074213 23 compo wall panel.pdf

PDF 120 KB Posted

Attached to
Construct Medical Readiness Facility Federal contract opportunity
Solicitation number
W50S9F22R0001
Issued by
Department of the Army National Guard

About this file

This solicitation requests proposals for the construction of a two-story 18,650 square foot Medical Readiness facility at Dane County Regional Airport - Truax Field in Madison, Wisconsin. The facility will include 15,250 square feet for Reserve Forces Medical Training/Administration and 3,400 square feet for Expeditionary Medical Support-Consequence Management storage.

The solicitation will result in a single firm fixed-price construction contract. Work includes site utilities, grading, landscaping, erecting precast concrete panels, and new mechanical, electrical, plumbing and technology systems. The project also includes demolition of two existing buildings. Nine optional items are included for permeable pavers, asphalt, storefront, wall panels, daylighting, blinds, terrazzo flooring, ducts and additional demolition.

The contract duration is 450 days from notice to proceed. Proposals are due May 5, 2022. Evaluation criteria are technical, past performance and price. The government intends to award without discussions. A pre-proposal conference will be held March 31, 2022 at the project site. The solicitation is available through SAM.gov. The estimated value is between $5-10 million. The NAICS code is 236220.

View the file

Other files for this federal contract opportunity

Other files attached to Construct Medical Readiness Facility, newest first.
File Type Posted
Questions and Answers 05 R1.pdf PDF
Questions and Answers 04 R1.pdf PDF
SECTION 26 0573.19 ARC FLASH HAZARD ANALYSIS.pdf PDF
60613250_WIANG_TRUAX-MED-E_v19 - Sheet - E-601 - ELECTRICAL SCHEDULES.pdf PDF
W50S9F-22-R-0001_0004.pdf PDF
Questions and Answers 05.pdf PDF
Questions and Answers 04.pdf PDF
W50S9F-22-R-0001_0003.pdf PDF
Photograph Log.docx DOCX document
Bldg_307 Floor Layout.pdf PDF
Bldg_311 Floor Layout.pdf PDF
Questions and Answers 03.pdf PDF
DEMO PLAN BLDG 311.pdf PDF
Questions and Answers 01.pdf PDF
Questions and Answers 02.pdf PDF
W50S9F-22-R-0001_0002.pdf PDF
Pre-Proposal Slides - Medical Readiness.pdf PDF
Pre-Proposal Conference Minutes.pdf PDF
Site Visit Sign In Log.pdf PDF
W50S9F-22-R-0001_0001.pdf PDF
ATTACHMENT 01_PLANS AND SPECIFICATIONS Vol 1 Project No. XGFG139001 dated 08 Jul 2021.pdf PDF
ATTACHMENT 02_PLANS AND SPECIFICATIONS Vol 2 Project No. XGFG139001 dated 08 Jul 2021.pdf PDF
ATTACHMENT 04_GEOTECHNICAL ENGINEERING REPORT Project No. XGFG139001 dated 08 Nov 2019.pdf PDF
ATTACHMENT 06_B311 ASBESTOS REPORT Project No. XGFG139001 dated 25 Nov 2019.pdf PDF
ATTACHMENT 07_SAP SINGLE SOURCE DETERMINATION ADVANTOR.pdf PDF
ATTACHMENT 11_SFS FORM 12.xlsx XLSX spreadsheet
EXHIBIT A PERFORMANCE RELEVANCY QUESTIONNAIRE AND SPECIALIZED COMPANY EXPERIENCE.docx DOCX document
EXHIBIT C LETTER OF COMMITMENT.docx DOCX document
W50S9F-22-R-0001.pdf PDF
ATTACHMENT 08_SAP SINGLE SOURCE DETERMINATION ANDOVER.pdf PDF
EXHIBIT B SUBCONTRACTOR TEAM KEY PERSONNEL INFORMATION AND CONSENT FORM.doc DOC document
EXHIBIT F SUBCONTRACTING PLAN FORMAT.docx DOCX document
EXHIBIT G PROPOSAL PRICE SCHEDULE.docx DOCX document
ATTACHMENT 03_DRAWINGS Project No. XGFG139001 dated 14 MAY 2021.pdf PDF
ATTACHMENT 05_B307 ASBESTOS REPORT Project No. XGFG139001 dated 25 Nov 2019.pdf PDF
ATTACHMENT 09_SAP SINGLE SOURCE DETERMINATION MONACO.pdf PDF
ATTACHMENT 10_SAP SINGLE SOURCE DETERMINATION MARSHALL BEST.pdf PDF
ATTACHMENT 12 PRE PROPOSAL SITE VISIT_DROP OFF INSTRUCTIONS.pdf PDF
EXHIBIT D PAST PERFORMANCE REFERENCE QUESTIONNAIRE.docx DOCX document
EXHIBIT E SMALL BUSINESS PARTICIPATION PLAN FORMAT.docx DOCX document
Show all 40

