2.1.1 Attachment 3 - 1BR NextGen CAD Drawings HVAC Wall Mounted - FEB-03-2025 PE Sealed.pdf

PDF 10 MB Posted

Attached to
Amendment # 5 70FB8025R00000018 - DHS FEMA Manufactured Housing Units (MHUs) 2025
Solicitation number
70FB8025R00000018
Issued by

About this file

This document contains detailed Computer-Aided Design (CAD) drawings for a Next Generation (NextGen) one-bedroom Manufactured Housing Unit (MHU) developed for the Federal Emergency Management Agency (FEMA). The 14-foot wide housing unit is designed with a wall-mounted HVAC packaged system and includes comprehensive technical specifications covering structural, electrical, plumbing, and architectural elements.

The drawings provide extensive technical details including floor plans, electrical layouts, water and drain line configurations, interior and exterior wall framing, roof structure, tie-down systems, and installation requirements. Key specifications include Wind Zone 3 compliance, R-38 attic insulation, accessibility standards (UFAS), sprinkler system integration, and design requirements for Wind Zone 3 with specific provisions for structural loads, framing, sheathing, and transportation protection. The document is dated February 3, 2025, and includes multiple detailed drawings covering every aspect of the manufactured housing unit's design and construction.

View the file

Other files

File Type Posted
2.1.1 Attachment 1 NextGen MHU Pricing Structure (for Offerors) 02.26.25.xlsx Rev. 2_August 3, 2025.xlsx XLSX spreadsheet
2.1.1 Attachment 1 NextGen MHU Pricing Structure (for Offerors) 02.26.25.xlsx_Rev. 2_August 3, 2025.xlsx XLSX spreadsheet
Sol_70FB8025R00000018_Amd_0005.pdf PDF
Sol_70FB8025R00000018_Amd_0004.pdf PDF
2.1.1 Attachment 1 NextGen MHU Pricing Structure (for Offerors) 02.26.25.xlsx_Rev. 1_August 1, 2025.xlsx XLSX spreadsheet
2.1.1+Attachment+12+MHU+Solicitation+and+Comment+Matrix+02.20.25_August 1, 2025.xlsx XLSX spreadsheet
Sol_70FB8025R00000018_Amd_0003.pdf PDF
Amendment 2_ 2.1.1 Attachment 12 MHU Solicitation and Comment Matrix 02.20.25_Responses July 8 2025_AC.xlsx XLSX spreadsheet
Sol_70FB8025R00000018_Amd_0002.pdf PDF
Sol_70FB8025R00000018_Amd_0001.pdf PDF
2.1.1 70FB8025R00000018_MHU Soliciation 2025_Final_Rev2_June 27, 2025.pdf PDF
2.1.1 70FB8025R00000018_MHU Soliciation 2025_Final_Rev1.pdf PDF
2.1.1 Attachment 3 - Express Cal Wildfire NextGen CAD Drawings Furnace-AC System - FEB-03-2025 PE Sealed.pdf PDF
2.1.1 Attachment 9 Acronyms NextGen Rev 2.20.25.pdf PDF
2 - Appendix C - FEB-03-2025.pdf PDF
2.1.1 Attachment 12 MHU Solicitation and Comment Matrix 02.20.25.xlsx XLSX spreadsheet
2.1.1 Attachment 8 MHU First Article Inspection Checklist (2.11.20) Rev 02.20.25.pdf PDF
2.1.1 Attachment 6 MHU Delivery Schedule and Daily Production Report Template 02.20.25.xlsx XLSX spreadsheet
2 - Appendix B Revision Log - FEB-03-2025.pdf PDF
2.1.1 Attachment 14 NextGen Warranty Repairs In The Field List 02.26.25.pdf PDF
2 - Appendix A Revision Log - FEB-03-2025.pdf PDF
2.1.1 Attachment 3 - 2 BR NextGen CAD Drawings HVAC Wall Mounted - FEB-03-2025 PE Sealed.pdf PDF
2.1.1 Attachment 3 - 3BR NextGen CAD Drawings Furnace-AC System - FEB-03-2025 PE Sealed.pdf PDF
2.1.1 Attachment 3 - 2BR NextGen CAD Drawings Furnace-AC System - FEB-03-2025 PE Sealed.pdf PDF
2.1.1 Attachment 3 - 3 BR NextGen CAD Drawings HVAC Wall Mounted - FEB-03-2025 PE Sealed.pdf PDF
2 - Appendix A Typical NextGen MHU Details - FEB-03-2025 PE Sealed.pdf PDF
2.1.1 Attachment 13 DAPIA Concurrence Letters Rev 02.20.25.pdf PDF
2.1.1 Attachment 11 MHU_Past Performance Questionnaire 02.20.25.docx DOCX document
2 - Appendix C Revision Log - FEB-03-2025.pdf PDF
2.1.1 Attachment 3 - 1BR Cal Wildfire NextGen CAD Drawings Furnace-AC System - FEB-03-2025 PE Sealed.pdf PDF
2.1.1 70FB8025R00000018_MHU Soliciation 2025_Final.pdf PDF
2.1.1 Attachment 15 Misc Parts and Materials 02.26.25.pdf PDF
2 - Appendix B Typical NextGen Cut Sheets - FEB-03-2025.pdf PDF
2.1.1 Attachment 3 - 3BR Cal Wildfire NextGen CAD Drawings HVAC Wall Mounted - FEB-03-2025 PE Sealed.pdf PDF
2.1.1 Attachment 3 - 2BR Cal Wildfire NextGen CAD Drawings HVAC Wall Mounted - FEB-03-2025 PE Sealed.pdf PDF
2.1.1 Attachment 3 - Express Cal Wildfire HVAC Wall Mounted Revision Log - FEB-03-2025.pdf PDF
2.1.1 Attachment 3 - Express NextGen CAD Drawings HVAC Wall Mounted - FEB-03-2025 PE Sealed.pdf PDF
2.1.1 Attachment 3 - 2BR Cal Wildfire NextGen CAD Drawings Furnace-AC System - FEB-03-2025 PE Sealed.pdf PDF
2.1.1 Attachment 5 NextGen MFG_shipment_Notification 02.20.25.xlsx XLSX spreadsheet
2.1.1 Attachment 7 Invoice-Sample_Blank 02.20.25.xlsx XLSX spreadsheet
2.1.1 Attachment 3 - 1BR Cal Wildfire NextGen CAD Drawings HVAC Wall Mounted - FEB-03-2025 PE Sealed.pdf PDF
2.1.1 Attachment 1 NextGen MHU Pricing Structure (for Offerors) 02.26.25.xlsx XLSX spreadsheet
2 - FEMA NextGen MHU Additional Requirements - Version 1 - FEB-03-2025.pdf PDF
2.1.1 Attachment 10 MHU_Quality_Assurance_Plan 28July2020 Rev.1 02.20.25.pdf PDF
1.1.3 Attachment 2 NextGen Statement of Work - Final.pdf PDF
2 - FEMA NextGen MHU Additional Requirements - Version 1 Revision Log - FEB-03-2025.pdf PDF
2.1.1 Attachment 3 - 1BR NextGen CAD Drawings Furnace-AC System - FEB-03-2025 PE Sealed.pdf PDF
2.1.1 Attachment 3 - Express NextGen CAD Drawings Furnace-AC System - FEB-03-2025 PE Sealed.pdf PDF
2.1.1 Attachment 3 - 3BR Cal Wildfire NextGen CAD Drawings Furnace-AC System - FEB-03-2025 PE Sealed.pdf PDF
2.1.1 Attachment 4 MHU Intake-Transfer Inspection Checklist (08.04.22) Rev 02.20.25.pdf PDF
Show all 50

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MANUFACTURED HOUSING UNIT

FEDERAL EMERGENCY MANAGEMENT AGENCY

NEXT GEN 1 BEDROOM UNIT

(HVAC WALL MOUNTED PACKAGED SYSTEM)

FEBRUARY 3, 2025

TITLE:

1/8" = 1'-0"

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DRAWING NO.DATE:

SCALE:

COMPANY: VERSION:

14B1-1.1COVER PAGE 14' WIDE MHU

(PACKAGED SYSTEM)

REV 02-03-25. Feb 03, 2025

Attachment 3

DWG. NO. TITLE

14B1-1.1 14B1-1.2

14B1-1.3 GENERAL NOTES

14B1-2 FLOOR PLAN

14B1-3

14B1-4.1

14B1-5

DOOR AND WINDOW SCHEDULE

14B1-6 14B1-7

DRAIN LINES14B1-8

HVAC DESIGN AND OVERHEAD DUCT LAYOUT14B1-9

INTERIOR WALL AND BACKPANELING LAYOUT (HORIZONTAL)

