Amendment 0008.pdf

PDF 1 MB Posted

Attached to
Building 740, Lee Barracks and Building 738, Sherman Barracks Repair
Solicitation number
W912DS21B0004
Issued by

About this file

This pre-solicitation notice outlines a forthcoming solicitation for repair work at two buildings located at the United States Military Academy at West Point. The U.S. Army Corps of Engineers, New York District intends to issue a solicitation seeking a firm-fixed price contract for repair of Building 740, Lee Barracks and repair of Building 738, Sherman Barracks, including supporting utility and site work. The scope of work for Building 740 involves full interior and exterior renovation, replacement of mechanical, electrical and plumbing systems, addition of a Cadet Health Clinic, and abatement of hazardous materials. Repairs for the optional work at Building 738 include similar full interior and exterior renovation and replacement of building systems. The period of performance is approximately 1034 calendar days from notice to proceed. The solicitation is expected to be posted on sam.gov on or about August 6, 2021 with proposals due approximately 30 days later. The NAICS code is 236220 and business size standard is $39.5M.

View the file

Other files

File Type Posted
Bid Abstract.pdf PDF
W912DS21B0004 Amendment 11.pdf PDF
Lee Barracks Electrical Drawings for Amendment.pdf PDF
Amendment 0010.pdf PDF
Amendment 0009.pdf PDF
Amendment 0008_Combined Drawings Final 9-10-21.pdf PDF
Amendment 0008_Combined Specifications 9-10-21.pdf PDF
Amendment 0007_LEE-SHERMAN SPECS rev.pdf PDF
Amendment 0007_Lee Sherman Section 01 32 00 Scheduling.pdf PDF
Amendment 0007_Dwgs_Sherman Barracks.pdf PDF
Amendment 0007_Building 740 Lee Barracks Site Walk through Sign in Sheet.pdf PDF
Amendment 0007.pdf PDF
Amendment 0007_Dwgs_Lee Barracks.pdf PDF
Amendment 0007_Sherman Barracks GER.pdf PDF
Amendment 0007_5.4 GER_West Point Lee Barracks signed.pdf PDF
Amendment 0006.pdf PDF
Amendment 0005.pdf PDF
Amendment 0004.pdf PDF
Amendment 0004_STEAM VAULT AMENDMENT DRAWINGS SHERMAN.pdf PDF
Amendment 0004_STEAM VAULT AMENDMENT DRAWINGS LEE.pdf PDF
Amendment 0004_Photos_Steam Vault F-4.pdf PDF
Amendment 0004_Photos_Steam Vault F-8.pdf PDF
Amendment 0004_WP Lee and Sherman Steam Vault Amendment SPECIFICATIONS 17 AUG 2021.pdf PDF
Amendment 0004_Photos_Steam Vault F-3.pdf PDF
Amendment 0003_RTA Drawings Lee Vol 1_Part3.pdf PDF
Amendment 0003_RTA Drawings Lee Vol 1_Part1.pdf PDF
Amendment 0003_RTA Drawings Lee Vol 1_Part2.pdf PDF
Amendment 0003_RTA Drawings Lee Vol 1_Part4.pdf PDF
Amendment 0003.pdf PDF
Amendment 0002.pdf PDF
Amendment 0001.pdf PDF
RTA Drawings Lee Vol 2.pdf PDF
RTA Drawings Lee Vol 3.pdf PDF
RTA Drawings Lee Vol 1_Part3.pdf PDF
RTA Drawings Lee Vol 1_Part2.pdf PDF
RTA Drawings Lee Vol 1_Part1.pdf PDF
RTA Drawings Sherman Vol 2_Part2.pdf PDF
RTA Drawings Sherman Vol 2_Part1.pdf PDF
RTA Drawings Sherman Vol 1_Part2.pdf PDF
RTA Drawings Sherman Vol 1_Part1.pdf PDF
VOL 3 WP Lee and Sherman RTA Specs 23 JULY 2021.pdf PDF
VOL 2 WP Lee and Sherman RTA Specs 23 JULY 2021.pdf PDF
W912DS-21-B-0004_Solicitation.pdf PDF
VOL 4 WP Lee and Sherman RTA Specs 23 JULY 2021.pdf PDF
VOL 1 WP Lee and Sherman RTA Specs 23 JULY 2021.pdf PDF
Show all 45

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AMENDMENT OF SOLICITATION/MODIFICATION OF CONTRACT

Except as provided herein, all terms and conditions of the document referenced in Item 9A or 10A, as heretofore changed, remains unchanged and in full force and effect.

15A. NAME AND TITLE OF SIGNER (Type or print)

30-105-04EXCEPTION TO SF 30

APPROVED BY OIRM 11-84

STANDARD FORM 30 (Rev. 10-83) Prescribed by GSA

FAR (48 CFR) 53.243

The purpose od Amendment 0008 is:

1) Bid opening date is hereby extended to 20 September 2021 at 2:00 P.M. EST

2) Revise and Reissue Bid Schedule

3) Changes to the Draw ings and Specif ications.

4) Respond to bidder requests for information. For information only.

NOTE: Bidders must acknow ledge receipt of this amendment by date specif ied in the bid (or as amended) by one of the follow ing methods: In space provided on the SF 1442, by separate letter, or by signing block 15 below . FAILURE TO ACKNOWLEDGE AMENDMENT BY DATE SPECIFIED MY RESULT IN REJECTION OF YOUR BID IN ACCORDANCE WITH THE LATE BID, LATE MODIFICATION OF BID, OR LATE WITHDRAWAL OF BID (FAR 14.304)

1. CONTRACT ID CODE PAGE OF PAGES

1 39

16A. NAME AND TITLE OF CONTRACTING OFFICER (Type or print)

16C. DATE SIGNED

BY 10-Sep-2021

16B. UNITED STATES OF AMERICA15C. DATE SIGNED15B. CONTRACTOR/OFFEROR

(Signature of Contracting Officer)(Signature of person authorized to sign)

8. NAME AND ADDRESS OF CONTRACTOR (No., Street , County, State and Zip Code) X W912DS21B0004

X 9B. DATED (SEE ITEM 11)

06-Aug-2021

10B. DATED (SEE ITEM 13)

9A. AMENDMENT OF SOLICITATION NO.

11. THIS ITEM ONLY APPLIES TO AMENDMENTS OF SOLICITATIONS

X The above numbered solicitation is amended as set forth in Item 14. The hour and date specified for receipt of Offer X is extended, is not extended.

