118ECE908 AMDT 004 10 21 13 dated 082017 updated 05142020 10 pages.pdf
PDF 38 KB Posted
- Attached to
- DLA Fitness Center Renovation
- Solicitation number
- W9123620B2011
About this file
This document provides specifications for toilet compartments and partitions to be installed as part of a fitness center renovation project. Key details include solid polyethylene plastic panels not less than one inch thick to comprise toilet enclosures and urinal screens. Toilet enclosures are to be overhead braced according to specification A-A-60003. Hardware is to include hinges, latches, coat hooks and other fittings resistant to common toilet chemicals and meeting accessibility standards. Installation drawings and product data must be submitted for approval, along with samples of colors and finishes, and a 25-year warranty is required.
This related federal contract opportunity notice announces the intent to award a firm-fixed-price contract for construction services to renovate Building 32, Bays F-G at the Defense Supply Center in Richmond, Virginia into a new fitness center. Functional spaces are to include offices, wellness facilities, courts, gymnasium, locker rooms and ancillary spaces. The pre-solicitation will be issued on April 9, 2020 via beta.sam.gov as a 100% small business set-aside using sealed bids. The receipt date for proposals is May 7, 2020 and the magnitude of construction cost is estimated between $5-10 million, requiring payment and performance bonds.
View the file
Other files
Show 40 more
Latest 50 of 76 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CONVERT B32, BAYS F-G FOR FITNESS CENTER W91236-19-R-0023
DEFENSE SUPPLY CENTER RICHMOND (DSCR)
SECTION 10 21 13
TOILET COMPARTMENTS
08/17
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
ALUMINUM ASSOCIATION (AA)
AA DAF45 (2003; Reaffirmed 2009) Designation System for Aluminum Finishes
ASTM INTERNATIONAL (ASTM)
ASTM A123/A123M (2017) Standard Specification for Zinc (Hot-Dip Galvanized) Coatings on Iron and Steel Products
ASTM A167 (2011) Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip
ASTM A336/A336M (2018) Standard Specification for Alloy Steel Forgings for Pressure and High-Temperature Parts
ASTM A385/A385M (2017) Standard Practice for Providing High-Quality Zinc Coatings (Hot-Dip)
ASTM A653/A653M (2018) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM B221 (2014) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM B36/B36M (2013) Standard Specification for Brass Plate, Sheet, Strip, and Rolled Bar
ASTM B86 (2013) Standard Specification for Zinc and Zinc-Aluminum (ZA) Alloy Foundry and Die Castings
ASTM D6386 (2016) Standard Practice for Preparation of Zinc (Hot-Dip Galvanized) Coated Iron and Steel Product and Hardware Surfaces for Painting
SECTION 10 21 13 Page 1
READY TO ADVERTISE
ASTM D7611/D7611M (2013; E 2014) Standard Practice for Coding Plastic Manufactured Articles for Resin Identification
INTERNATIONAL CODE COUNCIL (ICC)
ICC A117.1 COMM (2017) Standard And Commentary Accessible and Usable Buildings and Facilities
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
U.S. GENERAL SERVICES ADMINISTRATION (GSA)
CID A-A-60003 (Basic) Partitions, Toilet, Complete
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
UNDERWRITERS LABORATORIES (UL)
UL 2818 (2013) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" designation;
submittals not having a "G" designation are for Contractor Quality Control approval. Submittals with an "S" are for inclusion in the Sustainability eNotebook, in conformance to Section 01 33 29 SUSTAINABILITY REPORTING.
Submit the following in accordance with Section 01 33 00.00 50 SUBMITTAL
PROCEDURES:
SD-02 Shop Drawings
Fabrication Drawings
Installation Drawings; G
SD-03 Product Data
Cleaning and Maintenance Instructions
Colors And Finishes Galvanized Steel Sheet Sound-Deadening Cores
Anchoring Devices and Fasteners
Hardware and Fittings
Brackets
Door Hardware
SECTION 10 21 13 Page 2
Toilet Enclosures
Urinal Screens
Pilaster Shoes
Finishes; G
Recycled content for plastic, solid polyethylene partitions and screens; S
SD-04 Samples
Colors and Finishes; G
Hardware and Fittings
Anchoring Devices and Fasteners
SD-07 Certificates
Warranty
SD-10 Operation and Maintenance Data
Plastic Identification; G
SD-11 Closeout Submittals
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality
1.3.1.1 Solid Phenolic Products
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of CDPH Standard Method v1.1. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.4 REGULATORY REQUIREMENTS
Conform to ICC A117.1 COMM code for access for the handicapped operation of toilet compartment door and hardware.
