A06_Dwgs_01_ORCA_100CD_FINAL_8_ELECTRICAL.pdf

PDF 8 MB Posted

Attached to
ORCA 150025 - Correct Life Safety and Critical Def
Solicitation number
140P2019R0045
Issued by

About this file

This pre-solicitation notice seeks proposals for a single construction contract to Correct Life Safety and Critical Deficiencies at Oregon Caves Chateau. The project includes fire suppression and detection systems, code compliant egress doors and accessibility improvements, structural repairs, replacement of water supply and waste vent piping, and replacement of steam piping and radiators. The work will be conducted in one phase under a single prime contract, with an estimated price range of over $10 million and period of performance from April 2020 to September 2021. The solicitation will be issued on or around October 21, 2019 via www.fedbizopps.gov. The NAICS code is 236220 with a size standard of $36.5 million. The National Park Service encourages participation from small businesses, including veteran-, small disadvantaged-, and women-owned small businesses. Interested vendors should monitor the website for additional details.

Drawings - Electrical

View the file

Other files

File Type Posted
01 27 00-Definition of Contract Line Items_ORCA Amend 4_0004.pdf PDF
140P2019R0045 Amend 4 SOC_0004.pdf PDF
07_ContractPriceSchedule_ORCA150025_Amend 4_0004.xls XLS spreadsheet
Sol_140P2019R0045_Amd_0004.pdf PDF
09 80 00 Fiberboard Wall Ceiling Treatment_ORCA_0003.pdf PDF
Sol_140P2019R0045_Amd_0003.pdf PDF
B03_Wage_Determination_OR20200039 1-3-2020_0003.pdf PDF
140P2019R0045 Amend 3 SOC_0003.pdf PDF
Sol_140P2019R0045_Amd_0001.pdf PDF
Sol_140P2019R0045_Amd_0002.pdf PDF
00 01 10 Table of Contents_ORCA_r1_0002.pdf PDF
140P2019R0045 Amend 1 SOC.updated_0002.pdf PDF
09 80 00 Fiberboard Wall & Ceiling Treatment_0002.pdf PDF
Sign-in sheet_0002.pdf PDF
L8.03 Landscape Details - A1_0002.pdf PDF
A06_Specs_03_XAPPENDIX-C_ORCA_Chateau_Hazardous_Materials_Report.pdf PDF
A06_Specs_03_XAPPENDIX-D_ORCA_Fire_Protection_Basis_of_Design.pdf PDF
A06_Specs_03_XAPPENDIX-B_ORCA_STRUCT_CALCS_201900913_Pages_1_-_164.pdf PDF
A06_Specs_03_XAPPENDIX-A_ORCA_Geotech_Report.pdf PDF
A06_Specs_03_XAPPENDIX-B_ORCA_STRUCT_CALCS_201900913_Pages_165_-_330.pdf PDF
B08_Solit_PSP_Vol_II_SubKPlanForm_REQD.doc DOC document
B08_Solic_Contract_Price_Schedule_ORCA150025_FINAL.xls XLS spreadsheet
A06_Dwgs_01_ORCA_100CD_FINAL_0_TITLE.pdf PDF
A06_Dwgs_01_ORCA_100CD_FINAL_3_ARCHITECTURE.pdf PDF
A06_Dwgs_01_ORCA_100CD_FINAL_6_PLUMBING.pdf PDF
B08_Solit_PSP_Vol_II_GenRefs.doc DOC document
B08_Solic_140P2019R0045_SF_1442_&_Clauses.pdf PDF
A06_Specs_02_ORCA_100CD_FINAL_SPECS-DIV-01.pdf PDF
B08_Solit_PSP_Vol_I_Exp_REQD.docx DOCX document
B08_Solic_SF24-16d.pdf PDF
A06_Dwgs_01_ORCA_100CD_FINAL_7_MECHANICAL.pdf PDF
A06_Dwgs_01_ORCA_100CD_FINAL_4_FIRE_SUPPRESSION.pdf PDF
A06_Dwgs_01_ORCA_100CD_FINAL_2_STRUCTURAL.pdf PDF
A06_Dwgs_01_ORCA_100CD_FINAL_5_FIRE_DETECTION.pdf PDF
A06_Specs_02_ORCA_100CD_FINAL_SPECS-DIV-15-48.pdf PDF
B03_Wage_Determination_OR20190039_8-30-19.pdf PDF
B08_Solit_PSP_Vol_I_PastPerf_REQD.docx DOCX document
A06_Specs_02_ORCA_100CD_FINAL_SPECS-DIV-02-14.pdf PDF
A06_Dwgs_01_ORCA_100CD_FINAL_1_LANDSCAPE.pdf PDF
B08_Solit_PSP_Cover.rtf RTF text file
B08_Solit_PSP_Vol_II_Equals.doc DOC document
B08_Solit_PSP_Vol_II_HazMat.doc DOC document
Show all 42

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ELECTRICAL SYMBOLS AND LEGEND

RECEPTACLES / POWERFLOOR WALL CEILING

P

NOTE: ALL RECEPTACLE OUTLETS ON WALLS ARE MOUNTED AT 18" AFF, UON.

EXISTING / DEMOLITION

MULTI-OUTLET RACEWAY WITH PREWIRED RECEPTACLES

MOUNTED 12" ON CENTER UNLESS OTHERWISE NOTED.

NUMBER IN PARENTHESIS INDICATES DISTANCE

BETWEEN DEVICES. WHERE MULTIPLE CIRCUITS ARE

INDICATED CIRCUITS ALTERNATE ALONG ENTIRE LENGTH

OF RACEWAY. MOUNTED 4' AFF UON.

EXISTING EQUIPMENT TO REMAIN

EXISTING EQUIPMENT TO BE REMOVED

NEW EQUIPMENT / RACEWAYS

EXISTING TO REMAIN

EXISTING TO BE REMOVED

NEW EQUIPMENT, LIGHTING FIXTURE OR

DEVICE

SINGLE LINE DIAGRAM

P P

X

X X

X

X

X

LIGHTING

SURFACE MOUNTED TROFFER

WALL CEILING

EXAMPLES:

NORMAL EMERGENCY

LUMINAIRE

NOMENCLATURE:

"A" DENOTES FIXTURE TYPE

"3" DENOTES CIRCUIT NUMBER

"a" DENOTES SWITCH ZONE "z1" DENOTES DAYLIGHT ZONE "r1" DENOTES SITE RELAY ZONE

EXIT SIGN; SHADED PORTION INDICATES ILLUMINATED

FACE. DIRECTIONAL ARROWS AS INDICATED ON THE

DRAWINGS. REFER TO LUMINAIRE SCHEDULE FOR

MORE INFORMATION.

EXIT

E-6

P

A E-6

GENERAL ELECTRICAL SYMBOLSRECESSED SURFACE

DISCONNECT SWITCH, 30 AMP MINIMUM UNLESS

NOTED OTHERWISE

FREE STANDING SWITCHBOARD, MOTOR CONTROL

CENTER OR DISTRIBUTION PANELBOARD

A-1,3,5

J

J

J

J

J

A. CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING FIXTURE TYPE AND

MOUNTING CONDITIONS REGARDLESS OF SYMBOL USED ON PLANS.

B. REFER TO LUMINAIRE SCHEDULE FOR FIXTURE DESCRIPTION, MOUNTING AND

LAMP INFORMATION. SHADED FIXTURE SYMBOLS INDICATE FIXTURE IS

CONNECTED TO THE EMERGENCY POWER SUPPLY SYSTEM OR HAS

SECONDARY POWER SOURCE.

RECESSED MOUNTED TROFFER

SUSPENDED OR PENDANT MOUNTED LUMINAIRE

NORMAL EMERGENCY

STRIP OR TRACK LIGHT

SURFACE MOUNTED DOWNLIGHT

RECESSED MOUNTED DOWNLIGHT

PENDANT MOUNTED DOWNLIGHT

DIRECTIONAL LUMINAIRE

SIMPLEX RECEPTACLE

JUNCTION BOX WALL OR CEILING MOUNTED 7' 2"

AFF UON.

DUPLEX RECEPTACLE

QUADRUPLEX RECEPTACLE

SPECIAL RECEPTACLE

(DUPLEX & QUADRUPLEX)

GROUND FAULT CIRCUIT INTERRUPTING

RECEPTACLE, ABOVE COUNTER UNLESS NOTED.

ABOVE COUNTER RECEPTACLE. INSTALL ABOVE

COUNTER OR DEFINED HEIGHT

HALF CONTROLLED DUPLEX

SWITCHED RECEPTACLES

JUNCTION BOX SIZE AS REQUIRED FOR

NUMBER OF WIRES OR RACEWAYS

SYSTEM FURNITURE POWER FEED, REFER TO

DETAIL FOR RACEWAY AND BOX REQUIREMENTS

POLE MOUNTED LUMINAIRE (1, 2, 3, 4 HEADS)

WALL MOUNTED LUMINAIRE

XX

X33

+4'-6"

A 3,a,z1

FIRE TREATED PLYWOOD BACKBOARD 3/4"X96" HIGH X

LENGTH AS INDICATED

REFERENCE TO NOTE "1" ON SAME SHEET

LIGHTING FIXTURE DESIGNATION

XX = FIXTURE TYPE

MECHANICAL EQUIPMENT DESIGNATION "P-1" INDICATED

EQUIPMENT NAME OR NUMBER

MOUNTING HEIGHT FROM FINISHED FLOOR TO

CENTERLINE OF OUTLET OR EQUIPMENT

DETAIL REFERENCE NUMBER "1"

ON DRAWING "E-6"

SECTION OR ELEVATION REFERENCE LETTER

"A" ON DRAWING "E-6"

INDICATES HOMERUN WITH THREE CIRCUITS

AND SEPARATE NEUTRALS

FUSED DISCONNECT SWITCH, 30 AMP MINIMUM

UNLESS NOTED OTHERWISE

COMBINATION DISCONNECT SWITCH MOTOR

STARTED

MOTOR, 5 HP INDICATED

TRANSFORMER

RELAY OR EQUIPMENT CABINET AS INDICATED ON

THE DRAWINGS

LIGHTING OR POWER PANELBOARD

T

NOTES:

GROUNDING SYSTEMFLOOR WALL

POKE

THRU

HALF CONTROLLED QUADRUPLEX

(18)

G

EXOTHERMIC GROUND CONNECTION

GROUND WIRE

GROUNDING ELECTRODE

CIRCUIT BREAKER, 3 POLE UNLESS NOTED

OTHERWISE

NON-FUSED DISCONNECT SWITCH, 30 AMP, 3P

UNLESS NOTED OTHERWISE

FUSED DISCONNECT SWITCH, 3 POLE UNLESS

NOTED OTHERWISE

GROUNDING ELECTRODE

RACEWAYS AND WIRINGFLOOR WALL CEILING

CONDUIT CONCEALED IN CEILING OR WALL

SPACE

A-1 A-1A-1

(MS-01) (MS-01)