Offer must acknowledge receipt of this amendment prior to the hour and date specified in the solicitation or as amended by one of the following methods:

(a) By completing Items 8 and 15, and returning copies of the amendment; (b) By acknowledging receipt of this amendment on each copy of the offer submitted;

or (c) By separate letter or telegram which includes a reference to the solicitation and amendment numbers. FAILURE OF YOUR ACKNOWLEDGMENT TO BE RECEIVED AT THE PLACE DESIGNATED FOR THE RECEIPT OF OFFERS PRIOR TO THE HOUR AND DATE SPECIFIED MAY RESULT IN

REJECTION OF YOUR OFFER. If by virtue of this amendment you desire to change an offer already submitted, such change may be made by telegram or letter, provided each telegram or letter makes reference to the solicitation and this amendment, and is received prior to the opening hour and date specified.

12. ACCOUNTING AND APPROPRIATION DATA (If required)

13. THIS ITEM APPLIES ONLY TO MODIFICATIONS OF CONTRACTS/ORDERS.

IT MODIFIES THE CONTRACT/ORDER NO. AS DESCRIBED IN ITEM 14.

A. THIS CHANGE ORDER IS ISSUED PURSUANT TO: (Specify authority) THE CHANGES SET FORTH IN ITEM 14 ARE MADE IN THE

CONTRACT ORDER NO. IN ITEM 10A.

B. THE ABOVE NUMBERED CONTRACT/ORDER IS MODIFIED TO REFLECT THE ADMINISTRATIVE CHANGES (such as changes in paying office, appropriation date, etc.) SET FORTH IN ITEM 14, PURSUANT TO THE AUTHORITY OF FAR 43.103(B).

C. THIS SUPPLEMENTAL AGREEMENT IS ENTERED INTO PURSUANT TO AUTHORITY OF:

D. OTHER (Specify type of modification and authority)

E. IMPORTANT: Contractor is not, is required to sign this document and return copies to the issuing office.

14. DESCRIPTION OF AMENDMENT/MODIFICATION (Organized by UCF section headings, including solicitation/contract subject matter where feasible.)

10A. MOD. OF CONTRACT/ORDER NO.

2. AMENDMENT/MODIFICATION NO. 5. PROJECT NO.(If applicable)

6. ISSUED BY

3. EFFECTIVE DATE

10-Sep-2021

CODE

US ARMY CORPS OF ENGINEERS, NEW YORK

26 FEDERAL PLAZA, RM 16-300

NEW YORK NY 10278-0090

W912DS 7. ADMINISTERED BY (If other than item 6)

4. REQUISITION/PURCHASE REQ. NO.

CODE

See Item 6

FACILITY CODECODE

EMAIL:TEL:

W912DS21B0004

SECTION SF 30 BLOCK 14 CONTINUATION PAGE

The following items are applicable to this modification:

AMENDMENT 0008

Lee and Sherman Barracks

USMA, West Point, New York

W912DS21B0014

Amendment 0008

AMENDMENT 0008 for Renovation of Lee and Sherman Barracks at West Point, NY

W912DS21B0014.

TO BIDDERS:

Bid Opening: Bid due date/opening has been changed from 15 Sep 21 to 20 Sep 21.

Price Schedule Changes:

CLIN 0001 - Add exclusions to clarify what CLIN 0001 represents.

CLIN 0004 - Revised description to clarify intent and changed SF to LF for granite repointing.

CLIN 0010 - Add “and associated pipe work.”

CLIN 0013 - Revised description to clarify intent and changed SF to LF for granite repointing. And added SubCLINs 13E, F, and G representing the west elevation Sherman Barracks.

TOTAL: Revised the language to include all CLINs 0001-0020.

The following changes shall be made to the drawings and specifications.

DRAWINGS:

CIVIL

I. DRAWING CHANGES

NONE

II. NEW DRAWINGS

NONE

III. REISSUEDD DRAWINGS

NONE

STRUCTURAL

Lee S-002 Concrete Repair Notes #3A - added allowance for lineal feet of crack repair at slab on grade

Lee S-100S

Added note to address potential sheeting and shoring at installation of vaults F3 and F4

Lee S-101 Added note regarding fireproofing of FRP below slab

Lee S-102 Added note regarding fireproofing of FRP below slab

Lee S-103 Added note regarding fireproofing of FRP below slab

Lee S-104

1. Added note regarding fireproofing of FRP below slab

2. Revised note to remove FRP on top of slab (E.F.)

Lee S-105 Added note regarding fireproofing of FRP below slab

Lee S-106 Added note regarding fireproofing of FRP below slab

Lee S-305 Detail A7 - Revised note at crushed stone to EXISTING

Sherman S-002 Concrete Repair Notes #3A - added allowance for lineal feet of crack repair at slab on grade

Sherman S-101 Added note regarding fireproofing of FRP below slab

Sherman S-102

1. Added note regarding fireproofing of FRP below slab

2. Revised note to remove FRP on top of slab (E.F.)

Sherman S-103

1. Added note regarding fireproofing of FRP below slab

2. Revised note to remove FRP on top of slab (E.F.)

Sherman S-104

1. Added note regarding fireproofing of FRP below slab

2. Revised note to remove FRP on top of slab (E.F.)

Sherman S-105

1. Added note regarding fireproofing of FRP below slab

2. Revised note to remove FRP on top of slab (E.F.)

Sherman S-106

1. Added note regarding fireproofing of FRP below slab

2. Revised note to remove FRP on top of slab (E.F.)

II. NEW DRAWINGS

NONE

III. REISSUED DRAWINGS

ARCHITECTURAL

Lee A-600 Detail A1, F8, wall typ M4G and T2 has been revised

Lee A-612 Detail F1, Door type 5 was added

Lee A-613 Detail E8, Header detail call out was changed

Lee A-620 Exterior Window Schedule Window Type E quantity was changed

Sherman A-107 Parapet Guard rail has been added to plan

Sherman A-511 Details D1, A1 has been revised

Sherman A-600 Detail E8, A1, Wall type T2 was revised

Sherman A-610 Door Schedule - Exterior; EX 01-03 remarks have been revised

Sherman A-620 Window Schedule - Type A quantity has been revised

II. NEW DRAWINGS

INTERIORS

NONE

II. NEW DRAWINGS

NONE

III. REISSUED DRAWINGS

NONE

LIFE SAFETY / FIRE PROTECTION / FIRE ALARM

Lee FA001

Added note for antenna demolition.

Lee FA100S Added exterior FA/MNS strobes.

Lee FA100B Added exterior FA/MNS strobes.

Lee FA101 Added exterior FA/MNS strobes.

