This is a pre-solicitation notice for a construction contract to correct life safety and critical deficiencies at the Oregon Caves Chateau. The National Park Service seeks to address fire suppression, egress, accessibility, and structural issues through upgrades such as installing code-compliant egress doors, a fire detection and suppression system, and replacing plumbing and electrical systems. Work also includes adding a three-story elevator, internal stairways, shear walls, and steel-framed balconies. The estimated price range is over $10 million, with an anticipated period of performance from April 2020 to September 2021. The pre-solicitation will be issued on or around October 21, 2019 via FedBizOpps, and small businesses are encouraged to participate as subcontractors.
Drawings - Plumbing
View the file
Other files
Show all 42
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M M
M M
S
T
P
VFD
PIPING DISTRIBUTION SYSTEMS SHALL BE BRACED TO COMPLY WITH THE FORCES AND DISPLACEMENTS PRESCRIBED IN ASCE 7-10 SECTION 13.3 AS DEFINED IN ASCE 7-10 SECTION 13.6.8, 13.6.7, 13.6.5.6.
COPIES OF THE BRACING SYSTEM INSTALLATION GUIDE OR MANUAL SHALL BE AVAILABLE ON THE JOBSITE PRIOR TO THE START OF HANGING AND BRACING OF THE PIPE, DUCTWORK, AND ELECTRICAL
DISTRIBUTION SYSTEM.
THE STRUCTURAL ENGINEER OF RECORD SHALL VERIFY THE ADEQUACY OF THE STRUCTURE TO
SUPPORT THE HANGER AND BRACE LOADS.
PIPING, DUCTWORK, AND ELECTRICAL DISTRIBUTION SYSTEM
BRACING NOTE
GENERAL NOTES
1. PROVIDE COMPLETE AND FULLY FUNCTIONAL PLUMBING SYSTEMS AS INDICATED IN THE
CONTRACT DOCUMENTS. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE
INTERNATIONAL PLUMBING CODE, INTERNATIONAL MECHANICAL CODE, INTERNATIONAL BUILDING CODE AND LOCAL RULES AND REGULATIONS, STATE AND LOCAL FIRE MARSHAL REGULATIONS, THE SAFETY ORDERS OF THE DIVISION OF INDUSTRIAL SAFETY, THE NATIONAL ELECTRIC CODE, THE
STANDARDS OF THE NATIONAL PARK SERVICE PROTECTION ASSOCIATION, AMERICAN GAS
ASSOCIATION, OCCUPATION AND SAFETY ACT, AMERICAN NATIONAL STANDARDS INSTITUTE,
AMERICAN SOCIETY OF MECHANICAL ENGINEERS, AMERICAN SOCIETY FOR TESTING AND
MATERIALS, INSTALLATION STANDARDS PUBLISHED BY THE INTERNATIONAL ASSOCIATION OF
PLUMBING AND MECHANICAL OFFICIALS (IAPMO) AND OTHER APPLICABLE LAWS, CODES, OR
REGULATIONS. NOTHING IN THESE CONTRACT DOCUMENTS SHALL BE CONSTRUED TO PERMIT
WORK NOT CONFORMING TO THESE CODES.
2. VERIFY LOCATION OF UTILITIES PRIOR TO PERFORMING WORK. COORDINATE ALL WORK WITH
OTHER TRADES.
3. PLUMBING FIXTURES SHALL HAVE MAXIMUM FLOW RATES AS INDICATED ON SCHEDULES.
4. SEE ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS, MOUNTING HEIGHTS AND COLOR OF
PLUMBING FIXTURES.
5. COORDINATE ALL CORING OF FLOORS AND WALLS WITH CONTRACTING OFFICER PRIOR TO START
OF WORK.
6. PIPING SHALL HAVE SUFFICIENT CLEARANCE FROM STRUCTURE TO ALLOW FOR EXPANSION AND CONTRACTION OF THE PIPING. NO PIPING SHALL TOUCH WOOD, CONCRETE, OTHER PIPING, ETC.
7. ALL EQUIPMENT, FIXTURES, ETC. SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS AND INSTRUCTIONS.
8. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, AND EQUIPMENT NECESSARY AND
PERFORM ALL REQUIRED TESTING OF ALL PIPING AND ACCESSORIES INSTALLED. ALL SUCH
PLUMBING INSTALLATIONS SHALL BE TESTED, REPAIRED, AND ADJUSTED TO THE SATISFACTION OF
THE CONTRACTING OFFICER AND ALL GOVERNING AUTHORITIES.
9. ALL VALVES, UNIONS, ETC. SHALL BE ETC. TO BE SAME SIZE AS LINE SIZE UNLESS OTHERWISE
NOTED ON DRAWINGS.
10. PROVIDE UNIONS AFTER EACH THREADED VALVE AND PRIOR TO EQUIPMENT CONNECTIONS.
11. FOLLOW THE GENERAL ARRANGEMENT INDICATED ON THE DRAWINGS AS CLOSELY AS POSSIBLE, THE CONTRACTOR SHALL COORDINATE WITH THE ARCHITECTURAL, STRUCTURAL, MECHANICAL, PLUMBING, ELECTRICAL AND ALL OTHER TRADES PRIOR TO INSTALLATION OF THE MATERIALS AND
EQUIPMENT TO VERIFY ADEQUATE SPACE AVAILABLE FOR INSTALLATION OF THE WORK SHOWN.
THE CONTRACTING OFFICER (CO) SHALL BE IMMEDIATELY NOTIFIED IF AN AREA OF CONFLICT
OCCURS BETWEEN TRADES.
12. SPECIFICATIONS ARE AN INTEGRAL PART OF THIS PROJECT. CONTRACTOR SHALL BE
RESPONSIBLE FOR COMPLYING WITH SPECIFICATION REQUIREMENTS.
13. ALL FIXTURES, FLOOR DRAINS, FLOOR SINKS, ETC. SHALL BE TRAPPED AND VENTED. PROVIDE
TRAP GAURD TO ALL FLOOR DRAINS, FLOOR SINKS, HUB DRAINS AND AS INDICATED ON THE
DRAWINGS. ALL TRAP GAURDS SHALL BE ACCESSIBLE AND PROVIDED WITH A 12"X12" ACCESS
PANEL (MINIMUM).
14. PROVIDE ALL PIPING, VALVES, FITTINGS AND OTHER APPURTENANCES FOR A COMPLETE AND
FULLY FUNCTIONAL SYSTEM.
15. PIPING TO BE SLOPED AS FOLLOWS UNLESS OTHERWISE NOTED:
A. SANITARY SEWER = 2%
B. SANITARY VENT (BELOW FLOOD RIM) = 1%
C. SANITARY VENT (ABOVE FLOOD RIM) = 0.25%
D. TRAP PRIMER = 1%
E. CONDENSATE = 1%
F. STORM DRAIN = 1%
16. VERIFY IN FIELD EXISTING CONDITIONS, SIZE AND EXACT LOCATION OF SERVICES PRIOR TO START
OF WORK.
17. THE CONSTRUCTION DOCUMENTS FOR THIS PROJECT WERE PREPARED BY THE DESIGN TEAM
USING 3-D MODELING SOFTWARE. USING THIS SOFTWARE BY THE DESIGN TEAM DOES NOT
RELIEVE THE CONTRACTOR FROM PERFORMING THE NECESSARY COORDINATION TO PROVIDE
COMPLETE, CODE COMPLIANT AND OPERATIONAL BUILDING SYSTEMS. THE PLANS AND SECTIONS
PROVIDED ARE NOT COMPLETE AND ARE TO BE CONSIDERED DIAGRAMMATIC ONLY. THE EXACT
LOCATION OF THE PIPING, DUCTWORK, ELECTRICAL AND SUPPORT COMPONENTS ARE TO BE
DETERMINED IN THE FIELD. ALL BUILDING SECTIONS AND DETAILS PROVIDED ARE FOR
INFORMATION ONLY AND DO NOT RELIEVE THE CONTRACTOR FROM PERFORMING FINAL
COORDINATION. CONTRACTOR IS RESPONSIBLE FOR COORDINATING WITH ALL OTHER TRADES.
18. SUBMIT FOR APPROVAL MANUFACTURER’S SUBMITTAL DATA ON ALL MATERIALS, EQUIPMENT, AND
DEVICES PER SPECIFICATIONS.
19. REFER TO ARCHITECTURAL FOR HISTORIC TREATMENT PROCEDURES FOR REMOVAL AND
INSTALLATION OF NEW WORK.
20. WE'VE ADDED THE VARIOUS BID OPTIONS TO COORDINATE WITH OUR SPECS AND CONTRACT PRICE SCHEDULE. PLEASE PROVIDE ENOUGH INFORMATION FOR THESE BID ITEMS TO PROVIDE AN
APPROPRIATE DOLLAR AMOUNT (IF NOT DONE SO ALREADY).
