This sprinkler inspection certificate documents a quarterly inspection of the fire sprinkler system at Building 131 of the Fort McPherson VA Medical Center in Atlanta, Georgia. The inspection was conducted by United Fire Protection - Atlanta and found that of the 49 items inspected, 29 passed with no deficiencies noted. The inspection covered components across 14 wet pipe zones and two dry pipe areas, including control valves, alarms, sprinklers, gauges and other devices. No repairs or corrective actions were required based on the results of tests performed on February 9, 2023 that met applicable NFPA standards. The certificate provides detailed findings and performance readings for each individual device and area.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sprinkler Inspection Certificate For
Fort McPherson VAMC Bldg 131 1701 Hardee Ave SW
Atlanta, GA 30310
Tested to NFPA 25 Standards
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Quarterly Inspection Inspection Date Feb 9, 2023
Building: Fort McPherson VAMC Bldg 131 Company: United Fire Protection - Atlanta Contact: Mike McGill Contact: Wayne Huxtable
Title: Maintenance & Operations Supervisor Title: Technician
Page of 1 17United Fire Protection - Atlanta Download Date: 03/22/2023
Executive Summary Generated by: BuildingReports.com
Building Information Building: Fort McPherson VAMC Bldg 131 Contact: Mike McGill Address: 1701 Hardee Ave SW Phone: 14043216111 Address: Fax:
City/State/ZIP Code: Atlanta, GA 30310 Mobile:
Country: United States of America Email:
Inspection Performed By Company: United Fire Protection - Atlanta Inspector: Wayne Huxtable Address: 2150 Boggs Rd Bldg 100 Phone: 770-771-0999 Address: Suite 140 Fax:
City/State/ZIP Code: Duluth, GA 30096 Mobile:
Country: United States of America Email: whuxtable@united-fire.com
System Control Unit System Type System Location Protected Area Devices Dry Pipe Area- Attic 9
Dry Pipe Area- Attic and rest of the 5
Wet Pipe 5
Wet Pipe Zone- 1-1 5
Wet Pipe Zone- 1-2 5
Wet Pipe Zone- 2-1 5
Wet Pipe Zone- 2-2 5
Wet Pipe Zone- B-1 5
Wet Pipe Zone- B-2 5
Inspection Summary
Category:
Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty % Alarm 8 16.33% 8 100.00% 8 100.00% 0 0.00%
Device 9 18.37% 0 0.00% 0 0.00% 0 0.00%
Pump 2 4.08% 2 100.00% 2 100.00% 0 0.00%
Sprinkler 4 8.16% 0 0.00% 0 0.00% 0 0.00%
Valve 26 53.06% 19 73.08% 19 100.00% 0 0.00%
Totals 49 100% 29 59.18% 29 100.00% 0 0.00%
Certification
Company: United Fire Protection - Atlanta Building: Fort McPherson VAMC Bldg 131
Inspector: Wayne Huxtable Contact: Mike McGill
Page of 2 17United Fire Protection - Atlanta Download Date: 03/22/2023
Inspection & Testing Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 131 The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or
. Items are listed by Category. Each item includes the services performed, and the time & date at which testing Failed/Other occurred.
Device Type Location Service Time Date
Passed Dry Pipe, Area- Attic
Pressure Switch Attic High Pressure Quarterly 10:45:31 AM 02/09/2023
Pressure Switch Attic Low Pressure Quarterly 10:58:16 AM 02/09/2023
Air Compressor Attic Low Pressure Quarterly 10:48:02 AM 02/09/2023
Air Maintenance Device
Attic Supply Pressure Quarterly 10:47:52 AM 02/09/2023
Control Valve Attic Quarterly 10:43:12 AM 02/09/2023
Dry Pipe Valve Attic Supply Pressure Quarterly 10:58:24 AM 02/09/2023
Dry Pipe, Area- Attic and rest of the Dry Pipe Valve 2 second floor Sprinkler room Quarterly 10:59:04 AM 02/09/2023
Wet Pipe Control Valve Test Header Quarterly 10:39:55 AM 02/09/2023
Control Valve Test Header Quarterly 10:40:04 AM 02/09/2023
Control Valve Test Header Quarterly 10:40:20 AM 02/09/2023
Control Valve Sectional Quarterly 10:41:23 AM 02/09/2023
Wet Pipe, Zone- 1-1 Waterflow Switch 1st North Zone 1-1 Quarterly 10:44:50 AM 02/09/2023
Control Valve 1st North Zone 1-1 Quarterly 10:43:47 AM 02/09/2023
Inspector's Test 1st North Zone 1-1 Quarterly 4:35:21 PM 02/09/2023
Wet Pipe, Zone- 1-2 Waterflow Switch 1st South Zone 1-2 Quarterly 4:33:49 PM 02/09/2023
Control Valve 1st South Zone 1-2 Quarterly 4:33:55 PM 02/09/2023
Inspector's Test 1st South Zone 1-2 Quarterly 4:33:43 PM 02/09/2023
Wet Pipe, Zone- 2-1 Waterflow Switch 2nd North Zone 2-1 Quarterly 10:44:56 AM 02/09/2023
Control Valve 2nd North Building 131 Zone 2-1 Quarterly 4:34:07 PM 02/09/2023
Inspector's Test 2nd North Zone 2-1 Quarterly 4:34:01 PM 02/09/2023
Wet Pipe, Zone- 2-2 Waterflow Switch 2nd South Zone 2-2 Quarterly 10:46:56 AM 02/09/2023
Control Valve 2nd South Zone 2-2 Quarterly 4:34:20 PM 02/09/2023 javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133577');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133586');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133585');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','67977791');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','67977791');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133574');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133578');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','13765');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133580');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133581');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133582');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133583');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133547');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133544');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133548');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133552');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133549');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133553');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133557');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133554');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133558');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133562');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133559');
