Amendment 0006 - Drawing CK-505 (Revised).pdf
PDF 752 KB Posted
- Attached to
- Construction of Chilled Water Plant and Site Utility Upgrades at VA Medical Center in West Haven, CT
- Solicitation number
- W912WJ26RA008
About this file
This document is a civil details drawing sheet for a federal construction project. The sheet presents technical specifications and construction details for the Chilled Water Plant Replacement and Site Utility Improvements Phase A2 project located at 950 Campbell Avenue, West Haven, Connecticut 06516. The project is under the U.S. Department of Veterans Affairs, Office of Construction and Facilities Management, with the US Army Corps of Engineers serving as the Construction Agent. The Designer of Record is LEED Accredited, with consultants including Perkins&Will and Mabbett & Associates, Inc. (105 Central Street, Stoneham, MA 02180-1248).
The drawing (CK505) includes detailed specifications for multiple infrastructure components: light pole bases with concrete footings requiring 4000 PSI compressive strength at 28 days and minimum 600 pounds per cubic yard cement content; retaining wall construction with reinforced concrete; 8-foot high security double swing gates and wrought iron swing gates with "Invincible/Spear Pointed" style pickets; water meter vault construction; post indicator valve installation with safety red paint requirements; area drain specifications; and typical utility intersection vertical clearance requirements of 1.5 feet minimum with flowable fill provisions. All concrete work must comply with ACI standards and local governing codes, with reinforcing steel meeting minimum ASTM A615 Grade 60 specifications. The project was marked as "Ready to Advertise" with an RFI bidding date of 09/23/2026 and a designer approval date of 2026-07-31.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FULL DEPTH CONDITION
LEDGE ENCOUNTER CONDITION
NOTE:
1. POLE BASE HEIGHT REVEAL ABOVE FINISHED GRADE SHALL BE AS
36" UNLESS OTHERWISE SPECIFIED ON PLANS
M
I N
S E
E
N O
T E
M I N
(4) #6 REBAR DOWELS, 42" LONG,
WITH 24" EMBEDMENT, GROUT
VOID OPENING IN LEDGE
CIP CONCRETE LEVELING PAD
3" MIN. THICK WHERE NEEDED
36"x36" SQUARE
CONCRETE
FOOTING
GROUND ROD
AS REQUIRED
6" MIN. GRANULAR
FILL SURROUND
CADWELD TO
GROUND ROD
M I N
(3) #4 REBAR EACH WAY
FOOTING (3'Ø)
12" THICK COURSE
AGGREGATE
WRAPPED IN MIRAFI
180N
(4) #4 REBAR WITH TIES
@ 12" O.C. VERTICAL
24"Ø CONCRETE PIER
ELECTRICAL CONDUIT
SEE ELECTRICAL PLANS
FOR NO. OF CONDUIT
PER BASE & SIZES.
FINISH GRADE
ANCHOR BOLTS AS
PER MANUFACTURER
REQUIREMENTS
BARE COPPER GROUND
WIRE
CHAMFER EDGES
1 1/2" MIN.
BASE PLATE
EX. LIGHT POLE TO BE STOCKPILED AND REINSTALLED
WITH NEW FOUNDATION AND CONNECTION
S E
E
N
O T
E
24" FACE TO FACE OF CURB (TYP)
UNLESS OTHERWISE NOTED
EXISTING/PROPOSED GRADE
PROPOSED/EXISTING UTILITY
PROPOSED INTERSECTING UTILITY
MI
N.
O F
1.5 F
T
VE
RT
IC
AL
CL
EA
RA
NC
E
BACKFILL
EXISTING/PROPOSED GRADE
PROPOSED/EXISTING UTILITY
PROPOSED INTERSECTING UTILITY
ADD FLOWABLE FILL IN
BETWEEN PIPES WHEN
VERTICAL CLEARANCE IS LESS
THAN 1.5FT
BACKFILL
NTS
≥ 1.5 FT
NTS
NTS
2-TON LIFT ANCHOR
(4 PLACES IN TOP)
TOP
3'-6" LONG GALVANIZED "C" CHANNEL
(3 EACH SIDE)
BASE
18" X 18" KNOCKOUT
(2 EACH SIDE, 2 EACH END)
(ALTERNATIVE)
18" X 24" KNOCKOUT
(2 EACH SIDE, 2 EACH END)
(ALTERNATIVE)
12" DIA.
SUMP
1" DIA. GROUND ROD KNOCKOUT
LOCKING GALV. STEEL DOORS
NOTE: DESIGNED FOR 0 TO 5'-0" OF COVER
12"
GRADE
NOTES:
1. CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 4000 PSI AT 28 DAYS WITH A
MINIMUM CEMENT CONTENT OF 600 POUNDS PER CUBIC YARD FOR ALL FOOTINGS.
2. ALL CONCRETE SHALL HAVE A SLUMP OF NO GREATER THAN 4" (TO WITHIN A TOLERANCE OF 1").
3. ALL EXPOSED CONCRETE SHALL BE AIR-ENTRAINED, 6 (WITHIN 1% TOLERANCE), CONFORMING TO
ASTM C260.
4. REINFORCING STEEL BARS SHALL BE A MINIMUM ASTM A615, GRADE 60, AND SHALL BE FIELD WIRED IN
PLACE.