1. 2015 INTERNATIONAL BUILDING CODE
2. 2015 INTERNATIONAL ELECTRICAL CODE
3. 2015 INTERNATIONAL MECHANICAL CODE
4. 2015 INTERNATIONAL PLUMBING CODE
5. 2016 OREGON ENERGY CODE
6. 2015 INTERNATIONAL FIRE CODE
OREGON CODES
AND STANDARDS
PLUMBING ABBREVIATIONS
PLUMBING LEGEND
CW COLD WATER
HW HOT WATER SUPPLY
HWR HOT WATER RETURN
SAN SANITARY SEWER
SAN SANITARY SEWER (UNDERFLOOR)
V SANITARY VENT
G NATURAL GAS
SYMBOL
CD CONDENSATE DRAIN
TAG DESCRIPTION
RW RECYCLED WATER
CW
HW
HWR
SAN
SAN
V
G
CD
RW
SD STORM DRAINSD
OD OVERFLOW DRAINOD
ABAS ARCHITECTURAL BARRIERS ACCESSIBILITY
STANDARD
ABV ABOVE
AC ALTERNATING CURRENT
ACU AIR-CONDITIONING UNIT(S)
ADDL ADDITIONAL
ADJ ADJUSTABLE
AF ABOVE THE FLOOR
AFF ABOVE FINISHED FLOOR
AGA AMERICAN GAS ASSOCIATION
AHU AIR-HANDLING UNIT
AIR COND AIR CONDITION(-ING, -ED)
ALT ALTERNATE
AMB AMBIENT
AMP AMPERE (AMP, AMPS)
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
AP ACCESS PANEL
ARCH ARCHITECT, ARCHITECTURAL
ARF ABOVE RAISED FLOOR
ASC ABOVE SUSPENDED CEILING
ASHRAE AMERICAN SOCIETY OF HEATING,
REFRIGERATION AND AIR CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL
ENGINEERS
ASPE AMERICAN SOCIETY OF PLUMBING
ENGINEERS
ASTM AMERICAN SOCIETY FOR TESTING AND MAINTENACE
ATM ATMOSPHERE
AWS AMERICAN WELDING SOCIETY
AWWA AMERICAN WATER WORKS ASSOCIATION
B&S BELL AND SPIGOT
BDY BOUNDARY
BEL BELOW
BFP BACKFLOW PREVENTER
BHP BRAKE HORSEPOWER
BLDG BUILDING
BLR BOILER
BM BEAM
BOD BOTTOM OF DUCT
BOM BILL OF MATERIAL
BOP BOTTOM OF PIPE
BOT BOTTOM
BRF BELOW RAISED FLOOR
BSMT BASEMENT
BT BATHTUB
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNITS PER HOUR
BV BUTTERFLY VALVE
CAB CABINET
CAP CAPACITY
CB CATCH BASIN
CD CONDENSATE DRAIN
CF CUBIC FEET
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CISP CAST IRON SOIL/SEWER PIPE
CISPI CAST IRON SOIL PIPE INSTITUTE
CL CENTERLINE
CLG CEILING
CNTR CENTER
CO CLEANOUT
COEF COEFFICIENT
COL COLUMN
COM COMMON
CONC CONCRETE
CONN CONNECTION
COND CONDENS(-ER, -ING, -ATION)
CONST CONSTRUCTION
CONTR CONTRACTOR
CTR CENTER
CU COPPER (CHEMICAL ABBREVIATION)
CU FT CUBIC FEET
CU IN CUBIC INCH
CV CHECK VALVE
CW COLD WATER
CWP CIRCULATING WATER PUMP
D DEEP
DBL DOUBLE
DC DIRECT CURRENT
DCV DETECTOR CHECK VALVE
DEG DEGREE
DEMO DEMOLITION
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DFU DRAINAGE FIXTURE UNIT
DIA DIAMETER
DIM DIMENSION
DN DOWN
DP DEPTH OR DEEP
DS DOWNSPOUT
DWG DRAWING
DWV DRAIN, WASTE AND VENT
E EXISTING
EA EACH
EFF EFFICIENCY
ELEC ELECTRICAL
EMER EMERGENCY
ENCL ENCLOSURE
ENG ENGINEER
ENT ENTRANCE
EQ EQUAL
EST ESTIMATE
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EWT ENTERING WATER TEMPERATURE
EXP EXPOSED
EXT EXTINGUISH
F FAHRENHEIT
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FF FINISHED FLOOR
FFE FINISHED FLOOR ELEVATION
FG FINISH GRADE
FHY FIRE HYDRANT
FIXT FIXTURE
FL FLOOR
FND FOUNDATION
FP FIRE PROTECTION MAIN
FPM FEET PER MINUTE
FPS FEET PER SECOND
FR FIRE RISER
FS FLOOR SINK
FT FEET
FU FIXTURE UNIT
FURN FURNISH
FUT FUTURE
G GAS
GA GAGE OR GAUGE
GAL GALLON
GC GENERAL CONTRACTOR
GCO GRADE CLEANOUT
GND GROUND
GOVT GOVERNMENT
GP GALVANIZED PIPE
GPD GALLONS PER DAY
GPF GALLONS PER FLUSH GPM GALLONS PER MINUTE
GPH GALLONS PER HOUR
GPS GALLONS PER SECOND
GV GALVANIZED
GVA GATE VALVE
H HIGH
HB HOSE BIB
HD HEAD
HDR HEADER
HOR HORIZONTAL
HP HORSE POWER
HR HOUR
HRS HOURS
HT HEIGHT
HTG HEATING
HTR HEATER
HW HOT WATER
HWR HOT WATER RETURN
HZ HERTZ (CYCLES PER SECOND)
I IRON
ID INSIDE DIAMETER
IE INVERT ELEVATION
INC INCREASER, INCREASING
IN INCH
INCL INCLUDE
INCR INCREASE
INFO INFORMATION
INS INSULATION
INSP INSPECT
INSUL NSULATION
INT INTERIOR, INTERNAL
INV INVERT
IP IRON PIPE
IPS IRON PIPE SIZE
IW INDIRECT WASTE
JC JANITOR'S CLOSET
KF KITCHEN FIXTURE
KW KILOWATT
KWH KILOWATT HOUR
KVA KILOVOLT-AMPERE
KW KILOWATT
L LENGTH
LAT LATERAL
LAV LAVATORY
LBS POUNDS
LF LINEAR FEET
LG LENGTH
LH LEFT HAND
LPD LOW POINT DRAIN
MAX MAXIMUM
ME MECHANICAL ENGINEER
MECH MECHANICAL
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MS MOP SINK
MTR MOTOR
MWP MAXIMUM WORKING PRESSURE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NFWH NON-FREEZE WALL HYDRANT
NOM NOMINAL
N/A NOT APPLICABLE
NBS NATIONAL BUREAU OF STANDARDS
NC NOISE CRITERIA
NO, # NUMBER
NPS NOMINAL PIPE SIZE (ALSO CALLED IPS)
NTS NOT TO SCALE
OC ON CENTER
ODIA OUTSIDE DIAMETER
OD OVERFLOW DRAIN
OUT OUTLET
OZ OUNCE
P PITCH
PD PRESSURE DROP, OR DIFFERENCE
PDI PLUMBING DRAINAGE INSTITUTE
PE PROFESSIONAL ENGINEER
PERIM PERIMETER
PG PRESSURE GAUGE
PH PHASE (ELECTRICAL)
PIV POST INDICATOR VALVE
PL PROPERTY LINE
PLBG PLUMBING
POC POINT OF CONNECTION
PPM PARTS PER MILLION
PRESS PRESSURE
PRIM PRIMARY
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAUGE
PVC POLYVINYL CHLORIDE
PWR POWER
QT QUART
QTY QUANTITY
RAD RADIUS
RCP REFLECTED CEILING PLAN
RCVR RECEIVER
RD ROOF DRAIN
RECIRC RECIRCULATE
REF REFERENCE
REQD REQUIRED
RET RETURN
REV REVISION
RF ROOF
RH RIGHT HAND
RL ROOF LEADER
RM ROOM
RPBFP REDUCED PRESSURE BACKFLOW PREVENTER
RPM REVOLUTIONS PER MINUTE
RW RAW WATER
RWL RAIN WATER LEADER
SAD SEE ARCHITECTURAL DRAWING(S)
SMD SEE MECHANICAL DRAWING(S)
SSD SEE STRUCTURAL DRAWING(S)
SD STORM WATER
SK SINK
S&W SOIL & WASTE
SAN SANITARY
SCH SCHEDULE
SD STORM DRAIN
SEC SECOND
SECT SECTION
SERV SERVICE
SF SQUARE FOOT
SH SHOWER
SHT SHEET
SIM SIMILAR
SLV SLEEVE
SOV SHUTOFF VALVE
SP STANDPIPE
SP PRESSURE, STATIC
SPEC SPECIFICATION
SPM SPRINKLER MAIN
SS SERVICE SINK
STD STANDARD
STL STEEL
SUCT SUCTION
SV SAFETY RELIEF VALVE
SQ SQUARE
SQ FT SQUARE FEET
SS SERVICE SINK
ST SANITARY TAP
STD STANDARD
T TEE
T&P TEMPERATURE & PRESSURE
RELIEF VALVE
TD TRENCH DRAIN
TEMP TEMPERATURE
TLT TOILET
TYP TYPICAL
TAP TAP, TAPPED
TYP TYPICAL
UR URINAL
UON UNLESS OTHERWISE NOTED
V VENT
VT VOLT
VOL VOLUME
VAR VARIABLE
VB VALVE BOX
VEL VELOCITY
VERT VERTICAL
VLV VALVE
VOL VOLUME
VP VENT PIPE
VS VENT STACK
VTR VENT THROUGH ROOF
W WATT
W WASTE
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WCO WALL CLEANOUT
WFS WATER FLOW SWITCH
WH WATER HEATER
WM WATER METER
WS WATER STOP
WH WALL HYDRANT
WL WATER LEVEL
WP WEATHERPROOF
WSFU WATER SUPPLY FIXTURE UNIT
WT WEIGHT
% PERCENT
(E) EXISTING
(N) NEW
@ AT (THE RATE OF)
& AND
# NUMBER
P6.02
DETAIL DESIGNATION
SHEET NUMBER
CH
EQUIPMENT TYPE
NUMBER TYPE
REVISION CLOUD AND DELTA
PRESSURE REDUCING VALVE
PRESSURE REDUCING VALVE
GAS
2-WAY CONTROL VALVE,
2-POS
2-WAY CONTROL VALVE,
MODULATING
3-WAY CONTROL VALVE,
2-POS
3-WAY CONTROL VALVE,
MODULATING
BALL VALVE
BUTTERFLY VALVE
BUTTERFLY VALVE
W/OPERATOR
CHECK VALVE
CIRCUIT SETTER
DRAIN VALVE
FLOATING VALVE
NEEDLE VALVE
T&P RELIEF VALVE
THERMOSTATIC MIXING
VALVE
VALVE
GLOBE VALVE
GLOBE VALVE ANGLE
WYE STRAINER
WAY STRAINER WITH BLOW
OFF
GATE VALVE
GATE VALVE ANGLE
MANUAL AIR VALVE
COCK VALVE
SOLENOID VALVE
HYDRONIC FLOW METER
TEMP GUAGE
PRESSURE GUAGE
LIQUID FILLED
THERMOMETER
UNION
VFD
FLEX CONNECTOR
PETES PLUG
VACUUM BREAKER
POINT OF DISCONNECTION
POINT OF CONNECTION
END OF PIPE - CLEANOUT
END OF PIPE - FLOOR
CLEANOUT
END OF PIPE - WALL
CLEANOUT
2 WAY CLEANOUT CLEANOUT
VTR (VENT)
WMXX
BFP-XX
WHA
TP TRAP PRIMER
WATER HAMMER ARRESTOR
WATER METER
BACKFLOW PREVENTER
METER INLINE ACCESSORY
SEISMIC JOINT
CW-1
FD-1
GD-1
LAV-1
WC-1
MS-1
OD-1
PD-1
RD-1
UR-1
SH-1
REDUCER
MOTOR
AIR SEPARATOR
EXPANSION TANK
PUMP
SYMBOLS (PLANS) VALVES DIAGRAMS
FLOOR DRAIN
FLOOR DRAIN OR FLOOR SINK
FLOOR SINK
COMBINATION ROOF / OVERFLOW DRAIN
ROOF DRAIN
ROOF RECEPTOR
FLOOR CLEANOUT
WALL CLEANOUT
HOSE BIBB
LINE BREAK
PIPE CAP
END OF PIPE
TEMPERATURE SENSOR
FLEX CONNECTION
UNION
FLOW DIRECTION
DWV FITTING, 45° ELBOW
DWV FITTING, 90° ELBOW
DWV FITTING, 45° TEE
DWV FITTING, 90° TEE
PIPE DROP
PIPE BRANCH, TOP
PIPE BRANCH, BOTTOM
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:1 :0
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
PLUMBING COVER
P0.01 150 211
CONSTRUCTION DOCUMENTS
P .0
A
G
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and signature must be verified on any electronic copies.