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

COMPOSITE WALL PANELS 074213.23 - 1

SECTION 074213.23 - COMPOSITE WALL PANELS

PART 1 - GENERAL

1.1 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract and Division 01 Specification Sections, apply to this Section.

1.2 SUMMARY

A. Section includes metal-faced composite wall panel systems.

B. Related Sections:

1. Division 05 Section "Cold-Formed Metal Framing" for cold-formed metal framing supporting metal-faced composite wall panels.

2. Section 074213 "Metal Wall Panels" for horizontal metal wall panels.

3. Division 07 Section " Standing Seam Metal Roof Panels" for field-formed flashings and other sheet metal work not part of metal-faced composite wall panel assemblies.

1.3 DEFINITION

A. Metal-Faced Composite Wall Panel Assembly: Pressure-equalized, metal-faced composite wall panels, attachment system components, miscellaneous metal framing, and accessories necessary for a complete wall system.

1.4 PERFORMANCE REQUIREMENTS

A. General Performance: Design, fabricate and erect a pressure equalized wall panel system which prevents uncontrolled penetration of water through the wall system and includes provision for draining any leakage of water at joints and any condensation that may occur in the wall system to the exterior.

1. Pressure-equalized, metal-faced composite wall panel assemblies shall comply with performance requirements without failure due to defective manufacture, fabrication, installation, or other defects in construction.

2. System Assembly (Panels, substrate, waterproofing membrane, and attachment system) shall meet or exceed the requirements of AAMA 508 for Rainscreen Systems as tested by an independent agency qualified according to ASTM C 1093 for testing indicated.

B. Structural Performance: Provide metal-faced composite wall panel assemblies capable of withstanding the effects of the following loads and stresses within limits and under conditions indicated, based on testing according to ASTM E 330:

1. Wind Loads: Determine loads based on the following minimum design wind pressures:

a. Within 8-feet of building corners: 25 lb/sf inward and 34 lb/sf outward (suction)

b. Remaining wall face: 25 lb/ft inward and 30 lb/sf outward (suction)

COMPOSITE WALL PANELS 074213.23 - 2

2. Other Design Loads: As indicated on Drawings.

3. Deflection Limits: Metal-faced composite wall panel assemblies shall withstand wind loads with horizontal deflections no greater than 1/175 of the span at the perimeter and 1/60 of the span anywhere in the panel.

C. Thermal Movements: Allow for thermal movements from ambient and surface temperature changes by preventing buckling, opening of joints, overstressing of components, failure of connections, and other detrimental effects. Base calculations on surface temperatures of materials due to both solar heat gain and nighttime-sky heat loss.

1. Temperature Change (Range): 120 deg F, ambient; 180 deg F, material surfaces.

1.5 SUBMITTALS

A. Product Data: For each type of product indicated. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for each type of metal-faced composite wall panel and accessory.

B. Shop Drawings: Show fabrication and installation layouts of metal-faced composite wall panels;

details of edge conditions, joints, panel profiles, corners, anchorages, attachment system, trim, flashings, closures, and accessories; a and special details showing methods of forming and installing panels on curved surfaces indicated. Distinguish among factory-, shop-, and field-assembled work.

1. Accessories: Include details of the following items, at a scale of not less than 1-1/2 inches per 12 inches:

a. Flashing and trim.

b. Anchorage systems.

