2.1.1 Attachment 3 - Express Cal Wildfire NextGen CAD Drawings Furnace-AC System - FEB-03-2025 PE Sealed.pdf
PDF 4 MB Posted
- Solicitation number
- 70FB8025R00000018
- Issued by
-
Federal Emergency Management Agency
About this file
This document is a detailed technical drawing package for FEMA's NextGen Express Manufactured Housing Unit (MHU) with a Furnace/AC System, specifically designed for Wildland-Urban Interface Fire Area Construction. The drawings are part of Solicitation 70FB8025R00000018 and dated February 3, 2025. The 8' wide Express MHU includes comprehensive technical specifications covering electrical, HVAC, roof framing, chassis, transit protection, and tie-down system details. Key technical specifications include a 10 KW electric furnace, 1.5-ton air conditioning system, 7/16" OSB roof sheathing, wind zone 1 requirements, and compliance with California Residential Code standards for fire-resistant construction. The design incorporates specific requirements for exterior materials, insulation, ventilation, and structural integrity to withstand transportation and potential wildfire environments.
The technical drawings provide granular details on construction methods, including wall framing using 2x4 SPF studs, gypsum board interior finishing, LP SmartSide paneling, and specific fastening schedules for various building components. Transportation-related specifications cover lighting requirements, wind diverters, and tie-down systems designed to secure the unit during transit and installation. The package includes precise measurements for electrical layouts, HVAC design, roof overhangs, and exterior wall configurations, with notes addressing fire safety, wind resistance, and compliance with federal manufactured housing construction standards. Each drawing is meticulously annotated with technical specifications, installation guidelines, and regulatory compliance information.
View the file
Other files
Show all 50
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
MANUFACTURED HOUSING UNIT
FEDERAL EMERGENCY MANAGEMENT AGENCY
NextGen Express Unit
(Furnace/AC System)
APPENDIX D
Wildland - Urban Interface Fire Area Construction
Designs for NextGen 8' Wide Express MHU's
February 3, 2025
COVER PAGE
TITLE:
Scale: NTS
03/25/2020FEMA Manufactured Housing Units Federal Emergency Management Agency
DRAWING NO.
D-8F-1.1Express MHU (Furnace)
APPENDIX D
REV 02-03-25. Feb 03, 2025
Attachment 3
ADDITION/REPLACEMENT INDEX
EXISTING FEMA APPENDIX D ADDITION/
DWG. NO. REPLACEMENT DWG. NO. TITLE
8F-1.1 D-8F-1.1 COVER PAGE
NONE D-8F-1.2.1 ADDITION/REPLACEMENT PAGE INDEX
8F-1.3 D-8F-1.3 GENERAL NOTES
8F-1.4 D-8F-1.4 GENERAL NOTES (CONTINUED)
8F-2 D-8F-2 FLOOR PLAN
8F-3 D-8F-3 DOOR AND WINDOW SCHEDULE
8F-6 D-8F-6 ELECTRICAL PLAN
8F-9 D-8F-9 HVAC DESIGN AND OVERHEAD DUCT LAYOUT
8F-10 D-8F-10 ELEVATIONS
8F-11.1 D-8F-11.1 CHASSIS
8F-11.2 D-8F-11.2 CHASSIS DETAILS
8F-17.1 D-8F-17.1 FRONT END WALL FRAMING AND INTERIOR SHEATHING
8F-17.2 D-8F-17.2 REAR END WALL FRAMING AND INTERIOR SHEATHING
8F-18.1 D-8F-18.1 FRONT SHEARWALL FRAMING AND EXTERIOR SHEATHING
8F-19 D-8F-19 FRONT DOOR SIDEWALL
8F-20 D-8F-20 BACK DOOR SIDEWALL
8F-21 D-8F-21 ROOF FRAMING LAYOUT
8F-22 D-8F-22 ROOF SHEATHING LAYOUT
8F-23 D-8F-23 ROOF OVERHANG DETAIL
8F-27 D-8F-27 TRANSIT PROTECTION DETAILS
8F-28 D-8F-28 TRANSPORTATION LIGHTING
8F-29.1 D-8F-29.1 TIE DOWN SYSTEM
8F-29.2 D-8F-29.2 EXTERIOR WALL TIE DOWN DETAILS
APPENDIX D FOR WILDLAND - URBAN INTERFACE FIRE AREA CONSTRUCTION IS A SUPPLEMENT TO FEMA'S
STANDARD DRAWING PACKAGES.
APPENDIX D IS INTENDED TO ADD OR REPLACE EXISTING PAGES IN FEMA'S STANDARD DRAWING PACKAGES. THE ADDITION/REPLACEMENT INDEX BELOW IS TO BE USED IN ADDING AND REPLACING PAGES.
TITLE:
Scale: NTS
03/25/2020FEMA Manufactured Housing Units Federal Emergency Management Agency
DRAWING NO.
D-8F-1.2.1
APPENDIX D
Express MHU (Furnace)
REV 4-27-20
ADDITION/REPLACEMENT PAGE INDEX
. Feb 03, 2025
MANUFACTURED HOUSING UNIT
Federal Emergency Management Agency
GENERAL NOTES
CODES AND STANDARDS
Manufactured Home Construction and Safety Standards 24 CFR 3280 Manufactured Home Procedural and Enforcement Regulations 24 CFR 3282 Uniform Federal Accessibility Standards (UFAS) Standard for the installation of Sprinkler Systems in Manufactured Homes (NFPA 13D) Referenced 2005 National Electrical Code (NFPA 70) Articles as Incorporated in HUD 24 CFR 3280 2019 California Residential Code - Section R337 Materials and Construction Methods for Exterior Wildfire Exposure California Air Resources Board Phase 2 (CARB 2) Compliance
STRUCTURAL LOADS
Floor Live Load 40 PSF Floor Dead Load 10 PSF Roof Live Load 40 PSF Roof Dead Load 10 PSF Comply with Wind Zone 1 Requirements of 24 CFR 3280 Wood Roof Diaphragm Wall Height: 7'-6"
GENERAL NOTES
TITLE:
Scale: NTS
Date: 03/25/2020FEMA Manufactured Housing Units Federal Emergency Management Agency
DRAWING NO.
D-8F-1.3
APPENDIX D
Express MHU (Furnace)
GENERAL NOTES (CONT)
TITLE:
Scale: NTS
Date: 03/25/2020FEMA Manufactured Housing Units Federal Emergency Management Agency
DRAWING NO.
D-8F-1.4
APPENDIX D
Express MHU (Furnace)
REV 4-27-20. Feb 03, 2025
WD
REFER
BATH
70.1 SQ. FT.
KITCHEN
LIVING/DINING AREA
150.0 SQ. FT.
BEDROOM
9'-2"27'-1"7'-7" 9'-6"
14'-91 2"
48'-0"
22'-83 4"29'-2"
36'-101 2"
2'-11 2" 5'-01
2"12'-1"6'-111 2"
29'-71 2" 9'-6"
22'-33 4"
17'-3"
41'-51 2"
10'-6"
31'-10"
5'-111 2"
W/H
4"
4" 2'-41 2"
14'-10"
36'-101 2"
3'-2" 2'-10" 2'-6" 2'-10"
4"
39'-61 2"
4"
8' -0
4" 3060
3060E 3027
UTILITY
8" 251 2" 11
2"
1 2"
1 2"
7"
3"
1 2"
1 2"
1 2"
5" 251 2" 3"
2' -0
4"
2"
RANGE HOOD
RANGE
FIXED PANE
PANTRY
EXTERIOR
A/C
UNIT
4"
SHEARWALLS - WIND ZONE 1
NO. LENGTH PLF
1 96" 278 2 96" 278
SIDEWALL HEIGHT = 90"
TRUSS VERTICAL PROJECTION = 9 14"
2"
LIGHT & VENT SCHEDULE
ROOM TITLE AREA REQ'D LIGHT REQ'D VENT
LIVING/DINING
AREA 150 S.F. 12.0 S.F. 6.0 S.F.
BEDROOM 70.1 S.F. 5.61 S.F. 2.81 S.F.
28"
9'-2"
F
SHEAR WALLS WIND ZONE 1
DESIGNATES A 2X4 INTERIOR WALL
DESIGNATES A 2X6 INTERIOR WALL
20'-13 4"
24"
4" 24"
4"
1 2" 2"
RAG
OPTIONAL DEHUMIDIFIER -
SEE APPENDIX A, PAGE A-35.
FLOOR PLAN
TITLE:
Scale: 3/16" = 1'-0"FEMA Manufactured Housing Units Federal Emergency Management Agency
DRAWING NO.
D-8F-2
APPENDIX D
Express MHU (Furnace)
Date: 03/25/2020
REV 11-15-23
Floor Plan Notes:
1. All bedroom closet shelving shall be 12 inches deep.. Feb 03, 2025
BATH
KITCHEN
LIVING/DINING AREA
BEDROOM
W/H
UTILITY
D1
D2
D3
W1
W2
D3
W1
W1
PANTRY
MARK
W1 W2
WIDTH
2'-6" 2'-6"
HEIGHT
5'-0" 2'-3"
TYPE
Single Hung Window Fixed Pane Window
WINDOW SCHEDULE
TOTAL WINDOW AREA: 44.2 SQ. FT.
