This document is a technical drawing specification for pipe penetration through a fire-rated partition at Mansfield Lahm Air National Guard Base, Ohio, as part of Contract FA877006 for Repair B403 for Cyber. The drawing, prepared by Jacobs Government Services (2600 Michelson Drive, Suite 500, Irvine, California 92612), depicts the installation details for a PTB (pipe through boundary) secured to non-secured boundary pipe penetration at a 3-inch scale (3" = 1'-0").

The specification details the materials and installation requirements for the pipe penetration assembly. Key components include a metal conduit/pipe with RF (radiofrequency) shielding mechanically bonded to the flange using conductive tape, RF shielding around the metallic pipe with sealed seams, a pipe clamp to secure the shielding, a firestop pipe collar installed per manufacturer's instructions, and a PVC to EMT adaptor or dielectric coupler extending minimum 6" or 7 times the pipe diameter. The assembly requires insulation tightly packed in void space on both sides of the partition, fire-rated/acoustic sealant applied to all sides of the pipe penetration, and wire wheel cleaning of the metal surface for proper shielding contact. The document includes a note that the above specification is intended as an example only and that the contractor ultimately determines means and methods of installation while taking ownership of the work. The drawing sheet reference is RFI 03, Q.7., with project number PBXP222050.

View the file

Other files

File Type Posted
W50S8R26RA005 0005_B403 CYBER Repair (conformed version).pdf PDF
W50S8R26RA005 0005_B403 CYBER Repair.pdf PDF
RFI and Response Document (as of 07 July)_final.pdf PDF
W50S8R26RA005 0004_B403 CYBER Repair (conformed version).pdf PDF
RFI 04_question 6. attach._Geotech Report.pdf PDF
W50S8R26RA005 0004_B403 CYBER Repair.pdf PDF
RFI and Response Document (as of 03 July).pdf PDF
RFI 03_question 7. response attach. 02.pdf PDF
RFI and Response Document (as of 02 July).pdf PDF
RFI 02_question 8. response attachment.pdf PDF
W50S8R26RA005 0003_B403 CYBER Repair (conformed version).pdf PDF
W50S8R26RA005 0003_B403 CYBER Repair.pdf PDF
W50S8R26RA005 0002_B403 CYBER Repair.pdf PDF
EXHIBIT A rev01.pdf PDF
RFI and Response Document (as of 09 June).pdf PDF
Pre-Proposal sign-in sheet.pdf PDF
Pre-Proposal Conference-slides.pptx PPTX presentation
W50S8R26RA005 0002_B403 CYBER Repair (conformed version).pdf PDF
Pre-Proposal Conference minutes_B403 CYBER.pdf PDF
ATTACHMENT 06_B403 Cyber_Drawings (Full size)_B3.pdf PDF
ATTACHMENT 05_B403 Cyber_Drawings (Half size)_B3.pdf PDF
ATTACHMENT 03_B403 Cyber_Specifications (Div 09-25)_B3.pdf PDF
ATTACHMENT 01_B403 Cyber_Narrative_B3.pdf PDF
W50S8R26RA005 0001_B403 CYBER Repair (conformed version).pdf PDF
ATTACHMENT 02_B403 Cyber_Specifications (Div 01-08)_B3.pdf PDF
ATTACHMENT 04_B403 Cyber_Specificatioins (Div 26-33)_B3.pdf PDF
ATTACHMENT 07_B403 Cyber_Interior Design Specs and Drawings_B3.pdf PDF
ATTACHMENT 06_B403 Cyber_Drawings (Full size)_B3.pdf PDF
W50S8R26RA005 0001_B403 CYBER Repair.pdf PDF
ATTACHMENT 08_IDS Justification and Approval.pdf PDF
ATTACHMENT 05_B403 Cyber_Drawings (Half size)_B3.pdf PDF
EXHIBIT A.docx DOCX document
EXHIBIT B.docx DOCX document
EXHIBIT D_Letter of Commitment.docx DOCX document
EXHIBIT C_Reference Questionnaire Package.docx DOCX document
W50S8R26RA005_B403 CYBER Repair.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROVIDE FIRE

RATED/ACOUSTIC

SEALANT ALL SIDES OF

PIPE PENETRATION,

TYPICAL

METAL CONDUIT

PARTITION PER PLAN

SECURED SIDE

INSULATION TIGHTLY

PACKED IN VOID

SPACE, ALL AROUND

RF SHIELD MECHANICALLY

BONDED TO FLANGE USING RF

SHIELDING CONDUCTIVE TAPE

NON-SECURED SIDE

PVC TO EMT ADAPTOR

OR DIELECTRIC

COUPLER. EXTEND

MINIMUM 6" OR 7X THE

PIPE DIAMETER

METAL CONDUIT/PIPE

RF SHIELDING AROUND

METALLIC PIPE. SEAL SEAM

WITH CONDUCTIVE TAPE

PIPE CLAMP TO SECURE

SHIELDING TO PIPE

WIRE WHEEL METAL SURFACE

CLEAN TO ALLOW FOR GOOD

SHIELDING TO PIPE CONTACT

FIRESTOP PIPE

COLLAR. INSTALL PER

MANUFACTURES

INSTRUCTIONS

3"

DRAWN BY:

DESIGNED BY:

SUBMITTED BY:

CHECKED BY:

ISSUE DATE:

ANG PROJECT NO.:

SHEET ID:

PTB SECURE TO NON-SECURED PIPE PENETRATION

MANSFIELD LAHM AIR NATIONAL GUARD BASE, OH

JACOBS GOVERNMENT SERVICES

2600 MICHELSON SR, STE 500

IRVINE, CA 92612

Designer

Author

Checker

PBXP222050

REPAIR B403 FOR CYBER

FA877006

RFI 03, Q.7.

SCALE 3" = 1'-0"

PTB SECURED TO NON-SECURED

BOUNDARY PIPE PENETRATION

NOTE: above is intended as an example only; contractor ultimately determines means and methods of installation/takes ownership.

Sheets
BID RFI 7A - PTB SECURE TO NON-SECURED PIPE PENETRATION