RFI 03_question 7. response attach. 02.pdf

PDF 140 KB Posted

Attached to
PBXP 222050 - B403 CYBER REPAIR
Solicitation number
W50S8R26RA005
Issued by

About this file

This is a technical design detail drawing for floor drains at the secure boundary of Building B403 at Mansfield Lahm Air National Guard Base, Ohio, as part of a Repair B403 for Cyber project. The drawing is submitted by Jacobs Government Services (2600 Michelson Sr, Suite 500, Irvine, CA 92612) and serves as a response to RFI 03, Question 7, with project number PBXP222050 and federal contract number FA877006.

The diagram illustrates floor drain and vent piping options in the secured area, featuring a 5-foot section of stainless steel drain line with all welded joints. Key specifications include shielding as required by architectural and structural drawings, stainless steel band clamps, transition to CPVC as required, shielding extension 6 inches minimum above the finished floor, shielding extension 3 inches minimum below the slab bottom, bonding around the drain body, and overlapping the drain as required with secure attachment. The detail provides a cross-sectional view of the drain penetration through the finished floor and concrete slab, showing the relationship between drainage infrastructure and security boundary requirements at the facility.

View the file

Other files

File Type Posted
W50S8R26RA005 0005_B403 CYBER Repair (conformed version).pdf PDF
W50S8R26RA005 0005_B403 CYBER Repair.pdf PDF
W50S8R26RA005 0004_B403 CYBER Repair.pdf PDF
W50S8R26RA005 0004_B403 CYBER Repair (conformed version).pdf PDF
RFI and Response Document (as of 07 July)_final.pdf PDF
RFI 04_question 6. attach._Geotech Report.pdf PDF
RFI and Response Document (as of 03 July).pdf PDF
RFI 03_question 7. response attach. 01.pdf PDF
RFI 02_question 8. response attachment.pdf PDF
RFI and Response Document (as of 02 July).pdf PDF
W50S8R26RA005 0003_B403 CYBER Repair (conformed version).pdf PDF
W50S8R26RA005 0003_B403 CYBER Repair.pdf PDF
W50S8R26RA005 0002_B403 CYBER Repair.pdf PDF
Pre-Proposal Conference minutes_B403 CYBER.pdf PDF
W50S8R26RA005 0002_B403 CYBER Repair (conformed version).pdf PDF
RFI and Response Document (as of 09 June).pdf PDF
EXHIBIT A rev01.pdf PDF
Pre-Proposal Conference-slides.pptx PPTX presentation
Pre-Proposal sign-in sheet.pdf PDF
ATTACHMENT 06_B403 Cyber_Drawings (Full size)_B3.pdf PDF
ATTACHMENT 05_B403 Cyber_Drawings (Half size)_B3.pdf PDF
ATTACHMENT 04_B403 Cyber_Specificatioins (Div 26-33)_B3.pdf PDF
ATTACHMENT 03_B403 Cyber_Specifications (Div 09-25)_B3.pdf PDF
ATTACHMENT 02_B403 Cyber_Specifications (Div 01-08)_B3.pdf PDF
ATTACHMENT 08_IDS Justification and Approval.pdf PDF
ATTACHMENT 05_B403 Cyber_Drawings (Half size)_B3.pdf PDF
ATTACHMENT 01_B403 Cyber_Narrative_B3.pdf PDF
W50S8R26RA005 0001_B403 CYBER Repair.pdf PDF
ATTACHMENT 06_B403 Cyber_Drawings (Full size)_B3.pdf PDF
W50S8R26RA005 0001_B403 CYBER Repair (conformed version).pdf PDF
ATTACHMENT 07_B403 Cyber_Interior Design Specs and Drawings_B3.pdf PDF
EXHIBIT D_Letter of Commitment.docx DOCX document
EXHIBIT C_Reference Questionnaire Package.docx DOCX document
EXHIBIT A.docx DOCX document
EXHIBIT B.docx DOCX document
W50S8R26RA005_B403 CYBER Repair.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

1. SHIELDING AS REQUIRED BASED ON ARCHITECTURAL AND STRUCTURAL

DRAWINGS.

2. STAINLESS STEEL BAND CLAMP.

3. TRANSITION TO CPVC AS REQUIRED.

4. EXTEND SHIELDING UP A MINIMUM OF 6" ABOVE FINISHED FLOOR - COORDINATE

WITH SHIELDING CONTRACTOR.

5. EXTEND SHIELDING DOWN A MINIMUM OF 3" BELOW THE BOTTOM OF THE SLAB -

COORDINATE WITH SHIELDING CONTRACTOR.

6. BOND SHIELDING AROUND DRAIN BODY.

7. OVERLAP DRAIN AS REQUIRED - SECURE TO DRAIN AS REQUIRED (TYPICAL).

8. FINISH FLOOR - SEE DETAIL F1/A-505.

LINE WITH ALL WELDED JOINTS

5' OF STAINLESS STEEL DRAIN

FINISHED FLOOR

NOTE: DETAIL/DIAGRAM IS INTENDED TO SHOW OPTIONS FOR DRAIN AND VENT PIPING IN THE

SECURED AREA.

DRAWN BY:

DESIGNED BY:

SUBMITTED BY:

CHECKED BY:

ISSUE DATE:

ANG PROJECT NO.:

SHEET ID:

FLOOR DRAINS AT SECURE BOUNDARY

MANSFIELD LAHM AIR NATIONAL GUARD BASE, OH

JACOBS GOVERNMENT SERVICES

2600 MICHELSON SR, STE 500

IRVINE, CA 92612

Designer

Author

Checker

PBXP222050

REPAIR B403 FOR CYBER

FA877006

RFI 03, Q.7.

SCALE NTS

FLOOR DRAINS AT SECURE BOUNDARY

Sheets
BID RFI 7B - FLOOR DRAINS AT SECURE BOUNDARY

File details come from the government source that posted it. Updated .