CD
CC
NC
NB
NA
ND
SC
SB
SA
SE
CB
CA
SD
NA.4
NB.3
SA.3
SB.8
1.1
2.9
CD.9
SA.1 NA.1
6.1
3.2 5.8
MECHANICAL
B301
STAIRS
B300
(E) BOILER, SEE
MECHANICAL
(E) WATER HEATERS
0 4 84
SCALE OF FEET
SCALE I
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:1 :4
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
PLUMBING DEMO FLOOR
PLAN - BASEMENT 3P1.B3
151 211
CONSTRUCTION DOCUMENTS
P .B
A
G
P1.B3
1 PLUMBING DEMO FLOOR PLAN - BASEMENT 3
SHEET NOTES
1. EXISTING 4" SANITARY SEWER TO REMAIN TO POINT OF
CONNECTION OF NEW 4" SANITARY SEWER IN
CRAWLSPACE.
2. REMOVE EXISTING 3" AND 4" SANITARY SEWER LINES TO
POINT JUST INSIDE CRAWLSPACE AFTER EXISTING 4" LINE
PASSES THROUGH CONCRETE WALL.
3. COORDINATE WITH ARCHITECTURAL ON EXPANSION OF
EXISTING HOLE THROUGH CONCRETE WALL FROM
BASEMENT 3 INTO CRAWLSPACE.
GENERAL NOTES
A. DEMOLITION OF EXISTING DISTRIBUTION PIPE:
ASSUMPTIONS ARE AS FOLLOWS:
DEMO SPECIFIC PIPING AS INDICATED IN SHEET NOTES
EXISTING DWV TO REMAIN UNLESS OTHERWISE INDICATED
OR IS VISIBLY DAMAGED
IN ADDITION:
TWO VERTICAL RISERS - ONE FOR DOMESTIC HOT WATER
(DHW) AND ONE FOR DOMESTIC COLD WATER (DCW) -
1-1/2" GALVANIZED STEEL PIPE - APPROXIMATELY 8'-0" OF
EACH FOR A TOTAL OF 16'-0".
ALL ESTIMATED PIPE DEMO LENGTHS ARE APPROXIMATE
AS THERE WAS NOT ACCESS TO THE MAJORITY OF PIPING
AS THE HOTEL WAS STILL OCCUPIED AND DEMOLITION
WAS NOT ALLOWED - ESTIMATES ALSO INCLUDE A 10%
SAFETY FACTOR
BID OPTION E: REPLACEMENT OF PLUMBING PIPING AT BASEMENT 3
PLUMBING PIPING BID ALTERNATE: DEMO EXISTING DOMESTIC WATER PIPING
AS FOLLOWS: 80'-0" OF 1-1/2" DOMESTIC COLD WATER PIPING, 80'-0 OF 1-1/2"
DOMESTIC HOT WATER PIPING 60'-0" OF 3/4" DOMESTIC HOT WATER PIPING,
60'-0" OF 3/4" DOMESTIC COLD WATER PIPING, 60'-0" OF 1/2" DOMESTIC COLD
WATER PIPING AND 60'-0" OF 1/2" DOMESTIC HOT WATER PIPING.
ALL PIPING IS GALVANIZED STEEL UNLESS OTHERWISE INDICATED.
REPALCE WITH SAME SIZED NEW PIPING PER SPECIFIED MATERIALS.
BLDG.
TRUE
NORTH
.6
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
CD
CC
NC
NB
NA
ND
SC
SB
SA
SE
CB
CA
SD
NA.4
NB.3
SA.3
SB.8
1.1
2.9
CD.9
SA.1 NA.1
6.1
3.2 5.8
STORAGE
B211
LAUNDRY
B209B
RESTROOM
B210A
SERVICE ENTRY
B209
STAFF DINING
B208
ACCESSIBLE
STAFF BEDROOM
#3
B205
STAFF BEDROOM
#2
B206
STAFF BEDROOM
#1
B207
STAFF LOUNGE
B204
BATHROOM
B203A
STORAGE
B203
CORRIDOR
B201
WINE STOR
B202B
STORAGE
B202
STAIRS
B200
CLOSET
B207A
CLOSET
B206A
0 4 84
SCALE OF FEET
SCALE I
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:1 :3
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
PLUMBING DEMO FLOOR
PLAN - BASEMENT 2P1.B2
152 211
CONSTRUCTION DOCUMENTS
P .B
A
G
P1.B2
1 PLUMBING DEMO FLOOR PLAN - BASEMENT 2
SHEET NOTES
1. REMOVE EXISTING SHOWER, LAVATORY AND WATER
CLOSET, CAP ALL DWV, DCW AND DHW BELOW FLOOR
JOISTS IN CRAWLSPACE.
2. REMOVE EXISTING SINK AND SMALL DOMESTIC HOT
WATER HEATER BELOW. CAP EXISTING DHW, DWV, AND
DCW LINES.
3. REMOVE EXISTING 4" SANITARY SEWER LINE FROM POINT
OF PENETRATION FROM BASEMENT LEVEL 1 TO BELOW
FLOOR OF BASEMENT LEVEL 2.
4. REMOVE EXISTING UTILITY SINK AND WASHING MACHINE
DWV, DCW AND DHW IN THIS AREA. CAP SANITARY SEWER
BELOW SLAB FOR FUTURE CONNECTION(S). WASHING
MACHINES TO BE SAVED AND RELOCATED.
5. CHANNEL EXISTING CONCRETE SLAB FOR FUTURE 4"
SANITARY SEWER CONNECTION FROM RE-LOCATED
WASHING MACHINES AND TWO NEW UTILITY SINKS.
6. REMOVE EXISTING WATER CLOSET AND LAVATORY
CONTROLS. LAVATORY TO REMAIN AND HAVE NEW
CONTROLS INSTALLED. WATER CLOSET TO BE REPLACED.
7. PROVIDE TRENCH FOR NEW 2" SANITARY DRAIN LINE FROM
ELEVATOR SUMP PIT INTO CENTER SECTION OF BASEMENT
LEVEL 3.
8. PLUMBING RISERS NEED TO BE RELOCATED.
GENERAL NOTES
A. DEMOLITION OF EXISTING DISTRIBUTION PIPE:
ASSUMPTIONS ARE AS FOLLOWS:
DEMO SPECIFIC PIPING AS INDICATED IN SHEET NOTES
EXISTING DWV TO REMAIN UNLESS OTHERWISE
INDICATED OR IS VISIBLY DAMAGED
IN ADDITION:
TWO VERTICAL RISERS PER WING - ONE FOR DOMESTIC
HOT WATER (DHW) AND ONE FOR DOMESTIC COLD
WATER (DCW) - 1-1/2" GALVANIZED STEEL PIPE -
APPROXIMATELY 25'-0" OF EACH FOR A TOTAL OF 50'-0".
FIXTURE CONNECTIONS - 6'-0" EACH OF 1/2"
GALVANIZED STEEL PIPE PER FIXTURE FOR DHW AND
DCW EXCEPT FOR WATER CLOSETS ONLY DCW
ADDITIONAL DEMO OF PIPING AS FOLLOWS:
INCOMING DOMESTIC COLD WATER SERVICE - 80'-0" OF
1-1/2" GALVANIZED STEEL PIPE
EXISTING PLUMBING SERVING KITCHEN AREA - DWV
PIPING TO REMAIN UNLESS VISIBLY DAMAGED. 60'-0" OF
1" DOMESTIC COLD WATER PIPING, 60'-0" OF 1"
DOMESTIC HOT WATER PIPING, 40'-0" OF 3/4" DOMESTIC
COLD WATER PIPING, 40'-0" OF 3/4" DOMESTIC HOT
WATER PIPING, 70'-0" OF 1/2" DOMESTIC COLD WATER
PIPING AND 70'-0" OF 1/2" DOMESTIC HOT WATER PIPING
ALL ESTIMATED PIPE DEMO LENGTHS ARE
APPROXIMATE AS THERE WAS NOT ACCESS TO THE
MAJORITY OF PIPING AS THE HOTEL WAS STILL
OCCUPIED AND DEMOLITION WAS NOT ALLOWED -
ESTIMATES ALSO INCLUDE A 10% SAFETY FACTOR
BLDG.
TRUE
NORTH
.6
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
UP
UP
UP
CD
CC
NC
NB
NA
ND
SC
SB
SA
SE
CB
CA
SD
NA.4
NB.3
SA.3
SB.8
1.1
2.9
CD.9
SA.1 NA.1
6.1
3.2 5.8
COFFEE SHOP
B104
KITCHEN
B103
WALK-IN REFRIG.
