This pre-solicitation notice seeks proposals for a single construction contract to Correct Life Safety and Critical Deficiencies at Oregon Caves Chateau. The project includes fire suppression and detection systems, code compliant egress doors and accessibility improvements, structural repairs, replacement of water supply and waste vent piping, and replacement of steam piping and radiators. The work will be conducted in one phase under a single prime contract, with an estimated price range of over $10 million and period of performance from April 2020 to September 2021. The solicitation will be issued on or around October 21, 2019 via www.fedbizopps.gov. The NAICS code is 236220 with a size standard of $36.5 million. The National Park Service encourages participation from small businesses, including veteran-, small disadvantaged-, and women-owned small businesses. Interested vendors should monitor the website for additional details.
Drawings - Electrical
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ELECTRICAL SYMBOLS AND LEGEND
RECEPTACLES / POWERFLOOR WALL CEILING
P
NOTE: ALL RECEPTACLE OUTLETS ON WALLS ARE MOUNTED AT 18" AFF, UON.
EXISTING / DEMOLITION
MULTI-OUTLET RACEWAY WITH PREWIRED RECEPTACLES
MOUNTED 12" ON CENTER UNLESS OTHERWISE NOTED.
NUMBER IN PARENTHESIS INDICATES DISTANCE
BETWEEN DEVICES. WHERE MULTIPLE CIRCUITS ARE
INDICATED CIRCUITS ALTERNATE ALONG ENTIRE LENGTH
OF RACEWAY. MOUNTED 4' AFF UON.
EXISTING EQUIPMENT TO REMAIN
EXISTING EQUIPMENT TO BE REMOVED
NEW EQUIPMENT / RACEWAYS
EXISTING TO REMAIN
EXISTING TO BE REMOVED
NEW EQUIPMENT, LIGHTING FIXTURE OR
DEVICE
SINGLE LINE DIAGRAM
P P
X
X X
X
X
X
LIGHTING
SURFACE MOUNTED TROFFER
WALL CEILING
EXAMPLES:
NORMAL EMERGENCY
LUMINAIRE
NOMENCLATURE:
"A" DENOTES FIXTURE TYPE
"3" DENOTES CIRCUIT NUMBER
"a" DENOTES SWITCH ZONE "z1" DENOTES DAYLIGHT ZONE "r1" DENOTES SITE RELAY ZONE
EXIT SIGN; SHADED PORTION INDICATES ILLUMINATED
FACE. DIRECTIONAL ARROWS AS INDICATED ON THE
DRAWINGS. REFER TO LUMINAIRE SCHEDULE FOR
MORE INFORMATION.
EXIT
E-6
P
A E-6
GENERAL ELECTRICAL SYMBOLSRECESSED SURFACE
DISCONNECT SWITCH, 30 AMP MINIMUM UNLESS
NOTED OTHERWISE
FREE STANDING SWITCHBOARD, MOTOR CONTROL
CENTER OR DISTRIBUTION PANELBOARD
A-1,3,5
J
J
J
J
J
A. CONTRACTOR IS RESPONSIBLE FOR IDENTIFYING FIXTURE TYPE AND
MOUNTING CONDITIONS REGARDLESS OF SYMBOL USED ON PLANS.
B. REFER TO LUMINAIRE SCHEDULE FOR FIXTURE DESCRIPTION, MOUNTING AND
LAMP INFORMATION. SHADED FIXTURE SYMBOLS INDICATE FIXTURE IS
CONNECTED TO THE EMERGENCY POWER SUPPLY SYSTEM OR HAS
SECONDARY POWER SOURCE.
RECESSED MOUNTED TROFFER
SUSPENDED OR PENDANT MOUNTED LUMINAIRE
NORMAL EMERGENCY
STRIP OR TRACK LIGHT
SURFACE MOUNTED DOWNLIGHT
RECESSED MOUNTED DOWNLIGHT
PENDANT MOUNTED DOWNLIGHT
DIRECTIONAL LUMINAIRE
SIMPLEX RECEPTACLE
JUNCTION BOX WALL OR CEILING MOUNTED 7' 2"
AFF UON.
DUPLEX RECEPTACLE
QUADRUPLEX RECEPTACLE
SPECIAL RECEPTACLE
(DUPLEX & QUADRUPLEX)
GROUND FAULT CIRCUIT INTERRUPTING
RECEPTACLE, ABOVE COUNTER UNLESS NOTED.
ABOVE COUNTER RECEPTACLE. INSTALL ABOVE
COUNTER OR DEFINED HEIGHT
HALF CONTROLLED DUPLEX
SWITCHED RECEPTACLES
JUNCTION BOX SIZE AS REQUIRED FOR
NUMBER OF WIRES OR RACEWAYS
SYSTEM FURNITURE POWER FEED, REFER TO
DETAIL FOR RACEWAY AND BOX REQUIREMENTS
POLE MOUNTED LUMINAIRE (1, 2, 3, 4 HEADS)
WALL MOUNTED LUMINAIRE
XX
X33
+4'-6"
A 3,a,z1
FIRE TREATED PLYWOOD BACKBOARD 3/4"X96" HIGH X
LENGTH AS INDICATED
REFERENCE TO NOTE "1" ON SAME SHEET
LIGHTING FIXTURE DESIGNATION
XX = FIXTURE TYPE
MECHANICAL EQUIPMENT DESIGNATION "P-1" INDICATED
EQUIPMENT NAME OR NUMBER
MOUNTING HEIGHT FROM FINISHED FLOOR TO
CENTERLINE OF OUTLET OR EQUIPMENT
DETAIL REFERENCE NUMBER "1"
ON DRAWING "E-6"
SECTION OR ELEVATION REFERENCE LETTER
"A" ON DRAWING "E-6"
INDICATES HOMERUN WITH THREE CIRCUITS
AND SEPARATE NEUTRALS
FUSED DISCONNECT SWITCH, 30 AMP MINIMUM
UNLESS NOTED OTHERWISE
COMBINATION DISCONNECT SWITCH MOTOR
STARTED
MOTOR, 5 HP INDICATED
TRANSFORMER
RELAY OR EQUIPMENT CABINET AS INDICATED ON
THE DRAWINGS
LIGHTING OR POWER PANELBOARD
T
NOTES:
GROUNDING SYSTEMFLOOR WALL
POKE
THRU
HALF CONTROLLED QUADRUPLEX
(18)
G
EXOTHERMIC GROUND CONNECTION
GROUND WIRE
GROUNDING ELECTRODE
CIRCUIT BREAKER, 3 POLE UNLESS NOTED
OTHERWISE
NON-FUSED DISCONNECT SWITCH, 30 AMP, 3P
UNLESS NOTED OTHERWISE
FUSED DISCONNECT SWITCH, 3 POLE UNLESS
NOTED OTHERWISE
GROUNDING ELECTRODE
RACEWAYS AND WIRINGFLOOR WALL CEILING
CONDUIT CONCEALED IN CEILING OR WALL
SPACE
A-1 A-1A-1
(MS-01) (MS-01)
<RA-1> <RA-1>
CONDUIT RUN EXPOSED
CONDUIT RUN UNDERGROUND
OR CONCEALED IN FLOOR SPACE
EXISTING CONDUIT TO REMAIN
CONDUIT RISING UP FROM BELOW
CONDUIT DROPPING DOWN FROM ABOVE
HOMERUN TO PANELBOARD, CABINET
OR TERMINAL BACKBOARD AS
INDICATED
HOMERUN TO SWITCHBOARD OR MCC AS
INDICATED. REFER TO SINGLE LINE
DIAGRAM FOR CONDUIT AND WIRE SIZES
HOMERUN TO PANEL VIA INDICATED
LIGHTING CONTROL RELAY CABINET. REFER
TO INDICATED RELAY CABINET SCHEDULE
FOR ADDITIONAL INFORMATION AND
CONTROL REQUIREMENTS
SWITCHING
MANUAL MOTOR STARTER WITH THERMAL OVERLOAD
NUMBER OF POLES AS REQUIRED
P
P
M
X ab abc
L abc
X33
WALL CEILING
SWITCH, SUBSCRIPT INDICATES:
X = NONE - SINGLE POLE
X = 3 - THREE WAY
X = A,B,C - OUTLET CONTROLLED
X = 2 - DOUBLE POLE
X = KP - KEY OPERATED WITH PILOT LIGHT
X = P - PILOT LIGHT
X = R - MOMENTARY RELAY ON/OFF
X = S - INTEGRAL MOTION DECTOR
2-SINGLE POLE SWITCHES, UNDER COMMON PLATE, 42" AFF UON
3-SINGLE POLE SWITCHES, UNDER COMMON PLATE, 42" AFF UON
LOW VOLTAGE LIGHTING CONTROL. NUMBER IN ELONGATED
HEXAGON INDICATES CONTROL IDENTIFICATION. REFER TO
SEQUENCE OF OPERATIONS AND LIGHTING CONTROL DETAILS
FOR ADDITIONAL INFORMATION. 42" AFF UON
DIMMER WITH INTEGRAL SWITCH, 42" AFF UON. '600' INDICATES
RATING IN WATTS
PUSH-BUTTON STATION. 42" AFF UON
PHOTOSENSOR - WALL MOUNT WITH DIRECTIONAL VIEW.
ARROW INDICATES AIMING DIRECTION. MOUNTED 7' 2" AFF
UON
PHOTOSENSOR - CEILING MOUNT
LX LOW VOLTAGE LIGHTING CONTROL SUBSCRIPT
INDICATES:
X = D - DIMMER SWITCH
X = S - SENSOR SWITCH
X = T - TIMER SWITCH
X = M - MASTER CONTROL SWITCH 42" AFF UON
X = V - LOW VOLTAGE
DUAL TECHNOLOGY OCCUPANCY SENSOR, 360 DEGREE. 42" AFF UON
DUAL TECHNOLOGY OCCUPANCY SENSOR, DIRECTIONAL AS
INDICATED ON THE DRAWINGS. 42" AFF UON.
TELECOMMUNICATIONSFLOOR WALL CEILING
X
TELEPHONE OUTLET. SUBSCRIPT INDICATES:
X = H - HOUSE PHONE
X = J - HOUSE PHONE JACK
EMERGENCY LOW VOLTAGE REMOTE HEAD
REFER TO LUMINAIRE SCHEDULE FOR MORE
INFORMATION.