C. Samples for Initial Selection: For each type of metal-faced composite wall panel indicated with factory-applied color finishes.

1. Include similar Samples of trim and accessories involving color selection.

D. Samples for Verification: For each type of exposed finish required, prepared on Samples of size indicated below:

1. Metal-Faced Composite Wall Panels: Minimum 12 x 12 inches. Include fasteners, closures, and other metal-faced composite wall panel accessories.

a. Composite Panels: Include four-way joint.

2. Trim and Closures: 12 inches long. Include fasteners and other exposed accessories.

3. Accessories: 12-inch- long Samples for each type of accessory.

E. Qualification Data: For Fabricator and Installer.

F. Product Test Reports: Based on evaluation of comprehensive tests performed by a qualified testing agency, for each product. Include documentation that shows compliance with structural performance requirements.

G. Maintenance Data: For metal wall panels to include in maintenance manuals.

COMPOSITE WALL PANELS 074213.23 - 3

H. Warranties: Samples of special warranties.

1.6 QUALITY ASSURANCE

A. Source Limitations: Obtain each type of metal-faced composite wall panel from single source from single manufacturer.

B. Fabricator and Installer Qualifications: Fabricator and Installer shall have a minimum 10 years continuous successful experience and must have completed five projects in the specified aluminum composite wall panel system, similar in extent to that indicated for this Project, with a record of successful in-service performance. Include three references and contact numbers to verify.

C. Mockups: Build mockups to verify selections made under sample submittals and to demonstrate aesthetic effects and set quality standards for fabrication and installation.

1. Include at least the following details and conditions with their substrates:

a. Outside vertical corner and horizontal soffit juncture.

b. Four-way joint for metal-faced composite wall panels.

c. Formed coping if condition is part of the project.

2. Approval of mockups does not constitute approval of deviations from the Contract Documents contained in mockups unless Architect specifically approves such deviations in writing.

3. Approved mockups may become part of the completed Work if undisturbed at time of Contract Completion.

D. Preinstallation Conference: Conduct conference at Project site.

1. Meet with Owner, Architect, Construction Manager, testing and inspecting agency representative, metal-faced composite wall panel Installer, metal-faced composite wall panel manufacturer's factory authorized representative, structural-support Installer, and installers whose work interfaces with or affects metal-faced composite wall panels including installers of doors, windows, and louvers.

2. Review and finalize construction schedule and verify availability of materials, Installer's personnel, equipment, and facilities needed to make progress and avoid delays.

3. Review methods and procedures related to metal-faced composite wall panel installation, including manufacturer's written instructions.

4. Examine support conditions for compliance with requirements, including alignment between and attachment to structural members.

5. Review flashings, special siding details, wall penetrations, openings, and condition of other construction that will affect metal-faced composite wall panels.

6. Review governing regulations and requirements for insurance, certificates, and tests and inspections if applicable.

7. Review temporary protection requirements for metal-faced composite wall panel assembly during and after installation.

8. Review wall panel observation and repair procedures after metal-faced composite wall panel installation.

COMPOSITE WALL PANELS 074213.23 - 4

1.7 DELIVERY, STORAGE, AND HANDLING

A. Deliver components, sheets, metal-faced composite wall panels, and other manufactured items so as not to be damaged or deformed. Package metal-faced composite wall panels for protection during transportation and handling.

B. Unload, store, and erect metal-faced composite wall panels in a manner to prevent bending, warping, twisting, and surface damage.

C. Store metal-faced composite wall panels vertically, covered with suitable weathertight and ventilated covering. Store metal-faced composite wall panels to ensure dryness, with positive slope for drainage of water. Do not store metal-faced composite wall panels in contact with other materials that might cause staining, denting, or other surface damage. Do not allow storage space to exceed 120 deg F.

D. Retain strippable protective covering on metal-faced composite wall panel for period of panel installation.

1.8 PROJECT CONDITIONS

A. Weather Limitations: Proceed with installation only when existing and forecasted weather conditions permit assembly of metal-faced composite wall panels to be performed according to manufacturer's written instructions and warranty requirements.