B103A
DINING ROOM
B102
STORAGE
B100A
GIFT SHOP
B101
STAIRS
B100
0 4 84
SCALE OF FEET
SCALE I
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:1 :2
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
PLUMBING DEMO FLOOR
PLAN - BASEMENT 1P1.B1
153 211
CONSTRUCTION DOCUMENTS
P .B
A
G
P1.B1
1 PLUMBING DEMO FLOOR PLAN - BASEMENT 1
SHEET NOTES
1. REMOVE EXISTING WATER CLOSETS, URINALS AND
LAVATORYS. CAP EXISTING DWV, DCW AND DHW BELOW
FLOOR AT CONNECTION TO MAIN(S).
2. REMOVE EXISTING BAR SINK. CAP EXISTING DWV, DCW
AND DHW BELOW FLOOR AT CONNECTION TO MAIN(S).
GENERAL NOTES
A. DEMOLITION OF EXISTING DISTRIBUTION PIPE:
ASSUMPTIONS ARE AS FOLLOWS:
TWO VERTICAL RISERS - ONE FOR DOMESTIC HOT WATER
(DHW) AND ONE FOR DOMESTIC COLD WATER (DCW) -
1-1/2" GALVANIZED STEEL PIPE - APPROXIMATELY 15'-0" OF
EACH.
HORIZONTAL MAIN DISTRIBUTION PIPE - TWO EACH OF
DHW AND DCW - 1" GALVANIZED PIPE 30'-0" LONG FOR A
TOTAL OF 120'-0"
HORIZONTAL TERTIARY DISTRIBUTION PIPE - FOUR EACH
OF DHW AND DCW - 3/4" GALVANIZED PIPE 15'-0" LONG FOR
A TOTAL OF 120'-0"
FIXTURE CONNECTIONS - 6'-0" EACH OF 1/2" GALVANIZED
STEEL PIPE PER FIXTURE FOR DHW AND DCW EXCEPT FOR
WATER CLOSETS ONLY DCW
EXISTING DWV TO REMAIN UNLESS OTHERWISE INDICATED
OR IS VISIBLY DAMAGED
ALL ESTIMATED PIPE DEMO LENGTHS ARE APPROXIMATE
AS THERE WAS NOT ACCESS TO THE MAJORITY OF PIPING
AS THE HOTEL WAS STILL OCCUPIED AND DEOLITION WAS
NOT ALLOWED - ESTMATES ALSO INCLUDE A 10% SAFETY
FACTOR
BLDG.
TRUE
NORTH
.6
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
DNUP
CD
CC
NC
NB
NA
ND
SC
SB
SA
SE
CB
CA
SD
NA.4
NB.3
SA.3
SB.8
1.1
2.9
CD.9
SA.1 NA.1
6.1
3.2 5.8
LOBBY
OFFICE #1
OFFICE #2
CORRIDOR
LINEN
GUEST ROOM
BATHROOM
105A
GUEST ROOM
BATHROOM
103A
BATHROOM
101A
GUEST ROOM
GUEST ROOM
CLOSET
101B
BATHROOM
102A
GAME ROOM
SITTING ROOM
108 BATHROOM
104A
GUEST ROOM
0 4 84
SCALE OF FEET
SCALE I
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:1 :0
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
PLUMBING DEMO FLOOR
PLAN - LEVEL 1P1.01
154 211
CONSTRUCTION DOCUMENTS
P .0
A
G
P1.01
1 PLUMBING DEMO FLOOR PLAN - LEVEL 1
GENERAL NOTES
A. REMOVE ALL EXISTING WATER CLOSETS, BATHTUBS AND
LAVATORIES, INCLUDING ALL CONTROLS. SAVE
LAVATORIES FOR POSSIBLE RE-USE AND RE-
INSTALLATION WITH NEW CONTROLS. SERVICE SINK IN
LINENS ROOM TO REMAIN.
B. DEMOLITION OF EXISTING DISTRIBUTION PIPE:
ASSUMPTIONS ARE AS FOLLOWS:
TWO VERTICAL RISERS - ONE FOR DOMESTIC HOT WATER
(DHW) AND ONE FOR DOMESTIC COLD WATER (DCW) -
1-1/2" GALVANIZED STEEL PIPE - APPROXIMATELY 15'-0" OF
EACH.
HORIZONTAL MAIN DISTRIBUTION PIPE - TWO EACH OF
DHW AND DCW - 1" GALVANIZED PIPE 30'-0" LONG FOR A
TOTAL OF 120'-0"
HORIZONTAL TERTIARY DISTRIBUTION PIPE - FOUR EACH
OF DHW AND DCW - 3/4" GALVANIZED PIPE 15'-0" LONG FOR
A TOTAL OF 120'-0"
FIXTURE CONNECTIONS - 6'-0" EACH OF 1/2" GALVANIZED
STEEL PIPE PER FIXTURE FOR DHW AND DCW EXCEPT FOR
WATER CLOSETS ONLY DCW
EXISTING DWV TO REMAIN UNLESS OTHERWISE INDICATED
OR IS VISIBLY DAMAGED
ALL ESTIMATED PIPE DEMO LENGTHS ARE APPROXIMATE
AS THERE WAS NOT ACCESS TO THE MAJORITY OF PIPING
AS THE HOTEL WAS STILL OCCUPIED AND DEOLITION WAS
NOT ALLOWED - ESTMATES ALSO INCLUDE A 10% SAFETY
FACTOR
BID OPTION J: REMOVE ALL BATHTUBS AND SHOWER PANS
FOR REPLACEMENT WITH NEW.
BLDG.
TRUE
NORTH
.6
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
DN
CD
CC
NC
NB
NA
ND
SC
SB
SA
SE
CB
CA
SD
NA.4
NB.3
SA.3
SB.8
1.1
2.9
CD.9
SA.1 NA.1
6.1
3.2 5.8
STAIRS
BATHROOM
214A
BATHROOM
204A
BATHROOM
203A
BATHROOM
201A
BATHROOM
212A
BATHROOM
210A
GUEST ROOM
BATHROOM
209A
GUEST ROOM
202BATHROOM
202A
GUEST ROOM
GUEST ROOM
GUEST ROOM
GUEST ROOM
GUEST ROOM
CORRIDOR
200A
STAIRS
BATHROOM
211A
GUEST ROOM
GUEST ROOM
GUEST ROOM
GUEST ROOM
GUEST ROOM
STORAGE
200C
CORRIDOR
200B
GUEST ROOM
GUEST ROOM
BATHROOM
205A
CLOSET
212B
CLOSET
211B
CLOSET
210B
CLOSET
209B
CLOSET
215A
CLOSET
214B
CLOSET
202B
CLOSET
201B
CLOSET
203B
CLOSET
206B
CLOSET
204B
0 4 84
SCALE OF FEET
SCALE I
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:1 :1
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
PLUMBING DEMO FLOOR
PLAN - LEVEL 2P1.02
155 211
CONSTRUCTION DOCUMENTS
P .0
A
G
P1.02
1 PLUMBING DEMO FLOOR PLAN - LEVEL 2
SHEET NOTES
1. REPLACE LAVATORIES AT GUEST ROOMS
2. SALVAGE LAVATORY FOR REINSTALLATION
3. REMOVE LAUNDRY SINK AND CONTROLS
GENERAL NOTES
A. REMOVE ALL EXISTING WATER CLOSETS, BATH/SHOWER
CONTROLS AND FAUCETS AND CONTROLS ON
LAVATORIES.
B. COORDINATE WITH ARCHITECTURAL FOR WALL FINISH
REMOVAL ONLY ON WALL WHERE BATH/SHOWER
CONTROLS ARE BEING REMOVED AND PIPING PREPARED
FOR REPLACEMENT OF CONTROLS WITH NEW CONTROLS.
C. DEMOLITION OF EXISTING DISTRIBUTION PIPE:
ASSUMPTIONS ARE AS FOLLOWS:
TWO VERTICAL RISERS - ONE FOR DOMESTIC HOT WATER
(DHW) AND ONE FOR DOMESTIC COLD WATER (DCW) -
1-1/2" GALVANIZED STEEL PIPE - APPROXIMATELY 15'-0" OF
EACH.
HORIZONTAL MAIN DISTRIBUTION PIPE - TWO EACH OF
DHW AND DCW - 1" GALVANIZED PIPE 30'-0" LONG FOR A
TOTAL OF 120'-0"
HORIZONTAL TERTIARY DISTRIBUTION PIPE - FOUR EACH
OF DHW AND DCW - 3/4" GALVANIZED PIPE 15'-0" LONG FOR
A TOTAL OF 120'-0"
FIXTURE CONNECTIONS - 6'-0" EACH OF 1/2" GALVANIZED
STEEL PIPE PER FIXTURE FOR DHW AND DCW EXCEPT
FOR WATER CLOSETS ONLY DCW
EXISTING DWV TO REMAIN UNLESS OTHERWISE
INDICATED OR IS VISIBLY DAMAGED
ALL ESTIMATED PIPE DEMO LENGTHS ARE APPROXIMATE
AS THERE WAS NOT ACCESS TO THE MAJORITY OF PIPING
AS THE HOTEL WAS STILL OCCUPIED AND DEMOLITION
WAS NOT ALLOWED - ESTMATES ALSO INCLUDE A 10%
SAFETY FACTOR.
BID OPTION J: REMOVE ALL BATHTUBS AND SHOWER
PANS FOR REPLACEMENT WITH NEW.
BLDG.
TRUE
NORTH
.6
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
CD
CC
NC
NB
NA
ND
SC
SB
SA
SE
CB
CA
SD
NA.4
NB.3
SA.3
SB.8
1.1
2.9
CD.9
SA.1 NA.1
6.1
3.2 5.8
LINEN RM.
300C
SHOWER RM.
