ATTACHMENT 03_B403 Cyber_Specifications (Div 09-25)_B3.pdf
PDF 37 MB Posted
- Attached to
- PBXP 222050 - B403 CYBER REPAIR
- Solicitation number
- W50S8R26RA005
About this file
This is a Specification document for the B403 Cyber Repair project (Contract No. PBXP222050) at the 179th Civil Engineering Squadron, Mansfield Lahm ANG Base, Ohio, prepared by Jacobs Government Services Company. The specifications cover Divisions 09-25 of construction work and are organized according to the 2024 International Building Code as modified by UFC 1-200-01.
The document contains detailed technical specifications across multiple construction divisions including finishes (gypsum board, ceramic tiling, acoustical ceilings, resilient flooring, static-control flooring), specialties, equipment, fire suppression, plumbing, HVAC systems, integrated automation with cybersecurity controls, and electrical/communications systems. Key product requirements include: gypsum board with minimum 5 percent post-consumer or 20 percent post-industrial recycled content; porcelain and ceramic tile with specific water absorption rates and breaking strength standards; acoustical ceiling materials with sound absorption ratings; resilient flooring with electrical conductivity specifications; and HVAC equipment with BACnet direct digital control systems. Materials must comply with environmental standards including CDPH Section 01350 emissions limits and indoor air quality certifications (Greenguard Gold or equivalent). Installation requirements reference ASTM standards, manufacturer instructions, and code compliance. The specifications mandate comprehensive submittals including shop drawings, product data, test reports, and certifications for government approval, with particular emphasis on cybersecurity for facility-related control systems across fire/life safety, building control, and electronic security systems.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T Y P E B - 3 F I N A L
Repair B403 for Cyber Contract No. PBXP222050
Specifications (Divisions 09-25)
Prepared for
179th Civil Engineering Squadron
Ohio Air National Guard
Mansfield Lahm ANG Base, OH
May 2026
Jacobs Government Services Company
2600 Michelson Drive, Suite 500
Irvine, CA 92612
REPAIR B403 FOR CYBER FA877006_B403
PROJECT TABLE OF CONTENTS
DIVISION 01 - GENERAL REQUIREMENTS
01 11 00 02/24 SUMMARY OF WORK
01 14 00 11/22, CHG 1: 02/23 WORK RESTRICTIONS
01 20 00 11/20, CHG 3: 02/23 PRICE AND PAYMENT PROCEDURES
01 30 00 11/20, CHG 3: 08/23 ADMINISTRATIVE REQUIREMENTS
01 32 01.00 10 08/23 PROJECT SCHEDULE
01 32 52 04/26 SPECIAL SECURITY (24 NOV 2025)
01 33 00 08/18, CHG 4: 02/21 SUBMITTAL PROCEDURES
01 33 29 02/21 SUSTAINABILITY REQUIREMENTS AND
REPORTING
01 35 13 11/20, CHG 1: 02/22 SPECIAL PROJECT PROCEDURES
01 35 26 11/20, CHG 4: 08/23 GOVERNMENTAL SAFETY REQUIREMENTS
01 42 00 02/19, CHG 1: 08/23 SOURCES FOR REFERENCE PUBLICATIONS
01 45 00 08/23 QUALITY CONTROL
01 45 35 05/24 SPECIAL INSPECTIONS
01 50 00 11/20, CHG 2: 08/22 TEMPORARY CONSTRUCTION FACILITIES AND
CONTROLS
01 57 19 08/22 TEMPORARY ENVIRONMENTAL CONTROLS
01 58 00 08/19, CHG 5: 08/22 PROJECT IDENTIFICATION
01 74 19 02/19, CHG 3: 11/21 CONSTRUCTION WASTE MANAGEMENT AND
DISPOSAL
01 78 00 05/19, CHG 1: 08/21 CLOSEOUT SUBMITTALS
01 78 23 05/23 OPERATION AND MAINTENANCE DATA
01 91 00.15 05/23, CHG 2: 11/23 BUILDING COMMISSIONING
DIVISION 02 - EXISTING CONDITIONS
02 41 00 08/22 DEMOLITION AND DECONSTRUCTION
DIVISION 03 - CONCRETE
03 01 00 02/18 REHABILITATION OF CONCRETE
03 30 00 02/19, CHG 9: 08/24 CAST-IN-PLACE CONCRETE
DIVISION 04 - MASONRY
04 20 00 11/15, CHG 2: 05/19 UNIT MASONRY
DIVISION 05 - METALS
05 05 20 05/22, CHG 1: 08/24 POST-INSTALLED CONCRETE AND MASONRY
ANCHORS
05 05 23.13 10 08/18 ULTRASONIC INSPECTION OF WELDMENTS
05 05 23.16 08/18 STRUCTURAL WELDING
05 12 00 08/18, CHG 2: 05/21 STRUCTURAL STEEL
05 50 13 08/24 MISCELLANEOUS METAL FABRICATIONS
05 51 33 08/24 METAL LADDERS
05 52 00 08/23 METAL RAILINGS
DIVISION 06 - WOOD, PLASTICS, AND COMPOSITES
06 41 16.00 10 08/10, CHG 1: 11/18 PLASTIC-LAMINATE-CLAD ARCHITECTURAL
CABINETS
06 61 16 08/20 SOLID SURFACING FABRICATIONS
DIVISION 07 - THERMAL AND MOISTURE PROTECTION
PROJECT TABLE OF CONTENTS Page 1
07 19 00 08/23 WATER REPELLENTS
07 21 13 08/23 BOARD AND BLOCK INSULATION
07 21 16 08/23 MINERAL FIBER BLANKET INSULATION
07 21 23 08/23 LOOSE FILL THERMAL INSULATION
07 27 10 08/23 BUILDING AIR BARRIER SYSTEM
07 42 63 05/11, CHG 4: 08/20 FABRICATED WALL PANEL ASSEMBLIES
07 60 00 08/23 FLASHING AND SHEET METAL