Page of 3 17United Fire Protection - Atlanta Download Date: 03/22/2023
Device Type Location Service Time Date
Inspector's Test 2nd South Zone 2-2 Quarterly 4:34:14 PM 02/09/2023
Wet Pipe, Zone- B-1 Waterflow Switch Ground North Zone B-1 Quarterly 10:44:26 AM 02/09/2023
Control Valve Ground North Zone B-1 Quarterly 4:34:30 PM 02/09/2023
Inspector's Test Ground North Zone B-1 Quarterly 4:34:25 PM 02/09/2023
Wet Pipe, Zone- B-2 Waterflow Switch Ground South Zone B-2 Quarterly 10:45:46 AM 02/09/2023
Control Valve Ground South Zone B-2 Quarterly 4:34:44 PM 02/09/2023
Inspector's Test Ground South Zone B-2 Quarterly 4:35:45 PM 02/09/2023
Untested Dry Pipe, Area- Attic
Drain Attic Supply Pressure
Gauge Attic Air Pressure
Gauge Attic Supply Pressure
Dry Pipe, Area- Attic and rest of the Sprinkler Box Attic Air Pressure
Sprinkler Box Spares
Attic Air Pressure
Sprinkler Box Spares
Attic Air Pressure
Sprinkler Box Spares
Attic Air Pressure
Wet Pipe Check Valve Test Header
Wet Pipe, Zone- 1-1 Gauge 1st North Zone 1-1
Check Valve 1st North Zone 1-1
Wet Pipe, Zone- 1-2 Gauge 1st South Zone 1-2
Check Valve 1st South Zone 1-2
Wet Pipe, Zone- 2-1 Gauge 2nd South Zone 2-1
Check Valve 2nd North Zone 2-1
Wet Pipe, Zone- 2-2 Gauge 2nd South Zone 2-2
Check Valve 2nd South Zone 2-2
Wet Pipe, Zone- B-1 Gauge Ground North Zone B-1
Check Valve Ground North Zone B-1 javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133563');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133567');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133564');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133568');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133572');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133569');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133573');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133579');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780008');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780009');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133584');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','67977846');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','67977846');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','67977847');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','67977847');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','67977848');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','67977848');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133587');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780042');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133545');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780045');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133550');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780043');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133555');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780046');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133560');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780041');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133565');
Page of 4 17United Fire Protection - Atlanta Download Date: 03/22/2023
Device Type Location Service Time Date
Wet Pipe, Zone- B-2 Gauge Ground South Zone B-2
Check Valve Ground South Zone B-2 javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780044');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133570');
Page of 5 17United Fire Protection - Atlanta Download Date: 03/22/2023
Wet Pipe Fire Sprinkler Systems Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved Test Header 03/29/2018 4" 44133587
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Test Header 6" Open Supervised 44133580
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Test Header 6" Open Supervised 44133581
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Test Header 6" 44133582
Description Main Control
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 705 Sectional 6" Open Supervised 44133583
Description Main Control
Building: Fort McPherson VAMC Bldg
Zone- 1-1
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Waterflow Switch javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133587');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133580');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133581');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133582');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133583');
Page of 6 17United Fire Protection - Atlanta Download Date: 03/22/2023
Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 3" 1-M1-154 44133547
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved 1st North Zone 1-1 03/29/2018 4" 44133545
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Victaulic 705 1st North Zone 1-1
4" Open Supervised 44133544
Description Main Control
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1000 80 33 44133548
Location 1st North Zone 1-1
Devices Gauge
Location Service Date 1st North Zone 1-1 03/29/2018
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika Wika 75 1/4 57780042
Building: Fort McPherson VAMC Bldg
Zone- 1-2
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 3" 1-M1-162 44133552
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved 1st South Zone 1-2 03/29/2018 4" 44133550
