Amendment 0006 - Drawing 01-MP101 (Revised).pdf

PDF 504 KB Posted

Attached to
Construction of Chilled Water Plant and Site Utility Upgrades at VA Medical Center in West Haven, CT
Solicitation number
W912WJ26RA008
Issued by

About this file

This is a mechanical piping design drawing for a federal construction project at a Veterans Affairs facility. The drawing depicts Building 1 sub-ground level piping for Option Bid 0005 of the Chilled Water Plant Replacement and Site Utility Improvements Phase A2 project located at 950 Campbell Avenue, West Haven, CT 06516. The project is under the U.S. Department of Veterans Affairs, Office of Construction and Facilities Management, with the New England District of the U.S. Army Corps of Engineers serving as the construction agent.

The scope of work shown includes installation of new steam pressure reducing valve (PRV) stations configured in 1/3 and 2/3 ratios to match existing equipment loads (9,600 lbs/hr at 60 psi inlet/15 psi outlet for the primary station and 1,500 lbs/hr at 60 psi inlet/8 psi outlet for secondary station), routing of chilled water lines approximately 6 inches above finish floor, routing of steam, condensate, and chilled water piping through the building with multiple pipe sizes ranging from 2 inches to 20 inches in diameter, installation of double gate valves with globe valve bypass for steam and condensate piping, and piping anchoring to existing concrete structures. Sheet notes specify that all work is part of Option Bid 0005, system tie-in work must be coordinated with the owner during off-season periods, chilled water work shall occur during winter months, and steam/condensate work shall occur during summer months. The drawing was issued July 31, 2026, marked as "Ready to Advertise," and fully sprinklered. Bidding RFIs were dated September 23, 2026.

View the file

Other files

File Type Posted
Amendment 0006 - Drawing CK-505 (Revised).pdf PDF
Amendment 0006 - Drawing M-503 (Revised).pdf PDF
Amendment 0006 - 01 32 01.00 10 (Revised).pdf PDF
Amendment 0006.pdf PDF
Amendment 0006 - Drawing CK-502 (Revised).pdf PDF
Amendment 0005.pdf PDF
Amendment 0005 - Submission Requirements and Evaluation Criteria (Clean).pdf PDF
Amendment 0005 - Submission Requirements and Evaluation Criteria (Track Changes).pdf PDF
Amendment 0004 - VA Hospital New Customer Load Report - 7_28_26.pdf PDF
Amendment 0004 - 12018711_Spec013000_Response.pdf PDF
Amendment 0004 - 12018255_01-ED101_01-EP101-Response.pdf PDF
Amendment 0004.pdf PDF
Amendment 0004 - 12018718_12018724_Spec013000_Response.pdf PDF
Amendment 0003 - Submission Requirements and Evaluation Criteria (Track Changes).pdf PDF
Amendment 0003.pdf PDF
Amendment 0003 - Plan T600.pdf PDF
Amendment 0003 - Submission Requirements and Evaluation Criteria (Clean).pdf PDF
Solicitation - W912WJ26RA008.pdf PDF
Amendment 0003 - JA 03 (JCI ESS_Redacted).pdf PDF
Amendment 0003 - Revisions to Specification Sections 270511-280500-281300-282300.pdf PDF
Amendment 0002 - Specs Section 01 22 00.pdf PDF
Amendment 0002 - Submission Requirements and Evaluation Criteria (Clean).pdf PDF
Amendment 0002 - Submission Requirements and Evaluation Criteria (Track Changes).pdf PDF
Amendment 0002.pdf PDF
Amendment 0002 - Bidding Schedule.pdf PDF
Amendment 0001.pdf PDF
Amendment 0001 - Submission Requirements and Evaluation Criteria.pdf PDF
Specifications - Volume I.pdf PDF
Contractor Appendix Binder.pdf PDF
Specifications - Volume II.pdf PDF
JA 05 - AMAZ_Redacted.pdf PDF
JA 02 - JCI Fire_Redacted.pdf PDF
JA 03 - JCI ESS_Redacted.pdf PDF
JA 04 - Assa Abloy_Redacted.pdf PDF
JA (Class) - Interior Finishes_Redacted.pdf PDF
JA 01 - Siemens_or_JCI HVAC BAS_Redacted.pdf PDF
Submission Requirements and Evaluation Criteria.pdf PDF
Drawings.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T T

6 7 9 13 14 18 21 22 24 30 33 38

AA

BB

CC

DD

EE

EE'

FF

GG

HH

JJ

CC'

"C

H S

"C

H R

"P

C

PROVIDE NEW STEAM PRV STATION TO THIS LOCATION TO

ALLOW FOR PATH OF NEW STEAM, CONDENSATE, AND

CHILLED WATER LINES THROUGH BUILDING 1. NEW UNIT

TO BE IN 1/3 AND 2/3 CONFIGURATION AND MATCH

EXISTING EQUIPMENT LOAD OF 9,600 LBS/HR, 60PSI INLET,

15 PSI OUTLET.

PROVIDE NEW STEAM

PRESSURE REDUCING

STATION IN 1/3 AND 2/3

CONFIGURATION. MATCH

EXISTING EQUIPMENT

LOAD OF 1500 LBS/HR,

60PSI INLET, 8 PSI

OUTLET.

10"CHR

CHS, CHR AND LPS

PIPES FROM BLDG-6.

3" LPS SERVES

BUILDING 5

3"LPS

"H

P S

"P

C

"H

P S

10" LPS DN

8" MPS DN

10" LPS DN

REFER TO MS-201 SHEET MECHANICAL

SITE PLAN FOR CONTINUATION.

PENETRATIONS SHALL BE SEALED

WITH MODULAR OR LINK RUBBER SEAL

OR AS RECOMMENDED PER DIRECT

BURIED PIPING MANUFACTURER.

(TYPICAL)

"H

P S

"P

C

10"CHR

3"LPS

16"CHS

6"MPS

3"HPC

3"HPC

4"LPS

10"LPS

4"MPS

8"MPS

"M

P S

4"HWS

4"HWR

8"SV

8"SV

4"SV

4"MPS

2"LPC

4"MPS

8"SV

"S

V

6"MPS

2"MPS

4"MPS

6"MPS8"SV

6"MPS

6"MPS

3"HPC

CAP FOR FUTURE CONNECTION TO

SURGICAL TOWER PIPING SYSTEM.

CONNECT TO EXISTING PIPING AT THIS

LOCATION. PROVIDE DOUBLE VALVES

ON STEAM MAIN AS INDICATED.

ROUTE CHILLED WATER LINES

APPROXIMATELY 6" ABOVE FINISH

FLOOR ALONG PATH INDICATED.

ANCHOR PIPING TO EXISTING

CONCRETE STRUCTURE AT THIS

LOCATION. REFER TO F8/M404 FOR

ANCHOR DETAIL.

PIPE GUIDE

PIPE GUIDE

PIPE GUIDE

2"MPS

20"CHS

20"CHR

6"MPS

6"LPS

6"MPS

2" MPS

RELIEF VENT

PRV-2E

6"HPS

5"MPS

PRV-1E

10"MPS (MANIFOLD)

PRV-6E

2"MPS

01-PRV-2

01-PRV-1

5"LPS UP

2 1/2"PC

6"HPS

5"MPS

4"MPS

12"MPS

6"SV

12"MPS 10"SV RISER UP

PRV-E

HPS

HWR

HWS

8"SV

10"MPS

5"MPS

5"MPS

5"MPS

4"LPS

2"LPC

C9

01-MP101

5"LPS

5"LPS

10"SV 8"SV

20"CHR

6"PC

20"CHS

14"HPS

6"CHS

6"CHR

6"MPS

"H

P S

"P

C

"C

H S

"C

H R

6"SV

6"HPS

6"PC

14"HPS

6"CHR

6"CHS

4"HWS

4"HWR

"C

H R

20" CHR BELOW AND

20" CHS ABOVE.

20"CHR

20"CHS

REFER TO MS201 FOR

CONTINUATION.

WATER HEATER

16"CHS

5" HPS & 2 1/2" PC

UNDERGROUND

PIPING TO BUILDING 2

PROVIDE DOUBLE GATE VALVES WITH

GLOBE VALVE BYPASS WITH 1" TAP

AND BLEED VALVE BETWEEN GATE

VALVES. TYPICAL FOR ALL DOUBLE

VALVES SHOWN ON STEAM AND

CONDENSATE PIPING.

3"NHW

20"CHS

14"HPS

20"CHR

6"PC

6"SAN

4"SAN

2"MA

6"SAN

10"FP

10"FP

6"FP

6"FP

6"CHR

6"FP

3"CW

3/4"CW

6"CHS

15 SUNNEN DRIVE

SUITE 104

ST. LOUIS, MO 63143

P: 314.645.1132 F: 314.645.1173

The FUTURE. Built Smarter www.imegcorp.com

PROJECT #22000669.04

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

READY TO ADVERTISE

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD

A/E:

STAMPCONSULTANT

7 8 9 10

US Army Corps of Engineers ®

CONSTRUCTION AGENT

321 4 5 6

A u to d e s k D o c s /0

-1

-0

P h a s e

A

/6

V

A W

H -B

L D

G -0

M P

.r v t

/2 /2

:5

:0

P

M

01-MP101

BUILDING 1 - SUB-GROUND LEVEL -

MECHANICAL PIPING - OPTION BID 0005

New England District

CHILLED WATER PLANT

REPLACEMENT AND SITE UTILITY

IMPROVEMENTS PHASE A2

950 Campbell Avenue, West Haven, CT 06516

689-040

2026-07-31 RUSARN BHAACH

N O R

HT

1/8" = 1'-0"

BUILDING 1 - SUB-GROUND LEVEL - MECHANICAL PIPING - OPTION BID 0005

E4

SHEET NOTES:

1. ALL WORK SHOWN ON SHEET IS PART OF

OPTION BID 0005.

2. REFER TO CIVIL PLANS FOR PROJECT OPTIONS

AND PHASING PLANS.

3. COORDINATE SYSTEM SHUT DOWNS WITH

OWNER. SYSTEM TIE-IN WORK SHALL BE DONE

DURING THE OFF SEASON RELATED TO THE

SYSTEM. CHILLED WATER WORK SHALL BE

DONE DURING WINTER MONTHS AND STEAM

AND CONDENSATE WORK SHALL BE DONE

DURING SUMMER MONTHS.

NO SCALE

ENTRANCE VIEW – BUILDING 01 -

MECH SG182

C9

Revisions: Date:

BIDDING RFIS 09/23/2026