This solicitation requests proposals to construct a Medical Readiness Facility. The 115th Fighter Wing at Dane County Regional Airport - Truax Field in Madison, Wisconsin seeks to award a firm fixed-price contract for all labor, materials, equipment, and supervision necessary to build an 18,650 square foot, two-story facility including administrative space and storage areas. The project scope includes site work, erection of precast concrete panels, and new mechanical, electrical and technology systems. Proposals are due May 5th, 2022 with award planned for shortly thereafter and a 450 day period of performance. The contract is unrestricted but encourages small business participation. Brand name justification is provided for several specified systems.
View the file
Other files for this federal contract opportunity
Show all 40
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT MANUAL
BUILDING 506
MEDICAL READINESS FACILITY
B-3 SUBMITTAL
115th FIGHTER WING
TRUAX FIELD
AIR NATIONAL GUARD BASE
MADISON, WISCONSIN
W9133L-16-D-0009 W912J219F6007
PROJECT No. XGFG139001
07-08-2021
VOLUME 1 OF 2
AECOM
277 WEST NATIONWIDE BLVD., 5TH FLOOR, COLUMBUS, OHIO 43215-2566
T 614-464-4500 F 614-464-0588
Medical Readiness Facility 115th Fighter Wing Truax Field - Building 506, Madison, Wisconsin
Contract No. W9133L-16-D-0009 Delivery Order No. W912J2-19-F-6007
AECOM No. 60613250
B-3 Submittal
Section TOC Table of Contents
Project No. XGFG139001
MEDICAL READINESS FACILITY
July 8, 2021
TABLE OF CONTENTS
VOLUME 1
DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS
SECTION 00 0107 - SEALS PAGE
SECTION 00 3119 - EXISTING CONDITION INFORMATION
SECTION 00 3126 - EXISTING HAZARDOUS MATERIAL INFORMATION
Attachments
Asbestos Analytical Report – Building 307 Asbestos Analytical Report – Building 311
SECTION 00 3132 - GEOTECHNICAL DATA
Attachments
Geotechnical Engineering Report Addendum to Project Geotechnical Engineering Report
SECTION 00 4323 - ALTERNATES FORM
DIVISION 01 - GENERAL REQUIREMENTS
SECTION 01 1000 – SUMMARY
Attachment
Contractor's Security Briefing
SECTION 01 2300 - ALTERNATES
SECTION 01 2500 - SUBSTITUTION PROCEDURES
SECTION 01 2600 - CONTRACT MODIFICATION PROCEDURES
SECTION 01 3100 - PROJECT MANAGEMENT AND COORDINATION
SECTION 01 3200 - CONSTRUCTION PROGRESS DOCUMENTATION
SECTION 01 3233 - PHOTOGRAPHIC DOCUMENTATION
SECTION 01 3300 - SUBMITTAL PROCEDURES
Attachment
Submittal Report
SECTION 01 3329 – SUSTAINABILITY REPORTING
SECTION 01 4000 - QUALITY REQUIREMENTS
SECTION 01 4200 - REFERENCES
SECTION 01 5000 - TEMPORARY FACILITIES AND CONTROLS
SECTION 01 6000 - PRODUCT REQUIREMENTS
SECTION 01 7300 - EXECUTION
SECTION 01 7419 - CONSTRUCTION WASTE MANAGEMENT AND DISPOSAL
Attachments Form CWM-1 Form CWM-2 Form CWM-3 Form CWM-4 Form CWM-5 Form CWM-6 Form CWM-7 Form CWM-8
SECTION 01 7700 - CLOSEOUT PROCEDURES
SECTION 01 7823 - OPERATION AND MAINTENANCE DATA
SECTION 01 7839 - PROJECT RECORD DOCUMENTS
SECTION 01 7900 - DEMONSTRATION AND TRAINING
SECTION 01 9113 - GENERAL COMMISSIONING REQUIREMENTS
Contract No. W9133L-16-D-0009 Delivery Order No. W912J2-19-F-6007
AECOM No. 60613250
B-3 Submittal
Section TOC Table of Contents
Project No. XGFG139001
MEDICAL READINESS FACILITY
July 8, 2021
DIVISION 02 - EXISTING CONDITIONS
SECTION 02 4116 - STRUCTURE DEMOLITION
SECTION 08 8200 - ASBESTOS REMEDIATION
DIVISION 03 - CONCRETE
SECTION 03 3000 - CAST-IN-PLACE CONCRETE
SECTION 03 4100 - PRECAST STRUCTURAL CONCRETE
DIVISION 04 - MASONRY
SECTION 04 2000 - UNIT MASONRY
DIVISION 05 - METALS
SECTION 05 1200 - STRUCTURAL STEEL FRAMING
SECTION 05 2100 - STEEL JOIST FRAMING
SECTION 05 3100 - STEEL DECKING
SECTION 05 4000 - COLD-FORMED METAL FRAMING
SECTION 05 5000 - METAL FABRICATIONS
SECTION 05 5113 - METAL PAN STAIRS
SECTION 05 5213 - PIPE AND TUBE RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
SECTION 06 0513 - DECORATIVE PLASTIC LAMINATE FINISHES
SECTION 06 1000 - ROUGH CARPENTRY
SECTION 06 1600 - SHEATHING
SECTION 06 4116 - PLASTIC-LAMINATE-CLAD ARCHITECTURAL CABINETS
SECTION 06 4219 - PLASTIC-LAMINATE-FACED WOOD PANELING
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
SECTION 07 1326 - SELF-ADHERING SHEET WATERPROOFING
SECTION 07 1900 - WATER REPELLENTS
SECTION 07 2100 - THERMAL INSULATION
SECTION 07 2500 - WEATHER BARRIERS
SECTION 07 2600 - VAPOR RETARDERS
SECTION 07 4113.16 - STANDING SEAM METAL ROOF PANELS
SECTION 07 4210 - METAL WALL PANEL SUPPORT
SECTION 07 4213.13 - METAL WALL PANEL
SECTION 07 4293 - SOFFIT PANELS
SECTION 07 5323 - EPDM ROOFING
SECTION 07 6200 - SHEET METAL FLASHING AND TRIM
SECTION 07 7100 - ROOF SPECIALTIES
SECTION 07 7200 - ROOF ACCESSORIES
SECTION 07 7253 - SNOW GUARDS
SECTION 07 8413 - PENETRATION FIRESTOPPING
SECTION 07 8443 - JOINT FIRESTOPPING
SECTION 07 9100 - PREFORMED JOINT SEALS
SECTION 07 9200 - JOINT SEALANTS
DIVISION 08 - OPENINGS
SECTION 08 1113 - HOLLOW METAL DOORS AND FRAMES
SECTION 08 1416 - FLUSH WOOD DOORS
SECTION 08 3113 - ACCESS DOORS AND FRAMES
SECTION 08 3323 - OVERHEAD COILING DOORS
SECTION 08 3400 - SLIDING OFFICE DOORS
SECTION 08 4113 - ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS
Contract No. W9133L-16-D-0009 Delivery Order No. W912J2-19-F-6007
AECOM No. 60613250
B-3 Submittal
Section TOC Table of Contents
Project No. XGFG139001
MEDICAL READINESS FACILITY
July 8, 2021
SECTION 08 6250 - TUBULAR DAYLIGHTING SYSTEM
SECTION 08 7100 - DOOR HARDWARE