<RA-1> <RA-1>

CONDUIT RUN EXPOSED

CONDUIT RUN UNDERGROUND

OR CONCEALED IN FLOOR SPACE

EXISTING CONDUIT TO REMAIN

CONDUIT RISING UP FROM BELOW

CONDUIT DROPPING DOWN FROM ABOVE

HOMERUN TO PANELBOARD, CABINET

OR TERMINAL BACKBOARD AS

INDICATED

HOMERUN TO SWITCHBOARD OR MCC AS

INDICATED. REFER TO SINGLE LINE

DIAGRAM FOR CONDUIT AND WIRE SIZES

HOMERUN TO PANEL VIA INDICATED

LIGHTING CONTROL RELAY CABINET. REFER

TO INDICATED RELAY CABINET SCHEDULE

FOR ADDITIONAL INFORMATION AND

CONTROL REQUIREMENTS

SWITCHING

MANUAL MOTOR STARTER WITH THERMAL OVERLOAD

NUMBER OF POLES AS REQUIRED

P

P

M

X ab abc

L abc

X33

WALL CEILING

SWITCH, SUBSCRIPT INDICATES:

X = NONE - SINGLE POLE

X = 3 - THREE WAY

X = A,B,C - OUTLET CONTROLLED

X = 2 - DOUBLE POLE

X = KP - KEY OPERATED WITH PILOT LIGHT

X = P - PILOT LIGHT

X = R - MOMENTARY RELAY ON/OFF

X = S - INTEGRAL MOTION DECTOR

2-SINGLE POLE SWITCHES, UNDER COMMON PLATE, 42" AFF UON

3-SINGLE POLE SWITCHES, UNDER COMMON PLATE, 42" AFF UON

LOW VOLTAGE LIGHTING CONTROL. NUMBER IN ELONGATED

HEXAGON INDICATES CONTROL IDENTIFICATION. REFER TO

SEQUENCE OF OPERATIONS AND LIGHTING CONTROL DETAILS

FOR ADDITIONAL INFORMATION. 42" AFF UON

DIMMER WITH INTEGRAL SWITCH, 42" AFF UON. '600' INDICATES

RATING IN WATTS

PUSH-BUTTON STATION. 42" AFF UON

PHOTOSENSOR - WALL MOUNT WITH DIRECTIONAL VIEW.

ARROW INDICATES AIMING DIRECTION. MOUNTED 7' 2" AFF

UON

PHOTOSENSOR - CEILING MOUNT

LX LOW VOLTAGE LIGHTING CONTROL SUBSCRIPT

INDICATES:

X = D - DIMMER SWITCH

X = S - SENSOR SWITCH

X = T - TIMER SWITCH

X = M - MASTER CONTROL SWITCH 42" AFF UON

X = V - LOW VOLTAGE

DUAL TECHNOLOGY OCCUPANCY SENSOR, 360 DEGREE. 42" AFF UON

DUAL TECHNOLOGY OCCUPANCY SENSOR, DIRECTIONAL AS

INDICATED ON THE DRAWINGS. 42" AFF UON.

TELECOMMUNICATIONSFLOOR WALL CEILING

X

TELEPHONE OUTLET. SUBSCRIPT INDICATES:

X = H - HOUSE PHONE

X = J - HOUSE PHONE JACK

EMERGENCY LOW VOLTAGE REMOTE HEAD

REFER TO LUMINAIRE SCHEDULE FOR MORE

INFORMATION.

FIRE ALARM SYSTEMWALL CEILING

FIRE ALARM CONTROL PANELFACP

ABBREVIATIONS

RM REMOTE HEAD MDP MAIN DISTRIBUTION PANEL

PNL PANELBOARD SPD SURGE PROTECTION DEVICE

AFF ABOVE FINISHED FLOOR AWG AMERICAN WIRE GAUGE

CKT CIRCUIT UON UNLESS OTHERWISE NOTED

NEC NATIONAL ELECTRIC CODE CONN CONNECTION

EST ESTIMATE VFD VARIABLE FREQUECY DRIVE

WP WEATHERPROOF MCM THOUSAND CIRCULAR MILS

C CONDUIT BB BASE BOARD HEATER

MOCP MAXIMUM OVERCURRENT PROTECTION

GROUNDING BAR

GROUNDING BAR

EMERGENCY BATTERY PACK WITH REMOTE HEAD.

REFER TO LUMINAIRE SCHEDULE FOR MORE

INFORMATION.M ELECTRICAL MOTOR CONNECTION

M METER

SURGE PROTECTIVE DEVICE

G

GENERATOR, AS NOTED ON

SINGLE LINE DIAGRAM

(MS-01)

<RA-1>

GROUND BUS BAR

SPD

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OFOREGON CAVES NATIONAL MONUMENT

OREGON CAVES CHATEAU

138578

150025

R E

V

IT

/1

/2

:5

:1

P

M C

U s e rs

\p d a v is

\D o c u m e n ts \O

R C

A

M E

P -C e n tr a l_ p d a v is

.r v t

SM

MJL

CvB, WSP

09/13/19

ELECTRICAL LEGEND

E0.01 189 211

CONSTRUCTION DOCUMENTS

E .0

M

J L

This document has been digitally signed and sealed by

William S. Phillips, PE

OR PE #94068

Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.

Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:01:32-04'00'

DRAWINGS

PANELBOARD SCHEDULE LEGEND

S - PROVIDE SHUNT TRIP BREAKER.

G - PROVIDE GROUND FAULT CIRCUIT INTERRUPTER (GFCI).

H - PROVIDE HANDLE CLAMP DEVICE.

A - PROVIDE ARC FAULT CIRCUIT INTERRUPTER (AFCI).

M - PROVIDE CT FOR METERING SYSTEM AND CONNECTED TO

METER INDICATED ON THE METERING SCHEDULE.

RED SURFACE WITH WHITE

CORE PHENOLIC LABEL

SERVICE DISCONNECTING MEANS

#1 of 2

NOTES

1. NAMEPLATES SHALL BE PERMANENTLY INSTALLED ON EQUIPMENT WITH STAINLESS

STEEL SCREWS - ADHESIVE LABELS SHALL NOT BE USED

DESIGNATION

DISCONNECTS LOCATED IN RM B301

1. DISTRIBUTION PANEL 'MDP'

2. DISTRIBUTION PANEL 'FVDP'

#1 = DISTRIBUTION PANEL 'MDP'

MAIN BREAKER

#2 = DISTRIBUTION PANEL 'FVDP'

MAIN BREAKER

NO SCALE

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OFOREGON CAVES NATIONAL MONUMENT

OREGON CAVES CHATEAU

138578

150025

R E

V

IT

/1

/2

:5

:2

P

M C

U s e rs

\p d a v is

\D o c u m e n ts \O

R C

A

M E

P -C e n tr a l_ p d a v is

.r v t

SM

MJL

CvB, WSP

09/13/19

ELECTRICAL PANEL

SCHEDULES

E0.02 190 211

CONSTRUCTION DOCUMENTS

E .0

M

J L

Other 0.6 kVA 0.6 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 1.5 kVA 1.5 kVA Lighting and Receptacles - Hotel 16.1 kVA 8.0 kVA Design Current: 597.2 A Elevator 20.0 kVA 20.0 kVA Design Load: 143.3 kVA Motor 9.1 kVA 9.7 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 477.8 A Heating 53.3 kVA 53.3 kVA Total Connected Current: 532.0 A Cooling 0.0 kVA 0.0 kVA Total Estimated Demand Load: 114.7 kVA Lighting 3.6 kVA 4.6 kVA Total Connected Load: 127.7 kVA Receptacles 23.0 kVA 16.5 kVA Load Classification Connected Load Estimated Demand Panel Totals

-EQUIPMENT SHALL BE LABELED AS 'SUITABLE FOR USE AS SERVICE ENTRANCE.' PROVIDE LABEL IN ACCORDANCE WITH DETAIL 1/E0.02.

-PROVIDE SPD AS SPECIFIED.

-PROVIDE CUSTOMER METERING IN ACCORDANCE WITH SECTION 26 24 16.

-PROVIDE FULLY RATED MAIN BREAKER.

70.0 kVA 57.6 kVA

47 0.0 0.0 48 -- -- SPACE ONLY --

SPD 30 A 2

45 0.0 0.0 46 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 43 0.0 0.0 44 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 41 0.0 0.0 42 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 39 0.0 0.0 40 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 37 0.0 0.0 38 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 35 0.0 0.0 36

-- SPACE ONLY -- -- 33 0.0 0.0 34

2 150 A SPARE

31 0.0 0.0 32

SPARE 225 A 2

29 0.0 0.0 30

2 100 A SPARE

27 0.0 0.0 28

SPARE 150 A 2

25 0.0 0.0 26

2 100 A SPARE

23 0.0 10.0 24

SPARE 100 A 2

21 0.0 10.0 22

2 125 A DRYER RM B209B

19 0.0 3.4 20

SPARE 100 A 2

17 0.0 6.1 18

2 100 A PANEL 3.1

15 10.0 7.5 16

DRYER RM B209B 125 A 2

13 10.0 8.4 14

2 100 A PANEL 2.1

-- SPACE ONLY -- -- 11 0.0 3.1 12

-- SHUNT TRIP MODULE -- -- 9 0.0 7.9 10

2 100 A PANEL B3.1

7 10.0 2.7 8

S ELEVATOR 150 A 2

5 10.0 5.4 6

2 100 A PANEL B2.3

3 3.5 7.4 4

PANEL B1.1 100 A 2

1 5.0 7.2 2

2 100 A PANEL B2.1

DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION

Sections: 1

Mounting: SURFACE AIC Rating: 22,000 A

Wire: 3 Main Rating: 600 A

Phase: 1 Mains Type: MCB

Voltage: 120/240 Amp Rating: 600 A

Distribution Panelboard: MDP

DISTRIBUTION

PANELBOARD 'MDP'

DISTRIBUTION

PANELBOARD 'FVDP'

(BLANK) (BLANK)

E0.02

1 SERVICE DISCONNECT MEANS

Other 0.1 kVA 0.1 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 41.1 kVA 26.7 kVA Lighting and Receptacles - Hotel 0.0 kVA 0.0 kVA Design Current: 267.6 A Elevator 0.0 kVA 0.0 kVA Design Load: 64.2 kVA Motor 7.9 kVA 9.6 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 214.1 A Heating 0.0 kVA 0.0 kVA Total Connected Current: 266.7 A Cooling 8.5 kVA 8.5 kVA Total Estimated Demand Load: 51.4 kVA Lighting 0.6 kVA 0.7 kVA Total Connected Load: 64.0 kVA Receptacles 5.8 kVA 5.8 kVA Load Classification Connected Load Estimated Demand Panel Totals

-EQUIPMENT SHALL BE LABELED AS 'SUITABLE FOR USE AS A SERVICE ENTRANCE.' PROVIDE LABEL IN ACCORDANCE WITH DETAIL 1/E0.02.