1.5 DELIVERY, STORAGE, AND HANDLING
Deliver materials in the manufacturer's original unopened packages with the brand, item identification, and project reference clearly marked.
Store components in a dry location that is adequately ventilated; free from dust, water, other contaminants, and damage during delivery, storage, and construction.
SECTION 10 21 13 Page 3
1.6 WARRANTY
Provide certification or warranties that toilet partitions will be free of defects in materials, fabrication, finish, and installation and will remain so for a period of not less than 25 years after completion.
PART 2 PRODUCTS
2.1 SYSTEM REQUIREMENTS
Provide a complete and usable toilet partition system, including toilet enclosures, room entrance screens, urinal screens, system of panels, hardware, and support components. Furnish the partition system from a single manufacturer, with a standard product as shown in the most recent catalog data. Submit Fabrication Drawings for metal toilet partitions and urinal screens consisting of fabrication and assembly details to be performed in the factory. Submit manufacturer's Cleaning and Maintenance Instructions with Fabrication Drawings for review.
2.1.1 Plastic Identification
Verify that plastic products to be incorporated into the project are labeled in accordance with ASTM D7611/D7611M . Where products are not labeled, provide product data indicating polymeric information in the Operation and Maintenance Manual.
Type 2 High Density Polyethylene (HDPE)
2.2 MATERIALS
2.2.1 Galvanized Steel Sheet
Provide galvanized steel sheet cold-rolled, stretcher-level, commercial quality material, conforming to ASTM A653/A653M . Conform surface preparation of material for painting to ASTM D6386, Method A.
2.2.2 Sound-Deadening Cores
Provide sound deadening consisting of treated kraft paper honeycomb cores with a cell size of not more than 1 inch. Resin-material content must weigh not less than 11 percent of the finished core weight. Expanded cores must be faced on both sides with kraft paper.
2.2.3 Anchoring Devices and Fasteners
Provide steel anchoring devices and fasteners hot-dipped galvanized after fabrication, in conformance with ASTM A385/A385M and ASTM A123/A123M .
Conceal all galvanized anchoring devices.
2.2.4 Brackets
Wall brackets must be two-ear panel brackets, T-style, 1-inch stock.
Provide stirrup style panel-to-pilaster brackets.
SECTION 10 21 13 Page 4
2.2.5 Hardware and Fittings
2.2.5.1 General Requirements
Conform hardware for the toilet partition system to CID A-A-60003 for the specified type and style of partitions. Provide hardware finish highly resistant to alkalis, urine, and other common toilet room acids. Comply latching devices and hinges for handicap compartments with 36 CFR 1191 ;
provide stainless steel devices and hinges with door latches that operate without either tight grasping or twisting of the wrist of the operator.
Submit three samples of each item, including anchoring devices and fasteners. Approved hardware samples may be installed in the work if properly identified.
Material Conformance Standard
Cold-rolled sheet steel ASTM A336/A336M , commercial quality
Zinc-base alloy ASTM B86, Alloy AC41-A
Brass ASTM B36/B36M, Alloy C26800
Aluminum ASTM B221
Corrosion-resistant steel ASTM A167, Type 304
2.2.5.2 Finishes
a. Corrosion-resistant steel must have a No. 4 finish.
b. Exposed fasteners must match the hardware and fittings.
2.2.6 Door Hardware
2.2.6.1 Hinges
Hinges must be adjustable to hold in-swinging doors open at any angle up to 90 degrees and outswinging doors to 10 degrees. Provide self-lubricating hinges with the indicated swing. Hinges must be the surface-mounted type or be the cutout-insert type. have the following type of return movement:
a. Gravity return movement
2.2.6.2 Latch and Pull
Latch and pull must be a combination rubber-faced door strike and keeper equipped with emergency access.
2.2.6.3 Coat Hooks
Coat hooks must be combination units with hooks and rubber tipped pins.
2.3 PARTITION PANELS AND DOORS
Fabricate partition panels and doors not less than 1 inch thick , HDPE.
SECTION 10 21 13 Page 5
Material performance requirements: Meet Class B Fire Rating.
Provide solid polyethylene HDPE toilet partitions and screens with recycled content of 30 percent minimum. Provide data identifying percentage of recycled content for plastic, solid polyethylene partitions and screens.
2.3.1 Toilet Enclosures
Provide and conform toilet enclosures to CID A-A-60003 , Type I, Style C, overhead braced. Furnish width, length, and height of toilet enclosures as shown. Provide a width of 1 inch. Finish surface of panels must be solid polyethylene, Finish 5; water resistant; graffiti resistant;
non-absorbent; 1/4 inch radius beveled edges. Reinforce panels indicated to receive toilet paper holders or grab bars for mounting of the items required. Provide grab bars to withstand a bending stress, shear stress, shear force, and a tensile force induced by 250 lbf. Grab bars must not rotate within their fittings.