5. ALL FORMWORK AND PLACEMENT OF CONCRETE SHALL COMPLY WITH GOOD CONSTRUCTION
PRACTICED AND BE IN ACCORDANCE WITH ALL LOCAL GOVERNING CODES, AND REGULATIONS AS
WELL AS THE AC1 AND UNIFORM BUILDING CODE.
6. ALL STEEL SHALL BE GRADE F = 60,000
#6 BARS @ 18" O.C.
TOP & BOTTOM (TYP.)
3" CLEAR (TYP)
24" TYP.
4' - 0"
4"PVC WEEP HOLE @ O.C. (TYP.)
GRADE
12"
2" x 4" KEYWAY (TYP)
(3) #4 REBARS
CONTINUOUS
TOP & BOTTOM
CONCRETE FOOTING f'c = 4000 PSI
SUITBALE COMPACTED SUBGRADE
MAX. ALLOWABLE SOIL BEARING
CAPACITY = 2000 PSF. TO BE VERIFIED
IN FIELD PRIOR TO CONSTRUCTION
3" MIN. CLEAR
# 4 HORIZONTAL BARS @ 18" O.C. (TYP.)
REINFORCED, POURED CONCRETE WALL
#6 BARS VERTICAL @ 18" O.C. (TYP.)
FILTER FABRIC (TYP.)
CRUSHED STONE (TYP.)
COMPACTED BACKFILL IN 12"
LIFTS TO 95% OPTIMAL DENSITY
M
I N
M
A X
NTS
" TOP RAIL
POST SIZE VARIES
WITH HEIGHT
8' O.C.
VARIES
WITH
HEIGHT
2"
8'
HEIGHT
54"
MIN.
FOOTING DEPTH
3 3/4"
TYPICAL
20"
8' HIGH
"INVINCIBLE/SPEAR
POINTED" STYLE 3 RAIL
SWING GATE.
FACE CURVED
"INVINCIBLE/SPEAR
POINTED" STYLE
PICKETS OUTWARD
FROM PROTECTED SITE
EMBED POSTS IN
CONCRETE BASE,
MIN. 36"
12" 12"
REINFORCE WITH
6"x6"xW4 10
GAUGE MESH, 2"
CLEARANCE ALL
SIDES (TYP)
4000 PSI CONCRETE
@ 28 DAYS (TYP)
NTS
12"
DROP RODS
GATE LOCK
SYSTEM
NTS
NTS
M
A X
M
I N
OUTDOOR LISTED
SUPERVISORY TAMPER
SWITCH
WATER LINE
2 COATS OF RUSTOLEUM OIL
BASE SAFETY RED PAINT SHALL
BE APPLIED TO POST INDICATOR
AT LEAST EVERY FIVE YEARS.
POST INDICTOR WITH
BREAKAWAY PADLOCK.
PADLOCK SUPPLIED BY
VA, ALL SYSTEMS SHALL
BE LOCKED IN OPEN
POSITION.
NTS
NTS
6'
HEIGHT
POST CAPS
FENCE
CHANNELS
PICKETS
POST
BOTTOM RAIL
" TYPICAL
EMBED POSTS IN
CONCRETE BASE,
MIN. 36"
4000 PSI CONCRETE
@ 28 DAYS (TYP)
48"
MIN.
FOOTING DEPTH
6'
HEIGHT
POST CAPS
FENCE
CHANNELS
PICKETS
POST
BOTTOM RAIL
48"
MIN.
FOOTING DEPTH
GATE LEAF FRAME
NTS
SOLID GRATE PEDESTRIAN
RATED
18" MIN 18" MIN
MIN 12" BASIN
DRAIN PIPE DRAIN PIPE
4" M
IN
FO
R
"-2 4"
BA
SI
NS
NOTES
1. THE BACKFILL MATERIAL SHALL BE CRUSHED STONE OR OTHER
GRANULAR MATERIAL MEETING THE REQUIREMENTS OF CLASS I, CLASS II,
OR CLASS III MATERIAL AS DEFINED IN ASTM D2321. BEDDING & BACKFILL
FOR SURFACE DRAINAGE INLETS SHALL BE PLACED & COMPACTED
UNIFORMLY IN ACCORDANCE WITH ASTM D2321.
NOTES:
1. PROVIDE THRUST BLOCKS AS REQUIRED.
CK505
CIVIL DETAILS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseDESIGNER OF RECORD A/E:
STAMPCONSULTANT
7 8 9 10
US Army Corps of Engineers ®
CONSTRUCTION AGENT
321 4 5 6
A u t o d e s k
D o c s P h a s e A
B
L D
G A
R C
H I n t e r i o r r v t
New England District
CHILLED WATER PLANT
REPLACEMENT AND SITE UTILITY
IMPROVEMENTS PHASE A2
950 CAMPBELL AVENUE
WEST HAVEN, CT 06516
689-040
Revisions: Date:
Scientists I Engineers I Program Managers
Mabbett & Associates, Inc.
105 Central Street Stoneham, MA 02180-1248
T. 781-275-6050 www.mabbett.com
Mabbett
R
2026-07-31 RBB KRS
READY TO ADVERTISE
BIDDING RFIS 09/23/2026 2
| Sheets and Views |
| 505 20260206 |
File details come from the government source that posted it. Updated .