312B
GUEST ROOM
CLOSET
301B
BATHROOM
301A
TOILET RM
310A
CLOSET
310B
GUEST ROOM
BATHROOM
309A
BATHROOM
307A
GUEST ROOM
GUEST ROOM
BATHROOM
305A
BATHROOM
311A
GUEST ROOM
GUEST ROOM
GUEST ROOM
TOILET RM
312A
GUEST ROOM
GUEST ROOM
BATHROOM
304A
BATHROOM
302A
CORRIDOR
GUEST ROOM
GUEST ROOM
BATHROOM
303A
EAVES
300B
EAVES
311B
EAVES
300A
0 4 84
SCALE OF FEET
SCALE I
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:1 :2
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
PLUMBING DEMO FLOOR
PLAN - LEVEL 3P1.03
156 211
CONSTRUCTION DOCUMENTS
P .0
A
G
P1.03
1 PLUMBING DEMO FLOOR PLAN - LEVEL 3
GENERAL NOTES
A. REMOVE ALL EXISTING WATER CLOSETS, BATH/SHOWER
CONTROLS AND FAUCETS AND CONTROLS ON
LAVATORIES.
B. COORDINATE WITH ARCHITECTURAL FOR WALL FINISH
REMOVAL ONLY ON WALL WHERE BATH/SHOWER
CONTROLS ARE BEING REMOVED AND PIPING PREPARED
FOR REPLACEMENT OF CONTROLS WITH NEW CONTROLS.
C. DEMOLITION OF EXISTING DISTRIBUTION PIPE:
ASSUMPTIONS ARE AS FOLLOWS:
TWO VERTICAL RISERS - ONE FOR DOMESTIC HOT WATER
(DHW) AND ONE FOR DOMESTIC COLD WATER (DCW) -
1-1/2" GALVANIZED STEEL PIPE - APPROXIMATELY 15'-0" OF
EACH.
HORIZONTAL MAIN DISTRIBUTION PIPE - TWO EACH OF
DHW AND DCW - 1" GALVANIZED PIPE 30'-0" LONG FOR A
TOTAL OF 120'-0"
HORIZONTAL TERTIARY DISTRIBUTION PIPE - FOUR EACH
OF DHW AND DCW - 3/4" GALVANIZED PIPE 15'-0" LONG FOR
A TOTAL OF 120'-0"
FIXTURE CONNECTIONS - 6'-0" EACH OF 1/2" GALVANIZED
STEEL PIPE PER FIXTURE FOR DHW AND DCW EXCEPT
FOR WATER CLOSETS ONLY DCW
EXISTING DWV TO REMAIN UNLESS OTHERWISE
INDICATED OR IS VISIBLY DAMAGED
ALL ESTIMATED PIPE DEMO LENGTHS ARE APPROXIMATE
AS THERE WAS NOT ACCESS TO THE MAJORITY OF PIPING
AS THE HOTEL WAS STILL OCCUPIED AND DEMOLITION
WAS NOT ALLOWED - ESTMATES ALSO INCLUDE A 10%
SAFETY FACTOR.
BID OPTION J: REMOVE ALL BATHTUBS AND SHOWER
PANS FOR REPLACEMENT WITH NEW.
BLDG.
TRUE
NORTH
.6
SHEET NOTES
1. REPLACE LAVATORIES AT GUEST ROOMS
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
CD
CC
NC
NB
NA
ND
SC
SB
SA
SE
CB
CA
SD
NA.4
NB.3
SA.3
SB.8
1.1
2.9
CD.9
SA.1 NA.1
6.1
3.2 5.8
MECHANICAL
B301
STAIRS
B300
POC TO
EXISTING 4"
SANITARY
SEWER 4" SAN
4" SAN
EXISTING 4" SAN
EXISTING 4"
SAN TO
REMAIN
POC TO EXISTING
1-1/2" DHW
POC TO EXISTING
1-1/2" DCW
PROVIDE
ISOLATION
VALVE
PROVIDE
ISOLATION
VALVE
1-1/2" DCW & DHW UPCO
POC TO
EXISTING 4"
SANITARY
SEWER
4" SAN
4" SAN
SEE SHEET P2.B2
FOR CONTINUATION
2" SUMP PUMP
DISCHARGE PIPING
POC TO EXISTING 4"
SANITARY SEWER.
PROVIDE CLEANOUT
CO
4" SAN
0 4 84
SCALE OF FEET
SCALE I
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:2 :3
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
PLUMBING FLOOR PLAN -
BASEMENT 3P2.B3
157 211
CONSTRUCTION DOCUMENTS
P .B
A
G
P2.B3
1 PLUMBING FLOOR PLAN - BASEMENT 3
GENERAL NOTES
A. RECONFIGURE & REPLACE EXISTING DWV, CW, HW &
HWR IN BASEMENT 3 ONLY AS NEEDED TO
ACCOMMODATE NEW PLUMBING LAYOUT(S) & FIXTURES,
UNLESS OTHERWISE INDICATED. COORDINATE WITH
PHASING & ARCHITECTURAL WORK. INSULATE ALL NEW
PIPING PER SPECIFICATIONS.
B. PROVIDE ALL NEW COPPER PIPING FOR FIXTURES. SEE
DEMOLITION PLANS FOR SIZE AND QUANTITIES OF PIPE.
REPLACE PIPING LIKE FOR LIKE UNLESS OTHERWISE
INDICATED IN BID DOCUMENTS.
BLDG.
TRUE
NORTH
.6
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
CD
CC
NC
NB
NA
ND
SC
SB
SA
SE
CB
CA
SD
NA.4
NB.3
SA.3
SB.8
1.1
2.9
CD.9
SA.1 NA.1
6.1
3.2 5.8
STORAGE
B211
LAUNDRY
B209B
RESTROOM
B210A
SERVICE ENTRY
B209
STAFF DINING
B208
ACCESSIBLE
STAFF BEDROOM
#3
B205
STAFF BEDROOM
#2
B206
STAFF BEDROOM
#1
B207
STAFF LOUNGE
B204
BATHROOM
B203A
STORAGE
B203
CORRIDOR
B201
WINE STOR
B202B
STORAGE
B202
STAIRS
B200
ELEV MACHINE
B211B
ELEC RM
B211A
CLOSET
B209A
STORAGE
B202A
CLOSET
B205A
CLOSET
B207A
CLOSET
B206A
P4.01
P4.01
LV-3
WC-1
SK-1
POC 4" SANITARY
AT CEILING LEVEL
4" SANITARY
BELOW SLAB
2" SUMP PUMP
DISCHARGE PIPING
TERMINATE NEAREST FLOOR
SINK AT BASEMENT 1
SP-1
MS-1
0 4 84
SCALE OF FEET
SCALE I
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:2 :2
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
PLUMBING FLOOR PLAN -
BASEMENT 2P2.B2
158 211
CONSTRUCTION DOCUMENTS
P .B
A
G
P2.B2
1 PLUMBING FLOOR PLAN - BASEMENT 2
GENERAL NOTES
A. REPLACE ALL EXISTING DWV, CW, HW & HWR PIPING THAT
IS EXPOSED DURING REMOVAL & REPLACEMENT OF INDOOR
FINISHES. INSULATE ALL NEW PIPING PER
SPECIFICATIONS. COORDINATE WITH ARCHITECTURAL.
SHEET NOTES
1. NOT USED.
2. PROVIDE NEW 4" SANITARY SEWER LINE AT CEILING
LEVEL.
3. NEW 4" SANITARY SEWER LINE TO RUN DOWN WALL TO
BELOW SLAB. PROVIDE FITTINGS TO PICK UP RELOCATED
WASHING MACHINE DRAIN LINES.
4. RUN NEW 4" SANITARY DRAIN BELOW SLAB TO POINT OF
CONNECTION IN CENTER OF ROOM. CONNECT BELOW
SLAB THEN GROUT SLAB CUT TO COVER NEW DRAIN LINE.
5. PROVIDE NEW WASHING MACHINE BOXES AND HOSE
CONNECTIONS FOR RE-CONFIGURED WASHING
MACHINES.
6. PROVIDE NEW 3" SANITARY SEWER LINE AND 1-1/2" VENT
FOR NEW UTILITY SINK. ROUTE 3" SS TO POINT OF
CONNECTION BELOW SLAB. GROUT SLAB CUT TO COVER
NEW DRAIN LINE. CONNECT TO EXISTING 1-1/2" VENT
ABOVE.
7. RECONFIGURE EXISTING DCW AND DHW, AS WELL AS ALL
DWV IN THIS AREA TO ACCOMMODATE NEW LAYOUT OF
REUSED WASHING MACHINES.
8. INSULATE (MIN.2") EXISTING 4" FOUNTAIN SANITARY
DRAIN FROM FLOOR ABOVE TO EXTERIOR WALL.
9. PROVIDE ALL NEW COPPER PIPING FOR FIXTURES. SEE
DEMOLITION PLANS FOR SIZE AND QUANTITIES OF PIPE.
REPLACE PIPING LIKE FOR LIKE UNLESS OTHERWISE
INDICATED IN BID DOCUMENTS.
10. MOP SINK CONNECT TO NEAREST EXISTING DCW, DHW,
SAN, AND VENT PIPING.
BLDG.
TRUE
NORTH
.6
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
UP
UP
CD
CC
NC
NB
NA
ND
SC
SB
SA
SE
CB
CA
SD
NA.4
NB.3
SA.3
SB.8
1.1
2.9
CD.9
SA.1 NA.1
6.1
3.2 5.8
COFFEE SHOP
B104
KITCHEN
B103
WALK-IN REFRIG.
B103A
DINING ROOM
B102
MEN'S
RESTROOM
B101B
WOMEN'S
RESTROOM
B101A
STORAGE
B100A
GIFT SHOP
B101
STAIRS
B100
P4.02
HB-1
MS-1
0 4 84
SCALE OF FEET
SCALE I
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:2 :2
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
PLUMBING FLOOR PLAN -
BASEMENT 1P2.B1
159 211
CONSTRUCTION DOCUMENTS
P .B
A
G
P2.B1
1 PLUMBING FLOOR PLAN - BASEMENT 1
GENERAL NOTES
A. REPLACE ALL EXISTING DWV, CW, HW & HWR PIPING
THAT IS EXPOSED DURING REMOVAL & REPLACEMENT OF
INDOOR FINISHES. INSULATE ALL NEW PIPING PER
SPECIFICATIONS. COORDINATE WITH ARCHITECTURAL.