Lee F-701 Modified detail 2 to clarify RFI comment Sherman

Lee FA001 Parapet Guard rail has been added to plan

PLUMBING

NONE

II. NEW DRAWINGS

NONE

MECHANICAL

NONE

II. NEW DRAWINGS

NONE

ELECTRICAL

Lee E-401 Changed Fire Pump Switch from 400A to 200A Lee E-430 Modified Keyed Note #3 to include information related to splicing conductors.

TELECOMMUNICATIONS

Lee T-001 Revised description on Clock Symbol in response to RFI 9396080

Lee T-102 Removed floor boxes in Room L205 in response to RFI 9394190

Lee T-103 Removed floor boxes in Room L305a in response to RFI 9394190

Lee T-502 Revised detail A1 in response to RFI 9394199

Lee T-600 Revised routing of 144 SMF to CEAC in response to RFI 9398400

Lee T-604 Added General Note 1 to clarify Nurse call system in response to RFI 9394228

Lee TY601 Revised general note 4 in response to RFI 9404446

Sherman T-001 Revised description on Clock Symbol in response to RFI 9396080

Sherman TY502 Revised not on detail E4 in response to RFI 9404449

Sherman T-400 Added General Note 1 to clarify in response to RFI 9404439

Lee TS100 New Site Drawing in response to RFI 9398400

Sherman TS100 New Site Drawing in response to RFI 9398400

Sherman T600

SPECIFICATIONS

I. SPECIFICATION CHANGES

Section 00 00 01, # 5 states:” FAR Clause 52.222-21 location is in section 00 45 00 of the contract.”

Revise to “FAR Clause 52.222-21 location is in section 00 72 00 of the contract.”

01 78 00, paragraph 1.9.4. ADD the following:

Subtitle: Controls

“The BMS & controls contractor is required to be in good standing and maintain all applicable West Point network access credentials, training, and applicable criteria throughout the entire project warranty period.

Contractor to verify with Contracting Officer that all applicable information is up to date and the subcontractor is aware of this requirement prior to the warranty period commencing.

07 81 00 – SPRAY-APPLIED FIREPROOFING

Paragraph 2.1

Added language regarding the location of spray-applied fireproofing

08 11 16 – ALUMINUM DOORS AND FRAMES

Paragraph 1.5.1

Deleted requirement for blast engineer.

23 05 15 – COMMON PIPING FOR HVAC

Paragraph 3.13, subparagraph L. Revise to read

Drain and inspect the existing chilled water piping. Remove all scaling and flush the existing piping.

Provide a temporary bypass at each end of the existing piping. One end is within an existing chiller plant and will require existing piping and insulation to be removed for the bypass and reinstalled and reinsulated once the flushing is complete. Location to be determined by contracting officer within the chiller plant.

Victaulic fittings are required. Once bypasses are installed, flush the existing piping to remove all scale.

Flushing is complete when the conductivity is within 20% of the makeup water conductivity within the existing chiller plant and total iron is less than or equal to 3 PPM. Then add inhibitor to coat the inner walls of the piping. Once the flushing is complete circulate the chemically treated water from the plant for a period as determined by the chemical treatment provider prior to supplying the plant water to the new building system. Piping cannot be without water for no more than 4 hours at any given time once flushing is complete. Contractor to coordinate with on base water treatment provider for any testing and chemical treatment necessary. Provide chemical inhibitor as necessary and as determined by the chemical treatment contractor. All water used in conjunction with flushing is to be trucked out by the contractor and disposed of offsite. Sanitary and storm drains are not allowed to be used for disposal purposes of this water. Provided metrics for flushing completion and requirements for disposal of flush water.

26 56 10 – HISTORIC EXTERIOR LIGHTING RESTORATION

Paragraph 1.1.1

Revised number of historic fixtures to be restored

33 63 13 – EXTERIOR UNDERGROUND STEAM DISTRIBUTION SYSTEM

Paragraph Revision

1.2.1 added the following sentence to the pre-engineered system description, “Ensure there is adequate space allocated for welding of the piping joints.”

1.2.12 removed thermal performance testing section. This procedure that was included in the unedited UFC section does not serve any purpose.

1.4.2 Clarified what the high pressure steam and low pressure steam operating characteristics are.

1.4.3 Clarified what the high pressure steam and low pressure steam operating characteristics are.

1.4.4 indicated that the field installation instructions should be submitted to the USACE.

1.7 Revised site classification

2.1.6 indicated that the vents should be extended through the adjacent gravity wall and not the top of the vault. Indicated that the piping shall be schedule 80.

2.1.9 Added the sentence, “There shall be no off-gassing of any materials that would result in toxic air in the vault”.

2.4.1 indicated that all steam piping shall be schedule 80 steel.

II. NEW SPECIFICATIONS SECTIONS

NONE.

III. REISSUED SPECIFICATION SECTIONS

IV. DELETED SPECIFICATION SECTIONS

BIDDER’S QUESTIONS AND GOVERNMENT REPLY

(Questions that may be of general interest to all Bidders and/or the Government and that are not readily answered by the proceeding changes will appear below. These questions may have been paraphrased or altered to represent several questions regarding the same subject and/or simply revised to clarify and simplify the question(s).

Questions and answers are issued to the bidders “For Information Only” and do not revise the solicitation, plans or specifications.)

1. Q. Door Hardware Spec Section 087100; please provide specific model numbers for door hardware.

A. The finish hardware sets are detailed in Government / ANSI Numbers per bidding requirements. The finish hardware bidders are to convert ANSI numbers to any manufacturers model number just so finish hardware supplied meets project standards. Manufacturers that meet the standard in the finish hardware specification will be reviewed for Approval.

2. Q. Interior Windows: Please clarify which interior windows are required to be fire rated. For example: Window type H is shown on Floor Plan sheet A100BA in partition type " -/G4A" which according to the partition schedule on sheet A-601 is a non-rated partition, however door #LC012.1 is also located along this same partition and calls for a 20-minute rating.

A. The window, wall and door are not rated.

3. Q. Interior Windows on Sheet A-620: Notes on sheet A-620 require exterior windows to be aluminum. There is no indication provided as to whether the interior windows are aluminum, hollow metal or wood; please clarify frame types for interior windows.

A. Cadet level interior windows "Type F" at CMU block walls are HM (all are smoke rated 1/2hr corridor walls). At CHC levels on basement and sub-basement All other types of interior windows/sliding-windows are aluminum.