14B1-10

INTERIOR WALLS

14B1-11.1

FRONT SHEARWALL FRAMING AND EXTERIOR SHEATHING

14B1-12

ROOF FRAMING LAYOUT

14B1-13

ROOF SHEATHING LAYOUT

14B1-14 14B1-15

14B1-16.1-16.11 14B1-17.1-17.2

14B1-18.1

14B1-19 14B1-20

ROOF OVERHANG DETAIL

14B1-21 14B1-22

SPRINKLER SYSTEM LAYOUT

14B1-23

TRANSIT PROTECTION DETAILS

RESERVED

14B1-25.1

14B1-26 14B1-27 14B1-28

COVER PAGE

INDEX

UFAS LAYOUT

ELECTRICAL PLAN

WATER LINES

FURNITURE PLAN

FLOOR DECKING LAYOUT

INTERIOR WALL AND BACKPANELING LAYOUT (VERTICAL) - OPTIONAL

ELEVATIONS

CHASSIS

FLOOR FRAMING LAYOUT

ENDWALL FRAMING AND INTERIOR SHEATHING

SHIP LOOSE LAYOUT

FRONT DOOR SIDEWALL

BACK DOOR SIDEWALL

TIE DOWN SYSTEM14B1-29.1

EXTERIOR WALL TIEDOWN DETAILS14B1-29.2

KITCHEN ELEVATIONS14B1-24.1

BATHROOM #1 ELEVATIONS14B1-24.2

RESERVED14B1-24.3

DOUBLE STACK PIER LAYOUT AND DETAILS14B1-30

INDEX

14B1-11.2 CHASSIS DETAILS

14B1-18.2

RESERVED14B1-25.2

REAR SHEARWALL FRAMING AND EXTERIOR SHEATHING

14B1-4.2 INSTALLED FURNITURE LAYOUT

14B1-11.1.1 ALT. CHASSIS (95.5" I-BEAM SPACING)

ALT. TIE DOWN SYSTEM (95.5" I-BEAM SPACING)14B1-29.1.1

ALT. EXTERIOR WALL TIEDOWN DETAILS (95.5" I-BEAM SPACING)14B1-29.2.1

ALT. DOUBLE STACK PIER LAYOUT AND DETAILS (95.5" I-BEAM SPACING)14B1-30.1

TITLE:

1/8" = 1'-0"

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DRAWING NO.DATE:

SCALE:

COMPANY: VERSION:

14B1-1.2INDEX

14' WIDE MHU

(PACKAGED SYSTEM)

REV 04-30-21

. Feb 03, 2025

MANUFACTURED HOUSING UNIT

FEDERAL EMERGENCY MANAGMENT AGENCY

GENERAL NOTES

CODES AND STANDARDS

Manufactured Home Construction and Safety Standards 24 CFR 3280 Manufactured Home Procedural and Enforcement Regulations 24 CFR 3282 Uniform Federal Accessibility Standards (UFAS) Standard for the Installation of Sprinkler Systems in Manufactured Homes (NFPA 13D) Referenced 2005 National Electrical Code (NFPA 70) Articles as Incorporated in HUD 24 CFR 3280

STRUCTURAL LOADS

Floor Live Load 40 PSF Floor Dead Load 10 PSF Roof Live Load 40 PSF Roof Dead Load 10 PSF Comply with Wind Zone 3 Requirements of 24 CFR 3280 Wood Roof Diaphragm Wall Height: 7'-6"

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

14B1-1.3

DRAWING NO.

GENERAL NOTES

14' WIDE MHU

(PACKAGED SYSTEM)

3060-E-SG

SEAT

W/H

30603060

BA

TH

TPS

CLOSET

D R

YE

R

W

AS

H

ER

1 2

31 2

91 2

1 2

1 2

1 2

6" 20'-11"

2"

4'-9"

2" 8'-0"

2"

7'-31 2"

2"

5'-21 2"

2"

1'-101 2"

7'-91 2"

37'-01 2" 31'-43

4" 26'-83 4" 17'-61

4"

18'-83 4" 4'-03

4"

84.34 SF

42'-8"

16'-0"21'-01 2"

DESIGNATES A 2X4 WALL

SHEARWALLS - WIND ZONE 3

PLFLENGTHNO.

130"1

SIDEWALL HEIGHT = 90"

162" 341

TRUSS HEEL HEIGHT = 9-15/16"

LIGHT AND VENT SCHEDULE

REQUIRED VENTREQUIRED LIGHTROOM TITLE AREA

6.40 S.F.12.80 S.F.LIVING / DINING ROOM 160.00 S.F

3.36 S.F.6.72 S.F.BEDROOM #1 84.00 S.F.

'-6

6"

6"

18'-6"

SHEAR WALLS FOR WIND ZONE 3

(FIXED)

DINING & LIVING

ROOM

4 SHELVES

HVAC

PACKAGED

SYSTEM

LIVINGDINING

R

EF

ER

PANTRY

KITCHEN

36'-31 4"

BEDROOM #1160.00 SF

OPTIONAL DEHUMIDIFIER -

SEE APPENDIX A, PAGE A-35.

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

14B1-2

DRAWING NO.

FLOOR PLAN

14' WIDE MHU

(PACKAGED SYSTEM)

REV 11-15-23

Floor Plan Notes:

1. All bedroom closet shelving shall be 12 inches deep.

W/H

30603060

BA

TH

TPS

CLOSET

D R

YE

R

W

AS

H

ER

D1

D1

D1

D2

D2 D3

D3

MARK

D1 D2 D3

WIDTH

3'-0" 3'-0" 2'-0"

HEIGHT

6'-8" 6'-8" 6'-8"

THICKNESS

1-3/8" 1-3/8" 1-3/8"

TYPE

Outswing Door Hallway Doors Closet & W/H Doors

DOOR SCHEDULE

MARK

W1 W2

WIDTH

2'-6" 2'-6"

HEIGHT

5'-0" 2'-3"

TYPE

Single Hung Window Fixed Pane Window

WINDOW SCHEDULE

W2 W1

W1 W1

TOTAL EXTERIOR DOOR AREA: 64.5 SQ. FT.

TOTAL WINDOW AREA: 44.2 SQ. FT.

(FIXED)

Door Notes

1. Exterior doors shall meet 24 CFR 3280.405 requirements and shall comply with Wind Zone 3 requirements.

2. All exterior doors shall be insulated fiberglass or steel with a maximum U-Value of 0.33.

3. All doors shall have lever type handles in compliance with UFAS 4.13.9.

4. For additional information on exterior and interior doors see FEMA Additional Requirements document and Appendix A.

5. Return air grills shall be installed above doors unless the grill will be blocked by the sprinkler system and then may be installed in the door or wall.

6. Door stops shall be installed at all interior and wardrobe doors. Door stops may be installed on the door or the floor baseboard. Door stop finish to match interior hardware finish.

7. All bathroom and bedroom doors shall have a privacy lock. The lock mechanism shall be the button type (UFAS 4.13.9) and located on the inside of the bathroom or bedroom.

8. The water heater compartment side of the water heater access door shall be covered with minimum 5/16 inch thick gypsum board.

9. The closet door shall be equipped with a passage latchset with level handle.

10. All interior doors shall have a maximum gap of 1" between the finished floor and the bottom of the door.

Window Notes

1. Windows shall meet 24 CFR 3280.403 and 3280.404 requirements and shall comply with Wind Zone 3 requirements.

2. Windows shall be double paned, low E with vinyl frame. Windows shall have a maximum SHGC of 0.30 and a maximum U-Value of 0.36.

3. Windows shall have a design pressure rating of 58.

4. Windows shall have screens.

DINING & LIVING

ROOM

4 SHELVES

HVAC

PACKAGED

SYSTEM

LIVINGDINING

R

EF

ER

PANTRY

KITCHEN

BEDROOM #1

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

14B1-3

DRAWING NO.

DOOR AND WINDOW SCHEDULE

14' WIDE MHU

(PACKAGED SYSTEM)

REV 11-29-21. Feb 03, 2025

'-6

SEAT

W/H

D R

YE

R

W

AS

H

ER

42'-8"

(FIXED)

4 SHELVES

HVAC

PACKAGED

SYSTEM

BA

TH

TPS

CLOSET

KITCHEN

C O

FF

EE

T

AB

LE

TABLE

END-

DINING & LIVING

ROOM

1' -0

NIGHT-

STAND

D R

ES

SE

R

BEDROOM #1

ITEM

SOFA

ARM-CHAIR

COFFEE TABLE

SPECIFICATIONS

80" W x 38" D 36" W x 32" D 30" W x 18" D

LIVING ROOM

END TABLE 20" W x 20" D

ITEM

DINING TABLE

DINING CHAIR

PANTRY

SPECIFICATIONS

72" L x 36" W

6 IDENTICAL CHAIRS

36" W x 12" D

DINING ROOM

ITEM

FULL BED

BUNK BED

DRESSER (4 OR 5 DRAWER)

SPECIFICATIONS

75" L x 54" W 80" L x 39" W

BEDROOMS

NIGHTSTAND 25" W x 25" D

ITEM

MEDICINE CABINET

BATH TUB

WC

SPECIFICATIONS

15" W x 25" H X 3" D 30" W x 60" L, FIBERGLASS

SEE FEMA SPEC

BATHROOM

WATER HEATER 40 GALLONS

ITEM

REFRIGERATOR

RANGE

MICROWAVE

SPECIFICATIONS

30" W x 32.5" D, 18 CU. FT.

30" W, 4 BURNERS

19" D MIN., 1.2 CU. FT.

KITCHEN

DEHUMIDIFIER PER FEMA

32"W x19"Dx48.75"H

R

EF

ER

PANTRY

SEE NOTE 24

TITLE:

1/8" = 1'-0"

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

14B1-4.1

DRAWING NO.

FURNITURE PLAN

14' WIDE MHU

(PACKAGED SYSTEM)

Furniture and Appliance Notes

1. All refrigerators shall be ENERGY STAR qualified and have the ENERGY STAR label affixed to the appliance when delivered with the MHU.

2. Range and oven controls shall be at the front of the appliance.

3. The range hood shall extend the width of the range and a minimum of 3" beyond the front face of the overhead cabinet.

4. The range hood vent opening at the cap shall be screened with a corrosion-resistant, non-combustible wire mesh with 1/4" openings or equivalent.