B. Field Measurements: Verify locations of structural members and wall opening dimensions by field measurements before metal-faced composite wall panel fabrication and indicate measurements on Shop Drawings.

1.9 COORDINATION

A. Coordinate metal-faced composite wall panel assemblies with rain drainage work, flashing, trim, and construction of studs, soffits, and other adjoining work to provide a leakproof, secure, and noncorrosive installation.

1.10 WARRANTY

A. Special Warranty: Manufacturer's standard form in which manufacturer agrees to repair or replace components of metal-faced composite wall panel assemblies that fail in materials or workmanship within specified warranty period.

1. Failures include, but are not limited to, the following:

a. Structural failures, including rupturing, cracking, or puncturing.

b. Deterioration of metals and other materials beyond normal weathering.

2. Warranty Period: Two years from date of Contract Completion.

B. Special Warranty on Panel Finishes: Manufacturer's standard form in which manufacturer agrees to repair finish or replace metal-faced composite wall panels that show evidence of deterioration of factory-applied finishes within specified warranty period.

1. Exposed Panel Finish: Deterioration includes, but is not limited to, the following:

COMPOSITE WALL PANELS 074213.23 - 5

a. Color fading more than five Hunter units when tested according to ASTM D 2244.

b. Chalking in excess of a No. 8 rating when tested according to ASTM D 4214.

c. Cracking, checking, peeling, or failure of paint to adhere to bare metal.

2. Finish Warranty Period: 20 years from date of Contract Completion.

PART 2 - PRODUCTS

2.1 PANEL MATERIALS

A. Aluminum Sheet: Coil-coated sheet, ASTM B 209, alloy as standard with manufacturer, with temper as required to suit forming operations and structural performance required.

1. Surface: Smooth, flat finish.

2. Exposed Coil-Coated Finishes:

a. Two-Coat Fluoropolymer: AAMA 620. Fluoropolymer finish containing not less than 70 percent PVDF resin by weight in color coat. Prepare, pretreat, and apply coating to exposed metal surfaces to comply with coating and resin manufacturers' written instructions.

3. Concealed Finish: Apply pretreatment and manufacturer's standard white or light-colored acrylic or polyester backer finish, consisting of prime coat and wash coat with a minimum total dry film thickness of 0.5 mil.

2.2 MISCELLANEOUS METAL FRAMING

A. Miscellaneous Metal Framing, General: ASTM C 645, cold-formed metallic-coated steel sheet, ASTM A 653, G60 hot-dip galvanized or coating with equivalent corrosion resistance unless otherwise indicated.

B. Fasteners for Miscellaneous Metal Framing: Of type, material, size, corrosion resistance, holding power and other properties required to fasten miscellaneous metal framing members to substrates.

2.3 MISCELLANEOUS MATERIALS

A. Aluminum Extrusions: ASTM B 221, alloy and temper recommended by manufacturer for type of use and finish indicated.

B. Fasteners: Self-tapping screws, bolts, nuts, self-locking rivets and bolts, end-welded studs, and other suitable fasteners designed to withstand design loads. Provide exposed fasteners with heads matching color of metal-faced composite wall panels by means of plastic caps or factory-applied coating. Provide EPDM, PVC, or neoprene sealing washers.

C. Self-Adhering Sheet Membrane: Self-adhesive rubberized asphalt / polyethylene waterproofing air and water barrier minimum 3/64 inches thick, self-sealing, with release-paper backing; cold applied. Provide primer when recommended by underlayment manufacturer.

1. Thermal Stability: Stable after testing at 240 deg F; ASTM D 1970.

2. Low-Temperature Flexibility: Passes after testing at minus 20 deg F; ASTM D 1970.

COMPOSITE WALL PANELS 074213.23 - 6

3. Basis of Design: Subject to compliance with requirements provide Perm-a-Barrier Wall Membrane by Grace Construction Products or equivalent membrane by one of the following:

a. Carlisle Coatings & Waterproofing Inc., Div. of Carlisle Companies Inc.

b. Grace Construction Products; a unit of Grace, W. R. & Co.

c. Henry Company.

d. Owens Corning.