FIRE ALARM SYSTEMWALL CEILING
FIRE ALARM CONTROL PANELFACP
ABBREVIATIONS
RM REMOTE HEAD MDP MAIN DISTRIBUTION PANEL
PNL PANELBOARD SPD SURGE PROTECTION DEVICE
AFF ABOVE FINISHED FLOOR AWG AMERICAN WIRE GAUGE
CKT CIRCUIT UON UNLESS OTHERWISE NOTED
NEC NATIONAL ELECTRIC CODE CONN CONNECTION
EST ESTIMATE VFD VARIABLE FREQUECY DRIVE
WP WEATHERPROOF MCM THOUSAND CIRCULAR MILS
C CONDUIT BB BASE BOARD HEATER
MOCP MAXIMUM OVERCURRENT PROTECTION
GROUNDING BAR
GROUNDING BAR
EMERGENCY BATTERY PACK WITH REMOTE HEAD.
REFER TO LUMINAIRE SCHEDULE FOR MORE
INFORMATION.M ELECTRICAL MOTOR CONNECTION
M METER
SURGE PROTECTIVE DEVICE
G
GENERATOR, AS NOTED ON
SINGLE LINE DIAGRAM
(MS-01)
<RA-1>
GROUND BUS BAR
SPD
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:5
:1
P
M C
U s e rs
\p d a v is
\D o c u m e n ts \O
R C
A
M E
P -C e n tr a l_ p d a v is
.r v t
SM
MJL
CvB, WSP
09/13/19
ELECTRICAL LEGEND
E0.01 189 211
CONSTRUCTION DOCUMENTS
E .0
M
J L
This document has been digitally signed and sealed by
William S. Phillips, PE
OR PE #94068
Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.
Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:01:32-04'00'
DRAWINGS
PANELBOARD SCHEDULE LEGEND
S - PROVIDE SHUNT TRIP BREAKER.
G - PROVIDE GROUND FAULT CIRCUIT INTERRUPTER (GFCI).
H - PROVIDE HANDLE CLAMP DEVICE.
A - PROVIDE ARC FAULT CIRCUIT INTERRUPTER (AFCI).
M - PROVIDE CT FOR METERING SYSTEM AND CONNECTED TO
METER INDICATED ON THE METERING SCHEDULE.
RED SURFACE WITH WHITE
CORE PHENOLIC LABEL
SERVICE DISCONNECTING MEANS
#1 of 2
NOTES
1. NAMEPLATES SHALL BE PERMANENTLY INSTALLED ON EQUIPMENT WITH STAINLESS
STEEL SCREWS - ADHESIVE LABELS SHALL NOT BE USED
DESIGNATION
DISCONNECTS LOCATED IN RM B301
1. DISTRIBUTION PANEL 'MDP'
2. DISTRIBUTION PANEL 'FVDP'
#1 = DISTRIBUTION PANEL 'MDP'
MAIN BREAKER
#2 = DISTRIBUTION PANEL 'FVDP'
MAIN BREAKER
NO SCALE
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:5
:2
P
M C
U s e rs
\p d a v is
\D o c u m e n ts \O
R C
A
M E
P -C e n tr a l_ p d a v is
.r v t
SM
MJL
CvB, WSP
09/13/19
ELECTRICAL PANEL
SCHEDULES
E0.02 190 211
CONSTRUCTION DOCUMENTS
E .0
M
J L
Other 0.6 kVA 0.6 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 1.5 kVA 1.5 kVA Lighting and Receptacles - Hotel 16.1 kVA 8.0 kVA Design Current: 597.2 A Elevator 20.0 kVA 20.0 kVA Design Load: 143.3 kVA Motor 9.1 kVA 9.7 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 477.8 A Heating 53.3 kVA 53.3 kVA Total Connected Current: 532.0 A Cooling 0.0 kVA 0.0 kVA Total Estimated Demand Load: 114.7 kVA Lighting 3.6 kVA 4.6 kVA Total Connected Load: 127.7 kVA Receptacles 23.0 kVA 16.5 kVA Load Classification Connected Load Estimated Demand Panel Totals
-EQUIPMENT SHALL BE LABELED AS 'SUITABLE FOR USE AS SERVICE ENTRANCE.' PROVIDE LABEL IN ACCORDANCE WITH DETAIL 1/E0.02.
-PROVIDE SPD AS SPECIFIED.
-PROVIDE CUSTOMER METERING IN ACCORDANCE WITH SECTION 26 24 16.
-PROVIDE FULLY RATED MAIN BREAKER.
70.0 kVA 57.6 kVA
47 0.0 0.0 48 -- -- SPACE ONLY --
SPD 30 A 2
45 0.0 0.0 46 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 43 0.0 0.0 44 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 41 0.0 0.0 42 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 39 0.0 0.0 40 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 37 0.0 0.0 38 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 35 0.0 0.0 36
-- SPACE ONLY -- -- 33 0.0 0.0 34
2 150 A SPARE
31 0.0 0.0 32
SPARE 225 A 2
29 0.0 0.0 30
2 100 A SPARE
27 0.0 0.0 28
SPARE 150 A 2
25 0.0 0.0 26
2 100 A SPARE
23 0.0 10.0 24
SPARE 100 A 2
21 0.0 10.0 22
2 125 A DRYER RM B209B
19 0.0 3.4 20
SPARE 100 A 2
17 0.0 6.1 18
2 100 A PANEL 3.1
15 10.0 7.5 16
DRYER RM B209B 125 A 2
13 10.0 8.4 14
2 100 A PANEL 2.1
-- SPACE ONLY -- -- 11 0.0 3.1 12
-- SHUNT TRIP MODULE -- -- 9 0.0 7.9 10
2 100 A PANEL B3.1
7 10.0 2.7 8
S ELEVATOR 150 A 2
5 10.0 5.4 6
2 100 A PANEL B2.3
3 3.5 7.4 4
PANEL B1.1 100 A 2
1 5.0 7.2 2
2 100 A PANEL B2.1
DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION
Sections: 1
Mounting: SURFACE AIC Rating: 22,000 A
Wire: 3 Main Rating: 600 A
Phase: 1 Mains Type: MCB
Voltage: 120/240 Amp Rating: 600 A
Distribution Panelboard: MDP
DISTRIBUTION
PANELBOARD 'MDP'
DISTRIBUTION
PANELBOARD 'FVDP'
(BLANK) (BLANK)
E0.02
1 SERVICE DISCONNECT MEANS
Other 0.1 kVA 0.1 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 41.1 kVA 26.7 kVA Lighting and Receptacles - Hotel 0.0 kVA 0.0 kVA Design Current: 267.6 A Elevator 0.0 kVA 0.0 kVA Design Load: 64.2 kVA Motor 7.9 kVA 9.6 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 214.1 A Heating 0.0 kVA 0.0 kVA Total Connected Current: 266.7 A Cooling 8.5 kVA 8.5 kVA Total Estimated Demand Load: 51.4 kVA Lighting 0.6 kVA 0.7 kVA Total Connected Load: 64.0 kVA Receptacles 5.8 kVA 5.8 kVA Load Classification Connected Load Estimated Demand Panel Totals
-EQUIPMENT SHALL BE LABELED AS 'SUITABLE FOR USE AS A SERVICE ENTRANCE.' PROVIDE LABEL IN ACCORDANCE WITH DETAIL 1/E0.02.
-PROVIDE SPD AS SPECIFIED.
-PROVIDE CUSTOMER METERING IN ACCORDANCE WITH SECTION 26 24 16.
32.6 kVA 31.5 kVA
47 0.0 0.0 48 -- -- SPACE ONLY --
SPD 30 A 2
45 0.0 0.0 46 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 43 0.0 0.0 44 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 41 0.0 0.0 42 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 39 0.0 0.0 40 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 37 0.0 0.0 38 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 35 0.0 0.0 36 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 33 0.0 0.0 34 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 31 0.0 0.0 32 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 29 0.0 0.0 30 1 20 A SPARE
SPARE 20 A 1 27 0.0 0.0 28 1 20 A SPARE
SPARE 20 A 1 25 0.0 0.0 26
23 0.0 0.0 24
2 20 A SPARE
SPARE 20 A 2
21 0.0 0.0 22 19 0.0 0.0 20
2 20 A SPARE
SPARE 20 A 2
17 0.0 0.0 18 1 20 A SPARE
SPARE 20 A 1 15 0.0 0.0 16 1 20 A SPARE
LTG STAFF KITCHEN B208B 20 A 1 13 0.1 1.2 14 1 20 A ICE MACHINE RM B209
LTG COFFEE SHOP B104 20 A 1 11 0.4 1.0 12 1 20 A EXISTING FAN COIL RM B101
LTG KITCHEN B103 20 A 1 9 0.1 2.9 10
7 2.0 2.9 8
2 30 A WALK-IN REFRIGERATOR RM B103A
EXISTING FAN COIL RM B208 40 A 2
5 2.0 0.0 6 -- -- SHUNT TRIP MODULE --
3 22.0 3.2 4
PANEL B2.2 225 A 2
1 23.1 3.2 2
2 50 A KEF-1 S
DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION
Sections: 1
Mounting: SURFACE AIC Rating: 22,000 A
Wire: 3 Main Rating: 400 A
Phase: 1 Mains Type: MCB
Voltage: 120/240 Amp Rating: 400 A
Distribution Panelboard: FVDP
E0.02
2 SECONDARY TRENCH DETAIL
This document has been digitally signed and sealed by
William S. Phillips, PE
OR PE #94068
Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.
Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:01:24-04'00'
G - PROVIDE GROUND FAULT CIRCUIT INTERRUPTER (GFCI).
H - PROVIDE HANDLE CLAMP DEVICE.
A - PROVIDE ARC FAULT CIRCUIT INTERRUPTER (AFCI).
M - PROVIDE CT FOR METERING SYSTEM AND CONNECTED TO
METER INDICATED ON THE METERING SCHEDULE.