Material performance requirements: Meet Class B fire rating.
2.3.2 Urinal Screens
Provide and conform urinal screens to CID A-A-60003 , Type III, Style A, floor supported. Provide finish for surface of screens as solid polyethylene, Finish 5; water resistant; graffiti resistant;
non-absorbent; ; 1/4 inch radius beveled edges. Furnish width and height of urinal screens as shown. Provide thickness of 1 inch. Fabricate screens from the same types of panels and pilasters as the toilet partitions. Use corrosion-resistant stainless steel fittings and fasteners.
Material performance requirements: Meet Class B fire rating.
Amendment 004* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * *
2.4 OVERHEAD-BRACED PARTITIONS
Pilasters must be not less than 1 i nch thick with face sheets not less than
0.0393 inch thick. Provide anchoring device at the bottom of the pilaster consisting of a channel-shaped floor stirrup fabricated from not less than 0.0635 inch thick material and a leveling bolt. Secure the stirrup to the pilaster with not less than a 3/16 inch bolt and nut after the pilaster is leveled. Secure the stirrup to the floor with not less than two lead expansion shields and sheetmetal screws. Fabricate overhead brace from a continuous extruded aluminum tube not less than 1 inch wide by 1-1/2 inch high, 0.125-inch wall thickness. Finish must be AA-C22A31 in accordance with AA DAF45. Set and secure brace into the top of each pilaster. Fabricate 3 inch high trim piece at the floor from not less than
0.030 inch thick corrosion-resistant stainless steel.
* * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * * Amendment 004
2.5 PILASTER SHOES
Provide shoes at pilasters to conceal floor-mounted anchorage. Pilaster shoes must be one piece molded HDPE . Height must be 3 inches.
SECTION 10 21 13 Page 6
2.6 HARDWARE
Provide hardware for the toilet partition system that conforms to CID A-A-60003 for the specified type and style of partitions. Provide hardware pre-drilled by manufacturer. Use a hardware finish that is highly resistant to alkalis, urine, and other common toilet room acids.
Hardware includes: stainless steel hinges, gravity type, adjustable for door close positioning; nylon bearings; stainless steel door latch; door strike and keeper with rubber bumper; stainless steel coat hook and bumper. Provide latching devices and hinges for handicap compartments complying with 36 CFR 1191 and stainless steel door latches that operate without either tight grasping or twisting of the wrist of the operator.
Use stainless steel, tamper proof type screws and bolts. Wall mounting brackets must be continuous, full height, stainless steel , in accordance with toilet compartment manufacturer's instructions.
2.7 COLORS AND FINISHES
2.7.1 Colors
See interior finish legend for style and color. Submit three samples showing a finished edge on two adjacent sides and core construction, each not less than 12-inch square
2.7.2 Finishes No. 5
Provide solid plastic fabricated of polymer resins (polyethylene) formed under high pressure rendering a single component section not less than one inch thick. Colors must extend throughout the panel thickness. Provide exposed finish surfaces: smooth, waterproof, non-absorbent, and resistant to staining and marking with pens, pencils, or other writing devices.
Solid plastic partitions must not show any sign of deterioration when immersed in the following chemicals and maintained at a temperature of 80 degrees F for a minimum of 30 days:
Acetic Acid (80 percent) Hydrochloric Acid (40 percent)
Acetone Hydrogen Peroxide (30 percent)
Ammonia (liquid) Isopropyl Alcohol
Ammonia Phosphate Lactic Acid (25 percent)
Bleach (12 percent) Lime Sulfur
Borax Nicotine
Brine Potassium Bromide
Caustic Soda Soaps
Chlorine Water Sodium Bicarbonate
Citric Acid Trisodium Phosphate
SECTION 10 21 13 Page 7
Copper Chloride Urea; Urine
Core Oils Vinegar
PART 3 EXECUTION
3.1 PREPARATION
Take field measurements prior to the preparation of drawing and fabrication to ensure proper fits. Verify that field measurements, surfaces, substrates and conditions are as required, and ready to receive work. Verify correct spacing of plumbing fixtures. Verify correct location of built in framing, anchorage, and bracing. Report in writing to Contracting Officer prevailing conditions that will adversely affect satisfactory execution of the work of this section. Do not proceed with work until unsatisfactory conditions have been corrected.
3.2 INSTALLATION
Do not install items that show visual evidence of biological growth.
