WVA B120 - COMBINED DRAWING - RTA 300-345.pdf

PDF 6 MB Posted

Attached to
Repair Building 120 at Watervliet Arsenal (WVA), New York
Solicitation number
W912DS24R0020
Issued by

About this file

This document appears to be a set of construction drawings and related documents for the Repair Building 120 project at Watervliet Arsenal in New York. The project scope includes renovating a 102,000 square foot commercial and industrial building to consolidate a wood shop and general facility maintenance on the ground level, construct a new lab facility on the second level, and provide new office space on the third level.

The federal contract opportunity is a Solicitation (W912DS24R0020) issued by the U.S. Army Corps of Engineers Engineering District New York with an estimated value of $25M-$100M. The acquisition strategy is a single-step "Best Value Trade Off" procurement that will involve a Project Labor Agreement. Key details include the requirement to provide pathways, conduit, and back boxes for various security, communications, and audio visual systems, as well as coordination with the government's systems contractor. The solicitation is currently open with no specific closing date provided.

View the file

Other files

File Type Posted
Weapons Development Lab (Photo Lab sprinklers)_Bldg 120_2nd Floor_Drawing 4856-120_Sheet 36 of 79_1 Oct 71.pdf PDF
31 00 00.docx DOCX document
Miscellaneous Sprinkler Work_Bldg 120_Drawing 4782-120_Sheet 1 of 1_Aug 74.pdf PDF
Automatic Sprinkler System_Bldg 120_Drawing 2664-120_Sheet 1 of 1_Apr 52.pdf PDF
Sprinkler System Warehouse_Bldg 120_Drawing 2661-120_Sheet 1 of 1_6 Jun 45.pdf PDF
Lab 253 Work Order 7 fire protection_Bldg 120_Drawing 5877-120_Sheet M2_Apr 93.pdf PDF
C-WVA_B120_Amdt 7_C-500 Details_ UNSTAMPED.pdf PDF
C-WVA_B120_Amdt 7_C-101 Demolition Plan_ UNSTAMPED.pdf PDF
C-WVA_B120_Amdt 7_C-104 Natural Gas Service Line Plan_ UNSTAMPED.pdf PDF
33 51 15.docx DOCX document
C-WVA_B120_Amdt 7_C-102 Site Plan_ UNSTAMPED.pdf PDF
C-WVA_B120_Amdt 7_C-103 Utilities Plan_ UNSTAMPED.pdf PDF
Fire Protection_Bldg 120_Drawing 7557-6910 and 6911_Sheet 31 and 311 of 356_3 Nov 81.pdf PDF
Install Additions To Sprinkler System_Bldg 120_Drawing 5459-120_Sheet 1 of 1_Feb 84.pdf PDF
Amendment 9 W912DS24R0020.pdf PDF
Amendment 8 W912DS24R0020.pdf PDF
Amendment 8 W912DS24C0025.pdf PDF
A-606 - DOOR HARDWARE SCHEDULE_Amend7.pdf PDF
G-006 - PHASING PLAN_Amend7.pdf PDF
G-005 - PHASING PLAN_Amend7.pdf PDF
Amendment 7 W912DS24R0020.pdf PDF
G-008 - TEMPORARY BOX SHOP PLAN_Amend7.pdf PDF
A-102 - SECOND FLOOR PLAN_amend7.pdf PDF
A-605 - DOOR SCHEDULE PANEL FRAME TYPES DOOR HARDWARE SCHEDULE Amend7.pdf PDF
A-110 - ENTRY LEVEL REFLECTED CEILING PLAN_Amend7.pdf PDF
WVA B120 - Furniture Specification - RTA.pdf PDF
Site Visit Sign In Sheet 8 Aug 2024.pdf PDF
41 22 13.15.pdf PDF
Amendment 6 W912DS24R0020.pdf PDF
Amendment 5 W912DS24R0020.pdf PDF
Site Visit Sign In Sheet 24 July 2024.pdf PDF
Amendment 0004 -W912DS24R0020.pdf PDF
Amendment 3 Drawings.pdf PDF
Amendment 3 - W912DS24R0020.pdf PDF
WVA B120 - COMBINED DRAWING - RTA part 7.pdf PDF
WVA B120 - COMBINED DRAWING - RTA part 5.pdf PDF
WVA B120 - COMBINED DRAWING - RTA part 4.pdf PDF
WVA B120 - COMBINED DRAWING - RTA part 6.pdf PDF
WVA B120 - COMBINED DRAWING - RTA part 2.pdf PDF
Amendment 2 - W912DS24R0020.pdf PDF
12 35 53.19.pdf PDF
WVA B120 - COMBINED DRAWING - RTA part 3.pdf PDF
WVA B120 - COMBINED DRAWING - RTA part 1.pdf PDF
MP-WVA120_R22_PP-201.pdf PDF
MP-WVA120_R22_PP-200.pdf PDF
WVA Visitor Notificaton form - Site Visit B120 (002).pdf PDF
Amendment 1 W912DS24R0020.pdf PDF
WVA B120 - COMBINED DRAWING - RTA 150-175.pdf PDF
WVA B120 - COMBINED DRAWING - RTA 1-25.pdf PDF
WVA B120 - COMBINED DRAWING - RTA 200-249.pdf PDF
Show 40 more