5. A shower rod and new, neutral-colored plastic shower curtain (71" L x 71" H) with full set of rings/hooks shall be provided for all shower/bath fixtures.

6. Two (2) metal, rust-resistant, wall-mounted towel bars with chrome finish shall be installed in each bathroom.

7. Metal, rust-resistant, toilet-paper holder with chrome finish shall be installed in each bathroom.

8. Mattresses shall be innerspring, non-latex (can be polyester, cotton, or blend ticking and wadding) new mattresses with medium firmness and 9" to 11" height.

9. The range hood vent shall be vented through the exterior wall.

10. All kitchen appliances (range, refrigerator, microwave and range hood) are to be the same color in the same MHU. Manufacturer may choose color.

11. Alternate refrigerator style may be side-by-side, 18 cubic foot, frost-free, ENERGY STAR compliant, that complies with UFAS requirements.

12. Bed frames shall be readily available commercial frames.

13. Furniture shall be free from sharp, abrasive surfaces, edges and durable for up to five (5) years in storage and/or eighteen months during occupancy.

14. Furniture shall not infringe into the UFAS egress path or wheelchair turning area.

15. Furniture dimensions cannot exceed the maximum sizes shown.

16. All nightstands and dressers must be the same style and color in each MHU.

17. Dining table and chairs must be the same style and color in each MHU.

18. The combined length of the sofa and end table shall not exceed 102".

19. 4 and 5 drawer dressers cannot be intermixed in the same mhu.

20. Dresser style and color cannot be intermixed in the same mhu.

21. Living Room coffee table and end table must be the same style and color in each MHU.

22. Living Room sofa and armchair must be the same style and color in each MHU.

23. Bunk bed frames shall be sized to accommodate twin XL mattress.

24. Closet shelves shall be 16" deep and may be wood or Closetmaid white storage shelves and supports or equivalent. REV 11-15-23 . Feb 03, 2025

SEAT

W/H

D R

YE

R

W

AS

H

ER

42'-8"

(FIXED)

4 SHELVES

HVAC

PACKAGED

SYSTEM

BA

TH

TPS

CLOSET

KITCHEN

C O

FF

EE

T

AB

LE

TABLE

END-

DINING & LIVING

ROOM

NIGHT-

STAND

D R

ES

SE

R

BEDROOM #1

R

EF

ER

PANTRY

TITLE:

1/8" = 1'-0"

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

14B1-4.2

DRAWING NO.

INSTALLED FURNITURE LAYOUT

14' WIDE MHU

(PACKAGED SYSTEM)

General Notes

1. Vendor to tape a copy of this drawing to the inside of the water heater compartment door.

REV 11-15-23. Feb 03, 2025

W/H

30603060

D R

YE

R

W

AS

H

ER

10 9

5 6 7

UFAS MANEUVERING CLEARANCES AT DOORS AND TURNING SPACE CONFIGURATION LAYOUT

(FIXED)

4 SHELVES

HVAC

PACKAGED

SYSTEM

BA

TH

TPS

CLOSET

KITCHEN

C O

FF

EE

T

AB

LE

TABLE

END-

DINING & LIVING

ROOM

NIGHT-

STAND

D R

ES

SE

R

BEDROOM #1

R

EF

ER

PANTRY

3060-E-SG

SEAT

W/H

30603060

D R

YE

R

W

AS

H

ER

36" PATH

36" PATH

36" PATH

UFAS CLEAR FLOOR SPACE LAYOUT

(FIXED)

SEE NOTE 4

4 SHELVES

SEE NOTE 4

HVAC

PACKAGED

SYSTEM

BA

TH

TPS

CLOSET

KITCHEN

C O

FF

EE

T

AB

LE

TABLE

END-

DINING & LIVING

ROOM

NIGHT-

STAND

D R

ES

SE

R

BEDROOM #1

R

EF

ER

PANTRY

TITLE:

1/8" = 1'-0"

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

14B1-5

DRAWING NO.

UFAS LAYOUT

Location UFAS Section and/or Figure References Exterior Doors

1. Front Door - Hall to Front Door 4.13.6 - Figure c - Push side

2. Front Door - Living Room to Front Door 4.13.6 - Figure b - Push side

4. Rear Door - Kitchen to Rear Door 4.13.6 - Figure c - Push side

Bedroom 1

5. Hallway to Bedroom 1 4.13.6 - Figure a - Push side - See Note 1.

6. Bedroom 1 to Hallway 4.13.6 - Figure a - Pull side

7. Bedroom 1 to Closet 4.13.6 - Figure a - Pull side

8. Turning Space Configuration 4.2.3 - Figure a - 60” Diameter Space

Bath 1

9. Bedroom/Hallway to Bath 1 4.13.6 - Figure c - Push side

10. Kitchen/Hallway to Bath 1 4.13.6 - Figure b - Push side

11. Bath 1 to Hallway 4.13.6 - Figure a - Pull side

12. Turning Space Configuration 4.2.3 - Figure a - 60” Diameter Space

13. Lavatory Clear Floor Space 4.19.3 - 30” x 48”

14. Tub/Shower Clear Floor Space 4.20.2 - Figure 33(a) - 30” x 60”

15. Toilet Clear Floor Space 4.16.2 - Figure 28 - 56” x 60”

Living Room

16. Turning Space Configuration 4.2.3 - Figure b - T-Shaped Space

Location UFAS Section and/or Figure References Kitchen

17. Turning Space Configuration 4.2.3 - Figure a - 60” Diameter Space

18. Range Clear Floor Space 4.34.6.2 - 30” x 48”

19. Sink Clear Floor Space 4.34.6.5(7) - 30” x 48”

20. Counter Work Surface Clear Floor Space 4.34.6.2 - 30” x 48”

21. Refrigerator Clear Floor Space 4.34.6.2 - 30” x 48”

UFAS Maneuvering Clearances at Doors and Egress Chart

14' WIDE MHU

(PACKAGED SYSTEM)

Notes

1. Door does not have closer.

2. The minimum clear width for a single wheelchair continuous path is 36” (UFAS 4.2.1).

3. All appliances shall be UFAS Compliant.

4. 50% of shelf space shall be below 54" reach range (UFAS 4.25.3)

5. Location of tub/shower seat shall be within UFAS forward reach range of tub/shower controls (UFAS 4.20.3 and Fig. 5(a)).)

REV 11-15-23

W/H

D R

YE

R

W

AS

H

ER

SS

S3 S3GFCI-WP

NOAA

S3

TV

WP-16

SS

19-GFCI

SA

7-GFCI

SSS

Back box for exterior alarm.

GFCI

GFCI

GFCI

GFCI

GFCI

GFCI

RH-16

SS

WP-16

FE

T

GFCI-WP

GFCI

TV17

S

(FIXED)

4 SHELVES

HVAC

PACKAGED

SYSTEM

Single outlet recept for refrigerator

16 44" AFF

S 3

18" AFF TO

RECEPTACLE SCREW

S

R

EF

ER

PANTRY

SEE NOTE 24

SA 15

S

See Appendix A, A-51, Elevation 2 for exact location of light, light switch and receptacles.

TPS Annunciator Panel

S 19 GFCI-WP

H.T. UNDER FLOOR

GFCI-WP

TITLE:

1/8" = 1'-0"

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

Cir. Purpose Type Wire Size Amps Pole

Bedroom 1 14-2 15 1 2 N/A - - 3 N/A - - 4 Kitchen 20 1 5 Kitchen 1 6 Ext. Recep 1 7 Washer 1 8 Dryer 30 2 9 Electric Range

10 Water Heater 11 Package System 12 Smoke Detectors 15 1 13 Reserved

GFCI

12-2

10-3 Per MFR. Specs.

14-3

20GFCI 12-2

20GFCI 12-2

20GFCI 12-2

Per MFR. Specs.

Per MFR. Specs.

14 Living Room 15 114-2 15 TPS System 16 Lights/Recep 15 114-2 17 Dining Room 20 112-2 18 Refrigerator 20 112-2

Per MFR. Specs.

Per MFR. Specs.

19 Bath Receps / Heat Tape 20 112-2

GFCI

GFCI

14B1-6

DRAWING NO.

ELECTRICAL PLAN

14' WIDE MHU

(PACKAGED SYSTEM)

Electrical And Lighting Notes

1. The highest breaker in the panel box should be 48" maximum. Panel box bottom must be at least 24" from the floor.

2. The light bulbs shall be LED, equivalent to 60-watt incandescent bulbs, minimum 800 lumens, white in color, between 2,700 K and 4,100 K.

3. No glass shall be used in any of the lighting globes.

4. The exterior lights shall be stored in the refrigerator during transport.

5. Interconnected smoke alarms shall utilize the home's primary power source and shall have battery backup.

6. The center line of the switches and the top of the thermostat must be installed at no more than 48” above the finished floor.

7. Electrical outlets must be no lower than 18" above the floor to the center of the receptacle screw.

8. The junction box for the telephone and cable shall be located within 4' of the road side rear of the MHU.

9. Electric wiring may be done either through the floor or the ceiling.

10. Listed service entrance conduit, sized per 2005 NEC, shall be run from the main distribution panel straight down and extend below the bottom board no more than 3 inches with a listed threaded fitting. End of conduit shall be capped.