4. Q. Exterior window schedule on sheet Lee A-620 shows a quantity of '29' for window type E;

however North elevation sheet A-201 shows 6 required; South elevation sheet A-202 shows 6 required;

East elevation A-203 shows 28 required for a total of 40 required; please clarify if we should follow the exterior window schedule or exterior elevations for type 'E' window quantities A. The total window type 'E' count is 28, only located on the east façade as shown in the building elevation. Please disregard the Type 'E' window counts. Revised drawing attached.

5. Q. Door schedule on sheet Lee A-610 calls for doors #LBN001.1, LB002, LS09, EX01 to be type '05' doors; However, door types on sheet Lee A-612 does not show a door type 05. Please clarify door type for aluminum doors.

A. Type 5 are all-aluminum doors, Full glass, Medium stile.

6. Q. Specification 08116 aluminum Doors & Frames Section 2.3.2.1 Calls for doors to be "narrow stile" however specification 084113 Aluminum Framed Entrances and Storefronts section 2.1-A calls for medium stile doors and elevation A7/A-612 appears to show wide stile doors. Please clarify door stiles for aluminum doors.

A. All aluminum doors are Medium stile.

7. Q. Specification 084113 section 1.1 item C. "Interior Frameless Glass Wall System" & D. "Glass Smoke Baffles". We are not able to locate any frameless glass wall systems or glass smoke baffles;

please clarify if these items are required on this project and provide locations if required.

A. Sheet A-100BA calls out the GWS-1 (Interior Frameless Glass Wall System) walls. There are smoke baffles at the top and bottom of Stair 4 – see A453.

8. Q. Specification 088100 Glazing:

1). Section 2.1.4 Calls for "Decorative Patterned Laminated Glass - XW11" We unable to locate where this glazing type is required. Please clarify if this glazing type is required and provide locations.

2). Section 2.1.6.1 Ceramic-Opacified Spandrel Glass. We are unable to locate where this glazing type is required, please clarify if spandrel glass is required and provide locations.

A. 1). This glazing type is for the Frameless Glass Wall Systems – see specification section 08 41 13. This is also listed in the Finish Schedule on sheet I-003 and noted on the finish plan I-100BA.

2). Spandrel IGU's are indicated for window type D1 in Lee, and D1 in Sherman.

9. Q. Window schedule on sheet A-620 shows a quantity of 195 for window type A. Both the floor plans and exterior elevations show 160 type A windows is required. Please clarify if we should follow the window schedule quantities or quantities shown on floor plans & exterior elevations.

A. (Lee) There are 28 Type 'A' windows on the west façade, A-204, and 76 on the east façade, A-203, for a total of 104 Type A windows. This matches to the window schedule. (Sherman) There are 16 Type 'A' windows on the north façade, A-201, 12 on the south façade, A-202, 60 on the east façade, A- 203, and 72 on the west façade, A-204, for a total of 160 Type A windows. Please disregard the Type 'A' window counts on the Sherman window schedule. See the attached revised drawings.

10. Q. Window schedule shown on sheets A-620 for both Lee & Sherman Barracks shows a glazing type to be " 1/4" tempered"; as these windows must meet anti-terrorism requirements, the glass would need to be laminated in lieu of tempered. Also, as these are exterior windows shouldn't the glass be 1" insulated glazing in lieu of 1/4"?

A. Exterior windows are 1" Insulated Glazing Units, with a laminated and tempered component for ATFP. (on sheet General Window & Window Glazing Notes, Note #6) See Glazing Spec 08 81 00 Part 2 2.1.1 & 2.1.2

11. Q. Sheet Lee T-102 depicts a floor outlet location in collaboration room L205 with no lettering.

Sheet T-502 detail A1 has details for floor feed locations with "AV CHC" and "M CHC/NC" letters. Please advise on what type of floor locations are depicted on Sheet Lee T-102, and what type of cabling is needed if any.

A. Data floor outlets in L205 and L305a are not required under tables. These are deleted. See the attached drawing.

12. Q. Detail A1 on sheet T-502 for the Lee set show an AV floor outlet with 6x 4-pair category female jacks. A note labels the top 2x as green cables (assumed to be voice) and the bottom jacks as Gray (assumed to be CHC cables). Please advise on the middle 2x jacks coloring and cable type.

A. Provide 2x voice (green) cables and jacks and 4x data (gray cables and jacks). Revised, see the attached drawing.

13. Q. Please provide light fixture schedule for Swing Space Building.

A. Lighting fixtures to be selected, supplied, and installed by the trailer manufacturer. Keyed Note 1 and 3 on E-450 states that the trailer manufacturer provides 2x2 LED light fixtures and Emergency lighting for exterior fixtures.

14. Q. H3 fixtures shown on Sherman E300 detail drawing. Please provide location of these fixtures on a floor pan for circuiting.

A. "H3" Lighting fixtures located on exterior building on south exterior wall. Circuiting is shown on detail C7/E-300. See sheet A-202 south elevation for exact location.

15. Q. The spec for the restoration of historical fixtures indicates that there are 16 historical fixtures to be refurbished. We have only been able to locate only 3 on the provided drawings.

A. Please follow drawing E-010. There are 3 fixtures to be refurbished and 1 to be relocated, total of 4 shown on E-010. This correction will be issued via amendment.

16. Q. Spec section 27 52 24 Nurse Call System indicates there will be a Nurse call System in the Cadet Clinic. The drawings do not give any information about type, location, or wiring details. Are we responsible for providing the complete system including all Equipment, Wiring, Terminations, Testing etc.

or just the infrastructure [i.e. conduit/ back boxes etc.]? If the GC is required for a fully functioning system, please provide specification section.

A. Contractor shall provide a fully functional Nurse Call System as per specification section 27 52 24 and drawings that will include but not limited to hardware, cabling, testing, conduit and backboxes.

17. Q. The panel schedules show two panels labeled as MP2. There are no panels indicated with this designation. Please provide information for the missing panels.

A. MP2 Panel schedule is shown only on E-805. For location of MP2, see one-line on E-610 and floor plan on E-403.

18. Q. Is the GC required to furnish and install the Clocks and PA Systems in their entirety including all equipment, wiring, devices, terminations etc.? If so, please provide a specification for the clocks and PA systems.

A. Per general notes 3 and 4 on T-603, contractor shall provide a fully functional systems include but not limited to hardware, cabling, testing, conduit and backboxes for the Master clock and paging systems.

19. Q. Bradley barracks utilized lock hardware the included a door position switch into the lock hardware thus reducing the cost of the project by not requiring additional cabling, conduit, man hours, and materials to complete the same task as integrating it into the lock hardware. please see the attached door typical from Bradley and referenced sheet ty501 on both lee and Sherman. please note again that revising this will reduce overall cost of projects time and material required to complete.

