072113 Thermal Insulation 09192025.pdf

PDF 125 KB Posted

Attached to
Z1DA--NRM| 503-21-102 Correct FCA Electrical Deficiencies Phase 1 (VA-26-00004932)
Solicitation number
36C24426R0017
Issued by

About this file

This document is a Technical Specification Section 07 21 13 for Thermal Insulation at the James E. Van Zandt Medical Center in Altoona, PA, part of a project to Correct FCA Electrical Deficiencies – Phase 1. The specification covers thermal insulation requirements for perimeter and masonry cavity wall applications, detailing acceptable insulation types including polystyrene board, cellular glass block, mineral fiber board, polyurethane/polyisocyanurate board, and perlite board. Each insulation type must meet specific ASTM standards and have specified recycled content percentages ranging from 5-75% depending on the material.

The document provides comprehensive installation guidelines, including requirements for bonding insulation to surfaces using adhesives or hot asphalt, filling joints, and ensuring proper placement around building elements like door frames, windows, and expansion joints. Additional requirements include installing insulation without voids, maintaining required thickness, and using appropriate fastening methods for wood and metal framing. Sustainability considerations are emphasized, with requirements for tracking recycled content and low pollutant-emitting materials, and instructions for submitting documentation on these aspects during the project.

View the file

Other files

File Type Posted
36C24426R0017 0002.docx DOCX document
Revised_Statement of Work 503-21-102.pdf PDF
36C24426R0017 0001.docx DOCX document
FCA Electrical Sign In Sheet_1.22.26.pdf PDF
RFI 2.6.2026.docx DOCX document
NewSwitchGearBuildingElevationsDetails_Revision1_02032026.pdf PDF
Pre-bid Site Visit Meeting Location.png PNG image
503-21-102 FCA Electrical Construction Drawings.pdf PDF
503-21-102 CD Specifications_Revised 7-29-25.pdf PDF
36C24426R0017.docx DOCX document
Statement of Work 503-21-102.pdf PDF
S02 36C24426R0017 Liquidated Damages signed.pdf PDF
EXHIBIT C - Past Performance Questionnaire.pdf PDF
503-21-102 Pre-Bid RFI .docx DOCX document
P03 36C244-26-AP-0018 Honeywell Notifier signed_Redacted.pdf PDF
P03 36C244-26-AP-0018 Inpro Contego Signage signed _Redacted.pdf PDF
P03 Sole Source BNOE 503-21-102.pdf PDF
Pre-Bid Site Visit Meeting Location.pdf PDF
P03 36C244-26-AP-0018 Avigilon Camera signed Redacted.pdf PDF
01-EP-501.pdf PDF
P03 36C244-26-AP-0018 02_Salto Door signed_Redacted.pdf PDF
P03 36C244-26-AP-0018 Bettwy Systems signed Redacted.pdf PDF
P03 36C244-26-AP-0018 Wattstopper DLM signed Redacted.pdf PDF
P03 36C244-26-AP-0018_Trane Tracer Ensemble signed Redacted.pdf PDF
PA 20260077 01.09.2026.pdf PDF
EXHIBIT D - Price Proposal Breakdown.pdf PDF
Exhibit B - Subcontractor Information and Consent Form.pdf PDF
Exhibit A - Experience.pdf PDF
076000 Flashing.pdf PDF
Show all 29

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

09-2025 James E. Van Zandt Medical Center Altoona, PA Correct FCA Electrical Deficiencies – Phase 1

07 21 13 - 1

SECTION 07 21 13

THERMAL INSULATION

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Thermal insulation.

a. Board or block insulation at foundation perimeter.

b. Board or block insulation at masonry cavity walls.

1.2 RELATED WORK

A. Section 04 20 00, UNIT MASONRY: Insulation for Cavity Face of Masonry.

1.3 APPLICABLE PUBLICATIONS

A. Comply with references to extent specified in this section.

B. ASTM International (ASTM):

C516-19.................Vermiculite Loose Fill Thermal Insulation.

C549-18.................Perlite Loose Fill Insulation.

C552-17e1 ..............Cellular Glass Thermal Insulation.

C553-13(2019)...........Mineral Fiber Blanket Thermal Insulation for

Commercial and Industrial Applications.