07 84 00 05/10, CHG 1: 08/13 FIRESTOPPING
07 92 00 08/23 JOINT SEALANTS
DIVISION 08 - OPENINGS
08 11 13 08/20 STEEL DOORS AND FRAMES
08 13 73 02/11 SLIDING DOORS
08 31 00 05/17, CHG 1: 08/18 ACCESS DOORS AND PANELS
08 34 73 11/19, CHG 1: 02/21 SOUND CONTROL DOOR ASSEMBLIES
08 71 00 02/16, CHG 4: 02/22 DOOR HARDWARE
08 81 00 05/19 GLAZING
08 91 00 08/20 METAL WALL LOUVERS
DIVISION 09 - FINISHES
09 22 00 08/24 SUPPORTS FOR PLASTER AND GYPSUM BOARD
09 29 00 08/24 GYPSUM BOARD
09 30 10 08/20 CERAMIC, QUARRY, AND GLASS TILING
09 51 00 08/20 ACOUSTICAL CEILINGS
09 62 38 08/17, CHG 1: 08/18 STATIC-CONTROL FLOORING
09 65 00 11/24 RESILIENT FLOORING
09 68 00 11/24 CARPETING
09 69 13 11/24 RIGID GRID ACCESS FLOORING
09 84 20 08/16, CHG 1: 08/18 ACOUSTICAL WALL PANELS
09 90 00 02/21 PAINTS AND COATINGS
DIVISION 10 - SPECIALTIES
10 14 00.10 08/17, CHG 1: 11/18 EXTERIOR SIGNAGE
10 14 00.20 08/20 INTERIOR SIGNAGE
10 21 13 08/20 TOILET COMPARTMENTS
10 22 39 08/20 FOLDING PANEL PARTITIONS
10 26 00 08/20 WALL AND DOOR PROTECTION
10 28 13 08/20 TOILET ACCESSORIES
10 44 16 11/19 FIRE EXTINGUISHERS
10 51 13 08/24 LOCKERS
DIVISION 11 - EQUIPMENT
11 31 13 08/17, CHG 2: 11/24 ELECTRIC KITCHEN EQUIPMENT
DIVISION 12 - FURNISHINGS
DIVISION 13 - SPECIAL CONSTRUCTION
PROJECT TABLE OF CONTENTS Page 2
***REMOVED***
13 49 20.00 10 10/07 RF SHIELDING
DIVISION 21 - FIRE SUPPRESSION
21 13 13 08/20 WET PIPE SPRINKLER SYSTEMS, FIRE
PROTECTION
DIVISION 22 - PLUMBING
22 00 00 05/24, CHG 1: 11/24 PLUMBING, GENERAL PURPOSE
DIVISION 23 - HEATING, VENTILATING, AND AIR CONDITIONING (HVAC)
23 05 48.19 02/25 SEISMIC BRACING FOR MECHANICAL SYSTEMS
23 05 93 11/15 TESTING, ADJUSTING, AND BALANCING FOR
HVAC
23 07 00 08/24 THERMAL INSULATION FOR MECHANICAL
SYSTEMS
23 08 00 05/23, CHG 1: 08/24 COMMISSIONING OF MECHANICAL AND
PLUMBING SYSTEMS
23 09 00 08/24 INSTRUMENTATION AND CONTROL FOR HVAC
23 09 13 11/15, CHG 2: 05/21 INSTRUMENTATION AND CONTROL DEVICES
FOR HVAC
23 09 23.02 08/24 BACNET DIRECT DIGITAL CONTROL FOR HVAC
AND OTHER BUILDING CONTROL SYSTEMS
23 09 53.00 20 02/10, CHG 3: 08/24 SPACE TEMPERATURE CONTROL SYSTEMS
23 11 20 05/20 FACILITY GAS PIPING
23 23 00 08/21 REFRIGERANT PIPING
23 30 00 02/25 HVAC AIR DISTRIBUTION
23 81 00 05/24 DECENTRALIZED UNITARY HVAC EQUIPMENT
23 81 23 11/20 COMPUTER ROOM AIR CONDITIONING UNITS
DIVISION 25 - INTEGRATED AUTOMATION
25 05 11.21 08/24 CYBERSECURITY FOR FACILITY-RELATED
CONTROL SYSTEMS FIRE & LIFE SAFETY
25 05 11.23 08/24 CYBERSECURITY FOR FACILITY-RELATED
CONTROL SYSTEMS BUILDING CONTROL SYSTEM
25 05 11.28 08/24 CYBERSECURITY FOR FACILITY-RELATED
CONTROL SYSTEMS ELECTRONIC SECURITY
SYSTEMS
DIVISION 26 - ELECTRICAL
26 05 48 11/23 SEISMIC PROTECTION FOR ELECTRICAL
EQUIPMENT
26 05 73 08/23 POWER SYSTEM STUDIES
26 08 00 11/22 APPARATUS INSPECTION AND TESTING
26 12 19 05/24 PAD-MOUNTED, LIQUID-FILLED,
MEDIUM-VOLTAGE TRANSFORMERS
26 20 00 08/23 INTERIOR DISTRIBUTION SYSTEM
26 27 13.10 30 10/07, CHG 2: 08/18 ELECTRIC METERS
26 29 23 02/20, CHG 1: 05/21 ADJUSTABLE SPEED DRIVE (ASD) SYSTEMS
UNDER 600 VOLTS
26 32 15 05/24 ENGINE-GENERATOR SET STATIONARY
15-2500 KW, WITH AUXILIARIES
26 33 53 05/19 STATIC UNINTERRUPTIBLE POWER SUPPLY
(UPS)
26 36 23 05/20, CHG 1: 08/21 AUTOMATIC TRANSFER SWITCHES AND
PROJECT TABLE OF CONTENTS Page 3
BY-PASS/ISOLATION SWITCH
26 41 00 08/23 LIGHTNING PROTECTION SYSTEM
26 51 00 05/20, CHG 2: 11/21 INTERIOR LIGHTING
26 56 00 08/21 EXTERIOR LIGHTING
DIVISION 27 - COMMUNICATIONS
27 10 00 08/11 BUILDING TELECOMMUNICATIONS CABLING
SYSTEM
DIVISION 28 - ELECTRONIC SAFETY AND SECURITY
28 08 10 08/23 ELECTRONIC SECURITY SYSTEM ACCEPTANCE
TESTING
28 10 05 05/24 ELECTRONIC SECURITY SYSTEMS (ESS)
28 31 76 08/20 INTERIOR FIRE ALARM AND MASS
NOTIFICATION SYSTEM, ADDRESSABLE
DIVISION 31 - EARTHWORK
31 00 00 08/23 EARTHWORK
DIVISION 32 - EXTERIOR IMPROVEMENTS
32 11 20 05/22 BASE COURSE FOR RIGID PAVING
32 13 13.06 05/20 PORTLAND CEMENT CONCRETE PAVEMENT FOR
ROADS AND SITE FACILITIES
32 15 00 05/17 AGGREGATE SURFACING
32 16 19 05/18 CONCRETE CURBS, GUTTERS AND SIDEWALKS
32 31 13 11/21 CHAIN LINK FENCES AND GATES
DIVISION 33 - UTILITIES
33 71 02 08/21 UNDERGROUND ELECTRICAL DISTRIBUTION
33 82 00 02/26 TELECOMMUNICATIONS OUTSIDE PLANT (OSP)
-- End of Project Table of Contents --
PROJECT TABLE OF CONTENTS Page 4
REPAIR B403 FOR CYBER
MANSFIELD LAHM ANGB, OH
OHIO AIR NATIONAL GUARD
PROJECT NO. PBXP222050
CODES AND STANDARDS REFERENCED HEREIN
THIS PROJECT IS DESIGNED IN ACCORDANCE WITH THE 2024 INTERNATIONAL BUILDING
CODE (IBC) AS MODIFIED BY UFC 1-200-01, 17 DECEMBER 2024.
