This solicitation seeks a single firm fixed-price contract to construct a new 18,650 square foot Medical Readiness facility at Dane County Regional Airport - Truax Field in Madison, Wisconsin. Work includes site utilities, grading, landscaping, erecting precast concrete panels, and new mechanical, electrical, plumbing and technology systems. The project also includes demolition of existing Buildings 311 and 307. The contract duration is 450 days from notice to proceed. The solicitation closing date is May 5th, 2022. Evaluation factors are technical approach, past performance, and price. The government intends to award without discussions. Interested parties must register in the System for Award Management. A pre-proposal conference will be held on March 31st, 2022 at the project site. Inquiries must be submitted in writing by the specified deadline.
View the file
Other files for this federal contract opportunity
Show all 40
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NOTES:
1. THE CONTRACTOR SHALL PROVIDE THE LIGHT FIXTURES WITH THE MOUNTING METHOD REQUIRED FOR THE CEILING SYSTEM SET FORTH ON THE ARCHITECTURAL DRAWINGS, SUCH AS, THE REFLECTED CEILING PLANS, AND ROOM FINISH SCHEDULE, ETC.
2. THE ACTUAL APERTURE DIMENSION OF ALL LIGHT FIXTURES PROVIDED SHALL BE PLUS OR MINUS 1/2 INCH ON THE NOMINAL VALUE INDICATED.
3. LIGHT FIXTURES SHALL NOT BE SUPPORTED FROM SUSPENDED CEILING SUPPORTS UNLESS ADDITIONAL CEILING FRAMING AND SUPPORTS ARE ADDED BY THE CONTRACTOR, TO KEEP CEILING RIGID.
4. CONNECTIONS TO RECESSED LIGHT FIXTURES SHALL BE MADE WITH 1/2" MINIMUM FLEXIBLE CONDUIT 4'-0" TO 6'-0" IN LENGTH FROM FIXTURE TO OUTLET BOX.
FEEDER SCHEDULE - COPPER
1N
MAXIMUM
OCPD
FEEDER
NUMBER
NUMBER
OF SETS PHASE(3/C)
NEUTRAL
EQUIPMENT
GROUND
CONDUIT
SIZE
15 / 20
1 12 12 3/4"
2N 25 / 30
10 10 3/4"
3N 35 / 40
8 10
4N 45 / 50
6 10
5N 60 / 70
4 8
6N
3 8
7N
2 8
8N
100 / 110 /
1 6
9N
1/0
1/0 6
10N
10 --
11N
11 --
12N
12 --
13N
13 --
14N
14 --
15N
15 --
16N
17N
4/0
4/0
18N
MAXIMUM
OCPD
FEEDER
NUMBER
NUMBER
OF SETS
CONDUIT
SIZE
2 250 1
19N
1/0
20N
1/0
21N
1/0
22N
2/0
23N
3 3/0
24N
4 4/0
25N
5 250
26N
6 350
27N
8 400
28N
10 500
29N
12 700
CONDUCTOR SIZE
PHASE(3/C)
NEUTRAL
EQUIPMENT
GROUND
CONDUCTOR SIZE
3/4"
1"
1-1/4"
3-1/2"
3"
3-1/2"
2-1/2"
3"
3"
3-1/2"
3"
3"
3-1/2"
3-1/2"
4"
3-1/2"
5"
1"
1-1/4"
1-1/2"
1-1/4"
1-1/2"
2/0
3/0
4/0
2/0
3/0
4/0
1-1/2"
2"
2"
2"
2"
2-1/2"
2-1/2"
2-1/2"
3"
3"
2"
2-1/2"
3"
3-1/2"
4"
3-1/2"
4"
3-1/2"
4"
3-1/2"
4"
3-1/2"
4"
4"
NOTES:
1. WHERE LOCATED OUTDOORS, DISCONNECT SWITCHES SHALL BE NEMA 4X RATED.
2. WHERE NOT SHOWN ON PLANS BUT INDICATED IN SCHEDULE, PROVIDE LOCAL DISCONNECT SWITCHES ADJACENT TO EQUIPMENT SERVED IN AN ACCESSIBLE LOCATION AS NECESSARY.
