This document provides details for a federal solicitation seeking repair services for two barracks buildings at the United States Military Academy at West Point. The U.S. Army Corps of Engineers intends to issue a solicitation for a firm-fixed price contract to repair Building 740 at Lee Barracks and Building 738 at Sherman Barracks, with an optional scope to fully renovate Sherman Barracks. Building 740 repairs include interior renovations, mechanical/electrical/plumbing system replacements, and site work. The optional scope for Building 738 includes full renovation. The period of performance is approximately 1034 calendar days from notice to proceed. The estimated value is between $100-200 million. The NAICS code is 236220 and proposals are due approximately 30 days after the anticipated August 6th posting date on sam.gov. Contractors must register in SAM to receive solicitation amendments or be eligible for award.
View the file
Other files
Show all 45
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
EXHIBIT B-1
Preliminary Geotechnical Engineering Report
Lee Barracks Upgrade, Exterior Field Investigations US Military Academy, West Point, New York
September 12, 2018 Terracon Project No. JD185040
Prepared for:
JACOBS
299 Madison Avenue Morristown, NJ 07960
Prepared by:
Terracon Consultants-GeoConcepts Engineering, Inc.
Ashburn, Virginia
19955 Highland Vista Dr., Suite 170 Ashburn, Virginia 20147
(703) 726-8030 www.geoconcepts-eng.com
September 12, 2018
Mr. Gary Calligaro, RA
JACOBS
299 Madison Avenue Morristown, NJ 07960
Subject: Preliminary Geotechnical Engineering Report Lee Barracks Upgrade, Exterior Field Investigations US Military Academy, West Point, New York (Our JD185040)
Dear Mr. Calligaro:
GeoConcepts Engineering, Inc. (GeoConcepts) is pleased to present the following preliminary geotechnical engineering report prepared for Lee Barracks Upgrade, Exterior Field Investigations, US Military Academy, West Point, New York.
We appreciate the opportunity to serve as your geotechnical consultant on this project. Please do not hesitate to contact me if you have any questions or want to meet to discuss the findings and recommendations contained in the report.
Sincerely, GEOCONCEPTS ENGINEERING, INC.
Rebecca L. Smith-Zakowicz, PG Senior Associate rsmith@geoconcepts-eng.com
TABLE OF CONTENTS
Page No.
1.0 SCOPE OF SERVICES
2.0 SITE DESCRIPTION AND PROPOSED CONSTRUCTION
3.0 SUBSURFACE CONDITIONS
3.1 GEOLOGY
3.2 STRATIFICATION
3.3 GROUNDWATER
3.4 SOIL LABORATORY TEST RESULTS
3.5 SEISMIC SITE CLASSIFICATION
3.6 METAL CORROSION/CONCRETE ATTACK TEST RESULTS
3.7 ROCK UNCONFINED COMPRESSIVE STRENGTH TEST RESULTS
4.0 PRELIMINARY ENGINEERING ANALYSIS
4.1 PAVEMENTS
4.2 EARTHWORK
5.0 GENERAL LIMITATIONS
APPENDIX A SUBSURFACE INVESTIGATION
APPENDIX B SOIL LABORATORY TEST RESULTS
Preliminary Geotechnical Engineering Report Lee Barracks Upgrade, Exterior Field Investigations ■ US Military Academy September 12, 2018 ■ Terracon Project No. JD185040
September 12, 2018 JD185040 Page 1
1.0 SCOPE OF SERVICES
This preliminary geotechnical engineering report presents the results of the field investigation, soil laboratory testing, and engineering analysis of the geotechnical data. This report specifically addresses the following:
n An evaluation of subsurface conditions within the area of the proposed site development, including seismic site classification parameters per the 2015 International Building Code.
n An assessment of subgrade conditions for support of flexible and rigid pavements based on the field investigation and soil laboratory test results.
n Earthwork recommendations for construction of loadbearing fills, including an assessment of on-site soils to be excavated for re-use as fill.
Services not specifically identified in the contract for this project are not included in the scope of services.
2.0 SITE DESCRIPTION AND PROPOSED CONSTRUCTION
The site is located at the existing Lee Barracks at the United States Military Academy (USMA) in West Point, New York. Specifically, Lee Barracks is located on the east side of campus, southwest of the intersection of Thayer Road and Brewerton Road. Lee Barracks has two basement levels and five above grade levels.
Imagery provided by Google Earth dated April 2016.
Based on the Scope of Work dated January 11, 2018, it is our understanding that the Lee Barracks will be undergoing various renovations including improving surrounding pavements, landscape areas, and utility tie-ins.
September 12, 2018 ■ Terracon Project No. JD185040
September 12, 2018 JD185040 Page 2
3.0 SUBSURFACE CONDITIONS
Subsurface conditions were investigated by drilling a total of two Standard Penetration Test (SPT) borings in the building area. The SPT borings were completed by Uni-Tech Drilling of Franklinville, New Jersey under our observation between July 23 and 25, 2018, utilizing 3-¼ inch inside diameter hollow stem auger with automatic hammer. The sampler was advanced by driving the spoon into undisturbed soil under the impact of a 140-lbf hammer free-falling from 30 inches height per ASTM D1586-11. The borings were staked by GeoConcepts using available site plans in the field. The project civil engineer returned to the site at a later date and performed an “as-drilled” survey of our boring locations. The elevations from this survey are indicated on the logs.
Test boring logs and a boring location plan are presented in Appendix A of this report.
3.1 Geology
The site lies within the Hudson Highlands Physiographic Province of New York. According to local geologic maps, the site is mapped in Grenville and Canada Hill Granite. Based on our subsurface investigation, the sediments and strata correspond favorably to the geologic publications.
Bedrock was cored in test borings B-1 and B-2 for identification and evaluation of the rock. The Rock Quality Designation (RQD) value in the cored rock was measured to be 72 to 73 percent, indicating an overall fair rock quality.
3.2 Stratification
The subsurface materials encountered have been stratified for purposes of our discussions herein. These stratum designations do not imply that the materials encountered are continuous across the site. Stratum designations have been established to characterize similar subsurface conditions based on material gradations and parent geology. The generalized subsurface materials encountered in the test borings completed at the site have been assigned to the following strata:
Stratum A (Existing Fill) generally medium dense or firm, POORLY GRADED SAND
WITH SILT AND GRAVEL, SILTY SAND WITH GRAVEL,
SILTY CLAY WITH SAND, FILL, moist, brown, black
Stratum B (Rock) slightly weathered, very hard, slightly fractured, GRANITE, dark gray, white
The two letter designations included in the strata descriptions presented above and on the test boring logs represent the Unified Soil Classification System (USCS) group symbol and group name for the samples based on laboratory testing per ASTM D2487 and visual classifications per ASTM D2488. It should be noted that visual classifications per ASTM D2488 may not match classifications determined by laboratory testing per ASTM D2487. Rock is classified in accordance with the Engineering Descriptions of Rock provided in Appendix A of this report.