THE UNITED FACILITIES GUIDE SPECIFICATIONS (UFGS) ARE UPDATED REGULARLY. THE
VERSION OR EDITION OF CODES AND STANDARDS REFERENCED HEREIN MAY DIFFER FROM
THOSE SPECIFIED IN CHAPTER 35 OF THE IBC. IN THE EVENT OF DISCREPENCIES
REGARDING VERSION OR EDITION OF CODES AND STANDARDS, THE IBC WILL TAKE
PRECEDENCE.
SECTION 09 22 00
SUPPORTS FOR PLASTER AND GYPSUM BOARD
08/24
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
AISC 341 (2016) Seismic Provisions for Structural Steel Buildings
AMERICAN IRON AND STEEL INSTITUTE (AISI)
AISI S220 (2020) North American Standard for Cold-Formed Steel Nonstructural Framing
ASTM INTERNATIONAL (ASTM)
ASTM A653/A653M (2025a) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM C635/C635M (2022) Standard Specification for Manufacture, Performance, and Testing of Metal Suspension Systems for Acoustical Tile and Lay-In Panel Ceilings
ASTM C754 (2020) Standard Specification for Installation of Steel Framing Members to Receive Screw-Attached Gypsum Panel Products
ASTM C841 (2023) Installation of Interior Lathing and Furring
ASTM C847 (2018; R 2024) Standard Specification for Metal Lath
ICC EVALUATION SERVICE, INC. (ICC-ES)
ICC-ES AC98 (2021) Accreditation Criteria for Inspection Agencies
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SECTION 09 22 00 Page 1
SD-02 Shop Drawings
Metal Support Systems ; G
SD-03 Product Data
Metal Support Systems
Recycled Content for Metal Support Systems ; S
1.2.1 Sustainable Design Submittals
a. Product Data: For recycled content, indicating postconsumer and preconsumer recycled content and cost.
b. Environmental Product Declaration (EPD): For each product.
c. Construction and Demolition Waste Management: For each product.
d. Health Product Declaration (HPD): Provide documentation confirming product compliance with one of the following:
(1) Option 1: Material Ingredient Reporting: Use at least 20 different permanently installed products from at least five different manufacturers that use one of the qualifying programs to demonstrate the chemical inventory of the product to at least
0.1 percent (1000 ppm).
(2) Option 2: Material Ingredient Optimization: Use products that have a compliant material ingredient optimization report or action plan. Use at least five permanently installed products sourced from at least three different manufacturers.
SD-04 Evaluation Reports: Submit evaluation reports certified under an independent third-party inspection program administered by an agency accredited by IAS to ICC-ES AC98 accreditation criteria for inspection agencies.
1.3 DELIVERY, STORAGE, AND HANDLING
Deliver materials to the job site and store in ventilated dry locations permitting easy access for inspection and handling. If materials are stored outdoors, stack materials off the ground, supported on a level platform, and fully protected from the weather. Handle materials carefully to prevent damage. Remove damaged items and provide new items.
PART 2 PRODUCTS
2.1 MATERIALS
Provide steel materials for metal support systems with either a EQ (Equivalent Coating) coating or a galvanized coating AISI S220 G-60 or equivalent; aluminum coating T1-25; or a 55-percent aluminum-zinc coating AZ50. Provide support systems and attachments in accordance with AISC 341 in seismic zones.
Provide metal support systems containing a minimum of 20 percent recycled content. Provide data identifying percentage of recycled content for metal support systems .
SECTION 09 22 00 Page 2
2.1.1 Materials for Attachment of Lath
2.1.1.1 Suspended and Furred Ceiling Systems and Wall Furring
ASTM C841 and ASTM C847.
2.1.1.2 Non-load Bearing Wall Framing
AISI S220 .
2.1.2 Materials for Attachment of Gypsum Wallboard
2.1.2.1 Suspended and Furred Ceiling Systems
AISI S220 .
2.1.2.2 Non-load Bearing Wall Framing and Furring
a. Framing Members, General: Comply with AISI S220 for conditions indicated.
(1) Steel Sheet Components: Comply with AISI S220 requirements for metal unless otherwise indicated.
(2) Protective Coating: AISI S220 , provide EQ (Equivalent Coating) coating, galvanized coating G-60 or equivalent. G40 or coating with equivalent corrosion resistance of G40. Provide G-90 coating in high-humidity environments.
b. Studs and Runners: AISI S220 . Use either steel studs and runners or embossed steel studs and runners.
c. AISI S220 , but not thinner than 0.0179 inch thickness, with 0.0329 inch minimum thickness supporting wall hung items such as cabinetwork, equipment and fixtures.
d. Slip-Type Head Joints: Where indicated, provide one of the following:
(1) Slotted Deflection Track: Steel sheet top runner manufactured to prevent cracking of finishes applied to interior partition framing resulting from deflection of structure above; in thickness not less than indicated for studs and in width to accommodate depth of studs.
(2) Clip System: Clips designed for use in head-of-wall deflection conditions that provide a positive attachment of studs to tracks while allowing 1-1/2 inch minimum vertical movement.
(3) Single Long-Leg Track System: Top track with 2 inch deep flanges in thickness not less than indicated for studs, installed with studs friction fit into top track and with continuous bridging and spacer bar located within 12 inches of the top of studs to provide lateral bracing.
e. Firestop Tracks: Top runner manufactured to allow partition heads to expand and contract with movement of the structure while maintaining continuity of fire-resistance-rated assembly indicated; in thickness not less than indicated for studs and in width to accommodate depth of
SECTION 09 22 00 Page 3 studs.
f. Backing Plate: Fire-retardant-treated wood blocking used for fixture attachment.
g. Sound Isolation Clips: Used with 18 mil, (25 gauge), drywall furring channels to provide acoustical separation.
h. Framed Openings: Galvanized-steel, one-piece header and jamb studs in lieu of built-up members.
i. Partial Wall Framing Connection: Stud connector designed to support out-of-plane loading of cantilevered partial wall systems that are unsupported at the top track.
j. Drywall Penetration Barrier Mesh: Supply and install security mesh, as a penetration barrier behind gypsum wallboard walls and/or ceilings, where indicated on Drawings.