SECTION 08 8000 - GLAZING
SECTION 08 8813 - FIRE-RESISTANT GLAZING
SECTION 08 9119 - FIXED LOUVERS
DIVISION 09 - FINISHES
SECTION 09 2116.23 - GYPSUM BOARD SHAFT WALL ASSEMBLIES
SECTION 09 2216 - NON-STRUCTURAL METAL FRAMING
SECTION 09 2900 - GYPSUM BOARD
SECTION 09 3013 - CERAMIC TILING
SECTION 09 5113 - ACOUSTICAL PANEL CEILINGS
SECTION 09 6513 - RESILIENT BASE AND ACCESSORIES
SECTION 09 6516 - RESILIENT SHEET FLOORING
SECTION 09 6519 - RESILIENT TILE FLOORING
SECTION 09 6623 - RESINOUS MATRIX TERRAZZO FLOORING
SECTION 09 6813 - TILE CARPETING
SECTION 09 9106 - FLOOR SEALER - SC1
SECTION 09 9113 - EXTERIOR PAINTING
SECTION 09 9123 - INTERIOR PAINTING
SECTION 09 9600 - HIGH-PERFORMANCE COATINGS
DIVISION 10 - SPECIALTIES
SECTION 10 1423.16 - ROOM IDENTIFICATION PANEL SIGNAGE
SECTION 10 2113.13 - METAL TOILET COMPARTMENTS
SECTION 10 2123 - CUBICLE CURTAINS AND TRACK
SECTION 10 2239 - FOLDING PANEL PARTITIONS
SECTION 10 2800 - TOILET AND BATH ACCESSORIES
SECTION 10 4413 - FIRE PROTECTION CABINETS
SECTION 10 4416 - FIRE EXTINGUISHERS
SECTION 10 5123 - PLASTIC-LAMINATE-CLAD LOCKERS
DIVISION 11 - EQUIPMENT
SECTION 11 2429 - FALL PROTECTION EQUIPMENT
DIVISION 12 - FURNISHINGS
SECTION 12 2413 - ROLLER WINDOW SHADES
SECTION 12 3661.16 - SOLID SURFACE MATERIALS
SECTION 12 4816 - ENTRANCE FLOOR GRILLES
DIVISION 13 - SPECIAL CONSTRUCTION
NOT APPLICABLE
DIVISION 14 - CONVEYING EQUIPMENT
SECTION 14 2123.16 - MACHINE-ROOM-LESS ELECTRIC TRACTION PASSENGER ELEVATORS
DIVISION 21 - FIRE SUPPRESSION
SECTION 21 0517 - SLEEVES AND SLEEVE SEALS FOR FIRE-SUPPRESSION PIPING
SECTION 21 0523 - GENERAL-DUTY VALVES FOR FIRE PROTECTION PIPING
SECTION 21 0529 - HANGERS AND SUPPORTS FOR FIRE SUPRESSION PIPING AND EQUIPMENT
SECTION 21 0553 - IDENTIFICATION FOR FIRE-SUPPRESSION PIPING AND EQUIPMENT
SECTION 21 0800 - COMMISSIONING OF FIRE SUPPRESSION
SECTION 21 1100 - FACILITY FIRE-SUPPRESSION WATER-SERVICE PIPING
SECTION 21 1116 - FACILITY FIRE HYDRANTS
Contract No. W9133L-16-D-0009 Delivery Order No. W912J2-19-F-6007
AECOM No. 60613250
B-3 Submittal
Section TOC Table of Contents
Project No. XGFG139001
MEDICAL READINESS FACILITY
July 8, 2021
SECTION 21 1119 - FIRE DEPARTMENT CONNECTIONS
SECTION 21 1313 - WET-PIPE SPRINKLER SYSTEMS
VOLUME 2
DIVISION 22 - PLUMBING
SECTION 22 0501 - COMMON WORK RESULTS FOR PLUMBING
SECTION 22 0507 - EXCAVATION AND BACKFILL
SECTION 22 0513 - COMMON MOTOR REQUIREMENTS FOR PLUMBING EQUIPMENT
SECTION 22 0519 - METERS AND GAUGES FOR PLUMBING PIPING
SECTION 22 0523 - GENERAL-DUTY VALVES FOR PLUMBING PIPING
SECTION 22 0529 - HANGERS AND SUPPORTS FOR PLUMBING PIPING AND EQUIPMENT
SECTION 22 0548 - VIBRATION CONTROLS FOR PLUMBING PIPING AND EQUIPMENT
SECTION 22 0553 - IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT
SECTION 22 0561 - PREPARATION OF PLUMBING SYSTEMS
SECTION 22 0593 - PLUMBING SYSTEMS TESTING, ADJUSTING, AND BALANCING
SECTION 22 0700 - PLUMBING INSULATION
SECTION 22 1116 - DOMESTIC WATER PIPING
SECTION 22 1316 - BUILDING SANITARY, STORM DRAINAGE, AND ACID WASTE
SECTION 22 1331 - ELEVATOR SUMP PUMP
SECTION 22 2000 - FACILITY NATURAL GAS SYSTEM
SECTION 22 3100 - DOMESTIC WATER SOFTENERS
SECTION 22 3300 - DOMESTIC GAS WATER HEATERS
SECTION 22 4000 - PLUMBING FIXTURES
DIVISION 23 - HEATING, VENTILATING, AND AIR-CONDITIONING (HVAC)
SECTION 23 0500 - GENERAL MECHANICAL REQUIREMENTS
SECTION 23 0519 - METERS AND GAUGES FOR HVAC PIPING
SECTION 23 0523 - VALVES FOR HVAC PIPING
SECTION 23 0529 - HANGERS, SLEEVES, AND SUPPORTS
SECTION 23 0548 - VIBRATION CONTROL FOR HVAC PIPING AND EQUIPMENT
SECTION 23 0553 - IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT
SECTION 23 0593 - MECHANICAL SYSTEMS TESTING, ADJUSTING, AND BALANCING
SECTION 23 0700 - HVAC INSULATION
SECTION 23 0800 - MECHANICAL SYSTEMS COMMISSIONING REQUIREMENTS
SECTION 23 0900 - HVAC INSTRUMENTATION AND CONTROL
SECTION 23 2113 - HYDRONIC PIPING
SECTION 23 2116 - HYDRONIC SPECIALTIES
SECTION 23 2123 - HYDRONIC PUMPS
SECTION 23 2300 - REFRIGERANT PIPING
SECTION 23 2500 - HVAC WATER TREATMENT
SECTION 23 3000 - DUCTWORK AND ACCESSORIES
SECTION 23 3400 - EXHAUST AND VENTILATING FANS
SECTION 23 3616 - TERMINAL BOXES - DDC CONTROL
SECTION 23 5216 - CONDENSING BOILERS
SECTION 23 7415 - PACKAGED GAS HEATING AND ELECTRIC COOLING UNITS
SECTION 23 8126 - DUCTLESS SPLIT SYSTEM UNITS
SECTION 23 8223 - CABINET-TYPE UNIT HEATERS
SECTION 23 8224 - PROPELLER-TYPE UNIT HEATERS
SECTION 23 8236 - PERIMETER HEAT
DIVISION 25 - INTEGRATED AUTOMATION
NOT APPLICABLE
Contract No. W9133L-16-D-0009 Delivery Order No. W912J2-19-F-6007
AECOM No. 60613250
B-3 Submittal
Section TOC Table of Contents
Project No. XGFG139001
MEDICAL READINESS FACILITY
July 8, 2021
DIVISION 26 - ELECTRICAL
SECTION 26 0505 - BASIC ELECTRICAL REQUIREMENTS
SECTION 26 0519 - LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
SECTION 26 0523 - CONTROL-VOLTAGE ELECTRICAL POWER CABLES
SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
SECTION 26 0529 - HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
SECTION 26 0533 - RACEWAYS AND BOXES FOR ELECTRICAL SYSTEMS
SECTION 26 0543 - UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS
SECTION 26 0544 - SLEEVES AND SLEEVE SEALS FOR ELECTRICAL RACEWAYS AND CABLING
SECTION 26 0553 - IDENTIFICATION FOR ELECTRICAL SYSTEMS
SECTION 26 0573.13 - SHORT-CIRCUIT STUDIES
SECTION 26 0573.16 - COORDINATION STUDIES
SECTION 26 0913 - ELECTRICAL POWER MONITORING AND CONTROL