3.3 Groundwater
Groundwater level observations were made in the field during drilling of the test borings.
Groundwater was not encountered during drilling. Due to safety concerns to pedestrians, the boreholes were backfilled upon completion of drilling.
September 12, 2018 ■ Terracon Project No. JD185040
September 12, 2018 JD185040 Page 3
The groundwater observations presented herein and considered to be an indication of the groundwater levels at the dates and times indicated. Accordingly, the groundwater information presented herein should be used with caution. Also, fluctuations in groundwater levels should be expected with seasons of the year, construction activity, changes to surface grades, precipitation, or other similar factors.
3.4 Soil Laboratory Test Results
Selected soil samples obtained from the field investigation were tested for grain size distribution, Atterberg limits, and natural moisture contents. A summary of soil laboratory test results is presented below in Table 3.4-1, and the results of natural moisture content tests are presented on the test boring logs in Appendix A.
Table 3.4-1: Summary of Soil Laboratory Test Results
Test Boring
No.
Depth
(ft) Sample
Type Stratum Description of Soil Specimen
Sieve Results
Atterberg Limits Natural
Moisture Content
Percent
Retained #4 Sieve
Percent Passing
#200 Sieve
LL PL PI
B-1 1.0-2.5 Jar A
POORLY GRADED SAND
(SP-SM) WITH SILT AND
GRAVEL
34.2 9.4 NP NP NP 15.2
B-1 4.0-4.4 Jar A
POORLY GRADED SAND
(SP-SM) WITH SILT AND
GRAVEL
38.7 11.8 NP NP NP 3.1
B-1 6.0-8.0 Jar A SILTY SAND (SM) 14.4 24.0 NP NP NP 7.1
B-1 8.0-10.0 Jar A
POORLY GRADED
GRAVEL (GP-GM) WITH
SILT AND SAND
58.6 10.5 NP NP NP 3.5
B-1 10.0-12.0 Jar A SILTY GRAVEL (GM) WITH
SAND 55.5 15.2 NP NP NP 5.5
B-2 2.5-4.0 Jar A
POORLY GRADED
GRAVEL (GP-GM) WITH
SILT AND SAND
61.0 7.5 NP NP NP 8.1
B-2 4.0-6.0 Jar A SILTY SAND (SM) WITH
GRAVEL 36.0 15.2 NP NP NP 9.5
B-2 6.0-8.0 Jar A SILTY CLAY (CL-ML) WITH
SAND 2.6 73.9 22 17 5 19.1
B-2 8.0-10.0 Jar A
POORLY GRADED SAND
(SP-SM) WITH SILT AND
GRAVEL
44.8 10.0 NP NP NP 2.5
Notes:
1. Soil tests are in accordance with applicable ASTM standards
2. Soil classification symbols are in accordance with Unified Soil Classification System
3. Visual identification of samples is in accordance with ASTM D2488
4. Key to abbreviations: LL = liquid limit; PL = plastic limit; PI = plasticity index; NP = nonplastic
3.5 Seismic Site Classification
Based on the results of the subsurface investigation and our knowledge of local geological conditions, the site soils have been assigned to a site class C per the 2015 International Building Code (IBC).
September 12, 2018 ■ Terracon Project No. JD185040
September 12, 2018 JD185040 Page 4
The site coefficients and adjusted Maximum Considered Earthquake (MCE) spectral response acceleration parameters were obtained from the United States Geological Survey (USGS) website for Risk Category I/II/II and are presented below in Tables 3.5-1 and 3.5-2.
Table 3.5-1: Site Coefficients Mapped Spectral Accelerations for Site
Class B and 5% Damping (Step 1) Site Coefficients to Modify Accelerations Based on Site Classification C (Step 2) SS = 0.230 g Fa = 1.2
S1 = 0.069 g FV = 1.7
Table 3.5-2: Maximum Considered Earthquake (MCE) Spectral Response Acceleration
MCE Spectral Response Accelerations (Step 3)
Design Spectral Response Accelerations (Step 4)
SMS = 0.277 g (=SS*Fa) SDS = 0.184 g (=2/3*SMS)
SM1 = 0.117 g (=S1*FV) SD1 = 0.078 g (=2/3*SM1)
3.6 Metal Corrosion/Concrete Attack Test Results
In addition to standard geotechnical soil laboratory testing, one sample was submitted to an analytical laboratory for metal corrosion and concrete attack testing. Corrosion testing consisted of analysis for moisture content (EPA), pH (CA-643), resistivity (ASTM G187), chloride (CA-422), sulfides (EPA 376.2), and reduction-oxidation potential (Electrode). The results of these tests are presented below in Table 3.6-1:
Table 3.6-1: Analytical Laboratory Test Results Test
Boring No.
Sample Depth
(ft)
Moisture Content pH Resistivity
(ohm – cm) Chloride
(ppm) Sulfides (ppm)
Redox Potential
(mV) Point Total
B-1 0-5 13 9 1000 260 <1.2 +296 13
For each test presented in Table 3.6-1, points are assigned based on the range of the test results.
If the total points from the five tests completed for a particular sample are 10 or more, the soil is considered to be corrosive. The methods described herein are based on information from the American Water Works Association (AWWA) for ductile iron pipes. Using the methods described by AWWA, the point total for the sample was 13. Accordingly, the site soils are considered corrosive, and therefore, cathodic protection (i.e. polyethylene encasement) is recommended for ductile iron pipes below grade.
The low resistivity value and chloride test results suggest the soil may also be corrosive to steel.
Therefore, corrosion protection for steel is also recommended.
A sulfate test (EPA 375.4) was performed on a selected soil sample to determine the severity of sulfate attack on concrete structures. The results of sulfate testing are presented below in Table 3.6-2.
September 12, 2018 ■ Terracon Project No. JD185040
September 12, 2018 JD185040 Page 5
Table 3.6-2: Sulfate Test Results
Test Boring No. Sample Depth (ft)
Sulfate Concentration (ppm)
B-1 0-5 97
Based on correlations between sulfate concentrations and severity of sulfate attack as presented in American Concrete Institute (ACI) 318, the above sulfate concentrations are considered to pose a negligible threat of sulfate attack on concrete.
3.7 Rock Unconfined Compressive Strength Test Results
Unconfined compressive strength tests were conducted on core specimens of the granite rock.
The results of the unconfined compressive strength tests are presented below in Table 3.7-1.