A. The contractor requested change will only provide a latch position reading but not a door position reading. This was not the intent of the design.

20. Q. Drawing Lee S-102, Lee S-105, SHERM S-102, SHERM S-105 – The orientation of Example A is shown running only along the N-S side (i.e. 13' long span) of both the barracks. Please clarify if this type of repair will only be in the N-S side direction or can it also be in the E-W side direction.

A. Example A indicates a possible reinforcing scenario if there are cracks between the columns.

The size, quantity, and orientation will be as directed in the field. DO NOT USE THE EXAMPLES AS A TAKEOFF. Please refer to S-002 and the price schedule for allowances for each type of repair.

21. Q. The rebar equivalency for the FRP around the new slab openings on Drawings SHERM S-102 to SHERM S-106 is shown as 2#6 E.W, E.F. Please clarify if E.F. (each face) means the top and bottom sides of the slab or if it means each face of the new slab opening (i.e. each slab opening will have four faces). This clarification will help us design the FRP system accordingly.

A. EF means EACH FACE (top and bottom). The dashed line indicates bottom of slab only.

22. Q. Can you please provide a schematic of the actual rebar lay out at all Structural Keynote 2 – Install Fiber Reinforced Polymer for Slab Strengthening locations at both the barracks?

A. Drawings indicate quantity and dimensions.

23. Q. Drawing LEE S-002 & SHERM S-002 – Under the Concrete Repair Notes Section – No. 3 – Repair of Cracks at Slab on Grade – Drawings LEE S-100S & SHERM S-100B state to repair all cracks in the slab on grade. However, quantity is not provided for this repair type. The only crack repair quantity provided is for the supported structural slabs in both the barracks. Can you please provide a quantity for the crack repairs at slab on grade level?

A. See CLIN 009 for repair quantities.

24. Q. Drawing LEE S-106 & SHERM S-106 – All the FRP (Keynote 2) locations shown on these drawings state that the FRP system shall be installed on the bottom of the slab only. Please confirm that FRP will not be required on the topside of the slab which is also the exposed roof level of the barracks.

A. Please refer to the hatch key on each sheet for FRP location. Dashed outline indicates bottom.

There are a few locations that indicated E.F. There is no FRP required at both faces of slab. The hatch key will govern.

25. Q. Will intumescent topcoat or UL rated fireproofing be required for the FRP? If UL rated fireproofing is required, then please specify the hourly rating, and also note that this will affect the overall finish elevation of the slab, beams and columns as the UL fireproofing is much thicker than intumescent coating.

A. Please see the attached drawing for the locations requiring spray fireproofing of FRP-- these locations are confined to the underside of the slab as shown. Specification 07 81 00 attached is revised attached clarifying these locations. FRP used for crack repair only does not require fireproofing.

26. Q. Please confirm that prebagged specialty self-consolidating concrete repair mortar would be acceptable to use in lieu of the ready mix self-consolidated concrete at new shear capital locations.

A. No. Not acceptable.

27. Q. Please confirm that prebagged specialty concrete repair mortar would be acceptable to use in lieu of the ready-mix concrete at concrete spall repair locations.

A. Yes. Acceptable.

28. Q. Drawing LEE S-002 – Under the Concrete Repair Notes Section – No. 5 – New Shear Capitals – Note 5(b) states to include 4 shear capitals per floor as a base quantity of individual column capitals in the bid. However, Drawing LEE S-106 shows additional shear capitals to be constructed below the main roof level – Structural Keynote 14. Please confirm that these shear capitals on the main roof level are over and above the 4 shear capitals per floor that we need to carry in the bid.

A. THE BASE BIDS SHOULD INCLUDE ALL SHEAR CAPITALS NOTED ON THE STRUCTURAL

DRAWINGS AND ALL ALLOWANCES NOTED IN THE NOTES ON S-002. CAPITALS NOTED ON THE ROOF (AND ALL OTHER FLOORS) ARE REQUIRED. THE ALLOWANCES ON S-002 ARE ADDITIONAL IN CASE

CRACKS ARE DISCOVERED IN THE FIELD.

29. Q. Detail C2 on Drawings LEE S-502 & SHERM S-502 – Lightweight Concrete Infill - Please clarify for which repair item is this detail applicable. In addition, please provide a quantity for this repair as well as the type of surface preparation required in terms of CSP profile.

A. LW concrete is listed as an option at areas of crack repairs at depths larger than 1 1/2". Please use allowances noted on S-002 and the price schedule.

30. Q. Drawing LEE S-002, & SHERM S-002 - FRP NOTES - Note 2.C Item (c), states that "THERE ARE THREE PRIMARY TYPES OF FLEXURAL REINFORCEMENT LIKELY TO TAKE PLACE - NEGATIVE UNI-

DIRECTIONAL REINFORCEMENT UNDER NON-LOAD BEARING CMU DEVISING WALLS, SHOWN AS

EXAMPLE A IN PLANS, NEGATIVE BI-DIRECTIONAL REINFORCEMENT AROUND INTERIOR COLUMNS SHOWN AS EXAMPLE B AND POSITIVE REINFORCEMENT ON THE UNDERSLAB ON SLABS AND BEAMS."

Please provide a breakdown on the quantities for the 3 types of flexural reinforcement likely to take place

– SF of negative uni-directional reinforcement shown as Example A, SF of negative bi-directional reinforcement around interior columns shown as Example B and SF of positive reinforcement on the underside of slab and beams. There is a significant price difference between all the 3 repair types and between uni-directional and bi-directional FRP which can affect the overall bid pricing significantly given the bid quantity of 8,000 sf at Lee Barracks and 10,000 sf at Sherman Barracks. In addition, determination of approximate quantities during the pre-bid walk through is not possible as the existing finishes are not removed yet.

A. Yes you are correct. It is impossible to determine exact takeoffs of FRP required until all architectural finishes are removed, and a comprehensive survey has taken place. Quantities listed on S- 002 are best estimates based on field observation and past experience in similar barracks renovations of similar construction types. Beam reinforcement is less likely. Example A - UNI-DIR mid-span reinforcement will likely occur in similar quantities as Example B- punching shear reinforcement.

31. Q. Can you please provide an approximate quantity breakdown for the spalled concrete surfaces in terms of how much repairs are on topside of the slab vs underside of the slab vs column concrete repairs vs wall concrete repairs vs beam concrete repairs? There is a significant price difference between repairs at all the above listed locations which can affect the overall bid pricing significantly given the bid quantity of 1,300 sq. feet at Lee Barracks and 1,750 sq. feet at Sherman Barracks. In addition, determination of approximate quantities during the pre-bid walk through is not possible as the existing finishes are not removed yet.