D1
D2
EXTERIOR
A/C
UNIT
F
D4
Door Notes
1. Exterior doors shall meet 24 CFR 3280.405 requirements and shall comply with Wind Zone 1 requirements.
2. All exterior doors shall be insulated fiberglass or steel with a maximum U-Value of 0.33.
3. All doors shall have lever type handles in compliance with UFAS 4.13.9.
4. For additional information on exterior and interior doors see FEMA Additional Requirements document and
Appendix A.
5. Return air grills shall be installed above doors unless the grill will be blocked by the sprinkler system and then may be installed in the door or wall.
6. Door stops shall be installed at all interior and wardrobe doors. Door stops may be installed on the door or the floor baseboard. Door stop finish to match interior hardware finish.
7. All bathroom and bedroom doors shall have a privacy lock. The lock mechanism shall be the button type
(UFAS 4.13.9) and located on the inside of the bathroom or bedroom.
8. The water heater compartment side of the water heater access door shall be covered with minimum 5/16 inch thick gypsum board.
9. The closet door shall be equipped with a passage latchset with lever handle.
10. Sprinkler riser door lockset shall be keyed to match the water heater closet door lockset.
11. All interior doors shall have a maximum gap of 1" between the finished floor and the bottom of the door.
12. The exterior surface or cladding of exterior doors shall be of non-combustible material or ignition-resistant material to comply with R-337.8.3 Exterior Doors of the 2019 California Residential Code.
13. 14x4 RAG centered in door with bottom of opening 2 1/2" above floor. Minimum 20 S.I. of free air return area.
Window Notes
1. Windows shall meet 24 CFR 3280.403 and 3280.404 requirements and shall comply with Wind Zone 1 requirements.
2. Windows shall be double paned, low E with vinyl frame. Windows shall have a minimum SHGC of 0.30 and a maximum U-Value of 0.36.
3. Windows shall have a design pressure rating of 15.
4. Windows shall have screens.
5. Exterior windows shall be vinyl frame with minimum one tempered pane and comply with R-337.8.2.1 Exterior Windows of the 2019 California Residential Code.
SEE NOTE 13
MARK
D1 D2 D3
WIDTH
3'-0" 3'-0" 2'-0"
HEIGHT
6'-8" 6'-8" 6'-8"
THICKNESS
1-3/8" 1-3/8" 1-3/8"
TYPE
Outswing Door Hallway Doors Closet & W/H Doors
DOOR SCHEDULE
TOTAL EXTERIOR DOOR AREA: 43.03 SQ. FT.
D4 1'-6" 6'-8" 1-3/8" Sprinkler Riser Access Door
DOOR AND WINDOW SCHEDULE
TITLE:
Scale: 3/16" = 1'-0"
Date: 03/25/2020FEMA Manufactured Housing Units Federal Emergency Management Agency
DRAWING NO.
D-8F-3
APPENDIX D
Express MHU (Furnace)
REV 9-20-21. Feb 03, 2025
W/H
NOAA
GFCI-WP
S 3
S3
SC
FE
SS
GFCI-WP
WP
WP
SSS
H.T. GFCI
RH 16
SS
REFR
GFCI
S
G
FC
I
G
FC
I
TV
TV SS
13 10
G
FC
I
F
SC 12
T
44" AFF 18" AFF TO RECEPTACLE SCREW
SINGLE OUTLET RECEPTACLE
FOR REFRIGERATOR
WP
SEE
GENERAL
NOTE 2
S
S
TITLE:
FEMA Manufactured Housing Units Federal Emergency Management Agency
COMPANY:
Cir. Purpose Type Wire Size Amps Pole
Bedroom 1 14-2 15 1
2 NA - -
3 NA - -
4 Kitchen 20 1 5 Kitchen 1 6 Ext. Recep 1 7 Washer 1 8 Dryer 30 2 9 Electric Range
10 Water Heater 11 A/C 12 15 1 13 Furnace
GFCI
12-2
10-3 Per MFR. Specs.
14-3
20GFCI 12-2
20GFCI 12-2
2012-2
Per MFR. Specs.
Per MFR. Specs.
14 Living Room 15 114-2 16 Lights/Recep 15 114-2 17 Dining Room 20 112-2 18 Refrigerator 20 112-2
Per MFR. Specs.
19 Bath Receps / Heat Tape 20 112-2
GFCI
GFCI
ELECTRICAL PLAN
Scale: 3/16" = 1'-0"
DRAWING NO.
D-8F-6
TPS System
General Notes
1. The range electrical receptacle must be recessed.
2. Circuit #15 has an external TPS electrical connection with a female IEC 60 309-2 international pin and sleeve connection. The external TPS electrical connection shall be located 24" in from the road side of the MHU and 12" up from the bottom of the exterior siding.
30 28-3
Date: 03/25/2020 APPENDIX D Express MHU (Furnace)
Smoke Alarm/C.O.
Electrical and Lighting Notes
1. The highest breaker in the panel box should be 48” maximum. Panel box bottom must be at least 24” from the floor.
2. The light bulbs shall be LED, equivalent to 60-watt incandescent bulbs, min. 800 lumens, white in color, between 2,700 K and 4,100 K.
3. No glass shall be used in any of the lighting globes.
4. The exterior lights shall be stored in the refrigerator during transport.
5. Interconnected smoke alarms shall utilize the home’s primary power source and shall have battery backup.
6. The centerline of the switches and the top of thermostat must be installed at no more than 48” above the finished floor.
7. Electrical outlets must be no lower than 18" above the floor to the center of the receptacle screw.
8. The junction box for the telephone and cable shall be located within 4’ of the road side rear of the MHU.
9. Electric wiring may be done either through the floor or the ceiling.
10. Listed service entrance conduit, sized per 2005 NEC, shall be run from the main distribution panel straight down and extend below the bottom board no more than 3 inches with a listed threaded fitting.
End of conduit shall be capped.
11. Thermostat wire shall be run with the condenser line set and shall be supported at 48" O.C. with zip ties. Installation shall conform to low voltage wire requirements per 2005 NEC.
12. For additional information on optional dehumidifier wiring requirements see Appendix A, page A-35.
13. Circuit breaker, wire and junction box shall be installed at the plant. Junction box shall be located below wall framing for dehumidifier and cover plate facing into the Living Room, wire nut end of dehumidifier wire in junction box.
14.Bathroom exhaust fan with light to be 75 cfm with an integrated timer. Bath exhaust fan(s) after being turned on, shall run for a minimum of 60 minutes, even if the fan switch is turned off. Any over-ride to the minimum 60-minute requirement is not acceptable. Label with note shall be placed above bath fan switch stating, FAN ON TIMER AND SHUTS OFF AFTER 60 MINUTES.
15. Kitchen range hood exhaust fan with a white light shall be a minimum 100 cfm exhaust fan, with separate switches.
16. Bathroom and kitchen exhaust fans shall vent directly to the outside.
17. Ceiling lights shall have 2 LED bulbs.
18. The bathroom vanity light shall be wall mounted with 3 LED bulbs.
19. The circuit breaker(s) providing power to the TPS unit shall be equipped with a UL-listed locking device that can secure the breaker(s) in the ON position. Devices shall be installed set to the ON position.
20. Kitchen countertop receptacles and switches must be furred out to be 24" (max) from front edge of countertop and no more than 44" to the top of the switches or receptacles above finished floor.
21. N/A
22. Heat tape recept located within 24" of water inlet.
23. Smoke alarms shall not be located within 3 feet horizontally from any ceiling discharge grille.
24. Carbon Monoxide Alarms shall be approved and listed by the State of California Fire Marshal per California Information Bulletin 2012-03 (MH) - 06-26-2012.
S
WP
Sym. Description
110 volt duplex recep-wall mounted 110 volt duplex-GFCI protected recept
220 volt recept-wall mounted Light Fixture - Ceiling Mounted Light Fixture - Wall mounted Exhaust fan - Light Combo Distribution panel board - 200 amp Exterior light fixture - weather proof
TV
FE
S
S3
NOAA
T
Smoke Alarm w/ Strobe Light - wired in series Telephone Recept TV Outlet Fire Extinguisher Switch Switch - Three Way Outlet for NOAA Weather radio Thermostat
SA
Sym. Description
AC Disconnect
Service Entrance Conduit through bottom board from Main Distribution Panel Board
Optional Dehumidifier (Direct Wired)
20 Optional Dehumidifier 15 114-2GFCI
REV 02-03-25
x1
4x
4' -0
4'-8"40'-8"
4' -0
20'-8"
6' -0
16'-21 4"32'-8"
3' -2
12" R
ISER
F
HVAC DESIGN AND
TITLE:
Scale: 3/16" = 1'-0"
Date: 03/25/2020FEMA Manufactured Housing Units Federal Emergency Management Agency
DRAWING NO.