Table 3.7-1: Unconfined Compressive Strength Test Results
Test Boring No. Sample Depth (ft) Unconfined Compressive Strength (psi)
B-1 18.0-18.5 9,668
B-2 19.0-19.5 11,896
4.0 PRELIMINARY ENGINEERING ANALYSIS
Preliminary recommendations regarding pavements and earthwork are presented herein.
4.1 Pavements
Pavement subgrades are expected to consist of generally medium dense existing fill or new compacted fill. These materials are generally considered suitable for support of the planned roadways and parking areas. Where pavement subgrades consist of existing fill, we recommend budgeting for undercutting the existing fill to a depth of at least 2 feet and backfilling with new compacted fill. The decision to undercut the existing fill should be based on a thorough proofroll of the pavement subgrades under the observation of the geotechnical engineer. Pavements should be constructed to facilitate positive drainage of water to prevent ponding.
Based on the soil laboratory test results for the materials expected at pavement subgrades, a preliminary design CBR value of 5 is recommended for pavement design purposes. If fill placed at the site is generated from off-site borrow areas, the actual CBR value for the pavement subgrades may be significantly different from the preliminary value presented herein. Therefore, CBR tests should be performed on the in-place subgrade after rough grading and installation of utilities within roadways. Final pavement sections should be based on CBR tests taken on subgrade soils at the time of construction. Concrete pavements should be utilized in loading dock areas and for dumpster pads.
September 12, 2018 ■ Terracon Project No. JD185040
September 12, 2018 JD185040 Page 6
4.2 Earthwork
New fill may be required for the site improvements. Unsuitable existing fill, soft or loose natural soils, organic material, and rubble should be stripped to approved subgrades as determined by the geotechnical engineer.
Fill material should be placed in lifts not exceeding 8 inches loose thickness, with fill materials compacted by hand operated tampers or light compaction equipment placed in maximum 4-inch thick loose lifts. Fill should be compacted at +/- 2% of the optimum moisture content to at least 95 percent of the maximum dry density per ASTM D1557.
Materials used for compacted fill should consist of soils classifying SC, SM, SP, SW, GC, GM, GP, or GW per ASTM D2487. The Stratum A existing fill may not be suitable for re-use as new compacted fill due to deleterious man-made materials in the fill. The existing fill encountered in borings B-1 and B-2 contained boulders and/or construction debris at depths of approximately 4 and 5 feet, respectively. Also, an obstruction was encountered at a depth of about 13 feet in test boring B-2. In addition, drying of excavated soils by spreading and aerating may be necessary to obtain proper compaction. This may not be practical during the wet period of the year. Accordingly, earthwork operations should be planned for early spring through late fall, when drier weather conditions can be expected. Individual borrow areas, both from on-site and off-site sources, should be sampled and tested to verify classification of materials prior to their use as fill.
Fill materials should not be placed on frozen or frost-heaved soils, and/or soils that have been recently subjected to precipitation. All frozen or frost-heaved soils should be removed prior to continuation of fill operations. Borrow fill materials should not contain frozen materials at the time of placement.
Compaction equipment that is compatible with the soil type used for fill should be selected.
Theoretically, any equipment type can be used as long as the required density is achieved;
however, sheepsfoot roller equipment are best suited for fine-grained soils and vibratory smooth drum rollers are best suited for granular soils. Ideally, a smooth drum roller should be used for sealing the surface soils at the end of the day or prior to upcoming rain events. In addition, compaction equipment used adjacent to walls below grade should be selected so as to not impose undesirable surcharge on walls. All areas receiving fill should be graded to facilitate positive drainage of any water associated with precipitation and surface run-off.
After completion of compacted fill operations in building areas, construction of building elements should begin immediately, or the finished subgrade should be protected from exposure to inclement weather conditions. Exposure to precipitation and freeze/thaw cycles will cause the finished subgrade to soften and become excessively disturbed. If development plans require that finished subgrades remain exposed to weather conditions after completion of fill operations, additional fill should be placed above finished grades to protect the newly placed fill.
Alternatively, a budget should be established for reworking of the upper 1 to 2 feet of previously placed compacted fill.
5.0 GENERAL LIMITATIONS
Recommendations contained in this report are based upon the data obtained from the relatively limited number of test borings. This report does not reflect conditions that may occur between the points investigated, or between sampling intervals in test borings. The nature and extent of
September 12, 2018 ■ Terracon Project No. JD185040
September 12, 2018 JD185040 Page 7 variations between test borings and sampling intervals may not become evident until the course of construction. Therefore, it is essential that on-site observations of subgrade conditions be performed during the construction period to determine if re-evaluation of the recommendations in this report must be made. It is critical to the successful completion of this project that Terracon be retained during construction to observe the implementation of the recommendations provided herein.
This report has been prepared to aid in the evaluation of the site and to assist your office and the design professionals in the design of this project. It is intended for use with regard to the specific project as described herein. Changes in proposed construction, grading plans, etc. should be brought to our attention so that we may determine any effect on the recommendations presented herein.
An allowance should be established for additional costs that may be required for foundation and earthwork construction as recommended in this report. Additional costs may be incurred for various reasons including wet fill materials, soft subgrade conditions, unexpected groundwater problems, etc.
This report should be made available to bidders prior to submitting their proposals to supply them with facts relative to the subsurface conditions revealed by our investigation and the results of analyses and studies that have been performed for this project. In addition, this report should be given to the successful contractor and subcontractors for their information only.
We recommend the project specifications contain the following statement: “A geotechnical engineering report has been prepared for this project by Terracon Consultants – NY, Inc. This report is for informational purposes only and should not be considered part of the contract documents. The opinions expressed in this report are those of the geotechnical engineer and represent their interpretation of the subsoil conditions, tests and results of analyses that they performed. Should the data contained in this report not be adequate for the contractor’s purposes, the contractor may make their own investigations, tests and analyses prior to bidding.”
This report was prepared in accordance with generally accepted geotechnical engineering practices. No warranties, expressed or implied, are made as to the professional services included in this report.
We appreciate the opportunity to be of service for this project. Please contact the undersigned if you require clarification of any aspect of this report.
Sincerely, Terracon Consultants – NY, Inc.
Michele A. Fiorillo, PE Geotechnical Department Manager
RKS/DN/KF/RSZ/PEB/shm N:\Projects\2018\JD185040\Working Files\DRAFTS (Proposal-Reports-Communications)\GER\GER_West Point Lee Barracks.docx
Appendix A Subsurface Investigation Subsurface Investigation Procedures (1 page)
Identification of Soil (1 page)
Engineering Descriptions of Rock (2 pages)
Figure 1, Boring Location Plan (1 page)
Test Boring Notes (1 page)
Test Boring Logs (2 pages)
Rock Core Photograph (1 page)
Subsurface Investigation Procedures
1. Test Borings – Hollow Stem Augers The borings are advanced by turning an auger with a center opening of 3-¼ inches. A plug device blocks off the center opening while augers are advanced. Cuttings are brought to the surface by the auger flights. Sampling is performed through the center opening in the hollow stem auger, by standard methods, after removal of the plug. Usually, no water is introduced into the boring using this procedure.