N
D
C
B
A
13 2456
D
C
B
A
13 2456
L a s t
P lo tt e d
F ile n a m e
©2020 AECOM Corporation
ISSUE/REVISION
SHEET NUMBER
SHEET TITLE
PROJECT NUMBER
REGISTRATION
CLIENT
ARCHITECT / ENGINEER
PROJECT
/1
/2
:1 :2
P
M
B
IM
/6
-M e d ic a l R e a d in e s s F a c ili ty W
I A
N G
/6
W
IA
N G
T
R U
A X
-M E
D -E v
.r v t
ELECTRICAL SCHEDULES
E-601
60580469
TRUAX FIELD - BUILDING 506
MADISON, WI
MEDICAL READINESS FACILITY
3110 MITCHELL STREET
MADISON, WI 53704
WISCONSIN AIR NATIONAL
GUARD - 115TH FIGHTER WING
277 W. NATIONWIDE BLVD.
COLUMBUS, OH 43215
AECOM
EQUIPMENT ELECTRICAL CONNECTION SCHEDULE
EQUIPMENT
DESIGNATION DESCRIPTION VOLTAGE PHASE LOAD
ACC1 DUCTLESS AIR COOLING
CONDENSER
208 V 1 2.04 kVA
B1 HOT WATER BOILER 208 V 1 0.20 kVA
B2 HOT WATER BOILER 208 V 1 0.20 kVA
CUH1 CABINET UNIT HEATER 277 V 1 0.28 kVA
EF1 EXHAUST FAN 277 V 1 0.28 kVA
EF3 277 V 1 0.28 kVA
HP1 DUCTLESS HEAT PUMP 208 V 1 1.87 kVA
HP2 DUCTLESS HEAT PUMP 208 V 1 1.87 kVA
HWP3 HOT WATER PUMP 208 V 1 0.00 kVA
HWP4 HOT WATER PUMP 208 V 1 0.00 kVA
RTU1 ROOF TOP UNIT 480 V 3 24.94 kVA
RTU2 ROOF TOP UNIT 480 V 3 22.45 kVA
RTU3 ROOF TOP UNIT 480 V 3 11.64 kVA
SF1 SUPPLY FAN 277 V 1 0.28 kVA
UH1 UNIT HEATER 277 V 1 0.10 kVA
UH7 480 V 3 24.94 kVA
LIGHTING FIXTURE SCHEDULE
FIXTURE
DESIGNATION VOLTAGE WATTAGE LAMP DESCRIPTION COMMENTS
A1 UNV 35 VA 32W/LED 2'-0" X 2'-0" RECESSED LED TROFFER WITH PRISMATIC ACRYLIC LENS. 3000 LUMENS
A2 UNV 28 VA LED 6" RECESSED LED CAN LIGHT. 3017 LUMENS
A3 UNV 28 VA LED 0'-4" FLUSH MOUNTED ADA COMPLIANT LED WITH INTEGRAL OCCUPANCY SENSOR, RECESSED FIXTURE, 9'-0" LENGTH.
3000 LUMENS or 750 LUMENS PER FOOT
A4 UNV 28 VA 30W/LED 0'-4" FLUSH MOUNTED ADA COMPLIANT LED WITH INTEGRAL OCCUPANCY SENSOR, RECESSED FIXTURE, 6'-0" LENGTH.
3800 LUMENS
MOUNT 9'-0" TO BOTTOM OF LUMINAIRE
A5 28 VA 30W/LED 0'-4" FLUSH MOUNTED ADA COMPLIANT LED WITH INTEGRAL OCCUPANCY SENSOR, PERMIETER LIGHT. 3000 LUMENS or 750
LUMENS PER FOOT
B1 UNV 22 VA 23W/LED 6" RECESSED LED CAN LIGHT WITH WALL WASHING LENS. 2486 LUMENS
B2 UNV 15 VA LED 4" CYLINDER PENDANT, WITH 0-10V DIMMING, SOFT DIFFUSED LENS. 1600 LUMENS. MOUNT 6'-0" AFF TO BOTTOM OF
FIXTURE.