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Victaulic 705 1st South Zone 1-2
4" Open Supervised 44133549
Description javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133547');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133545');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133544');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133548');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780042');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133552');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133550');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133549');
Page of 7 17United Fire Protection - Atlanta Download Date: 03/22/2023
Main Control
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1000 80 28 44133553
Location 1st South Zone 1-2
Devices Gauge
Location Service Date 1st South Zone 1-2 03/29/2011
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika Wika 80 1/4 57780045
Building: Fort McPherson VAMC Bldg
Zone- 2-1
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 3" 1-M1-156 44133557
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved 2nd North Zone 2-1 03/29/2012 4" 44133555
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Victaulic 705 2nd North Building 131 Zone 2-1
4" Open Supervised 44133554
Description Main Control
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1000 80 35 44133558
Location 2nd North Zone 2-1
Devices Gauge
Location Service Date 2nd South Zone 2-1 03/29/2011 javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133553');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780045');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133557');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133555');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133554');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133558');
Page of 8 17United Fire Protection - Atlanta Download Date: 03/22/2023
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika Wika 80 1/4 57780043
Building: Fort McPherson VAMC Bldg
Zone- 2-2
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 3" 1-M1-164 44133562
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved 2nd South Zone 2-2 03/29/2018 4" 44133560
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Victaulic 705 2nd South Zone 2-2
4" Open Supervised 44133559
Description Main Control
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1000 80 22 44133563
Location 2nd South Zone 2-2
Devices Gauge
Location Service Date 2nd South Zone 2-2 03/29/2011
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika Wika 80 1/4 57780046
Building: Fort McPherson VAMC Bldg
Zone- B-1
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 3" 1-M1-152 44133567 javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780043');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133562');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133560');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133559');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133563');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780046');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133567');
Page of 9 17United Fire Protection - Atlanta Download Date: 03/22/2023
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved Ground North Zone B-1 03/29/2018 4" 44133565
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Victaulic 705 Ground North Zone B-1
4" Open Supervised 44133564
Description Main Control
Inspector's Test Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1000 80 41 44133568
Location Ground North Zone B-1
Devices Gauge
Location Service Date Ground North Zone B-1 03/29/2018
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika Wika 80 1/4 57780041
Building: Fort McPherson VAMC Bldg
Zone- B-2
This section lists out all the devices and components that have been associated with a Wet Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Alarms Waterflow Switch Type Manufacturer Model # Sec Size Zone/Address OK ScanID Vane Potter Electric VSR 3" 1-M1-161 44133572
Components Check Valve
Type Location Internal Date Size OK ScanID Grooved Ground South Zone B-2 03/29/2018 4" 44133570
Control Valve Type Manufacturer Model Location Size Position Status OK ScanID
Butterfly Victaulic 705 Ground South Zone B-2
4" Open Supervised 44133569
Description Main Control
Inspector's Test javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133565');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133564');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133568');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780041');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133572');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133570');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133569');
Page of 10 17United Fire Protection - Atlanta Download Date: 03/22/2023
Manufacturer Model # Pressure psi Valve Trip Time sec Water Flow Time sec OK ScanID
AGF 1000 80 51 44133573
Location Ground South Zone B-2
Devices Gauge
Location Service Date Ground South Zone B-2 03/29/2018
Type Manufacturer Model # Static psi Fill Type Size OK ScanID System Pressure Wika Wika 80 1/4 57780044 javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133573');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780044');
Page of 11 17United Fire Protection - Atlanta Download Date: 03/22/2023
Dry Pipe Fire Sprinkler Systems Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg
Area- Attic
This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Air Compressor Location Mfr. Model # Phase On psi Off psi Serial No.