11. Thermostat wire shall be run with the condenser line set and shall be supported at 48" O.C. with zip ties. Installation shall conform to low voltage wire requirements per 2005 NEC.

12. For additional information on optional dehumidifier wiring requirements see Appendix A, page A-35.

13. Circuit breaker, wire and junction box shall be installed at the plant. Junction box shall be located below wall framing for dehumidifier and cover plate facing into the Living Room, wire nut end of dehumidifier wire in junction box.

14. Bathroom exhaust fan with light to be 75 cfm with an integrated timer. Bath exhaust fan(s) after being turned on, shall run for a minimum of 60 minutes, even if the fan switch is turned off. Any over-ride to the minimum 60-minute requirement is not acceptable. Label with note shall be placed above bath fan switch stating, FAN ON TIMER AND SHUTS OFF AFTER 60 MINUTES.

15. Kitchen range hood exhaust fan with a white light shall be a minimum 100 cfm exhaust fan, with separate switches.

16. Bathroom and kitchen exhaust fans shall vent directly to the outside.

17. Ceiling lights shall have 2 LED bulbs.

18. The bathroom vanity light shall be wall mounted with 3 LED bulbs.

19. The circuit breaker(s) providing power to the TPS unit shall be equipped with a UL-listed locking device that can secure the breaker(s) in the ON position. Devices shall be installed set to the ON position.

20. Kitchen countertop receptacles and switches must be furred out to be 24" (max) from front edge of countertop, and no more than 44" to the top of the switches or receptacles above finished floor.

21. See TPS closet and TPS closet elevations for electrical locations in Appendix A.

22. Heat tape recept located within 24" of water inlet.

23. Smoke alarms shall not be located within 3 feet horizontally from any ceiling discharge grille.

24. HVAC electrical connection shall be routed through the back of the unit using the knockouts provided by the manufacturer. Running the electrical connection in conduit exposed to the exterior is not acceptable.

Electrical wiring shall not be installed within the plenum used for environmental air (wall mounted curb).

S

WP

Sym. Description

110 volt duplex recep-wall mounted 110 volt duplex-GFCI protected recept

220 volt recept-wall mounted Light Fixture - Ceiling Mounted Light Fixture - Wall mounted Exhaust fan - Light Combo Distribution panel board - 200 amp Exterior light fixture - weather proof

TV

FE

S

S3

NOAA

T

Smoke Alarm w/ Strobe Light - wired in series Telephone Recept TV Outlet Fire Extinguisher Switch Switch - Three Way Outlet for NOAA Weather radio Thermostat

SA

Sym. Description Service Entrance Conduit through bottom board from Main Distribution Panel Board

Optional Dehumidifier (Direct Wired)

20 Optional Dehumidifier 15 114-2GFCI

REV 02-03-25

Legend

CUT OFF VALVE LOCATION

3/4" LINE (HOT)

1/2" LINE (HOT)

3/4" LINE (COLD)

1/2" LINE (COLD)

ADJACENT PIPE SIZES.

FITTING SIZES TO CORRESPOND TO

ALL SIZING OF PIPE + OR -, MUST

MEET OR EXCEED ANY APPLICABLE

2)

CODES.

1)

Notes

W/H Washer

K.Sink

Inlet

Master Shutoff

Stool

Tub

Hose Bib

Lav

LOW POINT DRAIN IN WATER LINES

WITH SHUT-OFF VALVES

W/H

COLD

HOT

INLET

TYPICAL BYPASS VALVE.

SEE NOTE BELOW.

WATER LINES

WATER HEATER BYPASS

VALVE DETAIL

SEE NOTE 13

TITLE:

NTS

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

14B1-7

DRAWING NO.

WATER LINES

14' WIDE MHU

(PACKAGED SYSTEM)

Water Supply System Notes

1. The water supply lines shall be Cross-linked polyethylene (PEX) or chlorinated polyvinyl chlorine (CPVC) and comply with the requirements of 24 CFR 3280.

2. All water lines shall be 1/2” unless noted.

3. The water supply inlet shall be 3/4” and have a brass quarter turn ball valve.

4. The water supply inlet shall extend not more than 6” below the bottom board.

5. The water supply inlet shall be located within 12” of the curb side of the home.

6. The water supply inlet shall not be located under an exterior door.

7. Individual shut off valves shall be located on each water line at each fixture, except at the tub/shower or shower.

8. All water line floor penetrations shall be caulked or foamed. Caulk or foam shall be acceptable to be in contact with the water line material.

9. Access panels (minimum size 14" x 14") shall be located in the walls at all points where concealed plumbing slip joints exist. The access panels shall match the wall color and finish.

Access panels shall be unobstructed and accessible for inspection and repair.

10. The MHU shall be equipped with a frost-free hose bib located near the main water supply inlet. It shall not be located under an exterior door.

11. Low point drain in water lines with shut-off valves shall be located above bottom board and insulation. Vendor to provide access panel, labeled "Low Point Drain".

12. By-pass valves shall be quarter turn on-off valves.

13. Water heater pressure relief valve drain line shall be run to the exterior of the home. REV 02-03-25

To Sewer

A

MF

K.SinkK

A

B C Stool

D

H B

H M F

Lav

A

K

SEE NOTES 5 THRU 7

I L

SANITARY TEE

LONG TURN TY

CLEAN OUT PLUG

CAP & CHAIN

22.5° ELL

45° ELL

REDUCER BUSHING

90° CLOSET ST. ELL

DWV FITTING LEGEND

MECHANICAL VENT

90° LONG TURN ELL

DOUBLE SANITARY TEE

90° LONG TURN ST. ELL

LK

P-TRAP

COUPLING

NM

T R

S Q O P

45° Y

DOUBLE ELL

F

JI

H

B D

E G

A C

NOTES

1. FITTING SIZES CORRESPOND TO ADJACENT PIPE SIZES.

2. SINGLE (THIN) LINES REPRESENT 1-1/2" PIPE;

DARK (THICK) LINES REPRESENT 2" PIPE;

DOUBLE LINES REPRESENT 3" PIPE.

3. P-TRAP DIRECTIONS MAY VARY.

90 1/2"71 1/2"

SEE NOTE 8

A

F M

(Stool Vent)

B (optional)

Tub w/ Overflow

H

WasherK

A

DEHUMIDIFIER DRAIN IS STANDARD. SEE APPENDIX

A, PAGE A-35 FOR ADDITIONAL INFORMATION.

H

A

MF

K

M F

Dehumidifier

TITLE:

NTS

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

14B1-8

DRAWING NO.

DRAIN LINES

14' WIDE MHU

(PACKAGED SYSTEM)

Drain System General Notes

1. Drain lines shall be ABS or PVC and comply with the requirements of 24 CFR 3280.

2. All drain lines shall be 1 ½” diameter unless noted.

3. The drain line system shall be accessible without removing the axles and wheels.

4. All drain line floor penetrations, except at tub/shower and shower floor penetrations shall be caulked or foamed. Caulk or foam shall be acceptable to be in contact with the drain line material.

5. The drain line shall run below the floor and above the bottom board. The drain outlet shall be located a minimum of 2 feet and a maximum of 4 feet ahead of the front axle. The edge of the drain outlet shall be located a minimum of 4 inches from the closest edge of any crossmember.

6. The drain line outlet shall protrude at least six inches (6”), but not more than eight inches (8”), below the bottom board.

7. The drain line outlet shall be capped with a removable plastic cap and chain or strap.

8. Stool trap arm developed length shall not be over 72". REV 02-03-25 . Feb 03, 2025

W/H

30603060

D R

YE

R

W

AS

H

ER

SA

TPS

CLOSET

14x8 ID

180 CFM

8" FLEX

60 CFM

6" FLEX

100 CFM

8" FLEX

100 CFM

8" FLEX

100 CFM

8" FLEX

8x8 ID

BATH #1

BEDROOM #1

TPS

CLOSET

KITCHEN

LIVING & DINING

ROOM

2'-0"11'-7"26'-0"37'-0"

33'-11"

1 2

1 2

1 2

1 2

1 2

(FIXED)

4 SHELVES

HVAC

PACKAGED

SYSTEM

4" FLEX

60 CFM

1 2

17'-11"

R

EF

ER

PANTRY

14x30 GRILL

14x30 GRILL W/ FILTER 6'-0"23'-4"

TRANSITION DUCT

14 1/2"x30 1/2"x15" PLENUM

14 1/2"x30 1/2"x15" PLENUM

(1) 16" JUMPER DUCT OR

(2) 12" JUMPER DUCTS

SEE NOTE 15

SA

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

14B1-9

DRAWING NO.

OVERHEAD DUCT LAYOUT

HVAC DESIGN AND 14' WIDE MHU

(PACKAGED SYSTEM)

HVAC Wall Mounted Package Unit Notes

1. The MHU shall be equipped with a specifically engineered HVAC wall mounted package system based on the size and intended use of the MHU, in accordance with 24 CFR 3280.506, that is compatible with the HVAC wall mounted package system size and capable of maintaining an average temperature of seventy degrees Fahrenheit (70°F) in the MHU.

2. The HVAC wall mounted package system shall not cause vibration within the MHU. The HVAC wall mounted package system shall be mounted in such a way as to dampen the vibrations and any sound that accompany the packaged during operation cycles.

3. The HVAC wall mounted package system shall be able to maintain the temperature based on the coldest average temperature of the operating area of the MHU.

4. The HVAC wall mounted package system will require the manufacturer to have a current Alternative Construction letter from HUD.