Latest 50 of 59 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

07/01/2024

SYMBOL DESCRIPTION

KEYED NOTE (SEE SCHEDULE)

ROLLUP DOOR PROXIMITY DOOR CONTACT

CARD READER

ELECTRIC STRIKE

MOTION DETECTOR (TYPE DENOTED)

KEYPAD

MAGNETIC LOCK

COMBINATION LOCK

CCTV CAMERA WITH PAN/TILT DRIVE

CCTV CAMERA

ELECTRIC LOCK

ACCESS CONTROL SYSTEM PANEL

REQUEST TO EXIT PUSH BUTTON

REQUEST TO EXIT MOTION SENSOR

PROVIDE PATHWAYS, CONDUIT AND BACKBOXES

TO LOCATIONS INDICATED ON PLANS. OWNER SYSTEMS

CONTRACTOR WILL PROVIDE DEVICES AND WIRING FOR THESE

SYSTEMS.

DOOR CONTACT

1. SYSTEMS SCOPE INCLUDES BACK BOXES, CONDUIT AND PATHWAYS FOR SYSTEMS INDICATED. CABLING AND SYSTEM COMPONENTS ARE PROVIDED

BY OTHERS.

2. ALL WORK IS TO BE COMPLETED PER DIVISION 26 & 27 SPECIFICATIONS, NFPA 70 AND ALL APPLICABLE LOCAL STANDARDS AND CODE AMENDMENTS AS

ENFORCED BY THE LOCAL AUTHORITY HAVING JURISDICTION.

3. IN THE EVENT OF CONFLICTS BETWEEN THE DRAWINGS, SPECIFICATIONS, CODES AND REGULATIONS, THE STRICTER REQUIREMENT SHALL BE

FOLLOWED UNLESS PRIOR APPROVAL IS OBTAINED FROM THE GOVERNMENT'S REPRESENTATIVE.

4. SYMBOLS IN THE LEGEND ARE GENERALLY APPLICABLE. FOR EXACT REQUIREMENTS REFER TO THE SCHEDULES, LAYOUTS, DETAILS AND SPECIFICATIONS SINCE THE APPEARANCE OF A PARTICULAR SYMBOL IN THE LEGEND DOES NOT NECESSARILY IMPLY THAT THE ITEM IS INCLUDED IN

THE CONTRACT.

5. ALL EQUIPMENT CONTROL SYSTEM CUT-OVERS, OUTAGES AND SHUTDOWNS ARE TO BE COORDINATED WITH THE GOVERNMENT'S REPRESENTATIVES

PRIOR TO EXECUTION.

6. PROVIDE 200# PULL CORD IN EACH EMPTY CONDUIT.

7. CONDUIT RUNS THAT ARE ROUTED BEHIND PERMANENTLY FIXED LADDER POSITIONS SHALL BE ROUTED SUCH AS TO MAINTAIN 7" (MINIMUM)

CLEARANCE BETWEEN THE LADDER AND CONDUIT AND/OR MOUNTING HARDWARE.