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:5
:2
P
M C
U s e rs
\p d a v is
\D o c u m e n ts \O
R C
A
M E
P -C e n tr a l_ p d a v is
.r v t
SM
MJL
CvB, WSP
09/13/19
ELECTRICAL PANEL
SCHEDULES
E0.03 191 211
CONSTRUCTION DOCUMENTS
E .0
M
J L
Other 0.2 kVA 0.2 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 0.0 kVA 0.0 kVA Lighting and Receptacles - Hotel 1.3 kVA 0.6 kVA Design Current: 76.3 A Elevator 0.0 kVA 0.0 kVA Design Load: 18.3 kVA Motor 5.5 kVA 5.9 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 61.0 A Heating 0.0 kVA 0.0 kVA Total Connected Current: 60.6 A Cooling 0.0 kVA 0.0 kVA Total Estimated Demand Load: 14.6 kVA Lighting 1.4 kVA 1.8 kVA Total Connected Load: 14.6 kVA Receptacles 6.1 kVA 6.1 kVA Load Classification Connected Load Estimated Demand Panel Totals
-PROVIDE SPD AS SPECIFIED.
7.2 kVA 7.4 kVA
41 0.0 0.0 42 1 20 A SPARE
SPD 30 A 2
39 0.0 0.0 40 1 20 A SPARE
SPARE 20 A 1 37 0.0 0.0 38 1 20 A SPARE
SPARE 20 A 1 35 0.0 0.0 36 1 20 A SPARE
SPARE 20 A 1 33 0.0 0.0 34 1 20 A SPARE
SPARE 20 A 1 31 0.0 0.0 32 1 20 A SPARE
DOOR OPEN ALARM 20 A 1 29 0.2 0.0 30 1 20 A SPARE
REC. ROOM B211B 20 A 1 27 0.2 1.5 28 1 20 A WASHER RM B209B
A REC RM B205 20 A 1 25 0.9 1.5 26 1 20 A WASHER RM B209B
A REC RM B207 20 A 1 23 0.3 1.5 24 1 20 A WASHER RM B209B
A REC RM B206 20 A 1 21 0.4 0.3 22 1 20 A EF-8
LTG STAIR B200 20 A 1 19 0.1 0.3 20 1 20 A EF-7
REC RM B201,B203,B204 20 A 1 17 1.8 0.8 18 1 20 A LTG LEVEL B2
LIGHTING CONTROL PANEL 'LCPB2' 20 A 1 15 0.0 0.3 16 1 20 A LTG B2 - EMERGENCY
LTG B1 - EXTERIOR 20 A 1 13 0.1 0.1 14 1 20 A LTG STAIRS B300
LTG B2 - EXTERIOR 20 A 1 11 0.1 0.0 12 1 20 A ELEVATOR PIT LIGHT
LTG B1 EXTERIOR 20 A 1 9 0.0 0.5 10 1 20 A REC RM 202,202A,202B
ELEVATOR CAB LIGHT DISCONNECT 20 A 1 7 0.0 0.1 8 1 20 A LTG LEVEL B1
REC ELEVATOR PIT 20 A 1 5 0.2 0.5 6 1 20 A REC RM B204B
REC RM B208,B209,B211,B211C 20 A 1 3 2.0 0.6 4 1 20 A REC RM B204A
LTG LEVEL B2 20 A 1 1 0.0 0.0 2 1 20 A LTG RM B204
DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION
Mounting: SURFACE Sections: 1
Wire: 3 AIC Rating: 10,000 A
Phase: 1 Main: MLO
Voltage: 120/240 Amp Rating: 100 A
Panelboard: B2.1
Other 0.0 kVA 0.0 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 34.2 kVA 22.2 kVA Lighting and Receptacles - Hotel 0.0 kVA 0.0 kVA Design Current: 172.9 A Elevator 0.0 kVA 0.0 kVA Design Load: 41.5 kVA Motor 1.0 kVA 1.1 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 138.3 A Heating 0.0 kVA 0.0 kVA Total Connected Current: 187.7 A Cooling 4.0 kVA 4.0 kVA Total Estimated Demand Load: 33.2 kVA Lighting 0.0 kVA 0.0 kVA Total Connected Load: 45.0 kVA Receptacles 5.8 kVA 5.8 kVA Load Classification Connected Load Estimated Demand Panel Totals
-PROVIDE SPD AS SPECIFIED.
-PROVIDE LOW VOLTAGE WIRING FROM SHUNT-TRIP BREAKER BACK TO KITCHEN ANSUL SYSTEM.
23.1 kVA 22.0 kVA
59 0.0 0.0 60 1 20 A SPARE
SPD 30 A 2
57 0.0 0.0 58 1 20 A SPARE
SPARE 20 A 1 55 0.0 0.0 56 1 20 A SPARE
SPARE 20 A 1 53 0.0 0.0 54 1 20 A SPARE
SPARE 20 A 1 51 0.0 0.0 52 1 20 A SPARE
SPARE 20 A 1 49 0.0 0.0 50 1 20 A SPARE
SPARE 20 A 1 47 0.0 0.0 48 1 20 A SPARE
REC RM B104 20 A 1 45 0.4 0.0 46 1 20 A SPARE
REC DED RM B104 20 A 1 43 0.2 0.2 44 1 20 A REC DED RM B104
REC DED RM B104 20 A 1 41 0.2 0.2 42 1 20 A REC DED RM B104
EXISTING STAFF KITCHEN SUPPLY AIR 20 A 1 39 0.5 0.2 40 1 20 A REC DED RM B104
B100 STAIR ELECTRIC LOCK 20 A 1 37 0.8 0.2 38 1 20 A REC DED RM B104
GAS RANGE 20 A 1 35 0.2 2.0 36
EXISTING STAFF KITCHEN HOOD FAN 20 A 1 33 0.5 2.0 34
2 40 A EXISTING SERVICE ENTRY HOOD FAN
REC RM B101 20 A 1 31 0.7 0.4 32 1 20 A REC RM B101A,B101B
BEER COOLER RM B101 20 A 1 29 1.5 0.7 30 1 20 A REC RM B102
SALAD BAR REFRIGERATOR RM B102 20 A 1 27 1.5 0.4 28 1 20 A REC RM B104
-- SHUNT TRIP MODULE -- -- 25 0.0 0.7 26 1 20 A REC RM B104
23 2.9 1.5 24 1 20 A WINE COOLER RM B101
S DEEP FRYER RM B103 30 A 2
21 2.9 1.2 22 1 20 A COFFEE MACHINE RM B104
-- SHUNT TRIP MODULE -- -- 19 0.0 1.5 20 1 20 A SALAD BAR REFRIGERATOR RM B208B
S PROPANE OVEN RM B103 20 A 1 17 0.2 0.0 18 -- -- SHUNT TRIP MODULE --
REFRIGERATOR RM B101 20 A 1 15 1.5 0.2 16 1 20 A PROPANE OVEN RM B103 S
REFRIGERATOR RM B103 20 A 1 13 1.5 1.5 14 1 20 A REFRIGERATOR RM B101
REFRIGERATOR RM B103 20 A 1 11 1.5 1.5 12 1 20 A REFRIGERATOR RM B103
INDUSTRIAL DISHWASHER RM B103 30 A 1 9 1.8 1.5 10 1 20 A REFRIGERATOR RM B103
STEAM TABLE RM B208B 20 A 1 7 1.2 1.5 8 1 20 A REFRIGERATOR RM B208B
DEEP FREEZER RM B103 20 A 1 5 1.8 1.2 6 1 20 A STEAM TABLE RM B103
MICROWAVE RM B103 20 A 1 3 1.2 1.4 4 1 20 A MICROWAVE RM B208B
MICROWAVE RM B103 20 A 1 1 1.2 1.2 2 1 20 A MICROWAVE RM B103
DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION
Mounting: SURFACE Sections: 1
Wire: 3 AIC Rating: 22,000 A
Phase: 1 Main: MLO
Voltage: 120/240 Amp Rating: 225 A
Panelboard: B2.2
PANEL 'B2.1' PANEL 'B2.2'
PANEL 'B2.3' (BLANK)
Other 0.0 kVA 0.0 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 1.5 kVA 1.5 kVA Lighting and Receptacles - Hotel 0.0 kVA 0.0 kVA Design Current: 45.2 A Elevator 0.0 kVA 0.0 kVA Design Load: 10.9 kVA Motor 2.4 kVA 3.0 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 36.2 A Heating 4.0 kVA 4.0 kVA Total Connected Current: 33.7 A Cooling 0.0 kVA 0.0 kVA Total Estimated Demand Load: 8.7 kVA Lighting 0.0 kVA 0.0 kVA Total Connected Load: 8.1 kVA Receptacles 0.2 kVA 0.2 kVA Load Classification Connected Load Estimated Demand Panel Totals
-PROVIDE SPD AS SPECIFIED.
5.4 kVA 2.7 kVA
41 0.0 0.0 42 -- -- SPACE ONLY --
SPD 30 A 2
39 0.0 0.0 40 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 37 0.0 0.0 38 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 35 0.0 0.0 36 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 33 0.0 0.0 34 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 31 0.0 0.0 32 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 29 0.0 0.0 30 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 27 0.0 0.0 28 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 25 0.0 0.0 26 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 23 0.0 0.0 24 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 21 0.0 0.0 22 -- -- SPACE ONLY --
SPARE 20 A 1 19 0.0 0.0 20 1 20 A SPARE
SPARE 20 A 1 17 0.0 0.0 18 1 20 A SPARE
SPARE 20 A 1 15 0.0 0.0 16 1 20 A SPARE
SPARE 20 A 1 13 0.0 0.0 14 1 20 A SPARE
SPARE 20 A 1 11 0.0 0.0 12 1 20 A SPARE
SPARE 20 A 1 9 0.0 0.0 10 1 20 A SPARE
SPARE 20 A 1 7 0.0 0.2 8 1 20 A FACP H
SPACE HEATER RM B208 20 A 1 5 1.0 2.4 6 1 40 A ELEVATOR SUMP
SPACE HEATER RM B101 20 A 1 3 1.0 1.5 4 1 20 A REFRIGERATOR RM 110
SPACE HEATER RM 109 20 A 1 1 1.0 1.0 2 1 20 A SPACE HEATER RM B101
DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION
Mounting: SURFACE Sections: 1
Wire: 3 AIC Rating: 22,000 A
Phase: 1 Main: MLO
Voltage: 120/240 Amp Rating: 100 A
Panelboard: B2.3
This document has been digitally signed and sealed by
William S. Phillips, PE
OR PE #94068
Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.
Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:01:17-04'00'
G - PROVIDE GROUND FAULT CIRCUIT INTERRUPTER (GFCI).
H - PROVIDE HANDLE CLAMP DEVICE.
A - PROVIDE ARC FAULT CIRCUIT INTERRUPTER (AFCI).
M - PROVIDE CT FOR METERING SYSTEM AND CONNECTED TO
METER INDICATED ON THE METERING SCHEDULE.
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:5
:3
P
M C
U s e rs
\p d a v is
\D o c u m e n ts \O
R C
A
M E
P -C e n tr a l_ p d a v is
.r v t
SM
MJL
CvB, WSP
09/13/19
ELECTRICAL PANEL
SCHEDULES
E0.04 192 211
CONSTRUCTION DOCUMENTS
E .0
M
J L
Other 0.0 kVA 0.0 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 0.0 kVA 0.0 kVA Lighting and Receptacles - Hotel 0.0 kVA 0.0 kVA Design Current: 57.6 A Elevator 0.0 kVA 0.0 kVA Design Load: 13.8 kVA Motor 0.0 kVA 0.0 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 46.0 A Heating 9.3 kVA 9.3 kVA Total Connected Current: 45.8 A Cooling 0.0 kVA 0.0 kVA Total Estimated Demand Load: 11.1 kVA Lighting 0.2 kVA 0.3 kVA Total Connected Load: 11.0 kVA Receptacles 1.4 kVA 1.4 kVA Load Classification Connected Load Estimated Demand Panel Totals
-PROVIDE SPD AS SPECIFIED.
7.9 kVA 3.1 kVA
41 0.0 0.0 42 -- -- SPACE ONLY --
SPD 30 A 2
39 0.0 0.0 40 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 37 0.0 0.0 38 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 35 0.0 0.0 36 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 33 0.0 0.0 34 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 31 0.0 0.0 32 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 29 0.0 0.0 30 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 27 0.0 0.0 28 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 25 0.0 0.0 26 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 23 0.0 0.0 24 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 21 0.0 0.0 22 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 19 0.0 0.0 20 -- -- SPACE ONLY --
SPARE 20 A 1 17 0.0 0.0 18 1 20 A SPARE
SPARE 20 A 1 15 0.0 0.0 16 1 20 A SPARE
SPARE 20 A 1 13 0.0 0.0 14 1 20 A SPARE
SPARE 20 A 1 11 0.0 0.0 12 1 20 A SPARE
REC RM B301 20 A 1 9 1.1 0.4 10 1 20 A REC EXTERIOR
LTG RM B301 20 A 1 7 0.3 0.1 8 1 20 A B-1
P-3 25 A 1 5 1.8 1.8 6 1 25 A P-4
3 1.4 1.4 4 P-1 20 A 2
1 1.4 1.4 2 2 20 A P-2
DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION
Mounting: SURFACE Sections: 1
Wire: 3 AIC Rating: 22,000 A
Phase: 1 Main: MLO
Voltage: 120/240 Amp Rating: 100 A
Panelboard: B3.1
Other 0.1 kVA 0.1 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 0.0 kVA 0.0 kVA Lighting and Receptacles - Hotel 2.5 kVA 1.3 kVA Design Current: 39.3 A Elevator 0.0 kVA 0.0 kVA Design Load: 9.4 kVA Motor 0.7 kVA 0.9 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 31.4 A Heating 0.0 kVA 0.0 kVA Total Connected Current: 35.6 A Cooling 0.0 kVA 0.0 kVA Total Estimated Demand Load: 7.5 kVA Lighting 0.4 kVA 0.5 kVA Total Connected Load: 8.5 kVA Receptacles 4.9 kVA 4.9 kVA Load Classification Connected Load Estimated Demand Panel Totals
-PROVIDE SPD AS SPECIFIED.
5.0 kVA 3.5 kVA
41 0.0 0.0 42 -- -- SPACE ONLY --
SPD 30 A 2
39 0.0 0.0 40 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 37 0.0 0.0 38 -- -- SPACE ONLY --
-- SPACE ONLY -- -- 35 0.0 0.0 36 -- -- SPACE ONLY --
SPARE 20 A 1 33 0.0 0.0 34 1 20 A SPARE
SPARE 20 A 1 31 0.0 0.0 32 1 20 A SPARE
SPARE 20 A 1 29 0.0 0.0 30 1 20 A SPARE
SPARE 20 A 1 27 0.0 0.0 28 1 20 A SPARE
SPARE 20 A 1 25 0.0 0.0 26 1 20 A SPARE
SPARE 20 A 1 23 0.0 0.0 24 1 20 A SPARE
SPARE 20 A 1 21 0.0 0.8 22 1 20 A LTG RM B101A,B101B; EF-4
19 0.3 0.8 20 1 20 A AUTO DOOR OPEN
EXISTING WALL HEATER RM 111 20 A 2
17 0.3 0.2 18 1 20 A B1 DOOR OPEN ALARM
15 0.3 0.2 16 1 20 A REC RM 111
EXISTING WALL HEATER RM 110 20 A 2
13 0.3 0.7 14 1 20 A REC RM 107
REC RM 105A 20 A 1 11 0.2 1.1 12 1 20 A REC RM 106
A REC RM 105 20 A 1 9 0.6 0.3 10 1 20 A LTG LEVEL B1
REC RM 103A 20 A 1 7 0.2 0.2 8 1 20 A REC RM 104A
A REC RM 103 20 A 1 5 0.4 0.5 6 1 20 A REC RM 104 A
REC RM 101A 20 A 1 3 0.2 0.2 4 1 20 A REC RM 102A
A REC RM 101 20 A 1 1 0.5 0.6 2 1 20 A REC RM 102 A
DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION
Mounting: RECESSED Sections: 1
Wire: 3 AIC Rating: 10,000 A
Phase: 1 Main: MLO
Voltage: 120/240 Amp Rating: 100 A
Panelboard: B1.1
PANEL 'B1.1' PANEL 'B3.1'
(BLANK) (BLANK)
E0.04
2 BARRIER POST LAYOUT DETAIL
E0.04
3 BARRIER POST DETAIL
This document has been digitally signed and sealed by
William S. Phillips, PE
OR PE #94068
Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.
Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:01:10-04'00'
G - PROVIDE GROUND FAULT CIRCUIT INTERRUPTER (GFCI).
H - PROVIDE HANDLE CLAMP DEVICE.
A - PROVIDE ARC FAULT CIRCUIT INTERRUPTER (AFCI).
M - PROVIDE CT FOR METERING SYSTEM AND CONNECTED TO
METER INDICATED ON THE METERING SCHEDULE.
BRANCH CIRCUIT
PANEL
LIGHTING CONTROL PANEL 'LCPB2'.
PROVIDE 120V POWER FOR PANEL.
TIME
CLOCK
EXTERIOR
LUMINAIRES
PHOTOCELL 'ON'
ASTRONOMICAL
TIME CLOCK 'OFF'
TO
CONTROL
LIGHTING
LOADS
LIGHTING CONTROL PANEL. CIRCUIT
BREAKER TYP.
120V POWER FROM
PANEL. SEE PANEL
SCHEDULES FOR
CIRCUIT.
LOW VOLTAGE
SWITCHES AS
SHOWN ON PLANS
RELAY, QUANTITY AS
SCHEDULED
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:5
:3
P
M C
U s e rs
\p d a v is
\D o c u m e n ts \O
R C
A
M E
P -C e n tr a l_ p d a v is
.r v t
SM
MJL
CvB, WSP
09/13/19
ELECTRICAL PANEL
SCHEDULES
E0.05 193 211
CONSTRUCTION DOCUMENTS
E .0
M
J L
Other 0.3 kVA 0.3 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 0.0 kVA 0.0 kVA Lighting and Receptacles - Hotel 7.1 kVA 3.5 kVA Design Current: 66.8 A Elevator 0.0 kVA 0.0 kVA Design Load: 16.0 kVA Motor 0.5 kVA 0.6 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 53.4 A Heating 0.0 kVA 0.0 kVA Total Connected Current: 66.5 A Cooling 0.0 kVA 0.0 kVA Total Estimated Demand Load: 12.8 kVA Lighting 1.3 kVA 1.7 kVA Total Connected Load: 16.0 kVA Receptacles 6.3 kVA 6.3 kVA Load Classification Connected Load Estimated Demand Panel Totals
-PROVIDE SPD AS SPECIFIED.