-PROVIDE SPD AS SPECIFIED.

-PROVIDE CUSTOMER METERING IN ACCORDANCE WITH SECTION 26 24 16.

32.6 kVA 31.5 kVA

47 0.0 0.0 48 -- -- SPACE ONLY --

SPD 30 A 2

45 0.0 0.0 46 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 43 0.0 0.0 44 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 41 0.0 0.0 42 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 39 0.0 0.0 40 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 37 0.0 0.0 38 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 35 0.0 0.0 36 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 33 0.0 0.0 34 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 31 0.0 0.0 32 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 29 0.0 0.0 30 1 20 A SPARE

SPARE 20 A 1 27 0.0 0.0 28 1 20 A SPARE

SPARE 20 A 1 25 0.0 0.0 26

23 0.0 0.0 24

2 20 A SPARE

SPARE 20 A 2

21 0.0 0.0 22 19 0.0 0.0 20

2 20 A SPARE

SPARE 20 A 2

17 0.0 0.0 18 1 20 A SPARE

SPARE 20 A 1 15 0.0 0.0 16 1 20 A SPARE

LTG STAFF KITCHEN B208B 20 A 1 13 0.1 1.2 14 1 20 A ICE MACHINE RM B209

LTG COFFEE SHOP B104 20 A 1 11 0.4 1.0 12 1 20 A EXISTING FAN COIL RM B101

LTG KITCHEN B103 20 A 1 9 0.1 2.9 10

7 2.0 2.9 8

2 30 A WALK-IN REFRIGERATOR RM B103A

EXISTING FAN COIL RM B208 40 A 2

5 2.0 0.0 6 -- -- SHUNT TRIP MODULE --

3 22.0 3.2 4

PANEL B2.2 225 A 2

1 23.1 3.2 2

2 50 A KEF-1 S

DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION

Sections: 1

Mounting: SURFACE AIC Rating: 22,000 A

Wire: 3 Main Rating: 400 A

Phase: 1 Mains Type: MCB

Voltage: 120/240 Amp Rating: 400 A

Distribution Panelboard: FVDP

E0.02

2 SECONDARY TRENCH DETAIL

This document has been digitally signed and sealed by

William S. Phillips, PE

OR PE #94068

Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.

Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:01:24-04'00'

G - PROVIDE GROUND FAULT CIRCUIT INTERRUPTER (GFCI).

H - PROVIDE HANDLE CLAMP DEVICE.

A - PROVIDE ARC FAULT CIRCUIT INTERRUPTER (AFCI).

M - PROVIDE CT FOR METERING SYSTEM AND CONNECTED TO

METER INDICATED ON THE METERING SCHEDULE.

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OFOREGON CAVES NATIONAL MONUMENT

OREGON CAVES CHATEAU

138578

150025

R E

V

IT

/1

/2

:5

:2

P

M C

U s e rs

\p d a v is

\D o c u m e n ts \O

R C

A

M E

P -C e n tr a l_ p d a v is

.r v t

SM

MJL

CvB, WSP

09/13/19

ELECTRICAL PANEL

SCHEDULES

E0.03 191 211

CONSTRUCTION DOCUMENTS

E .0

M

J L

Other 0.2 kVA 0.2 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 0.0 kVA 0.0 kVA Lighting and Receptacles - Hotel 1.3 kVA 0.6 kVA Design Current: 76.3 A Elevator 0.0 kVA 0.0 kVA Design Load: 18.3 kVA Motor 5.5 kVA 5.9 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 61.0 A Heating 0.0 kVA 0.0 kVA Total Connected Current: 60.6 A Cooling 0.0 kVA 0.0 kVA Total Estimated Demand Load: 14.6 kVA Lighting 1.4 kVA 1.8 kVA Total Connected Load: 14.6 kVA Receptacles 6.1 kVA 6.1 kVA Load Classification Connected Load Estimated Demand Panel Totals

-PROVIDE SPD AS SPECIFIED.

7.2 kVA 7.4 kVA

41 0.0 0.0 42 1 20 A SPARE

SPD 30 A 2

39 0.0 0.0 40 1 20 A SPARE

SPARE 20 A 1 37 0.0 0.0 38 1 20 A SPARE

SPARE 20 A 1 35 0.0 0.0 36 1 20 A SPARE

SPARE 20 A 1 33 0.0 0.0 34 1 20 A SPARE

SPARE 20 A 1 31 0.0 0.0 32 1 20 A SPARE

DOOR OPEN ALARM 20 A 1 29 0.2 0.0 30 1 20 A SPARE

REC. ROOM B211B 20 A 1 27 0.2 1.5 28 1 20 A WASHER RM B209B

A REC RM B205 20 A 1 25 0.9 1.5 26 1 20 A WASHER RM B209B

A REC RM B207 20 A 1 23 0.3 1.5 24 1 20 A WASHER RM B209B

A REC RM B206 20 A 1 21 0.4 0.3 22 1 20 A EF-8

LTG STAIR B200 20 A 1 19 0.1 0.3 20 1 20 A EF-7

REC RM B201,B203,B204 20 A 1 17 1.8 0.8 18 1 20 A LTG LEVEL B2

LIGHTING CONTROL PANEL 'LCPB2' 20 A 1 15 0.0 0.3 16 1 20 A LTG B2 - EMERGENCY

LTG B1 - EXTERIOR 20 A 1 13 0.1 0.1 14 1 20 A LTG STAIRS B300

LTG B2 - EXTERIOR 20 A 1 11 0.1 0.0 12 1 20 A ELEVATOR PIT LIGHT

LTG B1 EXTERIOR 20 A 1 9 0.0 0.5 10 1 20 A REC RM 202,202A,202B

ELEVATOR CAB LIGHT DISCONNECT 20 A 1 7 0.0 0.1 8 1 20 A LTG LEVEL B1

REC ELEVATOR PIT 20 A 1 5 0.2 0.5 6 1 20 A REC RM B204B

REC RM B208,B209,B211,B211C 20 A 1 3 2.0 0.6 4 1 20 A REC RM B204A

LTG LEVEL B2 20 A 1 1 0.0 0.0 2 1 20 A LTG RM B204

DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION

Mounting: SURFACE Sections: 1

Wire: 3 AIC Rating: 10,000 A

Phase: 1 Main: MLO

Voltage: 120/240 Amp Rating: 100 A

Panelboard: B2.1

Other 0.0 kVA 0.0 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 34.2 kVA 22.2 kVA Lighting and Receptacles - Hotel 0.0 kVA 0.0 kVA Design Current: 172.9 A Elevator 0.0 kVA 0.0 kVA Design Load: 41.5 kVA Motor 1.0 kVA 1.1 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 138.3 A Heating 0.0 kVA 0.0 kVA Total Connected Current: 187.7 A Cooling 4.0 kVA 4.0 kVA Total Estimated Demand Load: 33.2 kVA Lighting 0.0 kVA 0.0 kVA Total Connected Load: 45.0 kVA Receptacles 5.8 kVA 5.8 kVA Load Classification Connected Load Estimated Demand Panel Totals

-PROVIDE SPD AS SPECIFIED.

-PROVIDE LOW VOLTAGE WIRING FROM SHUNT-TRIP BREAKER BACK TO KITCHEN ANSUL SYSTEM.

23.1 kVA 22.0 kVA

59 0.0 0.0 60 1 20 A SPARE

SPD 30 A 2

57 0.0 0.0 58 1 20 A SPARE

SPARE 20 A 1 55 0.0 0.0 56 1 20 A SPARE

SPARE 20 A 1 53 0.0 0.0 54 1 20 A SPARE

SPARE 20 A 1 51 0.0 0.0 52 1 20 A SPARE

SPARE 20 A 1 49 0.0 0.0 50 1 20 A SPARE

SPARE 20 A 1 47 0.0 0.0 48 1 20 A SPARE

REC RM B104 20 A 1 45 0.4 0.0 46 1 20 A SPARE

REC DED RM B104 20 A 1 43 0.2 0.2 44 1 20 A REC DED RM B104

REC DED RM B104 20 A 1 41 0.2 0.2 42 1 20 A REC DED RM B104

EXISTING STAFF KITCHEN SUPPLY AIR 20 A 1 39 0.5 0.2 40 1 20 A REC DED RM B104

B100 STAIR ELECTRIC LOCK 20 A 1 37 0.8 0.2 38 1 20 A REC DED RM B104

GAS RANGE 20 A 1 35 0.2 2.0 36

EXISTING STAFF KITCHEN HOOD FAN 20 A 1 33 0.5 2.0 34

2 40 A EXISTING SERVICE ENTRY HOOD FAN

REC RM B101 20 A 1 31 0.7 0.4 32 1 20 A REC RM B101A,B101B

BEER COOLER RM B101 20 A 1 29 1.5 0.7 30 1 20 A REC RM B102

SALAD BAR REFRIGERATOR RM B102 20 A 1 27 1.5 0.4 28 1 20 A REC RM B104

-- SHUNT TRIP MODULE -- -- 25 0.0 0.7 26 1 20 A REC RM B104

23 2.9 1.5 24 1 20 A WINE COOLER RM B101

S DEEP FRYER RM B103 30 A 2

21 2.9 1.2 22 1 20 A COFFEE MACHINE RM B104

-- SHUNT TRIP MODULE -- -- 19 0.0 1.5 20 1 20 A SALAD BAR REFRIGERATOR RM B208B

S PROPANE OVEN RM B103 20 A 1 17 0.2 0.0 18 -- -- SHUNT TRIP MODULE --

REFRIGERATOR RM B101 20 A 1 15 1.5 0.2 16 1 20 A PROPANE OVEN RM B103 S

REFRIGERATOR RM B103 20 A 1 13 1.5 1.5 14 1 20 A REFRIGERATOR RM B101

REFRIGERATOR RM B103 20 A 1 11 1.5 1.5 12 1 20 A REFRIGERATOR RM B103

INDUSTRIAL DISHWASHER RM B103 30 A 1 9 1.8 1.5 10 1 20 A REFRIGERATOR RM B103

STEAM TABLE RM B208B 20 A 1 7 1.2 1.5 8 1 20 A REFRIGERATOR RM B208B

DEEP FREEZER RM B103 20 A 1 5 1.8 1.2 6 1 20 A STEAM TABLE RM B103

MICROWAVE RM B103 20 A 1 3 1.2 1.4 4 1 20 A MICROWAVE RM B208B

MICROWAVE RM B103 20 A 1 1 1.2 1.2 2 1 20 A MICROWAVE RM B103

DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION

Mounting: SURFACE Sections: 1

Wire: 3 AIC Rating: 22,000 A

Phase: 1 Main: MLO

Voltage: 120/240 Amp Rating: 225 A

Panelboard: B2.2

PANEL 'B2.1' PANEL 'B2.2'

PANEL 'B2.3' (BLANK)

Other 0.0 kVA 0.0 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 1.5 kVA 1.5 kVA Lighting and Receptacles - Hotel 0.0 kVA 0.0 kVA Design Current: 45.2 A Elevator 0.0 kVA 0.0 kVA Design Load: 10.9 kVA Motor 2.4 kVA 3.0 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 36.2 A Heating 4.0 kVA 4.0 kVA Total Connected Current: 33.7 A Cooling 0.0 kVA 0.0 kVA Total Estimated Demand Load: 8.7 kVA Lighting 0.0 kVA 0.0 kVA Total Connected Load: 8.1 kVA Receptacles 0.2 kVA 0.2 kVA Load Classification Connected Load Estimated Demand Panel Totals

-PROVIDE SPD AS SPECIFIED.