SECTION 26 0923 - LIGHTING CONTROL DEVICES
SECTION 26 0936 - MODULAR DIMMING CONTROLS
SECTION 26 2213 - LOW-VOLTAGE DISTRIBUTION TRANSFORMERS
SECTION 26 2413 - SWITCHBOARDS
SECTION 26 2416 - PANELBOARDS
SECTION 26 2726 - WIRING DEVICES
SECTION 26 2816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS
SECTION 26 3323.11 - CENTRAL BATTERY EQUIPMENT FOR EMERGENCY LIGHTING
SECTION 26 3600 - TRANSFER SWITCHES
SECTION 26 4113 - LIGHTNING PROTECTION FOR STRUCTURES
SECTION 26 4313 - SURGE PROTECTION FOR LOW-VOLTAGE ELECTRICAL POWER CIRCUITS
SECTION 26 5119 - LED INTERIOR LIGHTING
SECTION 26 5213 - EMERGENCY AND EXIT LIGHTING
SECTION 26 5619 - LED EXTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
SECTION 27 0526 - GROUNDING AND BONDING FOR COMMUNICATIONS SYSTEMS
SECTION 27 0528 - PATHWAYS FOR COMMUNICATIONS SYSTEMS
SECTION 27 0529 - HANGERS AND SUPPORTS FOR COMMUNICATIONS SYSTEMS
SECTION 27 0536 - CABLE TRAYS FOR COMMUNICATIONS SYSTEMS
SECTION 27 0543 - UNDERGROUND PATHWAYS AND STRUCTURES FOR COMMUNICATION SYSTEMS
SECTION 27 0544 - SLEEVES AND SLEEVE SEALS FOR COMMUNICATIONS PATHWAYS AND CABLING
SECTION 27 0553 - IDENTIFICATION FOR COMMUNICATIONS SYSTEMS
SECTION 27 1100 - COMMUNICATIONS EQUIPMENT ROOM FITTINGS
SECTION 27 1116 - COMMUNICATIONS RACKS, FRAMES, AND ENCLOSURES
SECTION 27 1313 - COMMUNICATIONS COPPER BACKBONE CABLING
SECTION 27 1323 - COMMUNICATIONS OPTICAL FIBER BACKBONE CABLING
SECTION 27 1333 - COMMUNICATIONS COAXIAL BACKBONE CABLING
SECTION 27 1513 - COMMUNICATIONS COPPER HORIZONTAL CABLING
SECTION 27 1523 - COMMUNICATIONS OPTICAL FIBER HORIZONTAL CABLING
SECTION 27 1533 - COMMUNICATIONS COAXIAL HORIZONTAL CABLING
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
SECTION 28 1300 - ACCESS CONTROL SOFTWARE AND DATABASE MANAGEMENT
SECTION 28 1500 - ACCESS CONTROL HARDWARE DEVICES
SECTION 28 2000 - VIDEO SURVEILLANCE
SECTION 28 3100 - INTRUSION DETECTION
SECTION 28 4621.11 - ADDRESSABLE FIRE-ALARM/VOICE EVAC-MASS NOTIFICATION SYSTEMS
SECTION 28 4700 - MASS NOTIFICATION SYSTEMS
DIVISION 31 - EARTHWORK
Contract No. W9133L-16-D-0009 Delivery Order No. W912J2-19-F-6007
AECOM No. 60613250
B-3 Submittal
Section TOC Table of Contents
Project No. XGFG139001
MEDICAL READINESS FACILITY
July 8, 2021
SECTION 31 2000 - EARTH MOVING
SECTION 31 6613 - AGGREGATE PIERS
DIVISION 32 - EXTERIOR IMPROVEMENTS
SECTION 32 1443 - POROUS UNIT PAVING
DIVISIONS 33 - 48
NOT APPLICABLE
END OF TABLE OF CONTENTS
Medical Readiness Facility, 115th Fighter Wing Truax Field – Building 506, Madison, Wisconsin
P.O. No. W9133L-16-D-0009 Order No. W912J219F6007
AECOM No. 60613250
B-3 Submittal
Section 00 0107
SEALS PAGE
Project No. HTUV152005
MEDICAL REDINESS FACILITY
July 8, 2021
DOCUMENT 00 0107
SEALS PAGE
PART 1 - GENERAL
1.01 DESIGN PROFESSIONALS OF RECORD
A. Architect B. Civil Engineer:
C. Structural Engineer: D. Fire-Protection Engineer:
E. Plumbing Engineer: F. HVAC Engineer:
Medical Readiness Facility, 115th Fighter Wing Truax Field – Building 506, Madison, Wisconsin
P.O. No. W9133L-16-D-0009 Order No. W912J219F6007
AECOM No. 60613250
B-3 Submittal
Section 00 0107
SEALS PAGE
Project No. HTUV152005
MEDICAL REDINESS FACILITY
July 8, 2021
G. Electrical Engineer:
END OF DOCUMENT
Contract No. W9133L-16-D-0009 Delivery Order No. W912J2-19-F-6007
AECOM No. 60613250
B-3 Submittal
Section 00 3119
EXISTING CONDITION INFORMATION
Project No. XGFG139001
MEDICAL READINESS FACILITY
July 8, 2021
DOCUMENT 003119
EXISTING CONDITION INFORMATION
PART 1 - GENERAL
1.01 EXISTING CONDITION INFORMATION
A. This Document with its referenced attachments is part of the Procurement and Contracting Requirements for Project. They provide Owner's information for Bidders' convenience and are intended to supplement rather than serve in lieu of the Bidders' own investigations. They are made available for Bidders' convenience and information, but are not a warranty of existing conditions. This Document and its attachments are not part of the Contract Documents.
B. Existing specifications and submittals that include information on existing conditions including previous construction at Project site are available for viewing at the office of Government.
C. Survey information that includes information on existing conditions is available for viewing as part of Drawings.
D. Related Requirements:
1. Document 00 3126 "Existing Hazardous Material Information" for hazardous materials reports that are made available to bidders.
2. Document 00 3132 "Geotechnical Data" for reports and soil-boring data from geotechnical investigations that are made available to bidders.
Contract No. W9133L-16-D-0009 Delivery Order No. W912J2-19-F-6007
AECOM No. 60613250
B-3 Submittal
Section 00 3126
EXISTING HAZARDOUS MATERIAL INFORMATION
Project No. XGFG139001
MEDICAL READINESS FACILITY
July 8, 2021
DOCUMENT 00 3126
EXISTING HAZARDOUS MATERIAL INFORMATION
PART 1 - GENERAL
1.01 EXISTING HAZARDOUS MATERIAL INFORMATION
A. This Document with its referenced attachments is part of the Procurement and Contracting Requirements for Project. They provide Owner's information for Bidders' convenience and are intended to supplement rather than serve in lieu of Bidders' own investigations. They are made available for Bidders' convenience and information, but are not a warranty of existing conditions. This Document and its attachments are not part of the Contract Documents.