Attic Low Pressure General
Air
PS-40
Type Description Rated Speed Horsepower Volts Amps OK ScanID
44133585
Air Maintenance Device Type Model # Location Install Date Air Pressure ScanID Pressure Reducing Attic Supply Pressure 03/29/2017 40 67977791
Alarms Pressure Switch Type Description Manufacturer Low High Zone/Address OK ScanID Pressure Switch Alarm Potter Electric 0 10 1-M1-58 44133577 Pressure Switch Alarm Potter Electric 10 40 1 44133586
Components Control Valve
Type Manufacturer Model Location Size Position Status OK ScanID Butterfly Victaulic 13765 Attic 4" Open Supervised 44133574
Description Main Control
Dry Pipe Valve Manufacturer Model # Location Internal Date OK ScanID Viking F-2 Attic Supply Pressure 03/29/2018 44133578
Type Status Position Size Serial # Grooved Sealed Trim Open 4"
Water psi Air Pressure Trip Air Trip Time Total Timing (sec)
Partial Trip Date
Full Trip Date
45 50 03/29/2017 03/29/2018
Devices Drain
Current Inspection
Restored javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133585');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','67977791');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133577');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133586');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133574');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133578');
Page of 12 17United Fire Protection - Atlanta Download Date: 03/22/2023
Type Location Size Supply psi psi Residual psi Sec OK ScanID Main Attic Supply Pressure 2" 80 60 50 44133579
Previous Inspections
October 28, 2022
Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Attic Supply Pressure 2" 80 60 50 44133579
August 15, 2022
Type Location Size Supply psi Static psi Residual psi Sec OK ScanID Main Attic Supply Pressure 2" 80 60 50 44133579
Gauge Location Service Date Attic Air Pressure 03/29/2017
Type Manufacturer Model # Static psi Fill Type Size OK ScanID Air Pressure Wika Wika 20 1/4 57780008
Gauge Location Service Date Attic Supply Pressure 03/29/2017
Type Manufacturer Model # Static psi Fill Type Size OK ScanID Supply Pressure Wika Wika 80 1/4 57780009
Building: Fort McPherson VAMC Bldg
Area- Attic and rest of the
This section lists out all the devices and components that have been associated with a Dry Pipe System and provides details as to type of component, pressure readings, response time, etc. If a component has an OK checkbox that is checked, then that component was actually tested. However, for Pass/Fail test results, see the Inspection and Testing section.
Components Dry Pipe Valve
Manufacturer Model # Location Internal Date OK ScanID Viking F-2 2 second floor Sprinkler room 03/29/2012 13765
Type Status Position Size Serial # Grooved 4" 13765
Water psi Air Pressure Trip Air Trip Time Total Timing (sec)
Partial Trip Date
Full Trip Date
03/29/2017 03/29/2018
Devices Sprinkler Box
Qty Tool Available?
SIN List? Size Manufacturer Location OK ScanID
6 Yes 6 unit Viking Attic Air Pressure 44133584
Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID 3 Upright Viking Attic Air Pressure 67977846 javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133579');
javascript:openEditDevice('load-edit-p2-device','0','2686313','44133579');
javascript:openEditDevice('load-edit-p2-device','0','2603990','44133579');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780008');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','57780009');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','13765');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133584');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','67977846');
Page of 13 17United Fire Protection - Atlanta Download Date: 03/22/2023
Temperature KFactor Size Finish Response Time 290 1/2 Brass Fast Response
Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID 3 Upright Viking Attic Air Pressure 67977847
Temperature KFactor Size Finish Response Time 290 5.6 1/2 Brass Fast Response
Sprinkler Box Spares Qty Type Manufacturer Location OK ScanID 3 Upright Tyco Attic Air Pressure 67977848
Temperature KFactor Size Finish Response Time 212 5.6 1/2 Brass Standard Response javascript:openEditDevice('load-edit-p2-device','736897','2792109','67977847');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','67977848');
Page of 14 17United Fire Protection - Atlanta Download Date: 03/22/2023
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 131 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Air Compressor Pump 2.04% 1
Air Maintenance Device Pump 2.04% 1
Check Valve Valve 14.29% 7
Control Valve Valve 22.45% 11
Drain Device 2.04% 1
Dry Pipe Valve Valve 4.08% 2
Gauge Device 16.33% 8
Inspector's Test Valve 12.24% 6
Pressure Switch Alarm 4.08% 2