B. PROVIDE ALL NEW COPPER PIPING FOR FIXTURES. SEE
DEMOLITION PLANS FOR SIZE AND QUANTITIES OF PIPE.
REPLACE PIPING LIKE FOR LIKE UNLESS OTHERWISE
INDICATED IN BID DOCUMENTS.
SHEET NOTES
1. SEE SHEET P4.02 - ENLARGED PLUMBING PLANS.
2. CONNECT TO EXISTING DCW LINE INSIDE BUIDLING.
3. MOP SINK CONNECT TO NEAREST EXISTING DCW, DHW,
SAN, AND VENT PIPING.
BLDG.
TRUE
NORTH
.6
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
DNUP
UP
UP
UP
UP
UP
UP
UP
CD
CC
NC
NB
NA
ND
SC
SB
SA
SE
CB
CA
SD
NA.4
NB.3
SA.3
SB.8
1.1
2.9
CD.9
SA.1 NA.1
6.1
3.2 5.8
OFFICE #1
OFFICE #2
LOBBY
GAME ROOM
CORRIDOR
SITTING ROOM
LINEN
GUEST ROOM
BATHROOM
105A
GUEST ROOM
BATHROOM
103A BATHROOM
104A
GUEST ROOM
103GUEST ROOM
GUEST ROOM
BATHROOM
102A
CLOSET
101B
BATHROOM
101A
3" V UP
EXISTING
WC-2
WC-2
WC-2
WC-2
HB-1
HB-1
BT-1
LV-1
LV-1
LV-1
SH-1
LV-1BT-1
SH-1
LV-1
SH-1
WC-2
0 4 84
SCALE OF FEET
SCALE I
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:1 :5
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
PLUMBING FLOOR PLAN -
LEVEL 1P2.01
160 211
CONSTRUCTION DOCUMENTS
P .0
A
G
P2.01
1 PLUMBING FLOOR PLAN - LEVEL 1
GENERAL NOTES
A. RECONFIGURE ALL DWV, CW, & HW TO ACCOMMODATE
NEW CONFIGURATION. COORDINATE WITH
ARCHITECTURAL WORK.
B. REPLACE ALL EXISTING DWV, CW, HW PIPING THAT IS
EXPOSED DURING REMOVAL & REPLACEMENT OF INDOOR
FINISHES, INSULATE ALL NEW PIPING PER
SPECIFICATIONS. CORDINATE WITH ARCHITECTURAL.
C. INSTALL NEW FIXTURES PER SCHEDULE. COORDINATE
WITH ARCHITECTURAL FOR EXACT LOCATIONS AND
INTERFACE WITH FINISHES.
D. PROVIDE ALL NEW COPPER PIPING FOR FIXTURES. SEE
DEMOLITION PLANS FOR SIZE AND QUANTITIES OF PIPE.
REPLACE PIPING LIKE FOR LIKE UNLESS OTHERWISE
INDICATED IN BID DOCUMENTS.
BLDG.
TRUE
NORTH
.6
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
DN
DN
DN
CD
CC
NC
NB
NA
ND
SC
SB
SA
SE
CB
CA
SD
NA.4
NB.3
SA.3
SB.8
1.1
2.9
CD.9
SA.1 NA.1
6.1
3.2 5.8
STAIRS
BATHROOM
214A
BATHROOM
204A
BATHROOM
203A
BATHROOM
201A
BATHROOM
212A
BATHROOM
210A
GUEST ROOM
BATHROOM
209A
GUEST ROOM
BATHROOM
202A
GUEST ROOM
GUEST ROOM
GUEST ROOM
GUEST ROOM
GUEST ROOM
CORRIDOR
200A
STAIRS
BATHROOM
211A
GUEST ROOM
GUEST ROOM
GUEST ROOM
GUEST ROOM
GUEST ROOM
STORAGE
200C
CORRIDOR
200B
GUEST ROOM
GUEST ROOM
STAIRS
BATHROOM
205A
CLOSET
212B
CLOSET
211B
CLOSET
210B
CLOSET
209B
CLOSET
215A
CLOSET
214B
CLOSET
202B
CLOSET
201B
CLOSET
203B
CLOSET
206B
CLOSET
204B
BATHROOM
206A
WC-2
WC-2
WC-2
WC-2
WC-2
WC-2
SH-2
LV-2
SH-2
LV-1
SH-2
LV-1
LV-2
BT-2
LV-2
SH-3
LV-2
SH-2
LV-2
LV-1
SH-2
LV-2
WC-2
WC-2
SH-2
SH-2
SH-2
LV-2
LV-1
SH-2
EXISTING 3"
VENT UP
MS-1
0 4 84
SCALE OF FEET
SCALE I
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:1 :5
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
PLUMBING FLOOR PLAN -
LEVEL 2P2.02
161 211
CONSTRUCTION DOCUMENTS
P .0
A
G
P2.02
1 PLUMBING FLOOR PLAN - LEVEL 2
GENERAL NOTES
A. RECONFIGURE ALL DWV, CW, & HW TO ACCOMMODATE
NEW CONFIGURATION. COORDINATE WITH
ARCHITECTURAL WORK.
B. REPLACE ALL EXISTING DWV, CW, HW PIPING THAT IS
EXPOSED DURING REMOVAL & REPLACEMENT OF INDOOR
FINISHES, INSULATE ALL NEW PIPING PER
SPECIFICATIONS. COORDINATE WITH ARCHITECTURAL.
C. INSTALL NEW FIXTURES PER SCHEDULE. COORDINATE
WITH ARCHITECTURAL FOR EXACT LOCATIONS AND
INTERFACE WITH FINISHES.
D. PROVIDE ALL NEW COPPER PIPING FOR FIXTURES. SEE
DEMOLITION PLANS FOR SIZE AND QUANTITIES OF PIPE.
REPLACE PIPING LIKE FOR LIKE UNLESS OTHERWISE
INDICATED IN BID DOCUMENTS.
E. BID OPTION J: NEW BATHTUBS OR SHOWER PANS AT ALL
GUEST ROOM BATHROOMS
BLDG.
TRUE
NORTH
.6
SHEET NOTES
1. REPLACE LAVATORIES AT GUEST ROOMS
2. CONNECT MOP SINK TO NEAREST EXISTING DCW, DHW,
SAN, AND VENT PIPING.
3. REINSTALL SALVAGED HISTORIC LAVATORY FROM
SECOND FLOOR GUEST ROOMS. PROVIDE NEW FAUCET
AND HANDLES TOTAL OF (2) LOCATIONS.
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
CD
CC
NC
NB
NA
ND
SC
SB
SA
SE
CB
CA
SD
NA.4
NB.3
SA.3
SB.8
1.1
2.9
CD.9
SA.1 NA.1
6.1
3.2 5.8
LINEN RM.
300C
SHOWER RM.
312B
GUEST ROOM
CLOSET
301B
BATHROOM
301A
TOILET RM
310A
CLOSET
310B
GUEST ROOM
BATHROOM
309A
BATHROOM
307A
GUEST ROOM
GUEST ROOM
BATHROOM
305A
BATHROOM
311A
GUEST ROOM
GUEST ROOM
GUEST ROOM
TOILET RM
312A
GUEST ROOM
GUEST ROOM
STAIRS
BATHROOM
304A
BATHROOM
302A
CORRIDOR
GUEST ROOM
GUEST ROOM
BATHROOM
303A
EAVES
300B
EAVES
305B
EAVES
311B
EAVES
300A
WC-2
WC-2
WC-2
WC-2
WC-2
WC-2
WC-2
SH-4
LV-1
LV-2
SH-5
LV-2
WC-2
SH-4
LV-2
SH-2
SH-2
LV-2
LV-2
LV-2
SH-2SH-2
LV-2
SH-5
LV-2
LV-1
SH-4
LV-2
EXISTING 4" VENT
UP THROUGH ROOF
0 4 84
SCALE OF FEET
SCALE I
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:2 :0
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
PLUMBING FLOOR PLAN -
LEVEL 3P2.03
162 211
CONSTRUCTION DOCUMENTS
P .0
A
G
P2.03
1 PLUMBING FLOOR PLAN - LEVEL 3
GENERAL NOTES
A. RECONFIGURE ALL DWV, CW, & HW TO ACCOMMODATE NEW
CONFIGURATION. COORDINATE WITH ARCHITECTURAL WORK.
B. REPLACE ALL EXISTING DWV, CW, HW PIPING THAT IS EXPOSED
DURING REMOVAL & REPLACEMENT OF INDOOR FINISHES,
INSULATE ALL NEW PIPING PER SPECIFICATIONS. COORDINATE
WITH ARCHITECTURAL.
C. INSTALL NEW FIXTURES PER SCHEDULE. COORDINATE WITH
ARCHITECTURAL FOR EXACT LOCATIOINS AND INTERFACE WITH
FINISHES.
D. PROVIDE ALL NEW COPPER PIPING FOR FIXTURES. SEE
DEMOLITION PLANS FOR SIZE AND QUANTITIES OF PIPE. REPLACE
PIPING LIKE FOR LIKE UNLESS OTHERWISE INDICATED IN BID
DOCUMENTS.
E. REPALCE LAVATORIES AT GUEST ROOMS 302, 304, 309, 310, AND
312.
F. REMOVE AND REINSTALL LAVATORIES IN GUEST ROOMS AS
REQUIRED DUE TO NEW FINISHES. SEE ARCHITECTURAL.
SHEET NOTES
1. REINSTALL SALVAGED HISTORIC LAVATORY FROM FIRST
FLOOR GUEST ROOMS. PROVIDE NEW FACET AND
HANDLES. TOTAL OF (5) LOCATIONS.
2. THERE WAS NOT PREVIOUSLY A SINK IN THIS LOCATION.
PROVIDE NEW DWV, DCW & DHW TO ACCOMMODATE NEW
SINK. CONNECT TO EXISTING ADJACENT WC AND TUB
PLUMBING.
3. BID OPTION J: NEW BATHTUB OR SHOWER PANS AT ALL
GUEST ROOM BATHROOMS.
BLDG.