5.4 kVA 2.7 kVA

41 0.0 0.0 42 -- -- SPACE ONLY --

SPD 30 A 2

39 0.0 0.0 40 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 37 0.0 0.0 38 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 35 0.0 0.0 36 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 33 0.0 0.0 34 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 31 0.0 0.0 32 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 29 0.0 0.0 30 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 27 0.0 0.0 28 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 25 0.0 0.0 26 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 23 0.0 0.0 24 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 21 0.0 0.0 22 -- -- SPACE ONLY --

SPARE 20 A 1 19 0.0 0.0 20 1 20 A SPARE

SPARE 20 A 1 17 0.0 0.0 18 1 20 A SPARE

SPARE 20 A 1 15 0.0 0.0 16 1 20 A SPARE

SPARE 20 A 1 13 0.0 0.0 14 1 20 A SPARE

SPARE 20 A 1 11 0.0 0.0 12 1 20 A SPARE

SPARE 20 A 1 9 0.0 0.0 10 1 20 A SPARE

SPARE 20 A 1 7 0.0 0.2 8 1 20 A FACP H

SPACE HEATER RM B208 20 A 1 5 1.0 2.4 6 1 40 A ELEVATOR SUMP

SPACE HEATER RM B101 20 A 1 3 1.0 1.5 4 1 20 A REFRIGERATOR RM 110

SPACE HEATER RM 109 20 A 1 1 1.0 1.0 2 1 20 A SPACE HEATER RM B101

DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION

Mounting: SURFACE Sections: 1

Wire: 3 AIC Rating: 22,000 A

Phase: 1 Main: MLO

Voltage: 120/240 Amp Rating: 100 A

Panelboard: B2.3

This document has been digitally signed and sealed by

William S. Phillips, PE

OR PE #94068

Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.

Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:01:17-04'00'

G - PROVIDE GROUND FAULT CIRCUIT INTERRUPTER (GFCI).

H - PROVIDE HANDLE CLAMP DEVICE.

A - PROVIDE ARC FAULT CIRCUIT INTERRUPTER (AFCI).

M - PROVIDE CT FOR METERING SYSTEM AND CONNECTED TO

METER INDICATED ON THE METERING SCHEDULE.

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OFOREGON CAVES NATIONAL MONUMENT

OREGON CAVES CHATEAU

138578

150025

R E

V

IT

/1

/2

:5

:3

P

M C

U s e rs

\p d a v is

\D o c u m e n ts \O

R C

A

M E

P -C e n tr a l_ p d a v is

.r v t

SM

MJL

CvB, WSP

09/13/19

ELECTRICAL PANEL

SCHEDULES

E0.04 192 211

CONSTRUCTION DOCUMENTS

E .0

M

J L

Other 0.0 kVA 0.0 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 0.0 kVA 0.0 kVA Lighting and Receptacles - Hotel 0.0 kVA 0.0 kVA Design Current: 57.6 A Elevator 0.0 kVA 0.0 kVA Design Load: 13.8 kVA Motor 0.0 kVA 0.0 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 46.0 A Heating 9.3 kVA 9.3 kVA Total Connected Current: 45.8 A Cooling 0.0 kVA 0.0 kVA Total Estimated Demand Load: 11.1 kVA Lighting 0.2 kVA 0.3 kVA Total Connected Load: 11.0 kVA Receptacles 1.4 kVA 1.4 kVA Load Classification Connected Load Estimated Demand Panel Totals

-PROVIDE SPD AS SPECIFIED.

7.9 kVA 3.1 kVA

41 0.0 0.0 42 -- -- SPACE ONLY --

SPD 30 A 2

39 0.0 0.0 40 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 37 0.0 0.0 38 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 35 0.0 0.0 36 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 33 0.0 0.0 34 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 31 0.0 0.0 32 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 29 0.0 0.0 30 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 27 0.0 0.0 28 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 25 0.0 0.0 26 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 23 0.0 0.0 24 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 21 0.0 0.0 22 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 19 0.0 0.0 20 -- -- SPACE ONLY --

SPARE 20 A 1 17 0.0 0.0 18 1 20 A SPARE

SPARE 20 A 1 15 0.0 0.0 16 1 20 A SPARE

SPARE 20 A 1 13 0.0 0.0 14 1 20 A SPARE

SPARE 20 A 1 11 0.0 0.0 12 1 20 A SPARE

REC RM B301 20 A 1 9 1.1 0.4 10 1 20 A REC EXTERIOR

LTG RM B301 20 A 1 7 0.3 0.1 8 1 20 A B-1

P-3 25 A 1 5 1.8 1.8 6 1 25 A P-4

3 1.4 1.4 4 P-1 20 A 2

1 1.4 1.4 2 2 20 A P-2

DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION

Mounting: SURFACE Sections: 1

Wire: 3 AIC Rating: 22,000 A

Phase: 1 Main: MLO

Voltage: 120/240 Amp Rating: 100 A

Panelboard: B3.1

Other 0.1 kVA 0.1 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 0.0 kVA 0.0 kVA Lighting and Receptacles - Hotel 2.5 kVA 1.3 kVA Design Current: 39.3 A Elevator 0.0 kVA 0.0 kVA Design Load: 9.4 kVA Motor 0.7 kVA 0.9 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 31.4 A Heating 0.0 kVA 0.0 kVA Total Connected Current: 35.6 A Cooling 0.0 kVA 0.0 kVA Total Estimated Demand Load: 7.5 kVA Lighting 0.4 kVA 0.5 kVA Total Connected Load: 8.5 kVA Receptacles 4.9 kVA 4.9 kVA Load Classification Connected Load Estimated Demand Panel Totals

-PROVIDE SPD AS SPECIFIED.

5.0 kVA 3.5 kVA

41 0.0 0.0 42 -- -- SPACE ONLY --

SPD 30 A 2

39 0.0 0.0 40 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 37 0.0 0.0 38 -- -- SPACE ONLY --

-- SPACE ONLY -- -- 35 0.0 0.0 36 -- -- SPACE ONLY --

SPARE 20 A 1 33 0.0 0.0 34 1 20 A SPARE

SPARE 20 A 1 31 0.0 0.0 32 1 20 A SPARE

SPARE 20 A 1 29 0.0 0.0 30 1 20 A SPARE

SPARE 20 A 1 27 0.0 0.0 28 1 20 A SPARE

SPARE 20 A 1 25 0.0 0.0 26 1 20 A SPARE

SPARE 20 A 1 23 0.0 0.0 24 1 20 A SPARE

SPARE 20 A 1 21 0.0 0.8 22 1 20 A LTG RM B101A,B101B; EF-4

19 0.3 0.8 20 1 20 A AUTO DOOR OPEN

EXISTING WALL HEATER RM 111 20 A 2

17 0.3 0.2 18 1 20 A B1 DOOR OPEN ALARM

15 0.3 0.2 16 1 20 A REC RM 111

EXISTING WALL HEATER RM 110 20 A 2

13 0.3 0.7 14 1 20 A REC RM 107

REC RM 105A 20 A 1 11 0.2 1.1 12 1 20 A REC RM 106

A REC RM 105 20 A 1 9 0.6 0.3 10 1 20 A LTG LEVEL B1

REC RM 103A 20 A 1 7 0.2 0.2 8 1 20 A REC RM 104A

A REC RM 103 20 A 1 5 0.4 0.5 6 1 20 A REC RM 104 A

REC RM 101A 20 A 1 3 0.2 0.2 4 1 20 A REC RM 102A

A REC RM 101 20 A 1 1 0.5 0.6 2 1 20 A REC RM 102 A

DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION

Mounting: RECESSED Sections: 1

Wire: 3 AIC Rating: 10,000 A

Phase: 1 Main: MLO

Voltage: 120/240 Amp Rating: 100 A

Panelboard: B1.1

PANEL 'B1.1' PANEL 'B3.1'

(BLANK) (BLANK)

E0.04

2 BARRIER POST LAYOUT DETAIL

E0.04

3 BARRIER POST DETAIL

This document has been digitally signed and sealed by

William S. Phillips, PE

OR PE #94068

Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.

Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:01:10-04'00'

G - PROVIDE GROUND FAULT CIRCUIT INTERRUPTER (GFCI).

H - PROVIDE HANDLE CLAMP DEVICE.

A - PROVIDE ARC FAULT CIRCUIT INTERRUPTER (AFCI).

M - PROVIDE CT FOR METERING SYSTEM AND CONNECTED TO

METER INDICATED ON THE METERING SCHEDULE.

BRANCH CIRCUIT

PANEL

LIGHTING CONTROL PANEL 'LCPB2'.

PROVIDE 120V POWER FOR PANEL.

TIME

CLOCK

EXTERIOR

LUMINAIRES

PHOTOCELL 'ON'

ASTRONOMICAL

TIME CLOCK 'OFF'

TO

CONTROL

LIGHTING

LOADS

LIGHTING CONTROL PANEL. CIRCUIT

BREAKER TYP.

120V POWER FROM

PANEL. SEE PANEL

SCHEDULES FOR

CIRCUIT.