5. The HVAC wall mounted package system shall be installed with a curb unit to minimize vibration and sound transmitted to the MHU.

6. A motorized room ventilator shall be installed in the HVAC wall mounted package system.

7. The thermostat shall be designed to work with the HVAC wall mounted package system.

8. The ceiling return air grill located in the bedroom shall accommodate a filter.

9. Duct penetrations thru ceiling board shall be sealed.

HVAC General Notes

1. See FEMA specifications for programable and configurable thermostat requirements.

2. Duct system shall be constructed of class 0 or class 1 circular insulated flex ductwork or equal. All ducts to be insulated with a minimum of R-4 insulation.

3. Metal supply registers shall be 8” x 8” TRUaire A500 series square extruded aluminum ceiling supply register (4-way distribution) with damper OR equivalent.

4. All supply ducts shall be in the roof attic space.

5. All supply duct seams and fasteners shall be sealed with UL-181A or UL-181B listed duct tape.

6. The manufacturer shall provide a duct pressure test report (See FEMA Spec for testing procedure) for each MHU duct system showing duct leakage of 5 percent or less prior to FEMA acceptance of the

MHU.

7. No construction debris or sawdust shall be left in the duct system.

8. The main supply and return duct trunks shall be galvanized sheet metal (min. thickness per HUD IB H-1-84) or Johns Manville Mat-face Micro-aire (Type 475 or 800) fiberglass ductboard or equivalent.

Duct to be installed per manufacturer's installation instructions.

9. N/A

10. N/A

11. N/A

12. A 12” x 6” return air register shall be located 8” above the floor in the TPS Compartment/ bathroom wall. A register shall be placed on each side of the wall.

13. The manufactured home manufacturer is responsible to assure the wall mounted HVAC unit provided has the following features:

a. Unit is designed to have a ceiling return air system as shown in drawing above. A return air system through the room the unit is in, is not acceptable.

b. Unit is designed so that when unit is operating, and any dampers are open that no direct openings from the outside to the inside of the MHU occur. Standing in the room and being able to see outside through any unit openings is not acceptable.

c. Unit is designed with an anti-vibration curb between the MHU and the wall mounted HVAC unit.

14. Bathroom exhaust fan location shall not be located next to the bathroom supply register.

15. One (1) 16" dia. jumper duct with transition fitting (201 square inches min.) each end or two (2) 12" dia. jumper ducts.

Heating / Cooling

HVAC WALL MOUNTED PACKAGED SYSTEM SPECIFICATIONS

1.5 Ton Package System

Floors 0.0356

Air ducts in ceiling 0.0868

Ceilings and roofs of light color 0.0257

Walls (without windows and doors) 0.0575

U Values Heating

Duct Capacity

Air ducts in ceiling (Duct Area) 270 Sq. Ft.

37,605 Btuh

0.0362

0.0896

0.0258

0.0555

Cooling

REV 11-15-23. Feb 03, 2025

" M

AX

T O

T O

P O

F R

ID

G

E

VE

N T

14'-0" EAVE TO EAVE

13'-6"

'-6

" M

AX

T O

T H

E

TO

P O

F R

ID

G

E

VE

N T

14'-0" EAVE TO EAVE

13'-6"

HITCH END ELEVATION TAIL END ELEVATION

3"3"3"3"

HUD LABEL: APPROX. 12" UP

FROM FLOOR AND 12" FROM

ROADSIDE.

EXTERIOR RECEPTACLE (GFCI)

EXTERIOR RECEPTACLE (GFCI)

FRONT DOOR

BACK DOOR

PEEP HOLES

PEEP HOLES

ANGLE RAIN DIVERTER OVER DOOR

EXTERIOR LIGHT

EXTERIOR ALARM

DEVICE BOX w/

COVER PLATE

RIDGE VENT (TYP.)

INTERIOR FLOOR LINE

INTERIOR FLOOR LINE

FRONT DOOR SIDE ELEVATION

BACK DOOR SIDE ELEVATION

RIDGE VENT (TYP.)

RANGE VENT

EXTERIOR RECEPTACLE (GCFI)

(6" ABOVE FINISHED FLOOR)

EXTERIOR LIGHT

PROTECTIVE COVER

PER FEMA SPEC

TRANSPONDER

ANGLE RAIN DIVERTER

OVER DOOR

ANGLE RAIN DIVERTER OVER DOOR

TPS DOOR

DRYER VENT

HOSE BIBB

SPRINKLER DRAIN TPS CLOSET

FLOOR DRAIN

SERVICE ENTRANCE CONDUIT

TITLE:

Scale: 1/8" = 1'-0"

Date: 6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency 14B1-10

DRAWING NO.

ELEVATIONS

14' WIDE MHU

(PACKAGED SYSTEM)

Exterior Finishes Notes

1. Siding shall be light gray vinyl.

2. Siding shall be double 4" lap.

3. Siding shall be approved for HUD Wind Zone 3 requirements.

4. The manufacturer shall provide a transponder sled. See Appendix A.

5. The sled shall be painted with a powder coat paint to match the exterior color of the MHU or White.

6. The transponder sled shall be made out of sheet metal.

7. Vinyl siding, Versatek trim board, or equivalent shall be installed below all exterior doors, cover 2X8 perimeter rails, light gray in color and installed per Wind Zone 3 requirements. REV 11-15-23 . Feb 03, 2025

28'-0"

48 48

4'-0"8'-0"42'-8"

42'-8"

48 4848 20'-0"

16'-0" 12'-0"

38'-8"

1 4

1 4

1 2

- S

ID

E A

42'-8"

FRAME CLIPS IN AXLE AREA ARE LOCATED ON INSIDE OF SISTER BEAM AS SHOWN.

1'-4" 2'-8"

5'-4" 6'-8"

9'-7" (MOVED JOIST)

10'-8"

13'-4"

14'-5" (MOVED JOIST)

21'-51 2"25'-4"29'-4"

22'-8"30'-8"

33'-4"

40'-0"

LONGITUDINAL

BRACKET

LONGITUDINAL

BRACKET

27131

FRONT AND REAR HEADER SHEARWALL LAG BOLT SPACING

A-FRAME

RE-INFORCEMENT

CENTERED AND

UNDER FRONT

HEADER

DETAIL "B"

DETAIL "C", SEE CHASSIS DETAILS

SEE CHASSIS DETAILS, DETAIL "A"

3'-6"

12" X 10.8# I-BEAM HEADER

12" X 10.8# I-BEAM HEADER

96 LONGITUDINAL BRACKET

LONGITUDINAL

BRACKET

32'-0"

36'-0" 37'-4"41'-4"

24'-0"

26'-8"

- SPRING HANGER

- SISTER BEAM

Drawing Notes

FRAME CLIP DETAIL

(SAME ON BOTH MAIN I-BEAMS)

**DIMS ARE PULLED FROM END OF HEADER BEAM.

**BE SURE TO VERIFY FLOOR JOIST LAYOUT TO MATCH CLIPS TO JOISTS.

14'-8" 28'-0" (65.6% OF FRAME LENGTH)

17'-51 4"

17'-23 4"

227 27 27 27

34'-8"

21'-4"

25'-23 4"

13'-4" INSTALL TIRE BLOW-OUT PROTECTION

IN THIS AREA (BOTH SIDES)

28'-0"30'-91 4"

21'-4" START SISTER BEAM AND BLOW-OUT PROTECTION

MIN. 13'-4" LENGTH OF SISTER BEAM (TYP.)

34'-8"

19'-01 4"

18'-93 4"

OUTRIGGER LOCATION DIMENSIONS

ARE TO THE CENTERLINE OF THE

TOP FLANGE HOLE (TYP).

LONGITUDINAL BRACKETS

LOCATED PER NOTE 12.

TITLE:

Scale: 1/8" = 1'-0"

Date: 6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency 14B1-11.1

DRAWING NO.

CHASSIS

14' WIDE MHU

(PACKAGED SYSTEM)

Chassis Frame Notes

1. All metal-to-metal contact with 1/8” fillet weld minimum.

2. Floor shall be lagged to frame with frame clip, Fastec 9mm x 76mm listed lags or lags equivalent in size and strength at each joist and outrigger tip.

Alternate lags must be reviewed and approved by FEMA or their designee.

3. Clips shall be welded to the I-beam.

4. All parts of the chassis including added/welded parts shall be completely coated with waterproof paint.

5. Tires shall be new, 14.5” rim diameter, 14 ply with “G” load range.

6. Wheels and tires shall meet or exceed the axle rating and be rated for continuous speeds of 65 mph or greater.

7. All axles shall be new.

8. All axles shall be brake axles.

9. A valve stem cover shall be present on every tire.

10. The serial number shall be permanently stamped to the front header to comply with 3280.6. In addition, the serial number shall be painted with rust resistance contrasting color paint, 2 inches (2”) tall on the front header.

11. Rims, bolts, nuts, or other related tire-mounting hardware shall be new.

12. Longitudinal brackets shall be installed at 8'-0” and 16'-0" maximum from each end of the home.

13. Springs shall be 24 3/4" long multi-leaf.

14. All rims shall be the same color.

15. Maximum typical pier spacing along main I-beams @ 8'-0” o.c. Typical pier load = 6,400 lbs.

16. Manufacturer to place permanent indicators (paint or label) on each I-Beam @ 2'-0" from each end, 12'-0" on center max, and at door jambs for location temporary piers for storage.

