Amendment 0006 - Drawing M-503 (Revised).pdf

PDF 308 KB Posted

Attached to
Construction of Chilled Water Plant and Site Utility Upgrades at VA Medical Center in West Haven, CT
Solicitation number
W912WJ26RA008
Issued by

About this file

This is a mechanical diagrams document for a federal construction project issued by the U.S. Department of Veterans Affairs, Office of Construction and Facilities Management, in partnership with the U.S. Army Corps of Engineers as construction agent.

The document provides detailed technical specifications and flow diagrams for a Chilled Water Plant Replacement and Site Utility Improvements project at VA Medical Center, West Haven, Connecticut (950 Campbell Avenue, West Haven, CT 06516). The project includes design and installation of a 49,500-gallon insulated aboveground fuel oil storage tank system (typical of 5 tanks), electric oil heater systems, and fuel oil polisher equipment. Key components specified include double-wall insulated fuel oil piping with heat tracing routed through concrete trenches, primary and secondary fine filters, magnetic conditioner, coalescing water separator, pressure and vacuum monitoring systems, level switches and transmitters for tank control, 125 PSI safety valves, and control panels with LED indicator lights for system status. All fuel oil piping within the containment basin must be single-wall with 1-inch insulation and aluminum or stainless steel jacketing. The document contains detailed flow diagrams for tank yard fuel oil piping, electric oil heater systems, and fuel oil polisher operations, along with comprehensive symbols legend and installation requirements. The drawing is dated July 31, 2026, marked "Ready to Advertise" and "Fully Sprinklered," with bidding RFIs issued September 23, 2026. Project number is 689-040, and the designer of record is IMED Perkins&Will.

View the file

Other files

File Type Posted
Amendment 0006 - Drawing CK-505 (Revised).pdf PDF
Amendment 0006 - 01 32 01.00 10 (Revised).pdf PDF
Amendment 0006.pdf PDF
Amendment 0006 - Drawing 01-MP101 (Revised).pdf PDF
Amendment 0006 - Drawing CK-502 (Revised).pdf PDF
Amendment 0005.pdf PDF
Amendment 0005 - Submission Requirements and Evaluation Criteria (Clean).pdf PDF
Amendment 0005 - Submission Requirements and Evaluation Criteria (Track Changes).pdf PDF
Amendment 0004 - VA Hospital New Customer Load Report - 7_28_26.pdf PDF
Amendment 0004 - 12018711_Spec013000_Response.pdf PDF
Amendment 0004 - 12018255_01-ED101_01-EP101-Response.pdf PDF
Amendment 0004.pdf PDF
Amendment 0004 - 12018718_12018724_Spec013000_Response.pdf PDF
Amendment 0003 - Submission Requirements and Evaluation Criteria (Track Changes).pdf PDF
Amendment 0003.pdf PDF
Amendment 0003 - Plan T600.pdf PDF
Amendment 0003 - Submission Requirements and Evaluation Criteria (Clean).pdf PDF
Solicitation - W912WJ26RA008.pdf PDF
Amendment 0003 - JA 03 (JCI ESS_Redacted).pdf PDF
Amendment 0003 - Revisions to Specification Sections 270511-280500-281300-282300.pdf PDF
Amendment 0002 - Specs Section 01 22 00.pdf PDF
Amendment 0002 - Submission Requirements and Evaluation Criteria (Clean).pdf PDF
Amendment 0002 - Submission Requirements and Evaluation Criteria (Track Changes).pdf PDF
Amendment 0002.pdf PDF
Amendment 0002 - Bidding Schedule.pdf PDF
Amendment 0001.pdf PDF
Amendment 0001 - Submission Requirements and Evaluation Criteria.pdf PDF
Specifications - Volume I.pdf PDF
Contractor Appendix Binder.pdf PDF
Specifications - Volume II.pdf PDF
JA 05 - AMAZ_Redacted.pdf PDF
JA 02 - JCI Fire_Redacted.pdf PDF
JA 03 - JCI ESS_Redacted.pdf PDF
JA 04 - Assa Abloy_Redacted.pdf PDF
JA (Class) - Interior Finishes_Redacted.pdf PDF
JA 01 - Siemens_or_JCI HVAC BAS_Redacted.pdf PDF
Submission Requirements and Evaluation Criteria.pdf PDF
Drawings.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

"F

O F

"F

O R

"F

O F

"F

O R

"F

O R

"F

O F

"F

O F

"F

O R

"F

O R

"F

O F

TK-1

TK-2 TK-3

TK-4 TK-5

"F

O F

"F

O F

"F

O R

"F

O R

"F

O R

"F

O S

"F

O S

"F

O S

"F

O R

OPEN DIKE FUEL

OIL CONTAINMENT

49,500 GALLON INSULATED,

ABOVEGROUND FUEL OIL

STORAGE TANK, TYPICAL OF 5.