D. Glass-Mat Gypsum Wall Sheathing: ASTM C 1177.

1. Product: Subject to compliance with requirements, provide one of the following:

a. CertainTeed Corporation; GlasRoc.

b. G-P Gypsum Corporation; Dens-Glass Gold.

c. Temple-Inland Inc.; GreenGlass.

d. United States Gypsum Co.; Securock.

e. National Gypsum; e2XP Sheathing.

2. Type and Thickness: Regular, 1/2 inch thick.

3. Size: 48 by 96 inches for vertical installation.

2.4 METAL-FACED COMPOSITE WALL PANELS

A. General: Provide factory-formed and -assembled, metal-faced composite wall panels fabricated from two metal facings bonded, using no glues or adhesives, to solid, extruded thermoplastic core; formed into profile for installation method indicated. Include attachment system components and accessories required for weathertight system.

1. Products: Subject to compliance with requirements, provide one of the following:

a. Alcan Composites USA Inc.; Alucobond.

b. Alcoa Inc.; Reynobond.

c. ALPOLIC, Division of Mitsubishi Chemical America, Inc.; ALPOLIC.

2. Fabricators / System: Subject to compliance with requirements, provide wall systems fabricated by one of the following:

a. Shaffner Heaney Associates.

b. Sobotec Ltd.; SL2000 (Basis of Design).

c. Southern Aluminum Finishing

d. The Miller Clapperton Partnership, Inc.

e. Kanalco Ltd.

f. East Coast Metal Systems

B. Aluminum-Faced Composite Wall Panels: Formed with 0.020-inch- thick, coil-coated aluminum sheet facings.

1. Panel Thickness: 0.157 inch.

2. Core: Standard.

3. Exterior Finish: 2-coat fluoropolymer.

a. Color: As selected by the architect from the manufacturer’s full range of color selections.

http://www.specagent.com/LookUp/?ulid=4845&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456800028&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456800030&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456800031&mf=04&src=wd http://www.specagent.com/LookUp/?uid=123456800034&mf=04&src=wd

COMPOSITE WALL PANELS 074213.23 - 7

C. Panel Attachment System Components: Formed from extruded aluminum shapes.

1. Manufacturer's / fabricator’s standard perimeter extrusions with integral weather stripping, panel stiffeners, panel clips, and anchor channels.

2.5 ACCESSORIES

A. Wall Panel Accessories: Provide components required for a complete metal-faced composite wall panel assembly including trim, corner units, clips, flashings, gaskets, fillers, closure strips, and similar items. Match material and finish of metal-faced composite wall panels unless otherwise indicated.

B. Additional Substrates: Provide substrate materials required by the manufacturer for highest recommended system and as necessary to provide finished configurations and dimensions shown. For any additional substrate materials that affect the shown support system, provide coordination drawings to show the needed changes across all affected trades. Additional substrate materials and support adjustments required by any manufacturer’s system are to be provided as part of the Work not as a claim for extra.

C. Flashing and Trim: Provide flashing and trim formed from same material as metal composite material panels as required to seal against weather and to provide finished appearance.

Locations include, but are not limited to, bases, drips, sills, jambs, corners, endwalls, framed openings, rakes, fasciae, parapet caps, soffits, reveals, and fillers. Finish flashing and trim with same finish system as adjacent metal composite material panels.

2.6 FABRICATION

A. General: Fabricate and finish metal-faced composite wall panels and accessories at the factory to greatest extent possible, by manufacturer's standard procedures and processes, as necessary to fulfill indicated performance requirements demonstrated by laboratory testing.

Comply with indicated profiles and with dimensional and structural requirements.

B. Fabricate metal-face composite wall panels in a manner that allows for the system to drain to the exterior.

C. Metal-Faced Composite Wall Panels: Factory form panels in a continuous process with no glues or adhesives between dissimilar materials. Trim and square edges of sheets with no displacement of face sheets or protrusion of core material.

1. Form panel lines, breaks, and angles to be sharp and true, with surfaces free from warp and buckle.

2. Fabricate panels with sharply cut edges, with no displacement of face sheets or protrusion of core material.

3. For material that evidences ‘grain’ or directionality, produce panels with such property oriented in the same direction throughout the installation. Indicate ‘grain’ direction on the shop drawings.