B. An existing asbestos report for both Buildings 307 and 311, prepared by Eurofins, dated November 25, 2019, is available for viewing on Project Web site as appended to this Document.
C. Related Requirements:
1. Document 00 3119 "Existing Condition Information" for information about existing conditions that is made available to bidders.
2. Document 00 3132 "Geotechnical Data" for reports and soil-boring data from geotechnical investigations that are made available to bidders.
3. Section 02 4119 "Selective Demolition" for notification requirements if materials suspected of containing hazardous materials are encountered.
END OF DOCUMENT 003126
November 25, 2019
AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
CLIENT PROJECT: WI ANG - Medical Readiness Center, Building 307, 60613250
CEI LAB CODE: B198430
Dear Customer:
Enclosed are asbestos analysis results for PLM Bulk samples received at our laboratory on November 18, 2019. The samples were analyzed for asbestos using polarizing light microscopy (PLM) per the EPA 600 Method.
Sample results containing >1% asbestos are considered asbestos-containing materials (ACMs) per EPA regulatory requirements. The detection limit for the EPA 600 Method is <1% asbestos by weight as determined by visual estimation.
Thank you for your business and we look forward to continuing good relations.
730 SE Maynard Road • Cary, NC 27511 • 919.481.1413
Tianbao Bai, Ph.D., CIH Laboratory Director
Kind Regards, ASBESTOS ANALYTICAL REPORT
By: Polarized Light Microscopy
Prepared for
AECOM Columbus
CLIENT PROJECT:
LAB CODE:
TEST METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020
REPORT DATE:
TOTAL SAMPLES ANALYZED:
# SAMPLES >1% ASBESTOS:
WI ANG - Medical Readiness Center, Building 307, 60613250
B198430
11/25/19
Asbestos Report Summary By: POLARIZING LIGHT MICROSCOPY
PROJECT: WI ANG - Medical Readiness Center, Building 307, 60613250
LAB CODE: B198430
Client ID Lab ID Color Sample Description
ASBESTOS
%Layer
METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020
B127117 Black Plastic Trim None Detected01A
B127118 Yellow,Tan Mastic None Detected01B
B127119 Beige Floor Tile None Detected2A
Layer 1 B127120 Yellow Mastic None Detected2B
Layer 2 B127120 Gray Leveling Compound None Detected
B127121 White Tile None Detected3
B127122 Cream Tile None Detected4
B127123 Brown Grout None Detected5
B127124 White Grout None Detected6
B127125 Yellow Insulation None Detected7
B127126 White Drop Ceiling None Detected8
B127127 White Lightly Textured Dimpled Ceiling Tile
None Detected9
Layer 1 B127128 White Heavy Dimpled / Textured Dimpled Ceiling Tile
None Detected10
Layer 2 B127128 White Heavy Dimpled / Textured Dimpled Ceiling Tile
None Detected
B127129 Blue Paint None Detected11
B127130 Brown Plastic Trim None Detected12A
B127131 Yellow Mastic None Detected12B
B127132 Gray Carpet None Detected13A
B127133 Yellow Mastic None Detected13B
B127134 White Paint None Detected14
B127135 White Caulk None Detected15A
B127136 White Paint None Detected15B
B127137 White Caulk None Detected16
B127138 White Drywall None Detected17A
B127139 Cream Paint None Detected17B
B127140 Yellow Spray Foam None Detected18
B127141 Black Foam Pipe Wrap None Detected19A
B127142 Black Foam Pipe Wrap None Detected19B
B127143 Black Foam Pipe Wrap None Detected19C
PROJECT: WI ANG - Medical Readiness Center, Building 307, 60613250
LAB CODE: B198430
Client ID Lab ID Color Sample Description
ASBESTOS
%Layer
METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020
B127144 Yellow Pipe Wrap None Detected20A
B127145 Yellow Pipe Wrap None Detected20B
B127146 Yellow Pipe Wrap None Detected20C
B127147 Brown Putty None Detected21
B127148 Brown Older Pipe Wrap None Detected22A
B127149 Brown Older Pipe Wrap None Detected22B
B127150 Brown Older Pipe Wrap None Detected22C
B127151 Black Door Weather Stripping None Detected23
B127152 Black Twisted On Pipe Wrap None Detected24A
B127153 Black Twisted On Pipe Wrap None Detected24B
B127154 Black Twisted On Pipe Wrap None Detected24C
B127155 Clear Sealant None Detected25
B127156 Cream Exterior Paint None Detected26
B127157 White Caulk None Detected27
B127158 White Caulk None Detected28
B127159 White Sealant None Detected29
B127160 White Sealant None Detected30
B127161A Gray Tile None Detected31
B127161B Tan Mastic None Detected
B127162A Gray Tile None Detected32
B127162B Tan Mastic None Detected
ASBESTOS BULK ANALYSIS
Lab Code: B198430 Date Received: 11-18-19 Date Analyzed: 11-22-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 307, 60613250
Fibrous
Black Plastic Trim01A
B127117 Homogeneous
Non-fibrous Tightly Bound
100% Vinyl None Detected
Yellow,Tan Mastic01B
B127118 Homogeneous
Non-fibrous Bound
100% Mastic None Detected
Beige Floor Tile2A
B127119 Homogeneous
Non-fibrous Tightly Bound
100% Vinyl None Detected
Yellow 2B
B127120
Homogeneous
Non-fibrous Bound
100% Mastic None Detected Layer 1
Mastic
Gray Leveling Compound
B127120 10%Heterogeneous
Non-fibrous Bound
100%Cellulose Binder None DetectedLayer 2
White Tile3
B127121 Homogeneous
Non-fibrous Tightly Bound
60% 40%
Silicates Binder
None Detected
Cream Tile4
B127122 Homogeneous
Non-fibrous Tightly Bound
60% 40%
Silicates Binder
None Detected
Lab Code: B198430 Date Received: 11-18-19 Date Analyzed: 11-22-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 307, 60613250
Fibrous
Brown Grout5
B127123 Homogeneous
Non-fibrous Bound
75% 25%
Silicates Binder
None Detected
White Grout6
B127124 Homogeneous
Non-fibrous Bound
75% 25%
Silicates Binder
None Detected
Yellow Insulation7
B127125 100%Homogeneous
Fibrous Loose
Fiberglass None Detected
White Drop Ceiling8
B127126 15%Heterogeneous
Fibrous Bound
80% 5% <1%
Cellulose Gypsum Paint Vermiculite
None Detected
White Lightly Textured Dimpled Ceiling Tile
B127127
40% 25%
Heterogeneous
Fibrous Loosely Bound
30% 5%
Cellulose Fiberglass
Perlite Paint
None Detected
White
B127128
40% 25%
Heterogeneous
Fibrous Loosely Bound
30% 5%
Cellulose Fiberglass
Perlite Paint
None Detected Layer 1
Heavy Dimpled / Textured Dimpled Ceiling Tile
White Heavy Dimpled / Textured Dimpled Ceiling Tile
B127128 15%Heterogeneous
Fibrous Loosely Bound
