46938726 M1-93 Duct Detector Penthouse Attic Center Damper 46938727 M1-94 Heat Detector Penthouse Attic Center 46938744 M1-95 Heat Detector Penthouse Attic Center 46938745 M1-96 Heat Detector Penthouse Attic North 46938749 M1-97 Heat Detector Penthouse Attic North 46938750 M1-98 Heat Detector Penthouse Attic North 46938751 M1-99 Heat Detector 2nd Elevator Shaft 46938742
M1-100 Smoke Detector 2nd Elevator Shaft 46938704 javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938748');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938723');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938724');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938725');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938726');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938727');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938744');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938745');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938749');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938750');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938751');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938742');
javascript:openEditDevice('load-edit-f2-device','1267466','3049999','46938704');
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
File details come from the government source that posted it. Updated .