FANG BLDG 2640 ANN FA 7-2019.pdf

PDF 200 KB Posted

Attached to
Inspection of Fire Alarm Panels, Main Base
Solicitation number
W50S6T24QA011
Issued by

About this file

This document includes a federal contract opportunity solicitation for fire alarm system inspection and maintenance services at an Air National Guard base. The 144th Fighter Wing is soliciting quotes for inspection of fire alarm panels and devices in nineteen buildings to identify and correct deficiencies. The requirement is for a firm fixed price contract awarded without negotiations. Quotes are due by email before the specified date and time. A pre-proposal site visit will be held on January 3, 2023, with attendees required to complete a background check through the Defense Biometric Identification System prior to the visit. The solicitation instructs offerors to review submission requirements and notifies that the government may amend or cancel the solicitation before or after closing. Quotes shall remain valid for 30 days.

View the file

Other files

File Type Posted
FANG BLDG 145 ANN FA 7-2019.pdf PDF
FANG BLDG 122 ANN FA 7-2019.pdf PDF
FANG BLDG 130 ANN FA 6-2019.pdf PDF
Performance Work Statement - Inspection Fire Panel Main Base (HAYW231030)-Amd2.pdf PDF
FANG BLDG 135 ANN FA 6-2019.pdf PDF
FANG BLDG 2602 ANN FA 7-2019.pdf PDF
Solicitation Amendment W50S6T24QA0110002 SF 30.pdf PDF
FANG BLDG 102 ANN FA 7-2019.pdf PDF
FANG BLDG 121 ANN FA 7-2019.pdf PDF
FANG BLDG 159 ANNUAL FA 6-2019.pdf PDF
FANG BLDG 124 ANN FA 6-2019.pdf PDF
Solicitation Amendment - W50S6T24QA0110002 SF1449.pdf PDF
FANG BLDG 125 ANN FA 6-2019.pdf PDF
FANG BLDG 117 ANN FA 6-2019.pdf PDF
FANG BLDG 126 ANN FA 6-2019.pdf PDF
FANG BLDG 157 ANNUAL FA 6-2019.pdf PDF
FANG Bldg 100 Annual FA 6-2019.pdf PDF
FANG BLDG 155 ANN FA 7-2019.pdf PDF
FANG BLDG 104 ANN FA 7-2019.pdf PDF
FANG BLDG 225 ANN FA 6-2019.pdf PDF
FANG BLDG 2600 2601 ANN FA 7-2019.pdf PDF
FANG BLDG 194 ANN FA 7-2019.pdf PDF
Solicitation Amendment W50S6T24QA0110001 SF 30.pdf PDF
Base Access-144 SFS DVES FORM- 20230127 (Site Visit).pdf PDF
Wage Determinations SCA - 2015-5609 dated 3Aug2023.pdf PDF
Solicitation - W50S6T24QA011 SF1449 RFQ.pdf PDF
Performance Work Statement - Inspection Fire Panel Main Base.pdf PDF
Show all 27

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SimplexGrinnell BE SAFE

INSPECTION AND TESTING FORM

SR Number: 44909832 DATE: July 2, 2019

Task Number: TIME: 11:30AM

SERVICE ORGANIZATION PROPERTY NAME (USER)

Name: SimplexGrinnell Name: Fresno Air National Guard Bldg 2640

Address: 2788 N. Larkin Ave. Address: 5323 E. McKinley Ave

City, St., Zip: Fresno, CA, 93727 City, St., Zip: Fresno, CA, 93727

Representative: Jesus Salgado Owner Contact: Mike Scott

License No.: 986047 Telephone: 559-454-5137

Telephone: 559-348-0614 Occupied as: Master Chief

MONITORING ENTITY APPROVING AGENCY

Contact: In House Fire Department Contact: N/A

Telephone: 559-454-5145 Telephone: N/A

Monitoring Account Ref. No.: N/A

TYPE TRANSMISSION SERVICE

McCulloh Weekly

Multiplex Monthly

X Digital Quarterly

Reverse Polarity Semiannually

RF X Annually

Other (Specify) Other (Specify)

System Type: ( ) Local; ( ) Auxiliary; (X)Remote Station; ( ) Proprietary; ( ) Emergency Voice / Alarm

Control Unit Manufacturer: FCI Model No.: BMFC-6

Circuit Style: Class B

Number of Circuits: NA

Software Rev.: NA

Last Date System Had Any Service Performed: NA

Last Date That Any Software or Configuration Was Revised: NA

ALARM-INITIATING DEVICES AND CIRCUIT INFORMATION

Quantity of Devices Installed

Circuit Style

Devices Tested

3 B 3 Manual Fire Alarm Boxes (PSSA)

0 0 Ion Detectors (ISD)

3 B 3 Photo Detectors (PSD)

0 0 Duct Detectors (DSD)

8 B 8 Heat Detectors (HD)

0 0 Water Flow Switches (WF)

0 0 (Specify)

0 0 (Specify)

0 0 (Specify)

Alarm verification feature is Disabled X Enabled .