85%Cellulose Gypsum None DetectedLayer 2
Lab Code: B198430 Date Received: 11-18-19 Date Analyzed: 11-22-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 307, 60613250
Fibrous
Blue Paint11
B127129 Homogeneous
Non-fibrous Bound
100% Paint None Detected
Brown Plastic Trim12A
B127130 Homogeneous
Non-fibrous Tightly Bound
100% Vinyl None Detected
Yellow Mastic12B
B127131 Homogeneous
Non-fibrous Bound
100% Mastic None Detected
Gray Carpet13A
B127132 100%Homogeneous
Fibrous Bound
Synthetic Fiber None Detected
Yellow Mastic13B
B127133 Homogeneous
Non-fibrous Bound
100% Mastic None Detected
White Paint14
B127134 Homogeneous
Non-fibrous Bound
100% Paint None Detected
White Caulk15A
B127135 Homogeneous
Non-fibrous Bound
100% Caulk None Detected
Lab Code: B198430 Date Received: 11-18-19 Date Analyzed: 11-22-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 307, 60613250
Fibrous
White Paint15B
B127136 Homogeneous
Non-fibrous Bound
100% Paint None Detected
White Caulk16
B127137 Heterogeneous
Non-fibrous Bound
95% 5%
Caulk Paint
None Detected
White Drywall17A
B127138 15%Heterogeneous
Fibrous Bound
85%Cellulose Gypsum None Detected
Cream Paint17B
B127139 Homogeneous
Non-fibrous Bound
100% Paint None Detected
Yellow Spray Foam18
B127140 Homogeneous
Non-fibrous Bound
100% Foam None Detected
Black Foam Pipe Wrap19A
B127141 Homogeneous
Non-fibrous Bound
100% Foam None Detected
Black Foam Pipe Wrap19B
B127142 Homogeneous
Non-fibrous Bound
100% Foam None Detected
Lab Code: B198430 Date Received: 11-18-19 Date Analyzed: 11-22-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 307, 60613250
Fibrous
Black Foam Pipe Wrap19C
B127143 Homogeneous
Non-fibrous Bound
100% Foam None Detected
Yellow Pipe Wrap20A
B127144 10% 80%
Heterogeneous
Fibrous Bound
10%Cellulose Fiberglass
Metal Foil None Detected
Yellow Pipe Wrap20B
B127145 10% 80%
Heterogeneous
Fibrous Bound
10%Cellulose Fiberglass
Metal Foil None Detected
Yellow Pipe Wrap20C
B127146 10% 80%
Heterogeneous
Fibrous Bound
10%Cellulose Fiberglass
Metal Foil None Detected
Brown Putty21
B127147 Homogeneous
Non-fibrous Bound
100% Mastic None Detected
Brown Older Pipe Wrap22A
B127148 100%Homogeneous
Non-fibrous Loose
Fiberglass None Detected
Brown Older Pipe Wrap22B
B127149 100%Homogeneous
Non-fibrous Loose
Fiberglass None Detected
Lab Code: B198430 Date Received: 11-18-19 Date Analyzed: 11-22-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 307, 60613250
Fibrous
Brown Older Pipe Wrap22C
B127150 100%Homogeneous
Non-fibrous Loose
Fiberglass None Detected
Black Door Weather Stripping23
B127151 Homogeneous
Non-fibrous Bound
100% Caulk None Detected
Black Twisted On Pipe Wrap24A
B127152 Homogeneous
Non-fibrous Bound
100% Foam None Detected
Black Twisted On Pipe Wrap24B
B127153 Homogeneous
Non-fibrous Bound
100% Foam None Detected
Black Twisted On Pipe Wrap24C
B127154 Homogeneous
Non-fibrous Bound
100% Foam None Detected
Clear Sealant25
B127155 Homogeneous
Non-fibrous Bound
100% Caulk None Detected
Cream Exterior Paint26
B127156 Homogeneous
Non-fibrous Bound
100% Paint None Detected
Lab Code: B198430 Date Received: 11-18-19 Date Analyzed: 11-22-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 307, 60613250
Fibrous
White Caulk27
B127157 Homogeneous
Non-fibrous Bound
100% Caulk None Detected
White Caulk28
B127158 Homogeneous
Non-fibrous Bound
100% Caulk None Detected
White Sealant29
B127159 Homogeneous
Non-fibrous Bound
100% Caulk None Detected
White Sealant30
B127160 Homogeneous
Non-fibrous Bound
100% Caulk None Detected
Gray Tile31
B127161A 5%Homogeneous
Fibrous Bound
95%Cellulose Vinyl None Detected
Tan MasticB127161B Homogeneous
Non-fibrous Bound
100% Mastic None Detected
Gray Tile32
B127162A 5%Homogeneous
Fibrous Bound
95%Cellulose Vinyl None Detected
Lab Code: B198430 Date Received: 11-18-19 Date Analyzed: 11-22-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 307, 60613250
Fibrous
Tan MasticB127162B Homogeneous
Non-fibrous Bound
100% Mastic None Detected
LEGEND: Non-Anth = Non-Asbestiform Anthophyllite Non-Trem = Non-Asbestiform Tremolite Calc Carb = Calcium Carbonate
METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020
REPORTING LIMIT: <1% by visual estimation
REPORTING LIMIT FOR POINT COUNTS: 0.25% by 400 Points or 0.1% by 1,000 Points
REGULATORY LIMIT: >1% by weight
Due to the limitations of the EPA 600 method, nonfriable organically bound materials (NOBs) such as vinyl floor tiles can be difficult to analyze via polarized light microscopy (PLM). EPA recommends that all NOBs analyzed by PLM, and found not to contain asbestos, be further analyzed by Transmission Electron Microscopy (TEM). Please note that PLM analysis of dust and soil samples for asbestos is not covered under NVLAP accreditation. Estimated measurement of uncertainty is available on request.
This report relates only to the samples tested or analyzed and may not be reproduced, except in full, without written approval by Eurofins CEI. Eurofins CEI makes no warranty representation regarding the accuracy of client submitted information in preparing and presenting analytical results.
Interpretation of the analytical results is the sole responsibility of the client. Samples were received in acceptable condition unless otherwise noted. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. Government.
Information provided by customer includes customer sample ID and sample description.
ANALYST: APPROVED BY:
Tianbao Bai, Ph.D., CIH
Ryan Steele
November 25, 2019
AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
CLIENT PROJECT: WI ANG - Medical Readiness Center, Building 311, 60613250
CEI LAB CODE: B198450
Dear Customer:
Enclosed are asbestos analysis results for PLM Bulk samples received at our laboratory on November 18, 2019. The samples were analyzed for asbestos using polarizing light microscopy (PLM) per the EPA 600 Method.
Sample results containing >1% asbestos are considered asbestos-containing materials (ACMs) per EPA regulatory requirements. The detection limit for the EPA 600 Method is <1% asbestos by weight as determined by visual estimation.
Thank you for your business and we look forward to continuing good relations.