Sprinkler Box Sprinkler 2.04% 1
Sprinkler Box Spares Sprinkler 6.12% 3
Waterflow Switch Alarm 12.24% 6
Device Type Qty Model # Type Description Install Date
In Service - 3 Years to 5 Years Dry Pipe, Area- Attic
Gauge 1 Wika Air Pressure 07/11/2018
Dry Pipe, Area- Attic and rest of the Sprinkler Box 1 07/11/2018 Sprinkler Box Spares 1 VK 300 Upright 07/11/2018 Sprinkler Box Spares 1 VK 302 Upright 07/11/2018
Dry Pipe, Area- Attic Air Compressor 1 PS-40 03/29/2018 Pressure Switch 1 PS-10 Pressure Switch Alarm 03/29/2018 Pressure Switch 1 PS-40 Pressure Switch Alarm 03/29/2018 Control Valve 1 13765 Butterfly Main Control 03/29/2018
Wet Pipe Check Valve 1 705 Grooved 03/29/2018 Control Valve 4 705 Butterfly Main Control 03/29/2018
Wet Pipe, Zone- 1-1 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Check Valve 1 717H Grooved 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018 Gauge 1 Wika System Pressure 03/29/2018
Page of 15 17United Fire Protection - Atlanta Download Date: 03/22/2023
Wet Pipe, Zone- 1-2 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Check Valve 1 717H Grooved 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018
Wet Pipe, Zone- 2-1 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Check Valve 1 717H Grooved 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018
Wet Pipe, Zone- 2-2 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Check Valve 1 717H Grooved 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018
Wet Pipe, Zone- B-1 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Check Valve 1 717H Grooved 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018 Gauge 1 Wika System Pressure 03/29/2018
Wet Pipe, Zone- B-2 Inspector's Test 1 1000 03/29/2018 Waterflow Switch 1 VSR Vane Alarm 03/29/2018 Check Valve 1 717H Grooved 03/29/2018 Control Valve 1 705 Butterfly Main Control 03/29/2018 Gauge 1 Wika System Pressure 03/29/2018
In Service - 5 Years to 10 Years Dry Pipe, Area- Attic
Drain 1 Wika Main 03/29/2017 Air Maintenance Device 1 Pressure Reducing 03/29/2017 Dry Pipe Valve 1 F-2 Grooved 03/29/2017 Gauge 1 Wika Supply Pressure 03/29/2017
In Service - 10 Years to 15 Years Dry Pipe, Area- Attic and rest of the
Sprinkler Box Spares 1 TY 3180 Upright 07/11/2012 Dry Pipe Valve 1 F-2 Grooved 07/11/2012
Wet Pipe, Zone- 1-2 Gauge 1 Wika System Pressure 03/29/2011
Wet Pipe, Zone- 2-1 Gauge 1 Wika System Pressure 03/29/2011
Wet Pipe, Zone- 2-2
Page of 16 17United Fire Protection - Atlanta Download Date: 03/22/2023
Gauge 1 Wika System Pressure 03/29/2011
Page of 17 17United Fire Protection - Atlanta Download Date: 03/22/2023
Zone Address Report Generated by: BuildingReports.com
Building: Fort McPherson VAMC Bldg 131 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
Control Panel 1 M1-58 Pressure Switch Attic High Pressure Pressure Switch 44133577
M1-152 Waterflow Switch Ground North Zone B-1 Vane 44133567 M1-153 Control Valve Ground North Zone B-1 Butterfly 44133564 M1-154 Waterflow Switch 1st North Zone 1-1 Vane 44133547 M1-155 Control Valve 1st North Zone 1-1 Butterfly 44133544 M1-156 Waterflow Switch 2nd North Zone 2-1 Vane 44133557 M1-157 Control Valve 2nd North Building 131 Zone 2-1 Butterfly 44133554 M1-159 Control Valve Attic Butterfly 44133574 M1-160 Control Valve Ground South Zone B-2 Butterfly 44133569 M1-161 Waterflow Switch Ground South Zone B-2 Vane 44133572 M1-162 Waterflow Switch 1st South Zone 1-2 Vane 44133552 M1-163 Control Valve 1st South Zone 1-2 Butterfly 44133549 M1-164 Waterflow Switch 2nd South Zone 2-2 Vane 44133562 M1-165 Control Valve 2nd South Zone 2-2 Butterfly 44133559 javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133577');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133567');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133564');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133547');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133544');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133557');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133554');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133574');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133569');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133572');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133552');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133549');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133562');
javascript:openEditDevice('load-edit-p2-device','736897','2792109','44133559');
| Sprinkler Inspection Certificate |
| Executive Summary |
| Inspection & Testing |
| Wet Pipe Fire Sprinkler Systems |
| Dry Pipe Fire Sprinkler Systems |
| Inventory & Warranty Report |
| Zone Address Report |