LOW VOLTAGE

SWITCHES AS

SHOWN ON PLANS

RELAY, QUANTITY AS

SCHEDULED

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OFOREGON CAVES NATIONAL MONUMENT

OREGON CAVES CHATEAU

138578

150025

R E

V

IT

/1

/2

:5

:3

P

M C

U s e rs

\p d a v is

\D o c u m e n ts \O

R C

A

M E

P -C e n tr a l_ p d a v is

.r v t

SM

MJL

CvB, WSP

09/13/19

ELECTRICAL PANEL

SCHEDULES

E0.05 193 211

CONSTRUCTION DOCUMENTS

E .0

M

J L

Other 0.3 kVA 0.3 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 0.0 kVA 0.0 kVA Lighting and Receptacles - Hotel 7.1 kVA 3.5 kVA Design Current: 66.8 A Elevator 0.0 kVA 0.0 kVA Design Load: 16.0 kVA Motor 0.5 kVA 0.6 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 53.4 A Heating 0.0 kVA 0.0 kVA Total Connected Current: 66.5 A Cooling 0.0 kVA 0.0 kVA Total Estimated Demand Load: 12.8 kVA Lighting 1.3 kVA 1.7 kVA Total Connected Load: 16.0 kVA Receptacles 6.3 kVA 6.3 kVA Load Classification Connected Load Estimated Demand Panel Totals

-PROVIDE SPD AS SPECIFIED.

8.4 kVA 7.5 kVA

53 0.0 0.0 54 1 20 A SPARE

SPD 30 A 2

51 0.0 0.0 52 1 20 A SPARE

SPARE 20 A 1 49 0.0 0.0 50 1 20 A SPARE

SPARE 20 A 1 47 0.0 0.0 48 1 20 A SPARE

SPARE 20 A 1 45 0.0 0.0 46 1 20 A SPARE

SPARE 20 A 1 43 0.0 0.0 44 1 20 A SPARE

SPARE 20 A 1 41 0.0 0.1 42 1 20 A LTG RM 201-215

SPARE 20 A 1 39 0.0 0.0 40 1 20 A LTG RM 101-105

LTG RM 200C,200D 20 A 1 37 0.0 0.6 38 1 20 A LTG CORRIDOR LEVEL 1

LTG LEVEL 3 - EMERGENCY 20 A 1 35 0.1 0.5 36 1 20 A MOTORIZED DOOR

LTG LEVEL 2 - EMERGENCY 20 A 1 33 0.2 0.2 34 1 20 A LTG CORRIDOR LEVEL 3

LTG LEVEL 1 - EMERGENCY 20 A 1 31 0.1 0.2 32 1 20 A LTG CORRIDOR LEVEL 2

REC STAIRS 20 A 1 29 0.7 0.7 30 1 20 A REC RM 111

REC RM 109 20 A 1 27 0.9 0.9 28 1 20 A REC RM 110

REC RM 108,109 20 A 1 25 1.1 0.2 26 1 20 A REC RM 214A

A REC RM 215 20 A 1 23 0.6 0.6 24 1 20 A REC RM 214 A

REC RM 211A 20 A 1 21 0.2 0.2 22 1 20 A REC RM 212A

A REC RM 211 20 A 1 19 0.5 0.5 20 1 20 A REC RM 212 A

REC RM 209A 20 A 1 17 0.2 0.2 18 1 20 A REC RM 210A

A REC RM 209 20 A 1 15 0.5 0.5 16 1 20 A REC RM 210 A

A REC RM 207 20 A 1 13 0.4 0.4 14 1 20 A REC RM 208 A

REC RM 205A 20 A 1 11 0.4 0.4 12 1 20 A REC RM 206A

A REC RM 205 20 A 1 9 0.4 0.4 10 1 20 A REC RM 206 A

REC RM 203A 20 A 1 7 0.2 0.2 8 1 20 A REC RM 204A

A REC RM 203 20 A 1 5 0.5 0.5 6 1 20 A REC RM 204 A

REC RM 201A 20 A 1 3 0.2 0.2 4 1 20 A REC RM 202A

A REC RM 201 20 A 1 1 0.5 0.5 2 1 20 A REC RM 202 A

DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION

Mounting: RECESSED Sections: 1

Wire: 3 AIC Rating: 10,000 A

Phase: 1 Main: MLO

Voltage: 120/240 Amp Rating: 100 A

Panelboard: 2.1

Other 0.0 kVA 0.0 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 0.0 kVA 0.0 kVA Lighting and Receptacles - Hotel 5.2 kVA 2.6 kVA Design Current: 36.7 A Elevator 0.0 kVA 0.0 kVA Design Load: 8.8 kVA Motor 0.0 kVA 0.0 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 29.3 A Heating 0.0 kVA 0.0 kVA Total Connected Current: 39.9 A Cooling 0.0 kVA 0.0 kVA Total Estimated Demand Load: 7.0 kVA Lighting 0.3 kVA 0.4 kVA Total Connected Load: 9.6 kVA Receptacles 4.1 kVA 4.1 kVA Load Classification Connected Load Estimated Demand Panel Totals

-PROVIDE SPD AS SPECIFIED.

6.1 kVA 3.4 kVA

41 0.0 0.0 42 -- -- SPACE ONLY --

SPD 30 A 2

39 0.0 0.0 40 1 20 A SPARE

SPARE 20 A 1 37 0.0 0.0 38 1 20 A SPARE

SPARE 20 A 1 35 0.0 0.0 36 1 20 A SPARE

SPARE 20 A 1 33 0.0 0.0 34 1 20 A SPARE

SPARE 20 A 1 31 0.0 0.0 32 1 20 A SPARE

SPARE 20 A 1 29 0.0 0.0 30 1 20 A SPARE

DOOR OPEN ALARM CORRIDOR 20 A 1 27 1.0 0.0 28 1 20 A DOOR HOLD CORR 300

A REC CORRIDOR,RM 300C 20 A 1 25 0.5 0.0 26 1 20 A DOOR HOLD RM 200

REC RM 311A 20 A 1 23 0.2 0.2 24 1 20 A LTG RM 301-312

A REC RM 311 20 A 1 21 0.8 0.6 22 1 20 A REC RM 312A

REC RM 309A 20 A 1 19 0.2 0.4 20 1 20 A REC RM 312A

A REC RM 309 20 A 1 17 0.4 0.0 18 1 20 A REC RM 312 A

REC RM 307A 20 A 1 15 0.2 0.2 16 1 20 A REC RM 310 A

A REC RM 307 20 A 1 13 0.4 0.5 14 1 20 A REC RM 310 A

REC RM 305A 20 A 1 11 0.2 0.2 12 1 20 A REC RM 306 A

A REC RM 305 20 A 1 9 0.8 0.2 10 1 20 A REC RM 306 A

A REC RM 303 20 A 1 7 0.2 0.2 8 1 20 A REC RM 304 A

A REC RM 303 20 A 1 5 1.1 0.0 6 1 20 A REC RM 304 A

A REC RM 301 20 A 1 3 0.2 0.2 4 1 20 A REC RM 302A

A REC RM 301 20 A 1 1 0.4 0.3 2 1 20 A REC RM 302 A

DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION

Mounting: RECESSED Sections: 1

Wire: 3 AIC Rating: 10,000 A

Phase: 1 Main: MLO

Voltage: 120/240 Amp Rating: 100 A

Panelboard: 3.1

PANEL '2.1' PANEL '3.1'

(BLANK) (BLANK)

D EXHAUST FAN EF-4 SHALL TURN 'ON' WITH B101A AND/OR B101B. EF-4 SHALL REMAIN ON AS LONG AS ONE OR BOTH OF THE SPACES, B101A AND

B101B, ARE IN USE. EF-4 SHALL TURN OFF WHEN B101A AND B101B ARE BOTH OFF.

C EXTERIOR EMERGENCY LUMINAIRES SHALL BE NORMALLY 'OFF' AND SHALL TURN 'ON' WITH LOSS OF NORMAL POWER OR WHEN THERE IS AN

AUXILIARY INPUT SIGNAL TO LIGHTING CONTROL PANEL FROM FIRE ALARM.

B LUMINAIRES CONTROLLED BY PHOTOCELL SHALL TURN 'ON' AT DUSK AND 'OFF' AT MIDNIGHT (OR AS DIRECTED BY THE OWNER). MANUAL OVERRIDE SWITCH LOCATED BEHIND THE LEVEL 1 RECEPTION DESK SHALL OVERRIDE FUNCTIONALITY FOR A MAXIMUM OF TWO HOURS.

A LUMINAIRES SHALL BE CONTROLLED BY MANUAL LOW VOLTAGE SWITCH LOCATED BEHIND LEVEL 1 RECEPTION DESK. ALL LUMINAIRES SHALL BE 'ON' WHEN THERE IS AUXILIARY INPUT SIGNAL TO LIGHTING CONTROL PANEL FROM FIRE ALARM REGARDLESS OF SWITCH POSITION.

SEQUENCE OF OPERATION*

20 SPARE - -

19 SPARE - -

18 SPARE - -

17 SPARE - -

16 SPARE - -

15 SPARE - -

14 SPARE - -

13 B101B B1.1-22 D

12 B101A B1.1-22 D

11 EF-4 B1.1-22 D

10 EXTERIOR EMERGENCY 2.1-33 C

9 EXTERIOR EMERGENCY 2.1-31 C

8 EXTERIOR EMERGENCY B2.1-2 C

7 EXTERIOR B2.2-15 B

6 EXTERIOR B2.2-13 B

5 EXTERIOR B2.2-11 B

4 EXTERIOR B2.2-9 B

3 CORRIDOR 3 2.1-34 A

2 CORRIDOR 2 2.1-32 A

1 CORRIDOR 1 2.1-38 A

AREA CIRCUIT NUMBER SOO*

LIGHTING CONTROL PANEL 'LCPB2'

E0.05

2 LIGHTING CONTROL PANEL SCHEMATIC

This document has been digitally signed and sealed by

William S. Phillips, PE

OR PE #94068

Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.

Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:01:03-04'00'

NOTES: 1. CONTRACTOR SHALL CONFIRM EXACT SIZE, LOCATION AND WIRING REQUIREMENTS OF ALL MECHANICAL EQUIPMENT PRIOR TO INSTALLATION.

2. CONTRACTOR SHALL REVIEW DIVISION 21, 22 & 23 DRAWINGS AND SPECIFICATION TO ENSURE LOCATIONS AND QUANTITIES ARE CORRECT.

3. SINGLE SPEED STARTERS SHALL INCLUDE AN HOA POSITION SWITCH, PILOT LIGHT, AND 120 VAC CONTROL CIRCUIT.

4. CONTROL PANELS ARE SHIPPED LOOSE AND REQUIRE FIELD WIRING BY DIVISION 26.

5. PCS EQUIPMENT REQUIRES A SINGLE SOURCE ELECTRICAL CONNECTION. ANY INTERLOCKING WIRING SHALL BE FURNISHED UNDER DIVISION 23.