D-8F-9OVERHEAD DUCT DESIGN
Heating Cooling
Furnace/ A/C Specifications (10 KW Electric Furnace) Floors 0.0344
Air ducts in ceiling 0.0868
Ceilings and roofs of light color 0.0258
Walls (without windows and doors) 0.0804
U Values Heating
Duct Capacity
Air ducts in ceiling (Duct Area) 251 Sq. Ft.
22,535 Btuh
0.035
0.0896
0.0258
0.0766
Cooling
Express MHU (Furnace)
APPENDIX D
(1.5 Ton Air Conditioner)
HVAC Split Furnace / AC Notes
1. The furnace shall be at least a ninety-five percent (95%) efficient electric furnace (central heating system) capable of maintaining an average temperature of seventy degrees Fahrenheit (70°F) in the MHU.
2. The MHU shall be equipped with a specifically engineered HVAC split furnace /AC system based on the size and intended use of the MHU, in accordance with 24 CFR 3280.506, that is compatible with the HVAC split furnace
/AC system size.
3. The furnace shall also be built or equipped for the installation of a split type air conditioner and have enclosed space in water heater/furnace compartment for an A-coil evaporator unit, and with a 4-wire thermostat completely wired and installed.
4. A vibration damping pad shall be placed between the condensing unit and the mounting platform.
5. A 1” ratchet strap with 500 lb. capacity shall be installed around the outside of the condenser unit and bracket extension for transportation.
6. Air conditioning lines shall be pre-charged in the factory per manufacturers specifications and shall not have any leaks. Refrigerant lines shall be run next to the I-beam between the crossmembers and the bottom board where they will be protected from transportation damage. Refrigerant lines shall be secured to the I-beam at 48" O.C.
7. Furnace return air return grill shall be sized per furnace manufacturer's installation instructions.
8. Duct penetrations thru ceiling board shall be sealed.
9. All vent openings (intake or exhaust) to the exterior of the MHU HVAC wall mounted package system unit or furnace HVAC system shall have noncombustible corrosion-resistant mesh with a minimum of 1/16-inch, but not to exceed 1/8-inch openings, and comply with R337.6 of the 2019 California Residential Code.
HVAC General Notes
1. See FEMA specifications for programable and configurable thermostat requirements.
2. Duct system shall be constructed of Class 0 or Class 1 circular insulated flex ductwork or equal. Circular flex duct shall be sized per duct design calculations. All ducts to be insulated with a minimum of R-4 insulation.
3. Metal supply register sizes as shown on duct layout.
4. All supply ducts shall be in the roof attic space.
5. All supply duct seams and fasteners shall be sealed with UL-181A or UL-181B listed duct tape.
6. The manufacturer shall provide a duct pressure test report (See FEMA Spec for testing procedure) for each MHU duct system showing duct leakage of 5 percent or less prior to FEMA acceptance of the MHU.
7. No construction debris or sawdust shall be left in the duct system.
8. N/A
9. Return air grilles shall be sized per 24 CFR 3280.715(b)(4).
10. N/A
11. 14x4 RAG centered in bedroom entry door with bottom of opening 2 1/2" above floor. Minimum 20 S.I. of free air return area.
12. Bathroom exhaust fan location shall not be located next to the bathroom supply register.
REV 11-15-23
BACK DOOR SIDE ELEVATION
HITCH END ELEVATION TAIL END ELEVATION
FRONT DOOR SIDE ELEVATION
BACK DOOR
ANGLE RAIN DIVERTER OVER DOOR
RIDGE VENT (TYP.)
TRANSPONDER
INTERIOR FLOOR LINE
OUTSIDE
CONDENSER
UNIT WITH
PROTECTIVE
COVER
ANGLE RAIN DIVERTER OVER DOOR
RIDGE VENT (TYP.)
PEEP
HOLES
FRONT DOOR
INTERIOR FLOOR LINE
3" 3"
'-6 " M
AX
T
O T
O P
O F
R
ID
G E
VE
N
T
8'-6" EAVE TO EAVE MAX.
3" 3"
'-6
" M
AX
T O
T O
P O
F R
ID
G
E
VE
N T
8'-6" EAVE TO EAVE MAX.
24"
DRYER VENT.
12"HUD LABEL: APPROX. 12" UP FROM
FLOOR AND 12" FROM ROADSIDE.
HOSE BIB
OUTSIDE
CONDENSER
UNIT WITH
PROTECTIVE
COVER
TPS ELECTRICAL CONNECTION.
SEE D-8F-6, GENERAL NOTE 2.
METAL ROOF POD (TYP. 4 PLACES)
METAL ROOF POD (TYP.)
METAL ROOF POD (TYP. 4 PLACES)
8'-0"
EXTERIOR
RECEPT.
(GFCI)
8'-0"
AC DISCONNECT
EXTERIOR
LIGHT
EXTERIOR
LIGHT
PEEP
HOLES
EXTERIOR RECEPTACLE (GFCI)
RANGE EXHAUST FAN
SERVICE ENTRANCE CONDUIT
FEMA Manufactured Housing Units Federal Emergency Management Agency
TITLE: VERSION:
ELEVATIONS
Scale: 1/8" = 1'-0"
Date: 03/25/2020 DRAWING NO.
D-8F-10
APPENDIX D
Express MHU (Furnace)
Exterior Finish Notes
1. Siding shall be 19/32” thick LP SmartSide® panel (cedar texture) or equivalent.
2. Color of exterior paneling shall be light gray.
3. Siding shall be approved for Wind Zone 1 requirements.
4. The manufacturer shall provide a transponder sled. See Appendix A.
5. The sled shall be painted with a powder coat paint to match the exterior color of the MHU or white.
6. The transponder sled shall be made out of sheet metal.
7. Soffit, trim and J-Blocks shall be light gray or white.
8. All penetrations (i.e. electrical wires, HVAC lines, etc.) of the 19/32-inch LP SmartSide paneling or equivalent shall be caulked with a fire caulk. REV 11-15-23 . Feb 03, 2025
32'-0" CTR. OF AXLES (66.7% OF FRAME LENGTH)
48"48"
16'-0" CTR. OF AXLES
4" 291
2"
4"
4"
1 2"
10"x9# I-BEAM HEADER
10"x9# MAIN I-BEAM
CROSSMEMBER
(TYP)
Chassis Frame Notes
1. All metal-to-metal contact with 1/8” fillet weld minimum.
2. Floor shall be lagged to frame with frame clip, Fastec 9mm x 76mm listed lags or lags equivalent in size and strength at each joist and outrigger tip.
3. Clips shall be welded to the I-beam.
4. All parts of the chassis including added/welded parts shall be completely coated with waterproof paint.
5. Tires shall be new, 14.5” rim diameter, 14 ply with “G” load range.
6. Wheels and tires shall meet or exceed the axle rating and be rated for continuous speeds of 65 mph or greater.
7. All axles shall be new.
8. All axles shall be brake axles.
9. A valve stem cover shall be present on every tire.
10. The serial number shall be permanently stamped to the front header to comply with 3280.6. In addition, the serial number shall be painted with rust resistance contrasting color paint, 2 inches (2”) tall on the front header.
11. Rims, bolts, nuts, or other related tire-mounting hardware shall be new.
12. Longitudinal brackets shall be installed at 96” maximum from each end of the home.
13. Springs shall be 24 3/4" long multi-leaf.
14. All rims shall be the same color.
15. Maximum typical pier spacing along main I-beams at 8' O.C. Typical pier load = 4250 lbs.
16. Manufacturer to place permanent indicators (paint or label) on each I-beam at 2'-0" in from each end, 12'-0" O.C. max.
and at door jambs for locations of temporary piers for storage.
17. N/A
18. Structural steel shall be A36 and Fy: 36Ksi.
Frame Specs:
Main I-beam: 10X9# or equivalent with transportation test.
Front/Rear headers: 10x9# or equivalent with transportation test.
Cross members: 13 ga. C or Z, 1 12"x3"x1 12"@4'-0" O.C. Typ.
Outriggers: N/A.
Frame clip: 1"x1 12"x12 ga.
Hitch Specs:
See Chassis Details, Detail "A"
Welding Specs:
1. All welds to be a minimum 1/8" unless otherwise noted. Weld beads can be concave in application as long as the weld size is met.
2. Coupler and jack shall be welded per manufacture's installation instructions.
3. I-beam splice plate shall be 4" wide x height of I-beam minus 1 1/4"x13 GA. splice plate can be offset +/- 1/4". Weld shall be full width of splice plate. Splice plate only required on one side of I-beam.
4. All weld lengths stated or shown are minimum lengths and shall have a tolerance of minus 1/4" (except spring hangers). Weld lengths that are not noted shall be full length.
SEE
APPENDIX A,
PG. A-40
4"
42"
21"
48'-0"
10"
(MOVED JOIST)
2'-2"
(ADDED JOIST)
5'-4" 6'-8"
9'-4" 10'-8"
13'-4" 14'-8"
17'-4" 18'-8"
21'-4" 22'-8"26'-8"
28'-0"
29'-4"
30'-8" 32'-0"
33'-4"
34'-8"
36'-0" 37'-4"
38'-8"42'-8" 41'-4"45'-4"
46'-8"
FRAME CLIPS IN AXLE AREA ARE LOCATED ON INSIDE OF I-BEAM AS SHOWN.