2.2 SUSPENSION SYSTEMS
2.2.1 Structural Classification
a. Main Beam/ Tee is to be Fire-Rated Heavy Duty classification in accordance with ASTM C635/C635M.
b. Classification can require wires to be closer together for additional loading when used to support double layer gypsum, verticals, slopes, circles, soffits, canopies, and step conditions which call for loading or unusual designs and shapes in drywall construction.
c. Deflection of fastening suspension system supporting light fixtures, ceiling grilles, access doors, verticals and horizontal loads are to have a maximum deflection of 1/360 of the span.
2.2.2 Components
a. Main Beam/ Tee: Is to be commercial quality, cold-rolled steel, double-web construction (minimum 0.0179 inch prior to protective coating, AISI S220 ), hot dipped galvanized (per ASTM A653/A653M ) and 1-1/2 inch high minimum with knurled face .
b. Drywall Grid Cross Tees: Are to be commercial quality, cold-rolled steel, double-web steel construction (minimum 0.0179 inch prior to protective coating, AISI S220 ), hot dipped galvanized (minimum G40 or G90 in accordance with ASTM A653/A653M ) and 1-1/2 inch high minimum with knurled face.
c. Wall Molding/ Channel:
(1) 2 inch by 2 inch, knurled surface, pre-punched holes in top flange 4 inch on center, 33 mil (20 gauge)
(2) Locking Angle Molding, 1-1/4 inch by 1-1/4 inch with pre-engineered locking tabs punched 8 inches on center, knurled surface, screw stop hem, pre-punched holes in top flange, 4 inch on center, 18 mil. (25 gauge)
(3) Knurled Angle molding, 1-1/4 inch by 1-1/4 inch, knurled surface, SECTION 09 22 00 Page 4 screw stop hem, pre-punched holes in top flange, 4 inch on center, 18 mil. (25 gauge)
(4) Knurled Angle molding, 1-1/2 inch by 1-1/2 inch, knurled surface, screw stop hem, pre-punched holes in top flange 4 inch on center, 18 mil. (25 gauge)
(5) Simple Curve Knurled Angle Molding, 1-1/2 inch by 1-1/2 inch, knurled face radius 37 inch, screw stop hem, pre-punched holes in top flange, 4 inch on center, 28 mil. (22 gauge)
d. Support Hanger:
(1) Strong Back Support Hanger
(2) Channel beam splice 6 inch used to suspend main beams to 1-1/2 inch black iron carrying channels.
(3) Hanger Wire 12 gauge, galvanized or as noted on drawings.
e. Accessories
(1) Radius Clip
(2) 90 Degree Drywall Angle/ Transition Clip
(3) 45 Degree Drywall Angle/ Transition Clip
(4) 30 Degree Drywall Angle/ Transition Clip
(5) Double Drywall Clip
(6) Wall Attachment Clip
(7) Splice Plate
(8) Dome Hub
(9) Close Mount Attachment clip
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Systems for Attachment of Gypsum Wallboard
3.1.1.1 Suspended and Furred Ceiling Systems
ASTM C754, except provide framing members 16 inches on center unless indicated otherwise.
3.1.1.2 Non-load Bearing Wall Framing and Furring
ASTM C754, except as indicated otherwise. Provide a sealer gasket under bottom of track on concrete slab or foundation.
3.1.1.3 Firestop Tracks
In accordance with manufacturer's installation instructions, applicable
SECTION 09 22 00 Page 5 building code and UL assembly.
3.1.1.4 Backing Plates
In accordance with manufacturer's installation instructions.
3.1.1.5 Framed Openings
In accordance with manufacturer's installation instructions and approved design.
3.1.1.6 Partial Wall Framing Connection
In accordance with manufacturer's installation instructions. Anchor to floor as designed by Engineer of Record. Provide a sealer gasket under bottom of track on concrete slab or foundation.
3.1.1.7 Drywall Penetration Barrier Mesh
Per manufacturer's instructions. Installation and layout of the panels to be approved by General Contractor prior to installation, with the intent to attached panels on vertical framing members. Panels may be installed in either direction. Attachment with approved clips and threaded fasteners.
3.1.1.8 Suspension Systems
a. Install suspension system and panels in accordance with the manufacturer's instructions, in compliance with ASTM C635/C635M installation standard, and with applicable codes as required by the authorities having jurisdiction.
b. Install according to approved Pre-construction drawings recommended for complex projects. Contact your local manufacturer representative for support.
c. Drywall Grid System can be installed in interior or exterior applications.
d. Install hanger wire as required with necessary on center spacing to support expected ceiling load requirements, following local practices, codes and regulations. Provide additional wires at light fixtures, grilles, and access doors where necessary. A pigtail knot is to be used with three tight wraps at top and bottom fastening locations.
e. Main tees/ beams are to be suspended from the overhead construction with hanger wire, spaced as required for expected ceiling loads, along the length of the main beams.
f. Install cross tees at on center spacing as specified by the drywall manufacturer. Typical drywall cross tee spacing:
(1) 16 inches on center with 5/8 or 1/2 inch gypsum board.
(2) 24 inches on center with 5/8 inch gypsum board.
g. Use channel molding or angle molding to interface with Drywall Grid System to provide perimeter attachment or to obtain drop soffits, verticals, slopes.
SECTION 09 22 00 Page 6
3.2 ERECTION TOLERANCES
Provide framing members which will be covered by finish materials such as wallboard, plaster, or ceramic tile set in a mortar setting bed, within the following limits:
a. Layout of walls and partitions: 1/4 inch from intended position;
b. Plates and runners: 1/4 inch in 8 feet from a straight line;
c. Studs: 1/4 inch in 8 feet out of plumb, not cumulative; and
d. Face of framing members: 1/4 inch in 8 feet from a true plane.
Provide framing members which will be covered by ceramic tile set in dry-set mortar, latex-portland cement mortar, or organic adhesive within the following limits:
a. Layout of walls and partitions: 1/4 inch;
b. Plates and runners: 1/8 inch in 8 feet from a straight line;
c. Studs: 1/8 inch in 8 feet out of plumb, not cumulative and must not exceed minimum fastening requirements of sheathing or other finishing materials; and
d. Face of framing members: 1/8 inch in 8 feet from a true plane.