C578-19.................Rigid, Cellular Polystyrene Thermal Insulation.

C591-20.................Unfaced Preformed Rigid Cellular

Polyisocyanurate Thermal Insulation.

C612-14(2019)...........Mineral Fiber Block and Board Thermal

Insulation.

C665-17.................Mineral-Fiber Blanket Thermal Insulation for

Light Frame Construction and Manufactured

Housing.

C728-17a................Perlite Thermal Insulation Board.

C954-18.................Steel Drill Screws for the Application of

Gypsum Panel Products or Metal Plaster Base to

Steel Studs From 0.033 (0.84 mm) inch to 0.112 inch (2.84 mm) in thickness.

C1002-18................Steel Self-Piercing Tapping Screws for

Application of Gypsum Panel Products or Metal

Plaster Bases to Wood Studs or Steel Studs.

D312/D312M-16a..........Asphalt Used in Roofing.

E84-20..................Surface Burning Characteristics of Building

Materials.

F1667-18a...............Driven Fasteners: Nails, Spikes, and Staples.

Correct FCA Electrical Deficiencies – Phase 1

07 21 13 - 2

1.4 SUBMITTALS

A. Submittal Procedures: Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B. Submittal Drawings:

1. Show insulation type, thickness, and R-value for each location.

C. Manufacturer's Literature and Data:

1. Description of each product.

2. Adhesive indicating manufacturer recommendation for each application.

D. Sustainable Construction Submittals:

1. Recycled Content: Identify post-consumer and pre-consumer recycled content percentage by weight.

2. Low Pollutant-Emitting Materials: Show volatile organic compound types and quantities.

1.5 DELIVERY

A. Deliver products in manufacturer's original sealed packaging.

B. Mark packaging, legibly. Indicate manufacturer's name or brand, type, production run number, and manufacture date.

C. Before installation, return or dispose of products within distorted, damaged, or opened packaging.

1.6 STORAGE AND HANDLING

A. Store products indoors in dry, weathertight facility.

B. Protect products from damage during handling and construction operations.

C. Protect foam plastic insulation from UV exposure.

1.7 WARRANTY

A. Construction Warranty: FAR clause 52.246-21, "Warranty of Construction."

PART 2 - PRODUCTS

2.1 INSULATION - GENERAL

A. Insulation Thickness:

1. Provide thickness required by R-value shown on drawings.

2. Provide thickness indicated when R-value is not shown on drawings.

B. Insulation Types:

1. Provide one insulation type for each application.

C. Sustainable Construction Requirements:

1. Insulation Recycled Content:

Correct FCA Electrical Deficiencies – Phase 1

07 21 13 - 3

a. Polyisocyanurate/polyurethane rigid foam: 9 percent recovered material.

b. Polyisocyanurate/polyurethane foam-in-place: 5 percent recovered material.

c. Glass fiber reinforced: 6 percent recovered material.

d. Phenolic rigid foam: 5 percent recovered material.

e. Rock wool material: 75 percent recovered material.

2.2 THERMAL INSULATION

A. Perimeter Insulation In Contact with Soil:

1. Polystyrene Board: ASTM C578, Type IV, V, VI, VII, or IX.

2. Cellular Glass Block: ASTM C552, Type I or IV.

B. Masonry Cavity Wall Insulation:

1. Mineral Fiber Board: ASTM C612, Type II, with vapor retarder facing;

maximum permeance 29 ng/Pa/s/sq. m (0.5 perms).

2. Polyurethane or Polyisocyanurate Board: ASTM C591, Type I, with vapor retarder facing; maximum permeance 29 ng/Pa/s/sq. m

(0.5 perms).

3. Polystyrene Board: ASTM C578, Type X.

4. Perlite Board: ASTM C728.

5. Cellular Glass Block: ASTM C552, Type I or IV.

2.3 ACCESSORIES

A. Fasteners:

1. Staples or Nails: ASTM F1667, zinc-coated, size and type to suit application.

2. Screws: ASTM C954 or ASTM C1002, size and length to suit application with washer minimum 50 mm (2 inches) diameter.

3. Impaling Pins: Steel pins with head minimum 50 mm (2 inches) diameter.

a. Length: As required to extend beyond insulation and retain cap washer when washer is placed on pin.

b. Adhesive: Type recommended by manufacturer to suit application.