TRUE
NORTH
.6
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
6 7 8
NC
NB.3
6.1
STAFF LOUNGE
B204
BATHROOM
B204A
BATHROOM
B204B
STAFF DINING
B208
FD-1 FD-1
2" SAN
4" SAN
2" V 2" V
2" V2" V
4" SAN
3" V UP
4" SAN
FROM ABOVE
2" V2" V
2" SAN
4" SAN 4" SAN
2" SAN
2" SAN
6 7 8
NC
NB.3
6.15.8
STAFF LOUNGE
B204
BATHROOM
B204A
BATHROOM
B204B
STAFF DINING
B208
WC-2
LAV-1
SH-1
LAV-1
SH-1
WC-2
1 1/2" HW DN
1 1/2" CW DN
1 1/2" CW DN
1 1/2" HW DN
1" CW
1" CW
1/2" CW
1/2" HW
1/2" HW
1/2" CW
SCALE H
0 2 42
SCALE OF FEET
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:2 :4
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
ENLARGED PLUMBING
PLANS
P4.01 163 211
CONSTRUCTION DOCUMENTS
P .0
A
G
P4.01
1 PLUMBING ENLARGED FLOOR PLAN IN CRAWLSPACE - BASEMENT 2 - WASTE AND VENT
P4.01
2 PLUMBING ENLARGED FLOOR PLAN - BASEMENT 2 - DOMESTIC COLD AND HOT WATER PIPING
BLDG.
TRUE
NORTH
.6
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
7 8
NC
NB
NB.3
MEN'S
RESTROOM
B101B
WOMEN'S
RESTROOM
B101A
LAV-1 LAV-1 LAV-1
UR-1
WC-1 WC-1
WC-1WC-1WC-1
1" HW
1 1/4" CW
3/4" HW
1 1/4" CW
1" HW DN
1 1/2" CW DN
1 1/2" CW
1" CW
LAV-1LAV-1 LAV-1
WC-1
1" CW
3/4" HW
3/4" CW
7 8
NC
NB
NB.3
FD-1
FD-1
4" V UP
4" SAN
2" WCO 2" WCO
2" WCO
2" WCO
2" V ABOVE
CEILING
3" SAN
4" SAN
1 1/2" V
1 1/2" V
2" V ABOVE
CEILING
3" SAN 2" V UP TO
CEILING
2" V UP TO
CEILING
3" V DN
2" SAN DN
W/CO
2" SAN DN
W/CO
4" SAN DN
2" V UP
(TYP. 6)
SCALE H
0 2 42
SCALE OF FEET
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:2 :4
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
ENLARGED PLUMBING
PLANSP4.02
164 211
CONSTRUCTION DOCUMENTS
P .0
A
G
P4.02
2 PLUMBING ENLARGED FLOOR PLAN - BASEMENT 1 - DOMESTIC COLD AND HOT WATER PIPING
P4.02
1 PLUMBING ENLARGED FLOOR PLAN - BASEMENT 1 - WASTE AND VENT
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
3" SAN
3" V UP/DN
4" V UP
3" V
3" SAN
3" SAN
3" SAN
4" SAN
4" SAN
1.5" V
1" V
1 1/2" CW DN
1 1/2" HW DN
1 1/2" CW DN
3"V UP
2"SAN
2"
SAN
4"
SAN
1 1/2" HW
1 1/2" CW
1 1/2" HW
1 1/2" CW
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:2 :5
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
Checker
09/13/19
PLUMBING RISER DIGRAM
P5.01 165 211
CONSTRUCTION DOCUMENTS
P .0
A
G
P5.01
1 BASEMENT 1 RESTROOM DRAIN, WASTE & VENT
P5.01
2 BASEMENT 1 RESTROOM DOMESTIC HOT & COLD WATER
P5.01
3 BASEMENT 2 DRAIN, WASTE & VENT
P5.01
4 BASEMENT 2 RESTROOM DOMESTIC HOT & COLD WATER
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
1/2" x 1 1/4" HEX HEAD CAP
SCREWS & CHANNEL NUTS
PIPE CLAMP
CLEVIS HANGER
18 GAUGE GALVANIZED SHIELD,
WRAP COMPLETELY AROUND PIPE,
1/2" MIN. EXTENDED BEYOND EACH
SIDE OF HANGER
ADJUSTABLE HINGE
1/2" x 1 1/4" HEX HEAD
CAP SCREWS &
CHANNEL NUTS
ALL THREAD
ROD (TYP.)
CHANNEL
TRANSVERSE
BRACE
PIPE SLEEVE
(TYP.)
CLEVIS HANGER
(TYP.)
ADJUSTABLE
HINGE
INSULATION
PROTECTION SHIELD
WITH "LOC" TABS (TYP.
FOR PIPE WITH
INSULATION AT EACH
SUPPORT)
ADJUSTABLE HALF HINGE
ALL THREADED (TYP.)
PIPE (WITH
INSULATION)
ALL THREAD ROD (TYP.)
PIPE SLEEVE (TYP.)
CLEVIS HANGER (TYP.)
PIPE (WITHOUT INSULATION)
INSULATION PROTECTION
SHIELD WITH "LOC" TABS
PIPE (WITH INSULATION)
ROD STIFFENER (TYP.)
CHANNEL
LONGITUDINAL
BRACE
CHANNEL
TRANSVERSE
BRACE
1/2" x 1 1/4" HEX HEAD
CAP SCREWS &
CHANNEL NUTS2
CHANNEL
SQUARE
WASHER
(TYP.)
CHANNEL
LONGITUDINAL
BRACE
SQUARE NUT (TYP.)
PIPE CLAMP, SIZE
ACCORDING TO PIPE SIZE
WITH OR WITHOUT
INSULATION (TYP.)
HEX NUT (TYP.)
ALL THREAD
ROD (TYP.)
ROD STIFFENER
(TYP.)
SLOTTED HEX HEAD MACHINE
SCREW (TYP.)
1/2" x 1 1/4" HEX HEAD CAP
SCREWS & CHANNEL
NUTS (TYP.)
ADJUSTABLE HINGE - 45°
MAX (TYP. OF 2)
CHANNEL
TRANSVERSE
BRACE
BEAM SPAN
NOTES:
1. COMPLY WITH CALIFORNIA BUILDING CODE SECTION 1632A, ADOPTED EDITION.
2. BRACE ALL PIPING AND EQUIPMENT TRANSVERSELY AND LONGITUDINALLY ACCORDING
TO SMACNA GUIDELINES FOR SEISMIC RESTRAINTS OF MECHANICAL AND AND PLUMBING
PIPING SYSTEMS.
3. ALL PIPE SUPPORTS SHALL BE PIPING TECHNOLOGY & PRODUCTS, INC. OR APPROVED
EQUAL.
4. PROVIDE TRANSVERSE SEISMIC BRACING AT 20'-0" MAXIMUM AND AT EVERY CHANGE OF
DIRECTION.
5. PROVIDE LONGITUDINAL SEISMIC BRACING AT 40'-0" O.C. MAXIMUM, MINIMUM OF 2
REQUIRED.
6. REFER TO 2/P6.03 FOR ATTACHMENT TO DECK CONTINUATION.
SHEET NOTES:
1. INSTALL ROD STIFFENER WHEN LENGTH EXCEEDS THE SCHEDULE LENGTH:
ROD STIFFENERS ARE REQUIRED ONLY ON HANGER AND TRAPEZE ASSEMBLIES
THAT HAVE SEISMIC BRACING ATTACHED AT OR WITHIN 4" OF THE ROD. A MINIMUM
OF TWO ROD STIFFENERS MUST BE INSTALLED.
2.PROVIDE COPPER HANGERS AND/OR CLAMPS FOR BARE COPPER PIPING OR EPOXY
COATED CLEVIS HANGER AND/OR CLAMPS FOR NON-METALLIC SEPARATION
BETWEEN DISIMILAR METALS.
3.REFER TO PIPING TECHNOLOGY & PRODUCTS INC. FOR CHANNEL TYPE AND LOAD
RATING BASED ON BEAM SPAN FOR UNIFORM AND CONCENTRATED LOADING.
4.REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
25"
MAX. ROD LENGTH
WITHOUT ROD
STIFFENER
19"3/8" 1/2"
ROD SIZE
18" 13"
MAX. SPACING
BETWEEN ROD
STIFFENERS
37" 31"5/8"
3/4" 28" 23"
43"7/8" 33"
60" 50"1"
1-1/4" 43" 38"
ROD STIFFENER
(TYP.)
ROD STIFFENER (TYP.)1
NONHARDENING RESILIENT
SEALANT, BOTH SIDES (TYP.).
USE META CAULK 1000 BY
RECTOSEAL IF FIRE RATING IS
REQUIRED.
FIRE RATED WALL
GALVANIZED STEEL PIPE
SLEEVE
GALVANIZED STEEL PIPE
SLEEVE
NONHARDENING RESILIENT
SEALANT, BOTH SIDES (TYP.). USE
META CAULK 1000 BY RECTOSEAL IF
FIRE RATING IS REQUIRED.
FIRE STOPPING MATERIAL
WITH SAME FIRE RATING AS
WALL
PIPE INSULATION
FIRE RATED WALL
PIPE
PIPE
NOTES:
1. INSTALL FIRE STOPPING MATERIAL PER MANUFACTURER'S
DETAIL.
2. REFER TO ARCHITECTURAL DRAWING FOR WALL FIRE RATING.
NONHARDENING
RESILIENT SEALANT,
(SEALED TOP & BOTTOM
TYP.). USE META CAULK
1000 BY RECTOSEAL IF
FIRE RATING IS REQUIRED.
PIPE INSULATION
NONHARDENING RESILIENT
SEALANT, (SEALED TOP &
BOTTOM TYP.). USE META
CAULK 1000 BY RECTOSEAL IF
FIRE RATING IS REQUIRED.
NEOPRENE PAD
STEEL SHIM (OPTIONAL)
CONCRETE FLOOR
FIBROUS MATERIAL PACKING
ALL AROUND
PIPE PIPE
STEEL PIPE RISER CLAMP
BOLT WITH NUTS
STEEL SHIM (OPTIONAL)
NEOPRENE PAD
CONCRETE FLOOR
FINISHED FLOOR
STEEL PIPE RISER
CLAMP
WELD PIPE TO SUPPORT
BOLT WITH NUTS
PIPE
NOTES:
1. REFER TO SPECIFICATIONS FOR INSULATED PIPE RISER
SUPPORTS.