A. Bid as per S-002 and the price schedule.

32. Q. Please confirm if the any of the bays in both the barracks have depressed structural slab areas. Based on our experience working at Bradley and Eisenhower barracks, the center bay was depressed and additional surface preparation and FRP transitioning details were required to install the FRP system.

A. All know slab depressions are indicated on structural plans.

33. Q. Lee Barracks – Drawings S-100B to S-106 shows all the locations for the FRP system (Keynote

2) at the new concrete slab opening locations. With regards to the bi-directional FRP, only on Dwgs S- 100B & S-105 it shows installation on the top and bottom of the slab, the rest of the levels the installation is only on the underside of the slab. Please confirm that this is correct and the FRP system should be designed accordingly.

A. The EACH FACE (E.F.) note was inadvertent, and was only located at a few new penetrations, not at cracks. The dashed line indicates bottom of slab only. Revised drawings are attached.

34. Q. Sherman Barracks – Drawings S-101 to S-106 shows all the locations for the FRP system (Keynote 2) at the new concrete slab opening locations. With regards to the bi-directional FRP, only on Dwgs S-102 & S-105 it shows installation on the top and bottom of the slab, the rest of the levels the installation is only on the underside of the slab. Please confirm that this is correct and the FRP system should be designed accordingly.

A. The EACH FACE (E.F.) note was inadvertent, and was only located at a few new penetrations, not at cracks. The dashed line indicates bottom of slab only. Revised drawings are attached.

35. Q. Please confirm that the David Bacon wages provided in Amendment 3 are locked for the duration of the project or do we need to factor in wage rate escalations (which may be issued through new modification numbers after the bid due date) in our bid.

A. Wage rates are locked in at the time of bid opening if award is made within 90 days.

36. Q. Will the use of new elevators be allowed once installed (given that they will be protected)?

A. Installed systems are not to be used by the GC due to warranty matters.

37. Q. Column Line x3, detail A6/A-530 does not exist. Detail A7/A-530 seems to be the correct designation, please confirm? This detail illustrates the restoration of the exterior façade pier. There looks to be (12) twelve each of these piers on the East Elevation [A-203]. The detail is only flagged on Column Line x3. Is the intent to restore only this x1 Pier, or is the detail a typical for all of the piers to be restored?

A. Yes, the callout on Lee A-203 for detail A6/A-530 should be for detail A7/A-530. It is a general detail for any pier indicated for reconstruction / restoration on the demo elevations (applicable for both buildings). This pier indicated specifically has a completely failed cap stone to be fully replaced.

38. Q. Lee Barracks drawings AD201- AD204 provide repair quantities per elevation. Limestone restoration calls out for 270sf per elevation for a total of 1,080 sf. CLIN0004AA calls out for 846 sf. What is the intent of CLIN 0004AA? Is the 846 sf {per AD201- AD204} to be figured in addition to the 1,080 sf {to be part of CLIN0001}?

A. CLIN 0001 shall include the known repair quantities as shown on the elevations on the AD200 series drawings. CLIN 0004 represents estimated quantities for additional repairs above and beyond CLIN 0001 and is reflected in the AD200 series drawings on the Repair Quantities table and price schedule.

39. Q. Lee Barracks drawings AD201- AD204 provide repair quantities per elevation. Granite Veneer Repointing calls out for 540lf north elevation,540lf south elevation, 890lf east elevation and 890lf west elevation for a total of 2,860lf. Should this be reflected as a sf? CLIN0004AB calls out for 29,541 sf. What is the intent of CLIN 0004AB? Is the 29,541 sf {per AD201- AD204} to be figured in addition to the 2,860lf {to be part of CLIN0001}?

A. CLIN 0001 shall include the known repair quantities as shown on the elevations on the AD200 series drawings. CLIN 0004 represents estimated quantities for additional repairs above and beyond CLIN 0001 and is reflected in the AD200 series drawings on the Repair Quantities table and price schedule. Also, price schedule revised to change SF to LF for Granite Veneer repointing.

40. Q. For both Lee and Sherman, T-001 denotes clocks with an "A" as analog and clock with a "D" as digital. However, all clocks on the floor plan are not labeled with either. Please advise if this will be a digital clock system, or analog.

A. For both Lee and Sherman, T-001 denotes clocks with an "A" as analog and clock with a "D" as digital. However, all clocks on the floor plan are not labeled with either. Please advise if this will be a digital clock system, or analog. Drawing T-001 attached is revised.

41. Q. For both the Lee and Sherman drawings, some clocks have a sub script "2" next to them (See Corridor SB00a on sheet SHERM T-100B for an example). Please confirm this means these clocks are double-faced.

A. Clocks with no subscript are single face clocks and clocks with subscript '2' are double face clocks.

42. Q. What is the existing BMS system currently in Lee and Sherman Barracks?

A. The BAS in both barracks is to be removed entirely. A new LonWorks Direct Digital Control (DDC) BAS will be provided for monitoring and control of building HVAC systems. The BAS will be a Niagara Framework system using LonWorks controllers. The BAS network will communicate all integrated and hardwired points to the existing Niagara N4 UMCS network serving the campus.

43. Q. Detail D3/A511 shows a parapet rail. However, the roof plan on sheet A107 does not indicate any rail. Which is correct, should a rail be provided?

A. Railing should be showing on the roof plan and was accidentally omitted. Drawing A107 revised is attached.

44. Q. Is the ladder and sump pump pit grating shown in elevator shaft existing or shall new be provided?

A. The ladder shown in the elevator shaft of Sherman Barracks is new work. The sump pump pit grating shown in the elevator shaft of Sherman Barracks is existing to be replaced. The ladder shown in the elevator shaft of Lee Barracks (Elevator 01) is new work. The sump pump pit grating shown in the elevator shaft of Lee Barracks (Elevator 01) is existing to be replaced. The ladder and sump pump pit grating shown in the elevator shaft of Lee Barracks (Elevator 02) are both new as that install is all new work.

45. Q. Please confirm T-2, as indicated on Enlarged Stair (such as on A450 Sherman Building), is actually 2" polished block as depicted on A1/A412, and 2" glazed cmu is a 2 course band at each level.

Yes, finish plans indicate both block types and the banding pattern, the wall is both polished and glazed CMU types indicated on finish drawings.