2'-8"
25'-4"
10"x9# MAIN I-BEAM
13'-4" INSTALL TIRE BLOW-OUT
PROTECTION IN THIS AREA (BOTH SIDES)
25'-4" START BLOW-OUT PROTECTION
SEE CHASSIS DETAILS,
DETAIL "A"
DETAIL "B"
4'-0"
9'-4"
12'-0"16'-0"20'-0"24'-0"40'-0"44'-0"
13 GA. "C"
CROSSMEMBER
1-1/2"x3"x1-1/2"x2'
- SPRING HANGER
DRAWING NOTES
FRAME CLIP DETAIL (SAME ON BOTH MAIN I-BEAMS).
**DIMS ARE PULLED FROM END OF HEADER BEAM.
**BE SURE TO VERIFY FLOOR JOIST LAYOUT TO MATCH CLIPS TO JOISTS.
2"48" 331
4" 48"48"48"48"48"331 4"
48'-0" 4'-0"8'-0"12'-0"16'-0"20'-0"24'-0"44'-0" 40'-0" 37'-23 4" 34'-91
4" 32'-0" 26'-91 4"29'-23
4"
2"331
4"331 4"291
2"
32'-0" 16"
4" 5 HOLES AT 16" O.C.
16"
TYP.
FRONT AND REAR HEADER SHEARWALL LAG BOLT SPACING
16"
10"x9# I-BEAM
HEADER
ANGLE GUSSET INSTALLED ON
REAR OF THIS CROSS MEMBER
8'-0"
SEE A-40, NOTE 1.
CHASSIS
TITLE:
FEMA Manufactured Housing Units Federal Emergency Management Agency Scale: 3/16" = 1'-0"
DRAWING NO.
D-8F-11.1
VERSION:
APPENDIX D
Express MHU (Furnace)
Date: 03/25/2020
REV 11-15-23
DRAWBAR I-BEAM - 12" X 10.8#
DRAWBAR CROSSMEMBER I-BEAM - 12" X 10.8#
REINFORCEMENT UNDER FRONT HEADER AND
CENTERED BETWEEN FRONT HEADER AND TONGUE.
VENTURE 2-5/16" - 60 DEGREE, 10,000 LB. COUPLER OR EQUIVALENT
JACK - VENTURE TOP MOUNT,
10,000 LB. GALVANIZED OR EQUIVALENT.
7-3/8" X 4" NOSE PLATE
1"x1 1/2"x12 GA. FRAME CLIP.
1/8" x 1-1/2" FILLET WELD TO TOP
FLANGE OF I-BEAM.CROSSMEMBER -
C OR Z 1.5"x3"x1.5"
13 GA. AT 48" OC.
1-1/2" x 1-1/2" x 13 GA. ANGLE GUSSET 8" x 1"L FILLET WELD TO I-BEAM AND
CROSSMEMBER
I-BEAM - 10" X 9# AT 68 12"SPACING
FRONT AND REAR I-BEAM
HEADERS - 10" X 9#.
HITCH SHALL BE PAINTED GREEN
FULL
1"MAX
1"MAX
NO
WELD
3" Notes
1. Thickness is 4 gauge.
2. Vendor to assure all spring hangers are installed 90° to I-beam.
3. Shoulder bolts to be torqued per axle manufacturer requirements (Approximately 30 to 50 ft. lbs). Leaf spring to move freely in spring hanger.
4. Welds are not continuous around corners.
1/4" FILLET WELD
EACH SIDE
4"
I-BEAM FLANGE
LOOKING UP AT SPRING HANGER
SPRING HANGER
SPRING
HANGER
LEAF
SPRING
EQUALIZER
AXLE
U-BOLTS
LEAF
SPRING
SHACKLE LINK
WITH BOLTS
CENTER SPRING
HANGER
FRAME I-BEAM
FEMA Manufactured Housing Units Federal Emergency Management Agency
COMPANY:
DETAIL B: SPRING HANGER WELDING
DETAIL A: HITCH ASSEMBLY
CHASSIS DETAILS
TITLE:
Scale: NTS
03/25/2020 DRAWING NO.
D-8F-11.2
VERSION:
DETAIL D: EQUALIZER & SHACKLE LINK FASTENING
Notes
1. Shoulder bolts are to be used at all equalizer and shackle link locations.
2. Shoulder bolts shall be torqued per axle manufacturer requirements.
(Approximately 30 to 50 ft. lbs.)
3. Equalizer and shackle links are to move freely after shoulder bolts have been torqued.
4. Axle U-bolts shall be torqued per axle manufacturer requirements
(Approximately 70 to 95 ft. lbs.)
APPENDIX D
Express MHU (Furnace)
REV 11-29-21
H O
R
IZ
O N
TA
L
PA
N
EL
S
IZ
E
(IF
A
PP
LI
C
AB
LE
H O
R
IZ
O N
TA
L
PA
N
EL
S
IZ
E
(IF
A
PP
LI
C
AB
LE
/4
1/
E1
BATHROOM
/4 x
- B
AC
KE
R
U P
OPTIONAL VERTICAL WALL BOARD PANEL BREAKS
2x 6x
/2
BA
C
KE
R U
P
2x6 sprinkler head backer up.
Sprinkler head backer location may vary based on sprinkler design.
SEE NOTE 12.
TOP PLATE SPLICE
NTS
BOTTOM PLATE SPLICE
NTS
3" X 5" X 20 GA.
Metal connector plate, one each side
Min 2 x by top plate width by 10” splice block centered over splice, plus or minus 1 inch. Fastened with (6) - 7/16” x 15 Ga staples or (4) .131" nails each side of splice. Fasteners to have min. 1 inch penetration.
Min 1 x by bottom plate width by 10” splice block centered over splice, plus or minus 1 inch. Fastened with (6) - 7/16” x 15 Ga staples or (4) .131" nails each side of splice. Fasteners to have min. 1/2 inch penetration.
3" X 5" X 20 GA.
Metal connector plate, one each side
TITLE:
FEMA Manufactured Housing Units Federal Emergency Management Agency
COMPANY:
FRONT END WALL FRAMING AND
Scale: 3/8" = 1'-0"
DRAWING NO.
D-8F-17.1INTERIOR SHEATHING
Bottom plate to floor
Header to stud
Sill member (at opening) to stud
Multiple studs (to each other)
Multiple flat header members - 2 rows of fasteners 80% glue coverage.
Cripples to header, sill and plates
Gypsum to studs, 80% PVA glue
Exterior siding
Top plate to truss
Stud to plate
Layflats to top/bottom plate
FASTENING SCHEDULE - EXTERIOR WALLS
DESCRIPTION FASTENER APPLICATION
3 Each15 ga X 716" X 2 12" staple
OR 0.131 X 3" nail 2 Each
12" O.C0.131" X 3" nail OR
#8 X 3" wood screw 12" O.C
7 each ply15 ga X 716" X 2 12" staple
OR 0.131" X 3" nail 4 each ply
3 each
2 each
12" O.C
12" O.C
6" O.C
6" O.C
3 Each
2 Each
19 ga X 316" X 11 4" staple drywall screw
6" edges; &
12" field
0.131" X 3" nail OR
#8 X 4" wood screw
15 ga X 716" x 2 12" staple
15 ga X 716" X 2 12" staple
OR 0.131" X 3" nail
15 ga X 716" X 2 12" staple
OR 0.131" X 3" Nail
15 ga X 716" X 2 12" staple
OR 0.131" X 3" nail
15 ga X 716" X 2 12" staple
OR 0.131" X 3" nail
OR
Alternate Gypsum to studs, 100% one part urathane glue
19 ga X 316" X 11 4" staple drywall screw
6" edges
OR
2 Each
1 each
1 each
Backers to stud - Backers shall be #3 SPF min. and size as shown on drawings.
6 Each15 ga X 716" X 2 12" staple
OR 0.131 X 3" nail 3 Each
(end grain only)
(end grain or toed)
See Shearwall & Exterior Sheathing drawing
APPENDIX D
Express MHU (Furnace)
03/25/2020
Wall Framing Notes
1. The exterior wall framing shall be 2 x 4 nominal #2 SPF at 24” o.c.
2. Wall framing shall be 7'-6” from floor to ceiling.
3. Sidewall top plates shall be single 2 x 4 nominal #2 SPF.
4. Sidewall bottom plate shall be single 1 x 4 nominal SPF.
5. All major joints - wall to wall, wall to ceiling, wall to floor shall be caulked or gasketed to prevent air infiltration.
6. The wall insulation shall be kraft backed R-13 and will be installed without voids, gaps, or compression.
7. N/A
8. The walls shall be painted with latex, low VOC paint.
9. Housewrap applied over exterior sheathing.
10. All exterior penetrations (vents, lights, outlets, etc.) shall be flashed with ice and water shield 12” wide around penetration. Refer to Appendix 'A' for window and door flashing details.