2. Standard Penetration Tests Standard penetration tests are performed by driving a 2-inch O.D., 1-⅜ inch I.D. sampling spoon with a 140-pound hammer falling 30 inches, according to ASTM D1586. After an initial 6 inches penetration to assure the sampling spoon is in undisturbed material, the number of blows required to drive the sampler an additional 12 inches is generally taken as the N value. In the event 30 or more blows are required to drive the sampling spoon the initial 6-inch interval, the sampling spoon is driven to a total penetration resistance of 100 blows or 18 inches, whichever occurs first.
3. Rock Core Drilling Rock is core drilled using NQ size core bits set with carbide steel or diamond, depending upon the rock texture. The bit is fitted onto a double tube swivel-type core barrel in which an exterior tube and bit rotate, and an interior barrel remains stationary to receive the rock core. Water is circulated between the barrels and across the bit face to cool the core bit and to flush away cuttings.
4. Test Boring Stakeout The test boring stakeout was provided by GeoConcepts personnel using available site plans. The project civil engineer performed an as-drilled survey of the boring locations after a later date.
Identification of Soil I. DEFINITION OF SOIL GROUP NAMES ASTM D2487 Symbol Group Name
Coarse-Grained Soils More than 50% retained on No. 200 sieve
Gravels More than 50% of coarse fraction retained on No. 4 sieve
Clean Gravels Less than 5% fines
GW WELL GRADED GRAVEL
GP POORLY GRADED GRAVEL
Gravels with Fines More than 12% fines
GM SILTY GRAVEL
GC CLAYEY GRAVEL
Sands 50% or more of coarse fraction passes No. 4 sieve
Clean Sands Less than 5% fines
SW WELL GRADED SAND
SP POORLY GRADED SAND
Sands with fines More than 12% fines
SM SILTY SAND
SC CLAYEY SAND
Fine-Grained Soils 50% or more passes the No. 200 sieve
Silts and Clays Liquid Limit less than
Inorganic CL LEAN CLAY
ML SILT
Organic OL ORGANIC CLAY
ORGANIC SILT
Silts and Clays Liquid Limit 50 or more
Inorganic CH FAT CLAY
MH ELASTIC SILT
Organic OH ORGANIC CLAY
ORGANIC SILT
Highly Organic Soils Primarily organic matter, dark in color, and organic odor PT PEAT
II. DEFINITION OF MINOR COMPONENT PROPORTIONS
Minor Component Approximate Percentage of Fraction by Weight Gravelly, Sandy (adjective) 30% or more coarse grained Sand, Gravel 15% to 29% coarse grained Silt, Clay 5% to 12% fine grained
III. GLOSSARY OF MISCELLANEOUS TERMS
SYMBOLS Unified Soil Classification Symbols are shown above as group symbols. Use “A” Line Chart for laboratory identification. Dual symbols are used for borderline classification.
BOULDERS &
COBBLES
Boulders are considered pieces of rock larger than 12 inches, while cobbles range from 3 to 12 inches.
WEATHERED ROCK Residual rock material with a standard penetration test (SPT) resistance of at least 50 blows per 6 inches.
ROCK/SPOON
REFUSAL
Rock material with a standard penetration test (SPT) resistance of 50 blows for 1 inch.
ROCK FRAGMENTS Angular pieces of rock which have separated from original vein or strata and are present in a soil matrix. Only used in residual soils
QUARTZ A hard silicate mineral often found in residual soils. Only used when describing residual soils.
CEMENTED SAND Usually localized rock-like deposits within a soil stratum composed of sand grains cemented by calcium carbonate, iron oxide, or other minerals. Commonly encountered in Coastal Plain sediments, primarily in the Potomac Group sands (Kps).
MICACEOUS A term used to describe soil that “glitters” or is shiny. Most commonly encountered in fine-grained soils.
ORGANIC MATERIALS
(Excluding Peat)
Topsoil - Surface soils that support plant life and contain organic matter.
Lignite - Hard, brittle decomposed organic matter with low fixed carbon content (a low grade of coal).
FILL Man-made deposit containing soil, rock, and other foreign matter.
CONTAINS This is used when a soil contains a secondary component that does not apply to a USCS classification.
WITH This is used when a residual soil contains a secondary component that is included in the USCS classification.
PROBABLE FILL Soils which contain no visually detected foreign matter but which are suspect with regard to origin.
LAYERS ½ to 12 inch seam of minor soil component.
COLOR Two most predominant colors present should be described.
MOISTURE
CONDITIONS
Wet, moist, or dry to indicate visual appearance of specimen.
GRAIN SIZE Fine-medium-coarse
Engineering Descriptions of Rock The terminology used by GeoConcepts to describe rock cores can also be applied to rock outcrops and hand sized specimens.
Rock Hardness Very Hard Specimen cannot be scratched with a knife.
Hard Specimen can be scratched with a knife with difficulty.
Moderately Hard Specimen can be scratched with a knife with ease.
Soft Specimen can be scratched with a fingernail.
Very Soft Specimen can be deformed by hand.
Rock Weathering Unweathered No evidence of chemical or mechanical alteration Slightly Weathered slight discoloration on surface, slight alteration along fractures, <10% of the rock volume altered Moderately Weathered Obvious discoloration, iron and magnesium minerals look rusty, 10-
50% of the rock volume altered Highly Weathered Entire mass discolored, alteration through most of the rock, some pockets of slightly weathered rock, some minerals leached away Decomposed Rock reduced to soil with relic rock structure. Can be molded and crumbled by hand
Fracturing (excludes mechanical breaks) Very widely fractured: No observed fractures. Spacing >5 ft.
Slightly Fractured: Core recovered mostly in lengths of 2 ft. to less than 5 ft.
Moderately Fractured: Core recovered mostly in lengths of 0.7 ft. to less than 2 ft.
Highly Fractured: Core recovered mostly in lengths of 0.2 ft. to less than 0.7 ft.
Intensely Fractured: Core recovered mostly in lengths of less than 0.2 ft.
Percent Core Recovery and Rock Quality Designation Percent Core Recovery: Percent of recovered core calculated as the length of the core recovered, divided by the length of the core run, times 100.