-- End of Section --
SECTION 09 22 00 Page 7
THIS PAGE INTENTIONALLY LEFT BLANK
SECTION 09 22 00 Page 8
SECTION 09 29 00
GYPSUM BOARD
08/24
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI A108/A118/A136.1 (2024) American National Standard Specifications for the Installation of Ceramic Tile
ASTM INTERNATIONAL (ASTM)
ASTM A653/A653M (2025a) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process
ASTM B221 (2021) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes
ASTM C475/C475M (2017; R 2022) Standard Specification for Joint Compound and Joint Tape for Finishing Gypsum Board
ASTM C557 (2003; R 2017) Standard Specification for Adhesives for Fastening Gypsum Wallboard to Wood Framing
ASTM C840 (2024) Standard Specification for Application and Finishing of Gypsum Board
ASTM C954 (2022) Standard Specification for Steel Drill Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Steel Studs from 0.033 in. (0.84 mm) to
0.112 in. (2.84 mm) in Thickness
ASTM C1002 (2022) Standard Specification for Steel Self-Piercing Tapping Screws for the Application of Gypsum Panel Products or Metal Plaster Bases to Wood Studs or Steel Studs
ASTM C1047 (2019) Standard Specification for Accessories for Gypsum Wallboard and Gypsum Veneer Base
ASTM C1178/C1178M (2024) Standard Specification for Glass
SECTION 09 29 00 Page 1
Mat Water-Resistant Gypsum Backing Panel
ASTM C1235 (2022) Standard Specification for Fiber-Mat Reinforced Cementitious Backer Units
ASTM C1288 (2017) Standard Specification for Fiber-Cement Interior Substrate Sheets
ASTM C1396/C1396M (2024) Standard Specification for Gypsum Board
ASTM D226/D226M (2017) Standard Specification for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing
ASTM E336 (2024) Standard Test Method for Measurement of Airborne Sound Attenuation between Rooms in Buildings
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2017; Version 1.2) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
FM GLOBAL (FM)
FM APP GUIDE (updated on-line) Approval Guide https://www.approvalguide.com/
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial Use
GYPSUM ASSOCIATION (GA)
GA 214 (2010) Recommended Levels of Gypsum Board Finish
GA 216 (2016) Application and Finishing of Gypsum Panel Products
GA 600 (2021) Fire Resistance and Sound Control Design Manual
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2022) Adhesive and Sealant Applications
TILE COUNCIL OF NORTH AMERICA (TCNA)
TCNA Hdbk (2017) Handbook for Ceramic, Glass, and Stone Tile Installation
SECTION 09 29 00 Page 2
UL SOLUTIONS (UL)
UL 2818 (2022) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
UL Fire Resistance (2014) Fire Resistance Directory
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-02 Shop Drawings
Control Joint Shop Drawings
SD-03 Product Data
Gypsum Board
Cementitious Backer Units
Glass Mat Moisture-Resistant Gypsum Tile Backing Board
Moisture- and Mold-Resistant Gypsum Backing Board
Trim
Accessories
Recycled Content for Gypsum Board ; S
VOC Content of Joint Compound ; S
SD-06 Test Reports
ASTM E90 Factory Test Report ; G
ASTM E336 Field Test Report ; G
SD-07 Certificates
Asbestos Free Materials ; G
Indoor Air Quality for Gypsum Board ; S
Indoor Air Quality for Non-aerosol Adhesives ; S
Indoor Air Quality for Aerosol Adhesives ; S
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality Certifications
Submit required indoor air quality certifications in one submittal package.
SECTION 09 29 00 Page 3
1.3.1.1 Ceiling and Wall Systems
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.3.1.2 Adhesives and Sealants
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party program that products meet the requirements of this Section. Provide adhesive products certified to meet ASTM C557. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited herein.
1.4 DELIVERY, STORAGE, AND HANDLING
1.4.1 Delivery
Deliver materials in the original packages, containers, or bundles with each bearing the brand name, applicable standard designation, and name of manufacturer, or supplier.
1.4.2 Storage
Keep materials dry by storing inside a sheltered building. Where necessary to store gypsum board, glass mat faced gypsum board, and cementitious backer units outside, store flat and off the ground, properly supported on a level platform, and protected from direct exposure to rain, snow, sunlight, and other extreme weather conditions. Provide adequate ventilation to prevent condensation. Remove plastic wrapping that may inhibit ventilation. Store per manufacturer's recommendations for allowable temperature and humidity range. Do not store panels where temperatures may exceed 125 deg F. Do not store panels near materials that may offgas or emit harmful fumes, such as kerosene heaters, fresh paint, or adhesives. Do not use materials that have visible moisture or biological growth. Do not stack panels higher than manufacturer's recommendations, and no higher than 17 feet.
1.4.3 Handling
Neatly stack gypsum board, glass mat faced gypsum board, and cementitious backer units flat to prevent sagging or damage to the edges, ends, and surfaces. Handle per manufacturer's recommendations.
1.5 QUALIFICATIONS
Furnish type of gypsum board work specialized by the installer with a minimum of 3 years of documented successful experience.
SECTION 09 29 00 Page 4
1.6 ENVIRONMENTAL REQUIREMENTS
Do not expose the gypsum board to excessive sunlight prior to gypsum board application. Maintain a continuous uniform temperature of not less than 50 degrees F and not more than 80 degrees F for at least one week prior to the application of gypsum board work, while the gypsum board application is being done, and for at least one week after the gypsum board is set.
Shield air supply and distribution devices to prevent any uneven flow of air across the plastered surfaces. Provide ventilation to exhaust moist air to the outside during gypsum board application, set, and until gypsum board jointing is dry. In glazed areas, keep windows open top and bottom or side to side 3 to 4 inches. Reduce openings in cold weather to prevent freezing of joint compound when applied. For enclosed areas lacking natural ventilation, provide temporary mechanical means for ventilation.
In unglazed areas subjected to hot, dry winds or temperature differentials from day to night of 20 degrees F or more, screen openings with cheesecloth or similar materials. Avoid rapid drying. During periods of low indoor humidity, provide minimum air circulation following gypsum boarding and until gypsum board jointing complete and is dry.
1.7 FIRE RESISTIVE CONSTRUCTION
Comply with specified fire-rated assemblies for design numbers indicated per UL Fire Resistance or FM APP GUIDE.
PART 2 PRODUCTS
2.1 MATERIALS
Conform to specifications, standards and requirements specified. Provide gypsum board types, gypsum backing board types, cementitious backing units, and joint treating materials manufactured from asbestos free materials only.
2.1.1 Gypsum Board
ASTM C1396/C1396M . Gypsum board must contain a minimum of 5 percent post-consumer recycled content, or a minimum of 20 percent post-industrial recycled content. Provide data identifying percentage of recycled content for gypsum board . Paper facings must contain a minimum of 100 percent recycled paper content. Gypsum cores must contain a minimum of 95 percent post-industrial recycled gypsum content. Gypsum Board must not contain asbestos. Provide gypsum wall board and panels meeting the emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type). Provide certification or validation of indoor air quality for gypsum board .