17. Longitudinal bracket slot to face towards closest end of home.

18. Structural steel shall be A36 AND Fy: 36Ksi.

19. Longitudinal brackets located in the axle area must be located on the inside I-beam of the double I-beam.

Frame Specs

· Main I-Beam: 12" x 10.8# or equivalent with transportation test.

· Front and Rear Headers: 12" x 10.8# or equivalent with transportation test.

· Crossmember: 13 Ga. C or Z, 1-1/2" x 3" x 1-1/2"x13 Ga.

· Outriggers: 9" Min Depth at I-Beam tapered to 1" , 13 Ga min., C or Z type, with 1-1/2" flange top and bottom.

· Frame Clips: 1" x 1-1/2" x 12 Ga.

Hitch Specs

· See Chassis Details, Details "A"

Welding Specs

1. All welds to be a minimum 1/8" unless otherwise noted. Weld beads can be concave in application as long as the weld size is met.

2. Coupler and Jack shall be welded per manufacturer's installation instructions.

3. I-Beam splice plate shall be 4" wide x height of I-Beam minus 1-1/4" x 13 GA.

Splice plate can be offset +/- 1/4". Weld shall be full width of splice plate.

Splice plate only required on one side of I-Beam.

4. Sister I-Beam shall be welded with 1/8" butt welds 2" long at 24" o.c. top and bottom of I-beam

5. All weld lengths stated or shown are minimum lengths and shall have a tolerance of minus 1/4" (except spring hangers). Weld lengths that are not noted shall be full length.

REV 02-03-25

28'-0"

48 48

4'-0"8'-0"42'-8"

42'-8"

48 4848 20'-0"

16'-0" 12'-0"

38'-8"

1 4

1 4

1 2

- S

ID

E A

42'-8"

FRAME CLIPS IN AXLE AREA ARE LOCATED ON INSIDE OF SISTER BEAM AS SHOWN.

1'-4" 2'-8"

5'-4" 6'-8"

9'-7" (MOVED JOIST)

10'-8"

13'-4"

14'-5" (MOVED JOIST)

21'-51 2"25'-4"29'-4"

22'-8"30'-8"

33'-4"

40'-0"

LONGITUDINAL

BRACKET

LONGITUDINAL

BRACKET

27131

FRONT AND REAR HEADER SHEARWALL LAG BOLT SPACING

A-FRAME

RE-INFORCEMENT

CENTERED AND

UNDER FRONT

HEADER

DETAIL "B"

DETAIL "C", SEE CHASSIS DETAILS

SEE CHASSIS DETAILS, DETAIL "A"

3'-6"

12" X 10.8# I-BEAM HEADER

12" X 10.8# I-BEAM HEADER

96 LONGITUDINAL BRACKET

LONGITUDINAL

BRACKET

32'-0"

36'-0" 37'-4"41'-4"

24'-0"

26'-8"

- SPRING HANGER

- SISTER BEAM

Drawing Notes

FRAME CLIP DETAIL

(SAME ON BOTH MAIN I-BEAMS)

**DIMS ARE PULLED FROM END OF HEADER BEAM.

**BE SURE TO VERIFY FLOOR JOIST LAYOUT TO MATCH CLIPS TO JOISTS.

14'-8" 28'-0" (65.6% OF FRAME LENGTH)

17'-51 4"

17'-23 4"

227 27 27 27

21'-4"

25'-23 4"

13'-4" INSTALL TIRE BLOW-OUT PROTECTION

IN THIS AREA (BOTH SIDES)

28'-0"30'-91 4"

21'-4" START SISTER BEAM AND BLOW-OUT PROTECTION

34'-8"

19'-01 4"

18'-93 4"

OUTRIGGER LOCATION DIMENSIONS

ARE TO THE CENTERLINE OF THE

TOP FLANGE HOLE (TYP).

LONGITUDINAL BRACKETS

LOCATED PER NOTE 12.

TITLE:

Scale: 1/8" = 1'-0"

Date: 4/30/2021FEMA Manufactured Housing Units Federal Emergency Management Agency 14B1-11.1.1

DRAWING NO.14' WIDE MHU

(PACKAGED SYSTEM)

Chassis Frame Notes

1. All metal-to-metal contact with 1/8” fillet weld minimum.

2. Floor shall be lagged to frame with frame clip, Fastec 9mm x 76mm listed lags or lags equivalent in size and strength at each joist and outrigger tip.

Alternate lags must be reviewed and approved by FEMA or their designee.

3. Clips shall be welded to the I-beam.

4. All parts of the chassis including added/welded parts shall be completely coated with waterproof paint.

5. Tires shall be new, 14.5” rim diameter, 14 ply with “G” load range.

6. Wheels and tires shall meet or exceed the axle rating and be rated for continuous speeds of 65 mph or greater.

7. All axles shall be new.

8. All axles shall be brake axles.

9. A valve stem cover shall be present on every tire.

10. The serial number shall be permanently stamped to the front header to comply with 3280.6. In addition, the serial number shall be painted with rust resistance contrasting color paint, 2 inches (2”) tall on the front header.

11. Rims, bolts, nuts, or other related tire-mounting hardware shall be new.

12. Longitudinal brackets shall be installed at 8'-0” and 16'-0" maximum from each end of the home.

13. Springs shall be 24 3/4" long multi-leaf.

14. All rims shall be the same color.

15. Maximum typical pier spacing along main I-beams @ 8'-0” o.c. Typical pier load = 6,400 lbs.

16. Manufacturer to place permanent indicators (paint or label) on each I-Beam @ 2'-0" from each end, 12'-0" on center max, and at door jambs for location temporary piers for storage.

17. Longitudinal bracket slot to face towards closest end of home.

18. Structural steel shall be A36 AND Fy: 36Ksi.

19. Longitudinal brackets located in the axle area must be located on the inside I-beam of the double I-beam.

ALT. CHASSIS

(95.5" I-BEAM SPACING)

Frame Specs

· Main I-Beam: 12" x 10.8# or equivalent with transportation test.

· Front and Rear Headers: 12" x 10.8# or equivalent with transportation test.

· Crossmember: 13 Ga. C or Z, 1-1/2" x 3" x 1-1/2"x13 Ga.

· Outriggers: 9" Min Depth at I-Beam tapered to 1" , 13 Ga min., C or Z type, with 1-1/2" flange top and bottom.

· Frame Clips: 1" x 1-1/2" x 12 Ga.

Hitch Specs

· See Chassis Details, Details "A"

Welding Specs

1. All welds to be a minimum 1/8" unless otherwise noted. Weld beads can be concave in application as long as the weld size is met.

2. Coupler and Jack shall be welded per manufacturer's installation instructions.

3. I-Beam splice plate shall be 4" wide x height of I-Beam minus 1-1/4" x 13 GA.

Splice plate can be offset +/- 1/4". Weld shall be full width of splice plate.

Splice plate only required on one side of I-Beam.

4. Sister I-Beam shall be welded with 1/8" butt welds 2" long at 24" o.c. top and bottom of I-beam

5. All weld lengths stated or shown are minimum lengths and shall have a tolerance of minus 1/4" (except spring hangers). Weld lengths that are not noted shall be full length.

REV 02-03-25

I-BEAM 12" X 10.8#

DRAWBAR CROSSMEMBER I-BEAM 12" X 10.8# REINFORCEMENT

UNDER FRONT HEADER AND CENTERED BETWEEN FRONT HEADER AND TONGUE

VENTURE 2-5/16" - 60 DEGREE, 10,000LB COUPLER OR EQUIVALENT

JACK - VENTURE TOP MOUNT,

10,000LB GALVANIZED OR EQUIVALENT.

7-3/8" X 4" NOSE PLATE

1" x 1-1/2" X 12GA FRAME CLIP 1/8" x 1-1/2" FILLET WELD TO TOP

FLANGE OF I-BEAM.

9" x 1.5" x 1.5" x 13 Ga

FULL LENGTH OUTRIGGER

1-1/2" x 1-1/2" x 13"L x 13 GA. ANGLE 8" x 1"L FILLET WELD TO I-BEAM

AND CROSSMEMBER

FRONT AND REAR I-BEAM HEADERS - 12" X 10.8#

CROSSMEMBER

C OR Z 1-1/2" x 3" x 1-1/2"

13 GA. @ 48" O.C.

HITCH SHALL BE PAINTED GREEN

1/

1 1/21 1/2

BOTTOM OF FRAME I-BEAM

1/8" X 2" LONG FILLET WELD

3/4 1 1/2 3/4

1/

1/

1/

DIA. 9/16" HOLE

DETAIL - SEE SLOT

A

A

1/

1 1/21 1/2

1 1/2 3/43/4

3/

DETAIL "A-A"

SLOT DETAIL

1 5/8

13/16

5/

DIA. 9/16" HOLE

DIA. 9/16" HOLE

DIA. 9/16" HOLE

FULL

1"MAX

1"MAX

NO

WELD

3" Notes

1. Thickness is 4 gauge.

2. Vendor to assure all spring hangers are 90° to I-Beam.

3. Shoulder bolts to be torqued per axle manufacturer requirements (Approximately 30 to 50 ft. lbs). Leaf Spring to move freely in hanger.

4. Welds are not continuous around corners.

1/4" FILLET WELD

EACH SIDE

4"

I-BEAM FLANGE

LOOKING UP AT SPRING HANGER

SPRING HANGER

SPRING

HANGER

LEAF

SPRING

EQUALIZER

AXLE

U-BOLTS

LEAF

SPRING

SHACKLE LINK

WITH BOLTS

CENTER SPRING

HANGER

FRAME I-BEAM

TITLE:

FEMA Manufactured Housing Units Federal Emergency Management Agency 1/8" = 1'-0"

6/28/2019

VERSION:DATE:

SCALE:

COMPANY:

14B1-11.2

DRAWING NO.