11. Wall interiors shall be faced with 1/2" Gold Bond XP gypsum board with paint or equvalent installed per
ASTM C840 and GA-216.
12. When gypsum is installed horizontally a 1/8" x 3" continuous plywood backer strip shall be installed at the horizontal joint. Fasten to each stud with 2- 7/16 x 15 GA staples (min. 1" penetration).
REV 02-03-25. Feb 03, 2025
/4
E2
H O
R
IZ
O N
TA
L
PA
N
EL
S
IZ
E
(IF
A
PP
LI
C
AB
LE
H O
R
IZ
O N
TA
L
PA
N
EL
S
IZ
E
(IF
A
PP
LI
C
AB
LE
1/
BEDROOM #1
OPTIONAL VERTICAL WALL BOARD PANEL BREAKS
SEE NOTE 12.
TITLE:
FEMA Manufactured Housing Units Federal Emergency Management Agency
COMPANY:
REAR END WALL FRAMING AND
Scale: 3/8" = 1'-0"
DRAWING NO.
D-8F-17.2INTERIOR SHEATHING
APPENDIX D
Express MHU (Furnace)
Date: 03/25/2020
Wall Framing Notes
1. The exterior wall framing shall be 2 x 4 nominal #2 SPF at 24” o.c.
2. Wall framing shall be 7'-6” from floor to ceiling.
3. Sidewall top plates shall be single 2 x 4 nominal #2 SPF.
4. Sidewall bottom plate shall be single 1 x 4 nominal SPF.
5. All major joints - wall to wall, wall to ceiling, wall to floor shall be caulked or gasketed to prevent air infiltration.
6. The wall insulation shall be kraft backed R-13 and will be installed without voids, gaps, or compression.
7. N/A
8. The walls shall be painted with latex, low VOC paint.
9. Housewrap applied over exterior sheathing.
10. All exterior penetrations (vents, lights, outlets, etc.) shall be flashed with ice and water shield 12” wide around penetration. Refer to Appendix 'A' for window and door flashing details.
11. Wall interiors shall be faced with 1/2" Gold Bond XP gypsum board with paint or equvalent installed per ASTM C840 and GA-216.
12. When gypsum is installed horizontally a 1/8" x 3" continuous plywood backer strip shall be installed at the horizontal joint. Fasten to each stud with 2- 7/16 x 15 GA staples (min. 1" penetration). REV 02-03-25
90SI
D
EW
AL
L
SI
D
EW
AL
L
68 1/2 I-BEAM SPACING
24242424
SI
D
EW
AL
L
SI
D
EW
AL
L
68 1/2 I-BEAM SPACING
2424 2424
7/16" OSB ON EXTERIOR SIDE FASTENED
WITH 0.131x2-1/2" NAILS AT 6" OC ON
EDGES (DOUBLE STUDS REQUIRED AT
PANEL EDGES).
SHEATHING FASTENED TO TRUSS PER
SHEARWALL SCHEDULE
#8x4" SCREWS @ 5-1/4" OC
THRU TRUSS INTO TOP
PLATE. (STAGGER
FASTENERS). SEE NOTE 10.
(1) 2x4 TOP PLATE
#8x4 1/2" MIN.
SCREWS @ 10-1/2"
OC INTO SIDEWALL
STUD.
#8x4" SCREWS @
5-1/4" OC THRU
BOTTOM PLATE INTO
END FLOOR JOIST
10"x9# HEADER
2-2x8 #2 SPF
SHEARWALL JOISTS
1x4 BOTTOM PLATE
E2E1 FRONT SHEARWALL REAR SHEARWALL
SEE STRAP DETAIL BELOW
SEE NOTE 9.
SEE NOTE 9.
SEE NOTE 9.
END TRUSSES ONLY - ADD VERTICALS TO
MAINTAIN 24" O.C. SPACING. ADDED VERTICALS
SHALL BE 2X4 #2 SPF. FASTEN WITH 2 - 0.131x3"
NAILS TOED EACH CONNECTION.
/2 2x
LA
YF
LA
T
FO
R G
R
AB
B
AR
SEE STRAP
DETAIL BELOW
SEE NOTE 9.
SEE NOTE 9.
SEE NOTE 9.
SEE STRAP
DETAIL BELOW
(3) 1 1/2"x12"x26 ga.
straps w/ (6) 15 ga.
staples (1" min.
penetration) each end of strap.
See note 9.
TITLE:
FEMA Manufactured Housing Units Federal Emergency Management Agency
COMPANY:
Scale: 3/8" = 1'-0"
Date: 03/25/2020 DRAWING NO.
D-8F-18.1
SHEARWALL FRAMING AND
STRAP DETAIL
Scale: 1" = 1'-0"
EXTERIOR SHEATHING
APPENDIX D
Express MHU (Furnace)
Shearwall Notes
1. Shearwall joists shall be 2 - 2 X 8 #2 SPF.
2. Shearwall shall be lagged to 10" x 9 lb. header with five (5) equally spaced, Fastec 9mm x 76mm listed lags or lags equivalent.
3. 7/16" (24/16 span index) OSB shearwall sheathing shall be continuous over the shearwall joist and fastened with one (1) row of .131 x 3" nails at 6" o.c.
4. OSB shearwall sheathing shall be fastened to studs with .131 x 2" nails at 6" o.c. at edges and 12" o.c. in field.
5. OSB shearwall sheathing shall be continuous over the truss bottom chord and fastened one (1) row of .131 x 2" nails at 6" o.c.
6. Backers shall be #3 SPF min. and size as shown on drawings
7. Shearwall OSB sheathing to be overlaid with 19/32” thick LP SmartSide® panel (cedar texture) or equivalent.
8. 19/32” thick LP SmartSide® panel or equivalent shall be fastened with 0.113 diameter galvanized nails with a minimum 0.270-inch diameter head, minimum
1 ½ inch penetration into framing members. Fasteners to be spaced 3 inches o.c. at panel edges and 8 inches o.c. at intermediate framing members.
Nominal 1/4" bead of UL listed fire rated caulk required at all vertical joints.
9. Strap the first two sidewall studs with 1 1/2"x12"x26 ga. strap w/ (6) 15 ga. staples (1" min. penetration) each end of strap.
10. Truss to truss bottom chord fastening NOT required for double trusses over end shearwalls. Truss bottom chord fastening to top plate to be staggered from one truss bottom chord to the other truss bottom chord.
11. N/A
12. See Appendix A, Detail F.2 for clarification of shearwall OSB sheathing joint and fastening.
REV 9-8-22
1/
EXT. DOORWINDOW
48 21 1/2 37 1/4 DOOR HDR
30 1/2
WINDOW 4814 37 3/4
WINDOW
30 1/2
WINDOW36 3/4
37 1/4 78 1/489 3/4 30 1/2 30 1/2 48
8 10
/2
/2
H O
R
IZ
O N
TA
L
PA
N
EL
S
IZ
E
(IF
A
PP
LI
C
AB
LE
H O
R
IZ
O N
TA
L
PA
N
EL
S
IZ
E
(IF
A
PP
LI
C
AB
LE
HORIZONTAL
WALLBOARD
LAYOUT
VERTICAL
WALLBOARD
LAYOUT
OPTIONAL
117 1/2
48 41 1/24627 3/4
83 3/460 1/2 NO WALLBOARD
60 1/2 NO WALLBOARD
W/H
3060E3027 3680
FIXED PANE
F
0"
/4
2' -0
'-0
"4' -0
8' -0
'-0
'-0
30 1/2
/2
'-1
3/
4"
'-0
'-0
'-1
1/
4"
'-1
0"
'-0
'-0
K
.S
IN
K
1/
/4
S1
H
IT
C H
E N
D
'-0
'-5
/2
'-0
'-0
'-0
'-0
'-0
'-1
1/
4"
'-0
'-3
/4
'-0
'-0
'-0
30 1/2
/2
1/
/4
BA
C
KE
R
U P
BA
C
KE
R
U P
BA
C
KE
R
U P
BA
C
KE
R
U P
BA
C
KE
R
U P
BA
C
KE
R
U P
BA
C
KE
R
U P
BA
C
KE
R
U P
O H
EA
D
C
AB
IN
ET
S
O
VE
R H
EA
D
C
AB
IN
ET
S
'-2
/4
'-6
/4
O
H
EA
D C
AB
IN
ET
S
O
H
EA
D C
AB
IN
ET
S
6' -0
9' -7
/4
3' -0
'-0
/4
'-4
/2
10 1/2
R
AN
G
E
VE
N T 3
7/
DRYER VENT HOLE
37 1/4
/4
3/
/2
2x6
BCKR
UP
2x6
BCKR
UP
S
H O
W
ER
SEE NOTE 12.
SEE NOTE 12.
SEE NOTE 12.
SEE NOTE 12.
SEE NOTE 12.
'-6
/2
'-0
(1) 1 1/2"x12"x26 GA. STRAP W/ (6) 15 GA.
STAPLES (MIN. 1" PENETRATION) EACH
END OF STRAP. (SEE NOTE 12 ALSO)
(1) 1 1/2"x12"x26 GA. STRAP W/ (6) 15 GA.