8. PROVIDE SEAL-OFF FITTINGS IN CONDUITS THAT ENTER A CLASSIFIED OR CONDITIONED AREA FROM A NON-CLASSIFIED OR NON-CONDITIONED AREA.

9. ALL EQUIPMENT LOCATIONS AND CONDUIT ROUTES ARE APPROXIMATE AND ARE SHOWN FOR REFERENCE AND CLARITY. EXACT LOCATIONS ARE TO

BE VERIFIED WITH ALL APPLICABLE DISCIPLINES.

10. PROVIDE ADDITIONAL SUPPORTS FOR RACEWAYS AND OTHER ELECTRICAL DEVICES WHEREVER THE BUILDING STRUCTURE IS NOT SUITABLE FOR

DIRECT MOUNTING. ELECTRICAL EQUIPMENT SHALL NOT BE SUPPORTED BY EQUIPMENT OF OTHER TRADES.

11. COORDINATE ALL WORK WITH OTHER TRADES PRIOR TO ROUGH-IN.

12. PROVIDE ALL CONDUIT AND ACCESSORIES REQUIRED BY THE EQUIPMENT MANUFACTURER(S). COORDINATE REQUIREMENTS WITH THE EQUIPMENT

MANUFACTURER(S) DURING THE SUBMITTAL PROCESS.

13. WHERE DIMENSIONS ARE SHOWN ADJACENT TO A DEVICE (FOR EXAMPLE: +6"), THE DEVICE SHALL BE INSTALLED WITH IT'S CENTERLINE 6" ABOVE THE

FINISHED FLOOR.

14. AC POWER AND LIGHTING CIRCUIT RACEWAYS SHALL BE SEPARATED FROM AUDIO AND VISUAL SYSTEM RACEWAYS UTILIZING THE FOLLOWING

MINIMUM SEPARATION REQUIREMENTS (PARALLEL ROUTING):

A. LINE LEVEL AUDIO CONDUIT: 2' FROM SPEAKER AND POWER CONDUITS; 1' FROM CONTROL AND VIDEO CONDUITS.

B. CONTROL AND VIDEO CONDUIT: 1' FROM POWER CONDUITS.

C. SPEAKER CONDUIT: 1' FROM POWER CONDUIT.

D. ALL CROSSINGS SHALL BE AS CLOSE TO 90˚ AS POSSIBLE.

15. DURING ROUGH-IN COORDINATE PLACEMENT OF BOXES FOR DEVICES., TO ENSURE THAT BOXES ARE GANGED AND GROUPED TOGETHER, AND CENTERED ON WALL SECTIONS OR BENEATH WINDOWS EXCEPT AS NOTED ON PLANS. CONTRACTOR SHALL SPAN BETWEEN FRAMING CHANNELS AS NECESSARY TO ACCOMPLISH POSITIONING OF DEVICES DESCRIBED ABOVE. USE PARTITIONS WHERE VOLTAGE BETWEEN EXPOSED LIVE PARTS OF

ADJACENT SWITCHES MAY EXCEED 300 VOLTS.

16. DO NOT INSTALL BOXES IN WALLS BACK-TO-BACK. PROVIDE A MINIMUM SEPARATION OF 3" FOR BOXES TO BE INSTALLED ON OPPOSITE SIDES OF

WALLS.

17. REFER TO ARCHITECTURAL AND STRUCTURAL CONSTRUCTION DRAWINGS FOR EXACT LOCATIONS OF EQUIPMENT (I.E. TELEVISIONS, FAX MACHINES/COPIERS, MOTORIZED SCREENS, KITCHEN EQUIPMENT, MOTORS, ETC.). MAKE ADJUSTMENTS IN THE FIELD AS REQUIRED.

18. FOR ALL RATED FLOORS AND WALLS, PENETRATIONS SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE DETAILS SHOWN IN THIS PACKAGE AND/OR

THE MOST RECENT U.L. DETAILS AND STANDARDS.

19. ALL DETAILS ARE TYPICAL, UNLESS OTHERWISE NOTED. WHERE CONSTRUCTION ACTIVITIES MAY DICTATE MODIFICATION TO AN ELECTRICAL DETAIL NOTIFY ENGINEER WITH EXACT CONDITIONS AND PROPOSED SOLUTION FOR REVIEW AND APPROVAL TO PROCEED.