Rock Quality Designation: RQD is the summed length of individual rock core pieces 4 inches or greater divided by the length of the rock core run times 100. Based on the percent RQD the following designations are assigned:
RQD Designation 0 to 25 % Very Poor Rock 25 to 50 % Poor Rock 50 to 75 % Fair Rock 75 to 90 % Good Rock 90 to 100 % Excellent Rock
For example, the sum of the rock core pieces greater than 4 inches in length from a core run of
5.0 feet equals 3.5 feet, then the RQD equals 3.5 feet, divided by 5.0 feet, times 100, or 70 % - Fair Rock.
B-2
B-1
(703) 726-8032 fax
(703) 726-803019955 Highland Vista Dr., Suite 170
B-1
Test Boring Notes
1. Classification of soil is by visual inspection and is in accordance with the Unified Soil
Classification System.
2. Estimated groundwater levels are indicated on the logs. These are only estimates from available data and may vary with precipitation, porosity of soil, site topography, etc.
3. Sampling data presents standard penetrations for 6-inch intervals or as indicated with graphic representations adjacent to the sampling data.
4. The energy applied to the split-spoon sampler using the automatic hammer is about 33 percent greater than the applied energy using the standard safety hammer. The hammer blows shown on the boring logs are uncorrected for the higher energy.
5. The logs and related information depict subsurface conditions at the specific locations and at the particular time when drilled. Soil conditions at other locations may differ from conditions occurring at the test locations. Also, the passage of time may result in a change in the subsurface conditions at the test locations.
6. The stratification lines represent the approximate boundary between soil types as determined in the sampling operation. Some variation may be expected vertically between samples taken.
The soil profile, groundwater level observations and penetration resistances presented on the logs have been made with reasonable care and accuracy and must be considered only an approximate representation of subsurface conditions to be encountered at the particular location.
7. Weathered rock is defined as residual earth material with a penetration resistance between 50 blows per 6 inches and refusal. Spoon refusal at the surface of rock, boulders, or obstructions is defined as a penetration resistance of 50 blows for 1-inch penetration or less.
Auger refusal is taken as the depth at which further penetration of the auger is not possible without risking significant damage to the drilling equipment.
8. Rock Quality Designation (RQD) represents the sum of cores recovered with lengths of 4 inches or longer, divided by the total length of rock core, expressed in percentage.
97 73
9+12+18
50/5
32+7+7+17
25+8+6+5
11+7+5+3
50/1
172.6 172.4 171.9 171.6
168.6
166.6
164.6
162.6
158.6
153.6
A
B
Asphalt = 3 in.
Concrete = 9 in.
Fill, brown, fine to coarse, POORLY GRADED SAND WITH SILT AND GRAVEL, dense, moist, SP-SM
Very dense
Fill, brown, fine to coarse, SILTY SAND, medium dense, moist, SM
Fill, brown, fine to coarse, POORLY GRADED GRAVEL WITH SILT AND SAND, medium dense, moist, GP-GM
Fill, brown, fine to coarse, SILTY GRAVEL WITH SAND, medium dense, moist, GM
Slightly weathered, very hard, dark gray mottled white, GRANITE, slightly fractured
Bottom of Borehole at 19.0 ft.
15.2
3.1
7.1
3.5
5.5
DRILLER:
DRILLING METHOD:PROJECT NUMBER:
7/23/18 - 7/25/18Jacobs
JD185040
D. Evans
172.6
DATES DRILLED:OWNER/CLIENT:
GROUND SURFACE ELEVATION (ft.): DRILL RIG:
3.25 ID HSA; Automatic Hammer
SOIL
DRILLING CONTRACTOR:
BORING NUMBER:
SHEET 1 OF 1
MATERIAL DESCRIPTION
NOT ENCOUNTERED UPON COMPLETION
NOT ENCOUNTERED DURING DRILLING
19955 Highland Vista Dr., #170 Ashburn, Virginia 20147
703-726-8030 703-726-8032 fax
Lee Barracks Upgrade, Exterior Field Investigation
US Military Academy, West Point, New York
THE STRATIFICATION LINES REPRESENT APPROXIMATE BOUNDARIES. THE TRANSITION MAY BE GRADUAL.
SAMPLE TYPES:
SPT
Rock Core
REMARKS:
UniTech
J. Von Erden
B-1LOCATION:
LOGGED BY:
GROUND WATER LEVELS:
LOCATION:
PROJECT:
B O
R E
H O
LE
/T
E S
T P
IT
L
O G
S .G
P J
G E
O C
O N
C E
P T
S
6.
G D
T
/2 1/
R E
C
R Q
D
ROCK
SPT
BLOW
COUNTS R
E
C (in
ELEV.
(ft.)
ELEV. 167.6
20 40 60 80
STANDARD
PENETRATION
TEST RESISTANCE
(BPF)
5.0 ft.CAVED:
DEPTH
(ft.)
S T
R A
T U
M
S A
M P
LE
T
Y P
E
G R
A P
H
IC
M C
100 72
5+4+7
5+3+12
7+4+7+7
3+3+2+2
3+10+32+26
173.2 173.1 172.5
170.7
169.2
167.2
165.2
157.2
152.2
A
B
Asphalt = 1.5 in.
Concrete = 7.5 in.
Fill, brown-black, fine to coarse, POORLY GRADED GRAVEL WITH SILT AND SAND, medium dense, wet, GP-GM
Fill, brown-black, fine to coarse, SILTY SAND WITH GRAVEL, medium dense, moist, SM
Fill, brown, fine to coarse, SILTY CLAY WITH SAND, firm, moist, CL-ML
Fill, brown and black, fine to coarse, POORLY GRADED SAND WITH SILT AND GRAVEL, very dense, moist, SP-SM
Slightly weathered, dark gray white, GRANITE, slightly fractured
Bottom of Borehole at 21.0 ft.
8.1
9.5
19.1
2.5
DRILLER:
DRILLING METHOD:PROJECT NUMBER:
7/25/18 - 7/25/18Jacobs
JD185040
D. Evans
173.2
DATES DRILLED:OWNER/CLIENT:
GROUND SURFACE ELEVATION (ft.): DRILL RIG:
3.25 ID HSA; Automatic Hammer
SOIL
DRILLING CONTRACTOR:
BORING NUMBER:
SHEET 1 OF 1
MATERIAL DESCRIPTION
NOT ENCOUNTERED UPON COMPLETION
NOT ENCOUNTERED DURING DRILLING
19955 Highland Vista Dr., #170 Ashburn, Virginia 20147
703-726-8030 703-726-8032 fax
Lee Barracks Upgrade, Exterior Field Investigation
US Military Academy, West Point, New York
THE STRATIFICATION LINES REPRESENT APPROXIMATE BOUNDARIES. THE TRANSITION MAY BE GRADUAL.