4. Fabricate panels with panel stiffeners, as required to comply with deflection limits, attached to back of panels with structural silicone sealant or bond tape.

5. Dimensional Tolerances:

a. Panel Bow: 0.8 percent maximum of panel length or width.

b. Squareness: 0.25 inch maximum.

COMPOSITE WALL PANELS 074213.23 - 8

6. Panels with integral coping / soffit sections:

a. Do not change the indicated aesthetic effect by introducing joints in locations or orientations differing from those shown without advance approval of the architect.

b. Do not change the panel material or panel assembly methods at integral copings / soffits

c. Coordinate details and support fully with interfacing soffit and roof systems

D. Sheet Metal Flashing and Trim: Fabricate flashing and trim to comply with manufacturer's recommendations and recommendations in SMACNA's "Architectural Sheet Metal Manual" that apply to design, dimensions, metal, and other characteristics of item indicated.

1. Form exposed sheet metal accessories that are without excessive oil canning, buckling, and tool marks and that are true to line and levels indicated, with exposed edges folded back to form hems.

2. Seams for Aluminum: Fabricate nonmoving seams with flat-lock seams. Form seams and seal with epoxy seam sealer. Rivet joints for additional strength.

3. Sealed Joints: Form non-expansion, but movable, joints in metal to accommodate sealant and to comply with SMACNA standards.

4. Conceal fasteners and expansion provisions where possible. Exposed fasteners are not allowed on faces of accessories exposed to view.

5. Fabricate cleats and attachment devices from same material as accessory being anchored or from compatible, noncorrosive metal recommended in writing by metal panel manufacturer.

a. Size: As recommended by SMACNA's "Architectural Sheet Metal Manual" or metal wall panel manufacturer for application but not less than thickness of metal being secured.

2.7 GENERAL FINISH REQUIREMENTS

A. Comply with NAAMM's "Metal Finishes Manual for Architectural and Metal Products" for recommendations for applying and designating finishes.

B. Protect mechanical and painted finishes on exposed surfaces from damage by applying a strippable, temporary protective covering before shipping.

C. Appearance of Finished Work: Noticeable variations in same piece are not acceptable.

Variations in appearance of abutting or adjacent pieces are acceptable if they are within one-half of the range of approved Samples. Variations in appearance of other components are acceptable if they are within the range of approved Samples and are assembled or installed to minimize contrast.

PART 3 - EXECUTION

3.1 EXAMINATION

A. Examine substrates, areas, and conditions, with Installer present, for compliance with requirements for installation tolerances, metal-faced composite wall panel supports, and other conditions affecting performance of the Work.

COMPOSITE WALL PANELS 074213.23 - 9

1. Examine wall framing to verify that panel support members and anchorage have been installed within alignment tolerances required by metal-faced composite wall panel manufacturer.

2. Examine wall sheathing to verify that sheathing joints are supported by framing or blocking and that installation is within flatness tolerances required by metal-faced composite wall panel manufacturer.

3. Verify that weather-resistant sheathing paper has been installed over sheathing or backing substrate to prevent air infiltration or water penetration.

B. Examine roughing-in for components and systems penetrating metal-faced composite wall panels to verify actual locations of penetrations relative to seam locations of panels before panel installation.

C. For the record, prepare written report, endorsed by Installer, listing conditions detrimental to performance of the Work.

D. Proceed with installation only after unsatisfactory conditions have been corrected.

3.2 PREPARATION – LOCATIONS NOT FRAMED, CLAD AND WATERPROOFED

A. Miscellaneous Framing:

1. Provide materials in compliance with requirements of Section 054000 “Cold Formed Metal Framing”.

2. Install subgirts, base angles, sills, furring, and other miscellaneous wall panel support members and anchorage according to ASTM C 754 and metal-faced composite wall panel manufacturer's written instructions.

B. Substrate: Provide sheathing per this section over framing with all joints square and true and surfaces closely aligned and forming a single plane. .

1. Provide any minor gap between panels as recommended by the sheathing or cement board manufacturer to accommodate material expansion.

