RFI 03_question 7. response attach. 01.pdf
PDF 159 KB Posted
- Attached to
- PBXP 222050 - B403 CYBER REPAIR
- Solicitation number
- W50S8R26RA005
About this file
This document is a technical drawing specification for pipe penetration through a fire-rated partition at Mansfield Lahm Air National Guard Base, Ohio, as part of Contract FA877006 for Repair B403 for Cyber. The drawing, prepared by Jacobs Government Services (2600 Michelson Drive, Suite 500, Irvine, California 92612), depicts the installation details for a PTB (pipe through boundary) secured to non-secured boundary pipe penetration at a 3-inch scale (3" = 1'-0").
The specification details the materials and installation requirements for the pipe penetration assembly. Key components include a metal conduit/pipe with RF (radiofrequency) shielding mechanically bonded to the flange using conductive tape, RF shielding around the metallic pipe with sealed seams, a pipe clamp to secure the shielding, a firestop pipe collar installed per manufacturer's instructions, and a PVC to EMT adaptor or dielectric coupler extending minimum 6" or 7 times the pipe diameter. The assembly requires insulation tightly packed in void space on both sides of the partition, fire-rated/acoustic sealant applied to all sides of the pipe penetration, and wire wheel cleaning of the metal surface for proper shielding contact. The document includes a note that the above specification is intended as an example only and that the contractor ultimately determines means and methods of installation while taking ownership of the work. The drawing sheet reference is RFI 03, Q.7., with project number PBXP222050.
View the file
Other files
Show all 36
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROVIDE FIRE
RATED/ACOUSTIC
SEALANT ALL SIDES OF
PIPE PENETRATION,
TYPICAL
METAL CONDUIT
PARTITION PER PLAN
SECURED SIDE
INSULATION TIGHTLY
PACKED IN VOID
SPACE, ALL AROUND
RF SHIELD MECHANICALLY
BONDED TO FLANGE USING RF
SHIELDING CONDUCTIVE TAPE
NON-SECURED SIDE
PVC TO EMT ADAPTOR
OR DIELECTRIC
COUPLER. EXTEND
MINIMUM 6" OR 7X THE
PIPE DIAMETER
METAL CONDUIT/PIPE
RF SHIELDING AROUND
METALLIC PIPE. SEAL SEAM
WITH CONDUCTIVE TAPE
PIPE CLAMP TO SECURE
SHIELDING TO PIPE
WIRE WHEEL METAL SURFACE
CLEAN TO ALLOW FOR GOOD
SHIELDING TO PIPE CONTACT
FIRESTOP PIPE
COLLAR. INSTALL PER
MANUFACTURES
INSTRUCTIONS
3"
DRAWN BY:
DESIGNED BY:
SUBMITTED BY:
CHECKED BY:
ISSUE DATE:
ANG PROJECT NO.:
SHEET ID:
PTB SECURE TO NON-SECURED PIPE PENETRATION
MANSFIELD LAHM AIR NATIONAL GUARD BASE, OH
JACOBS GOVERNMENT SERVICES
2600 MICHELSON SR, STE 500
IRVINE, CA 92612
Designer
Author
Checker
PBXP222050
REPAIR B403 FOR CYBER
FA877006
RFI 03, Q.7.
SCALE 3" = 1'-0"
PTB SECURED TO NON-SECURED
BOUNDARY PIPE PENETRATION
NOTE: above is intended as an example only; contractor ultimately determines means and methods of installation/takes ownership.
| Sheets |
| BID RFI 7A - PTB SECURE TO NON-SECURED PIPE PENETRATION |