SAMPLE TYPES:
SPT
Rock Core
REMARKS:
UniTech
J. Von Erden
B-2LOCATION:
LOGGED BY:
GROUND WATER LEVELS:
LOCATION:
PROJECT:
Encountered obstruction at 13 feet. Advanced to 16 feet using rock core techniques and had zero recovery.
B O
R E
H O
LE
/T
E S
T P
IT
L
O G
S .G
P J
G E
O C
O N
C E
P T
S
6.
G D
T
/2 1/
R E
C
R Q
D
ROCK
SPT
BLOW
COUNTS R
E
C (in
ELEV.
(ft.)
ELEV. 168.2
20 40 60 80
STANDARD
PENETRATION
TEST RESISTANCE
(BPF)
5.0 ft.CAVED:
DEPTH
(ft.)
S T
R A
T U
M
S A
M P
LE
T
Y P
E
G R
A P
H
IC
M C
Lee Barracks Upgrade, Exterior Field Investigation
US Military Academy, West Point, New York
JD185040
Rock Core Photographs
Boring # Run # Length
(feet)
From
(feet)
To
(feet)
Recovery Length
(inches)
Recovery
RQD
Length
(inches)
RQD
B-1 1 5.0 14.0 19.0 58 97 43.5 73
B-2 1 5.0 16.0 21.0 60 100 43 72
Appendix B Soil Laboratory Test Results Liquid and Plastic Limit, and Grain Size Analysis Test Data (18 pages)
Unconfined Rock Compressive Strength Test Data (1 page)
Corrosion Series Test Results (3 pages)
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
#4 #200
POORLY GRADED SAND
with silt and gravel
NP NP NP 65.8 9.4 SP-SM 15.2
Color
Test Method: ASTM D 4318
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by
Material Description LL PL PI w (%)
Brown AASHTO Classification
% Passing
USCS
A-1-b
7/31/2018
LIQUID AND PLASTIC LIMIT - ASTM D4318
Project Name Lee Barracks Exterior
Depth (Feet) 1.0-2.5
JD185040
B-1
4367-1 Date
0 10 20 30 40 50 60 70 80 90 100
P L A
S T
IC
IT
Y I
N D
E X
P
I)
LIQUID LIMIT (LL)
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
SIEVE % Passing
1 ½ " 100
3/4" 78
3/8" 78
#4 66
#10 51
#20 41
#40 32
#60 23
#100 15
#200 9
Pan -- Test Method: ASTM D 422
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by:
A-1-b
NP
Gravel
Sand
Fines
AASHTO Classification
Cu
9.4
POORLY GRADED SAND with silt and
44.8
0.5
NP
34.2
56.4
USCS Group Name
SP-SMUSCS Group Symbol
LL
PI
Color Brown
Cc
Lee Barracks ExteriorJD185040
B-1
GRAIN SIZE ANALYSIS - ASTM D422
Project Name
Depth (Feet)
7/31/2018Date4367-1
1.0-2.5
0.010.1110100
Grain Size Diameter (mm)
N o
N o
N o
¾ in
P e rc e n t
F in e r
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
#4 #200
POORLY GRADED SAND
with silt and gravel
NP NP NP 61.3 11.8 SP-SM 3.1
Color
Test Method: ASTM D 4318
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by
Material Description LL PL PI w (%)
Grey AASHTO Classification
% Passing
USCS
A-1-a
7/31/2018
LIQUID AND PLASTIC LIMIT - ASTM D4318
Project Name Lee Barracks Exterior
Depth (Feet) 4.0-4.4
JD185040
B-1
4367-2 Date
0 10 20 30 40 50 60 70 80 90 100
P L A
S T
IC
IT
Y I
N D
E X
P
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
SIEVE % Passing
1 ½ " 100
3/4" 89
3/8" 74
#4 61
#10 46
#20 35
#40 27
#60 21
#100 16
#200 12
Pan -- Test Method: ASTM D 422
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by:
A-1-a
NP
Gravel
Sand
Fines
AASHTO Classification
Cu
11.8
POORLY GRADED SAND with silt and
NP
38.7
49.5
USCS Group Name
SP-SMUSCS Group Symbol
LL
PI
Color Grey
Cc
Lee Barracks ExteriorJD185040
B-1
GRAIN SIZE ANALYSIS - ASTM D422
Project Name
Depth (Feet)
7/31/2018Date4367-2
4.0-4.4
0.010.1110100
Grain Size Diameter (mm)
N o
N o
N o
¾ in
P e rc e n t
F in
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
#4 #200
SILTY SAND NP NP NP 85.6 24.0 SM 7.1
Color
Test Method: ASTM D 4318
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by
7/31/2018
LIQUID AND PLASTIC LIMIT - ASTM D4318
Project Name Lee Barracks Exterior
Depth (Feet) 6.0-8.0
JD185040
B-1
4367-3 Date
Brown AASHTO Classification
% Passing
USCS
A-1-b
Material Description LL PL PI w (%)
0 10 20 30 40 50 60 70 80 90 100
P L A
S T
IC
IT
Y I
N D
E X
P
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
SIEVE % Passing
1 ½ " 100
3/4" 100
3/8" 92
#4 86
#10 71
#20 58
#40 48
#60 39
#100 32
#200 24
Pan -- Test Method: ASTM D 422
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by:
4367-3
6.0-8.0
GRAIN SIZE ANALYSIS - ASTM D422
Project Name
Depth (Feet)
7/31/2018Date
Lee Barracks ExteriorJD185040
B-1
USCS Group Name
SMUSCS Group Symbol
LL
PI
Color Brown
Cc
24.0
SILTY SAND
NP
14.4
61.6
A-1-b
NP
Gravel
Sand
Fines
AASHTO Classification
Cu
0.010.1110100
Grain Size Diameter (mm)
N o
N o
N o
¾ in
P e rc e n t
F in
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
#4 #200
POORLY GRADED GRAVEL
with silt & sand
NP NP NP 41.4 10.5 GP-GM 3.5
Color
Test Method: ASTM D 4318
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by
Material Description LL PL PI w (%)
Brown AASHTO Classification
% Passing
USCS
A-1-a
7/31/2018
LIQUID AND PLASTIC LIMIT - ASTM D4318
Project Name Lee Barracks Exterior
Depth (Feet) 8.0-10.0
JD185040
B-1
4367-4 Date
0 10 20 30 40 50 60 70 80 90 100
P L A
S T
IC
IT
Y I
N D
E X
P
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
SIEVE % Passing
1 ½ " 100
3/4" 87
3/8" 53
#4 41
#10 34
#20 27
#40 22
#60 18
#100 14
#200 11
Pan -- Test Method: ASTM D 422
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by:
A-1-a
NP
Gravel
Sand
Fines
AASHTO Classification
Cu
10.5
POORLY GRADED GRAVEL with silt &