B. Insulation Adhesive: Nonflammable type recommended by insulation manufacturer to suit application.

C. Tape: Pressure sensitive adhesive on one face.

PART 3 - EXECUTION

3.1 PREPARATION

A. Examine and verify substrate suitability for product installation.

B. Protect existing construction and completed work from damage.

Correct FCA Electrical Deficiencies – Phase 1

07 21 13 - 4

C. Clean substrates. Remove contaminants capable of affecting subsequently installed product's performance.

3.2 INSTALLATION - GENERAL

A. Install products according to manufacturer's instructions and approved submittal drawings.

1. When manufacturer's instructions deviate from specifications, submit proposed resolution for Contracting Officer's Representative consideration.

B. Install insulation with vapor barrier facing the heated side, unless indicated otherwise.

C. Install board insulation with joints close and flush, in regular courses, and with end joints staggered.

D. Fit insulation tight against adjoining construction and penetrations, unless indicated otherwise.

3.3 THERMAL INSULATION

A. Perimeter Insulation In Contact with Soil:

1. Vertical insulation:

a. Fill joints of insulation with same material used for bonding.

b. Bond polystyrene board to surfaces with adhesive.

c. Bond cellular glass insulation to surfaces with hot asphalt or adhesive cement.

2. Horizontal insulation under concrete floor slab:

a. Lay insulation boards and blocks horizontally on level, compacted and drained fill.

b. Extend insulation from foundation walls towards center of building minimum 600 mm (24 inches).

B. Masonry Cavity Wall Insulation:

1. Install insulation on exterior faces of concrete and masonry inner wythes of cavity walls.

2. Bond polystyrene board to surfaces with adhesive.

3. Bond polyurethane or polyisocyanurate board, and perlite board to surfaces with adhesive.

4. Bond cellular glass insulation to surfaces with hot asphalt or adhesive cement.

5. Fill insulation joints with same material used for bonding.

3.4 ACOUSTICAL INSULATION

A. General:

1. Install insulation without voids.

Correct FCA Electrical Deficiencies – Phase 1

07 21 13 - 5

2. Pack insulation around door frames and windows, in building expansion joints, door soffits, and other voids.

3. Pack behind outlets, around pipes, ducts, and services encased in walls.

4. Hold insulation in place with pressure sensitive tape.

5. Lap facer flanges together over framing for continuous surface. Seal all penetrations through the insulation and facers.

6. Do not compress insulation below required thickness except where embedded items prevent required thickness.

B. Semi Rigid, Batts and Blankets:

1. When insulation is not full thickness of cavity, adhere insulation to one side of cavity, maintaining continuity of insulation and covering penetrations or embedments.

a. Wood Framing:

1) Fasten blanket insulation between wood framing and joists with nails or staples through flanged edges of insulation.

2) Space fastenings maximum 150 mm (6 inches) on center.

b. Metal Framing:

1) Fasten insulation between metal framing with pressure sensitive tape continuous along flanged edges.

2) At metal framing or ceilings suspension systems, install blanket insulation above suspended ceilings or metal framing at right angles to the main runners or framing.

3) Tape insulation tightly together so no gaps occur and metal framing members are covered by insulation.

3.5 CLEANING

A. Remove excess adhesive before adhesive sets.

3.6 PROTECTION

A. Protect insulation from construction operations.

B. Repair damage.

- - E N D - -

SECTION 07 21 13 thermal insulation
PART 1 - GENERAL
1.1 SUMMARY
1.2 RELATED work
1.3 APPLICABLE PUBLICATIONS
1.4 SUBMITTALS
1.5 DELIVERY
1.6 STORAGE AND HANDLING
1.7 WARRANTY
PART 2 - PRODUCTS
2.1 INSULATION - GENERAL
2.2 THERMAL INSULATION
2.3 ACCESSORIES
PART 3 - EXECUTION
3.1 PREPARATION
3.2 INSTALLATION - GENERAL
3.3 THERMAL INSULATION
3.4 ACOUSTICAL INSULATION
3.5 CLEANING
3.6 PROTECTION