Prototypical questions through December 12 Prototypical Project Questions
1. In reviewing both the contract specifications and drawings, there is no mention of the requirement of sprinklers (fire protection). Please confirm
Answer: No sprinklers are required.
2. The plans and scope conflict in that the specified bay spacing of 25ft on center places a column in the middle of entry doors #1 and #2. I suggest a bay spacing of 20ft on center to solve this problem.
Answer: Bay spacing can be adjusted to 20ft on center as the 25ft spacing would interfere with the door location.
3. Would you provide the typical and peak occupancy for proposed Room 112 (Common Area)?
Answer: Room 112 is a break room/conference room. Typical would be zero. Normal occupancy for a meeting would be 10-15 with approximately 8-10 hours of meetings a week. Peak occupancy would be 30.
4. When do you anticipate a new site drawing to be available?
Answer: New site drawing is included with these answers.