NP
58.6
30.8
USCS Group Name
GP-GMUSCS Group Symbol
LL
PI
Color Brown
Cc
Lee Barracks ExteriorJD185040
B-1
GRAIN SIZE ANALYSIS - ASTM D422
Project Name
Depth (Feet)
7/31/2018Date4367-4
8.0-10.0
0.010.1110100
Grain Size Diameter (mm)
N o
N o
N o
¾ in
P e rc e n t
F in
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
#4 #200
SILTY GRAVEL with sand NP NP NP 44.5 15.2 GM 5.5
Color
Test Method: ASTM D 4318
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by
Material Description LL PL PI w (%)
Brown AASHTO Classification
% Passing
USCS
A-1-a
7/31/2018
LIQUID AND PLASTIC LIMIT - ASTM D4318
Project Name Lee Barracks Exterior
Depth (Feet) 10.0-12.0
JD185040
B-1
4367-5 Date
0 10 20 30 40 50 60 70 80 90 100
P L A
S T
IC
IT
Y I
N D
E X
P
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
SIEVE % Passing
1 ½ " 100
3/4" 73
3/8" 53
#4 45
#10 39
#20 33
#40 28
#60 23
#100 20
#200 15
Pan -- Test Method: ASTM D 422
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by:
A-1-a
NP
Gravel
Sand
Fines
AASHTO Classification
Cu
15.2
SILTY GRAVEL with sand
NP
55.5
29.3
USCS Group Name
GMUSCS Group Symbol
LL
PI
Color Brown
Cc
Lee Barracks ExteriorJD185040
B-1
GRAIN SIZE ANALYSIS - ASTM D422
Project Name
Depth (Feet)
7/31/2018Date4367-5
10.0-12.0
0.010.1110100
Grain Size Diameter (mm)
N o
N o
N o
¾ in
P e rc e n t
F in
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
#4 #200
POORLY GRADED GRAVEL
with silt & sand
NP NP NP 39.0 7.5 GP-GM 8.1
Color
Test Method: ASTM D 4318
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by
Material Description LL PL PI w (%)
Brown AASHTO Classification
% Passing
USCS
A-1-a
7/31/2018
LIQUID AND PLASTIC LIMIT - ASTM D4318
Project Name Lee Barracks Exterior
Depth (Feet) 2.5-4.0
JD185040
B-2
4367-6 Date
0 10 20 30 40 50 60 70 80 90 100
P L A
S T
IC
IT
Y I
N D
E X
P
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
SIEVE % Passing
1 ½ " 100
3/4" 47
3/8" 43
#4 39
#10 32
#20 26
#40 20
#60 14
#100 9
#200 8
Pan -- Test Method: ASTM D 422
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by:
A-1-a
NP
Gravel
Sand
Fines
AASHTO Classification
Cu
7.5
POORLY GRADED GRAVEL with silt &
147.4
0.7
NP
61.0
31.4
USCS Group Name
GP-GMUSCS Group Symbol
LL
PI
Color Brown
Cc
Lee Barracks ExteriorJD185040
B-2
GRAIN SIZE ANALYSIS - ASTM D422
Project Name
Depth (Feet)
7/31/2018Date4367-6
2.5-4.0
0.010.1110100
Grain Size Diameter (mm)
N o
N o
N o
¾ in
P e rc e n t
F in
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
#4 #200
SILTY SAND with gravel NP NP NP 64.0 15.2 SM 9.5
Color
Test Method: ASTM D 4318
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by
Material Description LL PL PI w (%)
Brown AASHTO Classification
% Passing
USCS
A-1-b
7/31/2018
LIQUID AND PLASTIC LIMIT - ASTM D4318
Project Name Lee Barracks Exterior
Depth (Feet) 4.0-6.0
JD185040
B-2
4367-7 Date
0 10 20 30 40 50 60 70 80 90 100
P L A
S T
IC
IT
Y I
N D
E X
P
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
SIEVE % Passing
1 ½ " 100
3/4" 75
3/8" 73
#4 64
#10 53
#20 41
#40 32
#60 25
#100 20
#200 15
Pan -- Test Method: ASTM D 422
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by:
A-1-b
NP
Gravel
Sand
Fines
AASHTO Classification
Cu
15.2
SILTY SAND with gravel
NP
36.0
48.9
USCS Group Name
SMUSCS Group Symbol
LL
PI
Color Brown
Cc
Lee Barracks ExteriorJD185040
B-2
GRAIN SIZE ANALYSIS - ASTM D422
Project Name
Depth (Feet)
7/31/2018Date4367-7
4.0-6.0
0.010.1110100
Grain Size Diameter (mm)
N o
N o
N o
¾ in
P e rc e n t
F in
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
#4 #200 silty Clay with sand 22 17 5 97.4 73.9 CL-ML 19.1
Color
Test Method: ASTM D 4318
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by
Material Description LL PL PI w (%)
Brown AASHTO Classification
% Passing
USCS
A-4
7/31/2018
LIQUID AND PLASTIC LIMIT - ASTM D4318
Project Name Lee Barracks Exterior
Depth (Feet) 6.0-8.0
JD185040
B-2
4367-8 Date
0 10 20 30 40 50 60 70 80 90 100
P L A
S T
IC
IT
Y I
N D
E X
P
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
SIEVE % Passing
1 ½ " 100
3/4" 100
3/8" 100
#4 97
#10 95
#20 93
#40 90
#60 88
#100 85
#200 74
Pan -- Test Method: ASTM D 422
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by:
A-4
Gravel
Sand
Fines
AASHTO Classification
Cu
73.9 silty Clay with sand
2.6
23.5
USCS Group Name
CL-MLUSCS Group Symbol
LL
PI
Color Brown
Cc
Lee Barracks ExteriorJD185040
B-2
GRAIN SIZE ANALYSIS - ASTM D422
Project Name
Depth (Feet)
7/31/2018Date4367-8
6.0-8.0
0.010.1110100
Grain Size Diameter (mm)
N o
N o
N o
¾ in
P e rc e n t
F in
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
#4 #200
POORLY GRADED SAND
with silt and gravel
NP NP NP 55.2 10.0 SP-SM 2.5
Color
Test Method: ASTM D 4318
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by
Material Description LL PL PI w (%)
Brown AASHTO Classification
% Passing
USCS
A-1-a
7/31/2018
LIQUID AND PLASTIC LIMIT - ASTM D4318
Project Name Lee Barracks Exterior
Depth (Feet) 8.0-10.0
JD185040
B-2
4367-9 Date
0 10 20 30 40 50 60 70 80 90 100
P L A
S T
IC
IT
Y I
N D
E X
P
(703) 726-8030 www.geoconcepts-eng.com
Project No.