2. COORDINATE RISER CLAMP ORIENTATION TO BE WITHIN WALL
CAVITY.
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:2 :5
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
IG
JHW
09/13/19
PLUMBING DETAILS
P6.01 166 211
CONSTRUCTION DOCUMENTS
P .0
IG
P6.01
1 TYPICAL SINGLE AND TRAPEZE PIPE SUPPORT
P6.01
2 PIPE PENETRATION THRU FIRE-RATED WALL
P6.01
3 PIPE PENETRATION THUR FLOOR
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
NOTES:
1. HOT DIP GALVANIZE RESTRAINT FITTING
PIPE RISER
ELBOW RESTRAINT FITTING @ STACK BASE
HOLDRITE OR EQUAL
ELBOW
METAL COVER
HAND HOLE
CLEANOUT PLUG
SCREW
SANITARY OR
STORM PIPE
Y-BRANCH
AFF
WALL
FOR WALL CONSTRUCTION
REFER TO ARCHITECTURAL
DRAWINGS
CAST IRON CLEANOUT TEE
MAY EXTEND AS
WASTE OR VENT
45° BEND
SANITARY OR
STORM PIPE
FLOW
WYE
SCORIATED CAST
IRON COVER
FLUSH TO GRADE
PROVIDE 36"X18" CONCRETE
PAD IN ASPHALT/DIRT
PAVING
DO NOT ATTACH
CLEANOUT HOUSING TO
FERRULE
FOR PAVING OTHER
THAN CONCRETE
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:2 :0
A
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
PLUMBING DETAILS
P6.02 167 211
CONSTRUCTION DOCUMENTS
P .0
A
G
P6.02
1 PIPE ELBOW AND RISER SUPPORT
P6.02
2 WALL CLEANOUT
P6.02
3 GRADE CLEANOUT
This document has been digitally signed and sealed by
John H. Weale, PE using a Digital Signature.
Printed copies of this document are not considered signed and sealed and
TITLE OF SHEETSUB SHEET NO.DESIGNED:
TECH REVIEW:
DATE:
DRAWING NO.
PMIS/PKG NO.
SHEET
OFOREGON CAVES NATIONAL MONUMENT
OREGON CAVES CHATEAU
138578
150025
R E
V
IT
/1
/2
:1 :4
P
M C
U s e rs
\k p a y n e \D o c u m e n ts
\O R
C A
M
E P
-C e n tr a l_ k p a y n e U
S W
O A
K .r v t
BG
AG
JHW
09/13/19
PLUMBING SCHEDULES
P7.01 168 211
CONSTRUCTION DOCUMENTS
P .0
A
G
7 PROVIDE COMBINATION CHECK VALVE AND DIVERTER VALVE, WEIL 2616.
6 EMERGENCY POWER REQUIRED.
5 PLUMBING TO PROVIDE STARTER MOTOR AND ELECTRICAL CONTRACTOR TO INSTALL.
4 REFER TO CIVIL DRAWINGS FOR LOCATION AND INVERT ELEVATION OF THE INLET PIPE TO SANITARY DRAIN ON LEVEL P1
3 PROVIDE BRONZE IMPELLER.
2 PROVIDE FLOATS, WEIL 8234 OR EQUAL, AND CONTROL PANEL W/ ALARM OUTPUTS TO BMS SYSTEM, WEIL 8165 OR EQUAL.
1 PROVIDE EXPLOSION PROOF MOTOR
NOTES:
SP-1
SUBMERSIBLE
PUMP
BELL & GOSSETT -
ELEVATOR SUMP PIT
BELOW BASEMENT LEVEL 2
ELEVATOR SUMP WATER 20 25 3600 1.50 115/1/60 - 1-7
GPM HEAD... RPM HP (V/Ph/HZ) (LBS.)
PLAN
MARK
DESCRIPTION MANUFACTURER MODEL LOCATION SERVICE FLUID
PUMP ELECTRIC
GROSS
WEIGHT
NOTES
SUMP PUMP SCHEDULE
WHA WATER HAMMER ARRESTER ZURN 1250XL - LEAD-FREE, NSF/ANSI STANDARD 372, COPPER BODY, PRE-CHARGED AND SEALED.
WCO WALL CLEANOUT ZURN Z1446 - CAST IRON CLEANOUT TEE, BRONZE PLUG, STAINLESS STEEL COVER.
TG-1 TRAP GUARD PROVENT TG33 - FLEXIBLE ELASTOMERIC PVC
HB-1 NON-FREEZE WALL HYDRANT ZURN Z1300 6-1/2" SQ. NON-FREEZE, INTEGRAL VACUUM BREAKER
GCO GRADE CLEANOUT ZURN Z1400 7 1/4" CAST IRON BODY, HEAVY DUTY CAST IRON TOP, BRONZE PLUG.
FD-1 FLOOR DRAIN (GENERAL PURPOSE) ZURN Z415B 5" DIA. CHROME PLATED BRONZE TOP, CAST IRON BODY
FCO FLOOR CLEANOUT ZURN Z1400 7 1/4"
CAST IRON BODY, HEAVY DUTY NICKEL BRONZE TOP, ANCHOR FLANGE, BRONZE
PLUG.
CO CLEANOUT BOOT ZURN Z1445 - CAST IRON CLEANOUT TEE, BRONZE PLUG.
BCO BASE CLEANOUT ZURN Z1446 -
CLEANOUT WITH ROUND WALL ACCESS COVER. CAST IRON BODY. COORDINATE
FINISH WITH ARCHITECT.
TAG FIXTURE MANUFACTURER MODEL TYPE REMARKS
PLUMBING DRAIN, CLEANOUT, AND SPECIALTY SCHEDULE
MS-1 MOP SINK FLORESTONE PRODUCTS CO MODEL 92 (SIZE 24"X24"X12") 2.2 GPM NO 3" 2" 3/4" 3/4"
PROVIDE SPEAKMAN FAUCET MODEL: COMMANDER
SC-5812 WITH INTEGRAL STOPS, CAST BRASS NOZZLE
WITH 3/4" HOSE THREADED AND PAIL HOOK, BRASS
VACUUM BREAKER, BRASS TOP BRACE ASSEMBLY WITH
WALL FLANGE AND MOUNTING SCREWS.
FD-1 FLOOR DRAIN ZURN
Z451, SHALLOW TRAP CAST IRON
BODY BRONZE TOP HEELPROOF
GRATE, TYPE B STRAINER
N/A N/A 2" 1-1/2" - -
CAST IRON BODY WITH BRONZE TOP - HEEL PROOF
GRATE MAXIMUM 1/4" GRATE OPENING
HB-1 HOSE BIBB ZURN
Z1315 THROUGH WALL FREEZEPROOF
HOSEBIBB
N/A N/A - - 3/4" - ALL BRONZE FREEZEPROOF WALL HYDRANT WITH KEY
DF-1 DRINKING FOUNTAIN ELKAY
DRKR14C. COUNTERTOP
NON-REFRIGERATED, NON-FILTERED.
N/A NO 2" 1-1/2" 1/2" -
STAINLESS STEEL COUNTERTOP. COORDINATE WITH
ARCHITECTURAL FOR CABINET INSTALLATION.
UR-1 WALL MOUNT URINAL AMERICAN STANDARD
WASHBROOK FLOWISE WALL MOUNT
URINAL
.125 GPF YES 2" 1-1/2" 1" - HIGH EFFICIENCY FLUSH VALVE W/SENSOR
WC-2
WATER CLOSET (FLUSH TANK,
FLOOR MOUNT)
AMERICAN STANDARD
CADET FLOWISE FLOOR MOUNT
TOILET. 16.5" HIGH. COLOR WHITE
ONLY
1.1 GPF YES 4" 2" 1" -
HIGH EFFICIENCY PRESSURE ASSIST.
ELONGATED BOWL WITH CLOSED FRONT SEAT. PROVIDE
TANK WITH TANK COVER LOCKING DEVICE (4142.901).
WC-1
WATER CLOSET (FLUSH VALVE,
FLOOR MOUNT)
AMERICAN STANDARD
MADERA FLOWISE 16.5" HIGH. FLOOR
MOUNT TOILET. COLOR WHITE ONLY.
FLUSHOMETER AUTOMATIC FLUSH
VALVE. MODEL 2857.128
1.1 GPF YES 4" 2" 1" -
HIGH EFFICIENCY FLUSH VALVE W/SENSOR
ELONGATED BOWL WITH OPEN FRONT SEAT.
SK-1 LAUNDRY SINK FIAT
FLTD II. MOLDED-STONE. DEEP
DOUBLE LAUNDRY SINK
TOP MOUNT GOOSENECK WITH TWO
HANDLES 8" O.C.
1.0 GPM YES 3" 1-1/2" 1/2" 1/2" PROVIDE 1.0 GPM AERATOR.
SH-6
BATHTUB/ WAND SHOWER
(CONTROLS ONLY)
AMERICAN STANDARD
AMERICAN STANDARD DIVERTER
VALVE TRIMKIT T064430.002; DIVERTER
VALVE R422; BRASS ELBOW CHROME
8888068.002
1.4 YES - - 3/4" 3/4"
3-FUNCTION HAND SHOWER WITH PAUSE FEATURE
1660766.002; 59" METAL SHOWER HOSE 8888035.002; 36"
STANDARD SLIDE BAR 1660236.002
SH-5 SHOWER (CONTROLS ONLY) AMERICAN STANDARD
AMERICAN STANDARD ESTATE
PRESSURE BALANCE SHOWER FITTING
T722.507.002; R111.000 VALVE
1.75 GPM YES - - 3/4" 3/4" WATER SAVING 3-FUNCTION SHOWERHEAD.
SH-4 BATH (CONTROLS ONLY) AMERICAN STANDARD
AMERICAN STANDARD ESTATE
PRESSURE BALANCE BATH FITTING
T722.508.002; R111.000 VALVE
1.75 GPM YES - - 3/4" 3/4"
NO SHOWERHEAD, BATH FAUCET ONLY; CAP SHOWER
OUTLET BEHIND…