730 SE Maynard Road • Cary, NC 27511 • 919.481.1413
Tianbao Bai, Ph.D., CIH
Kind Regards, ASBESTOS ANALYTICAL REPORT
By: Polarized Light Microscopy
Prepared for
AECOM Columbus
CLIENT PROJECT:
LAB CODE:
TEST METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020
REPORT DATE:
TOTAL SAMPLES ANALYZED:
# SAMPLES >1% ASBESTOS:
WI ANG - Medical Readiness Center, Building 311, 60613250
B198450
11/25/19
PROJECT: WI ANG - Medical Readiness Center, Building 311, 60613250
LAB CODE: B198450
Client ID Lab ID Color Sample Description
ASBESTOS
%Layer
METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020
B127935 Yellow,Black Mastic Chrysotile1 3% B127936 White,Black Mastic None Detected2
B127937 Gray,Tan Drywall None Detected3
B127938 Yellow Insulation None Detected4
B127939 Yellow Pipe Insulation None Detected5a
B127940 Yellow Pipe Insulation None Detected5b
B127941 Yellow Pipe Insulation None Detected5c
B127942 Pink Pipe Insulation None Detected6a
B127943 Pink Pipe Insulation None Detected6b
B127944 Pink Pipe Insulation None Detected6c
B127945 White Pipe Insulation None Detected7a
B127946 White Pipe Insulation None Detected7b
B127947 White Pipe Insulation None Detected7c
B127948 White Tile None Detected8
B127949 Brown Tile None Detected9
B127950 Gray Grout None Detected10a
B127951 Gray Grout None Detected10b
B127952 Gray Grout None Detected10c
B127953 Yellow,Black Mastic None Detected11
B127954 Pink Tile None Detected12
B127955A Gray / White, Black / Beige
Tile None Detected13
B127955B Cream Mastic None Detected
B127956 Blue,White Linoleum None Detected14a
B127957 Yellow Mastic None Detected14b
Layer 1 B127958 Yellow Mastic None Detected15a
Layer 2 B127958 Gray Tile None Detected
B127959A Gray Flat Texture None Detected15b
B127959B Black Mastic Chrysotile 3% B127960 Black Pipe Foam None Detected16a
B127961 Black Pipe Foam None Detected16b
PROJECT: WI ANG - Medical Readiness Center, Building 311, 60613250
LAB CODE: B198450
Client ID Lab ID Color Sample Description
ASBESTOS
%Layer
METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020
B127962 Black Pipe Foam None Detected16c
B127963 Gray,Tan Pipe Wrap None Detected17a
B127964 Gray,Tan Pipe Wrap None Detected17b
B127965 Gray,Tan Pipe Wrap None Detected17c
B127966 White Caulk None Detected18
B127967 Gray Caulk None Detected19
B127968 Yellow Foam None Detected20
B127969 Yellow,Blue Mastic None Detected21
B127970 Orange Tile None Detected22
B127971 White,Beige Surfacing Material None Detected23a
B127972 White,Beige Surfacing Material None Detected23b
B127973 White Surfacing Material None Detected23c
B127974 White Surfacing Material None Detected23d
B127975 White Surfacing Material None Detected23e
B127976 Yellow,Brown Caulk None Detected24
B127977 Gray,White Caulk None Detected25
B127978 Gray,Clear Silicon None Detected26
B127979A Beige Linoleum None Detected27
B127979B Clear Mastic None Detected
B127980A Beige Tile None Detected28
B127980B Cream Mastic None Detected
B127981 Gray Tile None Detected29
Layer 1 B127982 Multicolored Tile None Detected30
Layer 2 B127982 Gray Grout None Detected
B127983A Cream Tile None Detected31
B127983B Yellow Mastic None Detected
Layer 1 B127984 Black,White Tile None Detected32
Layer 2 B127984 White Grout None Detected
B127985A White Tile None Detected33
B127985B Tan Mastic None Detected
B127986 White Grout None Detected34
PROJECT: WI ANG - Medical Readiness Center, Building 311, 60613250
LAB CODE: B198450
Client ID Lab ID Color Sample Description
ASBESTOS
%Layer
METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020
B127987 Black Pipe Wrap None Detected35a
B127988 Black Pipe Wrap None Detected35b
B127989 Black Pipe Wrap None Detected35c
B127990 White Foam None Detected36
B127991 Blue Foam Insulation None Detected37
B127992 White,Beige Heavy Texture Drop Ceiling None Detected38
B127993 Off-white,Tan Smooth Texture Drop Ceiling None Detected39
B127994 Red,Tan Paint None Detected40
Layer 1 B127995 White,Beige Paint None Detected41
Layer 2 B127995 Beige Mud Chrysotile 2% Layer 1 B127996 Gray,Tan Paint None Detected42
Layer 2 B127996 White Mud None Detected
B127997A Black Baseboard None Detected43
B127997B Tan Mastic None Detected
B127998A Gray Baseboard None Detected44
B127998B Cream,Black Mastic None Detected
B127999 Light Gray, White
Window And Door Caulk None Detected45
B128000 White,Yellow Pipe Wrap None Detected46a
B128001 White,Yellow Pipe Wrap None Detected46b
B128002 White,Yellow Pipe Wrap None Detected46c
B128003 White,Orange Paint None Detected47
B128004 Gray,White Weather Stripping None Detected48
Layer 1 B128005 Yellow Mastic None Detected49
Layer 2 B128005 Black Mastic Chrysotile 3%
Lab Code: B198450 Date Received: 11-18-19 Date Analyzed: 11-20-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 311, 60613250
Fibrous
Yellow,Black Mastic1
B127935 <1%Heterogeneous
Non-fibrous Bound
Lab Notes: Unable to separate yellow and black mastics for analysis.
95% 2%
Cellulose Mastic Silicates
3% Chrysotile
White,Black Mastic2
B127936 <1%Heterogeneous
Non-fibrous Bound
Lab Notes: Unable to separate white and black mastics for analysis.
100% <1%
Cellulose Mastic Paint
None Detected
Gray,Tan Drywall3
B127937 20%Heterogeneous
Fibrous Bound
80% <1%
Cellulose Gypsum Paint
None Detected
Yellow Insulation4
B127938 100%Homogeneous
Fibrous Loose
Fiberglass None Detected
Yellow Pipe Insulation5a
B127939 100% <1%
Homogeneous
Fibrous Loose
Fiberglass Cellulose
None Detected
Yellow Pipe Insulation5b
B127940 100%Homogeneous
Fibrous Loose
Fiberglass None Detected
Yellow Pipe Insulation5c
B127941 100%Homogeneous
Fibrous Loose
Fiberglass None Detected
Lab Code: B198450 Date Received: 11-18-19 Date Analyzed: 11-20-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 311, 60613250
Fibrous
Pink Pipe Insulation6a
B127942 100%Homogeneous
Fibrous Loose
Fiberglass None Detected
Pink Pipe Insulation6b
B127943 100%Homogeneous
Fibrous Loose
Fiberglass None Detected
Pink Pipe Insulation6c
B127944 100%Homogeneous
Fibrous Loose
Fiberglass None Detected
White Pipe Insulation7a
B127945 100%Homogeneous
Fibrous Loose
Fiberglass None Detected
White Pipe Insulation7b
B127946 100%Homogeneous
Fibrous Loose
Fiberglass None Detected
White Pipe Insulation7c
B127947 100%Homogeneous
Fibrous Loose
Fiberglass None Detected
White Tile8
B127948 Homogeneous
Non-fibrous Tightly Bound
90% 10%
Binder Silicates
Lab Code: B198450 Date Received: 11-18-19 Date Analyzed: 11-20-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 311, 60613250
Fibrous
Brown Tile9