6. ALL FIRE ALARM DEVICES WIRED BY DIVISION 28.

7. PROVIDE EMERGENCY SHUTDOWN FOR ALL BOILERS AT DOOR TO BOILER ROOM

8. PROVIDE 120 VOLT RECEPTACLE ON A DEDICATED CIRCUIT FOR ALL DDC PANELS. CONFIRM QUANTITIES AND LOCATIONS WITH DIVISION 23

(A) ABBREVIATIONS: E = DIVISION 26

M =DIVISION 23

O = THE CONTRACTOR OFFICER

K = KITCHEN CONTRACTOR

(B) STARTER TYPE: HOA = HAND-OFF-AUTO SWITCH

MS = MANUAL STARTER

CO = COMBINATION STARTER (HOA)

CO2 = 2-SPEED COMBINATION STARTER

VFD = VARIABLE FREQUENCY DRIVE

MRR = MOTOR RATED RELAY (24 VAC COIL AND MS)

PCS = PACKAGED CONTROL SYSTEM

(C) CONTROL TYPE: BA = BUILDING AUTOMATION SYSTEM

PCS = PACKAGED CONTROL SYSTEM

ES = END SWITCH

LT = LINE VOLTAGE THERMOSTAT

FS = FLOW SWITCH

GS = GAS SENSOR

H = HUMIDITY SENSOR

I = INTERLOCK

LS = LEVEL SWITCH

PS = PRESSURE SWITCH

TC = TIME CLOCK

(C) CONTROL TYPE: T = THERMOSTAT

VS = VARIABLE SPEED SWITCH

WS = WALL SWITCH

RT = REVERSE ACTING THERMOSTAT

FCCF = FIREFIGHTERS CENTRAL

CONTROL FACILITY

FA = FIRE ALARM SYSTEM

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OFOREGON CAVES NATIONAL MONUMENT

OREGON CAVES CHATEAU

138578

150025

R E

V

IT

/1

/2

:5

:4

P

M C

U s e rs

\p d a v is

\D o c u m e n ts \O

R C

A

M E

P -C e n tr a l_ p d a v is

.r v t

SM

MJL

CvB, WSP

09/13/19

ELECTRICAL SCHEDULES

E0.06 194 211

CONSTRUCTION DOCUMENTS

E .0

M

J L

MECHANICAL EQUIPMENT SCHEDULE

MECH. EQ. TAG

SYSTEM

DESCRIPTION LOCATION COUNT POWER FLA

SYSTEM

VOLTAGE MOCP POLES PANEL

CIRCUIT

NUMBER CONDUCTORS REMARKS

EF-2 EXAUST FAN BATHROOM

B204A

1 0.3 kVA 4.4 A 120 V 20.0 A 1 B2.1 4 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND INTERLOCKED WITH WASHROOM LIGHT SWITCH. REFER TO DETAIL 3/E6.01

EF-3 EXAUST FAN BATHROOM

B204B

1 0.3 kVA 4.4 A 120 V 20.0 A 1 B2.1 6 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND INTERLOCKED WITH WASHROOM LIGHT SWITCH. REFER TO DETAIL 3/E6.01

EF-4 EXAUST FAN BATHROOM

B101A/B101B

1 0.7 kVA 5.8 A 120 V 20.0 A 1 B1.1 22 3/4" C WITH 2 - #10 AWG + #12 AWG GROUND CONTROLLED THROUGH LIGHTING CONTROL PANEL. REFER TO RELAY-BASED LIGHTING

CONTROL PANEL SCHEDULE ON SHEET E0.05 FOR SEQUENCE OF OPERATION.

EF-5 EXAUST FAN BATHROOM

206A

1 0.3 kVA 4.0 A 120 V 20.0 A 1 2.1 12 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND INTERLOCKED WITH WASHROOM LIGHT SWITCH. REFER TO DETAIL 3/E6.01

EF-6 EXAUST FAN BATHROOM

205A

1 0.3 kVA 4.0 A 120 V 20.0 A 1 2.1 11 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND INTERLOCKED WITH WASHROOM LIGHT SWITCH. REFER TO DETAIL 3/E6.01

EF-7 EXAUST FAN ELEVATOR

MACHINE RM

1 0.3 kVA 4.4 A 120 V 20.0 A 1 B2.1 20 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND

EF-8 EXAUST FAN LAUNDRY

B209B

1 0.3 kVA 4.4 A 120 V 20.0 A 1 B2.1 22 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND

EXISTING TO-REMAIN

FAN COIL

FAN COIL SERVICE

ENTRY B209

1 4.0 kVA 0.0 A 240 V 40.0 A 2 B2.2 34,36 3/4" C WITH 2 - #8 AWG + #10 AWG GROUND

EXISTING TO-REMAIN

FAN COIL

FAN COIL STAFF

DINING B208

1 4.0 kVA 0.0 A 240 V 40.0 A 2 FVDP 5,7 3/4" C WITH 2 - #8 AWG + #10 AWG GROUND

EXISTING TO-REMAIN

HOOD FAN

HOOD FAN STAFF

KITCHEN

B208B

1 0.5 kVA 4.2 A 120 V 20.0 A 1 B2.2 33 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND

EXISTING TO-REMAIN

SUPPLY AIR

SUPPLY FAN STAFF

KITCHEN

B208B

1 0.5 kVA 4.2 A 120 V 20.0 A 1 B2.2 39 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND

EXISTING-TO-REMAIN

FAN COIL

FAN COIL COFFEE

SHOP

B104/GIFT

SHOP B101

2 0.5 kVA 4.2 A 120 V 20.0 A 1 FVDP 12 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND

KEF-1 EXAUST FAN KITCHEN

B103

1 6.4 kVA 31.0 A 240 V 60.0 A 2 FVDP 2,4 1" C WITH 2 - #8 AWG + #10 AWG GROUND

P-1 HOT WATER

PUMP

MECHANICAL

ROOM B301

1 2.8 kVA 15.0 A 240 V 20.0 A 2 B3.1 1,3 3/4" C WITH 2 - #8 AWG + #10 AWG GROUND

P-2 HOT WATER

PUMP

MECHANICAL

ROOM B301

1 2.8 kVA 15.0 A 240 V 20.0 A 2 B3.1 2,4 3/4" C WITH 2 - #8 AWG + #10 AWG GROUND

P-3 HOT WATER

PUMP

MECHANICAL

ROOM B301

1 1.8 kVA 20.0 A 120 V 25.0 A 1 B3.1 5 3/4" C WITH 2 - #8 AWG + #10 AWG GROUND

P-4 HOT WATER

PUMP

MECHANICAL

ROOM B301

1 1.8 kVA 20.0 A 120 V 25.0 A 1 B3.1 6 3/4" C WITH 2 - #8 AWG + #10 AWG GROUND

SP-1 ELEVATOR

SUMP

ELEVATOR

PIT

1 2.4 kVA 20.0 A 120 V 40.0 A 1 B2.3 6 3/4" C WITH 2 - #10 AWG + #10 AWG GROUND

MECH. EQ. TAG STARTER - TYPE

START -

SUPPLIED BY

STARTER -

INSTALLED BY

STARTER -

WIRED BY

DISCONNECT -

SUPPLIED BY

DISCONNECT -

INSTALLED BY

DISCONNECT -

WIRED BY

CONTROLS -

TYPE

CONTROLS -

SUPPLIED BY

CONTROLS -

INSTALLED BY CONTROLS - WIRED BY

EF-2 MS E E E E E E WS E E E

EF-3 MS E E E E E E WS E E E

EF-4 MS E E E E E E WS E E E

EF-5 MS E E E E E E WS E E E

EF-6 MS E E E E E E WS E E E

EF-7 MS E E E E E E LT E E E

EF-8 MS E E E E E E WS E E E

EXISTING TO-REMAIN FAN COIL MS EXISTING E E EXISTING E E BA M M M

EXISTING TO-REMAIN FAN COIL MS EXISTING E E EXISTING E E BA M M M

EXISTING TO-REMAIN HOOD FAN MS EXISTING E E EXISTING E E BA M M M

EXISTING TO-REMAIN SUPPLY AIR MS EXISTING E E EXISTING E E BA M M M

EXISTING-TO-REMAIN FAN COIL MS EXISTING E E EXISTING E E BA M M M

KEF-1 MS EXISTING E E EXISTING E E WS M M M

P-1 CO M E E E E E BA M M M

P-2 CO M E E E E E BA M M M

P-3 CO M E E E E E BA M M M

P-4 CO M E E E E E BA M M M

SP-1 CO M E E E E E LS M M E

This document has been digitally signed and sealed by

William S. Phillips, PE

OR PE #94068

Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.

Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:00:54-04'00'

SHEET NOTES

1. MATCH EXISTING LUMINAIRE MOUNTING HEIGHTS.

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OFOREGON CAVES NATIONAL MONUMENT

OREGON CAVES CHATEAU

138578

150025

R E

V

IT

/1

/2

:5

:4

P

M C

U s e rs

\p d a v is

\D o c u m e n ts \O

R C

A

M E

P -C e n tr a l_ p d a v is

.r v t

SM

MJL

CvB, WSP

09/13/19

ELECTRICAL SCHEDULES

E0.07 195 211

CONSTRUCTION DOCUMENTS

E .0

M

J L

LUMINAIRE SCHEDULE

TAG DESCRIPTION MANUFACTURER VOLTAGE

LAMP

TYPE POWER

INITIAL

ILLUMINANCE

INITIAL COLOR

TEMPERATURE REMARKS

WALL OR CEILING MOUNTED PLASTIC EDGE LIT EXIT SIGN WITH INTEGRAL BATTERY

BACK-UP, SELF-DIAGNOSTICS, AND CLEAR LETTERS ON GREEN BACKGROUND

LITHONIA PRECISE LRP-BZ-GC-120/240-ELN SERIES;

SURE-LITES EUX SERIES;

EMERGI-LITE PRESTIGE EDGE-LIT SERIES OR APPROVED

EQUAL

120 V LED 0 lm LUMINAIRE WITH GREEN LETTERS SHALL COMPLY WITH IBC-2015 SECTION 1013.6. CONTRACTOR SHALL CONFIRM COLOR WITH SERVING FIRE DEPARTMENT. PROVIDE DIRECTIONAL INDICATORS AS SHOWN ON

PLANS. PROVIDE GMR (GREEN MIRROR) FOR DOUBLE-FACE EXIT SIGNS AS SHOWN ON PLANS.

H1 EXISTING PADDLE FAN/LIGHT 120 V LED 10 W 800 lm 3000 K RETROFIT WITH NEW LED - SATCO 9.8A19/OMNI/220/LED/30K OR APPROVED EQUAL. 1 LAMP PER FIXTURE.

H2 EXISTING PENDANT 120 V LED 15 W 1600 lm 3000 K RETROFIT WITH NEW LED SCREW-IN LAMPS WITH EDISON BASE - SATCO 15A19/LED/3000K/1600L/120/D OR

APPROVED EQUAL. 1 LAMP PER FIXTURE.