Sample ID
Lab Order No.
SIEVE % Passing
1 ½ " 100
3/4" 100
3/8" 72
#4 55
#10 42
#20 33
#40 26
#60 21
#100 16
#200 10
Pan -- Test Method: ASTM D 422
Soil Classification by ASTM D2487 and AASHTO M 145
Reviewed by:
A-1-a
NP
Gravel
Sand
Fines
AASHTO Classification
Cu
10.0
POORLY GRADED SAND with silt and
NP
44.8
45.2
USCS Group Name
SP-SMUSCS Group Symbol
LL
PI
Color Brown
Cc
Lee Barracks ExteriorJD185040
B-2
GRAIN SIZE ANALYSIS - ASTM D422
Project Name
Depth (Feet)
7/31/2018Date4367-9
8.0-10.0
0.010.1110100
Grain Size Diameter (mm)
N o
N o
N o
¾ in
P e rc e n t
F in
Sample No.
Sample Depth
(feet) Rock Type Test Date
Length
Uncapped (0.01 in.)
Diameter
(0.01 in.)
Area
(in
Load (lbs.)
Compressive
Strength (psi) L/D
B-1 18.0-18.5 Granite 7/30/2018 3.86 1.99 3.11 30070 9668 1.94
B-2 19.0-19.5 Granite 7/30/2018 3.61 1.97 3.05 36260 11896 1.83
Reported by:
Project
Number:
JD185040
Project Name: Lee Barracks Upgrade
UNCONFINED ROCK COMPRESSIVE STRENGTH TEST REPORT
19955 Highland Vista Dr., Suite 170 Ashburn, Virginia 20147
(703) 726-8030 www.geoconcepts-eng.com
GeoConcepts Engineering, Inc Report Number: 184685 Katherine Fordnev Date Received: 08/14/18 16:00 19955 Highland Vista Dr., Suite 170 Date Reported: 08/17/18 14:05 Ashburn, VA 20147 Project Location: Lee Barracks, West Point, NY
Client Sample No: B-1 (0'-5') Lab Sample No.: 184685-01 Sample Matrix: Soil Collection Date/Time: 07/23/18 00:00 Sample Description:
Soil Corrosion Potential Tests
Parameter Method Result Units Limit Dilution Qualifier Cont. Analysis Date Analyst Resistivity ASTM G187 1000 ohm-cm N/A 1 A 08/15/18 JMP Redox Potential Electrode + 296 mV N/A 1 A 08/17/18 JMP pH CA-643 9.0 pH N/A A 08/15/18 JMP Chloride (Water Soluble) CA-422 260 mg/Kg 2.5 1 D A 08/16/18 JMP Sulfate (Water Soluble) EPA 375.4 97 mg/Kg 5.0 1 D A 08/16/18 JMP Sulfide (Water Soluble) EPA 376.2 < 1.2 mg/Kg 1.2 1 U A 08/16/18 JMP Moisture (Percent) EPA 13 % N/A A 08/15/18 JMP
Certificate of Laboratory Analysis
HP ENVIRONMENTAL INCORPORATED
GeoConcepts Engineering, Inc Report Number: 184685 Katherine Fordnev Date Received: 08/14/18 16:00 19955 Highland Vista Dr., Suite 170 Date Reported: 08/17/18 14:05 Ashburn, VA 20147 Project Location: Lee Barracks, West Point, NY
Qualifier Codes:
U = Analyte was not detected at or above reporting limit D = Analyte reported from a sample dilution
Sample Container Codes:
Plastic Bag A Soil
Notes:
Soil Results are reported on a wet weight basis (as received) unless stated as "dry".
The lab results reflect the measurement of the sample received only and may not be completely representative of the sampled site.
The Client has the responsibility for assessing risk and appropriate data interpretation of the results contained herein.
Laboratory reports issued are intended for the exclusive use by the Client and shall not be reproduced except in its entirety.
The chain-of-custody is a part of the entire analytical report.
Residual sample(s) will be disposed of in three months unless otherwise notified.
Laboratory Report Approved by:
J Pfaff Laboratory Director, Chemistry Date
Certificate of Laboratory Analysis
HP ENVIRONMENTAL INCORPORATED
08/17/18
P age 3 of 3
| 1.0SCOPE OF SERVICES |
| 2.0SITE DESCRIPTION AND PROPOSED CONSTRUCTION |
| 3.0SUBSURFACE CONDITIONS |
| 3.1 Geology |
| 3.2Stratification |
| 3.3Groundwater |
| 3.4Soil Laboratory Test Results |
| 3.5Seismic Site Classification |
| 3.6Metal Corrosion/Concrete Attack Test Results |
| 3.7 Rock Unconfined Compressive Strength Test Results |
| 4.0PRELIMINARY ENGINEERING ANALYSIS |
| 4.1Pavements |
| 4.2Earthwork |
| 5.0GENERAL LIMITATIONS |
| cover |
| cover page |
| GW |
| GP |
| GM |
| GC |
| SW |
| SP |
| SM |
| SC |
| CL |
| ML |
| OL |
| CH |
| MH |
| OH |
| PT |
| SYMBOLS |
| BOULDERS & COBBLES |
| WEATHERED ROCK |
| ROCK/SPOON REFUSAL |
| ROCK FRAGMENTS |
| QUARTZ |
| CEMENTED SAND |
| MICACEOUS |
| ORGANIC MATERIALS |
| ORGANIC MATERIALS (Excluding Peat) |
| FILL |
| CONTAINS |
| WITH |
| PROBABLE FILL |
| LAYERS |
| COLOR |
| MOISTURE CONDITIONS |
| GRAIN SIZE |
| 4. B. |
| B-1, 1.0-2.5 |
| B-1, 4.0-4.4 |
| B-1, 6.0-8.0 |
| B-1, 8.0-10.0 |
| B-1, 10.0-12.0 |
| B-2, 2.5-4.0 |
| B-2, 4.0-6.0 |
| B-2, 6.0-8.0 |
| B-2, 8.0-10.0 |
| Granite Core Test Report 07-30-2018 |
| RPT184685 |
| 3. A. rest |
| logs 8-21-18 |
| Lee Barracks Rock Core Photos |
| 2. A. Figure 1 |
| Sheets and Views |
| 11X17 |
| 2018-09-12T14:03:33-0400 | |
| Smith-Zakowicz, Rebecca L |
| 2018-09-12T14:14:29-0400 | |
| Fiorillo, Michele A |
| 2018-09-12T14:15:45-0400 | |
| Fiorillo, Michele A |
| 2018-09-12T14:15:47-0400 | |
| Fiorillo, Michele A |
File details come from the government source that posted it. Updated .