STAPLES (MIN. 1" PENETRATION) EACH
END OF STRAP. (SEE NOTE 12 ALSO)
SEE NOTE 12.
SEE NOTE 22.
TITLE:
FEMA Manufactured Housing Units Federal Emergency Management Agency
COMPANY:
FRONT DOOR SIDEWALL
Scale: 3/16" = 1'-0"
Date: 03/25/2020 DRAWING NO.
D-8F-19
APPENDIX D
Express MHU (Furnace)
Wall Framing Notes
1. The exterior wall framing shall be 2 x 4 nominal #2 SPF at 24” o.c.
2. Wall framing shall be 7’-6” from floor to ceiling.
3. Sidewall top plates shall be single 2 x 4 nominal #2 SPF.
4. Sidewall bottom plate shall be single 1 x 4 nominal SPF.
5. All major joints – wall to wall, wall to ceiling, wall to floor shall be caulked or gasketed to prevent air infiltration.
6. The wall insulation shall be kraft backed R-13 and will be installed without voids, gaps, or compression.
7. Siding shall be 19/32” thick LP SmartSide® panel (cedar texture) or equivalent.
8. The walls shall be painted with latex, low VOC paint.
9. Headers shall be (2) 2 x 4 #2 SPF flat or equal fastened together with 80% adhesive and 7/16 x 2 ½ x 15 GA staples or .131 x 3” pd nails, 2 rows @ 6” o.c.
10. Housewrap applied over exterior sheathing.
11. All exterior penetrations (vents, lights, outlets, etc.) shall be flashed with ice and water shield 12” wide around penetration. Refer to Appendix 'A' for window and door flashing details.
12. Fasten stud to floor edge rail and roof edge rail with one (1) 1 ½” x 12” x 26ga strap w/ (6) 15ga staples (1" min.
penetration) each end of strap. Straps spaced at 48" o.c.
13. Vertical tie-down connectors or equivalent to be installed 2’ from each end of home and spaced 4'-0" o.c. maximum.
See D-8B-29.2.
14. Grab bar backers to be centered at grab bar mounting height.
15. Toilet paper holder backer to be centered at toilet paper holder mount height.
16. Range hood through wall size and location may vary. Manufacturer to verify size and location from range hood vendor that will be used. Range hood vent screen shall have minimum of 1/16 inch, but not to exceed 1/8-inch openings, and shall comply with R337.6 of the 2019 California Residential Code.
17. Gypsum to be jointed above all doors in line with jambs.
18. Gypsum to be jointed above and below all windows in line with jambs.
19. Wall interiors shall be faced with 1/2" Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
20. 7/16” thick LP SmartSide® panel or equivalent shall be fastened with 0.113 diameter galvanized nails with a minimum 0.270-inch diameter head, minimum 1 ½ inch penetration into framing members. Fasteners to be spaced 3 inches o.c. at panel edges and 8 inches o.c. at intermediate framing members. Nominal 1/4" bead of UL listed fire rated caulk required at all vertical joints.
21. Backers shall be #3 SPF min. and size as shown on drawings.
22. When gypsum is installed horizontally a 1/8" x 3" continuous utility grade plywood backer strip shall be installed at the horizontal joint. Fasten to each stud with 2- 7/16 x 15 GA staples (min. 1" penetration). REV 02-03-25
1/
EXT. DOORWINDOW
4837 1/4 DOOR HDR
30 1/2
WINDOW48
WINDOW
30 1/2
WINDOW19 1/2
37 1/463 3/4 30 1/2131 3/4
/2
H O
R
IZ
O N
TA
L
PA
N
EL
S
IZ
E
(IF
A
PP
LI
C
AB
LE
H O
R
IZ
O N
TA
L
PA
N
EL
S
IZ
E
(IF
A
PP
LI
C
AB
LE
HORIZONTAL
WALLBOARD
LAYOUT
VERTICAL
WALLBOARD
LAYOUT
OPTIONAL177 1/2
32 3/448 48
46 3/430 1/2
/2
33 1/246 3/432
30603060
4825 1/4
0"
/4
2' -0
'-0
" 4' -0
8' -0
37 1/4
/4
'-0
'-1
3/
4"
'-9
/2
'-8
/2
'-0
H
IT
C H
E N
D
'-2
'-0
'-0
'-0
'-0
'-0
30 1/2
/2
/4
BA
C
KE
R
U P
'-0
'-0
30 1/2
/2
/4
/2 G
R
AB
B
AR
BA
C
KE
R
U P
BA
C
KE
R
U P
'-0
'-0
'-0
'-0
'-0
/4
'-9
/2
6' -0
9' -7
/4
T
O W
EL
B
AR
T
.P
1x
BA
C
KE
R
D O
W N
(T R
AN
SP
O N
D
ER
'-8
/4
'-0
'-0
'-3
/4
P
AN
TR
Y 72 P
AN
TR
Y
S
H
EL
F
/2
/2
A
LT
. U
FA
S
SH
EL
F
LO
C
AT
IO
N
BKR
UP
2X6
BACKER
UP
2X6 64
BKR
UP
2X6
BACKER
UP
2X6
BACKER
UP
2X6
BACKER
UP
2X6
S2
1/
1/
3/
SEE NOTE 12.
SEE NOTE 12.
SEE NOTE 12.
SEE NOTE 12.
SEE NOTE 12.
1x
BA
C
KE
R
D O
W N
(T R
AN
SP
O N
D
ER
'-0
SEE NOTE 12.
(1) 1 1/2"x12"x26 GA. STRAP W/ (6) 15 GA.
STAPLES (MIN. 1" PENETRATION) EACH
END OF STRAP. (SEE NOTE 12 ALSO)
(1) 1 1/2"x12"x26 GA. STRAP W/ (6) 15 GA.
STAPLES (MIN. 1" PENETRATION) EACH
END OF STRAP. (SEE NOTE 12 ALSO)
'-0
2x6 SPRINKLER
HEAD BACKER
2x6 SPRINKLER
HEAD BACKER
2x4 SPRINKLER
HEAD BACKER
SEE NOTE 22.
TITLE:
FEMA Manufactured Housing Units Federal Emergency Management Agency
COMPANY:
BACK DOOR SIDEWALL
Scale: 3/16" = 1'-0"
Date: 03/25/2020 DRAWING NO.
D-8F-20
APPENDIX D
Express MHU (Furnace)
Wall Framing Notes
1. The exterior wall framing shall be 2 x 4 nominal #2 SPF at 24” o.c.
2. Wall framing shall be 7’-6” from floor to ceiling.
3. Sidewall top plates shall be single 2 x 4 nominal #2 SPF.
4. Sidewall bottom plate shall be single 1 x 4 nominal SPF.
5. All major joints – wall to wall, wall to ceiling, wall to floor shall be caulked or gasketed to prevent air infiltration.
6. The wall insulation shall be kraft backed R-13 and will be installed without voids, gaps, or compression.
7. Siding shall be 19/32” thick LP SmartSide® panel (cedar texture) or equivalent.
8. The walls shall be painted with latex, low VOC paint.
9. Headers shall be (2) 2 x 4 #2 SPF flat or equal fastened together with 80% adhesive and 7/16 x 2 ½ x 15 GA staples or .131 x 3” pd nails, 2 rows @ 6” o.c.
10. Housewrap applied over exterior sheathing.
11. All exterior penetrations (vents, lights, outlets, etc.) shall be flashed with ice and water shield 12” wide around penetration. Refer to Appendix 'A' for window and door flashing details.
12. Fasten stud to floor edge rail and roof edge rail with one (1) 1 ½” x 12” x 26ga strap w/ (6) 15ga staples (1" min. penetration) each end of strap. Straps spaced at 48" o.c.
13. Vertical tie-down connectors or equivalent to be installed 2’ from each end of home and spaced 4'-0" o.c. maximum. See D-8B-29.2.
14. Grab bar backers to be centered at grab bar mounting height.
15. Toilet paper holder backer to be centered at toilet paper holder mount height.
16. Gypsum to be jointed above all doors in line with jambs.
17. Gypsum to be jointed above and below all windows in line with jambs.
18. Sprinkler head backer location may vary based on sprinkler design.
19. Wall interiors shall be faced with 1/2" Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.
20. 19/32” thick LP SmartSide® panel or equivalent shall be fastened with 0.113 diameter galvanized nails with a minimum 0.270-inch diameter head, minimum 1 ½ inch penetration into framing members. Fasteners to be spaced 3 inches o.c. at panel edges and 8 inches o.c.
at intermediate framing members. Nominal 1/4" bead of UL listed fire rated caulk required at all vertical joints.
21. Backers shall be #3 SPF min. and size as shown on drawings.
22. When gypsum is installed horizontally a 1/8" x 3" continuous utility grade plywood backer strip shall be installed at the horizontal joint. Fasten to each stud with 2- 7/16 x 15 GA staples (min.
1" penetration).