B3 UNV 10 VA 60W/LED SAME AS B4 BUT IN A 6'-0" LENGTH. 2400 LUMENS OR 400 LUMENS PER FOOT, 4000K COLOR TEMP
B4 UNV 10 VA 40W/LED PENDANT DIRECT LED, ALUMINUM FRAME, SURFACE MOUNTED. 400 LUMENS PER FOOT
B5 UNV 18 VA 40W/LED SINGLE SHEET PET FELT MATERIAL CONSTRUCTION. 0-10V DIMMING. MOUNTED ON UNISTRUT ALIGNMENT. 4000K COLOR.
2'-0" LENGTH LED. 445 LUMENS PER FOOT.
DA UNV 103 VA 103W/LED 4'-0" INDUSTRIAL HIGH BAY LED FIXTURE. STEEL HOUSING WITH FROSTED LENS. WIDE DISTRIBUTION, 5000K COLOR
TEMPERATURE, INTEGRAL OCCUPANCY SENSOR, 0-10V DIMMING. 18,000 LUMENS
DD UNV 18 VA 18W/LED 4'-0" LINEAR SURFACE MOUNT LED FIXTURE WITH FROSTED LENS, 4000K COLOR TEMPERATURE, STANDARD DRIVER. 3200
LUMENS,
LE5 UNV 25 VA 18W/LED WALL MOUNTED LED AREA LIGHT WITH SINGLE LIGHT SQUARE, TYPE III DISTRIBUTION W/ SPILL CONTROL, CUSTOM FINISH
DETERMINED BY ARCHITECT. 2800 LUMENS
PROVIDE EACH FIXTURE WITH AN ADDITIONAL
REMOTE MOUNTED BODINE GTD BALLAST,
COORDINATE MTG HEIGHT WITH ARCH ELEVATION
SHEETS
U1 UNV 14 VA LED 0'-4" COVE UNDERCABINET LED, RECESSED FIXTURE. 300 LUMENS PER FOOT, MINIMUM, DIMMABLE.
W1 UNV 20 VA LED VANDAL RESISTANT EXTERIOR WALL PACK. 3400 LUMENS
WA UNV 24 VA 24W/LED SURFACE MOUNTED, POLYCARBONATE HOUSING, FROSTED POLYCARBONATE LENS, GASKETED OPENING, WET LOCATION
LISTED, 3500 K COLOR, 50.3"(L)X5.4:(W)X3.8"(D)
WB UNV 28 VA 28.2W/LED LED WALL MOUNTED STAIR LUMINAIRE, STEEL HOUSING, LINEAR FACETED REFRACTOR, INTEGRAL OCCUPANCY SENSOR, 3500K COLOR TEMPERATURE. 6.75"(L) X 4.75"(W) X 3.875(D). MOUNT AT 8'-0" ABOVE FLOOR. 3200 LUMENS
X1 UNV 7 VA 2W/LED PENDANT MOUNTED, A/C POWERED, POLYCARBONATE LED EXIT SIGN WITH RED LETTERS, SINGLE FACE, FIXTURE SHALL
BE FURNISHED WITH DIRECTIONAL CHEVRONS PER PLANS
X2 UNV 7 VA 2W/LED PENDANT MOUNTED, A/C POWER, POLYCARBONATE LED EXIT SIGN WITH RED LETTERS, DOUBLE FACE, FIXTURE SHALL BE
FURNISHED WITH DIRECTIONAL CHEVRONS PER PLANS
I/R DATE DESCRIPTION
1 10 JULY 2020 B-1 SUBMITTAL
2 13 OCT 2020 B-2 SUBMITTAL
3 14 MAY 2021 B-3 SUBMITTAL
4 20 JUNE 2022 ADDENDUM 1
| Sheets |
| E-601 - ELECTRICAL SCHEDULES |