S06 Updated Drawings 250716 FP REV 2.pdf
PDF 704 KB Posted
- Attached to
- Z2EZ 523A5-10-316 Upgrade VISN 1 Laundry Building 45 Federal contract opportunity
- Solicitation number
- 36C24125R0008
About this file
These are fire suppression plan drawings for the Upgrade VISN 1 Laundry Building 45 project located at the Brockton Campus in Brockton, Massachusetts. The documents include detailed basement and first floor fire suppression plans with specific technical requirements, such as relocating existing sprinkler piping, modifying sprinkler layouts, and providing connections for equipment. The drawings are part of a 100% submittal for a fully sprinklered facility, with key notes addressing specific installation and modification requirements for different rooms, including the clean textile make-up room, drying production area, and various staging and processing spaces. The project involves the U.S. Department of Veterans Affairs and includes consulting services from multiple engineering and design firms, with the drawings prepared by Toland Mezzy Molnar and dated 08-21-2024.
View the file
Other files for this federal contract opportunity
Show all 43
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UP
DN
STORAGE
B005
VESTIBULE
B008
WOMENS
TOILET
B009A
WOMENS
SHOWER
B009 WOMEN'S
RESTROOM
B010
HAC
B019
MEN'S
RESTROOM
B014
MEN'S
LOCKER
ROOM
B013
STAFF
BREAK
ROOM
B004
STAIR
B007
CORRIDOR
B006
GAS METER
AND
REGULATING
ROOM
B002
MECHANICAL
ROOM
B003
CORRIDOR
B012
SECURE
STORAGE
B028
STORAGE
B015
MECHANICAL
STORAGE
B024
MECHANICAL
SHOP
B023
CONTROLLER
ROOM
B022
SERVICE
ELEVATOR
B025
MECHANICAL
B017
MECH &
CHEM
STORAGE
B018
IT ROOM
B020
SECURITY
OFFICE
B027
TANK ROOM
B001b
LINEN
STORAGE
B026
ELEC ROOM
E001
STORAGE
B001a
WOMEN'S
LOCKER
ROOM
B011
C5
FX001
H.7G.8F.8E.8D.8C.8B.8A.8A.1
8EE
DD CC
7FF
6.2
GG
5.1
4.1
3.2
2.2
2.1
AA B C D E F G H I
JJ
LLMMKKII
HH
OO
A
NN
PP
TRUE
NORTH
PLAN
NORTH
SCALE: 1/8" = 1'-0"
BASEMENT FIRE SUPPRESSION PLAN
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
100% SUBMITTAL
512 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
CHB DRD
UPGRADE VISN 1 LAUNDRY BUILDING 45
BROCKTON CAMPUS
523A5-10-316
BROCKTON, MA
08-21-2024 REVISIONS:
MECHANICAL, ELECTRICAL, &
PLUMBING ENGINEERING SERVICES:
CLARKNEXSEN
3920 ARKWRIGHT ROAD SUITE 385
MACON, GA 31210
478.314.1206 DIRECT
478.743.8415 OFFICE
GEORGE SIMPSON
STRUCTURAL ENGINEERING
SERVICES:
INNOVATIVE ENGINEERING, INC.
3380 TRICKUM ROAD
BLDG 500 SUITE 100
WOODSTOCK, GA 30188
678-883-5862 DIRECT
770-517-5508 FAX
STEPHEN MORGAN
COST ESTIMATING SERVICES:
AXIAS, INC.
225 REINEKERS LANE, SUITE 200
ALEXANDRIA, VA 22314
703-706-0400
GEORGE SHIELDS
LAUNDRY EQUIPMENT VENDOR
SERVICES:
LAUNDRY DESIGN GROUP, LLC
5940 S RAINBOW BLVD, LAS
VEGAS NV USA 89118
1-855-226-3500
BOB CORFIELD
BASEMENT FLOOR FIRE SUPPRESSION PLAN
FX101
1. EXISTING RISER COMPONENTS TO INCLUDE BACKFLOW PREVENTER, RISER CHECK VALVE, FLOW SWITCH AND
TAMPER SWITCH ARE TO BE MOVED TO EAST SIDE OF MECH ROOM B018.
1/8" = 1' - 0" 0 5' 10' 15' 30'
GRAPHIC SCALE(S)
# KEY NOTESGENERAL NOTES
2. SPRINKLER SYSTEM IN THIS AREA CURRENTLY ONLY CONSISTS OF MAINS. REMOVE/REINSTALL AS NECESSARY TO COORDINATE WITH STRUCTURAL REMEDIATION. FOLLOWING STRUCTURAL REMEDIATION, COMPLETE INSTALLATION OF SYSTEM, INCLUDING BUT NOT LIMITED TO, BRANCH LINE PIPING, SPRINKLERS, HANGERS, ETC.
4. SPRINKLER SYSTEM INSTALLATION IN THIS AREA IS SUBSTANTIALLY COMPLETE. REMOVE/REINSTALL IT IN ITS ENTIRETY TO FACILITATE STRUCTURAL REMEDIATION. EXISTING PIPING, FITTINGS, HANGERS, ETC., CAN BE REUSED AT CONTRACTOR'S
DISCRETION.
6. EXISTING FIRE DEPARTMENT CONNECTION.
7. EXISTING REDUCED PRESSURE BACKFLOW PREVENTER.
8. PROVIDE TEST HEADER HOSE VALVE.
9. ALL EXPOSED SPRINKLER PIPING SHALL BE PAINTED RED IN ACCORDANCE WITH SPECIFICATION SECTION 09 91 00.
1. REFER TO SHEET FX001 FOR GENERAL NOTES.
2. REFER TO SHEETS FX501 - FX503 FOR SPRINKLER
SHOP DRAWINGS FROM PREVIOUS CONTRACT.