8.4 kVA 7.5 kVA
53 0.0 0.0 54 1 20 A SPARE
SPD 30 A 2
51 0.0 0.0 52 1 20 A SPARE
SPARE 20 A 1 49 0.0 0.0 50 1 20 A SPARE
SPARE 20 A 1 47 0.0 0.0 48 1 20 A SPARE
SPARE 20 A 1 45 0.0 0.0 46 1 20 A SPARE
SPARE 20 A 1 43 0.0 0.0 44 1 20 A SPARE
SPARE 20 A 1 41 0.0 0.1 42 1 20 A LTG RM 201-215
SPARE 20 A 1 39 0.0 0.0 40 1 20 A LTG RM 101-105
LTG RM 200C,200D 20 A 1 37 0.0 0.6 38 1 20 A LTG CORRIDOR LEVEL 1
LTG LEVEL 3 - EMERGENCY 20 A 1 35 0.1 0.5 36 1 20 A MOTORIZED DOOR
LTG LEVEL 2 - EMERGENCY 20 A 1 33 0.2 0.2 34 1 20 A LTG CORRIDOR LEVEL 3
LTG LEVEL 1 - EMERGENCY 20 A 1 31 0.1 0.2 32 1 20 A LTG CORRIDOR LEVEL 2
REC STAIRS 20 A 1 29 0.7 0.7 30 1 20 A REC RM 111
REC RM 109 20 A 1 27 0.9 0.9 28 1 20 A REC RM 110
REC RM 108,109 20 A 1 25 1.1 0.2 26 1 20 A REC RM 214A
A REC RM 215 20 A 1 23 0.6 0.6 24 1 20 A REC RM 214 A
REC RM 211A 20 A 1 21 0.2 0.2 22 1 20 A REC RM 212A
A REC RM 211 20 A 1 19 0.5 0.5 20 1 20 A REC RM 212 A
REC RM 209A 20 A 1 17 0.2 0.2 18 1 20 A REC RM 210A
A REC RM 209 20 A 1 15 0.5 0.5 16 1 20 A REC RM 210 A
A REC RM 207 20 A 1 13 0.4 0.4 14 1 20 A REC RM 208 A
REC RM 205A 20 A 1 11 0.4 0.4 12 1 20 A REC RM 206A
A REC RM 205 20 A 1 9 0.4 0.4 10 1 20 A REC RM 206 A
REC RM 203A 20 A 1 7 0.2 0.2 8 1 20 A REC RM 204A
A REC RM 203 20 A 1 5 0.5 0.5 6 1 20 A REC RM 204 A
REC RM 201A 20 A 1 3 0.2 0.2 4 1 20 A REC RM 202A
A REC RM 201 20 A 1 1 0.5 0.5 2 1 20 A REC RM 202 A
DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION
Mounting: RECESSED Sections: 1
Wire: 3 AIC Rating: 10,000 A
Phase: 1 Main: MLO
Voltage: 120/240 Amp Rating: 100 A
Panelboard: 2.1
Other 0.0 kVA 0.0 kVA Spare 0.0 kVA 0.0 kVA Water Heating 0.0 kVA 0.0 kVA Electric Clothes Dryer 0.0 kVA 0.0 kVA Kitchen Equipment - Non-Dwelling Unit 0.0 kVA 0.0 kVA Lighting and Receptacles - Hotel 5.2 kVA 2.6 kVA Design Current: 36.7 A Elevator 0.0 kVA 0.0 kVA Design Load: 8.8 kVA Motor 0.0 kVA 0.0 kVA Noncoincident Loads 0.0 kVA 0.0 kVA Total Estimated Demand Current: 29.3 A Heating 0.0 kVA 0.0 kVA Total Connected Current: 39.9 A Cooling 0.0 kVA 0.0 kVA Total Estimated Demand Load: 7.0 kVA Lighting 0.3 kVA 0.4 kVA Total Connected Load: 9.6 kVA Receptacles 4.1 kVA 4.1 kVA Load Classification Connected Load Estimated Demand Panel Totals
-PROVIDE SPD AS SPECIFIED.
6.1 kVA 3.4 kVA
41 0.0 0.0 42 -- -- SPACE ONLY --
SPD 30 A 2
39 0.0 0.0 40 1 20 A SPARE
SPARE 20 A 1 37 0.0 0.0 38 1 20 A SPARE
SPARE 20 A 1 35 0.0 0.0 36 1 20 A SPARE
SPARE 20 A 1 33 0.0 0.0 34 1 20 A SPARE
SPARE 20 A 1 31 0.0 0.0 32 1 20 A SPARE
SPARE 20 A 1 29 0.0 0.0 30 1 20 A SPARE
DOOR OPEN ALARM CORRIDOR 20 A 1 27 1.0 0.0 28 1 20 A DOOR HOLD CORR 300
A REC CORRIDOR,RM 300C 20 A 1 25 0.5 0.0 26 1 20 A DOOR HOLD RM 200
REC RM 311A 20 A 1 23 0.2 0.2 24 1 20 A LTG RM 301-312
A REC RM 311 20 A 1 21 0.8 0.6 22 1 20 A REC RM 312A
REC RM 309A 20 A 1 19 0.2 0.4 20 1 20 A REC RM 312A
A REC RM 309 20 A 1 17 0.4 0.0 18 1 20 A REC RM 312 A
REC RM 307A 20 A 1 15 0.2 0.2 16 1 20 A REC RM 310 A
A REC RM 307 20 A 1 13 0.4 0.5 14 1 20 A REC RM 310 A
REC RM 305A 20 A 1 11 0.2 0.2 12 1 20 A REC RM 306 A
A REC RM 305 20 A 1 9 0.8 0.2 10 1 20 A REC RM 306 A
A REC RM 303 20 A 1 7 0.2 0.2 8 1 20 A REC RM 304 A
A REC RM 303 20 A 1 5 1.1 0.0 6 1 20 A REC RM 304 A
A REC RM 301 20 A 1 3 0.2 0.2 4 1 20 A REC RM 302A
A REC RM 301 20 A 1 1 0.4 0.3 2 1 20 A REC RM 302 A
DESCRIPTION RATING P CKT A B CKT P RATING DESCRIPTION
Mounting: RECESSED Sections: 1
Wire: 3 AIC Rating: 10,000 A
Phase: 1 Main: MLO
Voltage: 120/240 Amp Rating: 100 A
Panelboard: 3.1
PANEL '2.1' PANEL '3.1'
(BLANK) (BLANK)
D EXHAUST FAN EF-4 SHALL TURN 'ON' WITH B101A AND/OR B101B. EF-4 SHALL REMAIN ON AS LONG AS ONE OR BOTH OF THE SPACES, B101A AND
B101B, ARE IN USE. EF-4 SHALL TURN OFF WHEN B101A AND B101B ARE BOTH OFF.
C EXTERIOR EMERGENCY LUMINAIRES SHALL BE NORMALLY 'OFF' AND SHALL TURN 'ON' WITH LOSS OF NORMAL POWER OR WHEN THERE IS AN
AUXILIARY INPUT SIGNAL TO LIGHTING CONTROL PANEL FROM FIRE ALARM.
B LUMINAIRES CONTROLLED BY PHOTOCELL SHALL TURN 'ON' AT DUSK AND 'OFF' AT MIDNIGHT (OR AS DIRECTED BY THE OWNER). MANUAL OVERRIDE SWITCH LOCATED BEHIND THE LEVEL 1 RECEPTION DESK SHALL OVERRIDE FUNCTIONALITY FOR A MAXIMUM OF TWO HOURS.
A LUMINAIRES SHALL BE CONTROLLED BY MANUAL LOW VOLTAGE SWITCH LOCATED BEHIND LEVEL 1 RECEPTION DESK. ALL LUMINAIRES SHALL BE 'ON' WHEN THERE IS AUXILIARY INPUT SIGNAL TO LIGHTING CONTROL PANEL FROM FIRE ALARM REGARDLESS OF SWITCH POSITION.
SEQUENCE OF OPERATION*
20 SPARE - -
19 SPARE - -
18 SPARE - -
17 SPARE - -
16 SPARE - -
15 SPARE - -
14 SPARE - -
13 B101B B1.1-22 D
12 B101A B1.1-22 D
11 EF-4 B1.1-22 D
10 EXTERIOR EMERGENCY 2.1-33 C
9 EXTERIOR EMERGENCY 2.1-31 C
8 EXTERIOR EMERGENCY B2.1-2 C
7 EXTERIOR B2.2-15 B
6 EXTERIOR B2.2-13 B
5 EXTERIOR B2.2-11 B
4 EXTERIOR B2.2-9 B
3 CORRIDOR 3 2.1-34 A
2 CORRIDOR 2 2.1-32 A
1 CORRIDOR 1 2.1-38 A
AREA CIRCUIT NUMBER SOO*
LIGHTING CONTROL PANEL 'LCPB2'
E0.05
2 LIGHTING CONTROL PANEL SCHEMATIC
This document has been digitally signed and sealed by
William S. Phillips, PE
OR PE #94068
Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.
Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:01:03-04'00'
NOTES: 1. CONTRACTOR SHALL CONFIRM EXACT SIZE, LOCATION AND WIRING REQUIREMENTS OF ALL MECHANICAL EQUIPMENT PRIOR TO INSTALLATION.
2. CONTRACTOR SHALL REVIEW DIVISION 21, 22 & 23 DRAWINGS AND SPECIFICATION TO ENSURE LOCATIONS AND QUANTITIES ARE CORRECT.
3. SINGLE SPEED STARTERS SHALL INCLUDE AN HOA POSITION SWITCH, PILOT LIGHT, AND 120 VAC CONTROL CIRCUIT.
4. CONTROL PANELS ARE SHIPPED LOOSE AND REQUIRE FIELD WIRING BY DIVISION 26.
5. PCS EQUIPMENT REQUIRES A SINGLE SOURCE ELECTRICAL CONNECTION. ANY INTERLOCKING WIRING SHALL BE FURNISHED UNDER DIVISION 23.
6. ALL FIRE ALARM DEVICES WIRED BY DIVISION 28.
7. PROVIDE EMERGENCY SHUTDOWN FOR ALL BOILERS AT DOOR TO BOILER ROOM
8. PROVIDE 120 VOLT RECEPTACLE ON A DEDICATED CIRCUIT FOR ALL DDC PANELS. CONFIRM QUANTITIES AND LOCATIONS WITH DIVISION 23
(A) ABBREVIATIONS: E = DIVISION 26
M =DIVISION 23
O = THE CONTRACTOR OFFICER
K = KITCHEN CONTRACTOR
(B) STARTER TYPE: HOA = HAND-OFF-AUTO SWITCH
MS = MANUAL STARTER
CO = COMBINATION STARTER (HOA)
CO2 = 2-SPEED COMBINATION STARTER
VFD = VARIABLE FREQUENCY DRIVE
MRR = MOTOR RATED RELAY (24 VAC COIL AND MS)
PCS = PACKAGED CONTROL SYSTEM
(C) CONTROL TYPE: BA = BUILDING AUTOMATION SYSTEM
PCS = PACKAGED CONTROL SYSTEM
ES = END SWITCH
LT = LINE VOLTAGE THERMOSTAT
FS = FLOW SWITCH
GS = GAS SENSOR
H = HUMIDITY SENSOR
I = INTERLOCK
LS = LEVEL SWITCH
PS = PRESSURE SWITCH
TC = TIME CLOCK
(C) CONTROL TYPE: T = THERMOSTAT
VS = VARIABLE SPEED SWITCH
WS = WALL SWITCH
RT = REVERSE ACTING THERMOSTAT
FCCF = FIREFIGHTERS CENTRAL
CONTROL FACILITY
FA = FIRE ALARM SYSTEM
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:5
:4
P
M C
U s e rs
\p d a v is
\D o c u m e n ts \O
R C
A
M E
P -C e n tr a l_ p d a v is
.r v t
SM
MJL
CvB, WSP
09/13/19
ELECTRICAL SCHEDULES
E0.06 194 211
CONSTRUCTION DOCUMENTS
E .0
M
J L
MECHANICAL EQUIPMENT SCHEDULE
MECH. EQ. TAG
SYSTEM
DESCRIPTION LOCATION COUNT POWER FLA
SYSTEM
VOLTAGE MOCP POLES PANEL
CIRCUIT
NUMBER CONDUCTORS REMARKS
EF-2 EXAUST FAN BATHROOM
B204A
1 0.3 kVA 4.4 A 120 V 20.0 A 1 B2.1 4 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND INTERLOCKED WITH WASHROOM LIGHT SWITCH. REFER TO DETAIL 3/E6.01
EF-3 EXAUST FAN BATHROOM
B204B
1 0.3 kVA 4.4 A 120 V 20.0 A 1 B2.1 6 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND INTERLOCKED WITH WASHROOM LIGHT SWITCH. REFER TO DETAIL 3/E6.01
EF-4 EXAUST FAN BATHROOM
B101A/B101B
1 0.7 kVA 5.8 A 120 V 20.0 A 1 B1.1 22 3/4" C WITH 2 - #10 AWG + #12 AWG GROUND CONTROLLED THROUGH LIGHTING CONTROL PANEL. REFER TO RELAY-BASED LIGHTING
CONTROL PANEL SCHEDULE ON SHEET E0.05 FOR SEQUENCE OF OPERATION.