CHASSIS DETAILS

14' WIDE MHU

(PACKAGED SYSTEM)

DETAIL C: LONGITUDINAL TIE-DOWN BRACKETDETAIL B: AXLE HANGER

DETAIL A: HITCH ASSEMBLY DETAIL D: EQUALIZER & SHACKLE LINK FASTENING

Notes

1. Shoulder bolts are to be used at all equalizer and shackle link locations.

2. Shoulder bolts shall be torqued per axle manufacturer requirements.

(Approximately 30 to 50 ft. lbs.)

3. Equalizer and shackle links are to move freely after shoulder bolts have been torqued.

4. Axle U-bolts shall be torqued per axle manufacturer requirements

(Approximately 70 to 95 ft. lbs.)

LONGITUDINAL TIE-DOWN BRACKET (12Ga. MIN.) SHALL HAVE

3150 LB WORKING LOAD CAPACITY.

REV 11-29-21

42'-8"

(2 ) S

H

EA

R W

AL

L

JO

IS

TS

(2 ) S

H

EA

R W

AL

L

JO

IS

TS

'-8

'-4

'-0

'-8

'-4

'-0

'-8

'-4

'-0

'-8

'-4

'-0

'-8

'-4

'-0

'-8

'-4

(D O

U

BL

E

JO

IS

T)

0'

-0

(D O

U

BL

E

JO

IS

T)

8'

-1 1"

(D O

U

BL

E

JO

IS

T)

'-4

'-0

(M O

VE

D

J O

IS

T)

4'

-5

'-4

'-0

'-8

(M O

VE

D

J O

IS

T)

'-7

8' -0

6' -8

5' -4

4' -0

2' -8

1' -4

REQUIRED BLOCK(S) WHEN FLOOR JOIST IN AXLE AREA DOES

NOT ALIGN WITH OUTRIGGERS. SEE FLOOR FRAMING NOTE 4.

20'-9" TPS CLOSET FLOOR DRAIN

16'-7" SPRINKLER DRAIN

18'-3" DRYER VENT

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

14B1-12

DRAWING NO.

FLOOR FRAMING LAYOUT

14' WIDE MHU

(PACKAGED SYSTEM)

Floor joists to rim joist

Multiple joists (to each other)

7/16 x 2-1/2 x 15Ga staple OR 0.131 x 3" Nail 7/16 x 2-1/2 x 15Ga staple OR 0.131 x 3" Nail

7 each 5 each 12" o.c.

12" o.c.

DESCRIPTION FASTENER QTY

FASTENING SCHEDULE - FLOOR FRAMING

(80% PVA glue coverage) Floor Framing Notes

1. The floor joists shall be 2 x 8 #2 SPF 16” o.c.

2. Edge rails shall be 2 x 8 #2 SPF.

3. Edge rail splice 4 x 5 x 20 GA metal connector plate on each side, or 2 x 8 x minimum 6" each side of joint centered +/- 1”, to be fastened with 7/16 x 2 ½ x 15 GA staples or .131 x 3”

PD nails (8) each side of edge rail, with minimum 80% PVA coverage.

4. In the axle area floor joists that do not align with chassis outriggers add a 2x8x16" min. #2 SPF block to the side of the floor joist to meet lagging requirements. Fasten block to side of joist with 80% PVA glue and (4) .131 x 3” PD nails or (6) - 7/16 x 2 ½ x 15 GA staples staggered. if floor joist is offset from outrigger more than 1 3 4" a second block must be fastened to the side of first block. Second block, if required, same grade, specie and fastening.

5. TPS and Sprinkler drain lines to be installed through the perimeter rail. Hole size is a max. of 1 3/4” and must be a min. of 2 inches away from the top and bottom of the 2x8 perimeter rail.

Floor Insulation Notes

1. The insulation shall have a flame spread of 25 or less and a smoke develop of 450 or less.

2. The floor insulation shall be a minimum of R-26 (R-11 blanket with R-15 batts) fiberglass insulation. One full batt, one additional full width batt between the I-beams, and one additional 16” wide batt between joist outside of I-beams.

Bottom Board Notes

1. All penetrations sealed per bottom board manufacturer's installation instructions.

2. Bottom board shall be a minimum of twenty (20) mil thickness.

3. Multiple layers of acceptable material per 3280.305(g)(6) may be used.

4. Fasten bottom board to perimeter framing per manufacturer's installation instructions. REV 01-17-23 . Feb 03, 2025

1 2

1 2

1 2

1 2

TOILET

W/H DRAIN

A

B

C

D123456

123456

123456

24'-10" P.BOX

20'-7" W/H

18'-73 4"

18'-3" DRYER DUCT

18'-73

4" DRYER WIRE

14'-11" TOILET DRAIN

1 2

1 2

1 2

24'-8" P.BOX

24'-6" P.BOX

1 2

37'-11" K. SINK

37'-71

2" K. SINK

1 2

30'-9" RANGE WIRE

W/H SUPPLY

WASHER

WASHER DRAIN

20'-9" TPS CLOSET DRAIN 41

4"Ø

16'-7" SPINKLER DRAIN 1 1/2"Ø

LAV

8'-21

2" LAV

8'-10" TUB P-TRAP

8'-61

2" TUB SUPPLY

8'-31

2" TUB DRAIN

7'-103

4" PHONE & TV WIRE

1 4

1 2 P

H O

N E

1 2 T

V

1 2

15'-53

4" TOILET SUPPLY

21'-81

2" TV WIRE

21'-51

2" TV WIRE

21'-13

4"OPTIONAL DEHUMIDIFIER DRAIN 2"Ø - SEE APPENDIX A, A-35 FOR MORE INFORMATION

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

14B1-13

DRAWING NO.

FLOOR DECKING LAYOUT

14' WIDE MHU

(PACKAGED SYSTEM)

Decking to Joists 7/16 x 1-3/4 x 16Ga staple OR 0.092 x 2" Nail

4" edges / 6" field w/ glue 6" edges / 10" field w/ glue

DESCRIPTION FASTENER APPLICATION

FASTENING SCHEDULE - FLOOR DECKING

Floor Decking Notes

1. The floor decking shall be 23/32" APA rated (24" o.c. panel span rating), laid out as shown on decking layout.

2. Decking shall be Exposure 1 rated.

3. Long edges of the panel shall be T&G installed perpendicular to the floor joists.

4. PVA (polyvinyl acetate) or equal shall be used as adhesive with 80% coverage.

5. Vinyl flooring shall be installed on all interior floors of the home installed per manufacturer's instructions.

6. Reserved.

7. The run of 19 1/2" wide floor decking may be installed on the curb side (MHU back door side) of the floor decking layout. When this option is utilized, it is the responsibility of the manufacturer to assure all floor decking hole dimensions are adjusted so all floor decking holes remain in the same location.

Legend = Plumbing fixture water line hole unless noted.

= Plumbing fixture drain line hole unless noted.

REV 11-15-23 . Feb 03, 2025

W/H

30603060

BA

TH

TPS

CLOSET

D R

YE

R

W

AS

H

ER

P1

P2P3

P4

P6

P7

P10 P5

E1

91 2

270 371

2 HDR

E2

S2

S1

1 2

H D

R

1 2 H

D R

3 25 1 2

H D

R 31 2

61 2

1 2

BACKPANEL

BEFORE P5

IS SET

(FIXED)

P11

1 2

DINING & LIVING

ROOM

4 SHELVES

HVAC

PACKAGED

SYSTEM

LIVINGDINING

R

EF

ER

PANTRY

KITCHEN

BEDROOM #1P8P9

2" x 4" x 20 Ga. Metal Connector Plate, one each side

2" x 4" x 20 Ga. Metal Connector Plate, one each side

TOP PLATE SPLICE

BOTTOM PLATE SPLICE

Min 2x by top plate width by 10” splice block centered over splice, plus or minus 1 inch. Fastened with

(6) - 7/16” x 2-1/2” x 15 Ga staples each side of splice.

Min 2x by bottom plate width by 10” splice block centered over splice, plus or minus 1 inch.

Fastened with (6) - 7/16” x 15 Ga staples (min. ½” penetration) each side of splice.

FASTENING SCHEDULE - INTERIOR WALLS

STUD TO TOP/BOTTOM PLATE

FASTENER APPLICATION

DOOR HEADER TO STUD

15Ga. x 7/16" x 2-1/2" STAPLES or 0.131" X 3" NAIL

3 EACH

2 EACH

BOTTOM PLATE TO FLOOR

TOP PLATE TO CEILING

INTO LAYFLAT

INTO TRUSS

GYPSUM TO STUDS

STUD TO STUD

LAYFLAT TO TOP/BOTTOM PLATE

3 EACH

2 EACH

DESCRIPTION

15Ga. x 7/16" x 2-1/2" STAPLES or 0.131" X 3" NAIL

12" O.C.

12" O.C.

or #8 x 3" WOOD SCREW

12" O.C.

12" O.C.

GYPSUM TO STUDS, 80% PVA GLUE

12" O.C.

12" O.C.

2 EACH

12" O.C.