REV 02-03-25
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
'-0
" 0"
'-8
'-0
M O
VE
T
R U
SS
'-6
/4
'-0
'-0
'-0
2' -0
" 0"
48" 48" 48" 48" 48" 48" 48" 48" 48" 48" 48" 24"
CEILING BOARD LAYOUT
8' -0
6' -0
4' -0
DRAWING NOTES
· START WITH A 32" CUT PIECE OF CEILING BOARD AT REAR OF HOME
· 1x4 OR PLANT STANDARD CEILING BACKERS FOR WALL TIE-IN.
· ALL DUCTS TO BE MINIMUM R-4.
PANEL BOX
'-0
'-0
'-0
AD
D
T R
U
SS
'-1
1/ 4"
FU
R
N
AC
E M
IX
ER
B O
X
48 48
SC
9'-73 4" 6'-21
2"14'-113 4"29'-91
4"
6'-4"12'-8"
24'-8"
23'-4"
27'-3"
38'-4"
43'-4"
38'-31 4"
4' -0
4'-8"40'-8"
4' -0
20'-8"
6' -0
32'-8"
3' -2
3"" OVERHANG
3"" OVERHANG
SC
" V
TR
2x4x12" #2 SPF blocks at 2'-0" O.C.
2x4x12" #2 SPF blocks at 2'-0" O.C.
31'-4"
24"
37'-01 4"
39'-91 2"
36'-73 4" (2x6x48")
4" (2x6x84")
39'-5" (2x6x24")
FACIA SPLICE EDGE RAIL SPLICE
3" X 4" X 20 GA.
Metal connector plate, one each side
Min 2" X 4" X 14" block centered over splice +/- 1/4" and fastened with 80% coverage PVA adhesive and 4-.131x3" nails each side of splice
4" X 4" X 20 GA.
Metal connector plate, one each side
Min 2" X 6" X 14" block centered over splice +/- 1" and fastened with 80% coverage PVA adhesive and 6-.131x3" nails each side of splice
2x6 edge rail2x4 Fascia
2x4 Fascia 2x6 edge rail
FEMA Manufactured Housing Units Federal Emergency Management Agency
COMPANY:
ROOF FRAMING LAYOUT
Scale: 3/16" = 1'-0"
DRAWING NO.
D-8F-21
Roof Framing Notes
1. The roof trusses shall be spaced at 24” o.c. maximum.
2. Overall shipping width shall not exceed 8'-6".
3. The roof pitch shall be nominal 4:12.
4. The attic insulation shall be R-38 blown insulation.
5. The roof sheathing shall be at least 7/16” structurally rated OSB with 24/16 index minimum span rating.
6. Roof felt shall be 2 layers of 15# felt or 1 layer of 30# felt or equivalent synthetic underlayment.
7. The roof covering shall be cemented to the roof decking with 6” wide strip cement, around the perimeter.
8. Ice and water shield, per ASTM D1970 to be self-adhering rubberized asphalt 40 mils minimum thick shall be installed (36” width from eaves).
9. The roof shall have a light or white colored composition 240# architectural style shingle.
10. Ridge vent shall be Class A rated. Vent opening in ridge vent shall have a minimum of 1/16 inch, but not to exceed 1/8 inch openings, or equivalent and comply with R337.6 of the 2019 California Residential Code.
11. The roof sheathing shall span at least 2 truss bays.
12. 24” x 24” ice and water shield shall be installed around all roof penetrations.
13. All roof penetrations shall be capped with a galvanized or aluminum metal cap.
14. Foam baffles designed for 16” o.c. truss spacing to be used to maintain 1” air gap between the roof decking and insulation.
15. All framing members to be #2 SPF or equal.
16. N/A
17. N/A
18. Foam nail polyurethane structural foam adhesive, or equivalent, to be installed per dead load test fastening requirements.
19. Roof trusses must be aligned with studs below.
Sheathing to truss (for optional blocked diaphragm see note 17)
DESCRIPTION FASTENER APPLICATION
FASTENING SCHEDULE - ROOF
0.131 x 2" nail
Blocking to truss 2 each at each end.7/16"C x 2-1/2"L x 15Ga staple
Gypsum ceiling to truss Foam adhesive (as per installation instructions.)
Lay flat to gypsum ceiling - Lay flats shall be #3 SPF min. and size as shown on drawings.
Tack in place with foam adhesive.
Fascia to truss (3) each, 7/16"C x 2-1/2"L x 15Ga. staples through fascia Edge rail to truss (5) 7/16"C x 2-1/2"L x 15Ga. staples or (3) .131 x 3" nails
Edge rail to top plate 0.131 x 3-1/2" nails or #8x 4" screws @ 12" o.c. toed.
Strap to edge rail See sidewall drawings for type & quantity of fasteners.
Top plate to truss. 1 each0.131 x 3" nail
1 eachOR #8 x 4" screw 6" o.c. edge / 12" o.c.
field into each truss.
APPENDIX D
Express MHU (Furnace)
Date: 03/25/2020
REV 06-03-22
- ATTIC RIDGE VENT (INSTALL PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS.
2'-117 16" 8'-0"
6'-117 16" 8'-0"
2'-117 16"6'-8"8'-0"
2'-117 16"6'-8"
5'-77 16"
16'-97 16"15'-0"
48'-67 8"
16'-97 16"
8'-0" 8'-0" 8'-0" 8'-0"
8'-0" 8'-0" 8'-0"
8'-0"8'-0"8'-0"6'-117 16"
SEE GAP DETAIL BELOW
15 LINEAR FEET OF CERTAINTEED 9" FILTER CLASS A
FIRE RATED RIDGE VENT OR EQUIVALENT, CENTERED
ON ROOF. (16 SQ. IN. NET FREE VENT AREA PER FOOT)
SEE NOTE 8 (TYP. 4 PLACES)
1" GAP 1" GAP
2" GAP TOTAL
GAP DETAIL - ROOF DECKING AT RIDGE VENT LOCATION
SCALE 1/2" = 1'
233 4"
283 4"
8" W/O RIDGE VENT
23 3 4"
28 3 4"
8" W/O RIDGE VENT
FEMA Manufactured Housing Units Federal Emergency Management Agency
COMPANY:
ROOF SHEATHING LAYOUT
Scale: 3/16" = 1'-0"
Date: 03/25/2020 DRAWING NO.
D-8F-22
NOTE: ROOF DECKING CUT BACK ONLY AT RIDGE VENT AREA
APPENDIX D
Express MHU (Furnace)
Roof Edge Detail Notes
1. The roof sheathing shall be at least 7/16” structurally rated OSB with
24/16 index minimum span rating.
2. Decking cuts include endwall overhangs.
3. Use roof decking off-fall for roof wind diverters.
4. H clips shall be used at all joints between trusses.
5. Roof underlayment shall be a minimum of 15-pound asphalt felt. Typical manufactured housing full width paper underlayment is not acceptable.
6. Asphalt shingles shall be Class A rated and comply with R337.5 of the 2019 California Residential Code.
7. Ridge vent shall be Class A rated. Vent openings in ridge vent shall have a minimum of 1/16-inch, but not to exceed 1/8-inch openings, and comply with R337.6 of the 2019 California
Residential Code.
8. Roof low vents shall be metal roof pods, Class A rated, minimum 50 square inches of free air area. Metal roof pods shall have a minimum of 1/16-inch, but not to exceed 1/8-inch openings, and comply with R337.6 of the 2019 California Residential Code. Metal roof pods shall be evenly spaced along length of MHU and approximately 16 inches from edge of roof to centerline of metal roof pod.
REV 11-29-21. Feb 03, 2025
FURNACE PLENUM
4"
TRUSS @ 24" O.C.
GYPSUM CEILING BOARD
2x4 SIDEWALL STUD
2x4 FASCIA BOARD
SHINGLES W/ ICE AND
WATER SHIELD AND
ROOF UNDERLAYMENT.
ROOF DECKING
DRIP EDGE
METAL FASCIA
19/32" LP SMARTSIDE
PANELING OR
EQUIVALENT
CONTINUOUS
SOFFIT.
2x4 SIDEWALL TOP PLATE
1 4"
H
EE
L H
EI
G
H T
SHINGLE/TIP OF
DRIP EDGE
FOAM OR PLASTIC
BAFFLES TO MAINTAIN
1" AIR SPACE
2x6 ROOF EDGE RAIL
7'-6"
8'-0"
3"
19/32" LP SMARTSIDE
PANELING OR
EQUIVALENT
WEATHER RESISTANT
BARRIER
SEE NOTE 7.
GABLE ENDWALL OVERHANG DETAIL
TRUSS
TOP
CHORD
MIN. 2X3
2X4 #2 SPF
FASCIA BOARD.
FASTEN TO
BLOCKING WITH
(6) 7/16"X2 1/2"X
15GA STAPLES.
2X4X12" #2 SPF
BLOCKS AT 2'-0"
O.C. FASTEN TO
TRUSS TOP
CHORD WITH (6)
7/16"X2 1/2"X
15GA STAPLES .
7/16" OSB
STRUCTURALLY
RATED 24/16
SPAN INDEX
19/32" SMARTSIDE
PANELING OR
EQUIVALENT
3"
METAL DRIP
EDGE
19/32" LP
SMARTSIDE
PANELING OR
EQUIVALENT
CONTINUOUS
SOFFIT.