2.1.1.1 Type X (Special Fire-Resistant)
48 inch wide, 5/8 inch thick, tapered edges.
2.1.2 Regular Moisture- and Mold-Resistant Gypsum Backing Board
ASTM C1396/C1396M
2.1.2.1 Type X (Special Fire-Resistant)
48 inch wide, 5/8 inch thick, tapered edges.
SECTION 09 29 00 Page 5
2.1.3 Glass Mat Moisture-Resistant Gypsum Tile Backing Board
ASTM C1178/C1178M
2.1.3.1 Type X (Special Fire-Resistant)
48 inch wide, 5/8 inch thick, square edges. 2.1.4 Cementitious Backer Units
Cementitious backer units must not contain asbestos. ASTM C1288 or ASTM C1235, ANSI A108/A118/A136.1 and in accordance with the Tile Council of North America ( TCNA Hdbk).
2.1.5 Acoustically Enhanced Gypsum board
48 inch wide, 5/8-inch thick enhanced high density mold-resistant gypsum board with a viscoelastic damping polymer inner layer.
2.1.6 Joint Treatment Materials
ASTM C475/C475M. Product must be low emitting VOC types with VOC limits not exceeding 50 g/L. Joint materials must not contain asbestos. Provide data identifying VOC content of joint compound . Use all purpose joint and texturing compound containing inert fillers and natural binders, including lime compound. Pre-mixed compounds must be free of antifreeze, vinyl adhesives, preservatives, biocides and other slow releasing compounds.
2.1.6.1 Embedding Compound
Specifically formulated and manufactured for use in embedding tape at gypsum board joints and compatible with tape, substrate and fasteners.
2.1.6.2 Finishing or Topping Compound
Specifically formulated and manufactured for use as a finishing compound.
2.1.6.3 All-Purpose Compound
Specifically formulated and manufactured to serve as both a taping and a finishing compound and compatible with tape, substrate, and fasteners.
2.1.6.4 Setting or Hardening Type Compound
Specifically formulated and manufactured for use with fiber glass mesh tape.
2.1.6.5 Joint Tape
Use cross-laminated, tapered edge, reinforced paper, or fiber glass mesh tape recommended by the manufacturer.
2.1.7 Fasteners
2.1.7.1 Screws
ASTM C1002, Type "G", Type "S", or Type "W" steel drill screws for fastening gypsum board to gypsum board, wood framing members, and steel framing members less than 0.033 inch thick. ASTM C954 steel drill screws for fastening gypsum board to steel framing members 0.033 to 0.112 inch
SECTION 09 29 00 Page 6 thick. Provide cementitious backer unit screws with a polymer coating.
2.1.8 Adhesives
Provide non-aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) meeting either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of SCAQMD Rule 1168 . Provide aerosol adhesive products used on the interior of the building (defined as inside of the weatherproofing system) meeting either emissions requirements of CDPH SECTION 01350 (limit requirements for either office or classroom spaces regardless of space type) or VOC content requirements of GS-36. Provide certification or validation of indoor air quality for non-aerosol adhesives applied on the interior of the building (inside of the weatherproofing system). Provide certification or validation of indoor air quality for aerosol adhesives used on the interior of the building (inside of the weatherproofing system).
2.1.8.1 Adhesive for Fastening Gypsum Board to Metal Framing
Not permitted.
2.1.9 Accessories
ASTM C1047. Fabricate from corrosion protected steel designed for intended use. Accessories manufactured with paper flanges are not acceptable. Flanges must be free of dirt, grease, and other materials that may adversely affect bond of joint treatment. Provide prefinished or job decorated materials.
2.1.9.1 Trim
Provide trim, as required:
a. Cornerbeads.
b. Bullnose Beads.
c. LC Beads.
d. L-Beads.
e. U-Beads.
f. Control Joints.
g. Curved-edge Cornerbeads.
h. Base-of-wall Trim.
i. Trim required to complete the work.
2.1.9.2 Materials
Steel: ASTM A653/A653M Galvanized steel assemblies and fasteners.
Aluminum: ASTM B221 6063-T5 alloy aluminum extrusions with a factory applied corrosion inhibiting primer or baked enamel finish and stainless
SECTION 09 29 00 Page 7 steel fasteners.
2.1.10 Asphalt Impregnated Building Felt
Provide a 15 lb asphalt moisture barrier over glass mat covered or reinforced gypsum sheathing. Conforming to ASTM D226/D226M Type 1 (No.
15) for asphalt impregnated building felt.
2.1.11 Water
Provide clean, fresh, and potable water.
PART 3 EXECUTION
3.1 EXAMINATION
3.1.1 Framing and Furring
Verify that framing and furring are securely attached and of sizes and spacing to provide a suitable substrate to receive gypsum board and cementitious backer units. Verify that all blocking, headers and supports are in place to support plumbing fixtures and to receive soap dishes, grab bars, towel racks, and similar items. Do not proceed with work until framing and furring are acceptable for application of gypsum board and cementitious backer units.
3.1.2 Gypsum Board and Framing
Verify that surfaces of gypsum board and framing to be bonded with an adhesive are free of dust, dirt, grease, and any other foreign matter. Do not proceed with work until surfaces are acceptable for application of gypsum board with adhesive.
3.1.3 Masonry and Concrete Walls
Verify that surfaces of masonry and concrete walls to receive gypsum board applied with adhesive are dry, free of dust, oil, form release agents, protrusions and voids, and any other foreign matter. Do not proceed with work until surfaces are acceptable for application of gypsum board with adhesive.
3.1.4 Building Construction Materials
Do not install building construction materials that show visual evidence of biological growth.
3.2 APPLICATION OF GYPSUM BOARD
Apply gypsum board to framing and furring members in accordance with ASTM C840 or GA 216 and the requirements specified. Apply gypsum board with separate panels in moderate contact; do not force in place. Stagger end joints of adjoining panels. Neatly fit abutting end and edge joints.
Use gypsum board of maximum practical length; select panel sizes to minimize waste. Cut out gypsum board to make neat, close, and tight joints around openings. In vertical application of gypsum board, provide panels in lengths required to reach full height of vertical surfaces in one continuous piece. Lay out panels to minimize waste; reuse cutoffs whenever feasible. Surfaces of gypsum board and substrate members may not be bonded together with an adhesive, except where prohibited by fire
SECTION 09 29 00 Page 8 rating(s). Treat edges of cutouts for plumbing pipes, screwheads, and joints with moisture-resistant compound as recommended by the gypsum board manufacturer. Provide type of gypsum board for use in each system specified herein as indicated.
3.2.1 Semi-Solid Gypsum Board Partitions
Provide in accordance with ASTM C840, System IV or GA 216 .