B127949 Homogeneous
Non-fibrous Tightly Bound
90% 10%
Binder Silicates
None Detected
Gray Grout10a
B127950 <1%Homogeneous
Non-fibrous Tightly Bound
70% 30%
Cellulose Binder Silicates
None Detected
Gray Grout10b
B127951 <1%Homogeneous
Non-fibrous Tightly Bound
70% 30%
Cellulose Binder Silicates
None Detected
Gray Grout10c
B127952 <1%Homogeneous
Non-fibrous Tightly Bound
70% 30%
Cellulose Binder Silicates
None Detected
Yellow,Black Mastic11
B127953 7% 3%
Homogeneous
Fibrous Bound
85% 5%
Synthetic Fiber Cellulose
Mastic Tar
None Detected
Pink Tile12
B127954 Homogeneous
Non-fibrous Tightly Bound
90% 10%
Binder Silicates
None Detected
Gray / White, Black / Beige
Tile13 B127955A
Homogeneous
Non-fibrous Tightly Bound
100% Vinyl None Detected
Lab Code: B198450 Date Received: 11-18-19 Date Analyzed: 11-20-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 311, 60613250
Fibrous
Cream MasticB127955B Homogeneous
Non-fibrous Bound
100% Mastic None Detected
Blue,White Linoleum14a
B127956 Heterogeneous
Non-fibrous Tightly Bound
50% 40% 10%
Vinyl Foam Binder
None Detected
Yellow Mastic14b
B127957 Homogeneous
Non-fibrous Bound
100% Mastic None Detected
Yellow 15a
B127958
<1%Homogeneous
Non-fibrous Bound
100%Cellulose Mastic None Detected Layer 1
Mastic
Gray Tile
B127958 5%Homogeneous
Fibrous Bound
95%Cellulose Vinyl None DetectedLayer 2
Gray Flat Texture15b
B127959A 15%Homogeneous
Fibrous Bound
85%Cellulose Binder None Detected
Black MasticB127959B <1%Homogeneous
Non-fibrous Bound
97%Cellulose Tar 3% Chrysotile
Lab Code: B198450 Date Received: 11-18-19 Date Analyzed: 11-20-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 311, 60613250
Fibrous
Black Pipe Foam16a
B127960 Homogeneous
Non-fibrous Bound
100% Foam None Detected
Black Pipe Foam16b
B127961 Homogeneous
Non-fibrous Bound
100% <1%
Foam Mastic
None Detected
Black Pipe Foam16c
B127962 Homogeneous
Non-fibrous Bound
100% Foam None Detected
Gray,Tan Pipe Wrap17a
B127963 5%Heterogeneous
Fibrous Bound
70% 20% 5%
Cellulose Foam Binder Mastic
None Detected
Gray,Tan Pipe Wrap17b
B127964 5%Heterogeneous
Fibrous Bound
70% 20% 5%
Cellulose Foam Binder Mastic
None Detected
Gray,Tan Pipe Wrap17c
B127965 5%Heterogeneous
Fibrous Bound
70% 20% 5%
Cellulose Foam Binder Mastic
None Detected
White Caulk18
B127966 Homogeneous
Non-fibrous Bound
100% Caulk None Detected
Lab Code: B198450 Date Received: 11-18-19 Date Analyzed: 11-20-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 311, 60613250
Fibrous
Gray Caulk19
B127967 Homogeneous
Non-fibrous Bound
100% Caulk None Detected
Yellow Foam20
B127968 <1%Homogeneous
Non-fibrous Bound
100%Cellulose Foam None Detected
Yellow,Blue Mastic21
B127969 Heterogeneous
Non-fibrous Bound
100% <1%
Mastic Paint
None Detected
Orange Tile22
B127970 Homogeneous
Non-fibrous Tightly Bound
90% 10%
Binder Silicates
None Detected
White,Beige Surfacing Material23a
B127971 3%Heterogeneous
Non-fibrous Bound
65% 30% 2%
Talc Silicates Binder Paint
None Detected
White,Beige Surfacing Material23b
B127972 5% 3%
Heterogeneous
Fibrous Bound
60% 30% 2%
Cellulose Talc
Silicates Binder Paint
None Detected
White Surfacing Material23c
B127973 3%Heterogeneous
Non-fibrous Bound
65% 30% 2%
Talc Silicates Binder Paint
Lab Code: B198450 Date Received: 11-18-19 Date Analyzed: 11-20-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 311, 60613250
Fibrous
White Surfacing Material23d
B127974 3%Heterogeneous
Non-fibrous Bound
65% 30% 2%
Talc Silicates Binder Paint
None Detected
White Surfacing Material23e
B127975 3%Heterogeneous
Non-fibrous Bound
65% 30% 2%
Talc Silicates Binder Paint
None Detected
Yellow,Brown Caulk24
B127976 Heterogeneous
Non-fibrous Bound
100% <1%
Caulk Paint
None Detected
Gray,White Caulk25
B127977 Heterogeneous
Non-fibrous Bound
100% <1%
Caulk Paint
None Detected
Gray,Clear Silicon26
B127978 Homogeneous
Non-fibrous Bound
100% Caulk None Detected
Beige Linoleum27
B127979A Homogeneous
Non-fibrous Tightly Bound
100% Vinyl None Detected
Clear MasticB127979B Homogeneous
Non-fibrous Bound
100% Mastic None Detected
Lab Code: B198450 Date Received: 11-18-19 Date Analyzed: 11-20-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 311, 60613250
Fibrous
Beige Tile28
B127980A Homogeneous
Non-fibrous Tightly Bound
100% Vinyl None Detected
Cream MasticB127980B <1%Homogeneous
Non-fibrous Bound
100% <1%
Cellulose Mastic Binder
None Detected
Gray Tile29
B127981 Homogeneous
Non-fibrous Tightly Bound
70% 30%
Silicates Binder
None Detected
Multicolored
B127982
Homogeneous
Non-fibrous Tightly Bound
90% 10%
Binder Silicates
None Detected Layer 1
Tile
Gray Grout
B127982 <1%Homogeneous
Non-fibrous Tightly Bound
70% 30%
Cellulose Silicates Binder
None DetectedLayer 2
Cream Tile31
B127983A Homogeneous
Non-fibrous Tightly Bound
90% 10%
Binder Silicates
None Detected
Yellow MasticB127983B 5%Homogeneous
Fibrous Bound
95%Cellulose Mastic None Detected
Lab Code: B198450 Date Received: 11-18-19 Date Analyzed: 11-20-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 311, 60613250
Fibrous
Black,White
B127984
Homogeneous
Non-fibrous Tightly Bound
90% 10%
Binder Silicates
None Detected Layer 1
Tile
White Grout
B127984 Homogeneous
Non-fibrous Tightly Bound
70% 30%
Silicates Binder
None DetectedLayer 2
White Tile33
B127985A Homogeneous
Non-fibrous Tightly Bound
90% 10%
Binder Silicates
None Detected
Tan MasticB127985B <1%Homogeneous
Non-fibrous Bound
100%Cellulose Mastic None Detected
White Grout34
B127986 Homogeneous
Non-fibrous Tightly Bound
70% 30%
Silicates Binder
None Detected
Black Pipe Wrap35a
B127987 Homogeneous
Non-fibrous Bound
100% Foam None Detected
Black Pipe Wrap35b
B127988 Homogeneous
Non-fibrous Bound
100% Foam None Detected
Lab Code: B198450 Date Received: 11-18-19 Date Analyzed: 11-20-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 311, 60613250
Fibrous
Black Pipe Wrap35c
B127989 Homogeneous
Non-fibrous Bound
100% Foam None Detected
White Foam36
B127990 <1%Homogeneous
Non-fibrous Bound
100%Cellulose Foam None Detected
Blue Foam Insulation37
B127991 <1%Homogeneous
Non-fibrous Bound
100%Cellulose Foam None Detected
White,Beige Heavy Texture Drop Ceiling
B127992
50% 30%
Heterogeneous
Fibrous Loosely Bound
15% 5%
Fiberglass Cellulose
Perlite Paint
None Detected
Off-white,Tan Smooth Texture Drop Ceiling
B127993
15% 5%
Heterogeneous
Fibrous Loosely Bound
80%Cellulose Fiberglass
Gypsum None Detected
Red,Tan Paint40
B127994 3%Homogeneous
Fibrous Bound
97%Cellulose Paint None Detected
White,Beige
B127995
Homogeneous
Non-fibrous Bound
100% Paint None Detected Layer 1