Rev. D

ALARM NOTIFICATION APPLIANCES AND CIRCUIT INFORMATION

Appliances Installed

Appliances Tested

0 0 Bells

1 B 1 Horns with strobes

0 0 Chimes

0 0 Strobes

0 0 Speakers

4 B 4 (Specify) Horns

Number of alarm notification appliance circuits: 1

Are circuits monitored for integrity? X Yes No

SUPERVISORY SIGNAL-INITIATING DEVICES AND CIRCUIT INFORMATION

Devices Installed

Devices Tested

0 0 Valve Position Tamper Switch (TS)

0 0 Outside Stem and Yoke (OSY)

0 0 Post Indicator Valve (PIV)

0 0 High / Low Pressure Switch (HLPS)

0 0 Building Temperature

0 0 Site Water Temp

0 0 Site Water Level

0 0 Fire Pump Power

0 0 Fire Pump Running

0 0 Fire Pump Auto Position

0 0 Fire Pump or Fire Controller Trouble

0 0 Fire Pump Low Fuel

0 0 Other: Switch Transfer

0 0 Other: Generator Engine Running

SIGNALING LINE CIRCUIT

Quantity and style of signaling line circuits connected to system (see NFPA, Table 6.6.1):

Quantity Style(s)

SYSTEM POWER SUPPLIES

(a) Primary (Main): Nominal Voltage 110VAC Amps 2.5

Overcurrent Protection: Type Circuit Breaker Amps 20

Location (of Primary Supply Panel): Igloo 1

Disconnecting Means Location: Panel LPE-1 CKT# 5

(b) Secondary (Standby):

Back Up Batteries Storage Battery: Amp-Hr Rating Two 12V 7Ah batteries

Calculated capacity is 14 Amp-Hrs to operate system for 24 Hours.

Engine-driven generator dedicated to fire alarm system: N/A

Location of fuel storage: N/A

TYPE BATTERY

Dry Cell Lead-Acid

Nickel-Cadmium Other (Specify):

X Sealed Lead-Acid

(c) Emergency or standby system used as a backup to primary power supply, instead of using a secondary power supply:

NA Emergency system described in NFPA 70, Article 700

NA Legally required standby described in NFPA 70, Article 701

NA Optional standby system described in NFPA 70, Article 702, which also meets the performance requirements of Article 700 or 701

PRIOR TO ANY TESTING

NOTIFICATIONS ARE MADE Yes No Who Time

Monitoring Entity X Fire Department 11:30AM

Building Occupants X Staff 11:30AM

Building Management X Mike Scott 11:30AM

Other (Specify)

AHJ Notified of Any Impairments

SYSTEM TESTS AND INSPECTIONS

TYPE Visual Functional Comments

Control Unit X X Pass

Interface Equipment X X Pass Lamps / LEDs X X Pass Fuses X X Pass Primary Power Supply X X Pass Trouble Signals X X Pass Disconnect Switches X X Pass Ground Fault Monitoring X X Pass

SECONDARY POWER

TYPE Visual Functional Comments

Battery Condition X Good Condition

Load Voltage X Pass-26.64VDC

Discharge test X Pass-25.78VDC

Charger test X Passs-27.89VDC

TRANSIENT SUPPRESSORS N/A

REMOTE ANNUNCIATOR N/A

NOTIFICATION APPLIANCES

Audible X X Pass

Visible X X Pass

Speakers N/A

Voice Clarity N/A

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS

Location & Serial Number Device Type

Visual Check

Functional Test

Factory Setting

Measured Setting Pass Fail

See attached detailed report.

Date of Last Sensitivity Test: N/A

EMERGENCY COMMUNICATION EQUIPMENT Visual Functional Comments

Phone Set NA

Phone Jacks NA

Off-Hook Indicators NA

Amplifier(s) NA

Tone Generator(s) NA

Call-in Signal NA

System Performance NA

SPECIAL HAZARD SYSTEMS

Number Installed

Number Tested Comments

Kitchen Range Hood System NA

CO2 Extinguishing System NA

(Specify) NA

CONTROL FUNCTIONS / INTERFACE

EQUIPMENT

Number Installed

Number Tested

Elevator Recall NA

Fan Shutdown NA

Door Holders NA

Smoke Control System NA

Door Release (Security Maglocks) NA

(Specify) NA

Special Procedures:

Comments:

SUPERVISING STATION MONITORING Yes No Time Comments

Alarm Signal X

Alarm Restoration X

Trouble Signal X

Trouble Signal Restoration X

Supervisory Signal X

Supervisory Restoration X

NOTIFICATIONS THAT TESTING IS COMPLETE Yes No Time Comments

Building Management X Mike Scott

Monitoring Agency X Fire Department

Building Occupants X Staff

Other (Specify)

The following did not operate correctly: No deficiencies found during this inspection.

System restored to normal operation: Date: July 2, 2019 Time:

THIS TESTING WAS PERFORMED IN ACCORDANCE WITH APPLICABLE NFPA STANDARDS.

Name of Inspector: Jesus Salgado Date: July 2, 2019 Time:

Signature:

Name of Owner or Rep.: Date: Time:

Signature:

PROPERTY NAME: FRESNO AIR NATIONAL GUARD BUILDING 2640 DATE: July 2, 2019

ADDRESS: 5323 E. MCKINLEY AVE, FRESNO, CA, 93727 TIME:

INITIATING AND SUPERVISORY DEVICE TESTS AND INSPECTIONS (SUPPLEMENTAL SHEET)

Location & Serial Number Device Type VIS. FUNC. Address Pass Fail

Igloo 1 heat detector high ceiling HD X X ZN01 X

Igloo 1 heat detector high ceiling HD X X ZN01 X

Igloo 1 heat detector high ceiling HD X X ZN01 X

Igloo 1 heat detector high ceiling HD X X ZN01 X

Igloo 2 heat detector high ceiling HD X X ZN01 X

Igloo 2 heat detector high ceiling HD X X ZN01 X

Igloo 2 heat detector high ceiling HD X X ZN01 X

Igloo 2 heat detector high ceiling HD X X ZN01 X

Igloo 3 smoke detector high ceiling PSD X X ZN01 X

Igloo 3 smoke detector high ceiling PSD X X ZN01 X

Igloo 3 smoke detector high ceiling PSD X X ZN01 X

Igloo 1 by entry door PSSA X X ZN02 X

Igloo 2 by entry door PSSA X X ZN02 X

Igloo 3 by entry door PSSA X X ZN02 X