Install partitions rigid, straight, plumb, and level, with the panels centered between the fixtures. Provide a panel clearance of not more than 1/2 inch and secure the panels to walls and pilasters with not less than two wall brackets attached near the top and bottom of the panel. Locate wall brackets so that holes for wall bolts occur in masonry or tile joints. Secure Panels to pilasters with brackets matching the wall brackets. Provide for adjustment due to minor floor variations. Locate head rail joints at pilaster center lines. Install adjacent components for consistency of line and plane. Equip each door with hinges, one door latch, and one coat hook and bumper. Align hardware to uniform clearance at vertical edges of doors.
a. Secure panels to hollow plastered walls with toggle bolts using not less than 1/4-20 screws of the length required for the wall thickness. Toggle bolts must have a load-carrying strength of not less than 600 pounds per anchor.
b. Secure panels to ceramic tile on hollow plastered walls or hollow concrete-masonry walls with toggle bolts using not less than 1/4-20 screws of the length required for the wall thickness. Toggle bolts must have a load-carrying strength of not less than 600 pounds per anchor.
c. Secure panels to solid masonry or concrete with lead or brass expansion shields designed for use with not less than 1/4-20 screws, with a shield length of not less than 1-1/2 inch. Expansion shields must have a load-carrying strength of not less than 600 pounds per anchor.
d. Submit Installation Drawings for metal toilet partitions and urinal screens showing plans, elevations, details of construction, hardware, reinforcing and blocking, fittings, mountings and escutcheons.
Indicate on drawings the type of partition, location, mounting height, cutouts, and reinforcement required for toilet-room accessories.
3.3 OVERHEAD-BRACED PARTITIONS
Secure pilasters to the floor with the anchorage device specified. Make
SECTION 10 21 13 Page 8 all leveling devices readily accessible for leveling, plumbing, and tightening the installation. Secure overhead brace to the pilaster face with not less than two fasteners per face. Expansion shields must have a minimum 2-inch penetration into the concrete slab. Make tops of doors parallel with the overhead brace when doors are in a closed position.
3.4 FINAL ADJUSTMENT
After completion of the installation, make final adjustments to the pilaster-leveling devices, door hardware, and other working parts of the partition assembly. Doors must have a uniform vertical edge clearance of approximately 3/16 inch and must rest open at approximately 30 degrees when unlatched.
3.5 CLEANING
Baked enamel finish must be touched up with the same color of paint that was used for the finish. Clean all surfaces of the work, and adjacent surfaces soiled as a result of the work, in an approved manner compliant with the manufacturer's recommended cleaning and protection from damage procedures until accepted. Remove all equipment, tools, surplus materials, and work debris from the site.
-- End of Section --
SECTION 10 21 13 Page 9
THIS PAGE INTENTIONALLY LEFT BLANK
SECTION 10 21 13 Page 10
| 10 21 13 - TOILET COMPARTMENTS |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| 1.3 CERTIFICATIONS |
| 1.3.1 Indoor Air Quality |
| 1.3.1.1 Solid Phenolic Products |
| 1.4 REGULATORY REQUIREMENTS |
| 1.5 DELIVERY, STORAGE, AND HANDLING |
| 1.6 WARRANTY |
| PART 2 PRODUCTS |
| 2.1 SYSTEM REQUIREMENTS |
| 2.1.1 Plastic Identification |
| 2.2 MATERIALS |
| 2.2.1 Galvanized Steel Sheet |
| 2.2.2 Sound-Deadening Cores |
| 2.2.3 Anchoring Devices and Fasteners |
| 2.2.4 Brackets |
| 2.2.5 Hardware and Fittings |
| 2.2.5.1 General Requirements |
| 2.2.5.2 Finishes |
| 2.2.6 Door Hardware |
| 2.2.6.1 Hinges |
| 2.2.6.2 Latch and Pull |
| 2.2.6.3 Coat Hooks |
| 2.3 PARTITION PANELS AND DOORS |
| 2.3.1 Toilet Enclosures |
| 2.3.2 Urinal Screens |
| 2.4 OVERHEAD-BRACED PARTITIONS |
| 2.5 PILASTER SHOES |
| 2.6 HARDWARE |
| 2.7 COLORS AND FINISHES |
| 2.7.1 Colors |
| 2.7.2 Finishes No. 5 |
| PART 3 EXECUTION |
| 3.1 PREPARATION |
| 3.2 INSTALLATION |
| 3.3 OVERHEAD-BRACED PARTITIONS |
| 3.4 FINAL ADJUSTMENT |
| 3.5 CLEANING |