46. Q. In spec section 01 45 00.00 10 part 3.4.3 CQC Personnel, it is mentioned that there are additional personnel required to assist the CQC System Manager. 6 additional people, each with a different specialty, are being added to the mandatory staff that is already listed in spec section 01 30 00 Administrative Requirements. They are also to be hired by the prime Contractor directly and not through a supplier or a subcontractor. Please advise if the 6 additional personnel are to be full time on site during the construction process. If not, please advise.

A. The personnel identified in 01 45 00.00 10 paragraph 3.4.3 are to assist and support the CQC System manager. They shall be physically present at the construction site during work on the specialized personnel’s areas of responsibility. These are personnel that can be identified and submitted under another position provided they meet the qualification criteria listed under 01 45 00.00 10 paragraph

3.4.3. All of these positions within the matrix should be included as part of the QC plan and identified as such. Key Management Personnel identified within 01 30 00 paragraph 1.7 are still required as per contract.

47. Q. Granite Veneer Repointing gives a quantity of 29,541 SF, which is the entire elevation.

However, the drawings (AD201 – AD204) indicate to repoint 25% of the Granite. Is the granite to be repointed 25% or 100%?

A. CLIN 0001 shall include the known repair quantities as shown on the elevations on the AD200 series drawings. CLIN 0004 represents estimated quantities for additional repairs above and beyond CLIN 0001 and is reflected in the AD200 series drawings on the Repair Quantities table and price schedule. Also, price schedule revised to change SF to LF for Granite Veneer repointing.

48. Q. For areas indicated to provide a self-leveling topping, shall we provide self-leveling in these areas only? If additional self-leveling topping is required outside the areas shown this will be handled as a change order?

A. In reference to the S drawings identified in the question, topping is required only where shown. Contractor is required to also review architecture drawings for extent of self-leveling topping material as required by finishes and nonstructural components.

49. Q. Is any underground steam, chilled water, hot water piping required to be performed during off hours?

A. Work involving underground steam, chilled water, and hot water piping is not required to be performed off hours. Any off-hours work determined to be required during the course of the contract must be coordinated in advance with the Contract Officer as specified in the project contract documents.

50. Q. Granite Veneer Repointing gives a quantity of 29,541 SF, which is the entire elevation.

However, the drawings (AD201 – AD204) indicate to repoint 25% of the Granite. Is the granite to be repointed 25% or 100%?

A. See response to #47

51. Please qualify whether all underground piping costs fall under Lee Barracks SOW including from Steam Vaults F4 & F8. In other words, if Sherman building is not selected for renovation, does the remaining underground scope continue under Lee building?

A. All steam vault and piping work regardless of where it appears on the drawings should be priced in CLIN 0010. For phasing purposes, part of this work will be done during Sherman construction.

52. Q. Please confirm that the General Contractor is responsible for all Site Utility Water work. Or, will the Site Utility Water work be performed by local utility company.

A. Responsibility for specific elements of site utilities for the GC and the private utility providers are described on Sheet C-002, General Notes 24 and 25.

53. Q. Please advise as to the location(s) required to receive Spray on Fire Proofing. This scope cannot be located on the contract drawings.

A. Section 07 81 00 Spray Applied Fireproofing is only applicable to where Intumescent epoxy coating is required because it is a spray on. There are no metal deck on this job, so the normal reference of Spray Applied Fireproofing does not apply to this project. For the extent of the Spray Applied, specification 07 81 00 section 2.4 currently writes: All new structural steel tube columns installed on the Lee Barracks floors sub-basement, and basement, are to receive intumescent epoxy coating. Revise specification included states: "All foam plastic closed cell insulation exposed to the interior of the building without thermal barrier tested per NFPA 275 must also be coated with spray applied Intumescent epoxy Coating System." Per our plan, A101-A and A-101-B and detail B5&D5/A-540, this condition is occurring in the cavity between the column line xG/X2-X4 & xG/X11-X13; in addition to all new structural steel tube columns.

54. Q. Please refer to the bid form in addendum 5. In the total base bid, it refers to CLINS (0007- 0020) on page 19 of 20. Please advise if this should be CLINS (0001-0020) instead.

A. Revised price schedule is attached.

55. Q. Structural keynote 12 indicates to parge and point exposed stone at existing stone retaining wall. After site investigation it was observed this wall has cracks, bowed and structurally in need of additional repair. Shall any additional repair be required for this retaining wall? If so please provide requirements.

A. The structural wall is not visible. The cracks and bowing observed are the stone veneer, typically at the top of the wall because of vehicle damage at the rail above. This is what is being replaced in section A3/S-304. The top 4-feet of the retaining wall and 42” of balustrade above are being replaced with new concrete.

56. Q. Specifications indicates to provide qualified blast engineer must perform testing or calculations for door system design resistance to specified blast loads. Loads are not provided, please provide required blast loads.

A. Blast loads are not required. Revised specification is attached.

57. Q. Keynote 14 24-02 indicates to replace hydraulic piston caisson. Does the existing caisson hole need to be re-drilled or can existing caisson hole be reused?

A. Caisson is to be replaced in-full.

58. Q. At CMU partitions above door frames (headers) to Cadet rooms be constructed of metal framing and gypsum to allow room for duct work penetrations?

A. Area above cadet room doors in CMU are stud and GWB/plaster infill to accommodate MEP routing. See details F8 & C8 on A-614 for Sherman. On Lee, Drawing A-613 was revised. Detail E8 on A-613 was revised to call out detail C3 on A-613 instead of E6 (which was incorrectly identified as it does not exist on A-613). This revision is attached.

59. Q. Granite veneer pointing is not shown on the West elevation allowance quantities. Should this area be added to the bid form item #004AB?

A. The west façade of Sherman is all brick. See the attached revised price schedule which covers brick repairs. Note CLIN 004AB pertains to Lee Barracks.

60. Q. Façade Restoration Note #3 indicates Brick Façade Coat Stripping: Please identify location of the coating work. Confirm quantity listed in bid form items #003AD & #0012AD are for exterior brick masonry walls only.

A. The west façade of Sherman is all brick. See the attached revised price schedule which covers brick repairs. Coating, permeable AVB finish, is required on all brick restoration. Each area has a specification keynote tag for new masonry. See the price schedule as 3AD and 12AD is for lead removal.

61. Q. Cleaning methodology for the Gneiss Granite is not identified. Please clarify.

A. See SECTION 04 03 00 CONSERVATION TREATMENT FOR PERIOD MASONRY for cleaning requirements. Notes on cleaning and restoration are on the AD exterior elevations.

62. Q. For both Lee and Sherman, we do not have site plans showing all manholes locations and conduit runs that will be used for OSP cabling. Example would be the riser on T-600 showing MH-35C requiring a 144 strand to be run through it. I cannot locate MH-35C on the telecom site plans.