"F

O F

"F

O R

"F

O R

3"FOS

3"FOS

3"FOS

3"FOS

3"FOR

2"FOS

FP-1

2"FOR

ILD

HL

WL

HH

FL

ILD

HL

WL

HH

FL

WL

FL

HL

HH

ILD

WL

FL

HL

HH

ILD

WL

FL

HL

HH

ILD

TO/FROM DEDICATED ELECTRIC FUEL

OIL HEATING SYSTEM (1 SYSTEM PER

TANK), TYPICAL. REFER TO C1/M503.

/4 "F

O R

/4 "F

O S

/4 "F

O R

/4 "F

O R

/4 "F

O R

FUEL OIL OVERFILL PREVENTION

VALVE, TYPICAL.

2" FLANGED DRAIN VALVE WITH

BLIND FLANGE, TYPICAL.

"F

O S

"F

O R

2"FOS

"F

O S

"F

O R

2"FOR

"F

O R

"F

O F

"F

O R

2"FOS

2"FOR

2"FOS

2"FOR

"F

O F

2"FOR

2"FOS

3"FOS

REMOTE FUEL

TANK FILL PORT

TWO-POSITION CONTROL VALVE WITH

POSITION INDICATOR. LOCATE VALVE

WHERE VISIBLE FROM AUTOMATIC

CONTROL PANEL, TYPICAL.

"F

O F

3"FOF

3"FOF

3"FOF

3"FOF

1"SV

ILD

HL

WL

HH

FL

INTERSTITIAL LEAK DETECTOR

WATER LEVEL TRANSMITTER

HIGH LEVEL SWITCH

HIGH-HIGH LEVEL ALARM SWITCH

FLUID LEVEL TRANSMITTER

TANK CONTROLLER LIST

SYMBOL: DESCRIPTION:

AUTOMATIC FUEL

OIL POLISHER.

REFER TO 2/MP-605.

3"FOS

3"FOR

3"FOS

CONCRETE SUPPORT BASE FOR SUPPORTING

FUEL OIL TANKS AND PIPING.

FUEL OIL PIPING THAT CIRCULATES THROUGH FUEL OIL

HEATER CABINET SHALL BE INSULATED BUT NOT HEAT

TRACED, TYPICAL. (REPRESENTED BY DASHED LINES.)

FUEL OIL PIPING THAT DOES NOT CIRCULATE THROUGH FUEL

OIL HEATER CABINETS SHALL BE INSULATED AND HEAT

TRACED, TYPICAL. (REPRESENTED BY DOUBLE-DASHED LINES.)

FOS & FOR PIPING TO ROUTE ACROSS SITE WITHIN SHALLOW PRECAST OR POURED-IN-PLACE CONCRETE TRENCHES WITH REMOVABLE LIDS. REFER TO SECTION 33 63 00 FOR PRECAST TRENCH REQUIREMENTS. REFER TO STRUCTURAL DRAWINGS FOR POURED-IN-PLACE CONCRETE TRENCH REQUIREMENTS. PRECAST TRENCH BUTTS UP AGAINST CONCRETE TANK SUPPORT BASE. PROVIDE EXCAVATION OF SITE MATERIALS AS REQUIRED TO INSTALL PRECAST TRENCH WITH LID FLUSH WITH GRADE. REFER TO F5/M406 FOR PRECAST TRENCH DETAIL.

/4 "F

O R

ROUTE FOS & FOR PIPING ABOVE CONCRETE

CONTAINMENT WALL, BEHIND SCREEN WALL AND INTO

PRECAST CONCRETE TRENCH. NO PIPING SHALL BE

VISIBLE OUTSIDE OF SCREEN WALL. PLACE REMOVABLE

COVERS ON PRECAST TRENCH FOR PIPE CONCEALMENT.

SCREEN WALL INSTALLED

OUTSIDE OF CONTAINMENT

BASIN.