ALTERNATE GYPSUM TO STUDS

100% ONE PART URETHANE GLUE

19Ga. x 3/16" x 1-1/4" STAPLES or DRYWALL SCREWS

6" EDGES

6" EDGES

19Ga. x 3/16" x 1-1/4" STAPLES or DRYWALL SCREWS

6" Edges / 12" Field 6" Edges / 12" Field

As per product manufacturer's instructions

15Ga. x 7/16" x 2-1/2" STAPLES or 0.131" X 3" NAIL

15Ga. x 7/16" x 2-1/2" STAPLES or 0.131" X 3" NAIL

INTERIOR WALL TO SIDEWALL #8 SCREWS, MIN. 1" PENETRATION 16" O.C.

INTERIOR WALL TO INTERIOR WALL .131" NAIL, MIN. 1" PENTRATION 16" O.C.

or #8 x 3" WOOD SCREW or #8 x 3" WOOD SCREW

15Ga. x 7/16" x 2-1/2" STAPLES or 0.131" X 3" NAIL

12" O.C.

15Ga. x 7/16" x 2-1/2" STAPLES or 0.131" X 3" NAIL

BACKERS TO STUD - BACKERS SHALL BE

#3 SPF MIN. AND SIZE AS SHOWN ON

DRAWINGS.

15Ga. x 7/16" x 2-1/2" STAPLES

(END GRAIN ONLY)

OR .131" X 3" NAIL (END GRAIN OR TOED)

6 EACH

3 EACH

12" O.C.

TITLE:

1/8" = 1'-0"

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

14B1-14

DRAWING NO.

BACK PANEL LAYOUT (HORIZONTAL)

INTERIOR WALL AND 14' WIDE MHU

(PACKAGED SYSTEM)

REV 06-03-22

General Notes

1. Gypsum to be jointed above all doors in line with jambs.

2. 1x6 SPF backers may be used only for sprinkler system supports.

W/H

30603060

BA

TH

TPS

CLOSET

D R

YE

R

W

AS

H

ER

P1

P2P3

P4

P6

P7

P10 P5

E1

1 2

1 2

3 31 2 25 1 2

61 2

242201

1 2

E2

S2

S1

BACKPANEL

BEFORE P5

IS SET

(FIXED)

P11

1 2

1 2

DINING & LIVING

ROOM

4 SHELVES

HVAC

PACKAGED

SYSTEM

LIVINGDINING

R

EF

ER

PANTRY

KITCHEN

BEDROOM #1P8P9

2" x 4" x 20 Ga. Metal Connector Plate, one each side

2" x 4" x 20 Ga. Metal Connector Plate, one each side

TOP PLATE SPLICE

BOTTOM PLATE SPLICE

Min 2x by top plate width by 10” splice block centered over splice, plus or minus 1 inch. Fastened with

(6) - 7/16” x 2-1/2” x 15 Ga staples each side of splice.

Min 2x by bottom plate width by 10” splice block centered over splice, plus or minus 1 inch.

Fastened with (6) - 7/16” x 15 Ga staples (min. ½” penetration) each side of splice.

FASTENING SCHEDULE - INTERIOR WALLS

STUD TO TOP/BOTTOM PLATE

FASTENER APPLICATION

DOOR HEADER TO STUD

15Ga. x 7/16" x 2-1/2" STAPLES or 0.131" X 3" NAIL

3 EACH

2 EACH

BOTTOM PLATE TO FLOOR

TOP PLATE TO CEILING

INTO LAYFLAT

INTO TRUSS

GYPSUM TO STUDS

STUD TO STUD

LAYFLAT TO TOP/BOTTOM PLATE

3 EACH

2 EACH

DESCRIPTION

15Ga. x 7/16" x 2-1/2" STAPLES or 0.131" X 3" NAIL

12" O.C.

12" O.C.

or #8 x 3" WOOD SCREW

12" O.C.

12" O.C.

GYPSUM TO STUDS, 80% PVA GLUE

12" O.C.

12" O.C.

2 EACH

12" O.C.

ALTERNATE GYPSUM TO STUDS

100% ONE PART URETHANE GLUE

19Ga. x 3/16" x 1-1/4" STAPLES or DRYWALL SCREWS

6" EDGES

6" EDGES

19Ga. x 3/16" x 1-1/4" STAPLES or DRYWALL SCREWS

6" Edges / 12" Field 6" Edges / 12" Field

As per product manufacturer's instructions

15Ga. x 7/16" x 2-1/2" STAPLES or 0.131" X 3" NAIL

15Ga. x 7/16" x 2-1/2" STAPLES or 0.131" X 3" NAIL

INTERIOR WALL TO SIDEWALL #8 SCREWS, MIN. 1" PENETRATION 16" O.C.

INTERIOR WALL TO INTERIOR WALL .131" NAIL, MIN. 1" PENTRATION 16" O.C.

or #8 x 3" WOOD SCREW or #8 x 3" WOOD SCREW

15Ga. x 7/16" x 2-1/2" STAPLES or 0.131" X 3" NAIL

12" O.C.

15Ga. x 7/16" x 2-1/2" STAPLES or 0.131" X 3" NAIL

BACKERS TO STUD - BACKERS SHALL BE

#3 SPF MIN. AND SIZE AS SHOWN ON

DRAWINGS.

15Ga. x 7/16" x 2-1/2" STAPLES

(END GRAIN ONLY)

OR .131" X 3" NAIL (END GRAIN OR TOED)

6 EACH

3 EACH

12" O.C.

TITLE:

1/8" = 1'-0"

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

14B1-15

DRAWING NO.

PANEL LAYOUT (VERTICAL) - OPTIONAL

INTERIOR WALL AND BACK 14' WIDE MHU

(PACKAGED SYSTEM)

REV 06-03-22

General Notes

1. Gypsum to be jointed above all doors in line with jambs.

2. 1x6 SPF backers may be used only for sprinkler system supports.

01625

P1 x x

-3

/4

BA

C

KE

R

U P

/4

2X6 UP

/4 S

H

EL

F

S

H

EL

F

2X6 UP

BED#1 CLO.

VERTICAL WALL BOARD PANEL BREAKS

TITLE:

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

1/2" = 1'-0" 14B1-16.1

DRAWING NO.

INTERIOR WALLS 14' WIDE MHU

(PACKAGED SYSTEM)

Interior Wall Framing Notes

1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.

2. Top plates to be 2 x 3 (unless noted) #2 SPF.

3. Bottom plates to be 1 x 3 SPF (unless noted).

4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.

5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.

6. Wall panel trim (1/8” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.

7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)

8. Paint shall be any latex paint. See FEMA spec.

REV 6-18-21

/4

1/

25 1/2

/4

29 32

3/

P2

3 1/2

25 1/2

3 1/2

25 1/2

BED#1 CLO.

VERTICAL WALL BOARD PANEL BREAKS

3/

TITLE:

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

1/2" = 1'-0" 14B1-16.2

DRAWING NO.

INTERIOR WALLS 14' WIDE MHU

(PACKAGED SYSTEM)

Interior Wall Framing Notes

1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.

2. Top plates to be 2 x 3 (unless noted) #2 SPF.

3. Bottom plates to be 1 x 3 SPF (unless noted).

4. Wall interiors shall be faced with ½” Gold Bond XP gypsum board with paint or equivalent installed per ASTM C840 and GA-216.

5. Gypsum board shall run vertically or horizontally along the entire height of wall interiors. See fastening schedule.

6. Wall panel trim (1/8” x 2”) shall be used to cover the gypsum panel joints. Trim fastened to only one of the two gypsum panels into stud, 10" O.C. fastener spacing.

7. Walls shall be sanded as needed to assure a smooth finish (level 3 finish minimum)

8. Paint shall be any latex paint. See FEMA spec.

REV 11-29-21

/4

16 32 48 64 80 96

1/

37 1/2

/4

P3

/2 x x

-3 /4

BA

C

KE

R U

P

3/

BACKER

DOWN

1X6

/4

3/

37 1/2

109 1/2

H O

R

IZ

O N

TA

L

PA

N

EL

S

IZ

E

(IF

A

PP

LI

C

AB

LE

H O

R

IZ

O N

TA

L

PA

N

EL

S

IZ

E

(IF

A

PP

LI

C

AB

LE

1x

FILLER

2x BLOCK 18" MIN.

1' -6

" M

IN

NOTCH FOR SPRINKLER SYSTEM PIPE

-SEE APPENDIX A-30 DETAIL "B"

NOTCH FOR SPRINKLER

SYSTEM PIPE

48 48 13 1/2

37 1/2 3

BATHROOM #1

VERTICAL WALL BOARD PANEL BREAKS

BACKER

UP

2X6

/2 BACKER

UP

2X6

3/ x x

-1

/4

BA

C

KE

R

U P

NOTCH FOR SPRINKLER PIPE -

SEE APPENDIX A-30.1. DETAIL "F"

1X6 SPRINKLER HEAD BACKER, SPRINKLER

HEAD BACKER LOCATION MAY VARY BASED

ON SPRINKLER DESIGN.

TITLE:

6/28/2019FEMA Manufactured Housing Units Federal Emergency Management Agency

DATE:

SCALE:

COMPANY: VERSION:

1/4" = 1'-0" 14B1-16.3

DRAWING NO.

INTERIOR WALLS 14' WIDE MHU

(PACKAGED SYSTEM)

Interior Wall Framing Notes

1. All interior walls are 2 x 3 (unless noted) #2 SPF at 16” maximum o.c., except washer wall.

2. Top plates to be 2 x 3 (unless noted) #2 SPF.

3. Bottom…