20. ALL PENETRATIONS THRU FLOORS OR WALLS FOR CONDUITS, CABLE TRAY, ETC. SHALL BE SEALED TO MAINTAIN THE WALL OR FLOOR RATING AND SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE MOST CURRENT U.L. DETAILS AND STANDARDS, AND ANY SPECIFIC REQUIREMENTS CONTAINED IN THE ARCHITECTURAL/STRUCTURAL CONSTRUCTION DOCUMENTS. COORDINATION SHALL BE PERFORMED PRIOR TO MAKING ANY PENETRATION TO

DETERMINE THE APPROPRIATE METHOD REQUIRED FOR SEALING THE PENETRATION.

21. INSTALL EXPANSION FITTINGS IN CONDUITS CROSSING BUILDING EXPANSION JOINTS.

22. MAINTAIN CODE REQUIRED MINIMUM CLEARANCE AROUND EQUIPMENT.

23. DESIGN SHALL BE IN COMPLIANCE WITH APPLICABLE CYBER SECURITY REQUIREMENTS.

24. REFER TO G-003 SIGNAGE & DEVICE LOCATIONS FOR TYPICLA MOUNTING HEIGHTS, UON.

SYMBOL DESCRIPTION

COMMUNICATIONS OUTLET, VOICE ONLY; MOUNT AT 18” AFF

UNLESS OTHERWISE NOTED; PROVIDE 4 SQUARE BOX, SINGLE

GANG MUD RING, 1” CONDUIT STUBBED OUT ABOVE THE NEAREST

ACCESSIBLE CEILING SPACE, PLASTIC BUSHING, AND 200LB TEST

PULL STRING. PROVIDE ALL MOUNTING HARDWARE TO MAKE THIS

A COMPLETE AND FULLY FUNCTIONAL INSTALLATION. “W”

INDICATES WALL MOUNTED AT 54” AFF.

AUDIO VISUAL BACK BOX, PROVIDE 1"C TO ACCESSIBLE CEILING.

PROVIDE 1"C TO FLOOR BOX AS APPLICABLE.

POWER/COMMUNICATION FLOOR BOX. REFER TO FLOOR AND POKE

THRU SCHEDULE

PROVIDE PATHWAYS, CONDUIT AND BACKBOXES

TO LOCATIONS INDICATED ON PLANS. OWNER SYSTEMS

CONTRACTOR WILL PROVIDE DEVICES AND WIRING FOR THESE

SYSTEMS.

AV

DATA BACK BOX WITH 1" FMC WIP TO FURNIURE DATA TROUGH

FC

OPEN SPACE

COORDINATE CR INSTALLATION

WITH ELEVATOR EQUIPMENT.

60" A.F.F.

AV

SBB

COORDINATE LOCATION

WITH EQUIPMENT PRIOR

TO ROUGH-IN

COORDINATE LOCATION

WITH EQUIPMENT PRIOR

TO ROUGH-IN

COORDINATE LOCATION

WITH EQUIPMENT PRIOR

TO ROUGH-IN

COORDINATE LOCATION

WITH EQUIPMENT PRIOR

TO ROUGH-IN

SBB

PBB

SBB

' A

FF

' A

FF

' A

FF

12' AFF

DATA FOR VHP REMOTE

COMMUNICATIONS

EMERGENCY PHONE

EMERGENCY

PHONE

EMERGENCY PHONE

EMERGENCY PHONE

EMERGENCY

PHONE

EMERGENCY PHONE

EMERGENCY PHONE

CEILING

1/2" C (TYP)

1/2" C

JUNCTION BOX

1"C

1" FLEXIBLE C

TO BENCH TROUGH

CEILING

PBB

SBB

SBB

SBB

TO MAIN GROUND BAR

NOTES:

1. RISER IS DIGRAMITIC SEE FLOOR PLANS FOR ROOM LOCATIONS

SBB

(2) 4" SLEEVES

(2) 4" SLEEVES

CABLE TRAY

File details come from the government source that posted it. Updated .