3.2.2 Solid Gypsum Board Partitions
Provide in accordance with ASTM C840, System V or GA 216 .
3.2.3 Adhesive Application to Interior Masonry or Concrete Walls
Apply in accordance with ASTM C840, System VI or GA 216 .
3.2.4 Application of Gypsum Board to Steel Framing and Furring
Apply in accordance with ASTM C840, System VIII or GA 216 .
3.2.5 Gypsum Board for Wall Tile or Tile Base Applied with Adhesive
In dry areas (areas other than tubs, shower enclosures, saunas, steam rooms, gang shower rooms), apply glass mat moisture-resistant gypsum tile backing board or moisture-resistant gypsum backing board in accordance with ASTM C840, System X or GA 216 .
3.2.6 Control Joints
Install expansion and contraction joints in ceilings and walls in accordance with ASTM C840, System XIII or GA 216 . Joints in fire-rated and sound-rated ceiling and walls to maintain the fire and sound rating.
Fill control joints between studs in fire-rated construction with firestopping insulation to match the fire-rating of construction.
3.2.6.1 Control Joint Shop Drawings
a. Submit control joint shop drawings for approval.
b. Install control joints where a partition, wall, or ceiling traverses a construction joint in the base building structure.
c. Install control joints where a wall or partition runs in an uninterrupted straight plane exceeding 30 feet.
d. Install control joints in interior ceilings with a perimeter relief so that linear dimensions between control joints do not exceed 50 feet.
e. Install control joints in interior ceilings without perimeter relief so that linear dimensions between control joints do not exceed 30 feet.
f. Install control joints in exterior ceilings and soffits so that linear dimensions between control joints do not exceed 30 feet.
g. Install control joints or intermediate blocking where ceiling framing members change direction.
h. In addition to the above, install control joints where indicated on
SECTION 09 29 00 Page 9 the drawings as a design accent or architectural feature.
i. Do not install control joints where building or structural expansion or seismic joints are located. Install suitable joint expansion or seismic joint assemblies as indicated on the drawings.
3.3 APPLICATION OF CEMENTITIOUS BACKER UNITS
3.3.1 Application
In wet areas (tubs, shower enclosures, saunas, steam rooms, gang shower rooms), apply cementitious backer units in accordance with ANSI A108/A118/A136.1 . Place a 15 lb asphalt impregnated, continuous felt paper membrane behind cementitious backer units, between backer units and studs or base layer of gypsum board. Place membrane with a minimum 6 inch overlap of sheets laid shingle style.
3.3.2 Joint Treatment
ANSI A108/A118/A136.1 .
3.4 FINISHING OF GYPSUM BOARD
Tape and finish gypsum board in accordance with ASTM C840, GA 214 , and GA 216 . Finish plenum areas above ceilings to Level 1 in accordance with GA 214 . Finish and paint walls required to be sound rated assembly field tested from true floor to true ceiling to Level 5 in accordance with GA 214 .
Finish moisture-resistant gypsum backing board, ASTM C1396/C1396M , to receive ceramic tile to Level 2 in accordance with GA 214 . Finish walls and ceilings to receive a heavy-grade wall covering or heave textured finish before painting to Level 5 in accordance with GA 214 . Finish walls and ceilings without critical lighting to receive flat paints, light textures, or wall coverings to Level 5 in accordance with GA 214 . Unless otherwise specified, finish all gypsum board walls, partitions, and ceilings to Level 5 in accordance with GA 214 . Provide joint, fastener depression, and corner treatment. Tool joints as smoothly as possible to minimize sanding and dust. Do not use self-adhering fiber glass mesh tape with conventional drying type joint compounds; use setting or hardening type compounds only. Provide treatment for moisture-resistant gypsum board as recommended by the gypsum board manufacturer. Protect workers, building occupants, and HVAC systems from gypsum dust.
3.4.1 Uniform Surface
Wherever gypsum board is to receive eggshell, semigloss, or gloss paint finish, or where severe, up or down lighting conditions occur, finish gypsum wall surface in accordance to GA 214 Level 5. In accordance with GA 214 Level 5, apply a thin skim coat of joint compound to the entire gypsum board surface, after the two-coat joint and fastener treatment is complete and dry.
3.5 SEALING
Seal openings around pipes, fixtures, and other items projecting through gypsum board and cementitious backer units as specified in Section 07 92 00 JOINT SEALANTS. Apply material with exposed surface flush with gypsum board or cementitious backer units.
SECTION 09 29 00 Page 10
3.6 FIRE-RESISTANT ASSEMBLIES
Wherever fire-rated construction is indicated, provide materials and application methods, including types and spacing of fasteners, wall and ceiling framing in accordance with the specifications contained in UL Fire Resistance for the Design Number(s) indicated or GA 600 for the File Number(s) indicated. Joints of fire-rated gypsum board enclosures must be closed and sealed in accordance with UL test requirements or GA requirements. Seal penetrations through rated partitions and ceilings tight in accordance with tested systems.
3.7 SOUND RATED ASSEMBLIES
When sound rated assemblies are required, provide materials and application methods, including panels, insulation, types and spacing of fasteners, wall and ceiling framing in accordance with the contract document and the description of the assembly in the ASTM E90 Factory Test Report . Seal partitions continuously with acoustical foam or sealant (both sides) and finished to match wall wherever it abuts another element such as the floor, ceiling, wall, column, mullion, or another system or assembly.
3.8 PATCHING
Patch surface defects in gypsum board to a smooth, uniform appearance, ready to receive finishes.
3.9 SOUND RATED ASSEMBLY FIELD TESTING
Provide third party testing of sound rated assemblies tested in accordance with ASTM E336. Provide the ASTM E336 Field Test Report verifying that the installed assemblies perform no less than five ASTC rating points below the ASTM E90 Factory Test Report . Examine, modify adjust, and retest any installation not meeting the STC Rating until compliance is obtained.