5. SPRINKLER SYSTEM IN THIS AREA IS SUBSTANTIALLY COMPLETE. REMOVE/REINSTALL AS NECESSARY TO COORDINATE WITH STRUCTURAL REMEDIATION. EXISTING PIPING, FITTINGS, HANGERS, ETC., CAN BE REUSED AT CONTRACTOR'S DISCRETION.
3. SPRINKLER SYSTEM INSTALLATION IN THIS AREA UNDER PREVIOUS CONTRACT IS GENERALLY LIMITED TO MAINS ONLY. NO
BRANCH LINES OR SPRINKLERS WERE OBSERVED IN THIS AREA.
1 REV 2 07/18/25
RECEPTION
OFFICE
OFFICE
TRAINING
ROOM
100A
EQUIPMENT
SPACE
105 DRYING
PRODUCTION
WASHING
PRODUCTION
SOIL
TEXTILE
SORTING
SOIL
TEXTILE
RECEIVING
AIR LOCK
ROOM
SOIL CART
STAGING
CART
WASHING
CLEAN
CART
STAGING
VESTIBULE
LAUNDRY
SUPERVISOR
OFFICE
RESTROOM
RESTROOM
CART MAKE
UP
CLEAN
TEXTILE
MAKE UP
FLATWORK
FINISHING
SERVICE
ELEVATOR
B025
22222
HSKP
104A
H.7G.8F.8E.8D.8C.8B.8A.8A.1
8EE
DD CC
7FF
6.2
GG 6
5.1
4.1
3.2
2.2
2.1
AA B C D E F G H I
JJ
LLMMKKII
HH
OO
A
NN
PP
TRUE
NORTH
PLAN
NORTH
VA FORM 08-6231
1 2 3 4 5 6 7 8 9
DATE:
Drawing Title:
Approved Project Director
Project Title:
1 2 3 4 5 6 7 8 9
100% SUBMITTAL
512 MEANS ST NW
Phase Project Number
Building Number
Drawing NumberLocation
Issue Date CheckedFULLY SPRINKLERED
STAMP
STE. 400
ATLANTA, GA 30318
ARCHITECT/ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
U.S. Department of Veterans Affairs
Office of Construction and
Facilities Management
Drawn
CHB DRD
UPGRADE VISN 1 LAUNDRY BUILDING 45
BROCKTON CAMPUS
523A5-10-316
BROCKTON, MA
08-21-2024 REVISIONS:
MECHANICAL, ELECTRICAL, &
PLUMBING ENGINEERING SERVICES:
CLARKNEXSEN
3920 ARKWRIGHT ROAD SUITE 385
MACON, GA 31210
478.314.1206 DIRECT
478.743.8415 OFFICE
GEORGE SIMPSON
STRUCTURAL ENGINEERING
SERVICES:
INNOVATIVE ENGINEERING, INC.
3380 TRICKUM ROAD
BLDG 500 SUITE 100
WOODSTOCK, GA 30188
678-883-5862 DIRECT
770-517-5508 FAX
STEPHEN MORGAN
COST ESTIMATING SERVICES:
AXIAS, INC.
225 REINEKERS LANE, SUITE 200
ALEXANDRIA, VA 22314
703-706-0400
GEORGE SHIELDS
LAUNDRY EQUIPMENT VENDOR
SERVICES:
LAUNDRY DESIGN GROUP, LLC
5940 S RAINBOW BLVD, LAS
VEGAS NV USA 89118
1-855-226-3500
BOB CORFIELD
FIRST FLOOR FIRE SUPPRESSION PLAN
FX102
SCALE: 1/8" = 1'-0"
FIRST FLOOR FIRE SUPPRESSION PLAN
1. PROVIDE ADDITIONAL BRANCHLINE IN CLEAN TEXTILE MAKE UP ROOM 103 IF REQUIRED TO MEET CRITERIA FOR OBSTRUCTIONS PER NFPA 13.
1/8" = 1' - 0" 0 5' 10' 15' 30'
GRAPHIC SCALE(S)
# KEY NOTESGENERAL NOTES
2. PROVIDE 1-1/4" CONNECTION TO SPRINKLER SYSTEM (WITH TAMPER AND FLOW SWITCH) FOR CONNECTION TO DRYING EQUIPMENT.
3. MODIFY SPRINKLER LAYOUT AS NECESSARY TO ACCOMMODATE NEW ROOM.
1. REFER TO SHEET FX001 FOR GENERAL NOTES.
2. REFER TO SHEETS FX501 - FX503 FOR SPRINKLER
SHOP DRAWINGS FROM PREVIOUS CONTRACT.
4. CONTRACTOR TO RELOCATE EXISTING SPRINKLER PIPING ALONG COLUMN LINE E-E TO ABOVE NO FLY ZONE. REFER TO ARCHITECTURAL PLANS
FOR CLEARANCE REQUIREMENTS.
5. CONTRACTOR TO RELOCATE EXISTING SPRINKLER PIPING TO ABOVE NO FLY ZONE IF REQUIRED BY E-TECH TO AVOID CONFLICT WITH MONORAIL
SYSTEM. REFER TO ARCHITECTURAL PLANS FOR CLEARANCE REQUIREMENTS.
1 REV 2 07/18/25
| Sheets |
| FX101 - BASEMENT FLOOR FIRE SUPPRESSION PLAN |
| FX102 - FIRST FLOOR FIRE SUPPRESSION PLAN |
| 2025-07-17T08:19:02-0400 | |
| Christopher Born, PE |
| 2025-07-17T08:19:22-0400 | |
| Christopher Born, PE |