H3 EXISTING INTERIOR WALL SCONCE 120 V LED 8 W 800 lm 3000 K RELAMP WITH LED EQUIVALENT - CLEAR LED FILAMENT CHANDELIER BULB, FLAME TIP, 4 WATT, 2700K. 1

LAMP PER FIXTURE.

H4 EXISTING EXTERIOR WALL SCONCE 120 V LED 10 W 800 lm 3000 K RELAMP WITH LED EQUIVALENT - SATCO 9.8A19/OMNI/220/LED/30K OR APPROVED EQUAL. 1 LAMP PER

FIXTURE.

H5 EXISTING LINEAR 120 V LED 17 W 2000 lm 3000 K RELAMP WITH LED EQUIVALENT - PHILIPS 9290012811 OR APPROVED EQUAL. 4 4' LONG T8 LAMPS PER

FIXTURE.

H6 EXISTING TRACK LIGHT 120 V LED 6 W 500 lm 3000 K RETROFIT WITH NEW LED SCREW-IN LAMPS WITH EDISON BASE - SATCO 9.8A19/OMNI/220/LED/30K OR

APPROVED EQUAL. 1 LAMP PER FIXTURE.

H7 EXISTING BATHROOM MIRROR LIGHT 120 V LED 10 W 800 lm 3000 K RETROFIT WITH NEW LED - SATCO 9.8A19/OMNI/220/LED/30K OR APPROVED EQUAL. 1 LAMP PER FIXTURE.

H8 EXISTING SURFACE DOWNLIGHT 120 V LED 10 W 800 lm 3000 K RETROFIT WITH NEW LED - SATCO 9.8A19/OMNI/220/LED/30K OR APPROVED EQUAL. 1 LAMP PER FIXTURE.

H9 EXISTING 8' LINEAR 120 V LED 17 W 2000 lm 3000 K RELAMP WITH LED EQUIVALENT - PHILIPS 9290012811 OR APPROVED EQUAL. PROVIDE NEW ACRYLIC SHIELDING COVER AT ANY FIXTURES WITH EXPOSED LAMPS. 4 8' LONG T8 LAMPS PER FIXTURE.

H10 EXISTING INTERIOR SURFACE DOWNLIGHT 120 V LED 10 W 800 lm 3000 K RETROFIT WITH NEW LED EQUVALENT - SATCO 9.8A19/OMNI/220/LED/30K OR APPROVED EQUAL. 1 LAMP

PER FIXTURE.

H11 EXISTING EXTERIOR DOWNLIGHT 120 V LED 10 W 800 lm 3000 K RETROFIT WITH NEW LED EQUVALENT - SATCO 9.8A19/OMNI/220/LED/30K OR APPROVED EQUAL. 1 LAMP

PER FIXTURE.

L1 SUSPENDED DIRECT FIXTURE WITH FROSTED LENSE, WHITE FINISH CORELITE HUGO SERIES;

DAY-BRITE FLUXSTREAM STRIP SERIES;

PHILIPS SMARTBRIGHT SUSPENSION SERIES

120 V LED 23 W 3000 lm 3000 K

L2 WALL SCONCE WITH DOMED TURTLE SHADE, OPAL, WITH POLISHED NICKEL CANOPY. SCHOOLHOUSE ELECTRIC OTIS 2.25" SCONCE SERIES 120 V LED 8 W 800 lm 3000 K PROVIDE MEDIUM BASE, LED LAMP

L3 PENDANT LAMP, WHITE BLOWN GLASS, 12" LONG SUSPENSION CABLE FABBIAN - AEROSTAT 120 V LED 17 W 1800 lm 3000 K

L4 CUSTOM LIGHT FIXTURE TO MATCH EXISTING LUMINAIRE TYPE H10 CUSTOM FIXTURE. SEE DETAIL 5/A8.11 120 V LED 8 W 800 lm 3000 K PROVIDE MEDIUM BASE, LED LAMP

L5 CUSTOM LIGHT FIXTURE TO MATCH EXISTING LUMINAIRE TYPE H4 CUSTOM FIXTURE. SEE DETAIL 5/A8.11 120 V LED 8 W 800 lm 3000 K PROVIDE MEDIUM BASE, LED LAMP

L6 4' LONG LINEAR SURFACE MOUNT, EXTRUDED ALUMINUM HOUSING, DIE-CAST

ALUMINUM END PLATES, ELECTROSTICALLY APPLIED POLYESTER POWDER COAT

WHITE PAINT FINISH. FROSTED LENS.

CORELITE HGL-HUGO LINEAR DIRECT SERIES;

DAY-BRITE FLUXSTREAM STRIP SERIES;

COOPER INDUSTRIES SNLED SERIES OR APPROVED EQUAL

120 V LED 23 W 3000 lm 3000 K

L7 SURFACE MOUNT WITH DRUM SHADE, GLASS, MATTE BRONZE FINISH SCHOOLHOUSE ELECTRIC OTIS 4" 120 V LED 8 W 800 lm 3000 K PROVIDE MEDIUM BASE, LED LAMP

L8 SURFACE MOUNT WITH DRUM GLASS SHADE, OPAL GLASS, POLISHED NICKEL FINISH SCHOOLHOUSE ELECTRIC OTIS 4" 120 V LED 8 W 800 lm 3000 K

L9 SURFACE MOUNT WITH JAR GLASS SHADE, OPAL GLASS, MATTE BRONZE FINISH SCHOOLHOUSE ELECTRIC OTIS 4" 120 V LED 8 W 800 lm 3000 K

L10 WALL MOUNTED ADJUSTABLE ACCENT FLOOD WITH ONE HEAD AND BRONZE FINISH LITHONIA WST LED-P2-27K-*-120-E20WC-DDBTXD 120 V LED 25 W 3000 lm 3000 K

RM1 WHITE PATHWAY FLOOD WITH TWO HEADS WITH 5.4 WATT LINEAR PATTERN LAMPS

AND SELF-DIAGNOSTICS

LITHONIA ELMLT-*-LP06VS-LTP-HO;

EMERGI-LITE EL-2RHL SERIES;

SURE-LITES SEL17 SERIES OR APPROVED EQUAL

120 V LED 5 W 1000 lm 3200 K

RM2 COMPACT, CONCEALED WHITE PATHWAY FLOOD WITH TWO HEADS C/W SELF

CONTAINED BATTERY CAPABLE OR OPERATING 90 MIN MINIMUM

CONCEALITE F5000-LED8-90-SD-RB-NC-CF;

EMERGI-LITE REVELATION BATTERY SERIES;

MULE-LIGHTING COVERT SERIES

120 V LED 8 W 1000 lm 3200 K CUSTOM FINISH TO MATCH ADJACENT WALL SURFACE.

TAG DESCRIPTION Image

H9 EXISTING 8' LINEAR

H10 EXISTING INTERIOR SURFACE DOWNLIGHT

TAG DESCRIPTION Image

H4 EXISTING EXTERIOR WALL SCONCE

H5 EXISTING LINEAR

H7 EXISTING BATHROOM MIRROR LIGHT

H8 EXISTING SURFACE DOWNLIGHT

TAG DESCRIPTION Image

H1 EXISTING PADDLE FAN/LIGHT

H2 EXISTING PENDANT

H3 EXISTING INTERIOR WALL SCONCE

This document has been digitally signed and sealed by

William S. Phillips, PE

OR PE #94068

Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.

Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:00:48-04'00'

ALL NEW EQUIPMENT AND OVER CURRENT DEVICES SHALL

EXCEED THE SHORT CIRCUIT INTERRUPTING CAPACITY

INDICATED ON THE SINGLE LINE DIAGRAM.

CONRACTOR SHALL PROVIDE THE FOLLOWING:

• REMOVE THE EXISTING SECONDARY CONDUCTORS

FROM THE EXISTING-TO-REMAIN SECONDARY

DUCTBANK.

• INTERCEPT EXISTING SERVICE ENTRANCE CONDUIT

DOWNSTREAM OF THE EXISTING METERING CABINET.

PROVIDE AND INSTALL CONDUIT TO BRING EXISTING

PATHWAYS TO THE NEW LOCATION OF THE MAIN

DISTRIBUTION PANEL (MDP).

• PROVIDE NEW SERVICE ENTRANCE EQUIPMENT AS

INDICATED HEREIN.

REPLACE EXISTING MANUAL TRANSFER SWITCH WITH NEW,

MATCHING AMPERAGE, VOLTAGE AND SHORT CIRCUIT

INTERRUPTING RATING AS INDICATED ON THE SINGLE LINE

DIAGRAM.

GENERAL NOTES

1.

2.

3.

ELECTRICAL FEEDER SCHEDULE

PRIMARY

NUMBER

SECONDARY LETTER

A (CU, 1-PHASE, 2-WIRE)

2-#12 AWG 3/4" 4-#12 AWG 1-#12 AWG3/4"

2-#10 AWG 3/4" 4-#10 AWG 1-#10 AWG3/4"

2-#8 AWG 3/4" 4-#8 AWG 1-#10 AWG1"

2-#6 AWG 3/4" 4-#6 AWG 1-#8 AWG1"

2-#4 AWG 1" 4-#4 AWG 1-#8 AWG1"

2-#3 AWG 1" 4-#3 AWG 1-#6 AWG1-1/4"

2-#2 AWG 1" 4-#2 AWG 1-#6 AWG1-1/4"

2-#1 AWG 1-1/4" 4-#1 AWG 1-#6 AWG1-1/2"

2-1/0 AWG 1-1/4" 4-1/0 AWG 1-#6 AWG2"

2-2/0 AWG 1-1/2" 4-2/0 AWG 1-#6 AWG2"

2-3/0 AWG 1-1/2" 4-3/0 AWG 1-#4 AWG2"

2-4/0 AWG 2" 4-4/0 AWG 1-#4 AWG2-1/2"

2-250 MCM 2" 4-250 MCM 1-#4 AWG3"

2-300 MCM 2-1/2" 4-300 MCM 1-#4 AWG3"

2-350 MCM 2-1/2" 4-350 MCM 1-#3 AWG3"

2-400 MCM 2-1/2" 4-400 MCM 1-#3 AWG3"

2-500 MCM 3" 4-500 MCM 1-#3 AWG3-1/2"

2-600 MCM 3" 4-600 MCM 1-#2 AWG4"

2-750 MCM 3-1/2" 4-750 MCM 1-#2 AWG4"

2-1000 MCM 4" 4-1000 MCM 1-#1 AWG4"

1-#10 AWG

1-#8 AWG

1-#8 AWG

1-#6 AWG

1-#6 AWG

1-#6 AWG

1-#4 AWG

1-#4 AWG

1-#4 AWG

1-#3 AWG

1-#3 AWG

1-#2 AWG

1-#1 AWG

1-#1 AWG

1-#1/0 AWG

1-#1/0 AWG

1-#1/0 AWG

1-#2/0 AWG

1-#2/0 AWG

1-#3/0 AWG

(2 RUNS)