SECTION 09 29 00 Page 11
SECTION 09 29 00 Page 12
SECTION 09 30 10
CERAMIC, QUARRY, AND GLASS TILING
08/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI A108/A118/A136.1 (2024) American National Standard Specifications for the Installation of Ceramic Tile
ANSI A137.1 (2019) American National Standards Specifications for Ceramic Tile
ANSI A137.2 (2019) American National Standards Specifications for Glass Tile
ANSI A137.3/A108.19 (2017) American National Standard Specifications for Gauged Porcelain Tile and Gauged Porcelain Tile Panels/Slabs
ASTM INTERNATIONAL (ASTM)
ASTM C33/C33M (2024a) Standard Specification for Concrete Aggregates
ASTM C144 (2024) Standard Specification for Aggregate for Masonry Mortar
ASTM C150/C150M (2024) Standard Specification for Portland Cement
ASTM C206 (2014; R 2022) Standard Specification for Finishing Hydrated Lime
ASTM C207 (2024) Standard Specification for Hydrated Lime for Masonry Purposes
ASTM C373 (2018; R 2023)Standard Test Methods for Determination of Water Absorption and Associated Properties by Vacuum Method for Pressed Ceramic Tiles and Glass Tiles and Boil Method for Extruded Ceramic Tiles and Non-tile Fired Ceramic Whiteware Products
ASTM C648 (2020) Standard Test Method for Breaking Strength of Ceramic Tile
ASTM C1027 (2009; R 2017) Standard Test Method for Determining Visible Abrasion Resistance of
SECTION 09 30 10 Page 1
Glazed Ceramic Tile
CALIFORNIA DEPARTMENT OF PUBLIC HEALTH (CDPH)
CDPH SECTION 01350 (2017; Version 1.2) Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources using Environmental Chambers
GREEN SEAL (GS)
GS-36 (2013) Adhesives for Commercial Use
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
SOUTH COAST AIR QUALITY MANAGEMENT DISTRICT (SCAQMD)
SCAQMD Rule 1168 (2022) Adhesive and Sealant Applications
TILE COUNCIL OF NORTH AMERICA (TCNA)
TCNA Hdbk (2017) Handbook for Ceramic, Glass, and Stone Tile Installation
U.S. NATIONAL ARCHIVES AND RECORDS ADMINISTRATION (NARA)
36 CFR 1191 Americans with Disabilities Act (ADA) Accessibility Guidelines for Buildings and Facilities; Architectural Barriers Act (ABA) Accessibility Guidelines
UL SOLUTIONS (UL)
UL 2818 (2022) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:
SD-03 Product Data
Porcelain Tile ; G
Recycled Content for Porcelain Tile ; S
Gauged Porcelain Tile ; G
Glazed Ceramic Wall Tile ; G
Recycled Content for Glazed Ceramic Wall Tile ; S
Transition Strips ; G
SECTION 09 30 10 Page 2
Metal Strips ; G
Setting-Bed ; G
Mortar, Grout, and Adhesive ; G
Waterproof Membrane ; G
Crack Isolation Membrane ; G
SD-04 Samples
Tile ; G
Accessories ; G
Transition Strips ; G
Metal Strips ; G
Grout ; G
SD-07 Certificates
Indoor Air Quality for Adhesives ; S
Indoor Air Quality for Sealants ; S
Water Absorption Rates
SD-08 Manufacturer's Instructions
Manufacturer's Approved Cleaning Instructions
SD-10 Operation and Maintenance Data
Porcelain Tile , Data Package 1; G
Glazed Ceramic Wall Tile , Data Package 1; G
Transition Strips , Data Package 1; G
Metal Strips , Data Package 1; G
1.3 CERTIFICATIONS
1.3.1 Indoor Air Quality Certifications
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide certification or validation by other third-party programs that products meet the requirements of this Section. Provide current product certification documentation from certification body. When product does not have certification, provide validation that product meets the indoor air quality product requirements cited in this Section.
SECTION 09 30 10 Page 3
1.3.2 Water Absorption Rates Certification
Provide certification for each tile type indicating compliance with the following water absorption (wa) rates per ANSI A137.1 criteria as tested per ASTM C373 requirements.
a. Porcelain and Tile (Impervious): Provide water absorption (wa) of
0.5 percent or less.
1.4 QUALITY ASSURANCE
Provide installers having a minimum of two years of experience with a company specializing in performing the type of work described. Each type and color of tile to be provided from a single source. Each type and color of mortar, adhesive, and grout to be provided from the same source.
1.5 DELIVERY, STORAGE, AND HANDLING
Ship tiles in sealed packages and clearly marked with the grade, type of tile, producer identification, and country of origin. Deliver materials to the project site in manufacturer's original unopened containers with seals unbroken and labels and hallmarks intact. Protect materials from weather, and store them under cover in accordance with manufacturer's printed instructions. Store and handle tiles per manufacturer's instructions for gauged porcelain tile and gauged porcelain tile panels/slabs.
1.6 ENVIRONMENTAL REQUIREMENTS
Do not perform ceramic tile work unless the substrate and ambient temperature is at least 50 degrees F and rising. Maintain temperature above 50 degrees F while the work is being performed and for at least 7 days after completion of the work. When temporary heaters are used, ventilate the area to the outside to avoid carbon dioxide damage to new tilework.
1.7 WARRANTY
Provide manufacturer's warranty to repair or replace defective tiling materials and workmanship, including tile, mortar and grout products and installation as a system, for a period of one year from date of final acceptance of the work.
1.8 EXTRA MATERIALS
Supply an extra 2 percent of each type tile used in clean and marked cartons.
PART 2 PRODUCTS
2.1 TILE
Provide tiles that comply with ANSI A137.1 and are standard grade tiles, the exception is glass tile. Furnish glass tiles that comply with ANSI A137.2 . Furnish gauged porcelain tile that comply with ANSI A137.3/A108.19 . Provide a minimum breaking strength of 125 lbs. for wall tile and 250 lbs. for floor tile in accordance with ASTM C648.
Provide floor tiles with a minimum wet dynamic coefficient of friction (DCOF) value of 0.42 when tested in accordance with ANSI A137.1
SECTION 09 30 10 Page 4 requirements. Provide glazed floor tile with a Class IV-Commercial classification as rated by the manufacturer when tested in accordance with ASTM C1027 for visible abrasion resistance as related to foot traffic.
For materials like tile, accessories , and transition strips submit samples of sufficient size to show color range, pattern, type and joints.
Submit manufacturers' descriptive product data for each type of tiling indicated. Include manufacturers' literature, finishes, profiles and thicknesses of materials.
Submit manufacturers' operations and maintenance data for each type of ceramic, quarry and glass tiling indicated in accordance with Section
01 78 23 OPERATIONS AND MAINTENANCE DATA.
2.1.1 Porcelain Tile
Provide glazed color body (body of tile is stained to match the glaze color), porcelain tile. Provide tile with a V2 aesthetic classification.
Blend tiles in factory and in packages to have same color range and continuous blend for installation. Provide nominal tile size(s) indicated on drawings.
Provide porcelain tiling materials that contain a minimum of 10 percent recycled content. Provide data identifying percentage of recycled content for porcelain tile .
2.1.2 Gauged Porcelain Tile
Provide glazed color body (body of tile is stained to match the glaze color), rectified gauged porcelain tile and cove base and trim pieces.
Provide tile with a V2 aesthetic classification. Blend tiles in factory and in packages to have same color range and…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .