This document is a Technology Schedules drawing (T600) for a federal construction project at the U.S. Department of Veterans Affairs facility located at 950 Campbell Avenue, West Haven, Connecticut. The project involves a Chilled Water Plant Replacement and Site Utility Improvements Phase A2, with project number 689-040, Building 17. The drawing was issued on July 31, 2026, and is prepared by IMEG Corp. as designer of record with Perkins & Will and LEO A.M.V., under construction agent US Army Corps of Engineers, New England District.

The document specifies detailed technology equipment requirements organized into four primary schedules. The Technology Equipment Schedule defines 27 equipment types including security systems (dual authentication card readers, security management control panels), audio/visual systems (wall and ceiling-mounted speakers), information technology infrastructure (equipment racks, fiber distribution cabinets, patch panels, power distribution units, grounding busbars, wire managers, and uninterruptible power supplies), telecommunications equipment (terminal boards, information outlets for data and voice), and video surveillance cameras (interior and exterior IP cameras with specific technical specifications). The Data Connection Schedule establishes connection configurations for various device types including wireless access points, data outlets, voice outlets, television connections, and network connections, with specific cable types and termination standards. The Access Control Door Type Schedule lists 15 door designations with corresponding security requirements, including credential readers, electronic locking hardware, motion detectors, latch status monitoring, and integration with video surveillance and intercom systems. The Individual Camera Requirements Schedule specifies 17 camera installations across two telecom rooms, detailing camera types (CM-1 and CM-2), environment (interior/exterior), field of view locations (roof parapets, stairs, door entrances, telecom room entrances), and mounting specifications. All contractors are responsible for verifying quantities and furnishing complete materials to produce satisfactory working systems, with catalog numbers provided as design basis references only.

View the file

Other files

Show all 24

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

15 SUNNEN DRIVE

SUITE 104

ST. LOUIS, MO 63143

P: 314.645.1132 F: 314.645.1173

The FUTURE. Built Smarter www.imegcorp.com

PROJECT #22000669.04

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

READY TO ADVERTISE

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

DESIGNER OF RECORD

A/E:

STAMPCONSULTANT

7 8 9 10

US Army Corps of Engineers ®

CONSTRUCTION AGENT

321 4 5 6

A u to d e s k D o c s /0

-1

-0

P h a s e

A

/6

-0

V

A W

H B

L D

G -1

E T

.r v t

/2

/2

:4

:1

P

M

T600

TECHNOLOGY SCHEDULES

New England District

CHILLED WATER PLANT

REPLACEMENT AND SITE UTILITY

IMPROVEMENTS PHASE A2

950 CAMPBELL AVENUE

WEST HAVEN, CT 06516

689-040

2026-07-31 ADAJUN DAVLAR

2026-07-31

THE EQUIPMENT LIST ABBREVIATIONS AND THE TECHNOLOGY EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE CONTRACTOR.

EACH CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER

SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKING SYSTEM.

CATALOG NUMBERS ARE NOT TO BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE CONTRACTOR IN THE SEARCH FOR MATERIAL.

NO MATERIAL SHALL BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. EACH CONTRACTOR SHALL FIRST READ THE COMPLETE DESCRIPTION OF THE MATERIAL ON THESE DRAWINGS AND SPECIFICATIONS. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.

"STANDARD COLOR" INDICATES FACTORY FINISH AVAILABLE AT NO ADDITIONAL CHARGE.

TECHNOLOGY EQUIPMENT SCHEDULE

EQUIPMENT LIST

ABBREVIATION EQUIPMENT LIST DESCRIPTION

AC-CR1-W DUAL AUTHENTICATION CARD READER WITH KEYPAD. PROVIDED AS INTEGRAL PART OF SECURITY MANAGEMENT SYSTEM. REFER TO ACCESS CONTROL DOOR TYPE SCHEDULE ON T600 FOR ADDITIONAL INFORMATION. CARD READERS SHOWN ON PLANS TO IDENTIFY INTENDED MOUNTING LOCATION. REFER TO SPECIFICATION SECTION 28 13 00 FOR COMPLETE INFORMATION. PROVIDE PROGRAMMING FOR DUAL AUTHENTICATION. INTEGRATE WITH C-CURE 9000

MANAGEMENT.

AC-SCP-1 SECURITY MANAGEMENT SYSTEM CONTROL PANEL, FOR USE WITH INTEGRATED SECURITY MANAGEMENT SYSTEM.

REFER TO SPECIFICATION SECTION 28 13 00 FOR COMPLETE INFORMATION.

PA-S1-W WALL MOUNTED SPEAKER. MOUNT HORIZONTALLY AT +108" AFF. INSTALL 4" SQUARE BACKBOX WITH A 3/4"CONDUIT TO

THE NEAREST ACCESSIBLE

CEILING IN THE CORRIDOR. COORDINATE MOUNTING HEIGHT WITH ARCHITECTURAL DETAILS.

PA-S-C CEILING MOUNTED SPEAKER. INSTALL 4" SQUARE BACKBOX WITH A 3/4"CONDUIT TO THE NEAREST ACCESSIBLE CEILING

IN THE CORRIDOR.

PW-HH-1 HANDHOLE COMPOSITE POLYMER CONCRETE BODY AND COVER. STAINLESS STEEL HARDWARE BOLTED NON-SKID COVER RATED FOR 15,000LB. DESIGN LOAD OCCASIONAL NON-DELIBERATE VEHICULAR TRAFFIC. STACK UNITS TO ACIEVE DEPTH SHOWN ON PLANS. UNITS IN LANDSCAPED AREAS SHALL BE GREEN IN COLOR. “COMMUNICATIONS” LOGO ON HANHOLE COVER. CONTRACTOR SHALL FIELD VERIFY QUANTITY AND LOCATIONS. REFER TO F7/T400 FOR

DETAIL. PW-HH-1 = 24”WX24”L.

PW-MH-1 MANHOLE, REFER TO C1/T401 FOR DETAIL.

SC-BLK-1 RACK BLANKING PANEL, ANGLED. 1RU, 19" RACK MOUNT.

SC-ER-1 4-POST EQUIPMENT RACK WITH CAGE NUT RAILS, 84" HIGH, 23.75" WIDE SUPPORTING STANDARD 19" MOUNTING SPACE, 30" CHANNEL DEPTH. PRINTED RACK SPACE IDENTIFICATION ON ALL EQUIPMENT RAILS. UL LISTED FOR 2000LBS, PROVIDES (45) 1.75 MOUNTING SPACES. PROVIDE IN WHITE POWDERCOAT FINISH.

PROVIDE WITH FRONT AND REAR SECURITY DOORS WITH SECURITY DOOR MOUNTING HARDWARE. PROVIDE WITH (2)

PDU MOUNTING BRACKETS.

SC-FDC-1 ANGLED OPTICAL FIBER DISTRIBUTION CABINET, RACK MOUNT. HIGH DENSITY 144 FIBER MAXIMUM CAPACITY.

FOR PRE-TERMINATION TRUNKS FOR MCR-01 HDA DISTRIBUTION PROVIDE WITH OM4/OS1 MTP TYPE CASSETTES AS

NECESSARY (LEVITON HDX ENTERPRISE SPMPH SERIES)

FOR CAMPUS TR DISTRIBUTION PROVIDE WITH OM4/OS1 LC, FUSION SPLICE TYPE CASSETTES AS NECESSARY (LEVITON

HDX ENTERPRISE SPLCH SERIES)

REQUIRES (1) 19" X 1.75" RACK MOUNTING SPACES.

SC-GND-1 GROUNDING BUSBAR, WALL MOUNT. 4" H X 20" L X 1/4" D COPPER, ELECTRICALLY ISOLATED BY INSULATORS INTEGRAL TO MOUNTING BRACKETS. COPPER GROUND BAR IS 1/4" THICK AND STAND OFF 2.75" FROM WALL. THE 20" BUSBAR PROVIDES CONNECTION FOR EIGHTEEN (18) 2-HOLE COMPRESSION LUGS RESPECTIVELY WITH 5/8" OR 1" CENTERS.

ANSI/TIA-607 AND BICSI COMPLIANT. UL LISTED.

REFER TO GROUND BAR DETAIL ON 5/T400.

SC-GND-2 GROUNDING BUSBAR, RACK MOUNT.

SC-HWM-1 FLAT SINGLE-SIDED HORIZONTAL WIRE MANAGER WITH FRONT DOOR, (1) RU. 19" RACK MOUNT.

SC-HWM-2 FLAT SINGLE-SIDED HORIZONTAL WIRE MANAGER WITH FRONT DOOR, (2) RU. 19" RACK MOUNT.

SC-IO-C INFORMATION OUTLET, CEILING MOUNT. 2-PORT SURFACE MOUNT BISCUIT. REFER TO DATA CONNECTION SCHEDULE ON

T600 FOR PIN CONFIGURATION.

" # " INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE PLANS.

REFER TO ABOVE CEILING INFORMATION OUTLET DETAIL ON C7/T400.

SC-IO-W INFORMATION OUTLET, WALL MOUNT. COVERPLATE PORTS AS INDICATED ON DATA CONNECTION SCHEDULE, REFER TO

DATA CONNECTION SCHEDULE ON T600 FOR ADDITIONAL INFORMATION.

" # "INDICATES INFORMATION OUTLET FACEPLATE CONFIGURATION AS INDICATED ON THE DRAWINGS.

" W " PROVIDE (1) RJ-45 JACK FOR VOICE AT +42" AFF FOR WALL HUNG PHONE. PROVIDE WITH STAINLESS STEEL

FACEPLATE, MATING LUGS. (LEVITON 4108W-1SP)

INSTALL INFORMATION OUTLET IN EXISTING ROUGH-IN UNLESS OTHERWISE NOTED.

IF NEW ROUGH-IN IS REQUIRED, PROVIDE A 4" SQUARE BACKBOX WITH A SINGLE GANG PLASTER RING. INSTALL A 1.25"

EMT CONDUIT TO NEAREST ACCESSIBLE CEILING.

SC-MPP-1 ANGLED MODULAR PATCH PANEL, 48 MODULAR RJ-45 TERMINATIONS, MOUNTS DIRECTLY TO EIA/TIA STANDARD 19" RELAY RACK, PORT IDENTIFICATION NUMBERS, U.L. LISTED. REQUIRES (1) 1.75" MOUNTING SPACES.

PROVIDE WITH REAR CABLE MANAGER AND ANGLED PANEL COVER.

SC-PDU-1 POWER STRIP, VERTICALLY MOUNTS IN A STANDARD 19” RACK OR CABINET. 208V NOMINAL INPUT VOLTAGE, 120V/208V NOMINAL OUTPUT VOLTAGE. NEMA L21-20P INPUT CONNECTIONS. (36) IEC 60320 C13, (2) NEMA 5-20R, (6) IEC 60320 C19

OUTPUT CONNECTIONS.

PROVIDE WITH (2) PDU FOR EACH FLOOR MOUNTED TR CHANNEL RACK.

SC-TTB TELECOMMUNICATIONS TERMINAL BOARD, 4’X8’X3/4” A-C GRADE FIRE-RATED PLYWOOD. EXPOSED SIDE SHALL BE SMOOTH. MOUNT VERTICALLY WITH TOP OF PLYWOOD AT 8’-6” AFF. IN THE EVENT THE MANUFACTURER’S RATING STAMP IS NOT VISIBLE ON THE SMOOTH SIDE, THE CONTRACTOR SHALL PROVIDE A LAMINATED LETTER FROM THE MANUFACTURER OR SUPPLIER CERTIFYING THAT THE PLYWOOD IS FIRE-RATED AND ATTACH THE LETTER WITH A PICTURE OF THE RATING STAMP TO THE PLYWOOD. PAINT PLYWOOD WITH WHITE FINISH, REFER TO DIVISION 9. FIRE RATED PLYWOOD SHALL NOT BE PAINTED OR TREATED WITH ANY TYPE OF SEALANT THAT WOULD LESSEN THE

INTEGRITY OF THE FIRE RATING.

SC-UPS-1 UNINTERRUPTED POWER SUPPLY.

SC-VWM-1 VERTICAL WIRE MANAGER, 76.94"H X 6.45"W X 10.26"D. REMOVABLE FRONT HINGED DOOR. SPOOLS FOR INTEGRAL BEND

RADIUS CONTROL.

VS-CM-1 SINGLE LENS, SINGLE VARIFOCAL LENS, INTERIOR/EXTERIOR, IP CAMERA. 3.1 MEGAPIXEL, VARIFOCAL: 3.4-8.9 mm, MIN

ILLUMINATION: COLOR: 0.1 LUX, B/W: 0.0 LUX.

FEATURES: WIDE DYNAMIC RANGE, IR ILLUMINATION, VIDEO COMPRESSION: H.264, H.265, MOTION JPEG;

CASING:IP52-RATED; IK RATING; IK10 IMPACT-RESISTANT CASING WITH HARD-COATED DOME; POWER: TYPICAL 6.4W, MAX

10.7W; OPERATING CONDITIONS:

0-50 DEG C.; INCLUDES VANDAL RESISTANT SCREWS. CAMERA COLOR: WHITE.

(2) INFORMATION OUTLETS FOR CAMERA SHALL BE TERMINATED ON AN RJ-45 PLUG.

ALL EXTERIOR CAMERAS TO BE BLACK IN COLOR.

VS-CM-2 360° MULTI-DIRECTIONAL LENS IP CAMERA. 4X3.1 MEGAPIXEL SENSORS, VARIFOCAL: 3.18-8.12 mm, MIN ILLUMINATION:

COLOR: 0.14 LUX, B/W: 0 LUX.

FEATURES: WIDE DYNAMIC RANGE, IR ILLUMINATION, TWO-WAY AUDIO, AND I/O CONNECTIVITY. VIDEO COMPRESSION:

H.264, H.265, MOTION JPEG; CASING: IP66, IP67 -RATED; POWER: MAXIMUM VIDEO RESOLUTION 1920 X 1080; OPERATING CONDITIONS: -30 TO 50 DEG C.; INCLUDES VANDAL RESISTANT SCREWS. CAMERA COLOR: WHITE.

(2) INFORMATION OUTLETS FOR CAMERA SHALL BE TERMINATED ON AN RJ-45 PLUG.

ALL EXTERIOR CAMERAS TO BE BLACK IN COLOR.

AV: CAT6A MPTL MALE RJ45 ORANGE/NA

CAM: CAT6A MPTL MALE RJ45 GREEN/GREEN

WAP: CAT6A MPTL MALE RJ45 RED/NA

DEVICE CONNECTION TYPE

TV: RG-6 F-CONNECTOR

NC: BYN.C.C. BY N.C.C. BY N.C.C.

BLANK: MATCH FACEPLATE/BLUE

DATA: CAT6A RJ45 JACK BLUE/BLUE

FACEPLATE CONFIGURATION TYPE CABLE TYPE TERMINATION TYPE CONNECTOR/CABLE COLOR

LEGEND

NOTES: 1. PROVIDE REMOVABLE BLANK INSERT(S) FOR ALL UNUSED PORTS. 2. LABEL INFORMATION OUTLET FACEPLATES PORTS STARTING TOP LEFT TO BOTTOM RIGHT.

DATA CONNECTION SCHEDULE

CONFIGURATION/

DEVICE CONNECTION

CABLE

COUNT D

IR

E

C T

C O

N N

E C

T

IO

N T

Y P

E

N U

M B

E R

O F

F A

C E

P L

A T

E (S

F A

C E

P L

A T

E P

O R

T S

FACEPLATE PORT IDENTIFICATION

NOTESP

O

S

IT

IO

N

P O

S

IT

IO

N

P O

S

IT

IO

N

P O

S

IT

IO

N

P O

S

IT

IO

N

P O

S

IT

IO

N

1D-WAP 1 1 DATA

D1 1 1 DATA

D2 2 2 DATA DATA

W 1 1 VOICE

1. ELECTRONIC DOOR HARDWARE SUCH AS ELECTRIC STRIKES, ELECTRIC LATCH RETRACTION, ETC. SHALL BE PROVIDED AND INSTALLED BY THIS CONTRACT.

2. REFER TO THE TECHNOLOGY EQUIPMENT SCHEDULE FOR CREDENTIAL READER TYPE INFORMATION.

ACCESS CONTROL DOOR TYPE SCHEDULE

DOOR # S

E

C U

R

IT

Y D

O O

R T

Y P

E

R O

U G

H I N

O N

L Y

CREDENTIAL

READER

REQUEST TO

EXIT DOOR HARDWARE / MONITORING INTEGRATION

OTHER

(REFER TO NOTES)

D E

T A

IL

R

E F

E R

E N

C E

NOTESC

R

E D

E N

T

IA

L R

E A

D E

R T

Y P

E

M U

L T

IP

L

E C

R E

D E

N T

IA

L

R E

A D

E R

S O

P E

R A

T E

S S

IN

G

L E

D O

O R

O P

E R

A T

E S

M U

L T

IP

L

E D

O O

R S

IN

T

E R

N A

L E

L E

C T

R

IF

IE

D

H A

R D

W A

R E

C O

N N

E C

T

IO

N

M O

T

IO

N D

E T

E C

T O

R

L O

C A

L P

U S

H B

U T

T O

N D

O O

R H

A R

D W

A R

E O

V E

R R

ID

E

E L

E C

T R

O N

IC

L

O C

K

IN

G H

A R

D W

A R

E

M A

G L

O C

K

L O

C A

L A

L A

R M

H O

R N

L A

T C

H S

T A

T U

S D

E T

E C

T

IO

N

M O

N

IT

O R

L A

T C

H B

O L

T

M O

N

IT

O R

D O

O R

P O

S

IT

IO

N

S W

IT

C

H S

P D

T

M O

N

IT

O R

D O

O R

P O

S

IT

IO

N

S W

IT

C

H D

P D

T

M O

N

IT

O R

D O

O R

P O

S

IT

IO

N

S W

IT

C

H

O V

E R

H E

A D

D O

O R

M O

N

IT

O R

D O

O R

P O

S

IT

IO

N

S W

IT

C

H

R O

O F

H A

T C

H

A U

T O

M A

T

IC

D O

O R

O P

E R

A T

O R

E L

E V

A T

O R

L O

C K

E D

B Y

E M

E R

G E

N C

Y D

U R

E S

S S

E Q

U E

N C

E

IN

F

A N

T P

R O

T E

C T

IO

N

R E

M O

T E

U N

L O

C K

V

IA

I N

T E

R C

O M

M A

S T

E R

R E

M O

T E

U N

L O

C K

V

IA

P U

S H

B U

T T

O N

IN

T

R U

S

IO

N D

E T

E C

T

IO

N

R E

M O

T E

U N

L O

C K

V

IA

F

IR

E C

O M

M A

N D

C E

N T

E R

V

ID

E O

S U

R V

E

IL

L A

N C

E

W A

N D

E R

P R

E V

E N

T

IO

N S

Y S

T E

M

D E

L A

Y E

D E

G R

E S

S

L O

C A

L

V

A C

P O

W E

R S

U P

P L

Y

S C

H E

D U

L E

B A

S E

D L

O C

K

IN

G

V

IS

U A

L S

T R

O B

E /A

U D

IB

L

E A

L A

R M

000A RIM R1 ● ● ●

000B DPS ●

0S2A RIM R1 ● ● ●

1S1A RIM ● ● ●

100A DPS ●

100B DPS ●

100C DPS ●

100D DPS ●

100E DPS ●

102C RIM R1 ● ● ● DOUBLE DOOR

102D DPS ●

203A RIM R1 ● ● ●

203B RIM R1 ● ● ●

208 RIE R1 ● ● ● ●

WS101 RIM R1 ● ● ●

WS103 RIM R1 ● ● ●

WS104 RIM R1 ● ● ●

WS106A RIM R1 ● ● ●

INDIVIDUAL CAMERA REQUIREMENTS SCHEDULE

CAMERA

TYPE

CAMERA

ENVIRONMENT

TELECOM

ROOM # FIELD OF VIEW DESCRIPTION

MOUNTING

TYPE

DETAIL

REFERENCE

ADDITIONAL

INFORMATION NOTES

CM-2 EXTERIOR TR-1 EXTERIOR ROOF PARAPET 2/T400

CM-2 EXTERIOR TR-1 EXTERIOR ROOF PARAPET 2/T400

CM-2 EXTERIOR TR-1 EXTERIOR ROOF PARAPET 2/T400

CM-2 EXTERIOR TR-1 EXTERIOR ROOF PARAPET 2/T400

CM-1 INTERIOR TR-1 STAIRS WALL 4/T401

CM-1 INTERIOR TR-1 STAIRS WALL 4/T401

CM-1 INTERIOR TR-1 TR ENTRANCES WALL 4/T401

CM-2 EXTERIOR TR-1 EXTERIOR ROOF PARAPET 2/T400

CM-1 INTERIOR TR-1 DOOR ENTRANCES CEILING 3/T401

CM-1 INTERIOR TR-2 TR ENTRANCES WALL 4/T401

CM-1 EXTERIOR TR-2 DOOR ENTRANCES WALL 4/T401

CM-1 EXTERIOR TR-2 DOOR ENTRANCES WALL 4/T401

CM-1 INTERIOR TR-1 DOOR ENTRANCES CEILING 3/T401

CM-1 INTERIOR TR-1 STAIRS WALL 4/T401

CM-1 INTERIOR TR-1 DOOR ENTRANCES WALL 4/T401

CM-1 INTERIOR TR-1 TR ENTRANCES WALL 4/T401

CM-2 EXTERIOR TR-1 EXTERIOR ROOF PARAPET 2/T400

Revisions: Date:

BIDDING RFIs 09/23/2026

T600 - TECHNOLOGY SCHEDULES

File details come from the government source that posted it. Updated .