A. Will add site plan to show manhole locations not currently shown. Additional drawing is attached.

63. Q. Some subcontractors are requesting another site visit (group or individual). Is that something that can be granted? Please advise.

A. Another site visit is not currently planned.

64. Q. Door Hardware Spec Section 087100; please provide specific model numbers for door hardware.

A. The finish hardware sets are detailed in Government / ANSI Numbers per bidding requirements. The finish hardware bidders are to convert ANSI numbers to any manufacturers model number just so finish hardware supplied meets project standards. Manufacturers that meet the standard in the finish hardware specification will be reviewed for Approval.

65. Q. Some subcontractors are requesting another site visit (group or individual). Is that something that can be granted? Please advise.

A. Another site visit is not currently planned.

66. Q. Some subcontractors are requesting another site visit (group or individual). Is that something that can be granted? Please advise.

A. Another site visit is not currently planned.

67. Q. Masonry Façade Restoration Notes 1 & 2 indicate that after atmospheric soiling is removed Biological solution is to be applied to the façade to remove remaining biological substance. What percent of the façade surface should the bidders carry for this purpose?

A. Biologic cleaning is typically done in isolated areas, and there does not appear to be a systemic issue with biological growth on the buildings. Carry a 5% allowance to do a biologic treatment after the atmospheric soiling washdown is executed.

68. Q. If there will be no chilled water connection from Sherman to Lee (there is a proposed connection point at Sherman from the main campus CHW line to the West), will there be a temp chiller set up for Lee? If so, what capacity would be required?

A. Temporary chiller connections are required to be installed at Lee Barracks. 01 50 00 paragraph

3.3.1 states that on post produced chilled water is not to be utilized until the project reaches startup and testing. The government will provide a temporary chiller for startup and testing purposes if there is no chilled water connection from Sherman Barracks to Lee Barracks.

69. Q. Sherman drawing T-400 detail A1 Shows 30 cabinets labeled as spare, T-Mobile, Headend Platform, ATT and VZN. There is no detail on what these cabinets include, or their size. Are these provided Contractor Furnished and Installed? If we are to provide, please provide rack dimensions and internal equipment details.

A. Cabinets C2-1 thru C2-6 (VZN), C3-1 thru C3-6 (ATT), C5-1thru C5-6 (T-Mobile) and C6-1 thru C6-6 (Spare) are vendor furnished and installed. Cabinets C4-1 thru C4-6 (Headend Platform) are Contractor Furnished and Installed per keynote 1 on T-200. A note was added to T-400 and reissued.

70. Q. Drawing TY601 on Lee Building says Cameras are CFCI, while drawing TY601 on Sherman Building says Cameras are GFGI. Please advise which to follow for entire Project [ base and option] A. Lee and Sherman Cameras are Government Furnished and Installed (GFGI). Lee TY601, note 4 is revised on the attached drawing..

71. Q. Detail E4 on Drawing TY502 on Sherman Building says to provide 1" conduit to nearest accessible ceiling for camera wiring, while Drawing TY502 on Lee Building says provide 1" conduit all the way back to the nearest security wireway. Please advise if all cameras need to be piped, or will LV Wiring in J-Hooks be acceptable.

A. J hooks are not permitted per the UFC.

72. Q. Details Drawings TY503 on Lee and TY501 on Sherman show Access Control conduits from each door going back to the Telcom room. Is this necessary or will J-Hooks be acceptable for low voltage Access Control cabling? The sheer amount of conduits per floor most likely would not fit if each door had to be hard piped back to each Telcom room.

A. J hooks are not permitted per UFC.

73. Q. CLIN- 0002 - Work associated with Cadet Health Clinic. Please advise as to the specific work scope items that need to be included within this scope price item.

A. Refer to drawings G-100S, G-100B, and G-101 in the Lee drawings Vol 1 for the delineation of the CHC and schedules identifying the equipment specific to the CHC and relevant to CLIN 002.

73. Q. Regarding the underground steam distribution piping, spec section 33 63 13, 1.4.2, Under Operating Characteristics, states the steam and condensate return shall be designed for 380 deg F and 160 PSIG. Please confirm what is the system design temp and pressure for the low pressure condensate and low pressure steam.

A. The low-pressure steam and condensate system shall have an operating temperature of 250 degrees F and an operating pressure of 15 psig. Spec section 33 63 13 attached is revised documenting this data.

74. Q. Sherman A-610 indicates "restore existing wood door, see A-614" however sheet A-614 are header, frame and partition details for existing doors. Not how or to what extent to restore. Similar issue on Lee. Please confirm restoration requirements for this note.

A. Please see A-612 – DOOR TYPES & DETAILS. This is where the exterior restoration requirements are located. Note is revised in the attached revision to the correct sheet.

75. Q. Existing stairways drawings are removing Brick veneer per note 02-003 on demolition drawings. We assume the face bricks are 4" thick. Floor plans call for 2" structural glazed tile installed where 4" face brick removed. Can a detail be provided and will a required 2" backup system be required to fulfill this extra 2" space?

A. Drawing are revised and attached. Revisions to be included: 2" Glazed CMU (T-2 as shown on F8/A-600) will be mortared to the existing walls as tagged and dimensioned on stair plans.

4" Glazed CMU (M4G as show on A1/A-600) will be located as tagged and dimensioned on stair plans.

76. Q. Structural drawing S-001 call for vertical rebar #5 at 32" OC Architectural drawing A-600 call for vertical rebar #5 at 48" OC Which is correct? Please confirm rebar spacing in CMU walls.

A. Structural drawings are to be used as the reference for vertical rebar placement: vertical rebar #5 at 32" OC.

78. Q. Structural drawing S-001 call for vertical rebar #5 at 32" OC Architectural drawing A-600 call for vertical rebar #5 at 48" OC Which is correct? Please confirm rebar spacing in CMU walls.

A. Structural drawings are to be used as the reference for vertical rebar placement: vertical rebar #5 at 32" OC.

79. Q. Are allowances, that are in the repair quantity table on AD201 thru AD204, to be part of the CLIN 4 on Lee building and CLIN 13 on Sherman Building? Quantities and units do not match Amendment 5 bid schedule. Please advise.

A. See attached revised price schedule which clarifies the work.

80. Q. Section 00 00 01 Invitation for Bid #5 specifically point out Section 00 45 00 Representations and Certifications and particularly Prohibition Segregated Facilities.

This is the start of the file's text. The full file is on GovTribe.