EF-5 EXAUST FAN BATHROOM
206A
1 0.3 kVA 4.0 A 120 V 20.0 A 1 2.1 12 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND INTERLOCKED WITH WASHROOM LIGHT SWITCH. REFER TO DETAIL 3/E6.01
EF-6 EXAUST FAN BATHROOM
205A
1 0.3 kVA 4.0 A 120 V 20.0 A 1 2.1 11 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND INTERLOCKED WITH WASHROOM LIGHT SWITCH. REFER TO DETAIL 3/E6.01
EF-7 EXAUST FAN ELEVATOR
MACHINE RM
1 0.3 kVA 4.4 A 120 V 20.0 A 1 B2.1 20 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND
EF-8 EXAUST FAN LAUNDRY
B209B
1 0.3 kVA 4.4 A 120 V 20.0 A 1 B2.1 22 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND
EXISTING TO-REMAIN
FAN COIL
FAN COIL SERVICE
ENTRY B209
1 4.0 kVA 0.0 A 240 V 40.0 A 2 B2.2 34,36 3/4" C WITH 2 - #8 AWG + #10 AWG GROUND
EXISTING TO-REMAIN
FAN COIL
FAN COIL STAFF
DINING B208
1 4.0 kVA 0.0 A 240 V 40.0 A 2 FVDP 5,7 3/4" C WITH 2 - #8 AWG + #10 AWG GROUND
EXISTING TO-REMAIN
HOOD FAN
HOOD FAN STAFF
KITCHEN
B208B
1 0.5 kVA 4.2 A 120 V 20.0 A 1 B2.2 33 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND
EXISTING TO-REMAIN
SUPPLY AIR
SUPPLY FAN STAFF
KITCHEN
B208B
1 0.5 kVA 4.2 A 120 V 20.0 A 1 B2.2 39 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND
EXISTING-TO-REMAIN
FAN COIL
FAN COIL COFFEE
SHOP
B104/GIFT
SHOP B101
2 0.5 kVA 4.2 A 120 V 20.0 A 1 FVDP 12 3/4" C WITH 2 - #12 AWG + #12 AWG GROUND
KEF-1 EXAUST FAN KITCHEN
B103
1 6.4 kVA 31.0 A 240 V 60.0 A 2 FVDP 2,4 1" C WITH 2 - #8 AWG + #10 AWG GROUND
P-1 HOT WATER
PUMP
MECHANICAL
ROOM B301
1 2.8 kVA 15.0 A 240 V 20.0 A 2 B3.1 1,3 3/4" C WITH 2 - #8 AWG + #10 AWG GROUND
P-2 HOT WATER
PUMP
MECHANICAL
ROOM B301
1 2.8 kVA 15.0 A 240 V 20.0 A 2 B3.1 2,4 3/4" C WITH 2 - #8 AWG + #10 AWG GROUND
P-3 HOT WATER
PUMP
MECHANICAL
ROOM B301
1 1.8 kVA 20.0 A 120 V 25.0 A 1 B3.1 5 3/4" C WITH 2 - #8 AWG + #10 AWG GROUND
P-4 HOT WATER
PUMP
MECHANICAL
ROOM B301
1 1.8 kVA 20.0 A 120 V 25.0 A 1 B3.1 6 3/4" C WITH 2 - #8 AWG + #10 AWG GROUND
SP-1 ELEVATOR
SUMP
ELEVATOR
PIT
1 2.4 kVA 20.0 A 120 V 40.0 A 1 B2.3 6 3/4" C WITH 2 - #10 AWG + #10 AWG GROUND
MECH. EQ. TAG STARTER - TYPE
START -
SUPPLIED BY
STARTER -
INSTALLED BY
STARTER -
WIRED BY
DISCONNECT -
SUPPLIED BY
DISCONNECT -
INSTALLED BY
DISCONNECT -
WIRED BY
CONTROLS -
TYPE
CONTROLS -
SUPPLIED BY
CONTROLS -
INSTALLED BY CONTROLS - WIRED BY
EF-2 MS E E E E E E WS E E E
EF-3 MS E E E E E E WS E E E
EF-4 MS E E E E E E WS E E E
EF-5 MS E E E E E E WS E E E
EF-6 MS E E E E E E WS E E E
EF-7 MS E E E E E E LT E E E
EF-8 MS E E E E E E WS E E E
EXISTING TO-REMAIN FAN COIL MS EXISTING E E EXISTING E E BA M M M
EXISTING TO-REMAIN FAN COIL MS EXISTING E E EXISTING E E BA M M M
EXISTING TO-REMAIN HOOD FAN MS EXISTING E E EXISTING E E BA M M M
EXISTING TO-REMAIN SUPPLY AIR MS EXISTING E E EXISTING E E BA M M M
EXISTING-TO-REMAIN FAN COIL MS EXISTING E E EXISTING E E BA M M M
KEF-1 MS EXISTING E E EXISTING E E WS M M M
P-1 CO M E E E E E BA M M M
P-2 CO M E E E E E BA M M M
P-3 CO M E E E E E BA M M M
P-4 CO M E E E E E BA M M M
SP-1 CO M E E E E E LS M M E
This document has been digitally signed and sealed by
William S. Phillips, PE
OR PE #94068
Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.
Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:00:54-04'00'
SHEET NOTES
1. MATCH EXISTING LUMINAIRE MOUNTING HEIGHTS.
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:5
:4
P
M C
U s e rs
\p d a v is
\D o c u m e n ts \O
R C
A
M E
P -C e n tr a l_ p d a v is
.r v t
SM
MJL
CvB, WSP
09/13/19
ELECTRICAL SCHEDULES
E0.07 195 211
CONSTRUCTION DOCUMENTS
E .0
M
J L
LUMINAIRE SCHEDULE
TAG DESCRIPTION MANUFACTURER VOLTAGE
LAMP
TYPE POWER
INITIAL
ILLUMINANCE
INITIAL COLOR
TEMPERATURE REMARKS
WALL OR CEILING MOUNTED PLASTIC EDGE LIT EXIT SIGN WITH INTEGRAL BATTERY
BACK-UP, SELF-DIAGNOSTICS, AND CLEAR LETTERS ON GREEN BACKGROUND
LITHONIA PRECISE LRP-BZ-GC-120/240-ELN SERIES;
SURE-LITES EUX SERIES;
EMERGI-LITE PRESTIGE EDGE-LIT SERIES OR APPROVED
EQUAL
120 V LED 0 lm LUMINAIRE WITH GREEN LETTERS SHALL COMPLY WITH IBC-2015 SECTION 1013.6. CONTRACTOR SHALL CONFIRM COLOR WITH SERVING FIRE DEPARTMENT. PROVIDE DIRECTIONAL INDICATORS AS SHOWN ON
PLANS. PROVIDE GMR (GREEN MIRROR) FOR DOUBLE-FACE EXIT SIGNS AS SHOWN ON PLANS.
H1 EXISTING PADDLE FAN/LIGHT 120 V LED 10 W 800 lm 3000 K RETROFIT WITH NEW LED - SATCO 9.8A19/OMNI/220/LED/30K OR APPROVED EQUAL. 1 LAMP PER FIXTURE.
H2 EXISTING PENDANT 120 V LED 15 W 1600 lm 3000 K RETROFIT WITH NEW LED SCREW-IN LAMPS WITH EDISON BASE - SATCO 15A19/LED/3000K/1600L/120/D OR
APPROVED EQUAL. 1 LAMP PER FIXTURE.
H3 EXISTING INTERIOR WALL SCONCE 120 V LED 8 W 800 lm 3000 K RELAMP WITH LED EQUIVALENT - CLEAR LED FILAMENT CHANDELIER BULB, FLAME TIP, 4 WATT, 2700K. 1
LAMP PER FIXTURE.
H4 EXISTING EXTERIOR WALL SCONCE 120 V LED 10 W 800 lm 3000 K RELAMP WITH LED EQUIVALENT - SATCO 9.8A19/OMNI/220/LED/30K OR APPROVED EQUAL. 1 LAMP PER
FIXTURE.
H5 EXISTING LINEAR 120 V LED 17 W 2000 lm 3000 K RELAMP WITH LED EQUIVALENT - PHILIPS 9290012811 OR APPROVED EQUAL. 4 4' LONG T8 LAMPS PER
FIXTURE.
H6 EXISTING TRACK LIGHT 120 V LED 6 W 500 lm 3000 K RETROFIT WITH NEW LED SCREW-IN LAMPS WITH EDISON BASE - SATCO 9.8A19/OMNI/220/LED/30K OR
APPROVED EQUAL. 1 LAMP PER FIXTURE.