1-#8 AWG

1-#6 AWG

1-#6 AWG

1-#4 AWG

1-#3 AWG

1-#3 AWG

1-#2 AWG

1-#1 AWG

1-#1 AWG

1-#1/0 AWG

1-#1/0 AWG

1-#2/0 AWG

1-#3/0 AWG

1-#3/0 AWG

1-#4/0 AWG

1-#4/0 AWG

1-#4/0 AWG

1-#250 MCM

1-#250 MCM

1-#350 MCM

PARALLEL FEEDER

EQUIPMENT

GROUND (CU)

SINGLE FEEDER

EQUIPMENT

GROUND (CU)

(4 RUNS)(1 RUN)CONDUCTORS CONDUIT

B (CU, 1-PHASE, 3-WIRE)

3-#12 AWG 3/4"

3-#10 AWG 3/4"

3-#8 AWG 3/4"

3-#6 AWG 1"

3-#4 AWG 1"

3-#3 AWG 1-1/4"

3-#2 AWG 1-1/4"

3-#1 AWG 1-1/2"

3-1/0 AWG 1-1/2"

3-2/0 AWG 2"

3-3/0 AWG 2"

3-4/0 AWG 2"

3-250 MCM 2-1/2"

3-300 MCM 2-1/2"

3-350 MCM 3"

3-400 MCM 3"

3-500 MCM 3-1/2"

3-600 MCM 3-1/2"

3-750 MCM 4"

3-1000 MCM 4"

CONDUCTORS CONDUIT

C (CU, 3-PHASE, 4-WIRE)

CONDUCTORS CONDUIT

NO SCALE

SHEET NOTES

EXISTING TO REMAIN 3" CONDUIT CONTAINS 2 SETS OF 3 #350 MCM CU CONDUCTORS.

PROVIDE CIRCUIT FOR COORDINATION OF FIRE ALARM AND ELEVATOR SHUT DOWN IN

ACCORDANCE WITH DETAIL 3/E0.08.

PROVIDE TWO NEW 2" CONDUITS FOR NEW PARALLEL SETS OF SERVICE CONDUCTORS.

EXISTING UTILITY COMPANY CT AND METER.

NEW UTILITY COMPANY CT AND METER.

OWNER METER.

SHUNT TRIP CIRCUIT BREAKER

FOR ELEVATOR. REFER TO PANEL

SCHEDULE

M

CONTACTS SHALL CLOSE ON

ALARM ACTIVATE

+SUPERVISED 24 VDC FROM FACP

RELAY SHALL CLOSE UPON FLOW

OF WATER INTO ELEVATOR SHAFT

OR MACHINE ROOM

R

SEND SIGNAL TO FACP UPON LOSS

OF ELEVATOR SHUNT TRIP

CONTROL POWER

ADDRESSABLE RELAY MODULE

(TYPICAL)

SUPERVISED 24V DC FROM FACP

R

PANEL B2.2

11.6 kAIC

UTILITY

PANEL B1.1

7.8 kAIC

PANEL B2.3

11.6 kAIC

PANEL B2.1

9.3 kAIC

PANEL 3.1

7.8 kAIC

M

(ELEVATOR)

25 HP

EXISTING TO REMAIN 2 x 3 - #350 kcmil CU CONDUCTORS

M

7B7B 7B 7B

8C

STATIC PHASE

CONVERTER

9B

MDP

100/3/100

PANEL B3.1

13.9 kAIC

7B

PANEL 2.1

7.8 kAIC

7B7B

200/2/150

8C

2 x

EXISTING TO REMAIN

PAD-MOUNTED UTILITY

SERVICE TRANSFORMER

UTILITY

2 x 3 - #4/0 kcmil XHHW CU CONDUCTORS

IN PARALLEL 2" CONDUITS

M

NEW PAD-MOUNTED

UTILITY SERVICE

TRANSFORMER

FVDP

OR

12B1 x

17.4 kAIC 16.5 kAIC

SPD

600A - 2P

100A - 2P 100A - 2P 100A - 2P 100A - 2P 100A - 2P 100A - 2P 150A - 2P

SPD

225A - 2P

120/240V 120/240V 400A - 2P

M

(DRYER)

20 KW

240 - 2P

M

(DRYER)

20 KW

240 - 2P

8B 8B

30A - 2P 30A - 2P

125A - 2P 125A - 2P

2B 2B

120/240V 1 Phase - 208V 3 Phase

M M

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PKG NO.

SHEET

OFOREGON CAVES NATIONAL MONUMENT

OREGON CAVES CHATEAU

138578

150025

R E

V

IT

/1

/2

:5

:5

P

M C

U s e rs

\p d a v is

\D o c u m e n ts \O

R C

A

M E

P -C e n tr a l_ p d a v is

.r v t

SM

MJL

CvB, WSP

09/13/19

ELECTRICAL ONE-LINE

DIAGRAMS

E0.08 196 211

CONSTRUCTION DOCUMENTS

E .0

M

J L

E0.08

3 TYPICAL ELEVATOR SHUT DOWN CIRCUIT

NO SCALE

E0.08

2 SINGLE LINE DIAGRAM

E0.08

4 TRANSFORMER PADVAULT DETAIL

This document has been digitally signed and sealed by

William S. Phillips, PE

OR PE #94068

Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.

Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:00:35-04'00'

MECHANICAL

B301

REMOVE (E)

MAIN SERVICE

DISCONNECTS

REMOVE (E)

LOAD CENTER

REMOVE (E)

PACKAGED

ENGINE

GENERATOR

REMOVE (E)

ABANDONED

GENERATOR

ON CONCRETE

PAD

REMOVE (E) AIR

COMPRESSOR

DISCONNECT SWITCH

REMOVE (E) SWITCH

MOUNTED ON FACE

OF BENCH

+ 54"

REMOVE (E) OUTLET

MOUNTED TO

UNDERSIDE OF BEAM.

REMOVE (E) OUTLET

MOUNTED TO

UNDERSIDE OF BEAM

CD

CC

NC

NB

NA

ND

SC

SB

SA

SE

CB

CA

SD

NA.4

NB.3

SA.3

SB.8

1.1

2.9

CD.9

SA.1

NA.1

6.1

3.2 5.8

REMOVE (E) SURFACE

MOUNT LIGHT

FIXTURE

REMOVE (E) LINEAR

LIGHT FIXTURE

REMOVE (E) SURFACE

MOUNT LIGHT

FIXTURE

REMOVE (E) SURFACE

MOUNT LIGHT

FIXTURE

EXISTING TO

REMAIN CURRENT

TRANSFORMER

ENCLOSUREEXISTING-TO-BE-

RELOCATED PACIFIC

POWER METER #35

979 833

REMOVE (E) LINEAR

LIGHT FIXTURE

SHEET NOTES

DISCONNECT EXISTING MAIN SERVICE DISCONNECTS.

REMOVE WIRING DOWN & UPSTREAM OF EQUIPMENT.

INCOMING SERVICE CONDUITS SHALL BE REUSED TO FEED

NEW SERVICE. REFER TO THE SINGLE LINE DIAGRAM FOR

WIRING REQUIREMENTS OF NEW EQUIPMENT.

0 4 84

SCALE OF FEET

SCALE I

SCALE I

DEMOLITION NOTES

1. DEMOLISH ENTIRE POWER DISTRIBUTION SYSTEM, UNLESS

OTHERWISE NOTED. REFER TO DEMOLITION DRAWINGS

FOR LOCATIONS OF POWER PANELS. CONTRACTOR SHALL

ASSUME ALL EXISTING PANELS ARE 200A, 120/240V, SINGLE

PHASE, FED FROM MAIN DISCONNECTS ON BASEMENT 3.

CONTRACTOR SHALL ASSUME 2in. CONDUIT SIZE, 3-#3/0

AWG COPPER CONDUCTORS, AND LONGEST RUN POSSIBLE,

PARALLEL TO MAIN WALLS.

2. REMOVE ALL CONDUIT AND WIRING ASSOCIATED WITH

EQUIPMENT OR DEVICES BEING DEMOLISHED. REMOVE ALL

CONDUIT AND WIRING BACK TO EXISTING PANELS. REFER

TO SECTION 01 35 91 FOR HISTORIC PRESERVATION

TREATMENT PROCEDURES.

3. COORDINATE WITH CONTRACTING OFFICER FOR PROPER

DISPOSAL PROCEDURE OF DECOMMISSIONED ELECTRICAL

EQUIPMENT.

4. REPLACE ALL CONDUIT AND WIRING ASSOCIATED WITH

EQUIPMENT THAT IS EXISTING TO REMAIN.

5. REMOVE ALL ABANDONED BRANCH CIRCUITS AND CABLES

IN ACCORDANCE WITH DEMOLITION NOTES HEREIN AND

SECTION 26 05 05.

6. REFURBISH EXISTING LUMINAIRES H1-H9. WORK SHALL BE

PERFORMED BY A UL LISTED FACILITY. REPLACE WIRING,

BASE (TO MATCH EXISTING) AND RETROFIT WITH NEW LED

LAMPS PRIOR TO REINSTALLATION. REFER TO LUMINAIRE

SCHEDULE FOR MORE INFORMATION.

7. REMOVE ALL EXTERIOR CONDUIT AND WIRING MOUNTED ON

EXTERIOR WALLS. REPLACE IN ACCORDANCE WITH

RENOVATION GENERAL NOTES.

8. HAZARDOUS MATERIALS ARE KNOWN TO BE LOCATED ON

THIS SITE. AN INVESTIGATION FOR HAZARDOUS MATERIALS

HAS BEEN PERFORMED BY VISTA ENVIRONMENTAL

CONSULTING. THE RESULTING REPORT, DATED DECEMBER

27, 2017, IS AVAILABLE UPON REQUEST FROM THE NATIONAL

PARK SERVICE. SEE SPECIFICATION 028100 FOR

HAZARDOUS MATERIAL REMEDIATION.

9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING

THAT PERSONNEL WITHIN THE WORK AREA ARE

PROTECTED FROM EXPOSURE TO ANY HAZARDOUS

MATERIALS ENCOUNTERED. IF MATERIALS ARE

DISCOVERED THAT MAY BE HAZARDOUS, THE CONTRACTOR

SHALL IMMEDIATELY NOTIFY THE CONTRACTING OFFICER

AND CEASE WORK UNTIL CONDITIONS CAN BE MAINTAINED

IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS.

(APPLY TO SHEETS E1.B3,

E1.B2, E1.B1, E1.01, E1.02, E1.03)

TITLE OF SHEETSUB SHEET NO.DESIGNED:

TECH REVIEW:

DATE:

DRAWING NO.

PMIS/PK…

This is the start of the file's text. The full file is on GovTribe.