3"FOS

2"FOS

2"FOR

3"FOS

3"FOR

2-1/2"FOS

2-1/2"FOR

EXTEND 2-1/2" FOS&R PIPING

THROUGH WEST SIDE OF

MANHOLE FOR FUTURE

EXTENSION. REFER TO MS201.

MANHOLE LOCATED AT GRADE LEVEL OF

EXISTING BOILER PLANT. REFER TO E6/M302

& E5/M406 FOR ADDITIONAL REQUIREMENTS.

EXISTING BOILER

ROOM FLOOR

TRANSITION SUMP WITH REMOVABLE

COVER AND LEAK DETECTION

MONITORING CABLE.

EXTEND 2-1/2" FOS&R UNINSULATED

PIPING TO CONNECT WITH PIPING

SERVING EXISTING BOILERS.

SEAL WALL PENETRATION

PER F2/M406, TYPICAL.

TRANSITION TO SINGLE WALL PIPE

WITHIN TRANSITION SUMP WITH 1" THICK

INSULATION AND ALUMINUM OR SS

JACKETING.

ALL DIRECT BURIED PIPING SHALL

BE DOUBLE WALL WITH INSULATED

CARRIER PIPE, TYPICAL.

DOUBLE WALL FUEL OIL PIPING SHALL

CONTINUOUSLY SLOPE TO DRAIN AT

LOW POINTS IN TRANSITION SUMPS OR

MANHOLES, TYPICAL.

ALL FUEL OIL PIPING INSTALLED WITHIN PRECAST SHALLOW CONCRETE

TRENCH AND VERTICAL CMU SHAFT SHALL BE DOUBLE WALL WITH

INSULATED CARRIER PIPE. ALL DOUBLE WALL FUEL OIL PIPING SHALL

CONTINUOUSLY SLOPE TO LOW POINTS IN MONITORING SUMPS, TRANSITION

SUMPS, AND MANHOLES WHERE LEAK DETECTION MONITORING IS

INSTALLED. REFER TO SECTION 23 10 00 FOR REQUIREMENTS.

ALL FUEL OIL PIPING WITHIN CONTAINMENT BASIN

SHALL BE SINGLE WALL WITH 1" THICK INSULATION

AND ALUMINUM OR SS JACKETING, TYPICAL.

3/4" NORMALLY CLOSED MANUAL DRAIN

VALVE TO ALLOW FOR SERVICING PIPE

COMPONENTS, TYPICAL.

125 PSI SAFETY

VALVE.

125 PSI SAFETY

VALVE, TYPICAL.

FOR & FOF PIPING LOCATED

ABOVE STRIKER PLATES, TYPICAL.

REFER TO SECTION 23 10 00.

90% & 95% LEVEL

SWITCHES

FUEL LEVEL

TRANSMITTER

WATER LEVEL

TRANSMITTER

ELECTRIC OIL

HEATER

1 1/4"FOR

INSULATED FOS&R PIPING TO/FROM ABOVEGROUND

FUEL OIL STORAGE TANK, TYPICAL OF 5.

1 1/4"FOS

1 1/4"FOR

1 1/4"FOR

DASHED LINES REPRESENT A UL LISTED TYPE 304

STAINLESS STEEL NEMA 4 ENCLOSURE WITH ALL

INTERIOR COMPONENTS FACTORY ASSEMBLED.

/4 "F

O R

FOP-#

(10 GPM)

FOH-#

INDICATORS AND SWITCHES MOUNTED

ON FUEL OIL HEATER PANEL FACE

PANEL LAMPS SHALL BE:

• 18mm LED WITH PUSH-TO-TEST FUNCTION.

• G - GREEN

• R - RED

HIGH

VACUUM

HIGH

PRESSURE

BASIN

LEAK

E-STOP SYSTEM

POWER

PUMP

RUNNING

ALARM

RESET

HAND-OFF-

AUTO

H. O. A.

G G

R R R460V/3Ø

POWER

THERMOSTAT PROVIDE BY OIL

HEATER MANUFACTURER.

INSULATE ALL FUEL OIL PIPING

WITHIN CABINET, TYPICAL.

HEATER

ENERGIZED

G

30"HG-0-

60 PSI

0-100

PSI

COMPRESSED AIRA

FUEL OIL RETURNFOR

FUEL OIL SUPPLYFOS

HIGH-PRESSURE CONDENSATEHPC

HIGH-PRESSURE STEAMHPS

PITCH PIPE IN DIRECTION

DIRECTION OF FLOW IN PIPE

UNION/FLANGE

SHUTOFF VALVE NORMALLY OPEN

SHUTOFF VALVE NORMALLY CLOSED

THROTTLING VALVE

BALANCING VALVE (NO. INDICATES GPM)

0.5

CONTROL VALVE (THREE-WAY)

CONTROL VALVE (TWO-WAY)

CHECK VALVE

SAFETY/RELIEF VALVE

PRESSURE REDUCING VALVE (LIQUID/GAS)

"WYE" - STRAINER

"WYE" - STRAINER W/SHUTOFF VALVE

AND HOSE CONNECTION WITH CAP

FLEXIBLE CONNECTION

PRESSURE/TEMPERATURE TEST PLUG

REDUCER - REFERENCE SPECIFICATION

FOR CONCENTRIC/ECCENTRIC AND FOT/FOB

METER

PRESSURE GAUGE (FURNISHED WITH BALL VALVE)

SUCTION DIFFUSER WITH SUPPORT FOOT

AUTOMATIC AIR VENT

MANUAL AIR VENT W/ BALL VALVE

DRAIN WITH HOSE CONNECTION, CAP &

BALL VALVE

TEMPERATURE SENSOR WITH WELL

THERMOMETER WITH WELL (FILLED TYPE)

FLOW METER

FLOW DIAGRAM SYMBOLS LIST

SYMBOL: DESCRIPTION:

SOLENOID/TWO POSITION VALVE

AUTOMATIC BALANCING VALVE (NO. INDICATES GPM)

0.5

FUEL OIL FILLFOF

DRAIND

EXTERNAL EMERGENCY VALVE

VACUUM SWITCH

PRESSURE TRANSMITTER

FUEL OIL

POLISHER

CONTROLLER

VACUUM GAUGE ON

SUCTION SIDE OF

PUMP, TYPICAL.

0-160 PSI GAUGE ON

DISCHARGE SIDE OF

PUMP, TYPICAL

FUEL OIL PUMP

(FOP-6)

PRIMARY FINE FILTERS,

TYPICAL OF 2.

SECONDARY FINE FILTERS,

TYPICAL OF 2.

MAGNETIC

CONDITIONER

COALESCING WATER

SEPARATOR

AUTOMATIC WATER

DRAIN OUTLET.

2" OUTLET TO

FUEL OIL TANKS

FLOW METER

PRESSURE TRANSDUCER,

TYPICAL.

VACUUM

SWITCH

HIGH

VACUUM

R

INDICATORS AND SWITCHES MOUNTED

ON FUEL OIL POLISHER PANEL FACE

R R R R

GG

HIGH

PRESSURE

LOW

FLOW

BASIN

LEAK

HIGH

WATER

PUMP

RUNNING

SYSTEM

POWER

ALARM

RESET

E-STOP HAND-OFF-

AUTO

H. A.O.

PANEL LAMPS SHALL BE:

• 18mm LED WITH PUSH-TO-TEST FUNCTION.

• G - GREEN

• R - RED

2" FOS FROM

FUEL OIL TANKS

30"HG-0-

60 PSI

30"HG-0-

60 PSI

15 SUNNEN DRIVE

SUITE 104

ST. LOUIS, MO 63143

P: 314.645.1132 F: 314.645.1173

The FUTURE. Built Smarter www.imegcorp.com

PROJECT #22000669.04

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

READY TO ADVERTISE

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD

A/E:

STAMPCONSULTANT

7 8 9 10

US Army Corps of Engineers ®

CONSTRUCTION AGENT

321 4 5 6

A u to d e s k D o c s /0

-1

-0

P h a s e

A

/6

-0

V

A W

H B

L D

G -1

M P

.r v t

/2 /2

:4

:2

P

M

M503

MECHANICAL DIAGRAMS

New England District

CHILLED WATER PLANT

REPLACEMENT AND SITE UTILITY

IMPROVEMENTS PHASE A2

950 CAMPBELL AVENUE

WEST HAVEN, CT 06516

689-040

2026-07-31 RUSARN BHAACH

NO SCALEF5 TANK YARD FUEL OIL PIPING FLOW DIAGRAM

NO SCALEC1 ELECTRIC OIL HEATER FLOW DIAGRAM

NO SCALEE2 FUEL OIL POLISHER

Revisions: Date:

BIDDING RFIS 09/23/2026