METAL FASCIA
FEMA Manufactured Housing Units Federal Emergency Management Agency
COMPANY:
ROOF OVERHANG DETAIL
Date: 03/25/2020 DRAWING NO.
D-8F-23
Note:
Fasteners to be a minimum of ½” to a maximum of 1” from the top or bottom of the truss top chord or 2x4 fascia.
Fasteners to be staggered top and bottom.
APPENDIX D
Express MHU (Furnace)Scale: 1-1/2" = 1'-0"
Roof Overhang General Notes
1. The roof trusses shall be spaced at 24” O.C. with a 3” overhang. Overall shipping width shall not exceed 8.5 feet.
2. The roof pitch shall be nominal 4:12.
3. The attic insulation shall be R-38 blown.
4. Foam baffles designed for 24” o.c. truss spacing to be used to maintain 1” air gap between the roof decking and insulation.
5. Metal roof pods, Class A rated, shall provide the free air area required by 3280.504(d)(1)(i).
6. R Value per inch is a minimum of 2.81.
7. Roof low vents shall be metal roof pods, Class A rated, minimum 50 square inches of free air area. Metal roof pod vent screens shall have a minimum of
1/16-inch, but not to exceed 1/8-inch openings, and comply with R337.6 of the 2019 California Residential Code. Metal roof pods shall be evenly spaced along length of MHU and approximately 16 inches from edge of roof to centerline of metal roof pod. REV 11-29-21 . Feb 03, 2025
BACK DOOR SIDE ELEVATION
HITCH END ELEVATION TAIL END ELEVATION
FRONT DOOR SIDE ELEVATION
BACK DOOR
ANGLE RAIN DIVERTER OVER DOOR
RIDGE VENT (TYP.)
TRANSPONDER
INTERIOR FLOOR LINE
OUTSIDE
CONDENSER
UNIT WITH
PROTECTIVE
COVER
ANGLE RAIN DIVERTER OVER DOOR
RIDGE VENT (TYP.)
PEEP
HOLES
FRONT DOOR
INTERIOR FLOOR LINE
3" 3"
'-6 " M
AX
T
O T
O P
O F
R
ID
G E
VE
N
T
8'-6" EAVE TO EAVE MAX.
3" 3"
'-6
" M
AX
T O
T O
P O
F R
ID
G
E
VE
N T
8'-6" EAVE TO EAVE MAX.
24"
DRYER VENT.
SHINGLES COVERED BY PLASTIC WRAP
SHINGLES COVERED BY PLASTIC WRAP
OSB FROM BOTTOM OF SHINGLES
TO TOP OF ROOF
OSB FROM BOTTOM OF
SHINGLES TO TOP OF ROOF
12"HUD LABEL: APPROX. 12" UP FROM
FLOOR AND 12" FROM ROADSIDE.
OSB STRIPS FROM BOTTOM OF THE
SIDING TO BOTTOM OF THE EAVE
OSB WIND DIVERTERS
HOSE BIB
OUTSIDE
CONDENSER
UNIT WITH
PROTECTIVE
COVER
TPS ELECTRICAL CONNECTION.
SEE D-8F-6, GENERAL NOTE 2.
METAL ROOF POD (TYP. 4 PLACES)
METAL ROOF POD (TYP. 4 PLACES)
8'-0"
EXTERIOR
RECEPT.
(GFCI)
8'-0"
AC DISCONNECT
EXTERIOR
LIGHT
EXTERIOR
LIGHT
PEEP
HOLES
EXTERIOR RECEPTACLE (GFCI)
RANGE EXHAUST FAN
SERVICE ENTRANCE CONDUIT
FEMA Manufactured Housing Units Federal Emergency Management Agency
TITLE: VERSION:
TRANSIT PROTECTION DETAILS
Scale: 1/8" = 1'-0"
Date: 03/25/2020 DRAWING NO.
D-8F-27
APPENDIX D
Express MHU (Furnace)
Transit Protection Detail Notes
1. Temporary wind guards for shingles shall be installed on the MHU exterior.
2. Shingle wind guards shall be made of OSB.
3. Shingle wind guards shall not extend above the maximum transportation height.
4. Shingles shall be secured with a plastic wrap on the first 10' of the MHU from the hitch end.
5. OSB off-fall from roof decking may be used for roof wind diverters.
REV 11-15-23 . Feb 03, 2025
2 REAR SIDE MARKER LAMPS, ONE ON
EACH SIDE, PHOTOMETRICALLY
CERTIFIED AT INSTALLATION ANGLE,
AT 45" HEIGHT ABOVE GROUND.
2 REAR SIDE REFLEX REFLECTORS, ONE
ON EACH SIDE, FACING SIDEWARDS AT
45" HEIGHT ABOVE GROUND.
2 TAIL LAMPS, 2 STOP LAMPS, 2 REAR TURN
SIGNAL LAMPS, SYMMETRICALLY PLACED AT 45"
HEIGHT ABOVE GROUND. MIN. 2 REAR RELEX
REFLECTORS, SYMMETRICALLY PLACED, FACING
REARWARD.
LICENSE PLATE LAMP
PLACED ABOVE OR
ON EITHER SIDES OF
THE LICENSE PLATE
3 REAR IDENTIFICATION LAMPS AT THE CENTER
SPACED 12" C-C AS HIGH AS POSSIBLE.
REAR CLEARANCE LAMP AT WIDEST POINT FACING
REARWARD AT 16" FROM TOPMOST POINT.
MIN. 2 INTERMEDIATE SIDE REFLEX REFLECTORS, NEAR THE
CENTER, FACING SIDEWARDS AT 45" HEIGHT ABOVE GROUND.
2 REAR SIDE REFLEX REFLECTORS, ONE ON EACH SIDE,
FACING SIDEWARDS AT 45" HEIGHT ABOVE GROUND.
MIN. 2 INTERMEDIATE SIDE MARKER LAMPS, NEAR THE
CENTER, FACING SIDEWARDS AT 45" MIN. HEIGHT
ABOVE GROUND.
FRONT SIDE REFLEX REFLECTORS, ONE
ON EACH SIDE, FACING SIDEWARDS
FRONT SIDE MARKER LAMPS, ONE ON
EACH SIDE, PHOTOMETRICALLY
CERTIFIED AT INSTALLATION ANGLE AT
45" HEIGHT ABOVE GROUND.
FRONT CLEARANCE LAMPS AT WIDEST POINT
FACING FORWARD AT 16" FROM TOPMOST POINT.
2 FRONT SIDE MARKER LAMPS, ONE ON EACH SIDE PHOTOMETRICALLY
CERTIFIED AT INSTALLATION ANGLE AT 45" HEIGHT ABOVE THE GROUND.
2 FRONT SIDE REFLEX REFLECTORS ONE ON EACH SIDE
FACING SIDEWARDS AT 45" HEIGHT ABOVE GROUND.
REAR CLEARANCE LAMP AT WIDEST POINT
FACING REARWARD AT 16" FROM TOPMOST
POINT.
FLOOR PLAN
SCALE: 3/16" = 1'
F
HITCH END ELEVATIONTAIL END ELEVATION FRONT DOOR SIDE ELEVATION
FRONT CLEARANCE
LAMPS
TAIL LAMP,
STOP LAMP,
TURN SIGNAL
LAMP
REAR REFLEX
REFLECTOR
LICENSE PLATE
LAMP (ABOVE
THE PLATE)
REAR SIDE MARKER LAMP
REAR SIDE REFLEX REFLECTOR
SCALE: 1/8" = 1' SCALE: 1/8" = 1' SCALE: 1/8" = 1'
MIN. 2 INTERMEDIATE
SIDE MARKER LAMPS
FRONT SIDE MARKER LAMP
FRONT SIDE REFLEX REFLECTOR
MIN. 2 INTERMEDIATE SIDE
REFLEX REFLECTORS
TRANSPORTATION LIGHTING
TITLE:
Scale: N/A
Date: 03/25/2020FEMA Manufactured Housing Units Federal Emergency Management Agency
DRAWING NO.
D-8F-28
APPENDIX D
Express MHU (Furnace)
General Notes
1. Battery box and wiring shall be installed per specs.
2. The 8' wide Express unit shall be equipped with a permanent lighting per USDOT NHTSA FMVSS 571.108.
3. The 8' wide Express unit shall be able to be transported without special permits.
4. All wire penetrations of the 7/16-inch LP SmartSide paneling or equivalent shall be caulked with a fire caulk. REV 9-8-20
PIERS FRAME TIEDOWNS
2'-0"
MAX
TIEDOWN
SPACING
PER CHART
TYPICAL SIDE ELEVATION SHOWING TIEDOWN SPACINGS.
Tiedowns are based on roof diaphragm spanning the entire length of the unit (48'-0" Max) (i.e. Based on uplift and load into floor diaphragm only).
Therefore tiedowns are required at each end for end shearwall overturning and lateral forces as follows.
2'-0"
MAX
TIEDO…