2. Substrate board shall be continuous around corners including at copings and soffit areas;

use corner bead or sheet metal angle trim recommended by the board manufacturer as necessary to maintain sharp and true lines.

3. Anchors to be flush with surface or surface to be taped and finished to produce flat unblemished planes.

C. Waterproofing Membrane: Cover all substrate surfaces with continuous layer of self-adhering sheet membrane per this section with edges sealed and all joints lapped and sealed according to membrane manufacturer’s recommendations.

3.3 METAL-FACED COMPOSITE WALL PANEL INSTALLATION

A. General: Install metal-faced composite wall panels according to manufacturer's written instructions in orientation, sizes, and locations indicated on Drawings. Install panels perpendicular to girts and subgirts unless otherwise indicated. Anchor panels and other components of the Work securely in place, with provisions for thermal and structural movement.

1. Commence metal-faced composite wall panel installation and install minimum of 300 sq.

ft. in presence of factory-authorized representative.

2. Shim or otherwise plumb substrates receiving metal-faced composite wall panels.

COMPOSITE WALL PANELS 074213.23 - 10

3. Install flashing and trim as metal-faced composite wall panel work proceeds.

B. Fasteners:

1. Aluminum Wall Panels: Use aluminum or stainless-steel fasteners for surfaces exposed to the exterior and aluminum or galvanized-steel fasteners for surfaces exposed to the interior.

C. Metal Protection: Where dissimilar metals will contact each other or corrosive substrates, protect against galvanic action as recommended by metal-faced composite wall panel manufacturer.

D. Attachment System Installation, General: Install attachment system required to support metal-faced composite wall panels and to provide a complete weathertight wall system, including subgirts, perimeter extrusions, tracks, drainage channels, panel clips, and anchor channels.

1. Include attachment to supports, panel-to-panel joinery, panel-to-dissimilar-material joinery, and panel-system joint seals.

2. Do not begin installation until weather barrier and flashings that will be concealed by composite panels are installed.

E. Rainscreen-Principle Installation: Provide manufacturer's standard pressure-equalized, rainscreen-principle system with vertical channel that provides support and complete secondary drainage system, draining at base of wall. Leave horizontal and vertical joints with open reveal.

1. Install wall panels to allow individual panels to "free float" and be installed and removed without disturbing adjacent panels.

3.4 ACCESSORY INSTALLATION

A. General: Install accessories with positive anchorage to building and weathertight mounting and provide for thermal expansion. Coordinate installation with flashings and other components.

1. Install components required for a complete metal-faced composite wall panel assembly including trim, copings, flashings, gaskets, fillers, closure strips, and similar items.

B. Flashing and Trim: Comply with performance requirements, manufacturer's written installation instructions, and SMACNA's "Architectural Sheet Metal Manual." Provide concealed fasteners where possible, and set units true to line and level as indicated. Install work with laps, joints, and seams that will be permanently watertight and weather resistant.

3.5 ERECTION TOLERANCES

A. Installation Tolerances: Shim and align metal-faced composite wall panel units within installed tolerance of 1/4 inch in 20 feet, nonaccumulative, on level, plumb, and location lines as indicated and within 1/8-inch offset of adjoining faces and of alignment of matching profiles.

3.6 FIELD QUALITY CONTROL

A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust completed metal-faced composite wall panel installation, including accessories.

COMPOSITE WALL PANELS 074213.23 - 11

B. Metal-faced composite wall panels will be considered defective if they do not pass tests and inspections.

C. Additional tests and inspections, at Contractor's expense, will be performed to determine compliance of replaced or additional work with specified requirements.

D. Prepare test and inspection reports.

3.7 CLEANING

A. Remove temporary protective coverings and strippable films, if any, as metal-faced composite wall panels are installed unless otherwise indicated in manufacturer's written installation instructions. On completion of metal-faced composite wall panel installation, clean finished surfaces as recommended by panel manufacturer. Maintain in a clean condition during construction.

B. After metal-faced composite wall panel installation, clear weep holes and drainage channels of obstructions.

C. Replace metal-faced composite wall panels that have been damaged or have deteriorated beyond successful repair by finish touchup or similar minor repair procedures.

END OF SECTION 074213.23