H7 EXISTING BATHROOM MIRROR LIGHT 120 V LED 10 W 800 lm 3000 K RETROFIT WITH NEW LED - SATCO 9.8A19/OMNI/220/LED/30K OR APPROVED EQUAL. 1 LAMP PER FIXTURE.
H8 EXISTING SURFACE DOWNLIGHT 120 V LED 10 W 800 lm 3000 K RETROFIT WITH NEW LED - SATCO 9.8A19/OMNI/220/LED/30K OR APPROVED EQUAL. 1 LAMP PER FIXTURE.
H9 EXISTING 8' LINEAR 120 V LED 17 W 2000 lm 3000 K RELAMP WITH LED EQUIVALENT - PHILIPS 9290012811 OR APPROVED EQUAL. PROVIDE NEW ACRYLIC SHIELDING COVER AT ANY FIXTURES WITH EXPOSED LAMPS. 4 8' LONG T8 LAMPS PER FIXTURE.
H10 EXISTING INTERIOR SURFACE DOWNLIGHT 120 V LED 10 W 800 lm 3000 K RETROFIT WITH NEW LED EQUVALENT - SATCO 9.8A19/OMNI/220/LED/30K OR APPROVED EQUAL. 1 LAMP
PER FIXTURE.
H11 EXISTING EXTERIOR DOWNLIGHT 120 V LED 10 W 800 lm 3000 K RETROFIT WITH NEW LED EQUVALENT - SATCO 9.8A19/OMNI/220/LED/30K OR APPROVED EQUAL. 1 LAMP
PER FIXTURE.
L1 SUSPENDED DIRECT FIXTURE WITH FROSTED LENSE, WHITE FINISH CORELITE HUGO SERIES;
DAY-BRITE FLUXSTREAM STRIP SERIES;
PHILIPS SMARTBRIGHT SUSPENSION SERIES
120 V LED 23 W 3000 lm 3000 K
L2 WALL SCONCE WITH DOMED TURTLE SHADE, OPAL, WITH POLISHED NICKEL CANOPY. SCHOOLHOUSE ELECTRIC OTIS 2.25" SCONCE SERIES 120 V LED 8 W 800 lm 3000 K PROVIDE MEDIUM BASE, LED LAMP
L3 PENDANT LAMP, WHITE BLOWN GLASS, 12" LONG SUSPENSION CABLE FABBIAN - AEROSTAT 120 V LED 17 W 1800 lm 3000 K
L4 CUSTOM LIGHT FIXTURE TO MATCH EXISTING LUMINAIRE TYPE H10 CUSTOM FIXTURE. SEE DETAIL 5/A8.11 120 V LED 8 W 800 lm 3000 K PROVIDE MEDIUM BASE, LED LAMP
L5 CUSTOM LIGHT FIXTURE TO MATCH EXISTING LUMINAIRE TYPE H4 CUSTOM FIXTURE. SEE DETAIL 5/A8.11 120 V LED 8 W 800 lm 3000 K PROVIDE MEDIUM BASE, LED LAMP
L6 4' LONG LINEAR SURFACE MOUNT, EXTRUDED ALUMINUM HOUSING, DIE-CAST
ALUMINUM END PLATES, ELECTROSTICALLY APPLIED POLYESTER POWDER COAT
WHITE PAINT FINISH. FROSTED LENS.
CORELITE HGL-HUGO LINEAR DIRECT SERIES;
DAY-BRITE FLUXSTREAM STRIP SERIES;
COOPER INDUSTRIES SNLED SERIES OR APPROVED EQUAL
120 V LED 23 W 3000 lm 3000 K
L7 SURFACE MOUNT WITH DRUM SHADE, GLASS, MATTE BRONZE FINISH SCHOOLHOUSE ELECTRIC OTIS 4" 120 V LED 8 W 800 lm 3000 K PROVIDE MEDIUM BASE, LED LAMP
L8 SURFACE MOUNT WITH DRUM GLASS SHADE, OPAL GLASS, POLISHED NICKEL FINISH SCHOOLHOUSE ELECTRIC OTIS 4" 120 V LED 8 W 800 lm 3000 K
L9 SURFACE MOUNT WITH JAR GLASS SHADE, OPAL GLASS, MATTE BRONZE FINISH SCHOOLHOUSE ELECTRIC OTIS 4" 120 V LED 8 W 800 lm 3000 K
L10 WALL MOUNTED ADJUSTABLE ACCENT FLOOD WITH ONE HEAD AND BRONZE FINISH LITHONIA WST LED-P2-27K-*-120-E20WC-DDBTXD 120 V LED 25 W 3000 lm 3000 K
RM1 WHITE PATHWAY FLOOD WITH TWO HEADS WITH 5.4 WATT LINEAR PATTERN LAMPS
AND SELF-DIAGNOSTICS
LITHONIA ELMLT-*-LP06VS-LTP-HO;
EMERGI-LITE EL-2RHL SERIES;
SURE-LITES SEL17 SERIES OR APPROVED EQUAL
120 V LED 5 W 1000 lm 3200 K
RM2 COMPACT, CONCEALED WHITE PATHWAY FLOOD WITH TWO HEADS C/W SELF
CONTAINED BATTERY CAPABLE OR OPERATING 90 MIN MINIMUM
CONCEALITE F5000-LED8-90-SD-RB-NC-CF;
EMERGI-LITE REVELATION BATTERY SERIES;
MULE-LIGHTING COVERT SERIES
120 V LED 8 W 1000 lm 3200 K CUSTOM FINISH TO MATCH ADJACENT WALL SURFACE.
TAG DESCRIPTION Image
H9 EXISTING 8' LINEAR
H10 EXISTING INTERIOR SURFACE DOWNLIGHT
TAG DESCRIPTION Image
H4 EXISTING EXTERIOR WALL SCONCE
H5 EXISTING LINEAR
H7 EXISTING BATHROOM MIRROR LIGHT
H8 EXISTING SURFACE DOWNLIGHT
TAG DESCRIPTION Image
H1 EXISTING PADDLE FAN/LIGHT
H2 EXISTING PENDANT
H3 EXISTING INTERIOR WALL SCONCE
This document has been digitally signed and sealed by
William S. Phillips, PE
OR PE #94068
Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.
Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:00:48-04'00'
ALL NEW EQUIPMENT AND OVER CURRENT DEVICES SHALL
EXCEED THE SHORT CIRCUIT INTERRUPTING CAPACITY
INDICATED ON THE SINGLE LINE DIAGRAM.
CONRACTOR SHALL PROVIDE THE FOLLOWING:
• REMOVE THE EXISTING SECONDARY CONDUCTORS
FROM THE EXISTING-TO-REMAIN SECONDARY
DUCTBANK.
• INTERCEPT EXISTING SERVICE ENTRANCE CONDUIT
DOWNSTREAM OF THE EXISTING METERING CABINET.
PROVIDE AND INSTALL CONDUIT TO BRING EXISTING
PATHWAYS TO THE NEW LOCATION OF THE MAIN
DISTRIBUTION PANEL (MDP).
• PROVIDE NEW SERVICE ENTRANCE EQUIPMENT AS
INDICATED HEREIN.
REPLACE EXISTING MANUAL TRANSFER SWITCH WITH NEW,
MATCHING AMPERAGE, VOLTAGE AND SHORT CIRCUIT
INTERRUPTING RATING AS INDICATED ON THE SINGLE LINE
DIAGRAM.
GENERAL NOTES
1.
2.
3.
ELECTRICAL FEEDER SCHEDULE
PRIMARY
NUMBER
SECONDARY LETTER
A (CU, 1-PHASE, 2-WIRE)
2-#12 AWG 3/4" 4-#12 AWG 1-#12 AWG3/4"
2-#10 AWG 3/4" 4-#10 AWG 1-#10 AWG3/4"
2-#8 AWG 3/4" 4-#8 AWG 1-#10 AWG1"
2-#6 AWG 3/4" 4-#6 AWG 1-#8 AWG1"
2-#4 AWG 1" 4-#4 AWG 1-#8 AWG1"
2-#3 AWG 1" 4-#3 AWG 1-#6 AWG1-1/4"
2-#2 AWG 1" 4-#2 AWG 1-#6 AWG1-1/4"
2-#1 AWG 1-1/4" 4-#1 AWG 1-#6 AWG1-1/2"
2-1/0 AWG 1-1/4" 4-1/0 AWG 1-#6 AWG2"
2-2/0 AWG 1-1/2" 4-2/0 AWG 1-#6 AWG2"
2-3/0 AWG 1-1/2" 4-3/0 AWG 1-#4 AWG2"
2-4/0 AWG 2" 4-4/0 AWG 1-#4 AWG2-1/2"
2-250 MCM 2" 4-250 MCM 1-#4 AWG3"
2-300 MCM 2-1/2" 4-300 MCM 1-#4 AWG3"
2-350 MCM 2-1/2" 4-350 MCM 1-#3 AWG3"
2-400 MCM 2-1/2" 4-400 MCM 1-#3 AWG3"
2-500 MCM 3" 4-500 MCM 1-#3 AWG3-1/2"
2-600 MCM 3" 4-600 MCM 1-#2 AWG4"
2-750 MCM 3-1/2" 4-750 MCM 1-#2 AWG4"
2-1000 MCM 4" 4-1000 MCM 1-#1 AWG4"
1-#10 AWG
1-#8 AWG
1-#8 AWG
1-#6 AWG
1-#6 AWG
1-#6 AWG
1-#4 AWG
1-#4 AWG
1-#4 AWG
1-#3 AWG
1-#3 AWG
1-#2 AWG
1-#1 AWG
1-#1 AWG
1-#1/0 AWG
1-#1/0 AWG
1-#1/0 AWG
1-#2/0 AWG
1-#2/0 AWG
1-#3/0 AWG
(2 RUNS)
1-#8 AWG
1-#6 AWG
1-#6 AWG
1-#4 AWG
1-#3 AWG
1-#3 AWG
1-#2 AWG
1-#1 AWG
1-#1 AWG
1-#1/0 AWG
1-#1/0 AWG
1-#2/0 AWG
1-#3/0 AWG
1-#3/0 AWG
1-#4/0 AWG
1-#4/0 AWG
1-#4/0 AWG
1-#250 MCM
1-#250 MCM
1-#350 MCM
PARALLEL FEEDER
EQUIPMENT
GROUND (CU)
SINGLE FEEDER
EQUIPMENT
GROUND (CU)
(4 RUNS)(1 RUN)CONDUCTORS CONDUIT
B (CU, 1-PHASE, 3-WIRE)
3-#12 AWG 3/4"
3-#10 AWG 3/4"
3-#8 AWG 3/4"
3-#6 AWG 1"
3-#4 AWG 1"
3-#3 AWG 1-1/4"
3-#2 AWG 1-1/4"
3-#1 AWG 1-1/2"
3-1/0 AWG 1-1/2"
3-2/0 AWG 2"
3-3/0 AWG 2"
3-4/0 AWG 2"
3-250 MCM 2-1/2"
3-300 MCM 2-1/2"
3-350 MCM 3"
3-400 MCM 3"
3-500 MCM 3-1/2"
3-600 MCM 3-1/2"
3-750 MCM 4"
3-1000 MCM 4"
CONDUCTORS CONDUIT
C (CU, 3-PHASE, 4-WIRE)
CONDUCTORS CONDUIT
NO SCALE
SHEET NOTES
EXISTING TO REMAIN 3" CONDUIT CONTAINS 2 SETS OF 3 #350 MCM CU CONDUCTORS.