Paint
Lab Code: B198450 Date Received: 11-18-19 Date Analyzed: 11-20-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 311, 60613250
Fibrous
Beige Mud
B127995 Heterogeneous
Fibrous Bound
85% 13%
Binder Calc Carb
2% ChrysotileLayer 2
Gray,Tan
B127996
3%Homogeneous
Fibrous Bound
97%Cellulose Paint None Detected Layer 1
Paint
White Mud
B127996 Heterogeneous
Non-fibrous Bound
85% 15%
Binder Calc Carb
None DetectedLayer 2
Black Baseboard43
B127997A Homogeneous
Non-fibrous Tightly Bound
100% Vinyl None Detected
Tan MasticB127997B Homogeneous
Non-fibrous Bound
100% Mastic None Detected
Gray Baseboard44
B127998A Homogeneous
Non-fibrous Tightly Bound
100% Vinyl None Detected
Cream,Black MasticB127998B Heterogeneous
Non-fibrous Bound
100% <1% <1%
Mastic Binder Paint
Lab Code: B198450 Date Received: 11-18-19 Date Analyzed: 11-20-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 311, 60613250
Fibrous
Light Gray,White Window And Door Caulk
B127999
Homogeneous
Non-fibrous Bound
100% Caulk None Detected
White,Yellow Pipe Wrap46a
B128000 50% 20%
Heterogeneous
Fibrous Bound
20% 10%
Fiberglass Cellulose
Metal Foil Mastic
None Detected
White,Yellow Pipe Wrap46b
B128001 50% 20%
Heterogeneous
Fibrous Bound
20% 10%
Fiberglass Cellulose
Metal Foil Mastic
None Detected
White,Yellow Pipe Wrap46c
B128002 50% 20%
Heterogeneous
Fibrous Bound
20% 10%
Fiberglass Cellulose
Metal Foil Mastic
None Detected
White,Orange Paint47
B128003 Heterogeneous
Non-fibrous Bound
97% 3%
Paint Rust
None Detected
Gray,White Weather Stripping48
B128004 Heterogeneous
Non-fibrous Tightly Bound
100% <1%
Vinyl Paint
None Detected
Yellow
B128005
<1%Homogeneous
Non-fibrous Bound
100%Cellulose Mastic None Detected Layer 1
Mastic
Lab Code: B198450 Date Received: 11-18-19 Date Analyzed: 11-20-19 Date Reported: 11-25-19
Client ID Lab ID
Lab Attributes
Lab Description
ASBESTOS
ASBESTOS BULK PLM, EPA 600 METHOD
NON-ASBESTOS COMPONENTS
Non-Fibrous
Client: AECOM Columbus 277 West Nationwide Blvd Columbus, OH 43215
Project: WI ANG - Medical Readiness Center, Building 311, 60613250
Fibrous
Black Mastic
B128005 5%Homogeneous
Fibrous Bound
92%Cellulose Tar 3% ChrysotileLayer 2
LEGEND: Non-Anth = Non-Asbestiform Anthophyllite Non-Trem = Non-Asbestiform Tremolite Calc Carb = Calcium Carbonate
METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020
REPORTING LIMIT: <1% by visual estimation
REPORTING LIMIT FOR POINT COUNTS: 0.25% by 400 Points or 0.1% by 1,000 Points
REGULATORY LIMIT: >1% by weight
Due to the limitations of the EPA 600 method, nonfriable organically bound materials (NOBs) such as vinyl floor tiles can be difficult to analyze via polarized light microscopy (PLM). EPA recommends that all NOBs analyzed by PLM, and found not to contain asbestos, be further analyzed by Transmission Electron Microscopy (TEM). Please note that PLM analysis of dust and soil samples for asbestos is not covered under NVLAP accreditation. Estimated measurement of uncertainty is available on request.
This report relates only to the samples tested or analyzed and may not be reproduced, except in full, without written approval by Eurofins CEI. Eurofins CEI makes no warranty representation regarding the accuracy of client submitted information in preparing and presenting analytical results.
Interpretation of the analytical results is the sole responsibility of the client. Samples were received in acceptable condition unless otherwise noted. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. Government.
Information provided by customer includes customer sample ID and sample description.
ANALYST: APPROVED BY:
Tianbao Bai, Ph.D., CIH
Miguel Angel Maysonet
Contract No. W9133L-16-D-0009 Delivery Order No. W912J2-19-F-6007
AECOM No. 60613250
B-3 Submittal
Section 00 3132
GEOTECHNICAL DATA
Project No. XGFG139001
MEDICAL READINESS FACILITY
July 8, 2021
DOCUMENT 003132
GEOTECHNICAL DATA
PART 1 - GENERAL
1.01 GEOTECHNICAL DATA
A. This Document with its referenced attachments is part of the Procurement and Contracting Requirements for Project. They provide Government's information for Bidders' convenience and are intended to supplement rather than serve in lieu of Bidders' own investigations. They are made available for Bidders' convenience and information. This Document and its attachments are not part of the Contract Documents.
B. Because subsurface conditions indicated by the soil borings are a sampling in relation to the entire construction area, and for other reasons, the Government, the Architect, the Architect's consultants, and the firm reporting the subsurface conditions do not warranty the conditions below the depths of the borings or that the strata logged from the borings are necessarily typical of the entire site. Any party using the information described in the soil borings and geotechnical report shall accept full responsibility for its use.
C. A geotechnical investigation report for Project, prepared by GESTRA Engineering, Inc., dated November 8, 2019, as amended February 3, 2020, is available for viewing as appended to this Document.
1. The opinions expressed in this report are those of a geotechnical engineer and represent interpretations of subsoil conditions, tests, and results of analyses conducted by a geotechnical engineer. Government is not responsible for interpretations or conclusions drawn from the data.
2. Any party using information described in the geotechnical report shall make additional test borings and conduct other exploratory operations that may be required to determine the character of subsurface materials that may be encountered.
D. Related Requirements:
1. Document 00 3119 "Existing Condition Information" for information about existing conditions that is made available to bidders.
2. Document 00 3126 "Existing Hazardous Material Information" for hazardous materials reports that are made available to bidders.
GEOTECHNICAL ENGINEERING REPORT
Air National Guard Medical Readiness Building
Truax Field
Madison, Wisconsin
GESTRA Project No.: M19073-10
November 8, 2019
Prepared For:
AECOM
277 West Nationwide Blvd.
Columbus, OH 43215
Geotechnical Engineering Report
Air National Guard Medical Readiness Building
GESTRA Project No. M19073-10
November 8, 2019
Prepared For:
AECOM
277 W. Nationwide Blvd.
Columbus, OH 43215
Prepared By:
GESTRA Engineering, Inc.
191 W. Edgerton Avenue
Milwaukee, WI 53207
(414) 933-7444
Table of Contents
1.0 INTRODUCTION
1.1 PROJECT INFORMATION
2.0 SCOPE OF WORK
3.0 EXPLORATION RESULTS
3.1 SITE CONDITIONS
3.