PROVIDE CIRCUIT FOR COORDINATION OF FIRE ALARM AND ELEVATOR SHUT DOWN IN
ACCORDANCE WITH DETAIL 3/E0.08.
PROVIDE TWO NEW 2" CONDUITS FOR NEW PARALLEL SETS OF SERVICE CONDUCTORS.
EXISTING UTILITY COMPANY CT AND METER.
NEW UTILITY COMPANY CT AND METER.
OWNER METER.
SHUNT TRIP CIRCUIT BREAKER
FOR ELEVATOR. REFER TO PANEL
SCHEDULE
M
CONTACTS SHALL CLOSE ON
ALARM ACTIVATE
+SUPERVISED 24 VDC FROM FACP
RELAY SHALL CLOSE UPON FLOW
OF WATER INTO ELEVATOR SHAFT
OR MACHINE ROOM
R
SEND SIGNAL TO FACP UPON LOSS
OF ELEVATOR SHUNT TRIP
CONTROL POWER
ADDRESSABLE RELAY MODULE
(TYPICAL)
SUPERVISED 24V DC FROM FACP
R
PANEL B2.2
11.6 kAIC
UTILITY
PANEL B1.1
7.8 kAIC
PANEL B2.3
11.6 kAIC
PANEL B2.1
9.3 kAIC
PANEL 3.1
7.8 kAIC
M
(ELEVATOR)
25 HP
EXISTING TO REMAIN 2 x 3 - #350 kcmil CU CONDUCTORS
M
7B7B 7B 7B
8C
STATIC PHASE
CONVERTER
9B
MDP
100/3/100
PANEL B3.1
13.9 kAIC
7B
PANEL 2.1
7.8 kAIC
7B7B
200/2/150
8C
2 x
EXISTING TO REMAIN
PAD-MOUNTED UTILITY
SERVICE TRANSFORMER
UTILITY
2 x 3 - #4/0 kcmil XHHW CU CONDUCTORS
IN PARALLEL 2" CONDUITS
M
NEW PAD-MOUNTED
UTILITY SERVICE
TRANSFORMER
FVDP
OR
12B1 x
17.4 kAIC 16.5 kAIC
SPD
600A - 2P
100A - 2P 100A - 2P 100A - 2P 100A - 2P 100A - 2P 100A - 2P 150A - 2P
SPD
225A - 2P
120/240V 120/240V 400A - 2P
M
(DRYER)
20 KW
240 - 2P
M
(DRYER)
20 KW
240 - 2P
8B 8B
30A - 2P 30A - 2P
125A - 2P 125A - 2P
2B 2B
120/240V 1 Phase - 208V 3 Phase
M M
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:5
:5
P
M C
U s e rs
\p d a v is
\D o c u m e n ts \O
R C
A
M E
P -C e n tr a l_ p d a v is
.r v t
SM
MJL
CvB, WSP
09/13/19
ELECTRICAL ONE-LINE
DIAGRAMS
E0.08 196 211
CONSTRUCTION DOCUMENTS
E .0
M
J L
E0.08
3 TYPICAL ELEVATOR SHUT DOWN CIRCUIT
NO SCALE
E0.08
2 SINGLE LINE DIAGRAM
E0.08
4 TRANSFORMER PADVAULT DETAIL
This document has been digitally signed and sealed by
William S. Phillips, PE
OR PE #94068
Expires 06/30/2020 on 09/12/2019 using a Digital Signature and date. Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.
Digitally signed by William S. Phillips, PE Date: 2019.09.13 10:00:35-04'00'
MECHANICAL
B301
REMOVE (E)
MAIN SERVICE
DISCONNECTS
REMOVE (E)
LOAD CENTER
REMOVE (E)
PACKAGED
ENGINE
GENERATOR
REMOVE (E)
ABANDONED
GENERATOR
ON CONCRETE
PAD
REMOVE (E) AIR
COMPRESSOR
DISCONNECT SWITCH
REMOVE (E) SWITCH
MOUNTED ON FACE
OF BENCH
+ 54"
REMOVE (E) OUTLET
MOUNTED TO
UNDERSIDE OF BEAM.
REMOVE (E) OUTLET
MOUNTED TO
UNDERSIDE OF BEAM
CD
CC
NC
NB
NA
ND
SC
SB
SA
SE
CB
CA
SD
NA.4
NB.3
SA.3
SB.8
1.1
2.9
CD.9
SA.1
NA.1
6.1
3.2 5.8
REMOVE (E) SURFACE
MOUNT LIGHT
FIXTURE
REMOVE (E) LINEAR
LIGHT FIXTURE
REMOVE (E) SURFACE
MOUNT LIGHT
FIXTURE
REMOVE (E) SURFACE
MOUNT LIGHT
FIXTURE
EXISTING TO
REMAIN CURRENT
TRANSFORMER
ENCLOSUREEXISTING-TO-BE-
RELOCATED PACIFIC
POWER METER #35
979 833
REMOVE (E) LINEAR
LIGHT FIXTURE
SHEET NOTES
DISCONNECT EXISTING MAIN SERVICE DISCONNECTS.
REMOVE WIRING DOWN & UPSTREAM OF EQUIPMENT.
INCOMING SERVICE CONDUITS SHALL BE REUSED TO FEED
NEW SERVICE. REFER TO THE SINGLE LINE DIAGRAM FOR
WIRING REQUIREMENTS OF NEW EQUIPMENT.
0 4 84
SCALE OF FEET
SCALE I
SCALE I
DEMOLITION NOTES
1. DEMOLISH ENTIRE POWER DISTRIBUTION SYSTEM, UNLESS
OTHERWISE NOTED. REFER TO DEMOLITION DRAWINGS
FOR LOCATIONS OF POWER PANELS. CONTRACTOR SHALL
ASSUME ALL EXISTING PANELS ARE 200A, 120/240V, SINGLE
PHASE, FED FROM MAIN DISCONNECTS ON BASEMENT 3.
CONTRACTOR SHALL ASSUME 2in. CONDUIT SIZE, 3-#3/0
AWG COPPER CONDUCTORS, AND LONGEST RUN POSSIBLE,
PARALLEL TO MAIN WALLS.
2. REMOVE ALL CONDUIT AND WIRING ASSOCIATED WITH
EQUIPMENT OR DEVICES BEING DEMOLISHED. REMOVE ALL
CONDUIT AND WIRING BACK TO EXISTING PANELS. REFER
TO SECTION 01 35 91 FOR HISTORIC PRESERVATION
TREATMENT PROCEDURES.
3. COORDINATE WITH CONTRACTING OFFICER FOR PROPER
DISPOSAL PROCEDURE OF DECOMMISSIONED ELECTRICAL
EQUIPMENT.
4. REPLACE ALL CONDUIT AND WIRING ASSOCIATED WITH
EQUIPMENT THAT IS EXISTING TO REMAIN.
5. REMOVE ALL ABANDONED BRANCH CIRCUITS AND CABLES
IN ACCORDANCE WITH DEMOLITION NOTES HEREIN AND
SECTION 26 05 05.
6. REFURBISH EXISTING LUMINAIRES H1-H9. WORK SHALL BE
PERFORMED BY A UL LISTED FACILITY. REPLACE WIRING,
BASE (TO MATCH EXISTING) AND RETROFIT WITH NEW LED
LAMPS PRIOR TO REINSTALLATION. REFER TO LUMINAIRE
SCHEDULE FOR MORE INFORMATION.
7. REMOVE ALL EXTERIOR CONDUIT AND WIRING MOUNTED ON
EXTERIOR WALLS. REPLACE IN ACCORDANCE WITH
RENOVATION GENERAL NOTES.
8. HAZARDOUS MATERIALS ARE KNOWN TO BE LOCATED ON
THIS SITE. AN INVESTIGATION FOR HAZARDOUS MATERIALS
HAS BEEN PERFORMED BY VISTA ENVIRONMENTAL
CONSULTING. THE RESULTING REPORT, DATED DECEMBER
27, 2017, IS AVAILABLE UPON REQUEST FROM THE NATIONAL
PARK SERVICE. SEE SPECIFICATION 028100 FOR
HAZARDOUS MATERIAL REMEDIATION.
9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING
THAT PERSONNEL WITHIN THE WORK AREA ARE
PROTECTED FROM EXPOSURE TO ANY HAZARDOUS
MATERIALS ENCOUNTERED. IF MATERIALS ARE
DISCOVERED THAT MAY BE HAZARDOUS, THE CONTRACTOR
SHALL IMMEDIATELY NOTIFY THE CONTRACTING OFFICER
AND CEASE WORK UNTIL CONDITIONS CAN BE MAINTAINED
IN COMPLIANCE WITH ALL APPLICABLE REGULATIONS.
(APPLY TO SHEETS E1.B3,
E1.B2, E1.B1, E1.01, E1.02, E1.03)
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PK…